Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Introduction:
The air at atmosphere pressure is used as an arc extinguishing medium in air-Break
circuit breakers. These are circuit-breaker employ the high resistance interruption principal. The
arc is rapidly lengthened by means of the arc runners and arc chutes and the resistance of the of
the arc is increased by cooling lengthening and splitting the arc. The arc resistance increased by
cooling lengthening and splitting the arc becomes more then the supply voltage and the arc
extinguished.
The air-Break circuit breakers are used in D.C. circuits and A.C. circuit up-to The
Air-Break circuit breakers arc generally indoor type and installed on vertical panels or indoor
draw-out type switchgear.
A.C. air break circuit-breakers are widely used in indoor medium voltage and low
voltage switchgear typical reference values of ratings of air-break circuit-breaker are:
Magnetic fields for lengthening the arc in high voltage air-break circuit break.
Construction:
In the air-break circuit-break the contact separation and arc extinction tanks place in air
at atmospheric pressure in fig shows the closed current carrying contacts. As the contacts are
opened are drawn between them. The arc core is a conducting path of plasma. The surrounding
medium contains ionized air. By cooling the arc, the diameter of arc core is reduced, the arc
extinguished by lengthening the arc, cooling the arc and splitting the arc. The arc resistance is
increased to such an extent that the system voltage cannot maintain the arc and the arc get
extinguished at current zero of ac wave.
Fig: 1(A) Contact in closed
Introduction:
Air blast circuit-Breaker where used before 1980 for 11 To 1100 KV. A compressor
plant is necessary to maintain high air pressure in air receiver.
During the period 1950-1970 air –blast circuit breakers where preferred for 220KV and
above however today SF6 circuit-breakers are preferred for this range.
Construction:
In air blast circuit-breaker, high pressure air is forced on the arc through a nozzle at the
instant of contact separation. The ionized medium between the contacts is blown away by the blast
of the air. After the arc extinction the chamber is filled with the high pressure air, which prevents
restrict. In some low capacity circuit breakers the isolator is an integral part of the circuit-breaker.
The circuit-breaker opens and immediately after that the isolator opens, to provide additional gap.
Fig: 2 (A) show one pole of the EHV air blast circuit-breaker. In the complete assembly
there are three identical poles.
Fig: 2, (A) one pole Air blast circuit breaker:
Description: High pressure air, at a pressure between 20 to 30 atm is stored in the Air
reservoir (Item 1 in Fig.2 (A).Air is taken from compressed air system.
Three hollow insulator columns (Item 2) are mounted on the reservoir with valves (6)
at their base. The double arc extinguishing chambers (3) are mounted on the top of the hollow
Insulator chambers. The current carrying parts (9) connect the three arc extinction chambers to
each in series and the pole to the neighboring equipment. Since there exists a very high voltage
between the conductors and the air reservoir, the entire arc extinction chamber assembly is
mounted on insulators.
Fig: 2 (b) Details of (3) Double arc extinction chamber
In multi-unit breaker grading capacitors are connected across the interrupter unit for
the equal distribution of voltage between the units. Closing resister are connected across the
interrupter units for limiting the over voltages during closing operation. Opening resister is
connected across the interrupter units to make the circuit breakers restrict free
Specification for Air circuit breaker (415 V)
Introduction:
Bulk oil circuit-breakers have becomes obsolete and has been described here in
brief.
For voltage up-to 12KV, Minimum oil circuit breakers are generally enclosed in draw-
out type metal-clad switchgear.
For 245 KV and, above modular construction is necessary. In such a construction, the
twin interrupter units are connected in series in T or Y formation.
These causes led to the development of Minimum oil circuit breaker. As the name it-self signifies
the Minimum oil circuit breaker required is less oil. The arc extinction medium is dielectric oil,
the same as that used in tank type circuit breaker. There is no still tank but the arc extinction tank
but the arc extinction tanks place in porcelain containers
Fig: 3 (A) Bulk oil circuit breaker
This type is also known as poor oil or small oil circuit breaker. In minimum oil circuit
breakers the current interruption takes place inside Interrupter. The enclosure of the interrupter is
made of insulating material like porcelain. Hence the clearance between the live parts and the
enclosure can be reduced and lesser quantity of oil required for internal insulation. One pole of a
3 pole out-door minimum oil circuit breaker is illustrated in fig .4
Introduction:
When to current carrying contact are separated in a vacuum model, an arc is drawn
between them .An intensely hot spot is created at the instant of contact separation from which
metal vapors shoot off, constituting plasma. The amount of vapor in the plasma is proportional to
the rate of vapors emission from the electrodes, hence to the arc current. Thereby the rate of vapors
emission tends to zero and the amount of plasma tends to zero. With the alternation current arc the
current decreases during a portion of wave, and tends to zero. Soon after natural current zero, the
remaining metal vapor condenses and the dielectric strength builds up rapidly, and restricting of
arc is prevented.
