Sei sulla pagina 1di 8

engineers newsletter providing insights for today’s

hvac system designer

turning air distribution upside down…


Underfloor Air Distribution
from the editor… Underfloor air distribution, or UAD in floor itself, because it’s from there that
One of the “fallouts” of technology is this publication, is of increasing interest the conditioned air is distributed.
increasingly savvy consumers. Armed to those who own or design office
with cellular phones, personal digital buildings. Some industry-watchers
assistants, and wireless laptops, we’re predict that as many as 35 percent of
accustomed to immediate gratification. tomorrow’s office buildings will include Floor Choices
We also know that the seemingly UAD systems.1 Others question its The architect or structural designer
infinite possibilities of digital controls practicality or readiness for widespread can choose between a traditional floor-
mean that we need not content application. on-slab; a slightly raised floor or a
ourselves with “one-size-fits-all” channeled slab to accommodate wiring;
products and services. A brief review of underfloor air or an access floor, which is elevated
distribution will help us identify the enough to house wiring plus other
Ironically, it’s standard practice to advantages and difficulties of applying utilities and equipment. See Figure 1.
design comfort systems that create these systems. Let’s start with the
thermally uniform indoor environments. With a traditional floor-on-slab, wiring
How long will it be before we can fine- for power and communications and
1 I. Krepchin, “Underfloor air systems gain
tune our workspaces to satisfy plumbing for sprinklers are usually
foothold in North America,” E Source
individual preferences? Not as long located in a plenum above a suspended
Report ER-01-1 (January 2001), Boulder,
as you might think. Low-pressure CO: Financial Times Energy, Inc. ceiling. Holes are drilled through the
underfloor air distribution represents
one way to give occupants greater
control over their immediate
environments. Figure 1. Types of Floor Systems

Applied elsewhere in the world for


2.5 ft
many years, underfloor air distribution ceiling plenum
(0.8 m)
ceiling plenum
has made its way into a small but ceiling plenum
growing number of major U.S. office
facilities. Will it become the next occupied space
occupied space
serious alternative to conventional occupied space
breathing zone
overhead methods of air delivery? breathing zone 9.0 ft
breathing zone (2.7 m)
Time will tell.
12.0 ft 12.5 ft 13.5 ft
(3.6 m) (3.8 m) (4.0 m)

