Sei sulla pagina 1di 43

Project: -

UPS Load Calculation for Industrial Area Pumping Station PLC panel
Rev. 0
Al- Wefaq Control System
Sheet 2 PLC-5
Item Pt. no. Description Qty VA D.F Total Reference
1 6ES7414-5HM06-0AB0 SIMATIC S7-400H, CPU 414-5H 2 7.5 1 15 Page 6
2 6ES7960-1AA06-0XA0 SIMATIC S7-400H, SYNC SUBMODULE 4 0.77 1 3.08 Page 7
3 6ES7407-0KA02-0AA0 SIMATIC S7-400, POWER SUPPLY 2 20 1 40 Page 8
4 6GK5204-2BB10-2AA3 SCALANCE X204-2, MANAGED IE SWITCH 2 6.36 1 12.72 Page 9
5 6ES7153-2BA02-0XB0 SIMATIC DP, ET 200M INTERFACE IM 153-2 1 11 1 11 Page 10
6 6ES7331-1KF02-0AB0 SIMATIC S7-300, ANALOG INPUT SM 331 2 0.4 1 0.8 Page 11
7 6ES7321-1BL00-0AA0 SIMATIC S7-300, DIGITAL INPUT SM 321 5 6.5 1 32.5 Page 12
8 6ES7322-1BL00-0AA0 SIMATIC S7-300, DIGITAL OUTPUT SM 322 2 6.6 1 13.2 Page 13
9 6ES7197-1LA04 -0XA0 Y-Link for S7-400H SIMATIC S7-400H, Y-LINK 1 0 0 0 Page 14
10 46.52.9.024.0040 Relay 24VDC, 8A, 2 Pole,Lockable test button +mechanical 42 0.5 1 21 Page 25
14 FIT-201A/B Magnetic flow meters DN 500 2 15 1 30 Page 26
15 LSH-201A/B Level switch for hazarouds 2 2.5 1 5 Page 27
16 LIT-201A/B level indicator transmitter 2 23 1 46 Page 28
17 PIT-201A/B/C/D/E/F Pressure transmitter 6 0.4 1 2.4 Page 29

Summation 232.7
Auxiliary Rate 0

232.7
TOTAL IN VA
300

Page 1 of 43
Project: -
UPS Load Calculation Inlet Works panel
Rev. 0
Al- Wefaq Control System
Sheet 3,4 PLC-4
Item Pt. no. Description Qty VA D.F Total Reference
1 6ES7414-5HM06-0AB0 SIMATIC S7-400H, CPU 414-5H, CENTRAL UNIT 2 7.5 1 15 Page 6
2 6ES7960-1AA06-0XA0 SIMATIC S7-400H, SYNC SUBMODULE FOR 4 0.77 1 3.08 Page 7
3 6ES7407-0KA02-0AA0 SIMATIC S7-400, POWER SUPPLY PS407: 10A, WIDERANGE, 120/230V UC 2 20 1 40 Page 8
4 6GK5204-2BB10-2AA3 SCALANCE X204-2, MANAGED IE SWITCH 2 6.36 1 12.72 Page 9
5 6ES7153-2BA02-0XB0 SIMATIC DP, ET 200M INTERFACE IM 153-2 2 11 1 22 Page 10
6 6ES7331-1KF02-0AB0 SIMATIC S7-300, ANALOG INPUT SM 331,OPTICALLY ISOLATED, 8 AI, 13 BIT 2 0.4 1 0.8 Page 11
7 6ES7321-1BL00-0AA0 SIMATIC S7-300, DIGITAL INPUT SM 321,OPTICALLY ISOLATED 32DI 8 6.5 1 52 Page 12
8 6ES7322-1BL00-0AA0 SIMATIC S7-300, DIGITAL OUTPUT SM 322,OPTICALLY ISOLATED, 3 6.6 1 19.8 Page 13
9 46.52.9.024.0040 Relay 24VDC, 8A, 2 Pole,Lockable test button +mechanical indicator 74 0.5 1 37 Page 25
10 DLIT-301C Differential Level Indicator Transmitters 3 0.5 1 1.5 Page 30
11 AIT-401 Hydrocarbon Analyzer 1 0.6 1 0.6 Page 31
12 ASS-401 Auto Sampler 1 290 1 290 Page 32
13 FIT-401 FIT-401B Open Channel Ultrasonic level type flowmeter 2 23 1 46 Page 28

Summation 540.5
Auxiliary Rate 0

540.5
TOTAL IN VA
600

Page 2 of 43
Project: -

UPS Load Calculation SBR PLC panel Rev. 0


Al- Wefaq Control System
Sheet 5,6,7 SBR-PLC
Item Pt. no. Description Qty VA D.F Total Reference
1 6ES7414-5HM06-0AB0 SIMATIC S7-400H, CPU 414-5H, CENTRAL UNIT 2 7.5 1 15 Page 6
2 6ES7960-1AA06-0XA0 SIMATIC S7-400H, SYNC SUBMODULE FOR PATCH CABLES UP TO 10M 4 0.77 1 3.08 Page 7
3 6ES7407-0KA02-0AA0 SIMATIC S7-400, POWER SUPPLY PS407: 10A 2 20 1 40 Page 8
4 6GK5204-2BB10-2AA3 SCALANCE X204-2, MANAGED IE SWITCH 2 6.36 1 12.72 Page 9
5 6ES7153-2BA02-0XB0 SIMATIC DP, ET 200M INTERFACE IM 153-2 5 11 1 55 Page 10
6 6ES7331-1KF02-0AB0 SIMATIC S7-300, ANALOG INPUT SM 331 13 0.4 1 5.2 Page 11
7 6ES7332-5HF00-0AB0 SIMATIC S7-300, ANALOG OUTPUT SM 332 3 6 1 18 Page 15
8 6ES7321-1BH02-0AA0 SIMATIC S7-300, DIGITAL INPUT SM 321 25 3.5 1 87.5 Page 16
9 6ES7322-1BH01-0AA0 SIMATIC S7-300, DIGITAL OUTPUT SM 322 9 4.9 1 44.1 Page 17
10 6ES7197-1LA04 -0XA0 Y-Link for S7-400H SIMATIC S7-400H, Y-LIN
1 0 0 0 Page 14
11 46.52.9.024.0040 Relay 24VDC, 8A, 2 Pole,Lockable test button +mechanical indicator 104 0.5 1 52 Page 25
12 PIT-501A/B PIT601A/B Pressure Transmitter 4 0.5 1 2 Page 33
13 LIT-501A/B LIT-601A/B Level Indicator Transmitters 4 23 1 92 Page 28
14 Viberation Sensor 10 0.5 1 5 Page 34
15
FIT-701A/B Differential Pressure Type 2 0.5 1 1 Page 30
AIT-501A/B/C AIT-502A/B/C
AIT-601A/B/C AIT-602A/B/C
16 Analyzers 17 55 1 935 Page 35
LIT-502A/B LIT-602A-B
AIT-503

