Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
编 制:
Victor 程垒
校 核:
标准化审查: 秦嗣友
审 定: 吴书娜
YANG 杨卉卉
版 本 号: V1.01
文件代号: V1.01
出版日期: 2018 年 08 月
0000189070
2018年08月
Version: V1.01
Doc. Code: 0000189070
Issued Date: 2018.08
Copyright owner: Beijing Sifang Automation Co., Ltd
Note: the company keeps the right to perfect the instruction. If equipment
does not agree with the instruction at anywhere, please contact our
company in time. We will provide you with corresponding service.
®
is registered trademark of Beijing Sifang Automation Co., Ltd.
We reserve all rights to this document, even in the event that a patent is issued and a
different commercial proprietary right is registered. Improper use, in particular reproduction
and dissemination to third parties, is not permitted.
This document has been carefully checked. If the user nevertheless detects any errors, he
is asked to notify us as soon as possible.
The data contained in this manual is intended solely for the product description and is not to
be deemed to be a statement of guaranteed properties. In the interests of our customers,
we constantly seek to ensure that our products are developed to the latest technological
standards as a result; it is possible that there may be some differences between the
hardware/software product and this information product.
Target audience
This manual mainly face to installation engineer, commissioning engineer
and operation engineer with perfessional electric and electrical knowledge,
rich experience in protection function, using protection IED, test IED,
responsible for the installation, commissioning, maintenance and taking
the protection IED in and out of normal service.
Technical support
In case of further questions concerning the CSC family, please contact
Sifang company or your local Sifang representative.
We provide the users with protection function and test training, the
warranty period is 5 years.
Safety information
Avoid to touching the circuitry when covers are removed. The IED
contains electirc circuits which can be damaged if exposed to
static electricity. Lethal high voltage circuits are also exposed
when covers are removed
I
Using the isolated test pins when measuring signals in open
circuitry. Potentially lethal voltages and currents are present
Changing the setting value group will inevitably change the IEDs
operation. Be careful and check regulations before making the
change
II
Contents
Chapter 1 Introduction ......................................................................................................... 1
1 IED overview .............................................................................................................. 2
2 IED characteristic ....................................................................................................... 2
3 Basic function ............................................................................................................. 3
3.1 Protection function .............................................................................................. 3
3.2 Control function ................................................................................................... 7
3.3 Measurement function......................................................................................... 7
3.4 Monitoring function .............................................................................................. 8
3.5 Communication mode ......................................................................................... 8
Chapter 2 Common functions .............................................................................................. 9
1 Event record and analysis ........................................................................................ 10
1.1 Overview ........................................................................................................... 10
1.2 Fault record ....................................................................................................... 10
1.3 Waveform record ............................................................................................... 10
1.4 Sequence of event (SOE) ................................................................................. 10
1.5 Operation record ............................................................................................... 11
2 Diagnostic function ................................................................................................... 11
2.1 Overview ........................................................................................................... 11
2.2 Diagnostic principle ........................................................................................... 11
3 Time synchronization function .................................................................................. 11
3.1 Overview ........................................................................................................... 11
3.2 Synchronization principle .................................................................................. 12
3.3 IRIG-B code synchronization mode................................................................... 12
3.4 PPS synchronization mode ............................................................................... 13
3.5 SNTP time synchronization mode ..................................................................... 13
3.6 1588 synchronization mode .............................................................................. 13
4 Authorization ............................................................................................................ 13
Chapter 3 Fault phase selection component .................................................................. 15
1 Overview .................................................................................................................. 16
2 Function module description .................................................................................... 16
3 Detailed description .................................................................................................. 16
3.1 Protection principle............................................................................................ 16
3.1.1 Steady state component phase selector........................................................ 16
3.1.2 Undervoltage phase selection component ..................................................... 17
Chapter 4 Basic protection component .......................................................................... 19
1 Startup component ................................................................................................... 20
1.1 Overview ........................................................................................................... 20
1.2 Current sudden-change startup element ........................................................... 20
1.3 Differential current startup component .............................................................. 20
2 Report ...................................................................................................................... 20
Chapter 5 Differential protection (87T) ........................................................................... 21
1 Overview .................................................................................................................. 22
2 Function module description .................................................................................... 23
3 Protection principle ................................................................................................... 24
3.1 Differential and restraint current calculation ...................................................... 25
3.2 Automatic Ratio compensation ......................................................................... 26
3.3 Automatic Vector group and zero sequence current compensation .................. 29
3.4 Instantaneous differential protection characteristic ........................................... 34
3.5 Treble slope percent differential protection characteristic ................................. 35
3.6 CT failure supervision ....................................................................................... 40
3.7 CT Saturation supervision ................................................................................. 41
3.8 Differential current supervision .......................................................................... 42
3.9 Setting list ......................................................................................................... 43
3.10 Report list .......................................................................................................... 44
4 Technical data .......................................................................................................... 45
Chapter 6 Restricted earth fault protection (87REF) ...................................................... 47
III
1Overview .................................................................................................................. 48
2Function module description .................................................................................... 48
3Detailed description.................................................................................................. 48
4Protection principle................................................................................................... 50
4.1 Differential and restraint current calculation ...................................................... 50
4.2 Automatic Ratio compensation ......................................................................... 52
4.3 Positive sequence current blocking................................................................... 53
4.4 Restricted earth fault current alarm ................................................................... 54
5 Setting list ................................................................................................................ 54
6 Report list ................................................................................................................. 56
7 Technical data .......................................................................................................... 56
Chapter 7 Impedance protection (21) ............................................................................ 57
1 Overview .................................................................................................................. 58
2 Function module description .................................................................................... 58
3 Detailed description.................................................................................................. 59
3.1 Protection principle ........................................................................................... 59
3.2 Logic diagram ................................................................................................... 61
3.3 Setting list ......................................................................................................... 61
3.4 Report list .......................................................................................................... 66
3.5 Technical data ................................................................................................... 67
Chapter 8 Interturn protection ........................................................................................ 69
1 Overview .................................................................................................................. 70
2 Function module description .................................................................................... 70
3 Detailed description.................................................................................................. 70
3.1 Protection principle ........................................................................................... 70
3.2 Logic diagram ................................................................................................... 71
3.3 Setting list ......................................................................................................... 72
3.4 Report list .......................................................................................................... 72
3.5 Technical data ................................................................................................... 72
Chapter 9 Overcurrent Protection (50, 51, 67) ............................................................... 73
1 Overview .................................................................................................................. 74
2 Function module description .................................................................................... 74
3 Detailed description.................................................................................................. 75
3.1 Protection principle ........................................................................................... 75
3.1.1 Inrush blocking components .......................................................................... 75
3.1.2 Compound voltage blocking unit ................................................................... 76
3.1.3 Directional component ................................................................................... 77
3.1.4 Definite time .................................................................................................. 78
3.1.5 Inverse time ................................................................................................... 78
3.1.6 Trip characteristic .......................................................................................... 79
3.1.7 Logic diagram ................................................................................................ 80
3.2 Setting list ......................................................................................................... 80
3.3 Report list .......................................................................................................... 83
3.4 Technical data ................................................................................................... 84
Chapter 10 Earth fault protection (50N, 51N, 67N) .......................................................... 85
1 Overview .................................................................................................................. 86
2 Function module description .................................................................................... 86
3 Detailed description.................................................................................................. 87
3.1 Protection principle ........................................................................................... 87
3.1.1 Inrush blocking components .......................................................................... 87
3.1.2 Directional component ................................................................................... 88
3.1.3 Definite time .................................................................................................. 89
3.1.4 Inverse time ................................................................................................... 90
3.1.5 Trip characteristic .......................................................................................... 91
3.2 Setting list ......................................................................................................... 92
3.3 Report list .......................................................................................................... 98
3.4 Technical data ................................................................................................... 99
IV
Chapter 11 Negative sequence current protection (46) .................................................. 101
1 Overview ................................................................................................................ 102
2 Function module description .................................................................................. 102
3 Detailed description ................................................................................................ 102
3.1 Protection principle.......................................................................................... 102
3.1.1 Definite time ................................................................................................ 102
3.1.2 Inverse time ................................................................................................. 103
3.1.3 Trip characteristic ........................................................................................ 104
3.2 Setting list ....................................................................................................... 104
3.3 Report list ........................................................................................................ 107
3.4 Technical data ................................................................................................. 108
Chapter 12 Overvoltage protection (59) ......................................................................... 109
1 Overview ................................................................................................................ 110
2 Function module description .................................................................................. 110
3 Detailed description ................................................................................................ 110
3.1 Protection principle.......................................................................................... 110
3.1.1 Definite time ................................................................................................ 111
3.1.2 Inverse time ................................................................................................. 111
3.1.3 Trip characteristic ........................................................................................ 112
3.1.4 Logic diagram .............................................................................................. 112
3.2 Setting list ....................................................................................................... 113
3.3 Report list ........................................................................................................ 115
3.4 Technical data ................................................................................................. 115
Chapter 13 Zero sequence voltage protection (64) ........................................................ 117
1 Overview ................................................................................................................ 118
2 Function module description .................................................................................. 118
3 Detailed description ................................................................................................ 118
3.1 Protection principle.......................................................................................... 118
3.1.1 Definite time ................................................................................................ 118
3.1.2 Inverse time ................................................................................................. 119
3.1.3 Trip characteristic ........................................................................................ 120
3.2 Setting list ....................................................................................................... 120
3.3 Report list ........................................................................................................ 121
3.4 Technical data ................................................................................................. 122
Chapter 14 Negative sequence voltage protection (47) ................................................. 123
1 Overview ................................................................................................................ 124
2 Function module description .................................................................................. 124
3 Detailed description ................................................................................................ 124
3.1 Protection principle.......................................................................................... 124
3.1.1 Definite time ................................................................................................ 124
3.1.2 Inverse time ................................................................................................. 125
3.1.3 Trip characteristic ........................................................................................ 126
3.2 Setting list ....................................................................................................... 126
3.3 Report list ........................................................................................................ 128
3.4 Technical data ................................................................................................. 128
Chapter 15 Undervoltage protection (27) ....................................................................... 129
1 Overview ................................................................................................................ 130
2 Function module description .................................................................................. 130
3 Detailed description ................................................................................................ 130
3.1 Protection principle.......................................................................................... 130
3.1.1 Blocking condition........................................................................................ 131
3.1.2 Definite time ................................................................................................ 131
3.1.3 Inverse time ................................................................................................. 131
3.1.4 Trip characteristic ........................................................................................ 132
3.1.5 Logic diagram .............................................................................................. 133
3.2 Setting list ....................................................................................................... 134
3.3 Report list ........................................................................................................ 135
V
3.4 Technical data ................................................................................................. 136
Chapter 16 Thermal overload protection (49) ................................................................ 137
1 Overview ................................................................................................................ 138
2 Function module description .................................................................................. 138
3 Detailed description................................................................................................ 138
3.1 Protection principle ......................................................................................... 139
3.2 Setting list ....................................................................................................... 140
3.3 Report list ........................................................................................................ 140
3.4 Technical data ................................................................................................. 141
Chapter 17 Circuit Breaker Failure protection (50BF) .................................................... 143
1 Overview ................................................................................................................ 144
2 Function module description .................................................................................. 144
3 Detailed description................................................................................................ 145
3.1 Protection function .......................................................................................... 145
3.1.1 Current check .............................................................................................. 145
3.1.2 Breaker auxiliary contacts check ................................................................. 146
3.1.3 CBF protection trip logic .............................................................................. 147
3.2 Setting list ....................................................................................................... 147
3.3 Report list ........................................................................................................ 148
3.4 Parameters ..................................................................................................... 148
Chapter 18 Dead zone protection (50DZ) ...................................................................... 149
1 Overview ................................................................................................................ 150
2 Function module description .................................................................................. 150
3 Detailed description................................................................................................ 151
3.1 Protection principle ......................................................................................... 151
3.2 Setting list ....................................................................................................... 153
3.3 Report list ........................................................................................................ 153
3.4 Technical data ................................................................................................. 153
Chapter 19 Stub protection (50STUB) ........................................................................... 155
1 Overview ................................................................................................................ 156
2 Function module description .................................................................................. 156
3 Detailed description................................................................................................ 156
3.1 Protection principle ......................................................................................... 156
3.2 Setting list ....................................................................................................... 157
3.3 Report list ........................................................................................................ 158
3.4 Technical data ................................................................................................. 158
Chapter 20 Pole discrepance protection (62PD) ............................................................ 159
1 Overview ................................................................................................................ 160
2 Function module description .................................................................................. 160
3 Detailed description................................................................................................ 160
3.1 Protection principle ......................................................................................... 160
3.2 Logic diagram ................................................................................................. 161
3.3 Setting list ....................................................................................................... 162
3.4 Report list........................................................................................................ 162
3.5 Technical data ................................................................................................. 162
Chapter 21 Overexcitation protection (24) ..................................................................... 163
1 Overview ................................................................................................................ 164
2 Function module description .................................................................................. 164
3 Detailed description................................................................................................ 164
3.1 Protection principle ......................................................................................... 164
3.2 Setting list ....................................................................................................... 167
3.3 Report list ........................................................................................................ 168
3.4 Technical data ................................................................................................. 168
Chapter 22 Underfrequency Protection (81UF).............................................................. 169
1 Overview ................................................................................................................ 170
2 Function module description .................................................................................. 170
3 Detailed description................................................................................................ 170
VI
3.1 Protection principle.......................................................................................... 170
3.1.1 Protection function introduction ................................................................... 170
3.1.2 Logic diagram .............................................................................................. 172
3.2 Setting list ....................................................................................................... 172
3.3 Report list ........................................................................................................ 173
3.4 Technical data ................................................................................................. 173
Chapter 23 Overfrequency protection (81OF) ................................................................ 175
1 Overview ................................................................................................................ 176
2 Function module description .................................................................................. 176
3 Detailed description ................................................................................................ 176
3.1 Protection principle.......................................................................................... 176
3.1.1 Protection function introduction ................................................................... 176
3.1.2 Logic diagram .............................................................................................. 177
3.2 Setting list ....................................................................................................... 177
3.3 Report list ........................................................................................................ 178
3.4 Technical data ................................................................................................. 178
Chapter 24 Non-electric protection................................................................................. 179
1 Overview ................................................................................................................ 180
2 Function module description .................................................................................. 180
3 Detailed description ................................................................................................ 180
3.1 Protection principle.......................................................................................... 180
3.2 Setting list ....................................................................................................... 180
3.3 Report list ........................................................................................................ 181
Chapter 25 Side differential protection ........................................................................... 183
1 Overview ................................................................................................................ 184
2 Function module description .................................................................................. 184
3 Detailed description ................................................................................................ 184
4 Protection principle ................................................................................................. 185
4.1 Differential and restraint current calculation .................................................... 185
4.2 Automatic Ratio compensation ....................................................................... 187
4.3 CT failure supervision ..................................................................................... 187
4.4 Side differential CT Saturation supervision ..................................................... 188
4.5 Side differential current supervision ................................................................ 189
5 Setting list............................................................................................................... 190
6 Report list ............................................................................................................... 191
7 Technical data ........................................................................................................ 191
Chapter 26 Secondary circuit supervision ...................................................................... 193
1 Overview ................................................................................................................ 194
2 Function module description .................................................................................. 194
3 Detailed description ................................................................................................ 194
3.1 Protection principle.......................................................................................... 194
3.1.1. Protection function introduction ................................................................... 194
3.1.2. Logic diagram .............................................................................................. 195
3.2 Setting list ....................................................................................................... 196
3.3 Report list ........................................................................................................ 197
3.4 Technical data ................................................................................................. 197
Chapter 27 T-zone protection......................................................................................... 199
1 Overview ................................................................................................................ 200
2 Function module description .................................................................................. 201
3 Detailed description ................................................................................................ 202
3.1 Protection principle.......................................................................................... 202
3.1.1. Protection startup component ...................................................................... 202
3.1.2. Three-side current differential protection. .................................................... 203
3.1.3. Two-side current differential protection ........................................................ 204
3.1.4. Overcurrent protection ................................................................................. 205
3.1.5. Charging protection ..................................................................................... 205
3.1.6. Abnormality check and judgment ................................................................ 205
VII
3.2 Setting list ....................................................................................................... 206
3.3 Report list ........................................................................................................ 207
Chapter 28 Gap protection ............................................................................................. 209
1 Overview ................................................................................................................ 210
2 Function module description .................................................................................. 210
3 Detailed description................................................................................................ 210
3.1 Protection principle ......................................................................................... 210
3.2 Setting list ....................................................................................................... 211
3.3 Report list ........................................................................................................ 212
Chapter 29 User-defined protection ............................................................................... 213
1 Overview ................................................................................................................ 214
2 Function module description .................................................................................. 214
3 Detailed description................................................................................................ 214
3.1 Protection principle ......................................................................................... 214
3.2 Setting list ....................................................................................................... 215
3.3 Report list ........................................................................................................ 216
Chapter 30 User-defined function .................................................................................. 217
1 Overview ................................................................................................................ 218
2 User-defined configuration ..................................................................................... 218
2.1 Open project ................................................................................................... 218
2.2 Binary input configuration ............................................................................... 218
2.3 Binary output configuration ............................................................................. 219
2.4 LED configuration ........................................................................................... 221
2.5 IO Matrix configuration .................................................................................... 222
2.5.1 IO Matrix channel configuration ................................................................... 222
2.5.2 IO Matrix function configuration ................................................................... 222
2.6 Binary input switch setting group .................................................................... 222
2.6.1 Function description .................................................................................... 222
2.6.2 Setting list .................................................................................................... 223
2.7 Configuration startup....................................................................................... 223
2.8 Other configuration ......................................................................................... 224
2.9 Defined logic ................................................................................................... 225
Chapter 31 Substation communication .......................................................................... 227
1 Overview ................................................................................................................ 228
2 Communication protocol ........................................................................................ 228
2.1 IEC 61850-8-1 communication protocol .......................................................... 228
2.2 IEC 60870-5-103 communication protocol ...................................................... 228
3 Communication port ............................................................................................... 228
3.1 Front plate communication port ...................................................................... 228
3.2 RS485 communication port ............................................................................. 228
3.3 Ethernet communication port .......................................................................... 228
4 Technical data ........................................................................................................ 229
5 Typical substation communication mode................................................................ 230
6 Typical clock synchronization mode ....................................................................... 230
Chapter 32 Man-machine interface (MMI) and operation ............................................... 231
1 Overview ................................................................................................................ 232
2 Function description ............................................................................................... 232
2.1 Liquid crystal display(LCD) ............................................................................. 232
2.2 Man-machine interface (MMI) ......................................................................... 232
2.3 Menu structure ................................................................................................ 234
Chapter 33 IED hardware .............................................................................................. 239
1 Overview ................................................................................................................ 240
1.1 IED structure ................................................................................................... 240
1.1.1 4U, 19 2 inch device .................................................................................. 240
1.1.2 4U, 19inch device ........................................................................................ 241
1.2 Module arrangement diagram ......................................................................... 242
VIII
1.2.1 4U, 19 2 inch device .................................................................................. 242
1.2.2 4U, 19inch device ........................................................................................ 242
2 Analog input module .............................................................................................. 243
2.1 Overview ......................................................................................................... 243
2.2 Analog input moduleintroduction ..................................................................... 243
2.3 Technical data ................................................................................................. 244
3 BIO module ............................................................................................................ 245
3.1 Overview ......................................................................................................... 245
3.2 BIO module introduction.................................................................................. 245
3.3 Technical data ................................................................................................. 247
4 CPU module ........................................................................................................... 248
4.1 Overview ......................................................................................................... 248
4.2 CPU module terminal diagram ........................................................................ 248
4.3 Technical data ................................................................................................. 250
5 Power supply module ............................................................................................. 250
5.1 Overview ......................................................................................................... 250
5.2 Power supply module terminals diagram ........................................................ 250
5.3 Technical data ................................................................................................. 251
6 TCS Module ........................................................................................................... 251
6.1 Overview ......................................................................................................... 251
6.2 TCS Module instructions ................................................................................. 252
6.3 Technical data ................................................................................................. 254
7 Test......................................................................................................................... 256
8 Structural design .................................................................................................... 258
9 CE Certification ...................................................................................................... 258
Chapter 34 Appendix ..................................................................................................... 259
1 IED parameter ........................................................................................................ 260
2 Report list ............................................................................................................... 261
2.1 Alarm report .................................................................................................... 261
2.2 Operation Report............................................................................................. 262
4 Typical wiring .......................................................................................................... 268
5 Inverse time characteristic...................................................................................... 271
5.1 Twelve types of IEC and ANSI time inverse property curve ............................ 271
5.2 Definable properties by the user ..................................................................... 271
5.3 Explanation of abbreviations ........................................................................... 272
5.3.1 Explanation of setting abbreviations ............................................................ 272
5.3.2 Explanation of logic switch abbreviations .................................................... 284
5.3.3 Explanation of trip and alarm reoport abbreviations .................................... 291
5.3.4 Explanation of operation report abbreviations ............................................. 299
5.3.5 Explanation of device menu abbreviations .................................................. 300
IX
Chapter 1Chapter 1 Introduction
Chapter 1 Introduction
1
Chapter 1Chapter 1 Introduction
1 IED overview
It is selective, reliable and high speed IED (Intelligent Electronic Device)
for transformer protection with powerful capabilities, which is suitable for
large and medium two- or three-winding transformers, and can be the
complicated application as main protection unit or full functions unit and
the communication with station automation system. The integrated and
flexible logic makes IED suitable for all winding connection mode.
Table 1 CSC-326 Application description
Type Sub-type Description
This series of IEDs use the new design concept, all the IEDs are
established in a general hardware and software platform. All functions are
modulized designed and at the same time diagnosis and debugging tools
are also provided. According to the actual needs of the field, through the
visual chart logic, users can customize all kinds of protection and control
logic. The equipment is highly reliable, flexible and maintainable and can be
adapted to the different site conditions.
2 IED characteristic
CSC-326 series transformer protection IED contains selectivity, reliability
and speed, application range is as bellow:
1) Integrated protection function and monitor and control function.
2) Meeting demands for three-phase tripping in transmission and
distribution grid.
3) Adopt corresponding type for different bay.
a) It is applicable to low voltage side with branch of three-winding
transformer and equipped with six-side differential and three-side
backup protection.
b) Differential protection acquiescently picks up current IH1 from
high voltage side, IH2 from high voltage side 2, IM from medium
side, and IL1 from low voltage side 1, IL2 from low voltage side 2
and IL3 from low voltage side 3.
c) Backup protection of high voltage side acquiescently picks up the
sum current of IH1 and IH2, backup protection of high voltage
side acquiescently picks up IM current, backup protection of low
voltage side 1, side 2 and side 3 acquiescently picks up current of
IL1, IL2 and IL3 respectively.
d) The T protection device is mainly used for protection of T zone
under 1.5 circuit breaker connection modes of 220kV and above
voltage level. It is suitable when CT ratio of three ends is the same.
