Sei sulla pagina 1di 8

IEEE Transactions on Power Apparatus and Systems, Vol. PAS-100, No.

6 June 1981
3017
APPLYING POWER SYSTEM STABILIZERS
PART I: GENERAL CONCEPTS
E.V. Larsen (Member) D.A. Swann (Member)
General Electric Company, Schenectady, New York

ABSTRACT deals with the fundamental aspects of applying stabi-


lizers with the alternative input signals, and repre-
The general concepts associated with applying power sys- sents an extension of the concepts presented in the
tem stabilizers utilizing shaft speed, ac bus frequency, paper by Concordia and deMello [2]. The second part of
and electrical power inputs are developed in this first this paper discusses system performance criteria, devel-
part of a three-part paper. This lays the foundation ops tuning concepts which enable attainment of these
for discussion of the tuning concepts and practical criteria, and the relative performance attainable with
aspects of stabilizer application in Parts II and III. practical stabilizer equipment utilizing the three basic
The characteristics of the "plant" through which the input signals. The third part discusses the practical
power system stabilizer must operate are discussed and considerations of tuning equipment in the field and
the implications upon stabilizer tuning and performance equipment design, including minimizing the effects of
are noted. A general approach for analyzing stabilizers torsional destabilization, power system noise, and, when
utilizing an arbitrary input signal is described and using electrical power as an input signal, mechanical
applied to the frequency and electrical power input power variations.
signals.
INTRODUCTION BASIC CONCEPTS

Beginning in the late 1950's and early 1960's most The basic function of a power system stabilizer is
of the new generating units added to electric utility to extend stability limits by modulating generator
systems were equipped with continuously-acting voltage
excitation to provide damping to the oscillations of
regulators. As these units became a larger percentage synchronous machine rotors relative to one another.
of the generating capacity, it became apparent that the These oscillations of concern typically occur in the
voltage regulator action had a detrimental impact upon frequency range of approximately 0.2 to 2.5 Hz, and
the dynamic stability (or perhaps more properly steady- insufficient damping of these oscillations may limit the
state stability) of the power system. Oscillations of
ability to transmit power. To provide damping, the
small magnitude and low frequency often persisted for stabilizer must produce a component of electrical torque
on the rotor which is in phase with speed variations.
long periods of time and in some cases presented limita- The implementation details differ, depending upon the
tions on power transfer capability. Power system stabi-
lizers were developed to aid in damping these oscilla- stabilizer input signal employed. However, for any
tions via modulation of the generator excitation [1,2]. input signal the transfer function of the stabilizer
The art and science of applying power system stabilizers must compensate for the gain and phase characteristics
has developed considerably over the past ten to fifteen of the excitation system, the generator, and the power
years since the first widespread application to the system, which collectively determine the transfer func-
Western Systems of the United States. This development tion from the stabilizer output to the component of
has involved the use of various tuning techniques and electrical torque which can be modulated via excitation
input signals, and learning to deal with practical control. This transfer function, denoted GEP(s) in this
paper, is strongly influenced by voltage regulator gain,
problems such as noise and interaction with turbine-
generator shaft torsional modes of vibration. generator power level, and ac system strength. This
section discusses the general relationship of these
The desire on the part of the authors' Company to parameters to GEP(s) and hence to stabilizer perform-
ance.
provide stabilizing equipment which allows adjustment
for good power system performance while overcoming the
potential problems associated with noise and torsional The block diagram in Figure 1 illustrates, in terms
destabilization has led to considerable research in this of a few basic small-signal transfer functions, the
area in recent years, involving both analytical studies
relationship between the applied torques on the tur-
and field tests. In 1975, a torsional protective pack- bine-generator shaft and the resulting generator rotor
age was developed for application to stabilizers on
speed, w and rotor angular displacement, 6. The
large two-pole units [3]. The development of similar electricay torque may be considered to have two compo-
protection for four-pole units, with their inherently nents, viz. (a) that which is produced by the power
low torsional frequencies, has required much closer system stabilizer solely by modulation of generator
flux, T ep and (b) that which results from all other
scrutiny of power system stabilizer applications. This
paper describes the results of this research, with
emphasis on the power system performance attainable with
stabilizers utilizing each of the three input signals
considered most feasible: shaft speed, ac bus fre-
quency, and a combination of power and speed. These
results are presented in three parts: the first part
A8
ATm