wiring access
floor plenum

ceiling plenum ceiling plenum ceiling plenum

Floor-on-Slab Raised Floor Access Floor


0.5 ft (0.2 m) floor plenum 1.5 ft (0.4 m) floor plenum

© 2001 American Standard Inc. All rights reserved Volume 30, No. 4 ■
concrete slab to accommodate wires common; it is also expensive, Figure 3. Displacement Ventilation
for the floor above. especially for high-tech businesses. In
many cases, reducing churn-related 85˚F (29˚C)
Raised floors, which are elevated 3 to expenses such as rewiring costs can
6 inches (7.5 to 15 cm) above the slab, repay the additional investment of Requires high ceiling to limit
and channeled slabs provide electrical installing a non-traditional floor. “nose-to-toes” stratification to typically
5˚F (3˚C) 12 ft
and utility service on top of or within (3.6 m)
or more
the slab. Although these techniques
77˚F (25˚C) stratification layer
increase the initial cost of the floor,
they usually reduce wiring-related Air Distribution Options
expenses because slab drilling is Traditional overhead VAV distribution
unnecessary. (Figure 2) is used extensively in office 65˚F (18˚C)
73˚F (23˚C)
buildings. Supply ducts, VAV boxes,
With an access floor—which is 12 to and overhead diffusers—usually in an
18 inches (30 to 46 cm) or more above above-ceiling plenum formed by a
the slab—all wiring, utilities, and suspended ceiling—distribute cold,
equipment such as junction boxes, 50°F-to-55°F (10°C-to-13°C) supply air
outlet devices, and small terminal units to the spaces. This method of air the ceiling. Depending on the heat
are “sandwiched” between the access distribution produces relatively uniform sources, airflow rate, and ceiling height,
floor and the concrete slab below. temperatures throughout the space the air is 85°F (29°C) or more when it
because it induces significant mixing of enters the return openings near the
Like raised floors and channeled slabs, space air with supply air. Return air ceiling.
an access floor is more expensive to leaves the space at approximately room
install and can be partially subsidized by temperature. UAD systems represent a third choice,
simplifying the installation of wiring and “partial” displacement ventilation.
utilities. The premium for installing an Displacement ventilation (Figure 3) Floor-mounted diffusers release cool
access floor alone may be $5 USD /ft² or is commonly used in industrial spaces, 63°F-to-68°F (17°C-to-20°C) air, which
more, but the overall premium (which theaters, and other applications with induces local circulation and causes
varies widely2) may be only $3 USD /ft² very high ceilings. Diffusers, usually partial mixing and relatively uniform
when all of the initial costs for the mounted low in sidewalls, release temperatures from the floor to a height
building are considered. slow-moving, 65°F-to-72°F (18°C-to- of 3 to 6 ft (1 to 2 m). See Figure 4 and
22°C) air into the space; meanwhile, the inset below. Above that point, the
Why would a cost-conscious owner heat sources in the space induce local air temperatures stratify. At the return
or developer opt to pay the premium airflow from the floor toward the openings near the ceiling, the air
for an access floor? To reduce the ceiling. Along the way the air stratifies temperature ranges from 80°F to 85°F
expenses incurred by subsequent into temperature layers, which become (27°C to 29°C), depending on heat
changes in the office layout. Surveys progressively warmer from the floor to sources, airflow, and ceiling height.
show that more than 40 percent of the
occupants in modern office buildings
relocate at least once each year.3 Figure 2. Overhead VAV Distribution
Annual occupant relocation, quantified
as “churn” rate, is increasingly Partial Displacement Ventilation
ceiling plenum VAV
terminal
This EN only discusses floor-mounted
Coanda effect 55˚F
for mixing (13˚C) diffusers; however, furniture-mounted
12 ft diffusers can also be used to implement
(3.6 m) partial displacement ventilation. Such
2 F. Bauman and T. Webster, “Outlook for uniform
space temperature, systems, which are described as task/
underfloor air distribution,” ASHRAE 75˚F (24˚C) ambient conditioning (TAC) systems,
Journal 43 no. 6 (June 2001): 18–27. deliver supply air directly to the occupant/
task area as well as to the ambient space.
3 International Facility Management TAC systems are similar to UAD systems
Association (www.ifma.org), Benchmarks and deliver many of the same benefits. ■
I, II, III (1991, 1994, 1997). wiring access

