Sei sulla pagina 1di 3

SCHEDULE OF LOADS

Circuit SIZE OF OPD


Load No. of Outlets VOLTS AMPS WATTS
No. RATING
CO LO SWITCHES CONDUCTOR CONDUIT
2 - 2.00mm² 15mm ø 15AT, 2P
- 16 9 240 0.82 196
1 Lighting THHN Cu PVC CB
Small 2 - 2.00mm² 15mm ø 15AT, 2P
17 - - 240 12.75 3060
2 Appliance THHN Cu PVC CB
Washing 2 - 2.00mm² 15mm ø 15AT, 2P
1 - - 240 4.17 1000
3 Machine THHN Cu PVC CB
2 - 2.00mm² 15mm ø 15AT, 2P
1 - - 240 2.5 600
4 Refrigerator THHN Cu PVC CB
Electric 2 - 2.00mm² 15mm ø 15AT, 2P
1 - - 240 12 2880
5 Range THHN Cu PVC CB
Air
2 - 2.00mm² 15mm ø 30AT, 2P
Conditioning 1 - - 240 12.5 2875
THHN Cu PVC CB
6 Unit
Air
2 - 2.00mm² 15mm ø 30AT, 2P
Conditioning 1 - - 240 12.5 2875
THHN Cu PVC CB
7 Unit
20AT, 2P
1 - - 240 20 4600 - -
8 Spare CB
20AT, 2P
1 - - 240 20 4600 - -
9 Spare CB
20AT, 2P
1 - - 240 20 4600 - -
10 Spare CB
Branch Circuit Computations

Branch Circuit No. 1 Branch Circuit No. 5

Load : 8W LED Light Load : Electric Range


No. of Outlets: 12 No. of Outlets: 1
Wattage: 8 x 12 = 96W Wattage: 3600W
Branch Circuit Current: 96/240 = 0.4A Demand Factor: 80%
Branch Circuit Current: (3600 x 0.8)/240 = 12A
Load : 25W Fluorescent Lamp Size of Wire: Use 2 – 2.00 mm2 THHN
No. of Outlets: 4 Size of Conduit: Use 15 mm diameter PVC
Wattage: 25 x 4 = 100W Size of OPD: 15AT, 2P CB
Branch Circuit Current: 100/240 = 0.42A
Branch Circuit No. 6
Total Outlets: 12 + 4 = 16
Total Wattage: 96 + 100 = 196W Load : Air Conditioning Unit
Total Branch Current: 0.4 + 0.42 = 0.82 A No. of Outlets: 1
Size of Wire: Use 2 – 2.00 mm2 THHN Rating: 1.5HP, 10A, 240V
Size of Conduit: Use 15 mm diameter PVC Branch Circuit Current: 1.25 x 10 = 12.50A
Size of OPD: 15AT, 2P CB Size of Wire: Use 2 – 2.00 mm2 THHN
Size of Conduit: Use 15 mm diameter PVC
Branch Circuit No. 2 Maximum Setting of OPD: 250%x10 = 25A
Size of OPD: 30AT, 2P CB
Load : Small Appliance Load
No. of Outlets: 17 Branch Circuit No. 7
Wattage: 17 x 180 = 3060W
Branch Circuit Current: 3060/240 = 12.75A Load : Air Conditioning Unit
Size of Wire: Use 2 – 2.00 mm2 THHN No. of Outlets: 1
Size of Conduit: Use 15 mm diameter PVC Rating: 1.5HP, 10A, 240V
Size of OPD: 15AT, 2P CB Branch Circuit Current: 1.25 x 10 = 12.50A
Size of Wire: Use 2 – 2.00 mm2 THHN
Branch Circuit No. 3 Size of Conduit: Use 15 mm diameter PVC
Maximum Setting of OPD: 250%x10 = 25A
Load : Washing Machine Size of OPD: 30AT, 2P CB
No. of Outlets: 1
Wattage: 1000W Branch Circuit No. 8
Branch Circuit Current: 1000/240 = 4.17A
Size of Wire: Use 2 – 2.00 mm2 THHN Load: Spare
Size of Conduit: Use 15 mm diameter PVC Size of OPD: 20AT, 2P CB
Size of OPD: 15AT, 2P CB
Branch Circuit No. 9
Branch Circuit No. 4
Load: Spare
Load : Refrigerator Size of OPD: 20AT, 2P CB
No. of Outlets: 1
Wattage: 600W Branch Circuit No. 10
Branch Circuit Current: 600/240 = 2.5A
Size of Wire: Use 2 – 2.00 mm2 THHN Load: Spare
Size of Conduit: Use 15 mm diameter PVC Size of OPD: 20AT, 2P CB
Size of OPD: 15AT, 2P CB
Service Entrance Computations Service Equipment

General Lighting Load and General Use Receptacle A. Maximum Current Rating of Protective
Device, with
Area: 14.5m x 10 m = 145 m2 1. Non – Time Delay Fuse

145m2 x 24VA/ m2 = 3480VA [3000 + 1589 + 2880 + 300%(10 x 240) +


(10 x 230)]/240 = 70.70 A
Small Appliance Load
2. Inverse – Time Circuit Breaker
17 outlets x 180V = 3060VA
[3000 + 1589 + 2880 + 250%(10 x 240) +
Laundry Circuit (10 x 230)]/240 = 65.70A

One 4.35A circuit @1000VA/circuit = 1000VA B. Service Equipment Rating in Case of


Underground Service
Subtotal = 3480 + 3060 + 1000 = 7540VA
1. Use one 100A, 2PST, 250V safety switch
Application of Demand Factors with two 80A renewable fuses or

First 3000VA at 100% DF = 3000 x 1 = 3000VA 2. Use one 70AT, 2 pole, 240V, molded
Next 4540VA at 35% DF = 4540 x 0.35 = 1589VA case circuit breaker

Other Loads

Electric Range Load

One 3.6kW Range at 80% DF = 3600 x 0.8 = 2880VA

Air Conditioning Unit Load

Two 1.5HP, 10A ACU

[(10 + 10 + (0.25 x 10)] x 240 = 5400VA

Total Computed Load

3000 + 1589 + 2880 + 5400 = 12869VA

Total Computed Current

12869/240 = 53.62A

Service Entrance Conductors

Use 2 – 14 mm2 THHN Cu Wires


Use 20 mm diameter RCS