Summation 1367.6
Auxiliary Rate 0

1367.6
TOTAL IN VA
1400

Page 3 of 43
Project: -

Al- Wefaq Control System


UPS Load Calculation OCU PLC panel Rev. 0

Item Pt. no. Description Qty VA D.F Total Reference


Odor 1 PLC Panel
1 6ES7214-1AG31-0XB0 SIMATIC S7-1200, CPU 1214C, COMPACT CPU, DC/DC/DC 1 12 1 12 Page 37
2 6ES7221-1BH30-0XB0 SIMATIC S7-1200, DIGITAL INPUTSM 1221 , 16DI, 24 V DC, S 5 2.5 1 12.5 Page 38
3 6ES7222-1BH30-0XB0 SIMATIC S7-1200, DIGITAL OUTPUT SM 1222, 16 DO, 2 2.5 1 5 Page 39
4 6ES7231-4HF30-0XB0 SIMATIC S7-1200, ANALOG INPUT, SM 1231, 5 1.5 1 7.5 Page 40
5 6AV6647-0AB11-3AX0 SIMATIC HMI ,KTP600 BASIC ,MONO PN 1 6 1 6 Page 41
6 6GK7242-5DX30-0XE0 COMMUNICATION MODULE CM 1242-5 1 0.75 1 0.75 Page 42
7 46.52.9.024.0040 Relay 24VDC, 8A, 2 Pole,Lockable test button +m. indicator 21 0.5 0.6 6.3 Page 25
8 55.34.9.024.0040 Relay 24 VDC, 7A ,4 Pole, Lockable test button 14 1 0.6 8.4 Page 43
9 - Loop Powered Signal 3 0.576 1 1.728 not avaliable
60.178
Odor 2 PLC Panel
10 6ES7214-1AG31-0XB0 SIMATIC S7-1200, CPU 1214C, COMPACT CPU, DC/DC/DC 1 12 1 12
11 6ES7221-1BH30-0XB0 SIMATIC S7-1200, DIGITAL INPUTSM 1221 , 16DI, 24 V DC, S 5 2.5 1 12.5
12 6ES7222-1BH30-0XB0 SIMATIC S7-1200, DIGITAL OUTPUT SM 1222, 16 DO, 2 2.5 1 5
13 6ES7231-4HF30-0XB0 SIMATIC S7-1200, ANALOG INPUT, SM 1231, 5 1.5 1 7.5 The Same as
14 6AV6647-0AB11-3AX0 SIMATIC HMI ,KTP600 BASIC ,MONO PN 1 6 1 6 Odor 1 PLC
15 6GK7242-5DX30-0XE0 COMMUNICATION MODULE CM 1242-5 1 0.75 1 0.75 Panel
16 46.52.9.024.0040 Relay 24VDC, 8A, 2 Pole,Lockable test button +m. indicator 21 0.5 0.6 6.3
17 55.34.9.024.0040 Relay 24 VDC, 7A ,4 Pole, Lockable test button 14 1 0.6 8.4
18 - Loop Powered Signal 3 0.576 1 1.728
60.178
Summation 120.356
Auxiliary Rate 0

120.356
TOTAL IN VA
200

Page 4 of 43
Project: -

Al- Wefaq Control System


UPS Load Calculation Ultrafilters PLC panel Rev. 0

Item Pt. no. Description Qty VA D.F Total Reference


1 6ES7405-0KA02-0AA0 SIMATIC S7-400 , PS 405 2 95 1 190 Page 18
2 6ES7412-3HJ14-0AB0 SIMATIC S7-400H, CPU412H 2 5.5 1 11 Page 19
3 6ES7960-1AA04-0XA0 SIMATIC S7-400H, SYNC SUB MODULE 2 0.0011 1 0.0022 Page 20
4 6EP1 333-3BA00 SITOP MODULAR 5A 2 18 1 36 Page 21
5 6ES7153-2AR03-0XA0 IM153-2 INTERFACE REDUND.BUNDLE 3 5.5 1 16.5 Page 22
6 6ES7321-1BL00-0AA0 32DI DIGITAL INPUT MODULE 9 6.5 1 58.5 Page 12
7 6ES7322-1BL00-0AA0 32DO DIGITAL OUTPUT MODULE 8 6.6 1 52.8 Page 13
8 6ES7331-1KF02-0AA0 8AI ANALOG INPUT MODULE, 4-20mA 4 0.4 1 1.6 Page 23
9 6GK1503-3CB00 OLM/G12 2 4.8 1 9.6 Page 24
10 6ES7197-1LA04-0XA0 Y-Link 1 0 0 0 Page 14
11 46.52.9.024.0040 2-CONTACT RELAY 24VDC 300 0.5 1 150 Page 25
12 SCADA system computer 1 535 1 535 not avaliable
13 Printer 1 70 1 70 not avaliable
FIT-1001A/B/C/D/E/F FIT-
14 Magnetic flow meters DN 200/400/500 9 15 1 135 Page 26
1002 FIT-1003A/B
15 AIT-1002 TUT-1001 Nitrate/Turbidity analyzers 2 55 1 110 Page 35
16 AIT-1001 hydro-carbon analyzer 1 0.6 1 0.6 Page 31
17 flow switch low 19 10 1 190 Page 36
18 LIT-1001 level transmitter 1 23 1 23 Page 28
PIT-1001:6A/B
19 Pressure transmitter 20 0.5 1 10 Page 33
PIT-1001:6C
20 Solenoid valve of pneumatic 40 15 1 600 not avaliable

Summation 2199.6
Auxiliary Rate 0

2199.6
TOTAL IN VA
2200

Page 5 of 43
6ES7414-5HM06-0AB0 Page 2

Power losses
Power loss, typ. 7.5 W
Backup battery
Battery operation
Backup current, typ. 180 μA ; Valid up to 40°C
Backup current, max. 1000 μA
Backup time, max. Dealt with in the module data manual with the
secondary conditions and the factors of influence
Feeding of external backup voltage to CPU 5 to 15 VDC
Feeding of external backup voltage to CPU 5 to 15 VDC
Memory
Work memory
integrated 4 Mbyte
integrated (for program) 2 Mbyte
integrated (for data) 2 Mbyte
expandable No
Load memory
expandable FEPROM Yes ; with Memory Card (FLASH)
expandable FEPROM, max. 64 Mbyte
integrated RAM, max. 512 kbyte
expandable RAM Yes
expandable RAM, max. 64 Mbyte
Backup
present Yes
with battery Yes ; all data
without battery No
CPU processing times
for bit operations, min. 18.75 ns
for word operations, min. 18.75 ns
for fixed point arithmetic, min. 18.75 ns
for floating point arithmetic, min. 37.5 ns
CPU-blocks
DB
Number, max. 6000 ; Number range: 1 - 16.000

Date: subject to modifications


07/27/2012 32 © Copyright Siemens AG 2012

Page 6 of 43
productdatablad 6ES7960-1AA06-0XA0

SIMATIC S7-400H,
SYNC SUBMODULE V6 FOR PATCH CABLES UP TO 10M

Input current
from CPU, max. 220 mA

Power losses
Power loss, typ. 0,77 W

Dimensions
Breedte 13 mm

Hoogte 14 mm

Diepte 58 mm

Weight
Weight, approx. 14 g

Status 6-jul-2013

6ES7960-1AA06-0XA0 subject to modifications


Page 1/ 1 20.07.2013 © Copyright Siemens AG 2013

Page 7 of 43
6ES7407-0KA02-0AA0 Page 2

Input current
Rated value at 110 V DC 1 A ; at 120 V DC
Rated value at 230 V DC 0.5 A
Rated value at 120 V AC 0.9 A
Rated value at 230 V AC 0.5 A
Inrush current, max. 63 A ; Full width at half maximum 1 ms
Output voltage
Rated value, 5 V DC Yes
Rated value, 24 V DC Yes
Output current
for backplane bus (5 V DC), max. 10 A ; no base load required
for backplane bus (24 V DC), max. 1 A ; idling-proof
Short-circuit protection Yes
Power
Power consumption, typ. 95 W
Power losses
Power loss, typ. 20 W
Backup battery
Backup battery
Backup battery (optional) Yes ; 2 x lithium AA; 3.6 V/2.3 Ah
Galvanic isolation
primary/secondary Yes
EMC
Compliance with line harmonic distortion limits
Observance of line harmonic distortion acc. to IEC Yes
61000-3-2, IEC 61000-3-3
Degree and class of protection
Protection class 1 ; with protective conductor
Standards, approvals, certificates
FM approval Yes ; Ta: 0 °C to 60 °C T4
Connection method
Connecting cables/cross sections 3 x 1.5 mm2, solid or stranded wire with end sleeve,
external diameter 3 to 9 mm
Dimensions