■ 2 Trane Engineers Newsletter — Vol. 30, No. 4


Figure 4. “Partial” Displacement central air handler delivers primary air Rearranging the walls of private offices
Ventilation (Underfloor Air Distribution) to the floor plenum, pressurizing it to is another matter. In this situation,
approximately 0.05 to 0.10 in. wc underfloor air distribution avoids the
(12 to 25 Pa) above space pressure. expense of moving and rebalancing
ceiling plenum
Passive floor-mounted diffusers, either overhead ducts and diffusers.
82˚F (28˚C) manually or automatically adjusted,
stratification layer deliver the plenum air to the occupied Reduced floor-to-floor height.
space. Often cited as an initial cost benefit of
12 ft
uniformly (3.6 m) underfloor air distribution, removing the
75˚F (24˚C) or less
The next section evaluates pressurized- supply ducts, terminals, and diffusers
plenum UAD systems serving spaces from the ceiling can reduce overall
65˚F (18˚C) diffuser with relatively constant loads. (For this plenum height, and may reduce slab-to-
article, we chose to ignore underfloor slab and total building height…perhaps
air distribution in spaces with widely by as much as 10 percent.2
varying loads—perimeter zones and
conference rooms, for example— Improved comfort. A combination
because of the complexity of these of cold plenum air, low-induction floor-
applications.) mounted diffusers, and reduced airflow
can cause excessive (uncomfortable)
stratification. However, direct control of
Approaches to UAD Design supply airflow (a hallmark of most UAD
Let’s take a closer look at access floor Potential Advantages systems) increases the degree of
systems with underfloor air distribution. Some advocates claim that comfort that occupants perceive. 4
Designers usually pick one of two pressurized-plenum UAD systems
approaches to distribute air from an offer several advantages over traditional To assure that a UAD application
access-floor system: neutral-plenum or overhead VAV systems. Following is a provides the promised improvements
pressurized-plenum. discussion of the benefits most in individual thermal comfort, the
commonly associated with these design of the system must properly
Note: Due to high initial and operational advantages. account for all relevant parameters,
costs, most designers avoid a third including vertical load distribution,
possible approach that ducts primary air Lower churn-related life-cycle costs. diffuser throw, and floor temperature.
to each floor-mounted diffuser. Most of the savings related to office
reconfiguration result from the access Improved productivity. As implied
In neutral-plenum designs, a central floor, which lowers rewiring costs above, people express greater
air handler delivers conditioned primary regardless of how the air is distributed. satisfaction with thermal comfort when
air to the floor plenum. From there, the Can underfloor air distribution trim they can control their immediate
air is delivered to the space by either of additional expense from “churn”? The environment. Adjustable, floor-mounted
two types of floor-mounted diffusers: answer depends on the type of diffusers contribute to occupant
“passive” diffusers that are connected relocation. satisfaction because they allow at least
to fan-powered terminals or “active” some adjustment for individual
(fan-powered) diffusers. Although the Cubicle rearrangements in UAD preferences. Reducing or eliminating
local fans increase the cost of installing applications usually require the the distraction of thermal discomfort in
and operating the system, they may be relocation of floor-mounted diffusers. a space increases the productivity of
unavoidable if a leaky access floor or By contrast, rearranging cubicles in a those who occupy it.
building envelope makes it difficult to space with overhead VAV distribution
pressurize the plenum. seldom (if ever) affects the placement
of ceiling diffusers. In terms of air
When excessive leakage is not a distribution alone, then, UAD may
problem, a pressurized-plenum actually increase the cost of cubicle- 4 D.P. Wyon, “Individual microclimate
design can be used. In this case, a wall “churn.” control: required range, probable benefits,
and current feasibility,” Proceedings of
Indoor Air 96, no. 1 (1996): 1067–1072.