The device is configured with three-side current differential
2
Chapter 1Chapter 1 Introduction
3 Basic function
3.1 Protection function
Functions supported by CSC-326-EB(L) and its typical application are as
follows:
Table 2 Typical application configuration
IEC 61850
Description ANSI code Remark
Logic node name
Three-winding
87T PDIF
differential
Two-winding
87T PDIF
differential
Restricted earth
87N REFPDIF HV/MV
fault protection
Impedance
21 HV
protection
Overcurrent
50,51 PTOC HV/MV/LV
protection
Directional
overcurrent 51V, 67 PTOC HV/MV
protection
Self-produced
zero-sequence 50N, 51N PEFM HV/MV/LV
current protection
External earth fault
50G, 51G PEFM HV/MV
protection
Direction earth fault
67N PEFM HV/MV
protection
3
Chapter 1Chapter 1 Introduction
IEC 61850
Description ANSI code Remark
Logic node name
Negative sequence
46 PPBR HV/MV/LV
current protection
Overvoltage
59 PTOV HV/MV
protection
Zero sequence
64 LV
voltage protection
Negative sequence
47 PPBV HV/MV
voltage protection
Undervoltage
27 PTUV HV/MV
protection
Thermal overload
49 PTTR HV/MV
protection
CBF protection 50BF RBRF HV
Dead zone
50SH-Z LV
protection
Stub protection 50STUB PTOC HV/MV
Three-phase
discordance 62PD LV
protection
Overexcitation
24 HV
protection
Underfrequency
81UF PTUF HV
protection
Overfrequency
81OF PTOF HV
protection
Non-electric
(BI-BO)
protection
CT failure HV/MV/LV
Tripping monitoring
4
Chapter 1Chapter 1 Introduction
Figure 1 Application 1
5
Chapter 1Chapter 1 Introduction
Figure 2 Application 2
6
Chapter 1Chapter 1 Introduction
Busbar 1
Differential
protection
Side CB
Middle CB
T-area
protection
Busbar 2
Description
Circuit breaker, disconnector and other switching devices control
Description
Current: Ia, Ib, Ic
Voltage: Ua, Ub, Uc, Uab, Ubc, Uca
Active power: P, Pa, Pb, Pc
Reactive power: Q, Qa, Qb, Qc
Power factor: COSφ
Frequency: F
7
Chapter 1Chapter 1 Introduction
Description
Self-diagnosis function
Communication protocol
IEC61850 Protocol
IEC60870-5-103 Protocol
DNP3.0
MODBUS
8
Chapter 2 Chapter 1Common functions
9
Chapter 2 Chapter 1Common functions
10
Chapter 2 Chapter 1Common functions
2 Diagnostic function
2.1 Overview
The device realizes the hardware and software self-checking and
monitoring of the device by means of energizing self-diagnosis and
operation self-monitoring to ensure the high reliability of the operation of
the device. Self-checking objects include key components of hardware
(such as analog sampling circuit, BIO output circuit, RAM and ROM) and
hardware accessories (such as backup battery, communication interface)
and important running parameters (such as settings, soft connectors), in
addition, the embedded two level software monitor can be used to monitor
the operation conditions of the software. When the device detects any
abnormal conditions, the device will record the abnormal events and drive
signal node and LED lights. For the key abnormal conditions, the device
will block the protection function and the important output circuit to prevent
the device from malfunctions.
The user can also check the important hardware circuit of the device
through the test command provided by the device, such as the AC circuit,
BI circuit and BO circuit, etc..
In order to cooperate automation system engineering implementation, the
device provides remote point test function, so the local SCADA and remote
master database can be checked, so the complicated manual point check
operation between the SCADA operator and remote operator is avoided.
Mainly includes the telesignalisation point check, telemetry point check.
11
Chapter 2 Chapter 1Common functions
Module
12
Chapter 2 Chapter 1Common functions
4 Authorization
To safeguard the interests of customers, accesses to the IED and the
debugging software are restricted in terms of authorization. In practice,
attention should be paid to the following aspects in the use of the IED and
associated debugging software:
1) There are two types of access to the IED:
a) Local, through the local HMI
b) Remote, through the communication ports
2) Different users have different authority to access to or operate device
or test the software
13
Chapter 3 Chapter 1Fault phase selection component
15
Chapter 3 Chapter 1Fault phase selection component
1 Overview
The fault phase selector component can distinguish the fault phase, and
make use of various phase selection principles to judge the different fault
conditions, so as to meet the requirements of trip phase selection.
The fault uses steady-status sequence component to judge the phase, for
power supply, terminal fault small current or no current, the low voltage
phase selector is used to judge the phase.
Phase selection function can be blocked by external binary input, VT
failure and CT failure.
Figure 5 Input and output signal diagram of fault phase selector component function
Table 8 Parameter description
Input:
Output:
3 Detailed description
3.1 Protection principle
3.1.1 Steady state component phase selector
The steady status component phase selector selects the phase through
the angle between zero sequence current component and negative
sequence current components, and the phase impedance is used to
confirm whether the phase selection is correct.
16
Chapter 3 Chapter 1Fault phase selection component
The analysis shows that the angle between the zero sequence current
component and negative sequence current component of the fault current
can be used to select the fault phase, the analysis is shown in the following
figure:
I0a
0 0
+30 AN,BCN -30
ABN BCN
0 0
+90 -90
CN,ABN BN,CAN
0 0
+150 CAN -150
For example, the angle between the negative sequence component and
the zero sequence components is between -30 degrees and +30 degrees,
and the fault type is A phase grounding or fault between phase B and C or
grounding fault between phase B and C.
As shown in the table above, area 2, 4, and 6 directly reflect the relative
fault type, but area 1, 3, and 5 may reflect the existence of two types of
fault, at this point, it is distinguished through phase impedance calculation.
If the phase impedance is larger than that of the phase impedance setting
value, the possibility of phase fault is eliminated, and it is judged to the
corresponding single-phase grounding fault, or it is judged to the
corresponding phase fault.
3.1.2 Undervoltage phase selection component
The steady status component phase selector is not reliable in the weak
feedback system, and the low voltage phase selector is applied to the
weak feedback system.
Discriminant formula for single phase fault and interphase fault is as
follows:
Upe<k×Upe_Secondary
or
Upp <k×Upp_Secondary
17
Chapter 3 Chapter 1Fault phase selection component
Where:
1) Upe and Upp are phase-to-earth voltage and phase-to-phase voltage
respectively
2) U_Secondary is system secondary rated voltage value
3) k is internal coefficient
For example, if only A phase voltage is low, it is judged to be A phase fault;
if only the AB phase-to-earth voltage is low, it is judged to be AB phase
fault; if AB, BC and CA phase-to-earth voltage are all low, then it is judged
to be three-phase fault.
18
Chapter 4 Basic protection component
19
Chapter 4 Basic protection component
1 Startup component
1.1 Overview
Startup component is used to detect faults in power system and initiate
related programs to selectively remove faults. The main startup elements
of CSC-326 are abrupt-change current component and differential startup
component.
Startup element includes:
1) Current sudden-change startup element;
2) Differential current startup component.
2 Report
Table 10 Report list
Report Description
IED startup IED startup
20
Chapter 5 Differential protection(87T)
21
Chapter 5 Differential protection (87T)
1 Overview
The numerical current differential protection represents the main protection
function of the IED. It provides a fast short-circuit protection for power
transformers. The protected zone is selectively limited by the CTs at its
ends. The device is able to perform this function on 2 or 3 winding
transformers in a variety of voltage levels and protected object types.
The IED provides numerical differential protection function which can be
used to protect power transformers in various configurations. For example,
it is possible to use it for a two-winding transformer, three-winding
transformer as well as auto-transformer. Examples for some of
applications are illustrated in the below figure.
CSC-326
CSC-326
22
Chapter 5 Differential protection(87T)
CSC-326
CSC-326
23
Chapter 5 Differential protection (87T)
DiffTripBO
1 1
BIBlk PerDiffATrip
2
PerDiffBTrip
3
PerDiffCTrip
4
InstDiffATrip
5
InstDiffBTrip
6
InstDiffCTrip
7
CT_Fail
8
Diff_Alm
Input:
BIBlk BIBlk
Output:
CT_Fail CT failure
3 Protection principle
This section describes basic principle of differential protection function.
First, the case of a single phase transformer with two windings is
considered. The basic principle is based on current comparison at two
sides of the protected object. Indeed, the differential protection function
makes use of the fact that a protected object carries always the same
current at its two sides in healthy operation condition. This current flows
into one side of the protected object and leaves it from the other side. A
difference in currents is an indication of a fault within this section. An
example of this condition is shown in below figure, when a fault inside the
protected zone causes a current I1prim. + I2prim flowing in from both sides
of the protected object.
24
Chapter 5 Differential protection(87T)
IED area
I1-prim. I2-prim.
CT-1 CT-2
Protected
transformer
I1 I2
CSC-326
Figure 12 Basic principle of differential protection for two ends (single phase)
For protected objects with three or more sides, the basic principle is
expanded in that the total of all currents flowing into the protected object is
zero in healthy operation, whereas in case of a fault the total in-flowing
current is equal to the fault current.
When an external fault causes a heavy current to flow through the
protected transformer, differences in the magnetic characteristics of the
current transformers CT-1 and CT-2 under saturation condition may cause
a significant difference in the secondary currents I1+I2 connected to IED. If
the difference is greater than the pickup threshold, the differential
protection function can trip even though no fault occurred in the protected
zone. To prevent the protection function from such erroneous operation, a
restraint (stabilizing) current is brought in. For differential protection IED,
the restraint current is normally derived from the I1 and I2. The next
subsection goes on to demonstrate how the differential and restraint
currents are calculated.
N •
I diff =
∑ i =1
Ii
N −1 •
1 •
I res = 2 I j (max) −
∑
i =1
I i (i ≠ j )
25
Chapter 5 Differential protection (87T)
I1 flows into the protected zone,I2 leaves the protected zone, i.e. I2 = –I1.
Idiff = I1 + I2 = I1 – I1 = 0
Ires = 0.5×| I1 - (–I1) | = 0.5×|2I1| = |I1|
No tripping effect (Idiff = 0); the restraint (Ires) corresponds to the external
fault current flowing through the protected object.
2) Internal fault, fed with equal currents from both sides:
that isI2 = I1
Idiff = I1 + I2 = I1 + I1 = 2 I1
Ires = 0.5×| I1 - I1| = 0
Tripping effect (Idiff) corresponds to double the fault current, and restraint
value (Ires) are equal to zero.
3) Internal fault, fed from one side only:
supposeI2 = 0
Idiff = I1 + I2 = I1 + 0 = I1
Ires = 0.5×|I1 - I2| =0.5× |I1 - 0| = 0.5×|I1|=0.5 I1
Tripping quantity (Idiff) and restraint quantity (Ires) are equal and
correspond to the single-sided fault current.
The results show that the device is capable to properly discriminate
internal and external faults by using the definitions proposed for differential
and restraint current. However, the device is still subjected to some
influences that induce differential currents even during normal operation
condition. These influences should be compensated in appropriate
manners. The specific treatments designed to cope with these influences
includes automatic ratio compensation and automatic vector group
compensation which are explored in the next subsections.
26
Chapter 5 Differential protection(87T)
SN
I 1N =
3U 1N
27
Chapter 5 Differential protection (87T)
SN=160MVA
U1N-HV=230kV U1N-LV=63kV
CTRATIO=500/1A CTRATIO=2000/1A
160 MVA
=
I1N − HV = 402 A
3 × 230
I 1N − HV 402
I 2 N − HV = = = 0.804 A
nCT 500
160 MVA
I 1N − LV = = 1466 A
3 × 63
1466
I 2 N − LV = = 0.733 A
2000
0.804
K CT −LV = = 1.097
0.733
160MVA 160MVA
U1N-HV=230kV U1N-MV=63kV
CTRATIO=500/1A CTRATIO=2000/1A
U1N-LV=20kV 25MVA
CTRATIO=2500/1A
28
Chapter 5 Differential protection(87T)
I 1N − LV 4619
I 2N − LV = = = 1.848A
nCT 2500
0.804
K CT −LV = = 0.435
1.848
29
Chapter 5 Differential protection (87T)
A B C
Yy0 c b
C B
a b c
Figure 15 Vector Group and zero sequence compensation for Yy0 transformer
The equations including the coefficient matrix are as follow:
IA′ 1 -1 0 IA
1
I B′ = ⋅ 0 1 -1 ⋅ IB
I′ 3
-1 0 1 IC
C
Ia′ 1 -1 0 Ia
1
I b′ =⋅ 0 1 -1 ⋅ Ib
I′ 3
-1 0 1 Ic
c
According to these matrices, if we deduct side one currents IA − IB , the
resulting current IA′ has the same direction as IA′ on side two.
Multiplying it with 1 3 , matches the absolute value. The matrices
describe the con-version for all three phases. Using these matrices, the
elimination of zero sequence currents are warranted regardless of starpoint
earth connection.
As mentioned previously, the two above equations can be used similarly
for auto-transformers, as the auto-connected windings in
auto-transformers can only be connected Y(N)y(n)0. If the starpoint is
earthed, both the auto-connected HV and LV windings are affected. The
zero sequence components in current flowing through both sides of the
transformer are then coupled because of the common starpoint. These
zero sequence components are eliminated by the application of the
matrices presented in the above equations.
2) Take example for Yd1 connection, including similar ones of Yd1 and
YNd1 without earthing transformer installed at delta side. Below figure
shows an example in case of Yd1 connection group with no earthed
starpoint.
30
Chapter 5 Differential protection(87T)
A B C
A
a
Yd1 c
C b B
a b c
•′ •
I I
a 2 − 1 − 1 a
• 1 •
I ′b = .− 1 2 − 1. I b
• 3 − 1 − 1 2 •
I ′c I c
3) Take example for Ydd3 connection, including similar ones of Ydd3 and
YNdd3 without earthing transformer installed at delta sides. Below
figure shows an example in case of Ydd3 connection group with no
earthed starpoint in Wye side.
31
Chapter 5 Differential protection (87T)
A B C
A
c(c’)
Ydd3 a(a’)
C b(b’) B
A
c
Yd5 b
a
C B
c a b
32
Chapter 5 Differential protection(87T)
•′ •
Ia I
2 − 1 − 1 a
1
•
′ = − − . I•
I b . 1 2 1 b
• 3 − 1 − 1 2 •
I ′c I c
5) Take example for Dy1 connection, including similar ones of Dy1 and
Dyn1 without earthing transformer installed at delta side. Below figure
shows an example in case of Dy1 connection group with no earthed
starpoint.
A B C
Dy1 c
b
C B
a b c
Ia′ 1 -1 0 Ia
1
I b′ =⋅ 0 1 -1 ⋅ Ib
I′ 3
-1 0 1 Ic
c
Subsequent to application of the magnitude, vector group and zero
sequence compensation, the IED use the following calculated quantities
(per phase) to discriminate between internal and external faults:
fundamental component of differential and restraint currents together with
instantaneous value, second and 5th harmonic contents of differential
current. The following sections go on to demonstrate the fault recognition
criteria using these derived quantities.
33
Chapter 5 Differential protection (87T)
“InstantaneousDiffOn”=1
&
Instantaneous differential
phase A output
IDA>“InstantDiffCurrSet”
&
Instantaneous differential
phase B output
IDB> “InstantDiffCurrSet”
&
Instantaneous differential
phase C output
IDC> “InstantDiffCurrSet”
34
Chapter 5 Differential protection(87T)
Slope 3
Trip area
Slope 2 Restraint
Slope 1 area
Differential 1 restranit
startup
1 restraint break point 1 1 restraint break point 2 Restraint current
35
Chapter 5 Differential protection (87T)
36
Chapter 5 Differential protection(87T)
“DiffOn”=1
Phase A
I diff − A , I rest − A Ratio differential
ID>
& Phase A output
Ratio differential
blocking Phase A
Phase B
I diff − B , I rest − B
ID>
Ratio differential
& Phase B output
Ratio differential
blocking Phase B
Phase C
I diff −C , I rest −C
ID>
Ratio differential
& Phase C output
Ratio differential
blocking Phase C
“CTFailBlkDiff”=1
&
CT failure
37
Chapter 5 Differential protection (87T)
Equation3
The smaller values of X(k) represent that the calculated point corresponds
to fault condition with higher confidence level. Alternatively, the larger
values of X(k) gives a picture that there is large content of inrush current in
the waveform. Assume that X(k) belongs to “inrush Fuzzy class” with
membership function of A[X(k)]. Then, the fuzzy similarity coefficient for
the n calculated values of X(k) in one cycle is defined as below equation.
n
N= ∑ A[ X (k )] / n
k =1
Equation4
The derived value of N is used in the IED to assess the differential current
corresponds to inrush condition or not. To do so, the value of N is
compared with a threshold K, and inrush content is recognized in the
current waveform, if N>K.
“DiφφOn”=1
“ExcitInrushBlkDiφφ”=1 &
&
“2ndHRestr”=1 ≥1
T
I diφφ − A−φ 2
> Kϕ 2
I diφφ − A−φ
&
T 2ndHBlkDiφφ
≥1 ≥1
I diφφ − B −φ 2
> Kϕ 2
I diφφ − B −φ
≥1
I diφφ −C −φ 2 &
> Kϕ 2
I diφφ −C −φ T
Kφ 2 :“2ndHRestrCoeφ” T:“2ndHCrossBlkTime”
Figure 23 Logic diagram of excitation inrush detected by using the secondary harmonic
mode
38
Chapter 5 Differential protection(87T)
“DiffOn”=1
“ExcitInrushBlkDiff”=1 &
&
“2ndHRestr”=0 ≥1
T
&
≥1 2ndHBlkDiff
T
≥1
≥1
&
Phase C Fuzzy Recognition
T
T:“2ndHCrossBlkTime”
Figure 24 Logic diagram of excitation inrush detected by using fuzzy recognition mode
Equation5
39
Chapter 5 Differential protection (87T)
“OEBlkDiff”=1
“OE5thHOn”=1
“OE5thHOn”=0
I diff − A−f 3
> K ϕ −3 / 5
I diff − A−f &
&
I diff − A−f 5 ≥1
> K ϕ −3 / 5
T
T
≥1
I diff − A−f
&
I diff − B −f 3 &
> K ϕ −3 / 5 &
≥1
T
I diff − B −f T
≥1 ≥1 3rd/5thHBlkDiff
I diff − B −f 5 &
> K ϕ −3 / 5
I diff − B −f
≥1
& T
T
I diff −C −f 3 &
> K ϕ −3 / 5
I diff −C −f
≥1
I diff −C −f 5
> K ϕ −3 / 5 &
I diff −C −f
Kf −3/5 3rd/5thHBlkCoef
T:3rd/5thHBlkTime
40
Chapter 5 Differential protection(87T)
&
{IMV_A, IMV_B, IMV_C}和 {ILV_A, ILV_B,
ILV_C} All current is unchanged
CT Failure
In {IMV_A, IMV_B, IMV_C}, only one or
two phase reduce. &
≥
& 1
{IHV_A, IHV_B, IHV_C} 和 {ILV_A,
ILV_B, ILV_C} All current is
unchanged
&
{IHV_A, IHV_B, IHV_C} 和 {IMV_A, IMV_B,
IMV_C} All current is unchanged
Where:
Iφ2 is the secondary harmonic of current on each side;
Iφ3 is the third harmonic of current on each side;
41
Chapter 5 Differential protection (87T)
I D.alarm =
max{0.3 I _ Percent Diff , 0.1A} if I n 1A
I D.alarm =
max{0.3 I _ Percent Diff , 0.3 A} if I n 5 A
Logic of differential current supervision is shown in below figure.
42
Chapter 5 Differential protection(87T)
“DiffOn”=1
Idiff_A>ID.alarm
Idiff_C>ID.alarm
43
Chapter 5 Differential protection (87T)
44
Chapter 5 Differential protection(87T)
4 Technical data
Note: In is CT rated secondary current, 1A or 5A.
Table 15 Technical data for differential protection
Content Range and value Error
Instantaneous differential
0.5In to 20.00In ≤ ±3% setting or ±0.02In
current
Percentage differential
0.05In to 4.00In ≤ ±3% setting or ±0.02In,
current
Restraint current 1 0.1In to 1In ≤ ±3% setting or ±0.02In
Restraint current 2 0.1In to 10In ≤ ±3% setting or ±0.02In
Slope 1 0.0 to 0.2
Slope 2 0.2 to 0.7
Slope 3 0.25 to 0.95
Second harmonic restraint 0.05 to 0.80 fundamental
ratio wave
Third or fifth harmonic
0.05 to 0.80
restraint ratio
Reset ratio of restrained
About 0.7
differential
it ≤ 30ms when the setting is
Operating time of restraint
in 200% times, and
differential
IDifferential>2IRestraint
Typical trip time is 20ms
Operating time of
when the setting is in 200%
instantaneous differential
times
Reset time about 40ms
45
Chapter 6 Chapter 1Restricted earth fault protection
(87REF)
47
Chapter 6 Chapter 1Restricted earth fault protection
(87REF)
1 Overview
The restricted earth fault protection detects earth faults in power
trans-formers with earthed starpoint or in non-earthed power transformers
with a starpoint former (earthing transformer/reactor) installed inside the
protected zone. A precondition for using this function is that a CT should be
installed in the starpoint connection, i.e. between the starpoint and earth.
The starpoint CT and the phase CTs define the limits of the protected zone
by restricted earth fault protection. It includes a restricted earth fault
protection functional module.
Figure 29 The input and output signals of restricted earth fault protection function
diagram
Table 16 Parameter description
Input:
BIBlk BIBlk
REF Output:
Restricted earth fault
Trip
protection trip
Restricted earth fault current
Alarm
is over limit
3 Detailed description
The IED provides two restricted differential protection functions which can
be used independently at various locations. For example, it is possible to
use them for both windings of YNyn transformer which is earthed at both
starpoints. Further, one of them can be implemented to protect an earthed
transformer winding and the other for an earthing transformer/reactor. In
case of auto-transformers, one of them is sufficient to protect the
auto-windings. Examples for some of applications are illustrated in the
below figure.
48
Chapter 6 Chapter 1Restricted earth fault protection
(87REF)
HV LV
IA.2
A a
IB.2
B b
IC .2
C c
HV LV
Ia′ .2
A a
Ib′ .2
B b
Ic′.2
C c
3I01
′
3I02
′ = Ia′ .2 + Ib′ .2 + Ic′.2
CSC-326
HV LV
IA.2
Ia′ .2
A a
IB.2
Ib′ .2
B b
IC .2 Ic′.2
C c
3I01 3I01
′
CSC-326
3I02
′ = Ia′ .2 + Ib′ .2 + Ic′.2
49
Chapter 6 Chapter 1Restricted earth fault protection
(87REF)
IA.2
A Ia.3
a
IB.2
Ib .3
B
b
IC .2
C Ic .3
c
3I01
CSC-326
3I03 = Ia.3 + Ib.3 + Ic.3
4 Protection principle
Under proper operation condition, no neutral point current 3I0 flows
through the neutral point CT. Furthermore, the sum of the phase currents
3I02 =IA.2 + IB.2 + IC.2 which is almost zero. In case of auto-transformer,
both the neutral point currents 3I02 =IA.2 + IB.2 + IC.2 and 3I03 =IA.3 +
IB.3 + IC.3 are zero. With an earth fault inside the protected zone, a
neutral point current 3I01 flows.
