Course: TIMBER DESIGN LABORATORY Date: 05-12-19

Name: AGUINALDO, PATRICK A

STRUCTURAL DESIGN CRITERIA


LOADINGS

1. DEAD LOAD
 Ceiling 0.13kPa
 Roofing (Gi sheet & Purlins) 0.37 kPa
 Electrical, mechanical and plumbing 0.24 kPa

2. LIVE LOAD
 Restroom 2.40 kPa
 Residential 1.90 kPa
 Stairways 2.40 kPa

3. WIND LOAD – APPLICABLE PROVISION FOR ZONE 2.

4. SEISMIC LOAD – APPLICABLE PROVISION FOR ZONE 2.

 Seismic Zone Factor, z 0.40


 Numerical Coefficient, Rwx & Rwz 8.50
 Importance Factor 1.50
 Site Coefficient 4.00
 Na 1.128
 Nv 1.456
 Fundamental Period of Variation, T C(hn)%
 Ct 0.0731
 Heigh in meters, h hn

MATERIAL PROPERTIES

1. Unit weight of wood 6.13 kN/m^3


2. Ending and tension parallel to grain 16. 20 kPa
3. Modulus of elasticity of bending 5.56 kPa
4. Compression perpendicular to grain 2.33 kPa

FOUNDATION

Soil bearing capacity of 150 kPa shall be assumed for gravity loading.

REFERENCES

1. National Structural Code of the Philippines, Volume 1 – 7th edition.


2. National Building Code of the Philippines, Latest Edition