80 SM 558-7 A paper recommended and approved by the


IEEE Power Generation Committee of the IEEE Power I
Engineering Society for presentation at the IEEE PES AE
Summer Meeting, Minneapolis, Minnesota, July 13-18,
1980.Mianuscript submitted March 14, 1980; made
available for printing May 7, 1980. FIGURE STABILIZER WITH SPEED INPUT -
SYSTEM BLOCK DIAGRAM

-1-
3018
ing a large disturbance, higher gains may be required.
Some utilities [4] set their voltage regulators with
much higher transient gains, on the order of 200 pu
Efd/pu et, to ensure maximum performance. With an
excitation system having relatively little phase lag,
such high gains will result in satisfactory voltage
regulation at light generator loads, but will signifi-
cantly decrease damping of rotor oscillations and may
cause an instability which prevents full load operation
even for relatively strong transmission systems. The
remainder of this paper deals primarily with the more
typical regulator transient gains in the neighborhood of
20 pu Efd/pu Et, although many of the conclusions also
apply when employing high gain exciters.
+
For situations where the voltage regulator loop
crossover frequency is lower than the oscillation fre-
quency of concern, the gain of GEP(s) at the oscillation
frequency can be approximated by its forward path, i.e.:
I rI GEP (j )w
- K EXC(ijw )II/W T (2b)
It is also assumed that 1/K T' is less than the cross-
GEP (s) / over 3 do behind equation 2b are
frequency. The assumptions
usually valid for typical modern units. The gain is
therefore proportional to the exciter gain and inversely
proportional to the main generator open-circuit field
FIGURE 2 SIMPLIFIED MODEL OF SINGLE MACHINE TO INFINITE
time constant and the oscillation frequency. The gain
BUS
is also proportional to the parameter K which repre-
sources, including shaft motion, T The functional sents the effect of a change in generator2 flux (E') on
relationship between speed and torque is shown for a torque, and: q
stabilizer employing generator speed as an input signal.
The contribution of torque due to the stabilizer path is 1. Increases with generator loading.
given by:
2. Increases as the ac system becomes stronger.
AT
PSS (s) GEP(s)
A
= P(s) (1)
Hence, the gain in this portion of the loop is highest
with the generator at full load and operating into the
G strongest ac system.

(In this case speed input is used for clarity; extension For situations where the voltage regulator loop
to other input signals will be discussed subsequently.) crossover frequency is higher than the oscillation fre-
The transfer function GEP(s) represents the characteris- quency of concern, as it is in the case of very high
tics of the generator, the excitation system, and the regulator gain, the gain of GEP(s) is no longer pro-
power system. This transfer function can be approxi- portional to regulator gain but is inversely propor-
mated with the aid of Figure 2, representing a simpli- tional to the parameter K5
as indicated by equation 2a.
K represents the effect of E' on terminal voltage,
fied model of a machine connected to a large power
system through a transmission line as derived in Refer- which decreases as the ac systea becomes stronger and
ence 2. Study of this figure reveals that the dynamic hence causes the gain of GEP(s) to further increase as
characteristics of GEP(s) are proportional to those of the system strength increases.
the closed loop voltage regulator when the generator
speed is constant (AWG = 0), i.e.: Since the voltage regulator open-loop gain is
proportional to K6, the crossover frequency decreases as
the ac system becomes stronger. This influences stabi-
K aEt lizer performance, as there will be more phase lag to
GEP(s) - -