Date: subject to modifications


06/28/2012 © Copyright Siemens AG 2012

Page 8 of 43

26
Attenuation / of fiber-optic cable transmission link / minimum 0 dB
necessary

Range / at the optical interface / depending on the optical fiber used 0 … 5 km

design of the removable storage / C-PLUG Yes

Inputs/outputs
Operating voltage / of signaling contacts / at DC / rated value 24 V

Operating current / of signaling contacts / at DC / maximum 0.1 A

Supply voltage, current consumption, power loss


Type of voltage / of supply voltage DC

Supply voltage / external 24 V

• minimum 18 V

• maximum 32 V

Product component / fusing at power supply input Yes

Type of fusing / at input for supply voltage 0,6 A / 60 V

Consumed current / maximum 0.265 A

Active power loss / at 24 V / for DC 6.36 W

Permitted ambient conditions


Ambient temperature

• during operating -40 … +60 °C

• during storage -40 … +70 °C

• during transport -40 … +70 °C

Relative humidity / at 25 °C / without condensation / during operating 95 %


/ maximum

Protection class IP IP30

Design, dimensions and weight


Design compact

Width 60 mm

Height 125 mm

Depth 124 mm

Net weight 0.78 kg

Type of mounting

• 35 mm DIN rail mounting Yes

• wall mounting Yes

• S7-300 rail mounting Yes

Product properties, functions, components / general


Cascading in the case of a redundant ring / at reconfiguration time of 50
<\~0.3\~s

Cascading in cases of star structuring Any (depending only on signal propagation time)

Product function

• CLI Yes

6GK5204-2BB10-2AA3 subject to modifications


Page 2/ 4 12/03/2012 © Copyright Siemens AG 2012

108 Page 9 of 43
6ES7153-2BA02-0XB0 Page 2

I²t 0.1 A²·s


Output voltage
Rated value, 5 V DC Yes
Output current
for backplane bus (5 V DC), max. 1.5 A
Power losses
Power loss, typ. 5.5 W
Address area
Addressing volume
Outputs 244 byte
Inputs 244 byte
Hardware configuration
Number of modules per DP slave interface, max. 12
Time stamping
Accuracy 1 ms ; 1ms at up to 8 modules; 10ms at up to 12
modules
Number of message buffers 15
Messages per message buffer 20
Number of stampable digital inputs, max. 128 ; Max. 128 signals/station; max. 32 signals/slot
Time format RFC 1119
Time resolution 0.466 ns
Time interval for transmitting the message buffer if a 1000 ms
message is present
Time stamp on signal change rising / falling edge as signal entering or exiting
Interfaces
Interface physics, RS 485 Yes
Interface physics, FOC No
PROFIBUS DP
Node addresses 1 to 125 permitted
Automatic detection of transmission speed Yes
PROFIBUS DP, output current, max. 70 mA
Transmission procedure RS 485
Transmission rate, max. 12 Mbit/s
SYNC capability Yes

Date: subject to modifications


02/14/2012 © Copyright Siemens AG 2012

Page 10 of 43

60
6ES7331-1KF02-0AB0 Page 1

Product data sheet 6ES7331-1KF02-0AB0

SIMATIC S7-300, ANALOG INPUT SM 331,


OPTICALLY ISOLATED, 8 AI,
13 BIT RESOLUTION,
U/I/RESISTANCE/PT100, NI100, NI1000,
LG-NI1000, PTC / KTY,
66 MS MODULE UPDATE, 1 X 40 PIN

Input current
from backplane bus 5 V DC, max. 90 mA
Power losses
Power loss, typ. 0.4 W
Analog inputs
Number of analog inputs 8
Number of analog inputs for resistance 8
measurement
permissible input voltage for voltage input 30 V ; 12 V continuous, 30 V for max. 1 s
(destruction limit), max.
permissible input current for current input 40 mA
(destruction limit), max.
Input ranges
Voltage Yes
Current Yes
Thermocouple No

Date: subject to modifications


01/09/2012 © Copyright Siemens AG 2012

Page 11 of 43

73
6ES7321-1BL00-0AA0 Page 1

Product data sheet 6ES7321-1BL00-0AA0

SIMATIC S7-300, DIGITAL INPUT SM 321,


OPTICALLY ISOLATED 32DI, 24 V DC,
1 X 40 PIN

Supply voltage
Load voltage L+
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
from backplane bus 5 V DC, max. 15 mA
Power losses
Power loss, typ. 6.5 W
Digital inputs
Number/binary inputs 32
Input characteristic curve acc. to IEC 61131, Type 1 Yes
Number of simultaneously controllable inputs
horizontal installation
up to 40 °C, max. 32

Date: subject to modifications


65-1
01/29/2012 © Copyright Siemens AG 2012

Page 12 of 43
6ES7322-1BL00-0AA0 Page 1

Product data sheet 6ES7322-1BL00-0AA0


6ES7322-1BL00-0AA
AA
A0

SIMATIC S7-300, DIGITAL OUTPUT SM 322,


OPTICALLY ISOLATED, 32DO, 24V DC, 0.5A,
1 X 40 PIN,
SUM OF OUTPUT CURRENTS 4A/GROUP
(16A/MODULE)

Supply voltage
Load voltage L+
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
from load voltage L+ (without load), max. 160 mA
from backplane bus 5 V DC, max. 110 mA
Power losses
Power loss, typ. 6.6 W
Digital outputs
Number/binary outputs 32
Limitation of inductive shutdown voltage to L+ (-53 V)
Lamp load, max. 5 W
Load resistance range

Date: 69-1 subject to modifications


01/29/2012 © Copyright Siemens AG 2012

Page 13 of 43
Product data sheet 6ES7197-1LA04-0XA0

SIMATIC S7-400H,
Y-LINK FOR CONNECTING SINGLE-CHANNEL DP
SLAVES TO S7-400H BASED ON IM153-BA02 (NOT FIT
FOR PCS7 V6.1)

Dimensions
Width 40 mm

Height 125 mm

Depth 130 mm

Status Jul 1, 2013

6ES7197-1LA04-0XA0 subject to modifications


Page 1/ 1 07/20/2013 © Copyright Siemens AG 2013

Page 14 of 43
6ES7332-5HF00-0AB0 Page 1

Product data sheet 6ES7332-5HF00-0AB0

SIMATIC S7-300, ANALOG OUTPUT SM 332,


OPTICALLY ISOLATED, 8 AO, U/I;
DIAGNOSTICS;
RESOLUTION 11/12 BITS, 40 PIN,
REMOVE/INSERT W. ACTIVE, BACKPLANE BUS

Supply voltage
Load voltage L+
Rated value (DC) 24 V
Input current
from load voltage L+ (without load), max. 340 mA
from backplane bus 5 V DC, max. 100 mA
Power losses
Power loss, typ. 6 W
Analog outputs
Number of analog outputs 8
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 25 mA
Current output, no-load voltage, max. 18 V
Output ranges, voltage
0 to 10 V Yes