“providing insights for today’s HVAC system designer” 3 ■


Improved indoor air quality. Indoor In overhead VAV applications, mixing outdoor air for ventilation, then it
air quality (IAQ) relates to contaminant disperses contaminants throughout follows that the building ventilation
concentrations in the breathing zone. the space. In UAD applications, system can condition less outdoor air
Some studies report lower breathing- contaminants “collect” near the ceiling and, therefore, will require less heating
zone concentrations for UAD systems outside of the breathing zone, so and cooling capacity. How much less?
than for overhead VAV systems.5 Here’s occupants breathe “cleaner” air. Given That depends. As the example in
why… the higher air-change effectiveness “Effect of Air Distribution on Ventilation
(E ac ) of UAD spaces, proper space Airflow” demonstrates, when air-
ventilation requires less outdoor airflow change effectiveness increases from
5 D. Faulkner, W.J. Fisk, and D.P. Sullivan, at the diffusers. (See “Air-Change 0.95 (VAV) to 1.10 (UAD), system
“Indoor airflow and pollutant removal in a Effectiveness, Eac” on page 5.) ventilation efficiency, E, at design
room with floor-based task ventilation: conditions also improves—from 0.966
results of additional experiments,” Building Reduced outdoor airflow. If better (VAV) to 0.991 (UAD), in this case.
and Environment 30, no. 3 (1995): 323–
air-change effectiveness in UAD spaces
332.
means that each diffuser needs less Although the UAD system reduced
both outdoor airflow and, therefore, the
installed capacity required at the plant,
the reductions are significantly less
Effect of Air Distribution on Ventilation Airflow than one might expect. In multiple-
A simple example can help us determine Solving for system ventilation efficiency space mixed-air applications, improving
how underfloor air distribution (UAD) (E = 1 + X – Z) and total outdoor airflow, the air-change effectiveness in the
affects the amount of outdoor air that Vot = ∑Vo /(1 + X – Z), we find that the
space does not yield an equal
must be brought into the building for overhead VAV system requires 466 cfm
proper ventilation, as compared to while the UAD system requires only improvement in system ventilation
overhead VAVdistribution. Assume that a 454 cfm…about 2.6 percent less outdoor efficiency (or airflow reduction) at the
three-space system is served by a central air than the VAV system. outdoor air intake.
air handler. The system must comply with
the “multiple-space” equation (6-1) from System-Level
VAV UAD Note: System ventilation efficiency
ASHRAE Standard 62–1999. Each space Characteristics
needs 1,000 cfm of supply air at the design improves for UAD at design conditions,
Average breathing-zone
condition, and the per-space outdoor air ventilation requirement, X 0.150 0.150 which can reduce the installed capacity
requirements are 125 cfm, 150 cfm, and Critical-space ventilation of the heating/cooling plant. For
175 cfm, respectively. fraction, Z 0.184 0.159 overhead VAV distribution, system
Ventilation efficiency, E 0.966 0.991 ventilation efficiency improves at part
Determining how much outdoor air
Total outdoor airflow, Vot 466 cfm 454 cfm load, which can reduce the required
must be brought into the system entails
finding the diffuser (not breathing-zone) operating capacity if the system is
ventilation fraction, z = Vo /(Eac × Vs ), for It’s interesting to note that although equipped with proper ventilation-reset
each space, and then calculating the underfloor air distribution improves the controls.
critical-space ventilation fraction air-change effectiveness in each space by
(Z = largest z) as well as the average 16 percent (in this example), the system
ventilation fraction, X = ∑Vo /∑Vs , for the ventilation efficiency and total outdoor Less fan horsepower. If we assume
system. airflow required at the outdoor air intake that UAD and overhead VAV systems
only drop by 2.6 percent. The slight require the same supply airflow at
Note: The air-change effectiveness of reduction of system-level outdoor airflow design conditions (see “Airflow” on
the space does not affect the average makes sense when we remember that any
page 5), then the absence of supply
ventilation fraction for the system, which contaminants that escape the breathing
is based on breathing-zone needs. zone recirculate at the air handler. ■ ducts, terminals, and runouts in a
pressurized-plenum UAD system
Per-Space Ventilation Characteristics for Example Three-Space System reduces the external static pressure on
Air-Change Effectiveness, the supply fan. Less external static
Supply Outdoor
Eac Ventilation Fraction, z pressure results in the selection of a
Airflow Vs , Airflow Vo ,
cfm cfm VAV UAD VAV UAD smaller motor (lower initial cost)…but
Space 1 1,000 125 0.95 1.10 0.132 0.114 does it also mean that UAD requires
Space 2 1,000 150 0.95 1.10 0.158 0.136 less horsepower (costs less to operate)
Space 3 1,000 175 0.95 1.10 0.184 0.159 than overhead VAV distribution?
Totals 3,000 450

