Minimum cross section of the earthing conductor as per IS 3043

Formulae = A = (IFxSQRTt)/K
Where
A = Cross section area
t = Fault current time in seconds
K = Material constant
Corrosion considered 1% per year
Number of service years before replacement considered = 20 years
Safety considered = 1.5%
imum cross section area of earthing conductor

S.No Parameter unit


1 Fault current time t sec 3
2 Material constant K NA 80
3 Fault current If Amp 36000
4 Cross section area of the earthing conductor (A) Sq.mm 779.4229
5 No of years before replacement Y years 20
6 allowance of corrosion per year Cr % 1
7 Total allowance NA 20%
8 Safety factor NA 1.5
9 Required earthing condutor size sq mm 1402.961
10 Rounding of sq mm 1402.961
GI STRIP DIMENSION IN MM
LENGTH WIDTH
25 3 Nos 18.7
25 6 Nos 9.4
50 6 Nos 4.7
50 10 Nos 2.8
Material constant
GI 80 No
Copper 205 1
Aluminium 126 2
3
4
5
6
7
8
9
10
11
12
how to choose earth strip size- Typical value for your reference
Equipment Earth strip size
HT switchgear, structures, cable trays & fence, rails, gate and steel column 55 X 6 mm (GI)
Lighting Arrestor 25 X 3 mm (Copper)
PLC Panel 25 X 3 mm (Copper)
DG & Transformer Neutral 50X6 mm (Copper)
Transformer Body 50×6 mm (GI)
Control & Relay Panel 25 X 6 mm (GI)
Lighting Panel & Local Panel 25 X 6 mm (GI)
Distribution Board 25 X 6 mm (GI)
Motor up to 5.5 kw 4 mm2 (GI)
Motor 5.5 kw to 55 kw 25 X 6 mm (GI)
Motor 22 kw to 55 kw 40 X 6 mm (GI)
Motor Above 55 kw 55 X 6 mm (GI)