K6 3E
ref overcome with a strong ac system than with a weak ac
system. This effect is most pronounced with high volt-
This relationship forms the basis of stabilizer tuning age regulator gain since the crossover frequency is in
procedures which involve measurement of the closed-loop the same range as the intermachine oscillations of
voltage regulator characteristic to determine the phase concern.
compensation required of the stabilizer.
In summary, the power system stabilizer must oper-
The variation of GEP(s) with exciter gain, gener- ate through the "plant" GEP(s) which is dependent upon
ator loading, and ac system strength plays a dominant the generator, the excitation system, and the power
role in power system stabilizer tuning requirements and system. The basic characteristics of this plant which
performance. The closed-loop voltage regulator response are significant to stabilizer applications are as fol-
is primarily a function of the exciter characteristics lows:
and the ac system strength. Modern turbine-generators
typically have a voltage regulator transient gain (i.e., 1. The phase characteristics of GEP(s) are nearly
the gain in the frequency range of intermachine oscilla- identical to the phase characteristics of the
tions, viz, 0.2 to 2.5 Hz) of approximately 20 pu closed loop voltage regulator.
Efd/pu 't, which results in a voltage regulator loop 2. The gain of GEP(s) increases with generator load.
crossover at approximately 1 rad/sec with a nominal ac
system [2]. Experience has indicated that this gain
results in satisfactory operation over a fairly wide 3. The gain of GEP(s) increases as the ac system
range of system conditions. However, to obtain full becomes stronger. This effect is amplified with
benefit from high ceiling exciters for stability follow- high gain voltage regulators.
3019
4. For typical voltage regulator transient gains of Frequency Input
the order of 20 pu Efd/pu &t' the gain of GEP(s) at
the oscillation frequencies of concern is propor- The use of ac bus frequency as a stabilizer input
tional to the regulator gain and inversely pro- results in tuning procedures and performance character-
portional to the main generator open-circuit time istics somewhat different from those associated with
constant and the oscillation frequency. speed input stabilizers. The primary difference is that
the sensitivity of the frequency signal to rotor oscil-
5. The phase lag of GEP(s) increases as the ac system lations increases as the external transmission system
becomes stronger. This has the greatest influence becomes weaker, which tends to offset the reduction in
with high gain exciters, since the voltage regu- gain from stabilizer output to electrical torque,
lator loop crossover frequency approaches that of GEP(s), resulting with weaker transmission systems.
the oscillation of concern. This effect can be understood by utilizing the input
signal sensitivity factor concept developed in Appendix
CHARACTERISTICS OF ALTERNATIVE INPUT SIGNALS- B. This factor represents the transfer function from
speed to the stabilizer input signal, in this case ac
The general frequency response characteristics of bus frequency:
stabilizers utilizing alternative input signals are
discussed in this section, together with the basic
concepts governing the tuning aspects and performance
sF (s) =
af/awG (4)
capabilities. Speed input stabilizers are discussed
first, followed by an extension to frequency and power S (s) ranges from zero in the extreme case of a unit
input stabilizers. connected to an infinitely stiff system, to unity with
the unit under open circuit conditions. Between these
Speed Input extremes, one approximation of S (s) would be to equate
it to a voltage division between Fhe internal voltage of
A power system stabilizer utilizing shaft speed as the machine and the voltage of the infinite bus, i.e.:
an input must compensate for the lags in GEP(s) to pro- 1\1
duce a component of torque in phase with speed changes s X /[X + XGEN (s)] (5)
so as to increase damping of the rotor oscillations, as
detailed in Appendix A. An ideal stabilizer character-
istic would therefore be inversely proportional to This approximation is valid only for manual control,
GEP(s), i.e.: since, as described in Appendix B, there exists an
additional path from speed to the input signal via the
Ideal PSS (s) = Dp55/GEP(s) (3a) voltage regulator. This effect can be included by
calculating the effective internal impedance of the
generator with the voltage regulator and including this
where DPS represents the desired damping contribution in equation 5. For typical voltage regulator gains, the
of the stabilizer (detailed in Appendix A). Such a effective impedance of the machine is approximately
stabilizer characteristic is impractical since perfect equal to the subtransient reactance over the frequency
compensation for the lags of GEP(s) requires pure dif- range of interest to stabilizer application.
ferentiation with its associated high gain at high
frequencies. A practical speed stabilizer must utilize The off-setting effect of this characteristic is
lead/lag stages set to compensate for phase lags in illustrated in Figure 3, which shows the change in SF O
GEP(s) over the frequency range of interest. The gain Hz) calculated for a large fossil unit versus external
must be attenuated at high frequencies to limit the system impedance, and the compound effect of the in-
impact of noise and minimize torsional interaction, and crease in sensitivity with decrease in gain through
consequently low-pass and possibly band-reject [1] GEP(s) (the latter being proportional to the parameter
filters are required. A washout stage is included to K2 as previously indicated). The gain changes of K2 and
prevent steady-state voltage offsets as system frequency S with external system reactance tend to off-set each
changes. other with the result that the net gain from generator
speed (wG) to electrical torque (T ep) is reasonably
T s (l+sT1)(l+sT3) constant for a wide range of system reactances. For
Practical PSS (s) = K w
very low values of system reactance, the gain is re-
s(l+Tws) (l+sT2)(l+sT4) FILT(s)
duced. Hence, this analysis suggests that the gain of
(3b) the stabilizer may be adjusted to obtain the best possi-
ble performance under weak ac transmission system condi-
As discussed in the previous section the stabilizer tions, where the contribution of the stabilizer is
must operate through GEP(s), the characteristics of required most, without concern that the gain will be
which vary significantly with operating conditions. The excessive and cause the stabilizer to become unstable
gain increases as generator load increases, which is under strong system conditions.
desirable since the stability problems for which the
stabilizer is applied also increase with generator load. In addition, the frequency signal is more sensitive
However, the gain is very high for strong ac systems to modes of oscillation between power plants or large
where the stability problem is minimal, and decreases as areas than to modes involving only individual units,
the ac system becomes weaker. The latter effect causes including those between units within a power plant.
the influence of a speed input stabilizer to decrease This follows since the frequency at an ac bus between
when the power system requires it most. In addition to units is near a node for the latter modes of oscilla-
the fact that gain increases as the system becomes tion, whereas it is largely responsive to modes wherein
stronger, the phase lag also increases. As a conse- the units swing coherently. As a consequence, it ap-
quence, the stabilizer loop of Figure 1 is least stable pears to be possible to obtain greater damping contribu-
under strong ac system conditions, and therefore these tion for modes of oscillation between plants or areas
conditions establish the maximum permissible gain of the than would be obtainable with the speed input.
speed input stabilizer. Without adaptive gain control,
the stabilizer gain can not be as high as desired under Power Input
weak ac system conditions when the stabilizer contribu-
tion is needed most. The use of accelerating power as an input signal to
the power system stabilizer has recently received con-
3020
approach is to utilize the input signal sensitivity
factor concept, i.e., treat electrical power changes as
1.6 resulting from speed changes via the electric power
system, rather than causing speed changes. This ap-
proach yields insight into the generic differences
between power input and speed input stabilizers, partic-
ularly with regard to torsional interaction, as outlined
1.4 in the following discussion.
The input signal sensitivity factor for power is:
aP a(TewG) aTe
1.2 S (s) = e = (6a)
P
wG
w
eWG aw