Date: subject to modifications


02/09/2012 © Copyright Siemens AG 2012

Page 15 of 43

85
6ES7321-1BH02-0AA0 Page 1

Product data sheet 6ES7321-1BH02-0AA0

SIMATIC S7-300, DIGITAL INPUT SM 321,


OPTICALLY ISOLATED, 16DI, 24 V DC,
1 X 20 PIN

Supply voltage
Load voltage L+
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
from backplane bus 5 V DC, max. 10 mA
Power losses
Power loss, typ. 3.5 W
Digital inputs
Number/binary inputs 16
Input characteristic curve acc. to IEC 61131, Type 1 Yes
Number of simultaneously controllable inputs
horizontal installation
up to 60 °C, max. 16

Date: 66-1 subject to modifications


02/12/2012 © Copyright Siemens AG 2012

Page 16 of 43
6ES7322-1BH01-0AA0 Page 1

Product data sheet 6ES7322-1BH01-0AA0


6ES7322-1BH01-0AA
AA
A0

SIMATIC S7-300, DIGITAL OUTPUT SM 322,


OPTICALLY ISOLATED, 16 DO, 24V DC,
0.5A,
1 X 20 PIN SUM OF OUTPUT CURRENTS
4A/GROUP (8A/MODULE)

Supply voltage
Load voltage L+
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
from load voltage L+ (without load), max. 80 mA
from backplane bus 5 V DC, max. 80 mA
Power losses
Power loss, typ. 4.9 W
Digital outputs
Number/binary outputs 16
Limitation of inductive shutdown voltage to L+ (-53 V)
Lamp load, max. 5 W
Load resistance range

Date: subject to modifications


02/12/2012 © Copyright Siemens AG 2012

Page 17 of 43
70-1
for backplane bus (24 V DC), max. 1 A ; idling-proof

Short-circuit protection Yes

Power
Power consumption, typ. 95 W

Power losses
Power loss, typ. 20 W

Battery

Backup battery
Backup battery

Backup battery (optional) Yes ; 2 x lithium AA; 3.6 V/2.3 Ah

Galvanic isolation
primary/secondary Yes

Degree and class of protection


Protection class 1 ; with protective conductor

Standards, approvals, certificates


FM approval Yes ; Ta: 0 °C to 60 °C T4

Connection method
Connecting cables/cross sections 3 x 1.5 mm2, solid or stranded wire with end sleeve, external
diameter 3 to 9 mm

Dimensions
Width 50 mm

Height 290 mm

Depth 217 mm

Required slots 2

Weight
Weight, approx. 1200 g

Status Jul 11, 2013

6ES7405-0KA02-0AA0 subject to modifications


Page 2/ 2 07/16/2013 © Copyright Siemens AG 2013

Page 18 of 43
Product data sheet 6ES7412-3HJ14-0AB0

SIMATIC S7-400H,
CPU 412-3H CENTRAL UNIT FOR S7-400H AND S7-
400F/FH,
3 INTERFACES: 1 MPI/DP AND 2 FOR SYNC MODULES
768 KB MEMORY (256 KB DATA/512 KB CODE)

General information
Hardware product version 1

Firmware version V4.5

Engineering with
Programming package STEP7 V 5.3 SP2 or higher with HW update

CiR - Configuration in RUN


CiR synchronization time, basic load 150 ms

CiR synchronization time, time per I/O slave 40 μs

Supply voltage
24 V DC No ; Power supply via system power supply

Input current
from backplane bus 5 V DC, typ. 1.2 A

from backplane bus 5 V DC, max. 1.5 A

from backplane bus 24 V DC, max. 150 mA ; Per DP interface

from interface 5 V DC, max. 90 mA ; At each DP interface

Power losses
Power loss, typ. 5.5 W

Memory

6ES7412-3HJ14-0AB0 subject to modifications


Page 1/ 10 07/16/2013 © Copyright Siemens AG 2013

Page 19 of 43
Product data sheet 6ES7960-1AA04-0XA0

SIMATIC S7-400H,
SYNC SUBMODULE V4 FOR PATCH CABLES UP TO 10M

Input current
from CPU, max. 210 mA

Power losses
Power loss, typ. 1.1 mW

Dimensions
Width 25 mm

Height 53 mm

Depth 140 mm

Weight
Weight, approx. 65 g

Status Jul 6, 2013

6ES7960-1AA04-0XA0 subject to modifications


Page 1/ 1 07/16/2013 © Copyright Siemens AG 2013

Page 20 of 43
6EP1333-3BA00 Page 3

• Note > 60 °C Derating


delivered active power / typ. 120 W
constant overload current / at short-circuit during run- 5.5 A
up / typical
short-term overload current / at short-circuit during 15 A
operation / typical
Duration of overloading ability for excess current / on 25 ms
short-circuiting during the operational phase
Parallel switching for enhanced performance Yes
• Note switchable characteristic
Numbers of parallel switchable units for enhanced 2
performance
Efficiency
Efficiency at Vout rated, Iout rated, approx. 87 %
Power loss at Vout rated, Iout rated, approx. 18 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %), max. 0.1 %
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± 3%
typ.
Load step setting time 50 to 100%, typ. 2 ms
Load step setting time 100 to 50%, typ. 2 ms
Setting time / maximum 5 ms
Protection and monitoring
Output overvoltage protection < 35 V
Current limitation, typ. 5.5 A
Characteristic feature of the output / short-circuit Yes
protected
Short-circuit protection Alternatively, constant current characteristic approx.
5.5 A or latching shutdown
Enduring short circuit current / Effective level / typical 5.5 A
Overload/short-circuit indicator LED yellow for "overload", LED red for "latching
shutdown"
Safety
Primary/secondary isolation Yes
Potential separation Safety extra low output voltage Vout according to EN
60950-1 and EN 50178

Date: subject to modifications


02/09/2012 © Copyright Siemens AG 2012

Page 21 of 43

12
6ES7153-2BA02-0XB0 Page 2

I²t 0.1 A²·s


Output voltage
Rated value, 5 V DC Yes
Output current
for backplane bus (5 V DC), max. 1.5 A
Power losses
Power loss, typ. 5.5 W
Address area
Addressing volume
Outputs 244 byte
Inputs 244 byte
Hardware configuration
Number of modules per DP slave interface, max. 12
Time stamping
Accuracy 1 ms ; 1ms at up to 8 modules; 10ms at up to 12
modules
Number of message buffers 15
Messages per message buffer 20
Number of stampable digital inputs, max. 128 ; Max. 128 signals/station; max. 32 signals/slot
Time format RFC 1119
Time resolution 0.466 ns
Time interval for transmitting the message buffer if a 1000 ms
message is present
Time stamp on signal change rising / falling edge as signal entering or exiting
Interfaces
Interface physics, RS 485 Yes
Interface physics, FOC No
PROFIBUS DP
Node addresses 1 to 125 permitted
Automatic detection of transmission speed Yes
PROFIBUS DP, output current, max. 70 mA
Transmission procedure RS 485
Transmission rate, max. 12 Mbit/s
SYNC capability Yes

Date: subject to modifications


02/14/2012 © Copyright Siemens AG 2012

Page 22 of 43

60
(6.)$% 3DJH

3URGXFWGDWDVKHHW (6.)$%

6,0$7,&6$1$/2*,138760
237,&$//<,62/$7('$,
%,75(62/87,21
8,5(6,67$1&(371,1,
/*1,37&.7<
0602'8/(83'$7(;3,1

,QSXWFXUUHQW
IURPEDFNSODQHEXV9'&PD[ bP$
3RZHUORVVHV
3RZHUORVVW\S b:
$QDORJLQSXWV
1XPEHURIDQDORJLQSXWV 
1XPEHURIDQDORJLQSXWVIRUUHVLVWDQFH 
PHDVXUHPHQW
SHUPLVVLEOHLQSXWYROWDJHIRUYROWDJHLQSXW b99FRQWLQXRXV9IRUPD[V
GHVWUXFWLRQOLPLW PD[
SHUPLVVLEOHLQSXWFXUUHQWIRUFXUUHQWLQSXW bP$
GHVWUXFWLRQOLPLW PD[
,QSXWUDQJHV
9ROWDJH <HV
&XUUHQW <HV
7KHUPRFRXSOH 1R