■ 4 Trane Engineers Newsletter — Vol. 30, No. 4


For most climates, however, saturated designers will risk reducing the
Air-Change Effectiveness, Eac 65°F DB (18°C) supply air would installed capacity of the cooling plant.
The comparatively higher air-change unacceptably raise the relative humidity
effectiveness of a space that is served by in the space. Therefore, when a cold More hours of economizer cooling.
UAD rather than an overhead VAV system coil provides dehumidification, the When outdoor air enthalpy is less than
reduces the amount of outdoor air that
chilled water in most climates must be return air enthalpy, less energy is
must be brought into the building.
Consider the example below. cold enough to produce a supply-air required to mechanically cool outdoor
dew point of 58°F to 60°F (14°C to air than mixed air. Return air is warmer
A space requires 150 cfm (75 L/s) of 15°C), greatly reducing the anticipated in UAD systems than in VAV systems—
outdoor air within the breathing zone. If COP improvement. perhaps 80°F (27°C) versus 77°F
we assume an air-change effectiveness of
(25°C) at economizer conditions.
0.95 for overhead VAV distribution, then
150/0.95 = 158 cfm (75/0.95 = 79 L/s) of In other words, the warmer supply air Therefore, the changeover from
outdoor air must reach the diffusers. With temperatures of UAD systems can “mechanical cooling with minimum
underfloor air distribution and an air- improve the operating efficiency of outdoor air” to “mechanical cooling
change effectiveness of 1.10, the same chillers applied in dry climates. with maximum outdoor air” occurs at
space requires only 150/1.10 = 136 cfm
However, this advantage diminishes warmer outdoor conditions, reducing
(75/1.10 = 68 L/s) of outdoor air at the
diffusers. significantly in climates that routinely the cooling coil load and increasing
require mixed-air dehumidification (that economizer hours slightly during warm
Although 14 percent less outdoor air is is, cold water temperatures) at the weather.
needed at UAD diffusers than at overhead cooling coil.
VAV diffusers, this savings does not pass
UAD systems also supply warmer air
entirely to the outdoor air intake. To find
out why, see “Effect of Air Distribution on Note: Using a separate unit for than VAV systems—perhaps 65°F
Ventilation Airflow” on page 4. ■ dehumidification (an active desiccant (18°C) versus 55°F (13°C). So, the
dehumidifier, for example) allows the changeover from “mechanical cooling
chilled water temperature to rise along with maximum outdoor air” to
Many UAD systems supply a relatively with the chiller COP…but perhaps at “modulated economizer cooling”
constant volume of airflow to both the expense of overall system occurs at a warmer outdoor
interior and perimeter zones. According efficiency. Again, careful analysis is temperature, reducing the hours of
to the fan laws, a 50-percent reduction needed to assess the effects of such mechanical cooling operation during
in external static pressure (typical of a design. cool weather.
UAD) yields the same brake-
horsepower effect as a 30-percent Reduced electrical demand. In UAD
reduction in airflow. VAV systems that applications, the floor slab forms part of
Airflow
serve both types of zones often the supply duct for one floor and part of
Vertical distribution of the cooling loads
operate for many hours at less than the return duct for the floor below.
within the occupied space determines
70-percent of design airflow. Which Therefore, the thermal mass of the whether the required airflow for UAD
system actually uses less fan energy? floor slab can store heat (cooling load) systems is more or less than for overhead
Learning the answer requires a careful, during daytime hours and release it at VAV distribution. Lacking better load-
case-by-case analysis of part-load night; see “Thermal Storage” on modeling tools, most designers assume
that both types of systems require the
operation. page 6.
same supply airflow at the design cooling
condition. In effect, they’re assuming that
Improved chiller efficiency. In arid With proper controls and sufficient slab only 50 percent of the cooling load enters
climates, 65°F DB (18°C) supply air mass, lower daytime cooling peaks the “breathing zone.” Therefore, a
may be dry enough during most hours may permit smaller cooling equipment 50-percent reduction of the supply-to-
space temperature difference (typically
of operation to avoid elevating the and—when coupled with fan-
from 20°F to 10°F) can be tolerated
relative humidity in the space. If so, horsepower savings—may reduce without changing the supply airflow.
then raising the chilled water daytime electrical demand peaks and
temperature from 45°F (7°C) to 55°F charges. Unfortunately, without After researchers establish comfortable
(13°C), for example, will improve the dependable models to predict the stratification limits and devise tools to aid
air-distribution design, some UAD systems
chiller’s Coefficient of Performance slab’s thermal performance or a wealth
may actually be found to require less
or COP. of design experience, it is unlikely that supply airflow than overhead
alternatives. ■

“providing insights for today’s HVAC system designer” 5 ■


Finally, because UAD systems usually Stated simply, a UAD system can
deliver roughly constant airflow to decrease the cooling coil load during Thermal Storage
interior spaces, the change from warm weather and decrease the hours Although sometimes described as a
“modulated economizer cooling” to of mechanical cooling operation during potential “cool-storage device,” “heat-
“heating with minimum outdoor air” cool weather (especially in dry storage device” may be a more apt
descriptor for the floor slab. That’s because
may occur at a warmer or cooler climates). During cold weather,
the average temperature of the slab rises
outdoor temperature (depending on the however, underfloor air distribution may during the day as it absorbs and stores
building cooling load) than in VAV increase heating energy use and/or heat from internal cooling loads.
systems. In other words, heating hours hours of heating operation, depending
may either increase or decrease during on building loads. Operating a UAD system at night cools the
slab by allowing it to reject the stored
cold weather. Why? Interior zones
heat. This practice requires careful
usually do not require heating during Ultimately, local weather and load consideration, however. Cooling the slab
occupied hours. Therefore, while conditions, together with system below the “occupied” temperature may
“heating with minimum outdoor air,” control schemes, will determine how necessitate morning warm-up, which can
the heating coil warms the mixed air to much extra mechanical cooling energy be difficult from under the floor; it can also
greatly diminish thermal storage benefits.
the current cooling setpoint. UAD saves and how much extra (if any)
Furthermore, if the slab mass reaches
heating energy it adds. Once again, thermal equilibrium while the space is
Because UAD systems usually require careful analysis is needed on a job-by- occupied (that is, if the slab stops
warmer supply air, they may actually job basis to quantify the operating cost absorbing heat at 2 p.m., for example),
use more heating energy for interior savings. then the cooling load shift is not sufficient
to allow a reduction of the installed
spaces than VAV systems…even if the
capacity of the cooling plant. ■
hours of heating operation decrease.