1.0
wb Kle(s) + p

s eo (6b)

- wb Kle(s (1 + S/W))
POw (6c)
.8
-
where T,eX Pe, and wG are all in per unit on a con-
sistent base.
z
.6 This input signal sensitivity factor is dominated by the
(D first term of equation 6 for the low frequencies of
concern, since the lowest value of Kle is approximately
0.5 p.u./radian (for weak transmission systems) and with
BUS Peo maximum at 1.0 p.u. the break from the integral term
to the proporational term (w ) occurs at approximately
4
one-half synchronous frequency, i.e., near 30 Hz. This
INPUT implies that electrical power and torque are equivalent
ACTOR SF with respect to stabilizer performance for most subsyn-
chronous modes of oscillation. Since the input signal
.2 sensitivity factor for power has primarily an integral
characteristic, with approximately 900 of phase lag in
the frequency range of interest, it would appear that an
additional 90 of phase lead would be required in the
stabilizer. However, a non-minimum phase approach can
0 be utilized with the power input stabilizer, i.e., a lag
0 .2 .4 .6 .8 1.0 characteristic having 270° of phase shift can be used
TOTAL XE (P.U.) rather than a lead characteristic having 900 of phase
shift. The advantage of this approach is that the lag
characteristic yields a closed-loop interaction with
FIGURE 3 COMPENSATION OF GAIN BY FREQUE :NCY INPUT shaft oscillations which exhibits a decreasing gain with
SENSITIVITY FACTOR frequency, as opposed to the increasing gain with fre-
quency associated with the minimum-phase approach uti-
siderable attention due to its inherent low level of lizing a lead characteristic. Thus, the torsional
torsional interaction [5]. Practical di fficulties of interaction characteristics of ideal minimum versus
eliminating, or at least minimizing, t]he effect of non-minimum phase stabilizers diverge at a rate of 40
mechanical power changes appear to have bee.n overcome by db/decade as the torsional frequency increases, with
utilizing a heavily filtered speed signLal [6] which equal interaction at the local mode of oscillation
approximately corrects for mechanical powe.r variations. (assuming gains set for equal local mode performance).
The following analysis applies only to thLe closed loop A discussion of non-minimum phase stabilizers is in-
characteristics of electrical power feedb ack; however, cluded in Appendix C.
it must be recognized that a practical pouwer stabilizer
requires some compensating device for mec hanical power The phase lag of 270 can be obtained by inverting
variations. the electrical power signal and designing the stabilizer
such that the net contribution of the stabilizer and
The most common approach to analyziing the power GEP(s) produces 90Y of phase lag by an integral charac-
input stabilizer is to treat its input as tthe derivative teristic. With this criteria, an ideal stabilizer for
of speed and apply the same concepts utili2zed in analyz- power is defined by:
ing the speed input stabilizer. This appiroach leads to
the conclusion that the performance charactteristics of a
power input stabilizer are identical to th( Dse of a speed Ideal PSSp(s) = - GEPSS (7)
P sGEP (s)
input stabilizer. This conclusion is vralid for the
var: .jus power system modes of oscillatiLon where the
shaft behaves as a rigid body (provided t-he mechanical Note that this result is the same as would be obtained
power changes are compensated for so that tthe stabilizer by treating power as the derivative of speed, since
input is a true measure of average acceleraiting power on inverting P and integrating would yield speed, and
the turbine-generator). For shaft torsiconal modes of multiplying %y the ideal PSSw(s) from equation 3 would
vibration, however, the accelerating power on the gener- give equation 7.
ator rotor alone is considerably differ ent than the
average accelerating power across the entiire shaft, and
hence treating the stabilizer input signal as the deriv-
ative of generator speed is invalid. Ain alternative
3021
The frequency response of such a stabilizer is lizer application which follow. The characteristics of
shown in Figure 4. At low frequencies, lag must be the "plant" through which the power system stabilizer
introduced to compensate for the low phase lag of must operate i.e., the generator, exciter, and power
GEP(s), while at higher frequencies the stabilizer must system, denoted GEP(s), are such that the gain increases
add phase lead to compensate for the secondary lags of with generator loading and ac system strength. Also,
both GEP(s) and the stabilizer. Extending the lag at the phase lag of the "plant" increases as the ac system
low frequencies and the lead at high frequencies is becomes stronger. For stabilizers utilizing speed and