'DWH VXEMHFWWRPRGLILFDWLRQV
 k&RS\ULJKW6LHPHQV$*

Page 23 of 43

73
• for glass FOC with 50/125 μm / at 3 dB/km / maximum 10 dB

• for glass FOC with 62.5/125 μm

• at 3.5 dB/km / maximum 12 dB

Signal delay time in bit time 6.5 bit

Injectable optical power relating to 1 mW

• for glass FOC with 50/125 μm / at 3 dB/km -16 dB

• for glass FOC with 62.5/125 μm

• at 3.5 dB/km -13 dB

Optical sensitivity relating to 1 mW

• for glass FOC with 50/125 μm / at 3 dB/km -28 dB

• for glass FOC with 62.5/125 μm

• at 3.5 dB/km -28 dB

Wavelength

• for glass FOC with 50/125 μm / compatible with interface / at 3 860 nm


dB/km

• for glass FOC with 62.5/125 μm / compatible with interface

• at 3.5 dB/km 860 nm

Cable length

• for glass FOC with 50/125 μm / at 3 dB/km / maximum 3 km

• for glass FOC with 62.5/125 μm at 3.5 dB/km maximum

• 3 km

Inputs/outputs
Operating voltage / of signaling contacts / at DC / rated value 24 V

Operating current / of signaling contacts / at DC / maximum 0.1 A

Supply voltage, current consumption, power loss


Type of voltage / of supply voltage DC

Supply voltage / for DC

• rated value 24 V

• minimum 18.8 V

• maximum 28.8 V

Product component / fusing at power supply input Yes

Consumed current / At 24 V / with DC / maximum 0.2 A

Permitted ambient conditions


Ambient temperature

• during operating 0 … 60 °C

• during storage -40 … +70 °C

• during transport -40 … +70 °C

Relative humidity

• at 25 °C / without condensation / during operating / maximum 95 %

Protection class IP IP40

6GK1503-3CB00 subject to modifications


Page 2/ 3 07/16/2013 © Copyright Siemens AG 2013

Page 24 of 43
46 Series - Miniature industrial relays 8 - 16 A
Features 46.52 46.61
1 & 2 Pole relay range
46.52 - 2 Pole 8 A
46.61 - 1 Pole 16 A
• Socket mount or direct connection via Faston
connectors
• AC coils & DC coils
• Available with: lockable test button,
mechanical indicator & LED indicator
• 8 mm, 6 kV (1.2/50 μs) isolation, coil-contacts
• Cadmium Free contacts
• 2 Pole CO, 8 A • 1 Pole CO, 16 A
• Plug-in/Solder terminals • Plug-in/Faston 187

46.52

29 12.4
32.8
20

46.61

4.75 0.5 4.75


6.5

FOR UL HORSEPOWER AND PILOT DUTY RATINGS


SEE “General technical information” page V
Contact specification
Contact configuration 2 CO (DPDT) 1 CO (SPDT)
Rated current/Maximum peak current A 8/15 16/25
Rated voltage/Maximum switching voltage V AC 250/440 250/440
Rated load AC1 VA 2,000 4,000
Rated load AC15 (230 V AC) VA 350 750
Single phase motor rating (230 V AC) kW 0.37 0.55
Breaking capacity DC1: 30/110/220 V A 6/0.5/0.15 12/0.5/0.15
Minimum switching load mW (V/mA) 300 (5/5) 300 (5/5)
Standard contact material AgNi AgNi
Coil specification
Nominal voltage (UN) V AC (50/60 Hz) 12 - 24 - 48 - 110 - 120 - 230 - 240
V DC 12 - 24 - 48 - 110 - 125
Rated power VA/W /0.5
1.2/0.5 1.2/0.5
Operating range AC (0.8...1.1)UN (0.8...1.1)UN
DC (0.73...1.1)UN (0.73...1.1)UN
Holding voltage AC/DC 0.8UN /0.4UN 0.8UN /0.4UN
Must drop-out voltage AC/DC 0.2UN /0.1UN 0.2UN /0.1UN
Technical data
Mechanical life AC/DC cycles 10 · 106 10 · 106
Electrical life at rated load AC1 cycles 100 · 103 100 · 103
Operate/release time ms 10/3 15/5
Insulation between coil and contacts (1.2/50 μs)kV 6 (8 mm) 6 (8 mm)
Dielectric strength between open contacts V AC 1,000 1,000
Ambient temperature range °C –40 ... +70 –40 ... +70
Environmental protection RT II RT II
Approvals (according to type)

Page 25 of 43 1

138
Proline Promag 50W, 53W

1
2
3
4
5
6
7
a b
A0003194

a Signal cable
b Coil current cable
1 Core
2 Core insulation
3 Core shield
4 Core jacket
5 Core reinforcement
6 Cable shield
7 Outer jacket

Operation in zones of severe electrical interference


The measuring device complies with the general safety requirements in accordance with EN 61010 and
the EMC requirements of IEC/EN 61326 and NAMUR recommendation NE 21.

" Caution!
Grounding is by means of the ground terminals provided for the purpose inside the connection housing.
Ensure that the stripped and twisted lengths of cable shield to the ground terminal are as short as possible.

Power consumption • AC: < 15 VA (incl. sensor)


• DC: < 15 W (incl. sensor)
Switch-on current:
• Max. 3 A (< 5 ms) for 260 V AC
• Max. 13.5 A (< 50 ms) for 24 V DC

Power supply failure Lasting min. ½ cycle frequency: EEPROM saves measuring system data
• EEPROM or T-DAT (Promag 53 only) retain the measuring system data in the event of a power supply failure
• S-DAT: exchangeable data storage chip which stores the data of the sensor (nominal diameter, serial number,
calibration factor, zero point etc.)

10 Page 26 of 43 Endress+Hauser
Nivotester FTL 325 N

Power supply
Electrical connection Terminal blocks
The removable terminal blocks are separated into intrinsically safe connections (at top of the
instrument) and non-instrinsically safe connections (at bottom of the instrument). Also, the
terminal blocks have different colours to make them more easily recognisable. Blue for the
intrinsically safe section and grey for the non-intrinsically safe section. This difference helps to
ensure safe wiring.

Connecting the measuring sensor


(at upper, blue terminal blocks)
The two-wire connecting line between the Nivotester FTL 325 N and the Liquiphant, Nivopuls or
Soliphant measuring sensor can be either a commercially available installation cable or wires in
a multi-wire cable for measuring purposes. Line resistance may be a maximum of 25 Ω per wire.
If strong electromagnetic interference is expected, e.g. from machines or radio devices, a
screened cable must be used. Only connect the screen to the ground connection, and not to the
Nivotester.

Using the measuring sensor in explosion hazardous areas


Please observe all local regulations on explosion protection concerning the type and installation
of intrinsically safe signal cabling.
Please refer to the Safety Instructions XA 134F for maximum permissible values of capacitance
and inductance.

Connecting signal and control devices


(at lower, grey terminal blocks)
The relay function is dependent on the level and fail-safe circuit.
If an instrument is connected at high inductance (e.g. contactor, solenoid valve etc.), a spark
suppressor must be installed to protect the relay contact.

Connecting the supply voltage


(at lower, grey terminal blocks)
For voltage variants, see the Ordering Information on page 14.
A fuse is built into the supply current circuit. This obviates the need to connect a fine-wire fuse in
series. The Nivotester is equipped with reverse polarity protection.

