Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Proprietary Information: This document contains proprietary information and may not be partly or wholly reproduced without prior written
permission from Shell Petroleum Development Company
The Process Manager for this procedure is the Project Manager, the Process Owner is the Installation Manager
CONTENTS
1.0 PROJECT DESCRIPTION ................................................................................................................ 6
1.1 Objective 6
1.2 Definition and Abbreviation ................................................................................................................ 6
1.2.1 Definition 6
1.2.2 Abbreviation 7
1.3 Site Environmental Conditions .......................................................................................................... 8
2.0 APPLICABLE CODES & STANDARDS .......................................................................................... 10
2.1 List of Applicable Codes & Standards ............................................................................................. 10
2.1.1 Master Practices–WAEP Local Engineering Practices ................................................................... 10
2.1.2 International Standards.................................................................................................................... 11
2.1.3 WAEP Loss prevention procedures documents .............................................................................. 11
2.1.4 Project Documents .......................................................................................................................... 11
2.2 Order of Precedence ....................................................................................................................... 12
2.3 Health, Safety And Environmental Requirements ........................................................................... 12
3.0 F&G SYSTEM PHILOSOPHY ......................................................................................................... 12
3.1 FGS Scope 12
3.2 FGS Purpose 13
3.2.1 General 13
3.3 Hazards 13
3.3.1 Controlling Flammable Gas Hazards ............................................................................................... 13
3.3.2 Controlling Fire Hazards .................................................................................................................. 13
3.4 Fire Zones 13
3.5 Voting 14
3.6 Executive Actions ............................................................................................................................ 14
3.7 Design Efficiency ............................................................................................................................. 15
4.0 FLAMMABLE GAS DETECTION .................................................................................................... 15
4.1 Detection Requirement .................................................................................................................... 15
4.2 Detection Technology Selection ...................................................................................................... 15
4.3 Selection Hierarchy.......................................................................................................................... 15
4.3.1 Boundaries/Areas Monitoring .......................................................................................................... 15
4.3.2 Significant Potential Leak Sources .................................................................................................. 15
4.3.3 Congested Plant Modules................................................................................................................ 15
4.3.4 Ducting and Air Intakes.................................................................................................................... 15
4.3.5 Difficult Access or Conditions .......................................................................................................... 16
4.3.6 Building Interior 16
4.3.7 Oil Mist Area 16
4.4 Flammable Gas Connection Alarm Limits ....................................................................................... 16
5.0 FIRE DETECTIION .......................................................................................................................... 17
5.1 Detection Requirements .................................................................................................................. 17
5.2 Detector Technology Selection ........................................................................................................ 17
5.3 Selection Hierarchy.......................................................................................................................... 17
5.3.1 Wide Area Coverage ....................................................................................................................... 17
5.3.2 Single Point Coverage ..................................................................................................................... 17
5.3.3 Congested Platform/Plant Modules ................................................................................................. 17
5.3.4 Inside Enclosures ............................................................................................................................ 17
5.4 Other Selection Scenarios ............................................................................................................... 18
5.4.1 Building Interiors .............................................................................................................................. 18
5.4.2 Critical / High Value Equipment ....................................................................................................... 18
5.4.3 Wellheads 18
OML’s 71 and 72 are located at approximately 27km and 50 km respectively south of the Bonny
River inside the shallow Offshore Waters – Water depths are 65ft (OML71) and 131ft (OML72). To
date while oil production is from OML 72 only in the KALAEKULE field which was discovered in 1984
and production from the field started in July 1986. OML 71 is largely undeveloped.
KCPPA: A single train 3 stage (XHP, HP, LP) three phase Gas Separation (250 MMSCFD) and Oil
(25 MBBLs/Day). The KCDP-A and KCPP-A are located 30m apart and linked by a walk way bridge
while KCDPB and KCJV-A are located about 970m and 600m respectively from KCPP -A.
In an effort to monetize oil and gas in OML 72 based on the available resources, the COMPANY
has planned to re-furbish the existing facilities on KCPP-A and KCDP-A by installing new process
modules/packages.
1.1 Objective
This document provides the philosophy that defines the basic principles for the design of the Fire
and Gas detection and protection system and field devices for the KALAEKULE Platform re-
furbishment Project Facilities.
