Sei sulla pagina 1di 4

REACTIVE POWER REGULATOR

S5-60D, S5-120D

TAIK ELECTRIC
REACTIVE POWER REGULATOR S5-60D, S5-120D

■ FEATURES
  ● S5-60D for 6 steps regulator, S5-120D for   ● Over voltage protected is available
12 steps regulator   ● Setting of individual parameters including
  ● Digital indication of power factor and speci- targer power factor, switching delay time,
fied installation data limit of switching steps, etc
  ● Automatic self-adjustment for C/K value and   ● Outside dimension according to DIN stan-
operation frequency 50 or 60 Hz dard 144 x 144 mm
  ● Nine types of switching programs


⑥ ②

⑧ ⑦

① MANUAL OPERATION ⑤ POWER FACTOR VALUE


② SWITCHING ON CAPACITOR ⑥ ENERGIZED CAPACITOR STEPS
③ SWITCHING OFF CAPACITOR ⑦ KEPADS
④ FAULT ALARM ⑧ FAULT STATUS
REACTIVE POWER REGULATOR S5-60D, S5-120D

■ SPECIFICATION
Operating voltage range : AC 220V (240V) ± 15% & AC 380V (415V) ± 15%
Voltage burden : ≤ 4.5 VA (S5-60D), ≤ 7 VA (S5-120D)
Input current range : AC 0.05 ~ 5A, Max. 6A
Current burden : ≤ 0.5 VA
Power factor display : Digital display, red LED, 14.2 mmH, 0.01 PF resolution
Power factor setting range : Cap. 0.95 ~ Ind. 0.85 PF. The default value (0.97) set by factory
Power factor setting mode : Setting value to 1.00 PF. or setting point mode
C/K setting range : Auto/Man adjustment for C/K value or manual setting for C/K value
(0.01 ~ 2.40)
Switching delay time : 10 ~ 240 sec. delay time 30 sec. is set on delivery from factory
Number of steps : 3 ~ 6 steps for S5-60D, 3 ~ 12 steps for S5-120D
Over voltage setting : 110 ~ 130%, 120% is set on delivery from factory
Relay contact capacity : Max. AC 380V 5A, typical AC 220V 5A
Operating temperature : 0 ~ 60°C
Storage temperature : -10 ~ 70°C
Max. humidity : 90%
Dielectric strength : AC 2KV 60Hz 1 minute, input/output/case
Withstanding impulse voltage : IEC 61000-4-5
Electrical transient in burst : IEC 61000-4-4
Electrostatic discharge : IEC 61000-4-2
Voltage dips & interrups : IEC 61000-4-11
Connection : Plug-in terminal block
Weight : About 0.85 kgs for S5-60D, 1 kg for S5-120D

● TYPE OF SWITCHING PROGRAM

Switching program Alternate Circularity Switching program Alternate Circularity

1. 1:1:1:1:1 : ..... 1:1:..... 6. 1:1:2:4:4:..... 1:1 4: 4 : . . . . .


2. 1:2:2:2:2 : ..... 2:2:..... 7. 1:1:2:4:8:..... 1:1 8: 8 : . . . . .
3. 1:2:4:4:4 : ..... 4:4:..... 8. 1:1:2:2:4:..... 1:1, 2:2 4: 4 : . . . . .
4. 1:2:4:8:8 : ..... 8:8:..... 9. 1:1:1:1:1:.....
5. 1:1:2:2:2 : ..... 1:1 : 2:2:.....

● C/K VALUE SETTING

IC Example:
C/K = IC : Phae Current
K
K : CT Ratio First capacitor is 3φ 400V, 200KVar
Var Var: First step capacitor CT Ratio: 300A / 5A
IC =
V x √3 IC = 20000/400 x √3 = 28.86 (A)
K = 300A / 5A = 60
C/K = IC/K = 28.86 / 60 = 0.48
REACTIVE POWER REGULATOR S5-60D, S5-120D

■ CONNECTION DIAGRAM
S5-60D

S5-120D

■ OUTSIDE DIMENSION (mm)

TAIK ELECTRIC CO., LTD.


4TH FL., NO.3, ALLEY 11, LANE 327, CHUNG SHAN RD.,
SEC. 2, CHUNG HO SHIH, TAIPEI HSIEN, TAIWAN, R.O.C.
TEL: 886-2-22426825 FAX: 886-2-22426827
http://www.taik.com.tw E-mail: taikco@ms15.hinet.net FM 40649