Moreover, depending on the earthing conditions of the power system
outside the protected zone, a further earth current may be recognized in
the residual current path of the phase CTs (3I02 and 3I03). Since all the
currents flowing into the protected zone are defined positive, the residual
current from the system (3I02 and 3I03) is more or less in phase with the
neutral point current (3I01). With an earth fault outside the protected zone,
a neutral point current 3I01 flows into the protected zone, together with
equal residual current 3I02 and 3I03 which flows toward outside of the
protected zone, through the phase CTs. The direction of the current flowing
into the protection zone is the positive one, the neutral point current is in
phase opposition with 3I02 and 3I03.
With the described situations, it may seem to be simple to discriminate an
internal fault from an external one. With the described situations, it may
seem to be simple to discriminate an internal fault from an external one.
However, there are some difficulties to do so. For instance, when a strong
fault without earth connection occurs outside the protected zone, a
residual current may appear in the residual current path of the phase CTs.
The residual current is caused by different degrees of saturation in phase
CTs and could simulate a fault in the protected zone. Thus, additional
measures should be taken to prevent this current to cause false tripping.
To achieve this objective, the restricted earth fault protection provides a
restraint quantity.
50
Chapter 6 Chapter 1Restricted earth fault protection
(87REF)
I diff 0 = 3I01 + 3I02 + 3I03
{
I rest 0 = max 3I01 , 3I02 , 3I03 } (1)
Idiff0 and Irest0 are compared by the restricted earth fault protection with a
dual-slope operating characteristic defined by below equation and shown
in below figure.
I diff 0 ≥ I 0 D if I res 0 ≤ I 0 D / S 0 D
(2)
I diff 0 ≥ S 0 D × I res 0 if I res 0 > I 0 D / S 0 D
Trip Area
Slope _ REF
Restraint
Earth Fault Restraint Area
Startup
Current
I Res0
“REFTrip”=1
T1
“REFAlarm”=1
T2
T1:“REFTripTime” T2:“REFAlarmTime”
51
Chapter 6 Chapter 1Restricted earth fault protection
(87REF)
according to the definition of the positive direction of current, 3I02 shall be
a minus, which means 3I02 = –3I01.
Idiff0 = |3I01 + 3I02| = |3I01 – 3I02|= 0
Ires0 = max {|3I01|, |3I02|} = |3I01|
No differential current (Idiff0 = 0), the restricted current (Irest0) is the
external fault current flowing into the neutral point.
Internal fault, fed only from the starpoint:
In this case, 3I02=0, thus,
Idiff0 = |3I01 + 3I02| = |3I01 + 0| = |3I01|
IIres0 =Max{|3I01|, |3I02|} = |3I01|
Both the tripping (Idiff0) and the restraint (Irest0) quantities correspond to
the fault current flowing through the starpoint.
Internal fault, fed from the starpoint and from the system, e.g. with equal
earth current magnitude:
Both 3I01 and 3I02 flow into the protection zone, they are positive,
therefore, 3I02 = 3I01.
Idiff0 = |3I01 + 3I02 |= |3I01 + 3I02 |= 2 ×|3I01|
Ires0 = max {|3I01|, |3I02|} = |3I01|
Tripping quantity (Idiff0) corresponds to double the fault current flowing
through the starpoint connection, and restraint quantity (Irest0) is equal to
the fault current.
The results show that the device is capable to properly discriminate
internal and external earth faults by using the definitions proposed for
differential and restraint current. However, the device is still subjected to
some influences that induce differential currents even during normal
operation condition. These influences should be compensated in
appropriate manner. The specific treatments designed to cope with these
influences includes automatic ratio compensation which is explored as
follows.
52
Chapter 6 Chapter 1Restricted earth fault protection
(87REF)
secondary currents of starpoint CTs of ordinary transformers are
calculated as follow:
nStarpo int −W 1
K Starpo int −W 1 = (3)
nPhase −W 1
nStarpo int
K Starpo int = (5)
nPhase −W 1
53
Chapter 6 Chapter 1Restricted earth fault protection
(87REF)
Only when the ratio is greater than 15% can the REF protection trip.
5 Setting list
Table 17 Restricted earth fault protection of high voltage side setting
Default
Range
Number Setting name value Unit Remark
(In:5A/1A)
(In:5A/1A)
1. HVSideREFStartupCurr 0.05In~2In 2 A
2. HVSideREFAlarmCurr 0.05In~2In 2 A
2. MVSideREFAlarmCurr 0.05In~2In 2 A
54
Chapter 6 Chapter 1Restricted earth fault protection
(87REF)
Table 19 Restricted earth fault protection of low volatge side setting
Default
Range
Number Setting name value Unit Remark
(In:5A/1A)
(In:5A/1A)
1. LVSideREFStartupCurr 0.05In~2In 2 A
2. LVSideREFAlarmCurr 0.05In~2In 2 A
3. LVSideREFRestrCoef 0.2~0.95 0.5
4. LVSideREFTripTime 0~60 0.03 s
5. LVSideREFAlarmTime 0~60 0.03 s
Table 20 Restricted earth fault protection of high voltage side logic switch
Default
Number Logic switch name Set mode Remark
value
Enable restricted earth fault
HVSideREFProtTrip protection of high voltage side
1. 0/1 0
trip
1-On, 0-Off
Enable high restricted earth fault
2. HVSideREFAlarm 0/1 0 protection alarm
1-On, 0-Off
CT failure blocking restricted
3. CTFailBlkHVSideREF 0/1 0 earth fault protection
1-On, 0-Off
Table 21 Restricted earth fault protection of medium voltage side logic switch
Default
Number Logic switch name Set mode Remark
value
Enable restricted earth fault
MVSideREFProtTrip protection of medium voltage
1. 0/1 0
side trip
1-On, 0-Off
Enable restricted earth fault
MVSideREFAlarm protection alarm of medium
2. 0/1 0
voltage side
1-On, 0-Off
CT failure blocking restricted
CTFailBlkMVSideREF earth fault protection of medium
3. 0/1 0
voltage side
1-On, 0-Off
Table 22 Restricted earth fault protection of low voltage side logic switch
Default
Number Logic switch name Set mode Remark
value
Enable restricted earth fault
LVSideREFTrip protection of low voltage side
1. 0/1 0
trip
1-On, 0-Off
Enable restricted earth fault
LVSideREFAlarm protection alarm of low voltage
2. 0/1 0
side
1-On, 0-Off
CT failure blocking restricted
CTFailBlkLVSideREF earth fault protection of low
3. 0/1 0
voltage side
1-On, 0-Off
55
Chapter 6 Chapter 1Restricted earth fault protection
(87REF)
6 Report list
Table 23 Report list
7 Technical data
Note: In is CT rated secondary current, 1A or 5A.
Table 24 Restricted earth fault protection technical parameter
Content Range and value Error
Differential current 0.05 In to 2.00 In ≤±3% setting or 0.02In
Slope 0.2 to 0.95
≤ ±1% setting or +40 ms,
Time delay 0.00 to 60.00s, step 0.01s when trip value is set as
200% setting
Reset ratio Approx. 0.7, at tripping
≤ 30ms when the setting is in
Trip time
200% times
Reset time About 40ms
56
Chapter 7 Chapter 1Impedance protection (21)
57
Chapter 7 Chapter 1Impedance protection (21)
1 Overview
The sub-transmission lines are extended, including lots of branches and
different distance lines, so the situations are complicated. This kind of
system has higher requirement for fault isolating, in order to sustain the
stability and safety of power system.
The configuration of distance protection can meet basic requirements of
transformer and transmission line. This protection function has the
following characteristics:
It provides phase-to-phase and phase-to-earth impedance protection of 1
stage 4 times.
Figure 37 The input and output signals of distance protection function diagram
Table 25 Parameter description
Input:
BIBlk BIBlk
Output:
Input:
BIBlk 1: BI blocking
DISPN Output:
58
Chapter 7 Chapter 1Impedance protection (21)
3 Detailed description
3.1 Protection principle
Protection startup element: there are abrupt current startup element and
negative current startup element, where the abrupt current startup element
is equal to the main protection, and the negative current startup element is
as follows:
I 2 > I Qd 2
I Qd 2=0.2 I e
I
Where: I 2 is the effective value of negative current, Qd 2 is the fixed
threshold, I e rated current for transformer.
Distance measurement element: the action characteristics of phase-phase
distance protection and phase-earth distance protection can fixed as
full-distance characteristics or offset distance characteristics.
78° to 90°distance sensitivity angle can be fixed.
Phase-to-phase distance protection can adopt 0° connection, and the
voltage selects the phase-to-phase voltage, and the current takes the
• • • • • •
• • •
where: U ϕ is phase-to-earth voltage, I ϕ is phase current, 3 I 0 is self
calculated zero sequence current, K is zero sequence compensation
coefficient, in which the phase-to-earth distance zero compensation
coefficient K pointing to the main transformer is fixed as 0, and the
phase-to-earth distance zero compensation coefficient K pointing to the
busbar can be fixed by the setting.
When the software calculates, it regularly adopts the compensation
coefficient K as 0 to calculate the phase-earth distance, and makes the
compensation for the setting of phase-earth distance pointing to busbar
(whose zero sequence compensation coefficient can be fixed). The
specific implementation is as the following analysis
59
Chapter 7 Chapter 1Impedance protection (21)
jX jX
Z1 Z1
φ φ
R R
Z2
Z2P
a) b)
Figure 38 The trip characteristics of impedance components
The operation characteristics of distance protection is shown as figure 34
(φ is the sensitivity angle), in which figure a) is the circular characteristics
corresponding to the distance setting fixed according to the actual
operation; b) is the distance circular characteristics. where: Z1 is the value
of phase-earth distance pointing to main transformer, Z2 is the value of
phase-earth pointing to busbar, and the both can be fixed; Z2P is the value
after the compensation of phase-earth distance Z2 pointing to busbar,
automatically calculated by the software.
As for phase-to-earth distance pointing the main transformer, without
considering its protection range extending to the opposite busbar, its
corresponding phase-earth distance do not consider the zero
•
Uϕ
compensation, and the distance calculated by the equation Z ′ϕdϕ = •
is
Iϕ
matched with the actual setting protection value; as for the phase-earth
distance, Z2 is matched with the distance value calculated by the equation
•
Uj
Z jdj = • •
; a conversion relation between the equation and the
I j + K ⋅3 I 0
equation used in the actual calculation:
• • • •
Uj Uj Ij Ij
Z jdj = • •
= •
× • •
= Z ′jdj × • •
= Z ′jdj × M ,
Ij + K ⋅3I 0 Ij Ij + K ⋅3I 0 Ij + K ⋅3I 0
60
Chapter 7 Chapter 1Impedance protection (21)
“PPZ1On/PEZ1On”=1
I2>0.2Ie ≥1
&
T1
Phase-to-phase/
△iφ>0.2IN phase-to-earth
zone 1 trip
Zφ is within the
area
VT Failure
T:“PPZ1Time/PEZ1Time”
2. HVSidePEZSensitiveAngle 78~90 80 .
4. HVSidePPZ1PointToTransf 0.1~125 10 Ω
5. HVSidePPZ1PointToSystem 0.1~125 10 Ω
61
Chapter 7 Chapter 1Impedance protection (21)
Default
Number Setting name Range Unit Remark
value
6. HVSidePPZ1Time1 0.1~20.0 20 s
7. HVSidePPZ1Time2 0.1~20.0 20 s
8. HVSidePPZ1Time3 0.1~20.0 20 s
9. HVSidePPZ2PointToTransf 0.1~125 10 Ω
62
Chapter 7 Chapter 1Impedance protection (21)
Default
Number Setting name Range Unit Remark
value
39. HVSidePEZ3Time3 0.1~20.0 20 s
Note: Impedance setting of medium voltage side is the same to that of high
voltage side
Table 27 Distance protection logic switch
Default
Number Logic switch name Set mode Remark
value
Enable
phase-to-phase
impedance stage 1
1. HVSidePPZ1Time1On 0/1 0
time 1 protection of
high voltage side
1-On, 0-Off
Enable
phase-to-phase
impedance stage 1
2. HVSidePPZ1Time2On 0/1 0
time 2 protection of
high voltage side
1-On, 0-Off
Enable
phase-to-phase
impedance stage 1
3. HVSidePPZ1Time3On 0/1 0
time 3 protection of
high voltage side
1-On, 0-Off
Enable
phase-to-phase
impedance stage 2
4. HVSidePPZ2Time1On 0/1 0
time 1 protection of
high voltage side
1-On, 0-Off
Enable
phase-to-phase
impedance stage 2
5. HVSidePPZ2Time2On 0/1 0
time 2 protection of
high voltage side
1-On, 0-Off
Enable
phase-to-phase
impedance stage 2
6. HVSidePPZ2Time3On 0/1 0
time 3 protection of
high voltage side
1-On, 0-Off
Enable
7. HVSidePPZ3Time1On 0/1 0
phase-to-phase
63
Chapter 7 Chapter 1Impedance protection (21)
Default
Number Logic switch name Set mode Remark
value
impedance stage 3
time 1 protection of
high voltage side
1-On, 0-Off
Enable
phase-to-phase
impedance stage 3
8. HVSidePPZ3Time2On 0/1 0
time 2 protection of
high voltage side
1-On, 0-Off
Enable
phase-to-phase
impedance stage 3
9. HVSidePPZ3Time3On 0/1 0
time 3 protection of
high voltage side
1-On, 0-Off
Enable
phase-to-phase
10. HVSidePPZ4On 0/1 0 impedance stage 4 of
high voltage side
1-On, 0-Off
Phase-to-phase
impedance stage 1
blocking by power
11. HVSidePPZ1BlkByPowerSwing 0/1 0
swing of high voltage
side
1-On, 0-Off
Phase-to-phase
impedance stage 2
blocking by power
12. HVSidePPZ2BlkByPowerSwing 0/1 0
swing of high voltage
side
1-On, 0-Off
Phase-to-phase
impedance stage 3
blocking by power
13. HVSidePPZ3BlkByPowerSwing 0/1 0
swing of high voltage
side
1-On, 0-Off
Phase-to-phase
impedance stage 4
blocking by power
14. HVSidePPZ4BlkByPowerSwing 0/1 0
swing of high voltage
side
1-On, 0-Off
Enable phase-to-earth
impedance stage 1
15. HVSidePEZ1Time1On 0/1 0 time 1 protection of
high voltage side
1-On, 0-Off
Enable phase-to-earth
16. HVSidePEZ1Time2On 0/1 0
impedance stage 1
64
Chapter 7 Chapter 1Impedance protection (21)
Default
Number Logic switch name Set mode Remark
value
time 2 protection of
high voltage side
1-On, 0-Off
Enable phase-to-earth
impedance stage 1
17. HVSidePEZ1Time3On 0/1 0 time 3 protection of
high voltage side
1-On, 0-Off
Enable phase-to-earth
impedance stage 2
18. HVSidePEZ2Time1On 0/1 0 time 1 protection of
high voltage side
1-On, 0-Off
Enable phase-to-earth
impedance stage 2
19. HVSidePEZ2Time2On 0/1 0 time 2 protection of
high voltage side
1-On, 0-Off
Enable phase-to-earth
impedance stage 2
20. HVSidePEZ2Time3On 0/1 0 time 3 protection of
high voltage side
1-On, 0-Off
Enable phase-to-earth
impedance stage 3
21. HVSidePEZ3Time1On 0/1 0 time 1 protection of
high voltage side
1-On, 0-Off
Enable phase-to-earth
impedance stage 3
22. HVSidePEZ3Time2On 0/1 0 time 2 protection of
high voltage side
1-On, 0-Off
Enable phase-to-earth
impedance stage 3
23. HVSidePEZ3Time3On 0/1 0 time 3 protection of
high voltage side
1-On, 0-Off
Enable phase-to-earth
impedance stage 4 of
24. HVSidePEZ4On 0/1 0
high voltage side
1-On, 0-Off
Phase-to-earth
impedance stage 1 is
blocked by power
25. HVSidePEZ1BlkByPowerSwing 0/1 0
swing of high voltage
side
1-On, 0-Off
Phase-to-earth
impedance stage 2 is
26. HVSidePEZ2BlkByPowerSwing 0/1 0
blocked by power
swing of high voltage
65
Chapter 7 Chapter 1Impedance protection (21)
Default
Number Logic switch name Set mode Remark
value
side
1-On, 0-Off
Phase-to-earth
impedance stage 3 is
blocked by power
27. HVSidePEZ3BlkByPowerSwing 0/1 0
swing of high voltage
side
1-On, 0-Off
Phase-to-earth
impedance stage 4 is
blocked by power
28. HVSidePEZ4BlkByPowerSwing 0/1 0
swing of high voltage
side
1-On, 0-Off
Note: Impedance logic switch of medium voltage side is the same to that of
high voltage side.
66
Chapter 7 Chapter 1Impedance protection (21)
67
Chapter8 Chapter 1Interturn protection
69
Chapter8 Chapter 1Interturn protection
1 Overview
Inter-turn short circuit is a common internal fault form of the reactor. The
device adopts the principle of fault-tolerant recovery to adapt inter-turn
protection principle.
InterTurn Protection
1 1
BIBlk Operation
Figure 40 The input and output signals of interturn protection function diagram
Table 30 Parameter description
Function Identifier Description
Input:
BIBlk BIBlk
ITURN
Output:
3 Detailed description
Inter-turn short circuit is a common internal fault form of the reactor. The
device adopts the principle of fault-tolerant recovery to adapt inter-turn
protection principle.
70
Chapter8 Chapter 1Interturn protection
better distinguish the inter-turn fault of the small turn number. In order to
eliminate the influence of irrelevant zero flow on sensitivity of inter turn
protection during non full phase operation, impedance criterion is used.
The forward direction of zero sequence voltage and zero sequence
current is shown below.
PT
System
*
Reactor CT
Figure 41 Zero sequence voltage and zero sequence current positive direction
definition
The action equation of the zero sequence power directional element is:
(3U 0 + K ⋅ Z ⋅ 3I02 )
0° < Arg < 180°
3I
02
(3U 0 + K ⋅ Z ⋅ 3I0 ) ≥1
0 < rg < 180
3I
0
Z < 0.66 Z 2 n
VT failure ≥1
CT failure
71
Chapter8 Chapter 1Interturn protection
72
Chapter 9 Chapter 1Overcurrent protection (50, 51, 67)
73
Chapter 9 Chapter 1Overcurrent protection (50, 51, 67)
1 Overview
When the power system fault occurs, the current of the system increases,
and the overcurrent protection can avoid the damage of the fault current to
the equipment. The device provides three-stage of overcurrent protection
of high, middle and low voltage side, each stage provides options of
overcurrent definite time protection or inverse time protection. Each stage
of overcurrent protection has the same logic criterion, and each stage can
be enabled or disabled independently.
Each stage of the overcurrent protection can be selectively input harmonic
blocking element and directional element, and based on the phase
measurement of the current action. In addition, each stage of the
overcurrent definite-time protection can be selectively input the complex
pressure blocking component.
Main characteristics of overcurrent protection:
1) The device provides 3 stages of overcurrent protection on each high,
medium and low voltage side, each stage adopts definite time or 12
IEC and ANSI standard curve of inverse time characteristic, and it
adopts user defined characteristic curve as well;
2) The flow direction sensitive angle can be adjusted to meet different
application occasions;
3) Each section of the overcurrent protection can be respectively set
whether it inputs direction element, whether the action area is
"forward" or "reverse" action is set by the logic switch;
4) Each section of the overcurrent protection can be respectively set
whether it’s through harmonic locking;
5) Harmonic blocking can lock across;
6) Each section of the overcurrent protection can be respectively set
whether it’s through re-pressing locking;
7) The protection of the input direction component needs to detect
whether the VT secondary circuit disconnects. If VT is disconnected,
the protection of the input direction component can be set as VT
disconnection protection or VT disconnection protection blocking.
Figure 43 The input and output signals of overcurrent protection function diagram
74
Chapter 9 Chapter 1Overcurrent protection (50, 51, 67)
Output:
3 Detailed description
IED is equipped with 3 stages overcurrent protection, please refer to the
setting list for details.
75
Chapter 9 Chapter 1Overcurrent protection (50, 51, 67)
Time<“Iarm/rossBlkTime”
“h/1BlkBy2ndI”=1
“h/1BlkBy2ndI”=1
“h/1BlkBy2ndI”=1
76
Chapter 9 Chapter 1Overcurrent protection (50, 51, 67)
min(Uab,Ubc,Uca)<“PPVoltBlkSet”
≥1
Negative Sequence Voltage>
Multi-voltage
“U2BlkSet” Component Satisfied
min(Uab,Ubc,Uca)<“PPVoltBlkSet”
Multi-voltage
Component Satisfied &
≥1
Overcurrent Stage1 Multi-voltage
“OCStage1BlkByVolt”=1 Component Satisfied
“OCStage1BlkByVolt”=0
Bisector Bisector
RVD
Φ Φ
0° 0°
U BC_Ref U BC_Ref
5°
-IA -IA 5°
77
Chapter 9 Chapter 1Overcurrent protection (50, 51, 67)
“DirOCStage1”=0
78
Chapter 9 Chapter 1Overcurrent protection (50, 51, 67)
B are determined when the value is from 1 to 12, see the following Table;
when the value is 13, it is user defined characteristics, calculate the trip
delay according to the setting of the A, P, B, T. while timing, overcurrent
protection trips. When the delay is less than the "InvTimeOCMinTime", the
component trip according to the "InvTimeOCMinTime".
