Primary-switched QUINT POWER power supply for DIN rail mounting with SFB (Selective Fuse Breaking)
Technology, input: 1-phase, output: 24 V DC/5 A
Product Description
QUINT POWER power supplies with maximum functionality
QUINT POWER circuit breakers magnetically and therefore quickly trip at six times the nominal current, for selective and therefore cost-effective
system protection. The high level of system availability is additionally ensured, thanks to preventive function monitoring, as it reports critical
operating states before errors occur.
Reliable starting of heavy loads takes place via the static power reserve POWER BOOST. Thanks to the adjustable voltage, all ranges between 5
V DC ... 56 V DC are covered.
Your advantages
Reliable starting of difficult loads with the static POWER BOOST power reserve with up to 1.5 times the nominal current permanently
Fast tripping of standard circuit breakers with dynamic power reserve SFB (selective fuse breaking) technology with up to 6 times the nominal
current for 12 ms
For superior system availability
Preventive function monitoring
GTIN
GTIN 4046356113786
Technical data
Dimensions
Width 40 mm
Height 130 mm
Depth 125 mm
Width with alternative assembly 122 mm
Height with alternative assembly 130 mm
Depth with alternative assembly 43 mm
01/19/2020 Page 1 / 7
https://www.phoenixcontact.com/pi/products/2866750
Input data
Nominal input voltage range 100 V AC ... 240 V AC
Input voltage range 85 V AC ... 264 V AC
90 V DC ... 350 V DC
Dielectric strength maximum 300 V AC
AC frequency range 45 Hz ... 65 Hz
Frequency range DC 0 Hz
Discharge current to PE < 3.5 mA
Current consumption 1.2 A (120 V AC)
0.6 A (230 V AC)
1.3 A (110 V DC)
0.6 A (220 V DC)
Nominal power consumption 145 VA
Inrush current < 15 A
Mains buffering time > 55 ms (120 V AC)
> 55 ms (230 V AC)
Input fuse 5 A (slow-blow, internal)
Recommended breaker for input protection 6 A ... 16 A (AC: Characteristics B, C, D, K)
Power factor (cos phi) 0.94
Type of protection Transient surge protection
Protective circuit/component Varistor
Output data
Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN) 5 A (-25 °C ... 60 °C, UOUT = 24 V DC)
POWER BOOST (IBoost) 7.5 A (-25°C ... 40°C permanent, UOUT = 24 V DC )
Selective Fuse Breaking (ISFB) 30 A (12 ms)
Derating 60 °C ... 70 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series yes
Feedback voltage resistance max. 35 V DC
01/19/2020 Page 2 / 7
https://www.phoenixcontact.com/pi/products/2866750
General
Net weight 0.7 kg
Efficiency > 90 % (for 230 V AC and nominal values)
Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage input / PE 3.5 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE 500 V DC (routine test)
Protection class I
Degree of protection IP20
MTBF (IEC 61709, SN 29500) > 1134000 h (25 °C)
> 635000 h (40 °C)
> 270000 h (60 °C)
Mounting position horizontal DIN rail NS 35, EN 60715
alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active
components, 50 mm vertically
Assembly instructions
alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm
vertically bottom
01/19/2020 Page 3 / 7
https://www.phoenixcontact.com/pi/products/2866750
01/19/2020 Page 4 / 7
https://www.phoenixcontact.com/pi/products/2866750
Drawings
Block diagram
01/19/2020 Page 5 / 7
https://www.phoenixcontact.com/pi/products/2866750
Approvals
DNV GL / CSA / BV / LR / NK / ABS / RINA / UL Listed / UL Recognized / cUL Recognized / IECEE CB Scheme / SEMI F47 / DeviceNet / EAC /
EAC / Type approved / cULus Recognized
Ex Approvals
Approval details
DNV GL
https://approvalfinder.dnvgl.com/ TAE000014W
CSA
http://www.csagroup.org/services-industries/product-listing/ 1897779
http://www.veristar.com/portal/veristarinfo/generalinfo/
BV 21004-C0 BV
approved/approvedProducts/equipmentAndMaterials
LR
http://www.lr.org/en 08/20069 E4
NK
http://www.classnk.or.jp/hp/en/ 08A039
15-
ABS http://www.eagle.org/eagleExternalPortalWEB/
HG1375463-1-PDA
RINA
http://www.rina.org/en ELE316517XG
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 123528
01/19/2020 Page 6 / 7
https://www.phoenixcontact.com/pi/products/2866750
UL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 211944
cUL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 211944
IECEE CB Scheme
http://www.iecee.org/ SI-6188 A1
DeviceNet
http://www.odva.org 10825/05.01.2010
EAC
EAC-Zulassung
RU C-
EAC
DE.A*30.B.01082
Type approved
SI-SIQ BG 005/004
cULus Recognized