This document forms part of the overall safety philosophy with respect to project hazard
identification, risk assessment and mitigation and hence it is imperative that it is read in conjunction
with the project applicable documents. listed in Section 2.1.4
The primary design objective shall be to provide instrumentation, control and automation systems
that are:
Safe
Fit for purpose
Cost effective
Reliable and offer a high availability
Simple to operate and maintain
Capable of integrating and inter-operating with the rest of SPDC’s control and
communications infrastructure seamlessly
Flexible and capable of accommodating future modifications, updates, upgrades and
expansions
Based on the latest mature technology
Suitable for and supported through the project design lifespan
Maintainable by specialist personnel resident within easy reach
Centralized and offer enterprise-wide monitoring and control of all facilities within the
Project from a central location.
Standardized to afford spare parts commonality / Interchangeability, and reduction in
training effort and maintenance costs.
1.2.2 Abbreviation
ALARP As Low As Reasonably Practicable
API American Petroleum Institute
BS British Standards
CEM Cause and Effect Matrix
CR Control Room
ESD Emergency Shutdown
EWS Engineering Work Station
RTU Remote Terminal Unit
F&G Fire and Gas
F&GDM Fire & Gas Detection Mapping
F&GS Fire & Gas System
FDS Functional Design Specification
FEED Front End Engineering Design
FMEDA Failure Mode Effects and Diagnostic Analysis
FIREPRAN FIRE PRotection ANalysis
GOR Gas Oil Ratio
HART Highway Addressable Remote Transducer
HMI Human Machine Interface
HSE Health, Safety and Environment
HVAC Heating, Ventilation and Air Conditioning
I/O Input / Output
IC&A Instrumentation, control and automation
IASS Integrated Automation and Shutdown System
IEC International Electrotechnical Commission.
IP Institute of Petroleum
IR Infra Red
IS Intrinsically Safe
ISA Instrumentation, Systems and Automation Society
LED Light Emitting Diode
LFL Lower Flammable Limit
LFLm Lower Flammable Limit meter
NAG Non Associated Gas
OPC Object Linking & Embedding for Process Control
OSD Operational Shutdown
PA Public Address
PAS Process Automation System
PFD Probability of Failure on Demand
ROR Rate Of Rise
SER Sequence Of Event Recorder
SIF Safety Instrumented Function
SIL Safety Integrity Level
SIS Safety Instrumented System
WAEP West-African Exploration and Production
JV Joint Venture
KCDP-A Kaleakule Drilling Platform
KCPP-A Kaleakule Central Processing Platform
SCSSV Surface Control Sub-Surface Safety Valve
TDC Target Detection Coverage
TDO Target Detection Objectives
TDP Target Detection Perfromance
TuV Technischer Uberwachungsverein (German body, Translates to
Technical Inspection Agency).
UPS Uninterruptible Power Supply
VCE Vapour Cloud Explosion
environment with potential for saline corrosion and water ingress. The environmental data listed
below give an overview of the conditions prevalent over these locations in general, for the purpose
of selection and protection of the instruments.
The environmental conditions (weather and MetOcean) at the Kalaekule field are considered typical
of any shallow offshore location in the Niger Delta region. Available data shows that the extreme
conditions in this region are driven by both sea wind and swells. Company is in the process of
acquiring recent MetOcean data specific to OML-71 and -72.
Water Depth: The Mean Sea Level (MSL) at Kalaekule platforms’ location (OML 72) is 19.0m.
Tides: The highest astronomical tide and storm tide shall be assumed to occur simultaneously.
This total effect shall be considered in conjunction with both storm and operating waves and winds.
The astronomical and storm tides are 0.75m each. Tables 1 below provide the available data on
the wind and wave characteristics of the region for both operating and 100 year
Table 1: Operating and 100 Year Return MetOcean Data
Marine Growth: A 50mm radius increase shall be applied to the outside of all structural members
between the mudline and elevation +3m above MSL for the purpose of simulating marine growth.
Meteorological Data: The available meteorological data for the area are summarized in table 2 below.
Table 2: Meteorological Data
Minimum Air Temperature 20oC
All field devices, fittings and installation materials shall be suitable for and unaffected by the
indicated climatic conditions.
Individual process modules are normally treated as separate zones except where the modules are
in close proximity to one another and there is a high likelihood of a gas cloud or a fire enveloping
more than one module. In this case, the modules concerned may be treated as a single zone. A
key consideration is the location of effective boundaries or boundary isolations with respect to the
likely events.