Table 37 Curve definition
79
Chapter 9 Chapter 1Overcurrent protection (50, 51, 67)
“VTFailProtOff”=0
Overcurrent Stage1
&
Phase A Startup T1 &
&
Binary Blocking Overcurrent Stage1 Protection Trip
Overcurrent Stage 1
3 Phase Inrush Blocking
“OCStage1On”=1
T1:“OCSatge1Time”
80
Chapter 9 Chapter 1Overcurrent protection (50, 51, 67)
Default
Number Setting name Range Unit Remark
value
19. HVSideInvTimeOC3IndexP 0.01~10.00 10
20. HVSideInvTimeOCStage3TimeB 0.000~100.00 100 s
21. HVSideInvTimeOCStage3ConstT 0.025~1.5 0.025
22. HVSidePPVoltBlkOCSet 1.00~120.0 30 V
23. HVSideOCU2BlkOCSet 0.05~100.0 3 V
24. HVSideDirOCSensitiveAngle 0.00~90.00 30 degree
Overcurrent harmonic crossing
25. 0.000~100.00 100 s
blocking time of high voltage side
26. HVSideOCRstTime 0.01~100 0.04 s
27. HVInvTimeOCMinTripTime 0.10~100 0.1 s
28. HVSideOCSatge1Time2 0.10~100 100 s
29. HVSideOCSatge1Time3 0.10~100 100 s
30. HVSideOCSatge2Time2 0.10~100 100 s
31. HVSideOCSatge2Time3 0.10~100 100 s
32. HVSideOCSatge3Time2 0.10~100 100 s
33. HVSideOCSatge3Time3 0.10~100 100 s
Note: Overcurrent rotection setting of each middle and low voltage side is
the same to that of high voltage side
Table 39 Comman setting
Number Setting name Range Default Unit Remark
value
1. HVSideHarmUnblkPhCurr 0.05In~40 In 40 A
2. HVSideOC2ndHI2/I1Ratio 0.07~0.50 0.07
3. MVSideHarmUnblkPhCurr 0.05In~40 In 40 A
4. MVSideOC2ndHI2/I1Ratio 0.07~0.50 0.07
5. LVSideHarmUnblkPhCurr 0.05In~40 In 40 A
6. LVSideOC2ndHI2/I1Ratio 0.07~0.50 0.07
Table 40 Overcurrent protection logic switch of high voltage side
Set Default
Number Logic switch name Remark
mode value
1-Enable overcurrent stage
1 time 1 of high voltage
1. HVSideOCSatge1Time1On 1/0 0 side; 0-Disable overcurrent
stage 1 time 1 of high
voltage side.
1-overcurrent stage 1
2. HVSideDirOCStage1 1/0 0 Direction on, 0-Overcurrent
stage 1 Direction off
1-overcurrent stage 1
forward direction of high
3. HVSideOCStage1Fwd 1/0 0 voltage side, 0-overcurrent
stage 1 reverse direction of
high voltage side
1-overcurrent stage 1
voltage on of high voltage
4. HVSideOCStage1BlkByVolt 1/0 0 side, 0-Overcurrent stage 1
voltage off of high voltage
side
1-overcurrent stage 1 of
high voltage side secondary
5. HVSideOCStage1BlkBy2ndH 1/0 0
harmonic on, 0-Overcurrent
stage 1 of high voltage side
81
Chapter 9 Chapter 1Overcurrent protection (50, 51, 67)
Set Default
Number Logic switch name Remark
mode value
secondary harmonic off
1-Enable overcurrent stage
2 time 1 of high voltage
6. HVSideOCSatge2Time1On 1/0 0 side; 0-Disable overcurrent
time 2 time 1 of high voltage
side.
1-overcurrent stage 1
7. HVSideDirOCStage2 1/0 0 Direction on, 0-Overcurrent
stage 1 Direction off
1-overcurrent stage 1
forward direction of high
8. HVSideOCStage2Fwd 1/0 0 voltage side, 0-overcurrent
stage 1 reverse direction of
high voltage side
1-overcurrent stage 1
voltage on of high voltage
9. HVSideOCStage2BlkByVolt 1/0 0 side, 0-Overcurrent stage 1
voltage off of high voltage
side
1-overcurrent stage 1 of
high voltage side secondary
10. HVSideOCStage2BlkBy2ndH 1/0 0 harmonic on, 0-Overcurrent
stage 1 of high voltage side
secondary harmonic off
1-Enable overcurrent stage
3 time 1 of high voltage
11. HVSideOCSatge3Time1On 1/0 0 side; 0-Disable overcurrent
time 3 time 1 of high voltage
side.
1-overcurrent stage 3
12. HVSideDirOCStage3 1/0 0 Direction on, 0-Overcurrent
stage 3 Direction off
1-overcurrent stage 3
forward direction of high
13. HVSideOCStage3Fwd 1/0 0 voltage side, 0-overcurrent
stage 3 reverse direction of
high voltage side
1-overcurrent stage 3
voltage on of high voltage
14. HVSideOCStage3BlkByVolt 1/0 0 side, 0-Overcurrent stage 3
voltage off of high voltage
side
1-overcurrent stage 3 of
high voltage side secondary
15. HVSideOCStage3BlkBy2ndH 1/0 0 harmonic on, 0-Overcurrent
stage 3 of high voltage side
secondary harmonic off
HVSideOCSatge1Time2On 1/0 0 1-Enable overcurrent
stage 1 time 2 of high
16. voltage side; 0-Disable
overcurrent time 1 time 2
of high voltage side.
HVSideOCSatge1Time3On 1/0 0 1-Enable overcurrent
17. stage 1 time 3 of high
voltage side; 0-Disable
82
Chapter 9 Chapter 1Overcurrent protection (50, 51, 67)
Set Default
Number Logic switch name Remark
mode value
overcurrent time 1 time 3
of high voltage side.
HVSideOCSatge2Time2On 1/0 0 1-Enable overcurrent
stage 2 time 2 of high
18. voltage side; 0-Disable
overcurrent time 2 time 2
of high voltage side.
HVSideOCSatge2Time3On 1/0 0 1-Enable overcurrent
stage 2 time 3 of high
19. voltage side; 0-Disable
overcurrent time 2 time 3
of high voltage side.
HVSideOCSatge3Time2On 1/0 0 1-Enable overcurrent
stage 3 time 2 of high
20. voltage side; 0-Disable
overcurrent time 3 time 2
of high voltage side.
HVSideOCSatge3Time3On 1/0 0 1-Enab le overcurrent
stage 3 time 3 of high
21. voltage side; 0-Disable
overcurrent time 3 time 3
of high voltage side.
Note: Overcurrent protection logic switch of middle and low voltage side
are the same to that of high voltage side
Table 41 Common logic switch
Note: the report of each low voltage side is the same to that of low
voltageside
83
Chapter 9 Chapter 1Overcurrent protection (50, 51, 67)
84
Chapter 10Chapter 1 Earth fault protection (50N, 51
N, 67N)
85
Chapter 10Chapter 1 Earth fault protection (50N, 51N,
67N)
1 Overview
Under the condition of high resistance grounding fault in the neutral point
grounding system, the calculated impedance located out of the distance
impedance zone and the IED maloperate. Therefore, other protection trips
are needed to isolate the fault, earth fault protection can reliably identify
high resistance grounding fault. For example, in the double circuit lines,
the directional earth fault protection simultaneously distinguishes the size
and direction of fault current and cooperates with other protection devices
in the system.
The characteristics of earth fault protection are listed as follow:
1) There are 3 stagesthree stages of definite time on each high, medium
and low voltage side of which the definite stage or inverse time can be
selected.(including all inverse time characteristics that stipulated by
IEC/ANSI standard );
2) Direction characteristics of each stage is independent (selectable);
3) Negative sequence directional component(selectable);
4) The inrush blocking feature of each stage is independent ;
5) Inrush locking is distinguished by secondary harmonic currents;
6) The maximum current of open magnetizing inrush blocking can be
adjusted;
7) Earth fault protection of VT breaking blocking direction.
Figure 49 The input and output signals diagram of earth fault protection function
Table 44 Parameter description
Function Identifier Description
Output:
86
Chapter 10Chapter 1 Earth fault protection (50N, 51
N, 67N)
3 Detailed description
IED is equipped with 3 stages earth fault protection on each high, medium
and low voltage side, please refer to the setting list for details. The
overcurrent protection stage 1 will be taken as an example below and the
principle will be introduced.
3I02/3I0>“3I02ndHI02/I01”
“Extr3I0Stage1”=0 & ≥1
High 2nd Harmonic Current
“3I0HarmonChkExtrI02/I01”=1
&
Imax>“HarmUnblkPhCurr”
Ia2/Ia1>“OC2ndHI2/I1Ratio”
≥1
Ib2/Ib1>“OC2ndHI2/I1Ratio”
Ic2/Ic1>“OC2ndHI2/I1Ratio”
Figure 50 Logic diagram of the secondary harmonic blocking of earth fault protection
87
Chapter 10Chapter 1 Earth fault protection (50N, 51N,
67N)
3.1.2 Directional component
1) Zero sequence directional component
In order to meet the different operating conditions of power system, the
reference voltage can be clockwise rotate 0 to 90°according to the
"3I0DirectSensitiveAngle", this setting influences direction characteristics
of each stage. The reference voltage vector after rotation is closer to the
-3I0 of lag 3U0 angle Φd, which makes the direction distinguishing more
sensitive. Rotate reference voltage vector to define the forward direction
and reverse direction action zone. The direction range of the positive
direction is rotating voltage reference vector for the vertical bisector
between -80 degrees and +80 degrees. If the -3I0 vector is in this zone,
the device is considered to be in the forward direction.
An example is given to illustrate the direction discrimination of A phase
faults. In the figure, 3I0 exceeds 3U0, so the -3I0 lags 3U0, the reference
voltage 3U0 vector rotates "3I0DirectSensitiveAngle", in order to be closer
to the -3I0 vector. In addition, the yellow area in the diagram is a positive
direction.
3I 0 90° 90°
3I 0
Reverse
10°
10°
0° 0°
3 U 0_Ref 3U 0_Ref
Φ0 Φ0
-3 I 0 -3 I 0
88
Chapter 10Chapter 1 Earth fault protection (50N, 51
N, 67N)
Negative sequence directional characteristics diagram:
3I 2 90° 3I 2 90°
Reverse
10°
10°
0° 0°
3 U 2-Ref 3U 2-Ref
Φ2 Φ2
-3 I 2 -3 I 2
“VTFailProtOff”=0
Zero Sequence
& ≥1
Forward Zone Forward Direction
Calculated Zero
Voltage>1V
&
“ZeroSeqChkU2/I2DirOn”=1
Negative Sequence
Forward Zone
Zero Sequence Forward Zone:Calculate as 90° connection,zero sequence current is within the direction zone.
Negative Sequence Forward Zone:Calculate as 90° connection,negative current is within the direction zone.
89
Chapter 10Chapter 1 Earth fault protection (50N, 51N,
67N)
coefficient, timing component returns, earth fault protection resets.
3.1.4 Inverse time
When "3I0Stage1Curve"=1~13, zero sequence current is the definite time
characteristic, definite stage function is disabled.
A
=t P
+ B ⋅T
3I 0 − 1
3I 0set
Where:
A: "InvTime3I0Stage1CoefA"
P: "InvTime3I0Stage1IndexP"
B: "InvTime3I0Stage1TimeB"
T: "InvTime3I0Stage1ConstT"
3I 0 : Zero sequence current setting value
3I 0set "3I0Stage1CurrSet"
If the current exceeds "3I0Stage1CurrSet", the timing element starts,
inverse time characteristic curve is selected by "3I0Stage1Curve", A, P, B
are determined when the value is from 1 to 12, see the following Table;
when the value is 13, it is user defined characteristics, calculate the trip
delay according to the setting of the A, P, B, T. While timing, earth fault
protection trips. When the calculated delay is less than the minimum trip
delay time "3I0InvTimeMinTripTime", the component trips according to the
"3I0InvTimeMinTripTime".
Table 45 Curve definition
90
Chapter 10Chapter 1 Earth fault protection (50N, 51
N, 67N)
3.1.5 Trip characteristic
When earth fault protection function is enabled and no BI blocking, if the
"3I0Stage1On"=1 , the earth fault protection of the corresponding stage is
enabled.
If the action conditions are met, time component starts; take stage 1
protection for example, when time is over, "3I0Stage1Trip" is issued. LED
and protection trip can be configured by AESP. When IED trips each phase
trip states will be displayed.
When "3I0Stage1BlkBy2ndH"=1, the harmonic locking component is put
into operation, when the action timer is time out, the inrush current is
checked, and if the current is not blocked, unblock overcurrent trip,
otherwise it will output “InrushBlk” report.
When "Dir3I0Stage1"=1, protection is with the directional element, and
choose the positive or negative direction characteristic according to
"3I0Stage1FwdDir", when the directional element is not satisfied, earth
fault protection is blocked.
Element trip triggers action or alarm, meanwhile output analog quantity of
action time, when the element is based on the self-produce zero sequence
current judgment, self-produce zero sequence current is output; when it is
based on the external zero sequence current, external zero sequence
current is output.
&
VT Failure Blocking
“VTFailProtOff”=1
3I0>“3I0Stage1CurrSet”
&
T1
Binary Blocking
&
Zero Sequence Current Stage 1
Protection Trip
&
Forward Direction ≥1
“3I0Stage1FwdDir”=1
“Dir3I0Stage1”=1
&
2nd harmonic current is high
“3I0Stage1BlkBy2ndH”=1
“3I0Stage1On”=1
T1:“3I0Satge1Time”
91
Chapter 10Chapter 1 Earth fault protection (50N, 51N,
67N)
3.2 Setting list
Table 46 Zero sequence current setting on high voltage side
Default
Number Setting name Range Unit Remark
value
0: definite time
1? IEC INV.
2: IEC VERY
INV.
3: IEC
EXTERMELY
INV.
4: IEC SHORT
TIME INV.
5: IEC LONG
TIME INV.
6: ANSI INV.
7: ANSI
SHORT INV.
1. HVSide3I0Stage1Curve 0~13 0
8: ANSI LONG
INV.
9: ANSI
MODERATELY
INV.
10: ANSI
VERY INV.
11: ANSI
EXTERMELY
INV.
12: ANSI
DEFINITE INV.
13: User
defined
2. HVSide3I0Stage3CurrSet 0.05~200 40 A
3. HVSide3I0Satge1Time1 0.00~100.00 100 s
4. InvTime3I0Stage1CoefA 0.001~1000 10
5. InvTime3I0Stage1IndexP 0.01~10.00 10
6. InvTime3I0Stage1TimeB 0.000~100.00 100
7. InvTime3I0Stage1ConstT 0.025~1.5 0.025
0: definite time
1? IEC INV.
2: IEC VERY
INV.
3: IEC
EXTERMELY
INV.
4: IEC SHORT
TIME INV.
8. HVSide3I0Stage2Curve 0~13 0
5: IEC LONG
TIME INV.
6: ANSI INV.
7: ANSI
SHORT INV.
8: ANSI LONG
INV.
9: ANSI
MODERATELY
92
Chapter 10Chapter 1 Earth fault protection (50N, 51
N, 67N)
Default
Number Setting name Range Unit Remark
value
INV.
10: ANSI
VERY INV.
11: ANSI
EXTERMELY
INV.
12: ANSI
DEFINITE INV.
13: User
defined
9. HVSide3I0Stage2CurrSet 0.05~200 40 A
10. HVSide3I0Satge2Time1 0.00~100.00 100 s
11. InvTime3I0Stage2CoefA 0.001~1000 10
12. InvTime3I0Stage2IndexP 0.01~10.00 10
13. InvTime3I0Stage2TimeB 0.000~100.00 100
14. InvTime3I0Stage2ConstT 0.025~1.5 0.025
0: definite time
1: IEC INV.
2: IEC VERY
INV.
3: IEC
EXTERMELY
INV.
4: IEC SHORT
TIME INV.
5: IEC LONG
TIME INV.
6: ANSI INV.
7: ANSI
SHORT INV.
15. HVSide3I0Stage3Curve 0~13 0
8: ANSI LONG
INV.
9: ANSI
MODERATELY
INV.
10: ANSI
VERY INV.
11: ANSI
EXTERMELY
INV.
12: ANSI
DEFINITE INV.
13: User
defined
16. HVS3I0Stage3CurrSet 0.05~200 40 A
17. HVSideI3I0Stage3Time1 0.00~100.00 100 s
18. InvTime3I0Stage3CoefA 0.001~1000 10
19. InvTime3I0Stage3IndexP 0.01~10.00 10
20. InvTime3I0Stage3TimeB 0.000~100.00 100
21. InvTime3I0Stage3ConstT 0.025~1.5 0.025
22. HVSideDir3I0SensitiveAngle 0.00~90.00 30 degree
93
Chapter 10Chapter 1 Earth fault protection (50N, 51N,
67N)
Default
Number Setting name Range Unit Remark
value
23. HVSide3I0NSDSensitiveAngle 0.00~90.00 30 degree
24. HVSide3I0RstTime 0.10~100 0.1 s
25. HVInvTime3I0MinTripTime 0.00~100 0.04 s
26. HVSide3I0Satge1Time2 0.10~100 100 s
27. HVSide3I0Satge1Time3 0.10~100 100 s
28. HVSide3I0Satge2Time2 0.10~100 100 s
29. HVSide3I0Satge2Time3 0.10~100 100 s
30. HVSide3I0Satge3Time2 0.10~100 100 s
31. HVSide3I0Satge3Time3 0.10~100 100 s
Note: Earth fault protection setting of each middle and low voltage side are
the same to that of high voltage side
Table 47 Common setting
Default
Number Setting name Range Unit Remark
value
1. HVSideHarmUnblkPhCurr 0.05In~40 In 40 A
2. HVSideOC2ndHI2/I1Ratio 0.07~0.50 0.07
3. MVSideHarmUnblkPhCurr 0.05In~40 In 40 A
4. MVSideOC2ndHI2/I1Ratio 0.07~0.50 0.07
5. LVSideHarmUnblkPhCurr 0.05In~40 In 40 A
6. LVSideOC2ndHI2/I1Ratio 0.07~0.50 0.07
7. HVSide3I0HarmUnblkCurr 0.05In~40 In 40 A
8. HVSide3I02ndHI02/I01 0.07~0.50 0.07
9. MVSide3I0HarmUnblkCurr 0.05In~40 In 40 A
10. MVSide3I02ndHI02/I01 0.07~0.50 0.07
11. LVSide3I0HarmUnblkCurr 0.05In~40 In 40 A
12. LVSide3I02ndHI02/I01 0.07~0.50 0.07
Table 48 Earth fault protection of high voltage side logic switch
Set Default
Number Logic switch name Remark
mode value
1-Enable zero sequence
covercurrent stage 1 time 1
of high voltage side;
1. HVSide3I0Stage1Time1On 1/0 0
0-Disable zero sequence
current time 1 time 1 of high
voltage side.
1-3I0 external connection;
2. HVSide3I0Stage1Extr 1/0 0
0-3I0 calculated
1-zero sequence current
stage 1 of high voltage side
direction on, 0-zero
3. HVSideDir3I0Stage1 1/0 0
sequence current stage 1of
high voltage side direction
off
1-Zero sequence current
stage 1 of high voltage side
forward direction; 0-zero
4. HVSide3I0Stage1FowardDir 1/0 0
sequence current stage 1
of high voltage side reverse
direction
94
Chapter 10Chapter 1 Earth fault protection (50N, 51
N, 67N)
Set Default
Number Logic switch name Remark
mode value
1-High zero sequence
current stage 1 secondary
harmonic blocking on, 0-
5. HVSide3I0Stage1BlkBy2ndH 1/0 0
high zero sequence current
stage 1 secondary
harmonic blocking off
1-Enable zero sequence
covercurrent stage 2 time 1
of high voltage side;
6. HVSide3I0Stage2Time1On 1/0 0
0-Disable zero sequence
current time 1 time 1 of high
voltage side.
1-3I0 external connection;
7. HVSide3I0Stage2Extr 1/0 0
0-3I0 calculated
1-zero sequence current
stage 2 of high voltage side
direction on, 0-zero
8. HVSideDir3I0Satge 1/0 0
sequence current stage 1of
high voltage side direction
off
1-Zero sequence current
stage 2 of high voltage side
forward direction; 0-zero
9. HVSide3I0Stage2FowardDir 1/0 0
sequence current stage 1
of high voltage side reverse
direction
1-High zero sequence
current stage 2 secondary
harmonic blocking on, 0-
10. HVSide3I0Stage2BlkBy2ndH 1/0 0
high zero sequence current
stage 2 secondary
harmonic blocking off
1-Enable zero sequence
covercurrent stage 3 time 1
of high voltage side;
11. HVSide3I0Stage3Time1On 1/0 0
0-Disable zero sequence
current time 3 time 1 of high
voltage side.
1-3I0 external connection;
12. HVSide3I0Stage3Extr 1/0 0
0-3I0 calculated
1-zero sequence current
stage 3 of high voltage side
direction on, 0-zero
13. HVSideDir3I0Satge3 1/0 0
sequence current stage 3
of high voltage side
direction off
1-Zero sequence current
stage 3 of high voltage side
forward direction; 0-zero
14. HVSide3I0Stage2FowardDir 1/0 0
sequence current stage 1
of high voltage side reverse
direction
1-High zero sequence
current stage 3 secondary
harmonic blocking on, 0-
15. HVSide3I0Stage2BlkBy2ndH 1/0 0
high zero sequence current
stage 2 secondary
harmonic blocking off
95
Chapter 10Chapter 1 Earth fault protection (50N, 51N,
67N)
Set Default
Number Logic switch name Remark
mode value
1= check negative
sequence direction;
16. HVSideZeroSeqChkU2/I2DirOn 1/0 1
0= don't check negative
sequence direction
1-Zero sequence current
harmonics checking
external connection I02/I01;
17. HVSide3I0HarmonChkExtrI02/I01 1/0 0
0-Zero sequence current
harmonics checking phase
current I2/I1
HVSide3I0Satge1Time2On 1/0 0 1-Enable zero sequence
covercurrent stage 1
time 2 of high voltage
18. side; 0-Disable zero
sequence current time 1
time 2 of high voltage
side.
HVSide3I0Satge1Time3On 1/0 0 1-Enable zero sequence
covercurrent stage 1
time 3 of high voltage
19. side; 0-Disable zero
sequence current time 1
time 3 of high voltage
side.
HVSide3I0Satge2Time2On 1/0 0 1-Enable zero sequence
covercurrent stage 2
time 2 of high voltage
20. side; 0-Disable zero
sequence current time 2
time 2 of high voltage
side.
HVSide3I0Satge2Time3On 1/0 0 1-Enable zero sequence
covercurrent stage 2
time 3 of high voltage
21. side; 0-Disable zero
sequence current time 2
time 3 of high voltage
side.
HVSide3I0Satge3Time2On 1/0 0 1-Enable zero sequence
covercurrent stage 3
time 2 of high voltage
22. side; 0-Disable zero
sequence current time 3
time 2 of high voltage
side.
HVSide3I0Satge3Time3On 1/0 0 1-Enable zero sequence
covercurrent stage 3
time 3 of high voltage
23. side; 0-Disable zero
sequence current time 3
time 3 of high voltage
side.