Supply voltage AC version:


• Voltage ranges: 85...253 V AC, 50/60 Hz

DC version:
• Voltage ranges: 20...30 V AC / 20...60 V DC
• DC supply: max. 60 mA (1-channel)
• DC supply: max. 115 mA (3-channel)
• Permissible residual ripple within tolerance: Uss = max. 2 V
The Nivotester is equipped with reverse polarity protection.

Power consumption AC
1-channel: max. 1.75 W
3-channel: max. 2.75 W

DC
1-channel: max. 1.2 W (bei Umin 20 V)
3-channel: max. 2.25 W (bei Umin 20 V)

8 Page 27 of 43 Endress+Hauser
Prosonic S FMU90

PROFIBUS DP interface Profile 3.0

Transmittable values • main value (level or flow, depending on the instrument version)
• distances
• counters
• temperatures
• average/difference/sum
• relay states
• rake control
• pump control

Function blocks • 10 Analog Input Blocks (AI)


• 10 Digital Input Blocks (DI)
• 10 Digital Output Blocks (DO)

Supported baud rates • 9.6 kbaud


• 19.2 kbaud
• 45,45 kbuad
• 93.75 kbaud
• 187.5 kbaud
• 500 kbaud
• 1.5 Mbaud
• 3 Mbaud
• 6 Mbaud
• 12 Mbaud

Service Access Points (SAPs) 1

ID number 1540 (hex) 1540 (hex) = 5440 (dec)

GSD file EH3x1540.gsd

Addressing via dip switches at the instrument or via software (e.g. FieldCare)
Default address: 126 per software

Termination can be activated/deactivated in the instrument

Locking The device can be locked by hardware or software.

Auxiliary energy
Supply voltage/ Instrument version Supply voltage Power consumption Current consumption
Power consumption/
Current consumption AC voltage
90 ... 253 VAC (50/60 Hz) max. 23 VA max. 100 mA at 230 VAC
(FMU90 - ****A****)

DC voltage
10,5 ... 32 VDC max. 14 W (typically 8 W) max. 580 mA at 24 VDC
(FMU90 - ****B****)

Galvanic isolation The following terminals are galvanically isolated from each other:
• auxiliary energy
• sensor inputs
• analogue output 1
• analogue output 2
• relay outputs
• bus connection (PROFIBUS DP)

Fuse • 2 A T /DC
• 400 mA T /AC
accesible in the terminal compartment

10 Page 28 of 43 Endress + Hauser


Cerabar M PMC51, PMP51, PMP55

FOUNDATION Fieldbus
• Version for non-hazardous areas: 9 to 32 V DC

Start-up current HART 12 mA or 22 mA (selectable)

Current consumption • PROFIBUS PA: 11 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
• FOUNDATION Fieldbus: 16 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21

Cable entry o ä 75 ff, feature 50 "Electrical connection".

Cable specification • Endress+Hauser recommends using twisted, shielded two-wire cables.


• Terminals for wire cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)
• Cable outer diameter: 5 to 9 mm (0.2 to 0.35 in)

Residual ripple No influence on 4 to 20 mA signal up to r5 % residual ripple within the permitted voltage range [according to
HART hardware specification HCF_SPEC-54 (DIN IEC 60381-1)]

Influence of power supply d0.001% of URL/1 V

Endress+Hauser Page 29 of 43 19
Deltabar S

Supply voltage Note!


• When using the measuring device in hazardous areas, installation must comply with the corresponding
national standards and regulations and the Safety Instructions or Installation or Control Drawings.
• All explosion protection data are given in separate documentation which is available upon request. The
Ex documentation is supplied as standard with all devices approved for use in explosion hazardous areas.
o ä 85, "Safety Instructions" and "Installation/Control Drawings" sections.

4 to 20 mA HART
• Version for non-hazardous areas, jumper for 4 to 20 mA test signal in "Test" position
(delivery status): 11.5 to 45 V DC
• Version for non-hazardous areas, jumper for 4 to 20 mA test signal in "Non-test" position:
10.5 to 45 V DC

PROFIBUS PA
• Version for non-hazardous areas: 9 to 32 VDC

FOUNDATION Fieldbus
• Version for non-hazardous areas: 9 to 32 V DC

Current consumption • PROFIBUS PA: 13 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
• FOUNDATION Fieldbus: 15 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21

Cable entry o ä 69 ff, feature 30 "Housing; Cable entry; Protection".

Cable specification • Endress+Hauser recommends using shielded, twisted-pair two-wire cables.


• Terminals for core cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)
• Cable outer diameter: 5 to 9 mm (0.2 to 0.35 in)

Residual ripple Without influence on 4 to 20 mA signal up to r5 % residual ripple within the permitted voltage range
[according to HART hardware specification HCF_SPEC-54 (DIN IEC 60381-1)]

Influence of power supply d0.0006% of URL/1 V

18 Page 30 of 43 Endress+Hauser
x Power requirement 220 VAC
x Power consumption: 0.48 Watts
x Analog outputs: 4-20mA isolated
x Analog loop resistance: 500 Ohms, nominally @ 24V
x Alarms: Optional
x Certification: Available upon request

Mechanical

x Transmitter weight: 3 lbs.


x Enclosure: Extruded aluminum (optional NEMA or purged enclosures)
x 8" H x 3-7/8" W x 1-1/2" D

UV Lamp

x Type: Xenon flash lamp


x Wavelength range: 200 - 650 nm
x Lamp Life: Typically 3 years
x Size: 2" H x 4" W x 1-1/2" D
x Power requirements: 24 VDC (9-32 VDC)

6650 UVF Probe

x Materials: 316SS
x Max temperature rating: 315.5° C (600° F)
x Max pressure rating: 5000 psig

Sample Conditioning System

x All wetted parts of SCS components will be SS316


x Ultrasonic Homogenizer for sample mix
x Sample shut off valve
x Sample and fast loop bypass
x Pressure regulator with viewing gauge
x Sample flow meter with precision needle valves
x Extra Cuno filter

Mounting:

x NEMA 4 (IP65) free standing enclosure

Area Class

x Ex”d” certified Enclosure for Class 1 Div 2

Page 31 of 43
Liquistation CSF34

Mains fuse Optional fuses on DIN rail


• T10A (for 24V power supply)
• T3.15A (for 230V power supply)
• T10A (fuse for battery backup)

Power consumption • Version with vacuum pump: 290 VA


• Version with peristaltic pump: 290 VA

Power failure • Power supply via battery (optional): 2 x 12 V, 7.2 Ah, with additional charge controller

Replace batteries with battery type Panasonic LC-R127R2PG1.

• Real-time clock: lithium battery, type CR2032

Performance characteristics
Sampling methods Vacuum pump / peristaltic pump:
• Event sampling
• Single and multiple samples
• Sampling table
Vacuum pump:
• In proportion to time
• In proportion to volume
Peristaltic pump:
• In proportion to time
• In proportion to volume
• In proportion to flow

Dosing volume • Vacuum pump:


20 to 350 ml (0.7 to 12 fl.oz.)
• Peristaltic pump:
10 to 10,000 ml (0.3 to 340 fl.oz.)
A sample volume < 20 ml can vary in dosing accuracy and repeatability, depending on the
application.

Dosing accuracy • Vacuum pump:


±5 ml (0.17 fl.oz.) or 5 % of the set volume
• Peristaltic pump:
±5 ml (0.17 fl.oz.) or 5 % of the set volume

Repeatability • Vacuum pump: 5 %


• Peristaltic pump: 5 %

Intake speed > 0.5 m/s (> 1.6 ft/s) for ” 13 mm (1/2") ID, in accordance with EN 25667, ISO 5667
> 0.6 m/s (> 1.9 ft/s) for 10 mm (3/8") ID, in accordance with Ö 5893 (Austrian standard); US EPA

Suction height Max. 8 m (26 ft)

Hose length Max. 30 m (98 ft)

22 Page 32 of 43 Endress+Hauser
Cerabar S

Supply voltage Note!