Non-process areas such as offices, warehouses and other buildings are regarded as civil structures
and treated as separate zones, often on a per room or per building basis.
A detailed fire zones arrangement for the Kalaekule platform is shown in Appendix 4.
3.5 Voting
FGS voting is the configuration of the FGS to consider the indicated status of more than one
detector before executive actions are triggered. Detector voting is generally employed on a per
zone basis.
The purpose of voting is two-fold:
1. Removal of spurious alarms and executive actions by the fire system that would otherwise
result from detector falsely indicating hazardous situations.
2. Allowing detector redundancy and online maintenance to be performed more readily and
without compromising plant safety.
The voting scheme shall be 2ooN (Fire,gas and smoke detection systems) and shall be done taking
into account a number of factors including:
Relevant standards
The reliability of the detector correctly sensing a hazardous situation.
The sensor placement and plant layout.
Required SIL Rating of FGS.
Sensor redundancy
The magnitude of the risk being controlled
To ensure full consideration of plant operation, reliability, production continuance and maintenance
activities, WAEP’s approval of the voting system is required.
3.6 Executive Actions
In response to detected hazards, the FGS may trigger executive actions such as:
Fire suppression systems
Blowdown of platform or area
Isolation of fuel or energy supply
Annunciations such as sounders and lighting
Activation or isolation of ventilation systems
Remove notification of authorities’/emergency response groups
A Cause and Effects Matrix shall be prepared indicating a list of executive actions and their trigger
conditions.
Operator approval for particular executive actions shall be required in areas where automatic blow
down of facilities is not required. For instance, in certain plant locations it may not be appropriate
to blow down automatically as it will cause escalation of the hazardous event (e.g. a fire event
affecting the flare/vent system itself) executive action shall be manually initiated at the discretion
of the control system Operators.
If it is possible that concentrated gas might flow into the duct undetected using point detection, then
Line-Of-Sight detectors across the duct cross-section shall be employed, with consideration given
to how these detectors may be tested by maintenance in the future.
Where maintenance access is an issue, then remote testing facilities or aspirated detection should
be considered.
4.3.5 Difficult Access or Conditions
For high temperatures such as inside motor enclosures, or difficult access conditions such as
under-floor, aspirated detection systems may be employed.
For forced ventilation enclosures, the outlet may be monitored for gas.
Detection requirements for gas engine enclosures should be in accordance with applicable
international standard/industry practice (Gas generator/turbines for the petroleum, chemical, and
gas industry services).
4.3.6 Building Interior
The first preference for protecting building interiors from hydrocarbon build-up is the detection of
hydrocarbons much closer to their release in the field. If this is not possible then protection of the
building air inlet is preferred. If this is not possible, then detection within the building should be
employed.
4.3.7 Oil Mist Area
A pressurised leak of flammable fluid may produce an explosive oil mist that cannot be detected
by any of the previously described methods. In locations where this may occur, especially indoors,
then Oil Mist Detection shall be considered.
4.4 Flammable Gas Connection Alarm Limits
The following table indicates the alarm limits to be universally applied for gas detection systems,
according to their application and technology. Approval from WAEP is required to vary from these
values:
Application/ Low Alarm High Alarm Comment /
Detection Limit Limit Explanation
Technology
IR Point 20% LEL 60% LEL If only a single alarm limit is used, then set to
Detection 50% LEL
Catalytic Point 20% LEL 60% LEL
Detection
Gas 15% LEL 40% LEL Figures chosen to protect turbine from over-
Turbine/generator speed due to gas ingress into combustion air
Ingression inlet
Line Of Sight 1.0 LFLm 3.0 LFLm i.e. High Alarm on :
Detection (IR) 10m gas cloud of 30% LEL, or
100m gas cloud of 3% LEL.
Suggest calibrated FSD=5.0 LFLm.
the IR detectors. Where no substantial enclosure ventilation occurs, then consideration shall be
given to installing heat detectors high-up in the enclosure.
For heat producing packages such as diesel engines housed inside an enclosure, compensated
rate-of-rise heat detectors shall be installed as a back up to the IR detectors. Activation of a single
heat detector shall be regarded by the associated FGS as a confirmed fire and all associated
executive actions shall be triggered.
Where enclosure temperatures exceed the capability of the IR detectors, alternative techniques
may be employed. One option is the use of UV type fire detectors, however they shall not be
employed in dusty environments, for fires that produce heavy smoke, or where airborne oil droplets
may exists. WAEP approval is required for the use of UV type sensors due to their tendency to
false trip due to welding, X-rays (as used in on-site non-destructive testing), sunlight and lightning.
