Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
ABSTRACT
Current Transformers (CTs) have limited performance in transforming primary current during fault or
transient condition. This limitation induces errors on the secondary side and yields false current. On the
other hand, the relay’s measurement technique fallacy in estimating the current phasor/value also
contributes to the false current and surely affects relay’s performance. This paper provides a
comprehensive comparison of numeric differential and restricted earth fault (REF) relay current
measurement technique. Methods compared are measurement without elimination of DC and harmonic
components (true RMS) and the one with the elimination of DC and harmonic components (full-cycle
DFT and full-cycle cosine filter). Simulation is conducted by utilizing real-case fault records from sites
with software analysis. Simulation results have indicated that the elimination of DC and harmonic
component significantly enhanced the reliability of differential protection during external fault and REF
protection during an event of inrush.
Keywords: DC Component, Differential Protection, Harmonics, REF Protection, DFT, Cosine filter, True
RMS.
I. INTRODUCTION
Differential and REF protections are commonly used as main protection of transformer windings. As we
know, these protections only cover the area within the CT measurement points which connected into
relay inputs and will operate instantaneously when fault occurs at their coverage zone. In addition,
differential and REF protections also required to be reliable, in other words no room for maloperation.
Currently, numerical differential relays are widely used not only to improve reliability but also to ease
protection engineers during installation, maintenance, and in analysing relay’s performance. However,
the dynamics of power systems, the CT’s limited performance during transient condition, and the
precise measurement technique still become a huge challenge in maintaining reliability of differential
and REF protections. Lack performance of these protections can impact into unnecessary outages and
surely causing financial loss to the company.
1
restrained current equation, however some relay manufacturers may use different equation for
restrained factor.
The differential current for each phase, ID_L1, ID_L2, and ID_L3 can be calculated as following
equation,
and the magnitude of restrained current for each phase IR_L1, IR_L2, and IR_L3 can be obtained as
follow,
where Is_W1_L1’, Is_W1_L2’, and Is_W1_L3 are respectively winding 1 phase L1, L2, and L3 current
in per unit quantity, as well as Is_W2_L1’, Is_W2_L2’, and Is_W2_L3’ correspond to winding 2 phase
L1, L2, and L3 current in per unit quantity respectively.
Ip_W1 Ip_W2
Is_W1 Is_W2
Is_W1' Is_W2'
Fig. 1. Differential protection scheme and calculation process flow of two-winding transformer
2
compensate the CT ratio difference amongst phase and ground CTs. The magnitude of REF current,
ID_REF, can be calculated as follow,
𝐼𝐷_𝑅𝐸𝐹 = 𝑘𝑃 ∗ 3𝐼0_𝑐𝑎𝑙𝑐 + 𝑘𝐺 ∗ 𝐼𝐺 (4)
Mostly in REF protection, ground CT is chosen as reference CT, so to match the CT ratio amongst
phase and ground CT the matching factors should follow 𝑘𝑃 = 𝐶𝑇𝑃/𝐶𝑇𝐺 and 𝑘𝐺 = 1. CTP and CTG
are CT ratios of phase and ground CTs respectively. Then, the magnitude of REF restrained current,
IR_REF, can be obtained as follow,
1
𝐼𝑅_𝑅𝐸𝐹 = ∗ ( 𝑘𝑃 ∗ 3𝐼0_𝑐𝑎𝑙𝑐 + 𝑘𝐺 ∗ 𝐼𝐺 ) (5)
2
and again, some relay manufacturers may have different philosophy in determining REF restrained
current.
Winding 1
3I0_calc
Numerical Relay
Macthing
Factor (kP)
REF
calculation
IG
Macthing
Factor (kG)
i stic
c ter
ara
ch
ti ng ΔIF = Total false current
p era
la yo
Re ΔIF-CT = CT false current
3
As for REF protection, we can eliminate the tap changers factor, since REF protection only measures
currents at one side of transformers which windings connection is grounded.
False differential current could also exist due to relay’s algorithm fallacy in estimating the current
phasors of the waveforms, especially when transient condition happens, and this false current will be
escalating if the CTs start to saturate. Transient condition that often happens is when external fault
occurs and also in energization of power transformers. In these conditions the differential and REF
protections reliability are being tested.