Note: Earth fault protection logic switch of medium voltage side is the
96
Chapter 10Chapter 1 Earth fault protection (50N, 51
N, 67N)
same to that of high voltage side
Table 49 Low voltage side earth fault protection logic switch
Set Default
Number Logic switch name Remark
mode value
1: check negative
LVSide3I0ChkU2I2DirOn
sequence direction; 0:
1. 1/0 0
don't check negative
sequence direction
1-Zero sequence current
harmonics check external
connection I02/I01 of low
LVSide3I0HarmChkExtrI02/I01
voltage side;
2. 1/0 0
0-Zero sequence current
harmonics check Phase
current I2/I1 of low
voltage side
1-3U0 external
3. LVSideExtr3U0 1/0 0 connection; 0-3U0
calculated
1-Enable zero sequence
current stage 1 of low
4. LVSide3I0Satge1Time1On 1/0 0 voltage side; 0-Disable zero
sequence current stage 1 of
low voltage side
1-3U0 external connection;
5. LVSide3I0Stage1Extr 1/0 0
0-3U0 calculated
1-zero sequence current
stage 1 of low voltage side
6. LVSideDir3I0Stage1 1/0 0 direction on, 0-zero
sequence current stage 1 of
low voltage side direction off
1-Zero sequence current
stage 1 forward of low
voltage side;
7. LVSide3I0Stage1FwdDir 1/0 0
2-Zero sequence current
stage 1 reserve direction of
low voltage side
8. Extr3I0Stage2 1/0 0
1-Enable zero sequence
current stage 2 of low
9. LVSide3I0Satge2Time1On 1/0 0 voltage side; 0-Disable zero
sequence current stage 2 of
low voltage side
1-3U0 external connection;
10. LVSide3I0Stage2Extr 1/0 0
0-3U0 calculated
1-zero sequence current
stage 2 of low voltage side
11. LVSideDir3I0Stage2 1/0 0 direction on, 0-zero
sequence current stage 2 of
low voltage side direction off
1-Zero sequence current
stage 2 forward of low
voltage side;
12. LVSide3I0Stage2FwdDir 1/0 0
2-Zero sequence current
stage 2 reserve direction of
low voltage side
13. LVSide3I0Stage2BlkBy2ndH 1/0 0
97
Chapter 10Chapter 1 Earth fault protection (50N, 51N,
67N)
Set Default
Number Logic switch name Remark
mode value
1-Enable zero sequence
current stage 3 of low
14. LVSide3I0Satge3Time1On 1/0 0 voltage side; 0-Disable zero
sequence current stage 3 of
low voltage side
1-3U0 external connection;
15. LVSide3I0Stage3Extr 1/0 0
0-3U0 calculated
1-zero sequence current
stage 3 of low voltage side
16. LVSideDir3I0Stage3 1/0 0 direction on, 0-zero
sequence current stage 3 of
low voltage side direction off
1-Zero sequence current
stage 3 forward of low
voltage side;
17. LVSide3I0Stage3FwdDir 1/0 0
2-Zero sequence current
stage 3 reserve direction of
low voltage side
1-zero sequence current
stage 3 secondary harmonic
blocking on, 0-zero
18. LVSide3I0Stage3BlkBy2ndH 1/0 0
sequence current stage 2
secondary harmonic
blocking off
Table 50 Common logic switch
Set Default
Number Logic switch name Remark
mode value
1. VTFailProtOff 1/0 0 0-unblock; 1-lock.
Note: it is fixed with three phase voltage connection.
98
Chapter 10Chapter 1 Earth fault protection (50N, 51
N, 67N)
3.4 Technical data
Table 52 Earth fault protection technical data
Content Range and value Error
Definite time characteristics
Current 0.05In~40.00In ≤ ±2.5% setting or ±0.02In
≤ ±1% setting or +40 ms
Time delay 0.00s~100.00s, step 0.01s At 2 times of operating
current
Inverse time characteristic
Current 0.05In~40.00In ≤ ±2.5% setting or ±0.02In
IEC standard Normal inverse time IEC 60255-151
Very inverse time; ≤ ±5% setting or +40 ms
Extreme inverse time Under the condition 2< 3I 0 /
Long inverse time 3I 0set <20
ANSI Inverse time ANSI/IEEE C37.112,
Short inverse time ≤ ±5% setting or +40 ms
Long inverse time Under the condition 2< 3I 0 /
Medium inverse time
3I 0set <20
Very inverse time;
Extreme inverse time
Definite inverse time
User-defined
characteristic IEC 60255-151
curve ≤ ±5% setting or +40 ms
A
=t + B ⋅T Under the condition 2< 3I 0 /
IΦ P
− 1 3I 0set <20
Iset
Time coefficient of inverse 0.005~1000.0, step 0.001
time : A
Time delay of inverse time: B 0.000~100.00, step 0.01
Inverse time index: P 0.01~10.00, step 0.005
Inverse time constant: T 0.025~1.5, step 0.01
Minimum trip time 20ms
Return mode Instantaneous return
Directional component
Zero sequence direction
160° ≤ ±3°, when 3U0≥1V
element action angle range
Directional sensitive angle 0° to 90°, step 1°
Negative sequence direction
160° ≤ ±3°, when 3U2≥2V
element action angle range
Directional sensitive angle 0° to 90°, step 1°
99
Chapter 11 Negative sequence current protection (46)
101
Chapter 11 Negative sequence current protection (46)
1 Overview
Negative sequence current protection can detect the unbalance of power
system load. When the generator connect unbalanced load, negative
sequence current protection is particularly useful. Because the unbalanced
load will produce a reverse magnetic field in the three-phase induction
motor, resulting in overheating of the rotor end. Secondly, the negative
sequence current protection can also be used to detect the disconnection,
short circuit and polarity of current transformer. Besides, the negative
sequence current protection can also detect the single-phase or two-phase
faults in the system, and the fault statue when the fault current is less than
the load current.
The main characteristics of the negative sequence current protection: offer
3 stages on each high, medium and low voltage side, and definite time or
inverse time can be selected
Figure 55 The input and output signals diagram of negative sequence current
protection function
Table 53 Parameter description
Function Identifier Description
Output:
3 Detailed description
IED is equipped with 3 stages of negative sequence current protection on
each high, medium and low voltage side, please refer to the setting list for
details. The negative sequence current protection stage 1 will be taken as
an example below and the principle will be introduced.
102
Chapter 11 Negative sequence current protection (46)
I 2 set “3I2Stage1CurrSet”
Dropoff: Return coefficient
3.1.2 Inverse time
When "3I2Stage1Curve"=1~13, negative sequence current is the definite
time characteristic, inverse time function is disabled.
A
=t P
+ B ⋅T
I2 −1
I 2set
I 2 set :”3I2Stage1CurrSet”
Table 54 Curve definition
0. Definite time
103
Chapter 11 Negative sequence current protection (46)
Binary Blocking
T1:“3I2Stage1Time”
104
Chapter 11 Negative sequence current protection (46)
Default
Number Setting name Range Unit Remark
value
EXTERMELY
INV.
4: IEC SHORT
TIME INV.
5: IEC LONG
TIME INV.
6: ANSI INV.
7: ANSI
SHORT INV.
8: ANSI LONG
INV.
9: ANSI
MODERATELY
INV.
10: ANSI
VERY INV.
11: ANSI
EXTERMELY
INV.
12: ANSI
DEFINITE INV.
13: User
defined
2. HVSideI2Stage1CurrSet 0.05In~40 40 A
Negative
sequence
3. HVSideI2Stage1Time 0.00~100.00 100 s current stage 1
time 1 of high
voltage side
4. HVSideInvTimeI2Stage1CoefA 0.001~1000 10
5. HVSideInvTimeI2Stage1IndexP 0.01~10.00 10
105
Chapter 11 Negative sequence current protection (46)
Default
Number Setting name Range Unit Remark
value
11: ANSI
EXTERMELY
INV.
12: ANSI
DEFINITE INV.
13: User
defined
9. HVSideI2Stage2CurrSet 0.05In~40 In 40 A
Negative
sequence
10. HVSideI2Stage2Time 0.00~100.00 100 s current stage2
time 1 of high
voltage side
11. HVSideInvTimeI2Stage2CoefA 0.001~1000 10
106
Chapter 11 Negative sequence current protection (46)
Default
Number Setting name Range Unit Remark
value
19. HVSideInvTimeI2Stage3IndexP 0.01~10.00 10
Note: Negative sequence current protection setting of each middle and low
voltage side are the same to that of high voltage side
Table 56 Negative sequence current protection of high voltage side logic switch
Set Default
Number Logic switch name Remark
mode value
1. HVSideIStage1Time1On 1/0 0 1-On, 0-Off
2. HVSideIStage2Time1On 1/0 0 1-On, 0-Off
3. HVSideIStage3Time1On 1/0 0 1-On, 0-Off
4. HVSideIStage1Time2On 1/0 0 1-On, 0-Off
5. HVSideIStage1Time3On 1/0 0 1-On, 0-Off
6. HVSideIStage2Time2On 1/0 0 1-On, 0-Off
7. HVSideIStage2Time3On 1/0 0 1-On, 0-Off
8. HVSideIStage3Time2On 1/0 0 1-On, 0-Off
9. HVSideIStage3Time3On 1/0 0 1-On, 0-Off
Note: Earth fault protection logic switch of each middle and low voltage
side are the same to that of high voltage side
107
Chapter 11 Negative sequence current protection (46)
108
Chapter 12 Overvoltage protection (59)
109
Chapter 12 Overvoltage protection (59)
1 Overview
Overvoltage protection is used to prevent the impact of overvoltage on
electrical equipment. The abnormal overvoltage often occurs in low load,
long transmission line, generator voltage regulation fails in the islanded
system, or the load shedding of the generator in the system. Even if the
compensating capacitor can compensate line capacitance, lower the
overvoltage of the lines, when the compensating capacitor fails,
overvoltage will endanger the line insulation system, here the circuit must
be removed.
Overvoltage protection has the following characteristics:
1) Definite or inverse time can be selected on each 2 stages of
high/medium/low voltage side;
2) Set the alarm or trip in stage;
3) Measured voltage can be phase-to-earth voltage or phase-to-phase
voltage;
4) Dropoff coefficient is adjustable.
Overvoltage Protection
1
Start
2
Operation
3
PhaseA
4
PhaseB
5
PhaseC
Figure 57 The input and output signals of overvoltage protection function diagram
Table 59 Parameter description
Function Identifier Description
Output:
3 Detailed description
3.1 Protection principle
Overvoltage protection selects the phase voltage or line voltage through
110
Chapter 12 Overvoltage protection (59)
Where:
A: "InvTimeOVStage1CoefA"
P: "InvTimeOVStage1IndexP"
B: "InvTimeOVStage1TimeB"
T: "InvTimeOVStage1ConstT"
U Φ : Phase-to-earth/phase-to-phase voltage
U set "OVStage1VoltSet"
111
Chapter 12 Overvoltage protection (59)
112
Chapter 12 Overvoltage protection (59)
max(Ua,Ub,Uc)>“OVStage1VoltSet” &
“OVChk1Ph”=1 ≥1
min(Ua,Ub,Uc)>“OVStage1VoltSet” &
“OVChk1Ph”=0
&
“OVChkPEVolt”=1
max(Uab,Ubc,Uca)>“OVStage1VoltSet” &
“OVChk1Ph”=1 ≥1
min(Uab,Ubc,Uca)>“OVStage1VoltSet” &
“OVChk1Ph”=0 ≥1
& &
T1 Overvoltage Stage 1
Protection Trip
“OVChkPEVolt”=0
“OVStage1On”=1
T1:“OVStage1Time”
113
Chapter 12 Overvoltage protection (59)
Default
Number Setting name Range Unit Remark
value
Inverse time
4. HVSideInvTimeOVStage1CoefA 0.001~1000 10 s
characteristic
5. HVSideInvTimeOVStage1IndexP 0.01~10.00 10
114
Chapter 12 Overvoltage protection (59)
115
Chapter 12 Overvoltage protection (59)
116
Chapter 13 Zero sequence voltage protection(64)
117
Chapter 13 Zero sequence voltage protection (64)
1 Overview
Zero sequence voltage protection is generally used in the power network
with small grounding fault current.
The main features of zero sequence voltage protection are as follows:
1) It provides 1 stages of reverse time and reverse time selective
protection;
2) Fault phase selection function;
3) Zero sequence voltage 3U0 can be selected as self-produce zero
sequence voltage (the total of three phase measurement voltage), or
external zero sequence voltage (zero sequence residual voltage).
Figure 59 The input and output signals diagram of zero sequence voltage protection
function
Table 65 Parameter description
Function Identifier Description
Output:
3 Detailed description
3.1 Protection principle
Zero sequence voltage protection is used for ground fault check. Zero
sequence voltage protection can be set as alarm or trip, reverse and
reverse time are selective.
Compare the external or self-produce zero sequence voltage and the
corresponding setting value, if it is greater than the setting, trip timer starts.
Timer starts timed to the user defined time delay. The time delay setting
can be adjusted independently by settings. When time delay defined by
the users is over, the protection device sends out a trip command. The
zero sequence voltage protection stage 1 will be taken as an example
below and the principle will be introduced.
3.1.1 Definite time
When "3U0Stage1CurveSel" =1~0, zero sequence voltage is inverse time
118
Chapter 13 Zero sequence voltage protection(64)
characteristic.
3U0 > “3U0Stage1VoltSet”
If the zero sequence voltage exceeds the inverse time starting setting
"3U0Stage1VoltSet", the start signal is triggered and timing component
starts, time to "3U0Stage1Time", zero sequence voltage protection trips.
3.1.2 Inverse time
When "3U0Stage1CurveSel" =1~13, zero sequence voltage is the inverse
time characteristic.
A
=t P
+ B ⋅T
3U 0 − 1
3U 0set
Where:
A:”InvTime3U0Stage1CoefA”
P:”InvTime3U0Stage1IndexP”
B: "InvTime3U0Stage1TimeB"
T: "InvTime3U0Stage1ConstT"
3U 0 : 3U0
3U 0set : "3U0Stage1VoltSet"
0. Definite time
119
Chapter 13 Zero sequence voltage protection (64)
120
Chapter 13 Zero sequence voltage protection(64)
4. LVSideInvTime3U0Stage1CoefA 0.001~1000 10
5. InvTime3U0Stage1IndexP 0.01~10.00 10
Table 68 Low voltage side zero sequence voltage protection logic switch
Default
Number Logic switch name Range Remark
value
1. LVSide3U0Stage1On 1/0 0
121
Chapter 13 Zero sequence voltage protection (64)
122
Chapter 14 Negative sequence voltage protection (47)
123
Chapter 14 Negative sequence voltage protection (47)
1 Overview
In normal operating three-phase system, the negative sequence voltage is
almost 0, and the negative sequence voltage will occur when there is
asymmetrical situation in the system. Negative sequence voltage
protection is operated by checking negative sequence voltage.
The main features of negative sequence voltage protection are as follows:
High/medium voltage sides provide 2 stages of protection on each side
and definite or inverse time can be selected.
Figure 60 The input and output signals diagram of negative sequence voltage
protection function
Table 71 Parameter description
Function Identifier Description
Output:
3 Detailed description
3.1 Protection principle
The negative sequence voltage protection stage 1 will be taken as an
example below and the principle will be introduced.
3.1.1 Definite time
When "3U2Stage1Curve"=0, negative sequence voltage is the inverse
time characteristic, inverse time function is disabled.
The negative sequence voltage protection trip voltage is calculated by the
three-phase voltage as follow:
U̇ 2 = U̇ A + a2 U̇ B + aU̇ C
U2 > “3U2Stage1VoltSet”
If the voltage is exceeds "3U2Stage1VoltSet", timing component starts and
until timing to "3U2Stage1Time", negative sequence voltage protection
trips.
Where:
124
Chapter 14 Negative sequence voltage protection (47)
U 2 set : "3U2Stage1VoltSet"
0. Definite time
125
Chapter 14 Negative sequence voltage protection (47)
4. HVSideInvTimeU2Stage1CoefA 0.001~1000 10
126
Chapter 14 Negative sequence voltage protection (47)
Default
Number Setting name Range Unit Remark
value
5. HVSideInvTimeU2Stage1IndexP 0.01~10.00 10
127
Chapter 14 Negative sequence voltage protection (47)
128
Chapter 15 Undervoltage protection (27)
129
Chapter 15 Undervoltage protection (27)
1 Overview
Undervoltage protection can effectively protect the power equipment from
the impact of voltage drop.
The main features of undervoltage protection are as follows:
1) It provides 2 stages of protection, and definite and inverse time can be
selected.
2) Undervoltage protection voltage can be selected as phase-to-earth
voltage or phase-to-phase voltage.
3) Undervoltage blocking current check.
4) Detection of circuit breaker state
5) VT failure detection, VT failure blocking undervoltage protection.
6) Dropoff coefficient is adjustable.
Figure 61 The input and output signal diagram of undervoltage protection function
Table 77 Parameter description
Function Identifier Description
Output:
3 Detailed description
IED consists of four stages of undervoltage protection, phase-to-earth
voltage or phase-to-phase voltage, alarm or tirp and definite time or
inverse time are selectable, please refer to setting list for details. The
undervoltage protection stage 1 will be taken as an example below and the
principle will be introduced.
130
Chapter 15 Undervoltage protection (27)
With the limit of field condition, the voltage transformer of the circuit
breaker may be connected to the power supply side or the load side. The
installation position of VT is different, and the operation characteristics of
undervoltage protection are different. As the undervoltage protection starts
tripping and the breaker is off, the voltage beside power supply stays
unchangeable but the voltage beside load drops to zero, now undervoltage
protection resets. If the voltage transformer is installed on the power
supply side, and does not want to protect the undervoltage detection
current, the setting of "UVChkCurrOn" can be set to 0. In addition, the
undervoltage protection can also be controlled by the word
"UVChkCBState" to choose whether the action logic is to detect the circuit
breaker status. When the undervoltage protection is required to check the
circuit breaker state, the undervoltage protection sends out the trip
command only when the circuit breaker is closed. If the voltage
transformer is installed on the power supply side, and does not want the
undervoltage protection to check circuit breaker status, the logic switch
"UVChkCBState" is set to 0.
3.1.1 Blocking condition
When "UVChkCBState"=1, circuit breaker will be checked at blocking
protection during the trip, with non-blocking protection starting and
blocking protection delaying.
When the maximum value of the three-phase current is less than
"UVCurrSet", the blocking is protected, the non-blocking protection starts,
and the blocking is delayed.
As VT failure blocking is 1, the blocking is protected, the non-blocking
protection starts, and the blocking is delayed.
When "UVChkPEVolt"=1, and three-phase voltage is lower than
"3PhUVBlkSet", or when "UVChkPEVolt"=0 and three-phase voltage is
lower than the 1.732 times of "3PhUVBlkSet", the blocking is protected,
and the blocking protection starts.
3.1.2 Definite time
When "UVStage1CurveSel"=0, undervoltage is the definite time
characteristic, and inverse time function is disabled.
U < “UVStage1VoltSet”
When the voltage is lower than the setting "UVStage1VoltSet", ther timing
component will start and work until the setting "UVStage1Time", and
undervoltage protection trips. When
current U < Dropout × ”UVStage1VoltSet” , timing component drops out,
undervoltage protection drops out.
3.1.3 Inverse time
When "UVStage1CurveSel"=1~4, undervoltage is the definite time
characteristic, and inverse time function is disabled.
A
=t + B ⋅T
U P
1 −
Uset
131
Chapter 15 Undervoltage protection (27)
0. Definite time
1. Curve1 1 1 0
2. Curve2 40 2 1
3. Curve3 5 2 2
4. User defined
132
Chapter 15 Undervoltage protection (27)
Uc<“UVStage1VoltSet”
“UVChk1Ph”=1 ≥1
“UVChk1Ph”=0
Ua<“UVStage1VoltSet”
& &
&
Ub<“UVStage1VoltSet”
Uc<“UVStage1VoltSet”
≥1
“UVChkPEVolt”=1 Undervoltage Stage 1
Protection Startup
“UVChkPEVolt”=0
Uab<“UVStage1VoltSet”
≥1
Ubc<“UVStage1VoltSet” & &
Uca<“UVStage1VoltSet”
“UVChk1Ph”=1
≥1
“UVChk1Ph”=0
Uab<“UVStage1VoltSet”
&
&
Ubc<“UVStage1VoltSet”
Uca<“UVStage1VoltSet”
133
Chapter 15 Undervoltage protection (27)
“UVStage1On”=1
Binary Blocking
“UVChkCBState”=1 &
T1 Under Voltage Stage1
Protection Trip
“UVChkCBState”=0
max(Ia,Ib,Ic)>“UVCurrSet” &
≥1
≥1
“UVChkCurrOn”=1
“UVChkCurrOn”=0
VT Failure blocking
Ua<“3PhUVBlkSet”
Ub<“3PhUVBlkSet”
&
Uc<“3PhUVBlkSet”
“UVChkPEVolt”=1
≥1
“UVChkPEVolt”=0
Uab<“1.732×3PhUVBlkSet”
&
Ubc<“1.732×3PhUVBlkSet”
Uca<“1.732×3PhUVBlkSet”
T1:“UVStage1Time”
134
Chapter 15 Undervoltage protection (27)
Default
Number Setting name Range Unit Remark
value
11. HVSideInvTimeUVStage2A 0.001~1000 10
12. HVSideInvTimeUVStage2IndexP 0.01~10.00 10
13. HVSideInvTimeUVStage2TimeB 0.000~100.00 100 s
14. HVSideInvTimeUVStage2ConstT 0.025~1.5 0.025
15. HVSideUVChkCurrSet 0.0 5n ~ 40 In 10 A
16. HVSideUVMinVoltSet 0.000~40.00 2 V
17. HVSideUVDropoffCoef 1.00~2.00 1
18. HVSideUVRstTime 0.000~100.00 0.0 s
19. HVInvTimeUVMinTripTime 0.100~100.00 0.1 s
Note: Undervoltage common setting of medium voltage side is the same to
that of high voltage side
Table 80 Undervoltage protection logic switch of high voltage side
Set Default
Number Logic switch name Remark
mode value
1-low voltage stage 1 of high voltage
1. HVSideUVStage1On 1/0 0 side on, 0-low voltage stage 1 of high
voltage side off
1-low voltage stage 2 of high voltage
2. HVSideUVStage2On 1/0 0 side on, 0-low voltage stage 2 of high
voltage side off
1-Enable undervoltage check current
of high voltage side; 0-Disable
3. HVSideUVChkCurrOn 1/0 0
undervoltage check current of high
voltage side
1-undervoltage check CB state of high
4. HVSideUVoltChkCBState 1/0 0 voltage side on; 0-undervoltage check
CB state of high voltage side off
1-undervoltage check phase 1 voltage
of high voltage side; 0- undervoltage
5. HVsideUVChk1Ph 1/0 0
check phase 3 voltage of high voltage
side
1-undervoltage check phase-to-earth
voltage of high voltage side; 0-
6. HVSideChkPEVolt 1/0 0
undervoltage check phase-to-phase
voltage of high voltage side
Note 1: it is fixed with three phase voltage connection.