impractical, because of noise at the high frequencies power as inputs, these characteristics imply that the
and because of potentially excessive voltage offsets for stabilizer must be tuned for the case of the strong ac
low frequency phenomena on the power system, including system, and that the performance will decrease as the ac
changes in mechanical power if it is not perfectly system becomes weaker. Utilizing ac bus frequency as an
compensated to provide a pure accelerating power signal input, however, results in characteristics which dimin-
for the stabilizer. The low frequency gain is reduced ish the effect of ac transmission strength on the stabi-
by using a time constant rather than a pure integral, lizer performance, and thereby allow tuning for the weak
equivalent to the washout stage of speed input stabi- ac system condition. In addition, a frequency input
lizer. The combination of a small lead/lag stage and a stabilizer is less sensitive to modes of oscillation
lag at high frequencies provides a desirable declining associated with individual units, and more sensitive to
gain with frequency while maintaining adequate phase power swings between areas than either the speed or
near the highest local mode frequency. A practical power input stabilizers.
power input stabilizer would therefore have the fre-
quency response shown by the dashed line in Figure 4. Stabilizers utilizing power as an input can be
designed with a non-minimum phase characteristic, effec-
tively utilizing lag networks rather than the lead
networks associated with the minimum phase characteris-
tic utilized with speed or frequency input. This allows
damping performance equivalent to a speed input stabi-
100 lizer but with lower gain at high frequencies. In
particular, the interaction with torsional modes of
shaft vibration exhibits a declining gain versus fre-
quency characteristic as opposed to the increasing gain
with frequency associated with speed or frequency input
stabilizers. While this non-minimum phase characteris-
tic is less sensitive to high frequency noise and tor-
sional interaction, it is sensitive to low frequency
I0 phenomena, such as changes in mechanical power, and
power input stabilizers must therefore be provided with
compensation for these variations. If this is done with
washout stages, phase lead is introduced at low fre-
quencies which is detrimental to stability of interarea
-c swings.
LJ
cr-
REFERENCES
1) F.R. Schleif, H.D. Hunkins, G.E. Martin, E.E.
Hattan, "Excitation Control to Improve Powerline
Stability", IEEE Trans. Vol. PAS-87, June, 1968,
pp. 1426-1434.
2) C. Concordia, F.P. deMello, "Concepts of Synchro-
nous Machine Stability as Affected by Excitation
0.1 Control", IEEE Trans. Vol. PAS-88, April 1969, pp.
0.1 I0 316-329.
w4 RAD/SEC)
3) R.A. Lawson, D.A. Swann, G.F. Wright,, "Minimization
of Power System Stabilizer Torsional Interaction on
FIGURE 4 POWER INPUT STABILIZER. IDEAL AND PRACTICAL Large Turbine-Generator", IEEE Trans., Vol. PAS-97,
January/February 1978, pp. 183-190.
It should be noted that imperfect steady-state
compensation for power changes would necessitate adding 4) P. Kundur, D.C. Lee, H.M. Zein El-Din, "Power
a washout stage, which is equivalent to a second washout System Stabilizers for Thermal Units: Analytical
stage in a speed input stabilizer. The resulting phase Techniques and On-Site Validation", Paper F80-227-9
lead would be detrimental to the stabilizer performance presented at IEEE PES Winter Meeting, New York,
since, as described in Appendix A, it introduces a February 1980.
desynchronizing component of torque. Interarea modes
often have very little synchronizing torque due to 5) J.P. Bayne, D.C. Lee, W. Watson, "A Power System
relatively weak, heavily loaded ties, and adding a Stabilizer Stabilizing Signal for Thermal Units
desynchronizing effect via a power system stabilizer can Based on Derivation of Accelerating Power", IEEE
cause areas to lose synchronism following a relatively Trans. Vol PAS-96, November/December 1977, pp.
minor system disturbance under such conditions. 1777-1783.
SUMMARY AND CONCLUSIONS 6) F.P. deMello, L.N. Mannett, J.M. Undrill, "Prac-
tical Approaches to Supplementary Stabilizing from
The general concepts associated with applying power Accelerating Power", IEEE Trans. Vol PAS-97, Sep-
system stabilizers utilizing speed, frequency, or power tember/October 1978, pp. 1515-1522.
input signals have been described in this part of a
three-part paper, laying the foundation for discussion
of the tuning concepts and practical aspects of stabi-
3022
APPENDIX A APPENDIX B
Initial Impact of PSS Upon Analysis of Power System Stabilizer Application
Rotor Oscillation Eigenvalues With an Arbitrary Input Signal