Growing Pains
Naturally, the relative newness of Perimeter spaces. UAD systems can
Economizer Considerations underfloor air distribution presents readily accommodate thermally stable
It’s important to remember that certain difficulties for owners and interior spaces, but spaces with widely
economizer cooling removes only the designers who wish to apply it variable loads (conference rooms and
sensible cooling load in the space. In “non- successfully. perimeter spaces, for example) pose a
dry” (most) climates, the latent load must significant design challenge. Solutions
be removed, too…even when the outdoor
Design tools. Neither the guidelines ranging from series fan-powered VAV to
air temperature drops below the supply-
air target. for traditional air-distribution systems changeover-bypass VAV to variable-
nor existing computer-aided design speed fan–coils have been used with
If system controls sense and directly tools address partially stratified spaces. varying degrees of success. The “best”
limit relative humidity in the occupied What’s missing? solution may be something else
space, then underfloor air distribution
altogether and, in any case, will depend
requires approximately the same cooling
capacity as overhead VAV distribution. ■ A good room–stratification model upon architectural considerations (for
Furthermore, UAD may also require more to analyze the effects of supply example, window/wall construction and
reheat energy to avoid overcooling during airflow, temperature, diffuser access to vertical riser shafts).
dehumidification. performance, and ceiling height
Central systems. Should each floor
One final caveat: If your system design ■ A good load-prediction tool to
uses a return-air bypass configuration to have one or more air handlers, or
study the vertical distribution of
provide indirect dehumidification without should a central air handler provide
cooling and heating loads within the
sensing (and limiting) relative humidity, conditioned air to a shaft with “takeoff”
then return air will not be available for space and to determine the required
dampers on each floor? Perhaps the
“reheat” during “mechanical cooling with supply airflow
central air handler should provide
maximum outdoor air.” (Dehumidification
in constant-volume systems was discussed ■ A system–performance model 100-percent outdoor air to fan-powered
in a previous Engineers Newsletter, volume (one that includes various plenum mixing boxes on each floor. If so,
29–4. You can find it in our online archive configurations, slab dynamics, and should the central unit merely cool the
of newsletters in the commercial section flexible control schemes) to analyze air, or should it also dehumidify the air
of www.trane.com.) ■
and compare system economics