Note 2: Undervoltage protection logic switch of medium voltage side is the
same to that of high voltage side
135
Chapter 15 Undervoltage protection (27)
136
Chapter 16 Thermal overload protection (49)
137
Chapter 16 Thermal overload protection (49)
1 Overview
Thermal overload protection protects the device against overheating
caused by overload. Overheating can affect insulation characteristics of
insulation material between transformers, lines and other electrical
equipment. In fact, if the device temperature exceeds the allowable
operating temperature, the insulation material will accelerate aging.
Therefore, special protection should be provided to prevent the protected
equipment from excessive temperature. Since the temperature is
proportional to the square of the current, the thermal overload protection is
based on the square of the measured current flowing through the
protected device. In addition, due to the cumulative effect of over
temperature, the thermal overload protection needs to consider the
historical thermal effect of the device. The device realizes the above
functions by providing a thermal model of the simulated protected device.
In this way, the thermal overload protection of the device has the ability of
memory, which can consider the historical overload and heat loss.
Figure 63 The input and output signals of thermal overload protection function diagram
Table 83 Parameter description
Output:
3 Detailed description
The device provides 1 stage thermal overload trip stage and 2 stage
thermal overload alarm stage. The alarm stage needs to adjust the
"ThermalOLAlarmCoef", which means that the value of the alarm stage trip
setting is the product of the setting of the trip stage and the overload alarm
coefficient. The thermal overload protection function is realized by a
temperature model equivalent to the protected device. Temperature model
(low temperature curve or high temperature curve) is selected from
IEC60255-8 standard. Temperature model can be used to calculate the
138
Chapter 16 Thermal overload protection (49)
I − 1
I ϑ
Where, IP is the steady current before the overload, the formula is the heat
curve in the IEC60255-8 specification, and the trip time is calculated in
accordance with the cold curve, which is shown as follows:
I 2
I
τ = τ ln ϑ 2
I − 1
I ϑ
Thermal overload protection can reflect the current fundamental frequency
component or RMS value trip, which are divided into stage 1 trip and stage
2 alarm, whenI > “ThermalOLCurrSet”, over heat protection starts, take
stage 1 alarm for example, when the thermal overload percentage reaches
"ThermalOLAlarmCoef1", the report "ThermalOLAlarmCoef1" is sent out;
when the thermal load percentage reaches 100%, the report
"ThermalOLTrip" is sent out. Light, protection trip and others can be
configured by AESP after the alarm or trip report is issued.
While alarming or tripping, three-phase current value Ia, Ib, Ic of trip
moment and each phase of trip moment are sent out.
When overheating protection is enabled, three-phase thermal
accumulative percentage is sent out timely by ThermalA, ThermalB, and
ThermalC.
The stop load current is 0, and the time coefficient of the equipment in the
process of heat dissipation is the product of "ThermalOLCoolingCoef" and
"ThermalTimeConst".
139
Chapter 16 Thermal overload protection (49)
3. HVSideThermalOLCoolingCoef 0.1~10 10
4. HVSideThermalOLAlarmCoef1 0.5~1 1
5. HVSideThermalOLAlarmCoef2 0.5~1 1
Note: Thermal overload logic switch of medium voltage side is the same to
that of high voltage side
140
Chapter 16 Thermal overload protection (49)
141
Chapter 17 Circuit Breaker Failure protection (50BF)
143
Chapter 17 Circuit Breaker Failure protection (50BF)
1 Overview
CBF protection can detect whether CBF is operating or not during the fault
clearance. This protection can clear the fault by tripping the breaker of
corresponding busbars as fast backup protection. Once there is a breaker
failure on feeder or transformer, the connected busbar can be
disconnected from the power grid by CBF protection. In addition, the
device sends out a trip order to the protection of other end of the feeder. In
the event of a circuit breaker failure with a busbar fault, IED sends the trip
command to the opposite of the feeder.
In order to improve the reliability of circuit breaker failure protection, the
current criterion is added. Three phase current, zero sequence current and
negative sequence current can be selected.
In order to avoid the other around circuit breaker trip caused by the error of
judgment, circuit breaker failure protection can be set to issue a trip
command to the local circuit breaker once again.
CBF protection has the characteristics as below:
1) 2 trip stages (local breaker retrip and trip the busbar)
2) Transfer trip command to the remote line end in second stage
3) Internal/ external initiation
4) Three-phase initiating failure
5) Breaker auxiliary contact check
6) Current criteria checking (including phase current, zero and negative
sequence currents)
144
Chapter 17 Circuit Breaker Failure protection (50BF)
Input:
Output:
Circuit breaker failure startup
CBF CBF_Init
signal
Circuit breaker failure binary input
BIAlarm
is abnormal
Trip1 Circuit breaker failure stage I trip
3 Detailed description
3.1 Protection function
CBF protection can be enabled or disabled by setting the logic switch In
the case of the protection function is enabled, the protection function trips,
the relevant protection function start failure protection, and the timing of
the counter works until to setting time delay, and the time delay is set
to”CBFTime1". If the circuit breaker is still closed after the setting time,
circuit breaker failure protection will send trip command to trip the circuit
breaker (for example, through the secondary trip coil) If the breaker has no
response when the other time delay ”CBFTime2", then IED will send off trip
command to trip the corresponding breakers to isolate the fault (e.g. other
breakers on the same busbar connected with the failure circuit breaker).
After tripping, light, protection trip and others can be configured by AESP.
The internal and external protection function can both start circuit breaker
failure protection. If the external initiating function protection is failed, then
it needs to be equipped with "3PhaseCBFStartup".
CBF check includes two criteria. The first criterion is detecting the
disappeared current after issuing the trip command. The second criterion
is detecting the auxiliary contacts of breaker.
3.1.1 Current check
When the current is disappeared, the breaker is considered to be on the
open position. the first criterion (current criterion) is the most effective way
to detect the position of breaker. The current check, therefore, is used to
detect the breaker position in CBF protection. At this time, the current
145
Chapter 17 Circuit Breaker Failure protection (50BF)
Calculate3I0 >“CBF3I0Set” ≥1
&
≥1 &
3I2 > “CBFI2Set”
Ib >“CBFCurrSet”
Ic >“CBFCurrSet”
“CBFChk3I0/I2”=1
&
Ib >“CBFCurrSet”
Calculate3I0 >“CBF3I0Set” ≥1 ≥1
& CB Failure Current
≥1 & judged
3I2 > “CBFI2Set” by 3 Phase Current
Ia >“CBFCurrSet”
Ic >“CBFCurrSet”
“CBFChk3I0/I2”=1
&
Ic >“CBFCurrSet”
Calculate3I0 >“CBF3I0Set” ≥1
&
≥1 &
3I2 > “CBFI2Set”
Ia >“CBFCurrSet”
Ib >“CBFCurrSet”
“CBFChk3I0/I2”=1
146
Chapter 17 Circuit Breaker Failure protection (50BF)
≥1
3 Phase Startup Failure
Internal Startup Failure Signal
T_alarm:“CBFBIAlarmTime”
“CBFailureCheck
CBPosition” &
CB closed
≥1
T1:“CircuitBreakerFailureTime1”
&
0
CBFail input
T2:“CircuitBreakerFailureTime2”
2. HVSideCBF3I0Set 0.05In~40 In 40 A
3. HVSideCBFI2Set 0.05In~40 In 40 A
147
Chapter 17 Circuit Breaker Failure protection (50BF)
Note: Circuit breaker failure protection logic switch of middle and low
voltage side are the same to that of high voltage side
3.4 Parameters
Table 92 CBF protection technical data
Items Setting range Trip value error
Current setting 0.05 In ~ 40.00 In ≤ ±2.5% setting or ±0.02In
Negative sequence current
setting
Zero sequence current
setting
Time 1 of circuit breaker 0.00s~100.00 s, step 0.01s ≤ ± 1% times of setting or +40
failure ms, when trip current is set
Time 2 of circuit breaker 0.00s~100.00 s, step 0.01s as 200% setting
failure
DropoffCoef About 0.95
Reset time Less than20 ms
148
Chapter 18 Dead zone protection (50DZ)
149
Chapter 18 Dead zone protection (50DZ)
1 Overview
IED provides dead zone protection to detect dead zone fault, i.e. when
breaker is in open position, a fault occurs between CT and breaker. So,
when breaker auxiliary contact shows that the breaker is in open position,
IED can detect fault current of dead zone.
For busbar side CT, when dead zone fault occurs, IED trips all breakers on
the busbar where the fault bay is located. Trip logic is shown as below:
TrIp
Busbar
IFAULT
Example:
CB open position
CB close position
Interal trip
Busbar
IFAULT
Line
Line 2 Line N
1
Trip
装置
Example:
CB open position
CB close position
150
Chapter 18 Dead zone protection (50DZ)
Figure 73 The input and output signals of dead zone protection function diagram
Table 93 Parameter description
Input:
Output:
CBF
Start IED startup
3 Detailed description
3.1 Protection principle
When dead zone protection function is enabled (En=1) and binary input
blocking is disabled, if "DZProtOn"=1, then the corresponding dead zone
protection is enabled.
The trip conditions are shown below:
1) Trip initiates dead zone flag SigIntDZ =1, or external IB initiates dead
zone 'BI_IntDZ =1' and no abnormal alarm of external BI;
2) There should be open position but no close position;
3) I∅ > “DZCurrSet”, (∅ = a, b, c);
4) Enabled or disabled the criterion of zero current and negative sequence current
by setting the logic switch " DZChk3I0/3I2 ". If the logic switch is set as 1, the
zero or negative sequence current is also necessary to be larger than the
corresponding setting.
If the trip conditions are met, time component starts, when time is over,
"DZTrip" is issued. LED and protection trip can be configured by AESP. At
the same time, the three-phase fundamental current values Ia, Ib, Ic, zero
151
Chapter 18 Dead zone protection (50DZ)
and negative sequence current of trip time are displayed. When current or
breaker position is not satisfied, timing component returns, dead zone
protection resets. When the existing time of external BI initiating dead zone
is longer than the alarm time, "DZ BIErrAlarm”will be issued. LED and
protection trip can be configured by AESP.
&
“DZChk3I0/I2”=0
Ia>“DZCurrSet”
Ib>“DZCurrSet”
& ≥1
≥1 &
Ic>“DZCurrSet”
3I0>“DZ3I0Set”
3I2>“DZI2Set”
“DZChk3I0/I2”=1
“DZChk3I0/I2”=0
&
Ib>“DZCurrSet”
Ic>“DZCurrSet”
& ≥1 ≥1
≥1 & Dead zone current
Ia>“DZCurrSet” condition satisfied
3I0>“DZ3I0Set”
3I2>“DZI2Set”
“DZChk3I0/I2”=1
“DZChk3I0/I2”=0 &
Ic>“DZCurrSet”
Ib>“DZCurrSet”
& ≥1
≥1 &
Ia>“DZCurrSet”
3I0>“DZ3I0Set”
3I2>“DZI2Set”
“DZChk3I0/I2”=1
BI blocking
≥1
Protection trip initiate dead zone
&
“DZProtOn”=1
T:“DZTripTime”
T_BIErr:“BIErrTime”
152
Chapter 18 Dead zone protection (50DZ)
3. LVSideDZProt3I0Set 0.05In~40 In 40 A
4. LVSideDZProtI2Set 0.05In~40 In 40 A
Note: dead zone protection setting of low voltage side 1 is the same to that of low
voltage side
Table 95 Dead zone logic switch
Default
Number Logic switch name Set mode Remark
value
1. LVSideSideDZOn 1/0 0
2. LVSideDZChk3I0/I2 1/0 0
Note: dead zone protection logic switch of low voltage side 1 is the same to that of low
voltage side
153
Chapter 19 Stub protection (50STUB)
155
Chapter 19 Stub protection (50STUB)
1 Overview
The stub protection protects the zone between the CTs and the
dis-connectors. The stub protection is enabled when the open position of
the dis-connector is informed to the IED through connected binary input.
The function has 2 stages of definite time at high voltage and medium
voltage side seperately.
Figure 75 The input and output signals of stub protection function diagram
Table 98 Parameter description
Input:
BIConfig STUB_Enab
Isolation position signal input
le
Output:
3 Detailed description
3.1 Protection principle
The stub protection is an overcurrent protection which is only in service if
the status of the line disconnector indicates the open condition. Stub
protection is disabled while the disconnector is at the close position. The
stub protection stage provides one definite time stage with settable delay
time. This protection function can be enabled or disabled via the logic
switch. Corresponding current setting value can be inserted in setting.
When the current is greater than the setting value and the time delay is
over, the IED sends out "StubTrip". LED and protection trip can be
156
Chapter 19 Stub protection (50STUB)
configured by AESP.
Ia>“StubCurrSet”
≥1
Ib>“StubCurrSet”
Ic>“StubCurrSet”
&
Isolator in the open position T
Stub protection trip
BI blocking
“StubOn”=1
T:“StubTime”
CB1
STUB-Bus
CT1 Overcurrent fault
Line1
Switch1
CB3
CT3
Line2
Switch2
CT2
CB2
Bus line B
5. HVSideStubRstTime 0~100 40 s
157
Chapter 19 Stub protection (50STUB)
Note: Stub protection setting of medium voltage side is the same to that of
high voltage side
Table 100 Stub protection logic switch of high voltage side
Set Default
Number Logic switch name Remark
mode value
1. HVSideStubStage1On 0/1 0 0: Off; 1: On;
Note: Stub protection logic switch of medium voltage side is the same to
that of high voltage side
158
Chapter 20 Pole discrepance protection (62PD)
159
Chapter 20 Pole discrepance protection (62PD)
1 Overview
Under normal operating condition, all three poles of the circuit breaker
must be closed or open at the same time. The split phase operating circuit
breakers can be in different positions (close-open) due to electrical or
mechanical failures. This can cause negative and zero sequence currents
which gives thermal stress on rotating machines and can cause unwanted
operation of zero sequence or negative sequence current functions.
Single pole opening of the circuit breaker is permitted only in the short
period related to single pole dead times, otherwise the breaker is tripped
three pole to resolve the problem. If the problem still remains, the remote
end can be intertripped via circuit breaker failure protection function to
clear the unsymmetrical load situation.
The pole discrepance function operates based on information from
auxiliary contacts of the circuit breaker for the three phases with additional
criteria from unsymmetrical phase current.
Pole-Discrepancy Protection
1 1
CBOpenA Start
2 2
CBOpenB Operation
3
CBOpenC
Figure 78 Pole discrepancy protection function input and output signals diagram
Table 103 Parameter description
Input:
Output:
3 Detailed description
3.1 Protection principle
The CB position signals are connected to IED via binary input in order to
monitor the CB status. Poles discordance condition is established when
logic switch of three-pole discrepance is enabled, and at least one pole is
160
Chapter 20 Pole discrepance protection (62PD)
open and at the same time not all three poles are closed. The auxiliary
contact of the circuit breaker is inspected by the corresponding phase
current. When the auxiliary contact signal of the breaker is indicated as a
division, the current is in phase, and after the 5S, the device alarm is made
of "PDProtTripPosnErr". LED and protection trip can be configured by
AESP.
In addition, criterion for zero sequence current and negative sequence
current can be enabled or disabled through logic switch under this function.
Pole discrepance can be detected when current is not flowing through all
three poles. When current is flowing through all three poles, all three poles
must be closed even if the breaker auxiliary contacts indicate a different
status.
Ia > 0.06In
Ib > 0.06In
Ic > 0.06In
&
5s
“PDProtOn” 3 phase PD trip abnormal
Circuit breaker trip positionA
&
Circuit breaker trip positionB
&
Ia < 0.06In T_PD 3 phase PD
protection trip
Ib < 0.06In
Ic < 0.06In
&
≥1
“PDChk3I0/3I2”=1
“PDProtOn”=1
3I2Set:“PD3I2Set”
3I0Set:“PD3I0Set”
T_PD:“PDTripTime”
161
Chapter 20 Pole discrepance protection (62PD)
2. LVSidePDI2Set 0.05In~40In 40 A
3. LVSidePDTripTime 0~60 10 s
Note: dead zone protection three-phase unbalanced setting of low voltage side 1 is the
same to that of low voltage side
Table 105 Three-phase unbalanced protection logic switch of low voltage side
Set Default
Number Logic switch name Remark
mode value
1. LVSidePDOn 0/1 0 1-On, 0-Off
Note: dead zone protection three-phase unbalanced logic switch of low voltage side 1 is
the same to that of low voltage side
162
Chapter 21 Overexcitation protection(24)
163
Chapter 21 Overexcitation protection(24)
1 Overview
The overexcitation protection is used to detect impermissible
overexcitation conditions which can endanger power transformers. The
saturation of the iron core and large eddy current losses led by the
situation that the transformer flux exceeds the related values can cause
impermissible temperature rise in transformer core.
This protection function has the following characteristics:
1) The alarm or trip of the three stages of definite time can be selected
respectively, the alarm or trip of one stage of inverse time can be
selected respectively.
2) Phase voltage and line voltage is available.
Figure 80 The input and output signals of overexcitation protection function diagram
Table 108 Parameter description
Output:
3 Detailed description
3.1 Protection principle
Overexcitation will occur when the load uncouples from system and
voltage regulator can't control the increase of voltage promptly. Similarly,
the overexcitation condition may occur as result of a decrease in frequency,
164
Chapter 21 Overexcitation protection(24)
165
Chapter 21 Overexcitation protection(24)
u/f
V/F(T14)
V/F( T13)
V/F( T12)
V/F( T11)
V/F( T10)
V/F( T9)
V/F( T8)
V/F( T7)
V/F( T6)
V/F( T5)
V/F( T4)
V/F( T3)
V/F( T2)
V/F(T1)
166
Chapter 21 Overexcitation protection(24)
167
Chapter 21 Overexcitation protection(24)
168
Chapter 22 Underfrequency protection (81UF)
Chapter 22 Underfrequency
Protection (81UF)
169
Chapter 22 Underfrequency protection (81UF)
1 Overview
Underfrequency protection is used to monitor whether the network is
normal by detecting the frequency. When the frequency is lower than the
underfrequency protection setting value and meet other conditions, the
underfrequency protection trips to remove the specified load.
The main features of underfrequency protection are as follows:
1) Undervoltage blocking
2) Frequency changing rate(df/dt) blocking;
3) Circuit breaker position check and loaded current blocking;
4) VT secondary circuit failure blocking.
5) Underfrequency protection configuring 1 stage protection, can be
enabled or disabled respectively.
Figure 82 The input and output signals of underfrequency protection function diagram
Table 113 Parameter description
Input:
BinaryInput
CBOpen Circuit breaker trip position
Output:
3 Detailed description
3.1 Protection principle
3.1.1 Protection function introduction
The principle of underfrequency and load shedding protection is "shed in
the line of interval". Specifically, the principle means that each interval will
be configured with underfrequency load shedding protection rather than
the incoming line interval will be configured with underfrequency load
shedding protection and send off tripping command through outlet line
interval. Then, every interval can be set with appropriate frequency
170
Chapter 22 Underfrequency protection (81UF)
171
Chapter 22 Underfrequency protection (81UF)
frequency<“UFFreqSet”
frequency<54Hz
&
or frequency>66Hz
System frequency=60Hz ≥1
frequency<45Hz
&
or frequency>55Hz
System frequency=50Hz
VT failure blocking
≥1
switch trip position
BI blocking
&
max(Ia,Ib,Ic)< ≥1 T1 Underfrequency
&
“LoadShedCurrBlkSet” protection trip
“UFLSChkCurrOn”=1
min(Uab,Ubc,Uca)<
&
“LoadShedVoltBlkSet”
“3PhVoltConnect”=1 ≥1
“UFLSChkDf/dt”=1
T1:“UFTime”
2. HVSideLoadShedCurrBlkSet 0.05In~10.0In 10 A
172
Chapter 22 Underfrequency protection (81UF)
173
Chapter 23 Overfrequency protection (81OF)
175
Chapter 23 Overfrequency protection (81OF)
1 Overview
Overfrequency protection is used to monitor whether the network is normal
by detecting the frequency. When the frequency is higher than the
overfrequency protection setting value and meet other conditions, the
overfrequency protection trips to remove the specified load.
Main characteristics of overfrequency protection are as follow:
1) Undervoltage blocking;
2) VT secondary circuit failure blocking;
3) Overfrequency protection configuring 1 stage protection.
Figure 84 The input and output signals of overfrequency protection function diagram
Table 119 Parameter description
Output:
3 Detailed description
3.1 Protection principle
3.1.1 Protection function introduction
The device offers 1 stages of overfrequency protection. Function of each
stage will be enabled or disabled through corresponding logic switch with
logic switch of each stage. The overfrequency protection trip frequency
can be measured by the input three-phase voltage or single phase voltage.
Enable/Disable logic switch "3PhVoltAccess" to choose the input voltage
mode. Note that if the access voltage is a single-phase voltage, then the A
phase or B phase voltage is required to be accessed to measure the
system frequency. Similarly, if the access voltage is a single phase
phase-to-phase voltage, then it needs to access the phase-to-phase
voltage UAB. No matter what kind of voltage access, the measurement
frequency is obtained by the measurement of the voltage frequency. Take
overfrequency stage 1 as example, if the measured frequency is higher
than setting value "OFFreqSet", the timing component will start timing. As
time delay reaches "OFTime", trip command will be sent.
176
Chapter 23 Overfrequency protection (81OF)
frequency>“OFFreqSet”
frequency<54Hz
&
or frequency>66Hz
System frequency=60Hz ≥1
frequency<45Hz
&
or frequency>55Hz
System frequency=50Hz
VT failure blocking
&
≥1 ≥1 T1 Over frequency
Protection trip
3 phase trip
BI blocking
min(Uab,Ubc,Uca)<
“LoadShedVoltBlkSet” &
“3PhVoltConnect”=1
T1:“OFTime”
2. HVSideLoadShedCurrBlkSet 0.05In~10.0In 10 A
177
Chapter 23 Overfrequency protection (81OF)
178
Chapter 24 Non-electric protection
179
Chapter 24 Non-electric protection
1 Overview
Non-electric protection supports eight groups of consumer non-electric
tripping.
Figure 86 The input and output signals of non-electric protection function diagram
Table 125 Parameter description
Input:
BI Non electric BI
ExtBI Output:
3 Detailed description
3.1 Protection principle
External BI stay time reaches non-electric time setting, protection will trip.
LED and protection trip can be configured by AESP.
“NonElectricGrp1On”=1 &
T1
Non-electric 1 protectin trip
Non-electric 1 BI
T1:“NonElectric1Time”
180
Chapter 24 Non-electric protection
Default
Number Setting name Range Unit Remark
value
5. NonElectric5Time 0~100 100 s
181
Chapter 25 Side differential protection
183
Chapter 25 Side differential protection
1 Overview
The side differential protection detects earth faults in power trans-formers
with earthed starpoint or in non-earthed power transformers with a
starpoint former (earthing transformer/reactor) installed inside the
protected zone. A precondition for using this function is that a CT should be
installed in the starpoint connection, i.e. between the starpoint and earth.