UV type sensor shall not be used to trigger potentially destructive executive actions.
5.4 Other Selection Scenarios
The following is a discussion of other typical scenarios where fire detection system selection is
required for projects:
5.4.1 Building Interiors
All non-process buildings/carbins shall be fitted with redundant optical type smoke detectors in their
interiors. All HVAC intakes shall have redundant ionisation type smoke detectors.
Where a building is not adequately sealed from dusty / dirty conditions then consideration may be
given to the use of ceiling mounted point heat detection in lieu of smoke detection.
Single detection of smoke or heat shall be regarded as a confirmed fire for that zone, and all
executive actions shall be triggered.
5.4.2 Critical / High Value Equipment
For location with critical and /or high value equipment installed, such as instrument, telecoms and
switchgear equipment, the use of a High Sensitivity Smoke Detection (e.g. VESDATM type) system
may be considered, especially for detection of combustion in difficult access areas such as under
floor and ceiling areas.
These High Sensitivity Smoke Detection systems detect pre-combustion emissions from material,
and hence allow intervention prior to the equipment being damaged by smoke and /or effort to
contain the subsequent fire that might develop.
High Sensitivity Smoke Detection systems are sensitive to dust ingression, can be prone to false
alarms, and also require significant maintenance. Hence the genuine usefulness of the early
warning offered by these high sensitivity systems need to be well demonstrated to justify their
usage.
A high sensitivity smoke detection system shall be used for alarm only.
Approval of the Principal is required for inclusion of this type of system.
5.4.3 Wellheads
Wellheads shall be protected by heat detectors which perform the executive action to close the
well in the event of a 2ooN detection indicating confirmed fire.
This shall be implemented using suitably rated fusible alloy plugs installed in the hydraulic supply
lines to the SSSV, SCSSV and Wing valve actuators, at the wellhead. In the event of fire at the
wellhead, the fusible alloy plugs will fail causing the hydraulic pressure to be vented from the spring-
return valve actuators, resulting in closure of the SSSV, SCSSV and Wing valves.
The hydraulic control system shall include low pressure alarms to alert the operator to loss of
hydraulic pressure.
5.4.4 Gas Generator Enclosures
Detection requirements for gas generator enclosures shall use triple band IR detectors, and
compensated rate-of-rise heat detectors installed in accordance with applicable international
standard.
IR detector locations shall be selected so that all possible fire locations inside the enclosure are
monitored from two different angles / detector locations. A single detector location indicating fire
triggers an alarm. Two different detector locations indicating fire in the same location shall trigger
executive action. Additionally, each detector location shall have a pair of detectors installed for
equipment redundancy.
UV type flame detection shall not be used.
5.4.5 Low Hydrocarbon Fires
For outdoor applications, heat detection shall be used.
Multiple point detection is preferred. Fusible Loop (linear) detection may be employed where an
excessive number of point detectors would be required for coverage, or where a mechanical /
hydraulic triggered automatic deluge is required.
For indoor applications, UV type flame detection may be considered only with the approval of
WAEP. Careful consideration of redundancy, voting systems and operator approval of executive
actions shall be considered.
5.4.6 Manned Areas
Manual alarm call points shall be provided in all living quaters, located adjacent to fire points and
exits. They shall also be provided at designated locations on personnel egress routes within the
platform facilities.
Activation of any manual call point in either a building or process area shall be regarded by the
associated FGS as a confirmed fire in that zone and all associated executive actions shall be
triggered.
The well head shall be supplied with fusible loop for fire detection and shut down of the wells.
6.2 Main Fire And Gas Detection System (FGS)
The main FGS shall be located in the Kalaekule Platforms control room.
The FGS shall continuously monitor each zone for any potential hazards, and on detection the FGS
shall raise an alarm, bring up the appropriate displays, and (may) initiate executive actions in
accordance with the voting system adopted.
The FGS shall have native compatibility with the full range of detection and manual initiation
devices required in the design. Complex interface conversion devices shall not be employed
between the FGS processor and its field devices.
The FGS shall have in-built self diagnostic capability with data interfacing facilities to the PAS for
fault reporting and visual display of project wide FGS status and alarm conditions.
The FGS shall be capable of driving hard-wired mimics.