The vacuum circuit breaker comprises one and more sealed vacuum-interrupter units
per pole. The moving contact in the interrupter is connected to insulating operating rod linked with
the operating-mechanism. The contact travel is of the order of a few millimeters only. The
movement of the contact within the sealed interrupter units is permitted by metal- bellows.
Vacuum interrupters rated 3.6/ 7.2/ 36 KV for out-door porcelain housed, single interrupter per
pole, circuit-breaker.
Single phase 25 KV, 25 KA vacuum Circuit breaker having two interrupters per
pole are used for railway track-side 25KV single phase substation. Vacuum devices have several
merits such as high speed of dielectric recovery after rapid and silent operation, suitability for
repeated operations, simple operating mechanisms, freedom from explosion, flexibility design,
long of life etc.
The unique merits of vacuum interrupters are small contact travel and less weight
of moving parts. The vacuum interrupters have very long life of the order of several thousand
operations on rated normal current. However for outdoor installations the external insulation
requirements must be fulfilled and the advantages of high dielectric strength of vacuum cannot be
fully utilized. Some must recently developed 36 KV-GIS utilize SF6 gas and insulations and
vacuum – interrupters for arc –interruption. Such GIS are commercially manufactured in India
(1995).
Enclosure:
The enclosure is made of impermeable insulating material like glass. The enclosure
must not be porous and should retain high vacuum of the order 10^-10 torr.
End Flanges:
The and-flags support the enclosure fixed contact; vapor condensing shields; bellow
and the protective-cover for the bellows:
Contact:
The contacts are made of large stem with large disc-shaped faces. The disk is
provided with symmetrical grooves in such a way that the segments of the two contacts are not in
the same line. The magnetic field set-up by the components of currents with such a geometric
causes the plasma of the arc to move rapidly over the contacts instead of remaining stable at one
point the concentration of the arc is thus prevented and the arc remain in diffused state. The sintered
material used for contact tip is generally copper-chromium or bismuth alloy.
These metallic shields are supported on insulating housing such that they cover the
contact region the metal vapor released from the contact surface arcing is condensed on these
shields and is prevented from condensing on the insulating enclosure.
Metallic Bellows:
One end of the bellow is welded to the metal-flange. The other end is welded to the
moving contact. The bellows permit the sealed construction of the interrupter and yet permit
movement of the contact. Stainless steel bellows are generally used in vacuum interrupter. The
bellows are covered by a protective shield.
Seals: The sealing techniques are similar to those used by electronic value and power tube
manufacturers. These are like metal glass or metal ceramic seal.
In the switchgear installations, the interrupter is housed inside a sheet metal enclosure
and the metal flanges are supported on porcelain or epoxy insulators. The moving contact is
contacted to the operating mechanism by means of glass-fiber rod.
Motor-operated mechanisms
Auxiliary Power Charging time
Voltage Consumption (minimum) s
(v) VA/W
AC
110 150 15
220 150 15
240 170 15
DC
24 130 15
30 130 15
48 130 15
60 130 15
110 140 15
125 160 15
220 140 15
240 150 15
Technical specification:
Rated voltage KV 36 40.5
Rated frequency HZ 50/60 50/60
Rated lightning impulse withstand voltage KV 170 185
Rated power frequency withstands voltage (1 min.) KV Rate 70 95
of rise of transient recovery voltage kV/µs 0.57 0.69
Peak of transient recovery voltage KV 62 70
Rated operating sequence O-3min-CO-3min-CO
Rated operating sequence with auto-reclosing O-0.3s-CO-3min-CO
Breake Rated Rated Rated Rated short Rated Rated Pole Weigh
r type voltag curren short circuit short short canters fixed
e t circuit breaking circuit circuit fixed with
breaking current mreaking duration with draw-
current asymmetr.1) current , draw- able
symm.1) (peak)1) able
VD4 KV A KA KA KA S mm Approx.
kg
3612-25 36 1250 25 27.3 63 4 360- 320 290
280
3616-25 36 1600 320 290
3620-25 36 2000 355 340
3625-25 36 2500 355 340
3612-31 36 1250 31.5 34.3 80 4 360- 320 290
280
3616-31 36 1600 320 290
3620-31 36 2000 335 340
3625-31 36 2500 355 340
4012-25 40.5 1250 25 27.3 63 4 360- 290 290
280
4016-25 40.5 1600 290 290
4020-25 40.5 2000 340 340
4025-25 40.5 2500 340 340
4012-31 40.5 1250 31.5 34.3 80 4 360- 290 290
280
4016-31 40.5 1600 290 290
4020-31 40.5 2000 340 340
4025-31 40.5 2500 340 340
Signature:
.