The starpoint CT and the phase CTs define the limits of the protected zone
by side differential protection. It includes a side differential protection
functional module.
Figure 88 The input and output signals of side differential protection function diagram
Table 129 Parameter description
Input:
1: function is on; 0: function is
1. En BOOL
off;
2. BIBlk BOOL 1: BI blocking
Output:
3 Detailed description
The side differential protection provided by the protection device can be
applied to the auto-transformer of CT in the common winding.
184
Chapter 25 Side differential protection
IA.2
A Ia.3
a
IB.2
Ib .3
B
b
IC .2
C Ic .3
c
3I01
CSC-326
3I03 = Ia.3 + Ib.3 + Ic.3
4 Protection principle
4.1 Differential and restraint current calculation
The differential current Idiff and restricted current Irest are calculated as
the following equation:
• • • •
I
diff = I h1 + I h2 + I m + I g
(1)
• • • •
Irest = max{| I h 1 |,| I h 2 |,| I m |,| I g |}
• •
Where: I h1 is high voltage side 1 phase current; I h 2 is high voltage
•
side 2 phase current; I m is medium voltage side current by phase current
•
Idiff and Irest are compared by the side differential protection with a
dual-slope operating characteristic defined by below equation and shown
in below figure.
I diff ≥ S1I res + I D > I res ≤ I R1
I diff ≥ S2 ( I res − I R1 ) + S1 × I R1 + I D > I R1 < I res ≤ I R 2
I diff ≥ S3 ( I res − I R 2 ) + S2 ( I R 2 − I R1 ) + S1 × I R1 + I D > I R 2 < I res
(2)
Where, S1 is the slope 1 (setting "SideDiffSlope1RatioRestrCoef").
Where, S2 is the slope 2 (setting "SideDiffSlope2RatioRestrCoef").
Where, S3 is the slope 3 (setting "SideDiffSlope3RatioRestrCoef").
ID> is the threshold value of the side differential protection sensitivity (the
setting is “SideDiffStartupSet”);
IR1 is the first break point setting of restricted current
“SideDiffBreakPoint1CurrSet”;
185
Chapter 25 Side differential protection
Slope3
Trip area
current
Slope2 restraint
Slope1
area I
Differential restra
int
startup setting
I restraint point1 I restraint point2 Restraint current
186
Chapter 25 Side differential protection
“SideDiffOn”=1
Phase A
I diff − A , I rest − A
& Phase A trip of
ID
> side differential
Phase B
I diff − B , I rest − B
ID
>
Phase B trip of
&
side differential
Phase C
I diff −C , I rest −C
ID
>
Phase C trip of
&
side differential
“ CTFailBlkSideDiff”=1
&
CTFail
n Phase −WG
K WG = (5)
n Phase −W 1
Where, KW 2 is the ratio compensation factor for winding 2 (MV winding)
phase CT, is the ratio compensation factor for common winding CTs.
K WG
4.3 CT failure supervision
During steady-state operation, the CT failure supervision monitors the
transient behavior of the currents flowing through secondary circuit of each
phase and thus registers failures in the secondary circuit of the current
transformers for each side of the power transformer. The function can be
187
Chapter 25 Side differential protection
IDiffSet“SideDiffStartupSet”
188
Chapter 25 Side differential protection
Where:
Iφ2 is the secondary harmonic of current on each side;
Iφ3 is the third harmonic of current on each side;
Khar is the setting of comprehensive harmonic ratio, and the fixed setting
of software.
If the second and 3rd harmonic contents of any phase current are more
than Khar, then CT satisfies the above formulas and it is saturated. Usually
before the CT saturation status. there is a short time period in which CT
still works in its linear characteristic. By very fast CT saturation detection of
IED, it needs only 4ms before any CT saturation happening to detect the
fault which is internal or external fault. x In order to distinguish saturation
caused by internal faults and external faults effectively, percent differential
protection based on sample values is used. If CT saturation is induced by
external fault, differential protection will be blocked. However if CT
saturation is induced by internal fault, differential protection will send its trip
signal.
The typical saturation figure of phase A CT saturation is shown in below
figure.
189
Chapter 25 Side differential protection
I D.alarm =
max{0.3 I _ Percent Diff , 0.1A} if I n 1A
I D.alarm =
max{0.3 I _ Percent Diff , 0.3 A} if I n 5 A
Logic of side differential current supervision is shown in below figure.
“SideDiffOn”=1
Idiff_A>ID.alarm
Current overlimit
Idiff_B>ID.alarm ≥1 & 5s alarm of side
differential
Idiff_C>ID.alarm
5 Setting list
Table 130 Side differential protection setting
Default
Range
Number Setting name value Unit Remark
(In:5A/1A)
(In:5A/1A)
Differential
1. SideDiffStartupSet 0.05In~4In 2 A Startup
Current Setting
The current
setting of first
2. SideDiffBreakPoint1CurrSet 0.1In~In 0.6 A
break point
(IR1)
The 2nd
breakpoint
3. SideDiffBreakPoint2CurrSet 0.1In~10In 2 A
restraint
current (IR2)
Ratio restraint
4. SideDiffSlope1RatioRestrCoef 0.00~0.2 0.2 coefficient of
the first slope
Ratio restraint
coefficient of
5. SideDiffSlope2RatioRestrCoef 0.2~0.7 0.5
the second
slope
Ratio restraint
6. SideDiffSlope3RatioRestrCoef 0.25~0.95 0.7 coefficient of
the third slope
190
Chapter 25 Side differential protection
6 Report list
Table 132 Report list
7 Technical data
Note: In is CT rated secondary current, 1A or 5A.
Table 133 Technical data for side differential protection
Content Range and value Error
Side ratio differential current 0.05In to 4.00In ≤ ±3% setting or ±0.02In,
Side differential restraint
0.1In to 1In ≤ ±3% setting or ±0.02In
current 1
Side differential restraint
0.1In to10In ≤ ±3% setting or ±0.02In
current 2
Side differential slope 1 0.0 to 0.2
Side differential slope 2 0.2 to 0.7
Side differential slope 3 0.25 to 0.95
Side differential Reset ratio of
About 0.7
restrained differential
it ≤ 30ms when the setting is
Side differential operating
in 200% times, and
time of restraint differential
IDifferential>2IRestraint
Reset time about 40ms
191
Chapter 26 Secondary circuit supervision
193
Chapter 26 Secondary circuit supervision
1 Overview
When the secondary circuit of the voltage transformer is broken or short
circuit, the measured voltage is zero by the protections based on the
undervoltage criterion and this can cause the mis-operation of IED. VT
failure check provides voltage monitoring for such protections. VT
monitoring is used to monitor the voltage transformer circuit, single-phase
VT failure, two-phase VT failure and three-phase VT failure. Main
characteristics is as follows:
1) Symmetry/ asymmetry (asymmetric) VT failure;
2) Three-phase AC voltage miniature transformer failure monitoring;
3) It is used in grounding system, non-direct grounding system and
ungrounded system.
Input:
BIConfig
V3P_BI Three-phase VT failure BI
Output:
VTFail
VTFail VT failure alarm
3 Detailed description
3.1 Protection principle
3.1.1. Protection function introduction
VT failure function can be enabled or disable by setting the logic switch
“VTFailOn”, when the logic switch is set as 1, VT failure protection is
enabled, it can be used to detect single-phase, two-phase and
three-phase VT failure.
There are three main criteria for detecting VT failure, which are the check
of the three phase failure, the check of the asymmetric failure of the
grounding system, and the check of the asymmetry of the non-direct
grounding system. The prerequisite is that the protection device starting
194
Chapter 26 Secondary circuit supervision
component does not start and the zero sequence current and negative
sequence current are less than "VTFail3I03I2Set" Specifically as follows:
1) Three-phase (symmetry) VT failure: when the secondary side
three-phase of VT failure occurs, if the stating component does not
start, then the maximum of compounded zero sequence voltage
3U0 and three-phase phase-to-earth voltage are both less than
"VTFailPEVoltSet" and the maximum of three-phase current
exceeds "VTFailCurrSet".
2) Single-phase/ two-phase (asymmetric) VT failure
a) When the secondary side single-phase or two-phase of VT failure
occurs, if the system is directly grounded and the stating
component does not start, then the maximum of compounded
zero sequence voltage 3U0 exceeds "VTFailPEVoltSet".
b) When the secondary side single-phase or two-phase of VT failure
occurs, if the system is not directly grounded and the stating
component does not start, then then compounded zero sequence
voltage 3U0 exceeds "VTFailPEVoltSet" and the difference
between the maximum and minimum of voltage exceeds
"VTFailPPVoltSet".
In addition, when the device detects V3P_BI, then it is judged as
"3PhVTFail". If the device detects V3P_BI and the voltage exceeds
"VTFailPEVoltSet", it is judged as abnormal BI signal.
After "InstantVTFail", "VTFailAlarm" or "VTFailBIErrAlarm" are issued,
LED and protection trip can be configured by AESP.
3.1.2. Logic diagram
If the secondary circuit failure of VT is detected, the protection based on
the standard of direction or undervoltage will be blocked and it will send off
the report "VTFailAlarm" through the delay of "VTFailDelayAlarm". When
one of the following conditions is met within the delay of
"VTFailAlarmTime" (that is, before sending off the report "VTFailAlarm"),
VT failure blocking opens.
1) While the protection does not start, the minimum phase-to-phase
voltage exceeds "VTFailNormalVolt" with 500ms delay.
2) While the protection does not start, the minimum phase-to-phase
voltage exceeds "VTFailNormalVolt" and the zero sequence current
and negative current exceed "VTFail3I03I2Set".
3) While the protection does not start after the "VTFailAlarm" is sent off ,
the minimum phase-to-phase voltage exceeds "VTFailNormalVolt", VT
failure blocking opens through 10s delay.
The report "VTFailRst" is issued when the third VT failure recovery is
checked.
195
Chapter 26 Secondary circuit supervision
max(Ia,Ib,Ic)>“VTFailCurrSet”
&
max(Ua,Ub,Uc)<“VTFailPEVoltSet”
Calculated3U0<
“VTFailPEVoltSet”
“NutrPointEarth”=1 & ≥1
Calculated3U0>=
“VTFailPEVoltSet”
“NutrPointEarth”=0 &
Max(PPVoltage)-Min(PPVoltage)>
“VTFailPPVoltSet”
&
Current type ≥1
protection start-up &
InstantVTFailure=1
3PhaseVTFailureBI
VTFailureFunctionOn
“VTFailOn”=1
“VTFailOn”=0
&
Calculated3I0>“VTFail3I0/3I2Set” ≥1 &
≥1
InstantVTFailure=0
3I2>“VTFail3I0/3I2Set”
min(Ua,Ub,Uc)>“VTFailNormalVolt”
&
VTFailureAlarm=1
&
&
T
T
InstantVTFailure=1 VTFailureAlarm=1
T:“VTFailAlarmTime”
3 phase VT failure BI
T_Err:“VTFailBIErrTime”
196
Chapter 26 Secondary circuit supervision
2. HVSideVTFailOn 1/0 0
Note: VT Failure protection logic switch of each middle and low voltage
side is the same to that of high voltage side
3.3 Report list
Table 137 Report list
197
Chapter 27 T-zone protection
199
Chapter 27 T-zone protection
1 Overview
T-zone function includes three-side current differential protection, two-side
current differential protection, overcurrent protection and line charging
protection.
As shown in Figure 98 , when the isolator G1 of the outlet line is closed
(the isolator is closed, the position contact of isolator is open), T-zone
protection adopts three-side differential current mode. When there is fault
in T-zone, two breakers will be tripped and the signal will be sent to the
opposite end.
When the isolator G1 of the outlet line is open (when the isolator is open,
the position contact of it is closed), the three-side current differential
protection will convert to two-side current differential protection
automatically (if the dia is needed to operate, then the stub differential
protection should be enabled). And at the same time, the two stages of
current protection should be enabled on the line side and work as line-end
protection. When there is fault in T-zone, the two-side current differential
protection will trips two breakers (side and intermediate beakers). When
the two stages of overcurrent protection trips, and then remote tripping
signal will be sent to the opposite end.
The line charging protection should be enabled all the time.
Busbar 1
Differential
protection
Side CB
Middle CB
T-area
protection
Busbar 2
200
Chapter 27 T-zone protection
STUBDiff
1 1
En St_IAssist
2 2
CHGBIBlk St_IHL
3 3
OCBIBlk Startup
4 4
DiffBIBlk CHGOp
5 5
SwitchPos OC1Op
6
OC2Op
7
UnbalanceDiff
8
CTFailM
9
CTFailN
10
CTFailT
11
Diff2side
12
Diff3side
13
SwitchErr
14
SEQErr
15
TrFail
16
FaultI1
17
FaultI2
18
FaultI3
Input:
BinaryInput SwitchPo
Isolator open
s
Input:
Output:
201
Chapter 27 T-zone protection
3 Detailed description
The device is configured with three-side current differential protection,
two-side current differential protection, two stages of overcurrent
protection and line charging protection.
202
Chapter 27 T-zone protection
. . .
│ I 1 + I 2+ I 3│> 0.9 × min {"StubDiffCurrSet", "OCStage1CurrSet",
"OCStage2CurrSet"}
Where, min {"StubDiffCurrSet", "OCStage1CurrSet", "OCStage2CurrSet"}
are the minimum value when the corresponding functions are enabled.
. . .
I 1, I 2 and I 3 stand for CT currents of two circuit breakers and outlet
line respectively.
When the differential current of phase A or phase B or phase C meets the
condition, the protection starts up.
3) Current sum startup component
When the charge protection logic switch is enabled, current sum startup
component of two circuit breakers is set, the criterion is:
. .
│ I 1 + I 2│> 0.9 ×"ChargingProtCurrSet"
When the current sum of phase A or phase B or phase C meets the
condition, the protection starts up.
3.1.2. Three-side current differential protection.
After the enabling of differential protection soft and hard connectors and
logic switch, when the isolator G1 of the outlet line is closed (when the line
switch is closed, the position contact of isolator is open), three-side current
differential protection is enabled.
Three-side protection is a current differential protection with restraint
characteristic, which takes into account the characteristic differences of
the three groups of CTs.
The three-side differential protection are composed of A, B and C
respectively, when any differential current meets the condition, the
three-side differential protection starts up, the equation is:
. . .
│ I 1 + I 2+ I 3│>"StubDiffCurrSet"
. . . . . .
│ I 1 + I 2+ I 3│> K*(│ I 1│+│ I 2│+│ I 3│)/2
. . .
Where, I 1, I 2 and I 3 stand for CT currents of two circuit breakers and
outlet line respectively, K stands for restraint coefficient, differential current
. . . . . .
=│ I 1 + I 2+ I 3│, restraint current=(│ I 1│+│ I 2│+│ I 3│)/2.
Three-side differential protection characteristic curve is Figure 100 shown
as below.
203
Chapter 27 T-zone protection
Trip area
Trip area
204
Chapter 27 T-zone protection
Two-side differential protection trips two circuit breakers on the local side.
After the tripping, the output and indication light can be configured on IO
Matrix.
In order to prevent from incorrect trip of two-side differential protection
caused by the abnormal position of the switch, the three-side differential
protection is also required to meet the trip condition, when two-side
differential trips.
3.1.4. Overcurrent protection
After the enabling of overcurrent protection soft and hard connectors and
logic switch, when the isolator G1 of the outlet line is open (when the
isolator is open, the position contact of it is closed), overcurrent protection
is enabled.
There are two stages of overcurrent protection. The equation is:
IGL > IGLDZn
. . .
│ I 1 + I 2+ I 3│> 0.9 × IGLDZn
Where, IGL is any phase current for line CT, IGLDZn is
. . .
"OCStage1CurrSet", "OCStage2CurrSet",. n is 1 or 2, I 1, I 2 and I 3
stand for two circuit breakers and outlet line CT current, and overcurrent is
composed of phase A, phase B and phase C.
The current of any phase satisfies the above conditions, and the
overcurrent 1 or 2 stages are output according to their respective setting
time. After the tripping, the output and indication light can be configured on
IO Matrix.
When overcurrent protection trips, the trip signal will be sent to the
opposite end and trips the circuit breaker of the line.
3.1.5. Charging protection
After the enabling of the logic switch of line charge protection, when the
current of any phase meets the following conditions, the charge protection
trips in accordance with setting time.
The equation is:
. .
│ I 1 + I 2│>"ChargingProtCurrSet"
. .
Where, I 1 and I 2 are CT currents of the two circuit breakers and are
.
composed of the three phase A, phase B and phase C, current sum=│ I 1
.
+ I 2│.
Charge protection trips the two circuit breakers on the local side. After the
tripping, the output and indication light can be configured on IO Matrix.
3.1.6. Abnormality check and judgment
1) CT failure supervision
It is calculated that the differential current in the normal operation is greater
than the min {0.1In or “StubDiffCurrSet”} for 12 continuous seconds, while
205
Chapter 27 T-zone protection
2. OCStage1On 1/0 0
3. OCStage2On 1/0 0
4. ChargingProtOn 1/0 0
2. IEDCTSecVal 1 or 5 1 A
3. BISwitchSetGrp 1/0 0
206
Chapter 27 T-zone protection
207
Chapter 28 Gap protection
209
Chapter 28 Gap protection
1 Overview
Gap protection is a backup protection for single-phase grounding fault
when the neutral point of a non fully insulated transformer is grounded by
discharge gap.
Figure 102 The input and output signals of gap protection diagram
Table 146 Parameter description of input and output
Input:
Output:
Start IED startup
JX
bOperationLL1 Time 1 trip of gap zero sequence voltage
3 Detailed description
3.1 Protection principle
Gap protection includes zero sequence voltage protection and gap
overcurrent protection.
Zero sequence voltage protection trip voltage can be selected as external
or self-calculated by logic switch. When self-calculated is selected, it is
blocked by VT failure logic.
The trip current of gap overcurrent protection is taken from the gap zero
sequence CT current of the transformer earthing circuit through the gap,
and forms “OrLogic” time trip together with the zero sequence voltage.
The logic diagram of gap protection trip is shown in.
210
Chapter 28 Gap protection
Calculated3U0>“GapOVSet”
&
VTfailure
≥1
“GapCalc3U0”=1 3U0Component Trip
&
Calculated3U0> “GapOVSet”
“GapOVOn”=1
&
T_JXU0 Gap overvoltage
protection trip
3U0Component Trip
≥1
&
T_JXI0 Gap overcurrent
protection trip
Gap current>ISet_JX
“GapOCOn”=1
Iset_JX:“GapOCSet”
T_JXU0:“GapOVTime”
T_JXI0:“GapOCTime”
Note: Gap protection setting of medium voltage side is the same to that of
high voltage side
Table 148 Gap protection logic switch
Note: Gap protection logic switch of medium voltage side is the same to
that of high voltage side
211
Chapter 28 Gap protection
212
Chapter 29 User-defined protection
213
Chapter 29 User-defined protection
1 Overview
User-defined protection includes overload protection, start fan protection
and blocking voltage adjustment protection.
Define Function
1
Alarm
Figure 104 The input and output signals of user-defined protection diagram
Table 150 Parameter description of input and output
OL/QDTF/B Output:
STY Alarm IED alarm
3 Detailed description
3.1 Protection principle
The device is equipped with overload protection, delayed action on signal,
and overload protection to detect three-phase current.
In addition, user-defined protection is provided with overload start fan
protection and blocking voltage adjustment protection, and the
three-phase current of the high voltage side can be detected, and the
setting value can be set.
Overload alarm trip logic diagram is shown below:
Ia>“OLCurrSet”
≥1
&
Ib>“OLCurrSet” T
Overload
Ic>“OLCurrSet”
“OLOn”=1
T:“OLTime”
214
Chapter 29 User-defined protection
Ia>“StartFanCurrSet”
≥1
&
Ib>“StartFanCurrSet” T
StartFan
Ic>“StartFanCurrSet”
“StartFanOn”=1
T:“StartFanTime”
“BlkVoltAdjOn”=1
T:“eBlkVoltAdjTime”
Note: Overload protection setting of middle and low voltage side are the
same to that of high voltage side
Table 152 Overload protection logic switch of high voltage side
Logic switch Set Default
Number Remark
name mode value
1. HVSideOLOn 1/0 1 1-On, 0-Off
Note: Overload protection logic switch of middle and low voltage side are
the same to that of high voltage side
Table 153 Start fan protection setting of high voltage side
Default
Number Setting name Range Unit Remark
value
1. HVSideStartFanStage1CurrSet 0.05In~40In 40 A
3. HVSideStartFanStage2CurrSet 0.05In~40In 40 A
215
Chapter 29 User-defined protection
Table 154 Start fan protection logic switch of high voltage side
Set Default
Number Logic switch name Remark
mode value
1. HVStartFanStage1On 1/0 1 1-On, 0-Off
Table 155 Blocking voltage adjustment protection setting of high voltage side
Default
Number Setting name Range Unit Remark
value
1. HVSideBlkVoltAdjCurrSet 0.05In~40In 40 A
Table 156 Blocking voltage adjustment logic switch of high voltage side
Set Default
Number Logic switch name Remark
mode value
1. HVSideBlkVoltAdjOn 1/0 1 1-On, 0-Off
Note: the report of each low voltage side is the same to that of low voltage
side
216
Chapter 30 User-defined function
217
Chapter 30 User-defined function
1 Overview
The binary input and output, report, LED of device can be defined
secondly in accordance with demands. According to the actual situation of
the project, the user can user-definedize the logic. This chapter mainly
describes the function of the AESPStudio tool software which may be used
in engineering application to perform the user defined function and the
matters needing attention.
2 User-defined configuration
2.1 Open project
Click the file→open, in the open file dialog box, open the file named
aespro.
Configuration Description
item
Binary input Excitation changes from 0 to 1, and close position of binary input is defined
time 1 by time 1
Binary input Excitation changes from 1 to 0, and open position of binary input is defined
time 2 by time 2
Bay control
unit and
Configure "Prot", "BCU"
protection
property
218
Chapter 30 User-defined function
Note: when setting waveform record, if "DFR" is configured, then the BI will
be in the waveform recording; if "RisingEdgeTrigger" is configured, when
the BI changes from 0 into 1, the waveform record will be generated; if
"FallingEdgeTrigger" is configured, when the BI changes from 1 into 0, the
waveform record will be generated. The generated waveform record file
will be saved into the list of startup waveform records.
The work voltage can only be configured within ranges defined by this
module unit. Hardware board contains high power voltage level and low
power voltage level, respectively marked with the work voltage of DC
"110V", "125V", "220V", "250V" and "24V", "48V".
The time sequence explanation of "BITime1" and "BITime2" is shown as
below.
Excitation
Binary input
219
Chapter 30 User-defined function
Configuration Description
item
Holding time Excitation returns and BO also returns experiencing retention time.