Provision shall be made for hardware to be tested on-line using maintenance overrides.
6.3 FGS input
The FGS shall be designed with hard-wired field detector inputs. All input circuits shall be
continuously monitored for open circuit and closed circuit fault conditions. Alternatively, inputs may
use digital data bus connections to the field sensors; however consideration of the SIL
requirements and approvals ratings of the detectors shall be considered in accordance with
company LPP and process control philosophy.
The use of 0-20 mA transmitters which communicate sensor diagnostic messages in the 0-4 mA
range is encouraged over simple open / closed switch indicating type sensors is preferred.
Input cards as a minimum shall have status LEDs to indicate input status, override status and fault
status.
For process area related detectors, there shall be one input to the FGS per detector, allowing each
individual detector to be identified on the HMI interface, unless another approach is approved by
the Company.
For detectors in buildings, the inputs may be combined on a per zone basis, allowing many
detectors to be combined using field wiring and then connected to a single FGS input. (Field circuit
integrity monitoring must be maintained).
6.4 Voting Modules
Voting modules shall have status LEDs to indicate the status of each input channel / the output
status (vote) and fault status as a minimum.
6.5 FGS output
Output channels as a minimum shall not have output overrides. Output channels shall have status
LEDs to indicate output status and fault status.
All output circuits shall be continuously monitored for open circuit and closed circuit fault conditions.
Executive actions derived from automatic or manual initiation of the FGS shall be routed by hard-
wired connection to the ESD/OSD system, except for certain executive actions which shall be
performed directly from the FGS system (such as local deluge systems).
Output shall be fail-safe (normally closed or normally energised) unless the consequences of a
spurious trigger of the executive action might result in excessive damage to plant or personnel, or
pose an unnecessary hindrance to plant operations (for example, deluge/foam systems).
Where practical, IR technology is preferred unless the catalytic technology is required to ensure
sensitivity to specific fuel types (such as hydrogen, which cannot be detected by IR absorption).
8.6 Calibration Gas
Where a single gas type is being detected, the sensor shall be calibrated on this type of gas.
Where a range of gas types are being detected, the Manufacturer shall be consulted to determine
which of the possible gases the sensor is least sensitive to (for hydrocarbons, the worst-case gas
is most likely to be methane). The sensor shall be calibrated using the worst-case gas mixed in air.
This ensures the minimum required sensitivity is achieved for all gas types.
8.7 Line-Of-Sight Gas Detectors
Flashgun (pulse light) type detectors are preferred as these are the most reliable.
Detectors of the type that utilise a separate transmitter and receiver shall be selected. Combined
transmitter-receiver types that utilise retro-reflectors shall not be used as these halve the effective
path length.
8.7.1 Boundary Monitoring
Consideration should be given to using two pairs of detectors for each path, with 2ooN voting
applied, where two detectors are employed on a single path, they shall be configured with both a
transmitter and a receiver at opposing ends of the path (i.e two opposing beams).
8.7.2 Area Monitoring
At minimum, two detectors shall be used for area monitoring.
8.7.3 Installation
The recommended path length for open path detectors is 20 to 30 meters for offshore applications,
and 30 to 60 meters for onshore applications.
LOS detectors must be mounted on substantial, laterally-braced supports that do not flex or vibrate
to ensure consistent alignment.
Typically the optical alignment accuracy is of the order of 0.5 to 1 degree, and this must be taken
into consideration for structures that experience varying structural loading, or are subjected to
differential heating, as both of these can lead to ongoing sensor alignment problems.
Typically, LOS detectors are mounted 3 to 5 m off grade or deck.
Where possible, floor markings should be used to show LOS optical paths in order to avoid
inadvertent obstruction.
8.7.4 Sensor Robustness
LOS detectors shall be unaffected by short-term beam blockages. Blockages greater than 60
seconds duration shall result in a beam blocked warning. Blockages greater than typically 5
minutes shall indicate that the detector is in fault.
Routine maintenance of IR LOS type detectors requires cleaning of the sensor windows only.
Calibration tests require the introduction of a piece of calibrated film into the beam path.
Each instrument shall be provided with software to compensate for drift by utilisation of an auto-
zero tracking system.
8.8 Point Gas Detectors
Test gas inlet to be provided for calibration and testing of sensor operation. Remote facilities shall
be provided where sensors are not readily accessible, e.g. inside ducting.