It is shown here that the eigenvalue nominally When using an input signal other than shaft speed
associated with the rotor oscillation mode of interest for the power system stabilizer, two additional factors
initially moves an amount proportional to stabilizer must be considered in the analysis. The first is the
gain as the gain is increased from zero, and in a direc- "input signal sensitivity factor" which represents the
tion determined by the net phase of the stabilizer, transfer function from shaft speed to the signal being
excitation system, generator and power system. This used as a stabilizer input. This transfer function is
concept is useful in understanding the relationship in series with the stabilizer loop and thereby directly
between the phase characteristics of the stabilizer path influences the performance. The second factor is the
from speed to torque and performance of the power system "stabilizer inner loop" which is formed by virtue of the
with the stabilizer loop closed. We start with the stabilizer output having an effect upon its input signal
eigenvalue expressed approximately as per equation Al, independent of shaft speed, via flux changes in the
where it is assumed that the damping is light. generator. This is illustrated in Figure B1 which shows
the stabilizer path from shaft speed to electrical
Dv torque with an arbitrary input signal X. This can be
1
-
+
-
J MM =
_
i- jw i
i+ (Al) expressed mathematically as:
AX = SX(S) AWG + FBX(s) AEpss (Bla)
Adding the power system stabilizer results in effective
damping and synchronizing component contributions: = ) AwG + FBx(s) PSX(s) AX (Blb)
aT
P(s) = ep due to adding PSS (A2a) X = stabilizer input signal
aWG w generator shaft speed
EGpss stabilizer output signal

=
DpSS(wi) -
iW.1 KpSS(Wi) (A2b)
SX(S) =
axG
aM,

= "input signal sensitivity factor"


Including this contribution in the expression for the FB (s) = ax
eigenvalue results in equation A3, and A4 represents the BE pss
change expressed in terms of the damping and synchroniz-
ing contributions of the stabilizer. ="input signal feedback factor"

1L
+ aI = - °(D+D
214
PSS) + j
wb
(Ko+KPSS)
14 (A3)
The resulting contribution of the stabilizer path is
therefore:

Au. =
1
Dp55(Wj) (A4a)
P(S) =
A\Tep/ G
= Sx(s) PSSx(s) GEP(s)/[l - FBx(s) PSSx(s)] (B2)
AWi 2M KpSS(Wi) W (A4b)