■ 6 Trane Engineers Newsletter — Vol. 30, No. 4


to mitigate the interior latent load? designers, installers, and operators ■ Except for passive floor-mounted
These questions may be easy to raise their estimates to cover diffusers, manufacturers offer only a
answer for some applications and unforeseen contingencies associated limited selection of UAD equipment
impossible for others. One thing is with the unfamiliar UAD technology. and systems.
certain: Evaluating the alternatives
■ Will spilled coffee and dirt in
requires good performance models. Will operating cost savings, including
the floor plenum affect indoor air
the cost of “churn,” provide rapid
quality?
Controls. Minimizing temperature payback for any initial premium? A fair
swings at “head” level while comparison of life-cycle costs requires ■ Will the occupants of buildings with
controlling “nose-to-toes” temperature an economic analysis tool that access floors and UAD systems
stratification is critical for thermal accurately models both UAD and remain satisfied after five or ten
comfort. The ability to model a stratified conventional HVAC systems and their years of operation?
space would let designers compare the controls.
effects of constant- versus variable- Time and attention may eventually
temperature supply air, constant versus Retrofit limitations. Existing buildings resolve these “growing pains,” and
variable supply airflow, neutral versus account for more than half of HVAC perhaps significantly alter our existing
pressurized plenums, and so on. equipment sales. Although possible, it’s paradigms for air distribution. Once
not easy to install an access floor and these “growing pains” are
Economizer changeover control and UAD system in an existing building. understood—and after designs for
supply-air-temperature reset must be UAD systems are proven,
coordinated to maximize economizer Other uncertainties… implemented, commissioned, and
hours without causing high levels of ■ Standards and codes assume well-
properly operated—we may find that
relative humidity in the space or mixed spaces and ceiling plenums. UAD systems are a viable and practical
requiring excessive reheat. The thermal UAD shifts the traditional system alternative for specific applications. We
mass in UAD applications may paradigm for code authorities as well may also find that many UAD
significantly alter the characteristics as for designers. Aspects of “advantages” result in real benefits for
and requirements for night setback and underfloor air distribution may building owners and occupants.
morning warm-up operation. Operable conflict with existing code
windows, which are increasingly requirements.
popular, create another design
perplexity: defining a control strategy
UAD Research Initiatives Closing Thoughts
that effectively accommodates hybrid
At the University of California in Should you raise the floor merely
(mechanical plus passive) ventilation
Berkeley, the Center for the Built to accommodate underfloor air
systems. Control challenges abound.
Environment (CBE) conducts research distribution?
related to underfloor air distribution for
Installed cost. Does a building with industry partners and several government
Probably not. It is seldom economical
a UAD system cost more or less than departments, as well as for the American
Society of Heating, Refrigerating, and Air- to spend many first-cost dollars on an
a building with a conventional air
Conditioning Engineers, Inc. (ASHRAE). access floor to save only a few first-
distribution system? Although most
With ASHRAE sponsorship, the CBE is cost or operating-cost dollars on the air
designers believe that buildings with also developing the ASHRAE Design distribution system.
UAD systems demand a first-cost Guide for Task/Ambient Conditioning and
premium, study results to date are Underfloor Air Distribution Systems
(1064-RP). For more details about UAD Why use underfloor rather than
inconclusive. Obtaining true cost
technology and the CBE’s research overhead air distribution in an office?
comparisons is difficult because many
programs, visit www.cbe.berkeley.edu/
underfloorair/. ■ If the plan includes an access floor
to reduce the cost of churn, UAD
ASHRAE and the Air-Conditioning and
Refrigeration Technology Institute (ARTI) systems can help subsidize the cost
also sponsor UAD research by Carnegie- added by the flooring. They typically
Mellon University in Pittsburgh. The require less ductwork and certainly
university’s ongoing demonstration project less “above-ceiling” height than
serves as a test-bed for adaptations of
overhead systems. This trait often
underfloor air distribution. ■

“providing insights for today’s HVAC system designer” 7 ■


avoids the increase in slab-to-slab studies and through operating
height that might otherwise result experience in both demonstration
from raising the floor. projects and actual buildings. (See
“UAD Research Initiatives” on page 7.)
■ In some climates, UAD systems
may significantly reduce operating
From these initiatives, we can expect
costs.
to resolve many of the uncertainties You can find this and other issues
■ Occupant-controlled airflow identified earlier in this article…and to of the Engineers Newsletter in the
seems to improve both comfort and benefit from the development of commercial section of www.trane.com.
productivity. design guidelines and tools that will To comment, send a note to Trane,
help us use underfloor air distribution to Engineers Newsletter Editor, 3600
■ Architectural constraints imposed
best advantage. ■ Pammel Creek Road, La Crosse, WI
by some building designs may
54601-7599, or e-mail us at
necessitate underfloor air
By Dennis Stanke, staff applications comfort@trane.com.
distribution.
engineer, and Brenda Bradley,
information designer, Trane.
What lies ahead? With the help of
university researchers, the HVAC
industry is expanding its knowledge of
underfloor air distribution through

… with these live telecasts hosted by your


local Trane office:

An American Standard Company


www.trane.com

For more information, contact your Trane believes the facts and suggestions presented here to be accurate. However,
local district office or e-mail us at final design and application decisions are your responsibility. Trane disclaims
comfort@trane.com
any responsibility for actions taken on the material presented.

■ 8 ADM-APN001-EN

Potrebbero piacerti anche