MCC 10 - BRANCH CIRCUIT DATA

Motor Number HP Motor Distance Conductor


or Load Starting Control or Rated Insulation Start to Load AWG or
Designation Method Method kVA Enclosure Location S.F. Voltage Class Code (Meters) KCMIL Comments
Hand/Off/ Class 1
PM-1A ESS 50 TEFC 1.17 460 B H 120
Auto Zone 2
Hand/Off/ Class 1
PM-2A ESS 40 TEFC 1.15 460 B H 113
Auto Zone 2
Hand/Off/ Class 1
PM-3A VFD 75 TEFC 1.2 460 B G 95
Auto Zone 2
Hand/Off/ Class 1
PM-4A VFD 75 TEFC 1.18 460 B G 86
Auto Zone 2
Hand/Off/ Class 1
PM-5A FVNR 60 TEFC 1.16 460 H H 78
Auto Zone 2
Hand/Off/ Class 1
PM-6A FVNR 50 TEFC -- 460 B H 92
Auto Zone 2
Hand/Off/ Class 1
PM-7A FVNR 75 TEFC 1.23 460 B H 105
Auto Zone 2
Hand/Off/ Class 1
PM-8A FVNR 100 TEFC 1.16 460 B H 85
Auto Zone 2
Transformer 480-
45 IP 54 Outdoor 55
LP10-1 120/208
Transformer 480-
30 IP 54 Outdoor 65
LP10-2 120/208
Panel
83 IP 54 Outdoor 480 60
WP10-1
DESIGN NOTES:
 Requires a Bypass Contactor c/w manual Control Circuit for a Full Voltage start in an Emergency situation
 Transformer and Panel LP 10-1 co-located on one I beam
 Transformer and Panel LP 10-2 co-located on one I beam
 Panel WP 10-1 is a 480V, 100 Amp Panel Board
 Values are in kVA for designated transformer loads.

D:\_DSGN2383\2014F\Motor Control Center Schedules for MCC .xlsx


MCC 20 - BRANCH CIRCUIT DATA

Motor Number HP Motor Distance Conductor


or Load Starting Control or Rated Insulation Start to Load AWG or
Designation Method Method kVA Enclosure Location S.F. Voltage Class Code (Meters) KCMIL Comments
Hand/Off/ Class 1
PM-1B ESS 40 TEFC 1.17 460 B H 120
Auto Zone 2
Hand/Off/ Class 1
PM-2B ESS 50 TEFC 1.15 460 B H 113
Auto Zone 2
Hand/Off/ Class 1
PM-3B VFD 75 TEFC 1.20 460 B G 95
Auto Zone 2
Hand/Off/ Class 1
PM-4B VFD 60 TEFC 1.18 460 B G 86
Auto Zone 2
Hand/Off/ Class 1
PM-5B FVNR 40 TEFC 1.16 460 H H 78
Auto Zone 2
Hand/Off/ Class 1
PM-6B FVNR 60 TEFC -- 460 B H 92
Auto Zone 2
Hand/Off/ Class 1
PM-7B FVNR 100 TEFC 1.23 460 B H 105
Auto Zone 2
Hand/Off/ Class 1
PM-8B FVNR 125 TEFC 1.16 460 B H 85
Auto Zone 2
Transformer 480-
45 IP 54 Outdoor 55
LP20-1 120/208
Transformer 480-
30 IP 54 Outdoor 65
LP20-2 120/208
Panel
83 IP 54 Outdoor 480 60
WP20-1
DESIGN NOTES:
 Requires a Bypass Contactor c/w manual Control Circuit for a Full Voltage start in an Emergency situation
 Transformer and Panel LP 20-1 co-located on one I beam
 Transformer and Panel LP 20-2 co-located on one I beam
 Panel WP 20-1 is a 480V, 100 Amp Panel Board
 Values are in kVA for designated transformer loads.