𝑁
2 2𝜋𝑘
𝐼𝑟𝑒𝑎𝑙 = ∗ 𝑆𝑘 ∗ sin
( ) (6)
𝑁 𝑁
𝑘=1
𝑁
2 2𝜋𝑘 (7)
𝐼𝑖𝑚𝑎 𝑔 = ∗ 𝑆𝑘 ∗ 𝑐𝑜𝑠
( )
𝑁 𝑁
𝑘=1
Ireal and Iimag are the real and imaginary part of the current phasor, N is number of samples in one full-
cycle discrete data, and Sk is the value of k-th sample.
2
(𝐼𝑟𝑒𝑎𝑙 2 + 𝐼𝑖𝑚𝑎𝑔 (8)
𝐼𝑟𝑚𝑠 =
2
and the phase angle of current phasors, Ɵ, can be defined by the following equation,
𝐼𝑖𝑚𝑎𝑔 (9)
𝜃 = arctan
( )
𝐼𝑟𝑒𝑎𝑙
Another technique to estimate phasors is cosine filter [5]. According to [2] and [3] full-cycle cosine filter
satisfyingly eliminates odd and even harmonics and has good response against DC component. The
real-case differential relay records also will be utilized by using this technique, and then we will evaluate
the differential and REF current calculation results. The cosine filter calculation of fundamental
components can be defined by the following equations,
𝑁
2 2𝜋𝑘
𝐼𝑘 = ∗ 𝑆𝑘 ∗ cos
( ) (10)
𝑁 𝑁
𝑘=1
Where Ik is the cosine filter output of k-th sample, The RMS value of current phasors, Irms can be
obtained as follow,
4
(𝐼𝑘 )2 + (𝐼𝑘 − 𝑁 )2 (11)
4
𝐼𝑟𝑚𝑠 =
2
Where Ik-N/4 is the cosine filter output a quarter-cycle lagged from Ik. Finally, the phase angle of current
phasors, Ɵ, can be defined by the following equation,
𝐼𝑘−𝑁/4
𝜃 = arctan (12)
𝐼𝑘
𝑋1 2 + 𝑋2 2 + ⋯ + 𝑋𝑁 2 (13)
𝐼𝑟𝑚𝑠 =
𝑁
Where N is the number of instantaneous data in one data window, and XN is the N-th instantaneous
value of waveform.
87GT-B
CT3
CT1 CT2
GT, 125MVA
150/11kV
YND1
5
Generally, the fault current not only has a fundamental component but also harmonics and a decaying
dc component [6]. A phase-to-phase-to-ground (A-B to ground) fault happened at the transmission lines
near to the substation. From the relay record, the measured currents obviously contained DC and
harmonic components during the fault (see Tab.1). We use this record data to perform differential and
restrained current calculation following the process in Fig.1 by using all three-measurement technique
as narrated at section IV.
Harmonics
Current Inputs DC
2nd 3rd 4th 5th
Phase A 70.10% 4.20% 1.30% 1.20% 0.90%
CT1 Phase B 104.80% 5.50% 4.60% 2.70% 1.90%
Phase C 53.90% 7.30% 4.20% 3.80% 2.70%
Phase A 57.40% 3.30% 1.40% 0.70% 0.50%
CT2 Phase B 110% 5.50% 2.90% 2.00% 1.30%
Phase C 121.10% 5.30% 3.60% 2.80% 1.90%
Phase A 92.10% 6.80% 5.20% 3.00% 2.50%
CT3 Phase B 84% 10.60% 4.80% 3.60% 2.00%
Phase C 65.90% 10.90% 3.30% 2.50% 1.70%
Since power systems are basically designed to operate at their fundamental value, we expect by only
extracting the fundamental component of the measured current could reduce the false differential
current calculated by the relay, so it would make differential protection more reliable during external
fault. The lower the differential current, the more reliable. The full-cycle DFT and full-cycle cosine filter
as said in [2] and [3] are satisfyingly eliminates harmonics but have different response against DC
component. We will investigate which one is better to be applied in numerical differential relay from the
magnitude of false differential current point of view. The true RMS measurement is also conducted to
investigate whether the DC and harmonic components affect the false differential current magnitude.