8.12.2 Installation
Flame detectors shall be located as determined by the Fire Safety Assessment, to monitor
equipment containing major flammable inventories and likely fire sources. Detector location and
coverage, spacing and orientation shall take into account any obstructions.
Detectors shall be supplied complete with adjustable mounting brackets that allow the detector
alignment to be adjusted on both vertical and horizontal planes and shall be mounted in accordance
with manufacturers’ recommendations.
Detectors shall be located and oriented such that they cannot be accidentally triggered by detection
of flare systems (including reflections off equipment) under high flame conditions.
8.13 Smoke Detection
8.13.1 Technologies
Typically Ionisation type smoke detection will be employed, due to their high sensitivity to fully
formed fires.
Optical type detection is suited to detecting smouldering fires, but relatively insensitive to fully
formed fire. Hence when Optical Smoke Detection is employed, additional heat detection shall be
included to detect fires that build up rapidly without smouldering.
8.13.2 Installation
Smoke detectors are suitable for indoor use only.
All smoke detectors covering a single zone may be ‘daisy chained’ to a single FGS input card such
that activation of any single detector raises an alert and triggers executive actions for that zone.
Other types of detector in the same zone shall not be connected on the same loop.
The detectors shall incorporate a latching indicator that preferentially is an LED which illuminates
when the detector is in the alarm condition. It shall be reset from the fire and gas control panel only.
Detectors in inaccessible areas (e.g. floor / ceiling voids) shall have the capability of driving a
remote indicator lamp. The system certification for the detector shall include its use with the
indicator. Maintenance access (e.g. hatches) shall be provided.
Detectors shall be plug-in type. The sensor head assemblies shall be constructed so that the base
may be installed without the sensing element and all field wiring terminations made and sealed
against the atmosphere until subsequent installation of the sensing element at the pre-
commissioning stage.
8.13.3 High Sensitivity Smoke Detection:
High sensitivity smoke detection systems if fitted should be of the optical type and should include
an alarm to denote when any of the sampling system flow rates fall below acceptable limits.
High sensitivity smoke detectors of the type that detect chlorine emissions from overheated PVC
type cable insulation are not recommended as experience has shown that they are ineffective at
detecting emissions from low-chlorine emission cables which are now in common usage.
8.14 Heat Detection
Heat detection shall be employed where high reliability and low spurious trips is required and slow
response time can be tolerated.
Heat detection shall be considered as a backup to optical system which is faster but less reliable.
In open, naturally ventilated areas point heat detectors should be sited with a density in the order
of one detector per 25 m² and at a maximum spacing of up to approximately 7 meter apart. The
maximum distance from a bulkhead should be approximately 3.5 meter.
In enclosed mechanically ventilated modules, point heat detectors should be sited at a density of
at least one per 37 m² and at a maximum spacing of up to approximately 9 meter apart. The
maximum distance from a bulkhead should be approximately 4.5 meter.
8.14.1 Voting
Confirmation of fire detection is typically required before Executive Action is taken in response.
In a 2ooN voted configuration, triggering of two detectors in a zone is classed as “Confirmed fire”.
Point heat type devices shall not be voted.
Pneumatic fire detection systems may be voted at the discretion of the Principal. If voting is
deployed, then first detection loop provides an alarm, with the second loop detection providing
Executive Action.
Detectors used to automatically shut down machinery / plant equipment and initiate the fire
protection system shall be voted in a 2ooN configuration.
8.14.2 Point Heat Detection
The preferred heat detector characteristic shall be combined rate-of-rise-compensated and fixed
temperature threshold type. These characteristic detectors alarm on when either:
Absolute temperature exceeds a predetermined value in degrees, OR
Temperature rises at a rate faster than a predetermined value in degrees-per-minute.
The sensor head assembly shall be constructed so that the base may be installed without the
sensing element, all field terminations made and then ingress protected until the subsequent
installation of sensing element at the commissioning stage. The detector package shall consist of
the detector, base and termination box.
8.14.3 Linear Heat Detection
Linear heat detection is performed using Pressurised Fusible Loop (polyflo tubing or fusible plug)
type fire detection systems, which offer slow response times and high reliability.
Fire detected inputs to the FGS from fusible loop shall be via a pressure transmitter interfaced with
the FGS I/O via an analogue input card.
Executive actions may be triggered directly from the pressure drop in the detection loop, such as
deluge system valves opening or well head SSSV closure on loss of detector loop pressure.