• When using the measuring device in hazardous areas, installation must comply with the corresponding
national standards and regulations and the Safety Instructions or Installation or Control Drawings.
• All explosion protection data are given in separate documentation which is available upon request. The
Ex documentation is supplied as standard with all devices approved for use in explosion hazardous areas.
o ä 89 ff, "Safety Instructions" and "Installation/Control Drawings" sections.

4 to 20 mA HART
• Version for non-hazardous areas, jumper for 4 to 20 mA test signal in "Test" position
(delivery status): 11.5 to 45 V DC
• Version for non-hazardous areas, jumper for 4 to 20 mA test signal in "Non-test" position:
10.5 to 45 V DC

PROFIBUS PA
• Version for non-hazardous areas: 9 to 32 V DC

FOUNDATION Fieldbus
• Version for non-hazardous areas: 9 to 32 V DC

Current consumption • PROFIBUS PA: 13 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
• FOUNDATION Fieldbus: 15 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21

Cable entry o ä 76 ff, feature 30 "Housing; Cable entry; Protection".

Cable specification • Endress+Hauser recommends using shielded, twisted-pair two-wire cables.


• Terminals for core cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)
• Cable outer diameter: 5 to 9 mm (0.2 to 0.35 in)

Residual ripple Without influence on 4 to 20 mA signal up to r5 % residual ripple within the permitted voltage range
[according to HART hardware specification HCF_SPEC-54 (DIN IEC 60381-1)]

Influence of power supply d0.0006% of URL/1 V

18 Page 33 of 43 Endress+Hauser
Page 34 of 43
Liquiline CM442

Cable specification Cable gland Permitted cable diameter

M16x1.5 mm 4 to 8 mm (0.16 to 0.32")

M12x1.5 mm 2 to 5 mm (0.08 to 0.20")

M20x1.5 mm 6 to 12 mm (0.24 to 0.48")

NPT3/8" 4 to 8 mm (0.16 to 0.32")

G3/8 4 to 8 mm (0.16 to 0.32")


NPT1/2" 6 to 12 mm (0.24 to 0.48")

G1/2 7 to 12 mm (0.28 to 0.47")

Power consumption Depending on supply voltage


• 100 to 230 V AC and 24 V AC:
Max. 55 VA
• 24 V DC:
Max. 22 W

Fuse For all versions:


5x20 mm, 250 V, 4.0 A, slow-blow (T4.0A)

Performance characteristics
Response time Current outputs
t90 = max. 500 ms for an increase from 0 to 20 mA

Reference temperature 25 ƒC (77 ƒF)

Maximum measured error of --> Documentation of the connected sensor


inputs

Maximum measured error of < 20 —A at 4 mA


current outputs < 50 —A at 20 mA
at 25 ƒC (77ƒ F) each
Additional measured error depending on the temperature:
< 1.5 —A/K

Resolution of current output < 5 —A

Repeatability --> Documentation of the connected sensor

10 Page 35 of 43 Endress+Hauser
Limit reed switch ZE 951 for DFM 165 - 350
bistable

Advantage Switching Current


• reliable limit value determination using reed switches • max. 0,5 A
• direct power control of consumers with contact protection relay
ZE 3061 Electric Switching Capacity
• 2-point control for monostable switches with ZE 3060 • max. 10 VA
• freely adjustable flow limit value - fastened with a clamping Resistance
piece to the measuring tube dovetail guide • < 150 mOhm
• reliable, simple installation, easy to retrofit in existing plants
Insulation Resistance
Description • > 1010 Ohm
• The limit reed switch ZE 951 serves as signal transmitters of the
flow values. They are clamped to the dovetail guides and signal Ambient Temperature
when the magnetic float in the measuring tube has reached or • 0°C to +55°C
exceeded the signal transmitter position. As soon as this
Hysteresis
happens, a contact in the signal transmitter, as the actual
• 10 mm
switching element (reed switch), opens or closes.
Function Type Of Protection
• IP 65 with mounted connector plug
• Type ZE 951 bistable (normally open contact/normally closed
contact) The contact is closed (normally open contact) or opened Connection Cable
(normally closed contact), as soon as the magnetic float moves • nominal cross-section: 1.5 mm²
up from below or is at the direct height of the signal transmitter. • cable outside diameter: 4…6 mm
If the float goes above the signal transmitter, the switching state
remains unaffected. The switching state is only cancelled if the Pin Assignment
float goes below the signal transmitter. • the polarity of the connections has no influence on the function

Body Colour
• ABS • anthracite grey

Connector Plug Accessories


• according to DIN EN 175301-803 • 2-Point Control Unit ZE 3060 (Article number 136245, 1326244)
• Contact Protection Relay ZE 3061 (Article number 136240,
Voltage 136239)
• 2V 'C
2V 'C

> data sheet no.: 330207 - 2010/05/05 Page 36 of 43 All rights for technical modifications withheld 1
ASV Stübbe GmbH & Co. KG · Hollwieser Str. 5 · D-32602 Vlotho · Tel. +49(0)5733. 799-0 · Fax +49(0)5733. 799-5000 · contact@asv-stuebbe.de · www.asv-stuebbe.de
Current output to backplane bus (DC 5 V), max. 1600 mA ; Max. 5 V DC for SM and CM

Power losses
Power loss, typ. 12 W

Memory
Usable memory for user data 75 kbyte

Work memory
integrated 75 kbyte

expandable No

Load memory
integrated 4 Mbyte

Backup
present (maintenance-free)

without battery Yes

CPU processing times


for bit operations, typ. 0.085 µs ; / instruction

for word operations, typ. 1.7 µs ; / instruction

for floating point arithmetic, typ. 2.5 µs ; / instruction

CPU-blocks
Number of blocks (total) DBs, FCs, FBs, counters and timers. The maximum number of
addressable blocks ranges from 1 to 65535. There is no restriction,
the entire working memory can be used

OB
Number, max. Limited only by RAM for code

Data areas and their retentivity


retentive data area in total (incl. times, counters, flags), max. 10 kbyte

Flag
Number, max. 8 kbyte ; Size of bit memory address area

Address area

I/O address area


I/O address area, overall 1024 bytes for inputs / 1024 bytes for outputs

Process image
Inputs, adjustable 1 kbyte

Outputs, adjustable 1 kbyte

Hardware configuration
Number of modules per system, max. 3 comm. modules, 1 signal board, 8 signal modules