(a)
6
(b)
(c)
The simulation results are showed in Fig.4. Since the fault is A-B to ground fault, we get phase A and
B restrained current much higher than phase C (see Fig.4.a and Fig.4.b), and as described in section
III, the higher the through current, the higher the false differential current due to CT transformation
errors. It is clear that the harmonic filtered measurements (full-cycle DFT and full-cycle cosine filter)
yield much better performance than true RMS measurement.
7
(a)
(b)
(c)
Fig.5. RMS value of phase differential current for harmonic filtered measurement
8
As illustrated in Fig.5 full-cycle cosine filter gives better results since it gives lower false differential
currents for the faulted phases. However, each filter does not completely eliminate the false current so
the appropriate setting value of differential protection still need to be well considered [8].
42 MVA, 150/20kV
87 REF
9
Fig.8. RMS value of REF differential current for harmonic filtered measurement
Harmonics
Current DC
2nd 3rd 4th 5th
HV - IA 115.90% 29.40% 23.20% 12.00% 5.10%
HV - IB 79.20% 45.40% 10.10% 20.70% 6.70%
HV - IC 86.10% 32.20% 14.00% 4.10% 5.60%
HV - IG 143.10% 44.20% 13.00% 13.00% 8.90%
Still similar to previous case results, the full-cycle DFT and full-cycle cosine filter give much better result
compare to true RMS measurement. It is clear that eliminating DC and harmonic component makes
REF protection more reliable during energization of a transformer since the magnitude of false REF
differential current calculated by the relay reduce significantly (see Fig.7). Compared to full-cycle DFT,
as illustrated in Fig.8, full-cycle cosine filter yields lower false current which means offer more reliable
performance during inrush current. However, the appropriate setting value of REF still need to be well
considered [8].
VI. CONCLUSIONS
1. Eliminating DC and harmonic components by using full-cycle DFT or full-cycle cosine filter gives
much lower false differential current output for both differential and REF protection compare to
not eliminate DC dan harmonic components (true RMS measurement). Simulation with more
similar case data is recommended to strengthen the conclusion.
2. Comparing full-cycle DFT to full-cycle cosine filter, cosine filter gives lower false differential
current which means provide more reliability for differential and REF protection under transient
conditions that have been described in the simulation.
3. From the simulation results, applying true RMS measurement for differential and REF
protection tends to cause false tripping during external fault and in event of inrush because the
results yield high false currents and current trajectory enters relay’s operating characteristic.
4. Another factor that need to be considered is the appropriate settings for differential and REF
protection characteristics, as well as the formula for determining restrained factor. Performing
relay testing with real-case transient simulation could help to ensure the appropriate settings
have been implemented and also could verify the relay performance under several system
conditions.
10
REFERENCES
[1] G. Ziegler, “Numerical Differential Protection Principles and Application, 2nd edition”. Germany:
Siemens-Erlangen Publicis, 2012.
[2] J. M. Kennedy, J. S. Thorp, “Variable Digital Filter Response Time in a Digital Distance Relay,”
General-Electric. Could be found at https://store.gegridsolutions.com/faq/.../alps/GER-3798.pdf
[3] G. Benmouyal, “Removal of dc-offset in current waveforms using digital mimic filtering,” IEEE
Trans. Power Del., vol. 10, no. 2, pp. 621–630, Apr. 1995.
[4] E. O. Schweitzer and D. Hou, “Filtering for protective relays,” presented at the 19th Annual
Western Protective Relay, Spokane, WA, 1992.
[5] Y. S. Cho, C. K. Lee, G. Jang. “An Innovative Decaying DC Component Estimation Algorithm for
Digital Relaying”. IEEE Transactions on Power Delivery. 2009.
[6] J. Arrilaga, B. C. Smith, N. R. Watson, A. R. Wood, “Power System Harmonic Analysis”. John
Wiley & Sons. 2000.
[7] A. Hargrave, M. J. Thompson, B. Heilman. ”Beyond the Knee Point: A Practical Guide to CT
Saturation”. 72nd Annual Georgia Tech Protective Relaying Conference. Atlanta, Georgia, 2018.
[8] M. J. Thompson, “Percentage Restrained Differential, Percentage of What?”, presented at 64th
Annual Conference for Protective Relay Engineers, April 2011.
[9] Technical Reference Manual Transformer Protection IED RET 670 – Innovation from ABB,
Sweden, 2007
11