Excitation
Reset
Relay
Excitation
Relay
220
Chapter 30 User-defined function
Light configuration.
Configuration Description
item
Flashing The LED is flashing or constant on, n represents the flash frequency is
n*50ms; when it is 0 or 1, the LED is always on.
Redundancy As the configuration is "Redundancy" property, multiple CPU will trigger light
at the same time and the LED will be enlightened
As CPU and other redundant CPU all send out lighting commands, the
LED configured with "Redundancy" can be enlightened. If LED doesn't
have redundancy property, "Redundancy" property can not be set.
221
Chapter 30 User-defined function
222
Chapter 30 User-defined function
223
Chapter 30 User-defined function
224
Chapter 30 User-defined function
225
Chapter 31 Substation communication
Chapter 31 Substation
communication
227
Chapter 31 Substation communication
1 Overview
Each IED provides communication port to communicate with one or more
substation system. IED supports following communication protocols:
1) IEC 61850-8-1 communication protocol
2) IEC 60870-5-103 communication protocol
3) DNP 3.0
4) MODBUS
2 Communication protocol
2.1 IEC 61850-8-1 communication protocol
Protocol IEC61850-8 allows two or more IED in one or more factories to
communicate and cooperate on the basis of their functions.
Standard IEC 61850-8-1 rules GOOSE (generic object of substation event).
By publishing and subscribing mechanism, GOOSE standardizes
communication state and control information between IEDs. That is to say,
if event is tested to happen, IED shall send information to devices which
have subscribed the event by multi cast.
3 Communication port
3.1 Front plate communication port
Front plates of all IEDs have a RJ45 communication port respectively. By
this port, users can use PC to operate Sifang debug software to connect
IED for setting, testing, configuring and so on.
228
Chapter 31 Substation communication
4 Technical data
Table 164 Front plate communication port
Items Data
No. 1
Connection mode Debugging RJ45 port for software
Communication rate 100Mbit/s
229
Chapter 31 Substation communication
Switch
Work Station 3
Gateway Switch
or
converter
230
Chapter 32 Man-machine interface (MMI) and operation
231
Chapter 32 Man-machine interface (MMI) and operation
1 Overview
The MMI is composed of liquid crystal display (LCD), LED, panel buttons
and panel Ethernet port. Users can view information, set parameters and
debug through MMI.
2 Function description
2.1 Liquid crystal display(LCD)
The LCD back light of HMI is blue, 9 lines can be displayed. When
operating Sifang key or IED issuing alarm or trip report, background blue
light automatically lights up. Soon after the latest trip or alarm, background
blue light dies out after 5 minutes of time setting.
CSC-326
232
Chapter 32 Man-machine interface (MMI) and operation
running lights and alarm light are fixed, and the functions of other 22 lamps
can carry out the configuration of light color, light property according to the
needs of the user ; in key areas, there is indicator indicating device state
on each of the remote, local and blocking key respectively.
RUN: When running lights, the green light is lightened during the normal
operation, while the running light is off if there is an alarm of class 1.
ALARM: alarm indicator, the device alarm lightens the red light.
The faceplate uses the Ethernet port to connect PC and device, which
supports setting device parameter, measuring function, downloading
programs and analyzing data. The debugging IP address of Ethernet port
is 196.178.111.1 which is unchangeable.
The key includes basic key and control functional key. Basic key is on the
right of the screen and control functional key is below the screen to realize
human-computer interaction. Keys for IED of CSC series contain the same
appearance and operation mode, for details in below table.
Table 168 IED MMI Key
Key Function
+
Page down
Logic switch shift from the present value to the opposite
value; namely "1" to "0", or "0" to "1"
233
Chapter 32 Man-machine interface (MMI) and operation
Key Function
Value minus 1
-
Page up
Logic switch shift from the present value to the opposite
value; namely "1" to "0", or "0" to "1"
F1
F4
Switching to remote operation mode, and earthing control
shall be blocked.
Switching to earthing control mode, remote operation shall
be blocked.
It is used for locking and unlocking control key and
user-defined key so as to prevent mistakenly touching.
Breaker closes
Breaker opens
234
Chapter 32 Man-machine interface (MMI) and operation
235
Chapter 32 Man-machine interface (MMI) and operation
236
Chapter 32 Man-machine interface (MMI) and operation
Click the key in the recycle main interface, the menu tree will be shown
in the MMI interface; click the key or to select menu items, when the
cursor stays in the corresponding menu item, if there is a symbol ""
behind this menu item, it can click the key or to enter the next menu; if
there is no signal "", it can click the key to enter the menu items.
237
Chapter 32 Man-machine interface (MMI) and operation
238
Chapter 33 IED hardware
239
Chapter 33 IED hardware
1 Overview
1.1 IED structure
19
1.1.1 4U, 2 inch device
Height for IED crate is 4U and width is 19 2 inches. The whole is for
embedded installation with back-wiring mode.
240
Chapter 33 IED hardware
241
Chapter 33 IED hardware
242
Chapter 33 IED hardware
243
Chapter 33 IED hardware
244
Chapter 33 IED hardware
3 BIO module
3.1 Overview
BIO module provides a certain of protection tripping and closing control so
as to realize telecontrol switching of the switch and isolator.
The BIO hardware of BI module includes two types of welding : 1) high
power voltage level, adaptive 110V, 220V, 125V, 250V and 2) low power
voltage level, adaptive 24V and 48V. Work rated power source of device
BI is modified by configuration file before applying.
Due to the different location of the slot, the BIO module can be set at
different address of board cards, and the address is set through the jumper
J6. Take the side away from single board as L side, the side near single
board as H side, from bottom to top is AD0, AD1, AD2, AD3.
Table 173 Definition of BIO module address
Slot
Jumper Control content Jumper settings
location
BIO1 J6 BIO1 address AD3~AD0 are short connected to the L side
AD3 and AD1 are short connected to the L
BIO2 J6 BIO2 address
side, AD0 is short connected to the H side
AD3, AD2, AD0 are short connected to the L
BIO3 J6 BIO3 address
side, AD1 is short connected to the H side
AD3, AD2 are short connected to the L side,
BIO4 J6 BIO4 address AD1 and AD0 are short connected to the H
side
Each BIO board has 6 BI and 12 BO. 6 BI are divided into 2 groups, and
each of 3 BI shares a common terminal.
12 BO are divided into 4 groups, and each group can be set as whether
through the starting through jumper, with total four groups of jumpers
J11~J14. The jumper inserting into 1, 2 pin represents through starting
relay outlet, inserting into 2, 3 pin represents not through starting relay
outlet.
245
Chapter 33 IED hardware
BO12 can switch normally open or normally closed node by JP1 jumper ,
that is, jumper jumping to the NC side is the normally closed node, while
jumper jumping to the NO side is the normally open node.
Table 175 Description 2 for jumper of BIO module
Jumper Binary output NC NO
Normally closed
JP1 BO12 Normally open node
node
246
Chapter 33 IED hardware
Executive
Items Data
standard
5A continuous,
Current carrying capacity IEC 60255-1
30A, 200ms On, 15s Off
IEC 60255-1
Authentication IEC 60255-23 UL/CSA, TŰV
IEC 61810-1
IEC 60255-1
Contact circuit resistance IEC 60255-23 30mΩ
IEC 61810-1
Contact insulation test (AC IEC 60255-1
AC1000V 1min
dielectric strength ) IEC 60255-27
247
Chapter 33 IED hardware
4 CPU module
4.1 Overview
CPU module is the core of the IED and responsible for running all
protection logic to carry out the hardware self-check and communication
with external devices such as MMI, PC, measurement, substation
automatic system, working station, RTU, printers and so on. Besides, CPU
module sends telemetry, telesignalisation, SOE, event report and recorded
wave to backstage, it provides time synchronization and communication
port.
CPU module provides multiple configuration for user's need. Differences
lie in quantities for Ethernet port, optical/electric port, time synchronization
mode, storage capacity and so on.
248
Chapter 33 IED hardware
249
Chapter 33 IED hardware
250
Chapter 33 IED hardware
6 TCS Module
6.1 Overview
It shall be noticed that the facia shall be assembled and welded according
to the different rated working power, please make sure before use.
The built-in TCS function is applicable to the occasion when the trip
contacts in device are used for trip directly; generally, it is applied to the
occasion when installing protection device with medium voltage in switch
251
Chapter 33 IED hardware
cabinet. In 80% occasions, only the trip circuit is monitored, the closing
circuit doesn't get monitored. Therefore, the device provides a module with
TCS circuit and trip relay cooperating with each other.
252
Chapter 33 IED hardware
253
Chapter 33 IED hardware
Figure 134 Binary output circuit with large capacity schematic diagram
When the binary output current is larger than 6A, then the terminals of list
and list c need to be connected in parallel.
3) Ordinary BO circuit
254
Chapter 33 IED hardware
255
Chapter 33 IED hardware
7 Test
Table 191 Insulation test
Items Executive standard Measurement methods
Front panel: IP54
IEC 60255-27
Protection level (IP) Side panel: IP52
IEC 60529
back panel: IP30
2KV, 50Hz (rated
voltage >63V) tested between
the following circuits:
Power supply
CT / VT input
IEC 60255-5
Binary input
EN 60255-5
Binary output
Dielectric Strength ANSI C37.90
Case grounding 500V ,
GB/T 15145-2008
50Hz(rated voltage ≤63V)
DL/T 478-2013
Test between the following
circuits,
Communication port
Time synchronization port
Case earthing
5kV (rated voltage>60V)
1kV (rated voltage≤60V)
1.2/50Μs, 0.5J
IEC 60255-5 Test between the following
IEC 60255-27 circuits,
EN 60255-5 Power supply
Impulse voltage
ANSI C37.90 CT / VT input
GB/T 15145-2008 Binary input
DL/T 478-2013 Binary output
Communication port
Time synchronization port
Case earthing
IEC 60255-5
IEC 60255-27
EN 60255-5
Insulation resistance ≥ 100MΩ,500V DC
ANSI C37.90
GB/T 15145-2008
DL/T 478-2013
Earthing resistance IEC 60255-27 ≤0.1Ω
Flame rating IEC 60255-27 Level V2
256
Chapter 33 IED hardware
257
Chapter 33 IED hardware
8 Structural design
Table 195 1Structural design
Items Data
Dimension 4U×1/2 19 inches
Weight ≤ 9kg
9 CE Certification
Table 196 CE Certification
Items Data
EN 61000-6-2 and EN61000-6-4(EMC guide
EMC
committee 2004/108/EC)
LVD EN 60255-27(LVD 2006/95 EC)
258
Chapter 34 Appendix
Chapter 34 Appendix
259
Chapter 34 Appendix
1 IED parameter
Table 197 IED parameter
Number Name Range Default Unit Remark
260
Chapter 34 Appendix
2 Report list
About operation report and protection alarm report, please see the report
list in the protection chapter.
2 IEDParmErr 32770
3 ROMSumChkErr 32771
5 UnconfirmConnMode 32773
6 SoftConnErr 32774
7 SystemCfgErr 32775
9 SetGrpPointerErr 32780
11 CfgFileErr 35769
12 CfgFileInconsist 35770
16 BIBreakdown 33784
261
Chapter 34 Appendix
21 BISelfChkCircuitErr 33787
22 BOLatchedPropertyCfgErr 33793
You need to confirm the module
address jumper, module should be
23 BICommInterrupt 33781
plugged tightly, and confirm that the
program of BI is correct.
You need to confirm the module
address jumper, module should be
24 BOCommInterrupt 33782
plugged tightly, and confirm that the
program of BI is correct.
Table 199 Alarm report list of class I
2 TestStateNotRst 33772
3 OperFail 33773
4 CanCommInterrupt 33775
5 FLASHSelfChkErr 33776
6 WorkInTestSetGrp 33783
7 BIInputErr 33785
8 DualPosnInputIncosist 33786
9 BIOInputPowerErr 33788
262
Chapter 34 Appendix
3 Analog list
Table 201 Analog list
Number LCD display Description Remark
263
Chapter 34 Appendix
The currents of
each branch of
the high voltage
side should be
converted to the
currents of first
Calculated Zero sequence current of high branch of high
28 Ih_3I0Cal
voltage side voltage side,
and then
calculate the
zero sequence
current by using
the sum
currents.
264
Chapter 34 Appendix
The currents of
each branch of
the medium
voltage side
should be
converted to the
currents of first
Calculated Zero sequence current of medium
41 Im_3I0Cal branch of
voltage side
medium voltage
side, and then
calculate the
zero sequence
current by using
the sum
currents.
265
Chapter 34 Appendix
266
Chapter 34 Appendix
267
Chapter 34 Appendix
4 Typical wiring
As for transformer backup protection IED, the typical wiring is shown as
below:
A
B
C
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
AIM1
* I01
I02
I1
Figure 136 Apply to transformer backup protection measurement three phase current,
zero sequence current and neutral point earth current
268
Chapter 34 Appendix
A
B
C
AIM2
U01
UA
U02
UB
U03
UC
U04
UN
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
AIM1
* I01
I02 I1
A
B
C
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
AIM2
U01
UA
U02
UB
U03
UC
U04
UN
AIM1
* I01
I02 I1
269
Chapter 34 Appendix
A
B
C
AIM2
U01
UA
U02
UB
U03
UC
U04
UN
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
AIM1
* I01
I02 I1
Figure 139 Apply to transformer backup protection measurement three phase current,
zero sequence current and neutral point earth current and single line voltage beside
busbar
A
B
C
AIM2
U01
UA
U02
UB
U03
UC
U04
UN
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
AIM1
* I01
I02 I1
Figure 140 Apply to transformer backup protection measurement three phase current,
zero sequence current and neutral point earth current and single-phase voltage beside
busbar
270
Chapter 34 Appendix
A
t= � i p
+ B�T
� � −1
I
Where:
A: time coefficient of inverse time
B: time delay of inverse time
P: inverse time index
T: inverse time constant
271
Chapter 34 Appendix
Abbreviations Explanation
272
Chapter 34 Appendix
Abbreviations Explanation
273
Chapter 34 Appendix
Abbreviations Explanation
Phase-to-earth zone 2 point to transformer of high voltage
HVSidePEZ2PointToTransf
side
HVSidePEZ2PointToSystem Phase-to-earth zone 2 point to system of high voltage side
274
Chapter 34 Appendix
Abbreviations Explanation
Index P of inverse time overcurrent stage 2 of high voltage
HVSideInvTimeOCStage2IndexP
side
Time B of inverse time overcurrent stage 2 of high voltage
HVSideInvTimeOCStage2TimeB
side
HVSideInvTimeOCStage2Const Constant T of inverse time overcurrent stage 2 of high
T voltage side
HVSideOCStage3Curve Overcurrent stage 3 curve of high voltage side
275
Chapter 34 Appendix
Abbreviations Explanation
276
Chapter 34 Appendix
Abbreviations Explanation
277
Chapter 34 Appendix
Abbreviations Explanation
Constant T of inverse time negative sequence current stage
HVSideInvTimeI2Stage2T
2 of high voltage side
Negative sequence current stage 3 curve of high voltage
HVSide3I2Stage3Curve
side
Current setting of negative sequence current stage 3 of high
HVSide3I2Stage3CurrSet
voltage side
Time 3 of negative sequence current stage 1 of high voltage
HVSideI2Stage3Time1
side
Constant A of inverse time negative sequence current stage
HVSideInvTimeI2Stage3A
3 of high voltage side
Constant P of inverse time negative sequence current stage
HVSideInvTimeI2Stage3P
3 of high voltage side
Constant B of inverse time negative sequence current stage
HVSideInvTimeI2Stage3B
3 of high voltage side
Constant T of inverse time negative sequence current stage
HVSideInvTimeI2Stage3T
3 of high voltage side
HVSideI2RstTime Negative sequence current reset time of high voltage side
Minimum trip time of inverse time negative sequence current
HVInvTimeI2MinTripTime
of high voltage side
Time 1 of negative sequence current stage 2 of high voltage
HVSideI2Satge1Time2
side
Time 1 of negative sequence current stage 3 of high voltage
HVSideI2Satge1Time3
side
Time 2 of negative sequence current stage 2 of high voltage
HVSideI2Satge2Time2
side
Time 2 of negative sequence current stage 3 of high voltage
HVSideI2Satge2Time3
side
Time 3 of negative sequence current stage 2 of high voltage
HVSideI2Satge3Time2
side
Time 3 of negative sequence current stage 3 of high voltage
HVSideI2Satge3Time3
side
HVSideOVStage1Curve Overvoltage stage 1 curve of high voltage side
278
Chapter 34 Appendix
Abbreviations Explanation
Time B of inverse time overvoltage stage 2 of high voltage
HVSideInvTimeOVStage2TimeB
side
Constant T of inverse time overvoltage stage 2 of high
HVSideInvTimeOVStage2ConstT
voltage side
HVSideOVDropoffCoef Overvoltage dropoff coefficient of high voltage side
279
Chapter 34 Appendix
Abbreviations Explanation
280
Chapter 34 Appendix
Abbreviations Explanation
Negative sequence current setting of circuit breaker failure
HVSideCBFI2Set
of high voltage side
HVSideCBFTime1 Time of circuit breaker failure 1 of high voltage side
LVSideDZ3I0Set Dead zone zero sequence current setting of low voltage side
Dead zone negative sequence current setting of low voltage
LVSideDZI2Set
side
LVSideDZ BIErrTime Dead zone binary input error time of low voltage side
281
Chapter 34 Appendix
Abbreviations Explanation
282
Chapter 34 Appendix
Abbreviations Explanation
283
Chapter 34 Appendix
Abbreviations Explanation
Abbreviations Explanation
284
Chapter 34 Appendix
Abbreviations Explanation
285
Chapter 34 Appendix
Abbreviations Explanation
Enable phase-to-earth impedance zone 3 time 1 of high
HVSidePEZ3Time1On
voltage side
Enable phase-to-earth impedance zone 3 time 2 of high
HVSidePEZ3Time2On
voltage side
Enable phase-to-earth impedance zone 3 time 3 of high
HVSidePEZ3Time3On
voltage side
Enable phase-to-earth impedance zone 4 of high voltage
HVSidePEZ4On
side
Phase-to-earth impedance zone 1 is blocked by power
HVSidePEZ1BlkByPowerSwing
swing of high voltage side
Phase-to-earth impedance zone 2 is blocked by power
HVSidePEZ2BlkByPowerSwing
swing of high voltage side
Phase-to-earth impedance zone 3 is blocked by power
HVSidePEZ3BlkByPowerSwing
swing of high voltage side
Phase-to-earth impedance zone 4 is blocked by power
HVSidePEZ4BlkByPowerSwing
swing of high voltage side
InterturnProtIsOn Enable interturn protection
286
Chapter 34 Appendix
Abbreviations Explanation
287
Chapter 34 Appendix
Abbreviations Explanation
288
Chapter 34 Appendix
Abbreviations Explanation
Enable time 3 of negative sequence current stage 3 of high
HVSideI2Stage3Time3On
voltage side
HVSideOVStage1On Enable stage 1 of overvoltage of high voltage side
289
Chapter 34 Appendix
Abbreviations Explanation
290
Chapter 34 Appendix
Abbreviations Explanation
Abbreviations Explanation
291
Chapter 34 Appendix
Abbreviations Explanation
292
Chapter 34 Appendix
Abbreviations Explanation
Time 3 trip of phase-to-earth impedance protection zone 3
HVSidePEZ3Time3Trip
of high voltage side
Trip of phase-to-earth impedance protection zone 4 of high
HVSidePEZ4Trip
voltage side
Time 1 trip of phase-to-phase distance zone 1 of middle
MVSidePPZ1Time1Trip
voltage side
Time 1 trip of phase-to-phase distance zone 2 of middle
MVSidePPZ1Time2Trip
voltage side
Time 1 trip of phase-to-phase distance zone 3 of middle
MVSidePPZ1Time3Trip
voltage side
Time 2 trip of phase-to-phase distance zone 1 of middle
MVSidePPZ2Time1Trip
voltage side
Time 2 trip of phase-to-phase distance zone 2 of middle
MVSidePPZ2Time2Trip
voltage side
Time 2 trip of phase-to-phase distance zone 3 of middle
MVSidePPZ2Time3Trip
voltage side
Time 3 trip of phase-to-phase distance zone 1 of middle
MVSidePPZ3Time1Trip
voltage side
Time 3 trip of phase-to-phase distance zone 2 of middle
MVSidePPZ3Time2Trip
voltage side
Time 3 trip of phase-to-phase distance zone 3 of middle
MVSidePPZ3Time3Trip
voltage side
Trip of phase-to-phase impedance stage 4 of middle
MVSidePPZ4Trip
voltage side
MVSidePEZ1Time1Trip Time 1 trip of phase-to-earth zone 1 of middle voltage side
293
Chapter 34 Appendix
Abbreviations Explanation
Time 1 trip of overcurrent stage 3 of high/middle/low voltage
H/M/LVSideOCSatge1Time3Trip
side
H/M/LVSideOCInrushBlk Overcurrent inrush blocking of high/middle/low voltage side
Time 1 trip of zero sequence stage 1 of high/middle/low
H/M/LVSide3I0Satge1Time1Trip
voltage side
Time 1 trip of zero sequence stage 2 of high/middle/low
H/M/LVSide3I0Satge1Time2Trip
voltage side
Time 1 trip of zero sequence stage 3 of high/middle/low
H/M/LVSide3I0Satge1Time3Trip
voltage side
Zero sequence inrush blocking of high/middle/low voltage
H/M/LVSide3I0InrushBlk
side
Time 1 trip of negative current stage 1 of high/middle/low
H/M/LVSideI2Satge1Time1Trip
voltage side
Time 1 trip of negative current stage 2 of high/middle/low
H/M/LVSideI2Satge1Time2Trip
voltage side
Time 1 trip of negative current stage 3 of high/middle/low
H/M/LVSideI2Satge1Time3Trip
voltage side
HVSideOVStage1Trip Trip of overvoltage stage 1 of high voltage side
294
Chapter 34 Appendix
Abbreviations Explanation
LVSideDZ BIErrAlarm Binary input error alarm of dead zone of low voltage side
295
Chapter 34 Appendix
Abbreviations Explanation
296
Chapter 34 Appendix
Abbreviations Explanation
297
Chapter 34 Appendix
Abbreviations Explanation
BIO CPUErr The CPU of binary input and output works improperly
298
Chapter 34 Appendix
Abbreviations Explanation
Abbreviations Explanation
299
Chapter 34 Appendix
Abbreviations Explanation
Abbreviations Explanation
300
Chapter 34 Appendix
CHN Chinese
ENG English
RUS Russian
Analog Analog
Measure Measurement
GOState GO state
301
Chapter 34 Appendix
Bay0 Bay 0
302
Chapter 34 Appendix
Contrast Contrast
Mode1 Mode 1
Mode2 Mode 2
303