Time of day

Clock
Hardware clock (real-time clock) Yes

6ES7214-1AG31-0XB0 subject to modifications


Page 2/ 8 07/20/2013 © Copyright Siemens AG 2013

Page 37 of 43
Product data sheet 6ES7221-1BH30-0XB0

SIMATIC S7-1200, DIGITAL INPUT SM 1221,


16 DI, 24VDC, SINK/SOURCE INPUT

Supply voltage
24 V DC Yes

permissible range, lower limit (DC) 20.4 V

permissible range, upper limit (DC) 28.8 V

Input current
from backplane bus 5 V DC, max. 130 mA

Digital inputs
from load voltage L+ (without load), max. 4 mA ; per channel

Output voltage

Power supply to the transmitters


present Yes

Power losses
Power loss, typ. 2.5 W

Digital inputs
Number/binary inputs 16

In groups of 4

Input characteristic curve acc. to IEC 61131, Type 1 Yes

Number of simultaneously controllable inputs

6ES7221-1BH30-0XB0 subject to modifications


Page 1/ 3 07/20/2013 © Copyright Siemens AG 2013

Page 38 of 43
Product data sheet 6ES7222-1BH30-0XB0

SIMATIC S7-1200,
DIGITAL OUTPUT SM 1222, 16 DO, 24V DC,
TRANSISTOR 0.5A

Supply voltage
permissible range, lower limit (DC) 20.4 V

permissible range, upper limit (DC) 28.8 V

Input current
from backplane bus 5 V DC, max. 140 mA

Power losses
Power loss, typ. 2.5 W

Digital inputs
Number/binary inputs 0

Digital outputs
Number/binary outputs 16

In groups of 1

Functionality/short-circuit strength No ; to be provided externally

Limitation of inductive shutdown voltage to typ. (L+) -48 V

Switching capacity of the outputs


with resistive load, max. 0.5 A

on lamp load, max. 5W

Output voltage

6ES7222-1BH30-0XB0 subject to modifications


Page 1/ 3 07/20/2013 © Copyright Siemens AG 2013

Page 39 of 43
Product data sheet 6ES7231-4HF30-0XB0

SIMATIC S7-1200, ANALOG INPUT, SM 1231,


8 AI, +/-10V, +/-5V, +/-2.5V,
OR 0-20 MA 12 BIT + SIGN OR (13 BIT ADC)

Supply voltage
24 V DC Yes

Input current
Current consumption, typ. 45 mA

from backplane bus 5 V DC, typ. 90 mA

Power losses
Power loss, typ. 1.5 W

Analog inputs
Number of analog inputs 8 ; Current or voltage differential inputs

permissible input frequency for current input (destruction limit), ± 35 V


max.

permissible input voltage for voltage input (destruction limit), max. 35 V

permissible input current for voltage input (destruction limit), max. 40 mA

permissible input current for current input (destruction limit), max. 40 mA

Cycle time (all channels) max. 625 µs

Input ranges
Voltage Yes ; ±10 V, ±5 V, ±2.5 V

Current Yes ; 0 to 20 mA

Thermocouple No

6ES7231-4HF30-0XB0 subject to modifications


Page 1/ 4 07/20/2013 © Copyright Siemens AG 2013

Page 40 of 43
Alphanumeric keyboard Yes ; Onscreen keyboard

Touch operation
Design as touch screen Yes

Installation type/mounting
Mounting in portrait format possible Yes

Mounting in landscape format possible Yes

Supply voltage
Type of supply voltage DC

Rated voltage/DC 24 V

permissible range, lower limit (DC) 19.2 V

permissible range, upper limit (DC) 28.8 V

Input current
Current consumption (rated value) 0.24 A

Inrush current A²s 0.5 A²·s

Power
Power consumption, typ. 6W

Processor
Processor type

X86 No

ARM Yes ; RISC 32-bit

Memory
Flash Yes

RAM Yes

Usable memory for user data 1 Mbyte

Type of output
Acoustics

Buzzer Yes

Speaker No

Time of day

Clock
Hardware clock (real-time clock) No

Software clock Yes

Battery-backed No

Synchronizable Yes

Interfaces
Number of RS 485 interfaces 0

Number of USB interfaces 0

Number of SD card slots 0

6AV6647-0AB11-3AX0 subject to modifications


Page 2/ 9 07/20/2013 © Copyright Siemens AG 2013

Page 41 of 43
Product data sheet 6GK7242-5DX30-0XE0

Product-type designation CM 1242-5

COMMUNICATION MODULE CM 1242-5;


FOR CONNECTION OF SIMATIC S7-1200 TO PROFIBUS
AS DP SLAVE MODULE

Transmission rate
Transmission rate / at interface 1 / in accordance with PROFIBUS 9.6 kbit/s … 12 Mbit/s

Interfaces
Number of electrical connections

• at interface 1 / in accordance with PROFIBUS 1

• for power supply 0

Design of electrical connection

• at interface 1 / in accordance with PROFIBUS 9-pin Sub-D socket (RS485)

Supply voltage, current consumption, power loss


Type of voltage / of supply voltage DC

Supply voltage

• 1 / from backplane bus 5V

Consumed current

• from backplane bus / at 5 V / for DC / Typical 0.15 A

Resistive loss 0.75 W

Permitted ambient conditions


Ambient temperature

• for vertical installation / during operating phase 0 … 45 °C

• for horizontal installation / during operating phase 0 … 55 °C

• during storage -40 … +70 °C

6GK7242-5DX30-0XE0 subject to modifications


Page 1/ 2 07/20/2013 © Copyright Siemens AG 2013

Page 42 of 43
55 Series - General purpose relays 7 - 10 A
Features 55.32 55.33 55.34
Plug-in mount, general purpose
2, 3 & 4 Pole relays
55.32 - 2 Pole 10 A
55.33 - 3 Pole 10 A
55.34 - 4 Pole 7 A
• Lockable test button and mechanical flag
indicator as standard on 2 & 4 pole types
• AC coils & DC coils
• UL Listing (certain relay/socket combinations)
• Cadmium Free contacts (preferred version)
• 2 pole, 10 A • 3 pole, 10 A • 4 pole, 7 A
• Contact material options • Plug-in 94 series sockets • Plug-in 94 series sockets • Plug-in 94 series sockets
• 94 series sockets
• Coil EMC suppression
• Timer accessories 86 series
• European Patent

55.32 55.33 55.34

FOR UL RATINGS SEE:


“General technical information” page V
Contact specification
Contact configuration 2 CO (DPDT) 3 CO (3PDT) 4 CO (4PDT)
Rated current/Maximum peak current A 10/20 10/20 7/15
Rated voltage/Maximum switching voltage V AC 250/400 250/400 250/250
Rated load AC1 VA 2,500 2,500 1,750
Rated load AC15 (230 V AC) VA 500 500 350
Single phase motor rating (230 V AC) kW 0.37 0.37 0.125
Breaking capacity DC1: 30/110/220 V A 10/0.25/0.12 10/0.25/0.12 7/0.25/0.12
Minimum switching load mW (V/mA) 300 (5/5) 300 (5/5) 300 (5/5)
Standard contact material AgNi AgNi AgNi
Coil specification
Nominal voltage (UN) V AC (50/60 Hz) 6 - 12 - 24 - 48 - 60 - 110 - 120 - 230 - 240
V DC 6 - 12 - 24 - 48 - 60 - 110 - 125 - 220
Rated power AC/DC VA (50 Hz)/W 1.5/1 1.5/1 1.5/1
Operating range AC (0.8…1.1)UN (0.8…1.1)UN (0.8…1.1)UN
DC (0.8…1.1)UN (0.8…1.1)UN (0.8…1.1)UN
Holding voltage AC/DC 0.8 UN/0.5 UN 0.8 UN/0.5 UN 0.8 UN/0.5 UN
Must drop-out voltage AC/DC 0.2 UN/0.1 UN 0.2 UN/0.1 UN 0.2 UN/0.1 UN
Technical data
Mechanical life AC/DC cycles 20 · 106/50 · 106 20 · 106/50 · 106 20 · 106/50 · 106
Electrical life at rated load AC1 cycles 200 · 10 3
200 · 10 3
150 · 103
Operate/release time ms 10/5 10/5 11/3
VII-2012, www.findernet.com

Insulation between coil and contacts (1.2/50 μs) kV 4 4 4


Dielectric strength between open contacts V AC 1,000 1,000 1,000
Ambient temperature range °C –40…+85 –40…+85 –40…+85
Environmental protection RT I RT I RT I
Approvals (according to type)

2 Page 43 of 43