Andean Power S.A.

CARHUAC HYDROPOWER PROJECT, PERU

T/L from-to HPP Carhuac - SS Callahuanca 60 kV


Rated voltage VLL (kV) 60
Network frequency f (Hz) 60
Conductor type AAAC 150 mm2 (19 strands, 12/6/1)
Material of conductor (Al/Cu) Al
Conductors per bundle b 1
Bundle diameter db (mm)
Phase spacing dab (m) 7.00 dbc (m) 6.60 dca (m) 6.60
Line length L (km) 25.4

AC resistance at 75 oC RACa ( /km) 0.2867 RAC ( ) 7.282 Conditions for short-line Ok


+
Inductive reactance XLa ( /km) 0.5271 XL ( ) 13.388 VLL (kV) < 110 L (km) < 50.0

MODEL VOLTAGES, CURRENTS AND POWER

line-neutral receiving-end voltage (phase-angle ref.) = 100% voltage regulation

line-neutral transmitting-end voltage T/L = = 100% transmission line efficiency

inductive receiving-end load current 1-phase receiving-end power

= 1-phase transmitting-end
cos power
= + =3 active power loss

line-neutral no-load receiving-end voltage =3 reactive power loss

voltage drop active power supply

cos sin reactive power supply

VOLTAGE REGULATION
Active power load P2 (MW) 19.1 3-phase receiving-end power P1ph2 (MW) 6.4 1-phase receiving-end power
Reactive power load Q2 (Mvar) 9.0 3-phase receiving-end power Q1ph2 (Mvar) 3.0 1-phase receiving-end power
Load power factor cos 2 0.90 receiving-end power factor I2 (A) 203.2 load current

Receiving-end voltage VLL2 (kV) 60.0 line-line voltage (rated voltage) VLN2 (kV) 34.6 line-neutral voltage
Transmitting-end voltage VLL1 (kV) 64.3 line-line voltage VLN1 (kV) 37.1 line-neutral voltage
Line voltage drop V (kV) 1.83 line voltage regulation Vreg (%) 3.05 Ok Vreg (%) 5.0

POWER LOSSES
Active power loss P (MW) 0.90 3-phase power P1ph (MW) 0.30 1-phase power
Reactive power loss Q (Mvar) 1.66 3-phase power Q1ph (Mvar) 0.55 1-phase power
Active power supply P1 (MW) 20.0 3-phase transmitting-end power P1ph1 (MW) 6.7 1-phase transmitting-end power
Reactive power supply Q1 (Mvar) 10.7 3-phase transmitting-end power Q1ph1 (Mvar) 3.6 1-phase transmitting-end power
Supply power factor cos 1 0.88 transmitting-end power factor I1 (A) 203.2 supply current
T/L efficiency T/L (%) 95.5

ENERGY LOSSES
Plant factor PF (%) 70.6
Active energy loss Ea (GWh) 5.58 3-phase energy E1pha (GWh) 1.86 1-phase energy

AC SHORT TRANSMISSION LINE MODEL


0 25.07.2014 P. Iturri P. Iturri
Page 1 of 1 441 Calculation Sheet Designed: 05.05.2014 Copyright © Pöyry 2014 Rev. Date Project Eng. Dept. Head