From equation A4, it is seen that the change in the real


and imaginary components of the eigenvalue are propor-
tional to the real and imaginary components of the'
contribution of the stabilizer path, and hence the
change in eigenvalue is related to this stabilizer
contribution:
A.1 = -
2iF P(jw
Piw~ (A5)
AWG
Note that a zero phase characteristic for Pjw.)
will cause the real part of the eigenvalue to increase
in a negative direction, which implies positive damping. FIGURE BI STABILIZER LOOPS WITH ARBITRARY INPUT X
Phase lag in P(jw.) results in a positive synchronizing
component (as per equation A2c) and an increase in fre-
quency. Conversely, phase lead yields a negative syn- The impact of the stabilizer inner loop, which appears
chronizing contribution and a decrease in frequency. in the denominator term of equation B2, is a function of
the input signal chosen. For the case of shaft speed
input, the feedback term is zero and hence the inner
loop has no effect. As an opposite extreme, utilizing
terminal voltage for stabilization would result in a
very large feedback term and a low sensitivity factor.
For ac bus frequency as a stabilizer input, the feedback
term is sufficiently small and, at least for analyzing
the inpact of the stabilizer as its gain is increased
from zero, the feedback term can be neglected, resulting
in the approximation of equation B3.
3023

P(s) ~ P'(s) = Sx(s) PSSx(s) GEP(s) (C3) Note that an additional zero at the origin is introduced
into the loop when using power as opposed to speed
input.
where P'(s) represents the forward part of the stabi-
lizer path. APPENDIX C
It should be noted that the input signal sensitiv- Non-Minimum Phase Stabilizers
ity factor is a function of the voltage regulator as
well as power system conditions such as transmission
line strength. This follows since the stabilizer input The objective of a power system stabilizer is to
signal is sensitive to changes in the voltage error add damping to rotor oscillations, which is accomplished
signal (in the same manner it is affected by stabilizer by modulating voltage regulator setpoint such that
output signal), and the voltage is affected by shaft resulting torque changes are in phase with shaft speed.
speed. This can be expressed mathematically as follows: In conventional stabilizers lead networks are provided
to compensate for the phase lags associated with the
Ae t =AE ref +tE pss -AE t (B4) generator and excitation system (GEP(s) of Figure 1),
resulting in a "minimum phase" control loop.
B8t/BWG = - S (B5)
An alternative approach is to add appropriate lag
Sx(s) = S (s) - SEM (s) FB(s) (B6) networks such that the net phase is -360 at the fre-
quency of concern, resulting in a "non-minimum phase"
where SM, SEM = input signal sensitivity factors for X control loop. Figure Cl gives an example where the 3600
and Et, respectively, under manual control (i.e., volt- phase lag is accomplished by:
age regulator gain = 0).
P(s) = GEP(s) PSS w(s) = - Kw/s (C1)
The input signal feedback factor (FBx(s)) repre-
sents the effect of a change in stabilizer output upon
the input signal via flux changes in the generator, and In this figure, all other contributions to torque have
hence includes the closed-loop voltage regulator charac- been lumped into the effective synchronizing constant
teristics. K (s) defined in equati-on 6.
To analyze the closed-loop performance of the power
system with a stabilizer, it is useful to consider the
stabilizer as closing a loop around a system which
includes both the input signal feedback factor and the
A8
rotor. Based on Figure Bl, this can be expressed as: ATn
Gx(s) = FBx(s) + GEP(s) R(s) SX(S) (B7)
where
R(s) = -s/(MS + Kle(s) wb) (B8a)
=- -
"
2 2
S/M(s _2a.s
3
+ W.)
IL
(B8b)
FIGURE Cl NON-MINIMUM PHASE SPEED INPUT STABILIZER
The open-loop transfer function of the system is With a speed input stabilizer yielding a pure
then double-integral characteristic, as per equation Cl, an
instability will result as soon as the gain is increased
from zero. This can be understood by examining the
GHX(s) = Gx(s) PSSX(S) (B9a) nature of the control loop. From Figure Cl, the forward
path can be defined as R(s) as per equation B8, with the
= GxCs) P'(s)/S xs) GEP(s) (B9b) feedback path P(s) as per equation Cl. The system has a
net of one open-loop pole at the origin, since one of
For speed input, the poles of the stabilizer path is cancelled by the
FBw is zero and S w is unity, zero of R(s). In addition, there exists a complex pair
hence: associated with rotor oscillations. Since the open loop
gain is inverted in sign, when K is increased the
Gw (s) = GEP(s) R(s) (B1O) complex poles will move further into the left-half plane
and become more stable, but the pole at the origin will
For power input, FB can be determined by realizing that move towards the right-half plane and become unstable
it represents the Peffect of stabilizer output signal immediately. This is illustrated in Figure C2a.
upon power independent of shaft motion. Hence power and
torque are equivalent and the feedback factor becomes: Thus, to successfully implement a non-minimum phase
stabilizer with speed input it is necessary to use a
BP time constant at a low frequency rather than a pure
aT integral characteristic, i.e.:
FB (s) BE e
= =
= GEP(s) (Bll)
p -pss Epss P(s) = GEP(s) PSSw (s) ~= - K /s(w + s) (C3)
w s
Using the power input signal sensitivity factoir from
equation 5, together with equations B7, B8, an.d Ri1, The pole at the origin has now been shifted into the
results in: left-half plane by w . This pole will still move
towards the right-halt plane and eventually become
G (s) = s GEP(s) R(s) (B12) unstable, but will permit some damping contribution to
rotor oscillations as shown in Figure C2b.
3024

4 wtG = generator shaft speed.