The installation shall give careful consideration to the mechanical integrity and protection of the
loop, especially where polyethylene piping is involved.
Approval from the Company is required for the use of pressurised fusible loop systems.
8.15 Manual Call Point
Manual call points associated with civil facilities shall be of the break-glass type.
Manual call points associated with process facilities shall lock on activation and require a separate
action to release the switch.
Manual Call Points shall be installed at strategic locations around the facilities.
Manual call points shall be positioned so that they stand out against the background, i.e. they shall
be clearly recognizable from a distance. If necessary they shall be provided with signs to enhance
their visibility from access routes.
Manual call points should be positioned as follows:
1. Along routes in the platform area at intervals not exceeding 100 m, preferably at or near to lamp
posts;
2. Near or at locations having a higher risk such as remote pump floors, manifolds, motor control
centres and Wells.
3. Inside Carbins, office/control room entrance etc.
4. Inside the process area and positioned:
Outside room(s)
Outside hazardous enclosed areas
Along logical escape routes
8.16 Audible Alarm Sounders
FGS system audible alarms shall comprise a combination of
Site siren
Individual alarm sounders
Visual indications
Civil facilities sirens.
Field-mounted fire and gas alarm annunciators shall be powered from critical supplies that have
the same (high) availability as the main FGS system supply.
The tonal characteristics of each alarm are dependent upon the location / type of the alarm
annunciator and the type of hazard triggering the alarm. The tonal characteristics of the alarms
shall be in accordance with the Alarm Tone Table in appendix 3.
8.16.1 Site Siren
Wide area coverage shall be implemented using high-reliability electric-motor operated sirens that
emit an on-off modulated tone.
8.16.2 Individual Alarm Sounder
Where additional local enunciation is required, individual alarm sounders shall be installed.
They shall have facilities for adjustment to the sound level.
In area where there is a public address (PA) system the local audible alarms shall be temporarily
silenced during PA announcements.
8.16.3 Civil Facilities
Fire, gas and smoke alarms in buildings, including auxiliary/control rooms and offices, shall be
annunciated in the buildings themselves by means of a sounder with the same sonic characteristics
as individual alarm sounders.
These alarms shall be temporarily muted during public address (PA) system announcements.
8.16.4 Visual Alarm Device
Where it has been identified that beacons are required for high noise areas, e.g. compressor or
generator area, weatherproof flashing xenon beacon(s) shall be employed.
The beacon assembly shall be a tough impact resistant material and coloured red (See Appendix
3).
Infrared Detects Rapid hydrocarbon Reliable and proven Unsuitable for high
(Multi-band) flickering fire detection within technology. temp environments.
Flame infrared light a given area. Fast response. Unsuitable for low
Detector from hydrocarbon fires
hydrocarbon fire. (Hence cannot detect
Multiple IR Hydrogen or
bands are Methanol fires)
monitored to
reduce false
triggers.
Infrared Detects Rapid hydrocarbon Reliable and proven Unsuitable for high
(single band) flickering fire detection within technology. temp environments.
Flame infrared light a given area. Fast response. Unsuitable for low
Detector from hydrocarbon fires
hydrocarbon fire. (Hence cannot detect
Hydrogen or
Methanol fires)
Can be prone to false
triggers from sunlight
Multi-band version is
preferred
UV Flame Detection of UV Rapid hydrocarbon Suitability for hot Affected by oil
Detector emissions from fire detection within environments. droplets, dust and
flame a given area, suited Can detect non- smoke.
to heated hydrocarbon fires. False triggering due
environments. to light sources such
Suitable for non- as arc welding.
hydrocarbon fires False triggering due
(eg. Hydrogen, to radiation sources.
Methanol) Principal Approval
Required
Manual Call Flame and Plant-wide fire and Highly discriminating Reliant upon staff
Point Smoke smoke detection in sensor – ultra being present to raise
(Flame, Detection: manned areas– very reliable. manual alarm.
Smoke & Human detects versatile Smoke, heat and
Heat) fire/smoke and flame sensitive.
manually raises
alarm
Optical Smoke detection Point or open-path Best suited to Reduced sensitivity to
Scattering by scattering of detection of smoke detection of fully formed fires
Smoke light by smoke from smouldering smouldering fires. Some sensitivity to
Detector particles fires Can be used as fog
Line-Of-Sight Use indoors only
detector.