-Kw -KW
6 = generator shaft angular displace-
S2 (s )S El - generator internal voltage.
q
Efd = generator field voltage.
Kinst :Q Kinst >0
Et = generator terminal voltage.
-ws
Ef = voltage reference signal.
(a) (b) Eref
£t
----- error signal.
FIGURE C2 ROOT LOCt WITH NON-MINIMUM - PHASE SPEED INPUT STABILIZER

To analyze the characteristics of the power input PSSX(S) = stabilizer with input X.
stabilizer, the concepts developed in Appendix B for an
arbitrary input signal are utilized. First, a develop- EXC (s) = excitation system =
AEfd/A&t-
ment parallel to that used above for speed input is
followed. Utilizing equations B2, Bll, and B3 yields Wub system base frequency (377 rad/sec @
the following for the stabilizer path with power input: 60 Hz).
stabilizer gain.
P(s) = Sp(s) PSSp (s) GEP(s)/[l - GEP(s) PSSp (s)] (C4a) KS
= P'(s)/[l - P'(s)/Sp(s)] (C4b) Tw washout time constant.

T1T 2T3sT4 lead/lag time constants.


To provide a non-minimum phase characteristic for low
values of stabilizer gain, the forward part of the FILT(s) filtering in stabilizer.
stabilizer path, P(s), is set to the double-integral
characteristic of equation Cl, with S (s) from equation x- -reactance external to generator.
e
6c assuming w = . Including the effect of the stabi- effective reactance of generator.
lizer inner 1Toop by substituting into equation C4b GEN
yields the following for the stabilizer contribution: pe electrical power.
P(s) = - K/s[(K/K le(s) tu) + s)] (C5) p eo steady-state power level.
K1 (s) effective synchronizing coefficient,
Note that including the stabilizer inner loop has re- AT /36, including all sources other
sulted in a stabilizer contribution which is actually an than stabilizer path.
integral plus a time constant similar to equation C3.
Unlike the breakpoint w introduced into the stabilizer
with speed input, however, the breakpoint in equation C5
w
-po
wb Kle(S)/Peo
is inherently proportional to the gain of the stabilizer th
A. eigenvalue associated with i- mode
forward path, K, and hence suggests that the pole asso- 1
of rotor oscillation.
ciated with this breakpoint will not become unstable as th
the gain is increased. This can be verified by deter-
W. rotor oscillation frequency of i-
mining the open-loop transfer function as per equation mode.
B9b with the ideal characteristic of equation Cl for
P'(s), equation B12 for the system, and equation 6 for ci. " ----- damping ------
the input siganl sensitivity factor:
GH (s) = R(s)K/w% Kl(s) (1 + s/wtu) (C6) Dp55,Kp55 effective damping and synchronizing
coefficients resulting from stabi-
lizer path.
This ideal open-loop transfer function has less than D ,K damping and synchronizing coeffi-
1800 of phase lag at low frequency, and hence the non- 0o 0 cients.
minimum phase characteristic can be implemented with
power input without having the low frequency instability M inertia of turbine-generator shaft.
which is associated with a speed input non-minimum phase
stabilizer. feedback =
LIST OF SYMBOLS
FBX (s) input
8X/8Ep55.
signal factor

P (s) ATTpl/wG neglecting FBX(s).


GEP.(s) = T /AE PSS = 'plant"
through which
stanilizer must operate. Gx(s) AX/E PSS including rotor motion.
T
e
= generator electrical torque. R(s) = WG/ATep
of
T
ep
= component of T due solely to flux
changes caused Cy Ep55.
GHX(s) = open-loop
stabilizer control loop.
transfer function

T eo = component of T due to all other The following are defined in [2]:


sources (= T e - fep ).
K3 ZE /REfd
K1 = T
e/m6 K
2
=
3T /WE
e q
=

stabilizer output signal.


EPSS =

K5 =
3Et/36 K
6
=
aE /aEE
t q
Tm = mechanical torque.
For Combined discussion see page 3024

Potrebbero piacerti anche