Service & Factory Logs can be downloaded from Transfix devices, either remotely over a network,
or directly from a Transfix via a USB connection.
http://www.kelman.co.uk/downloads/transfix/KelmanDownload_1.0.10.zip
To configure the download, use the menu option “Tools>Download Service Logs..”. The dialog
shown in Figure 2 opens.
40-0147-05 Page 1 of 7
Transfix Download Service Logs
For a USB direct connection, you just have to
supply the destination folder on your laptop.
Note: You must use the USB port inside the
Transfix, behind the Control panel.
To install the utility, open the zip file and run the executable file. Click Next.
40-0147-05 Page 2 of 7
Transfix Download Service Logs
Create a desktop icon if required and click next,
40-0147-05 Page 3 of 7
Transfix Download Service Logs
To run the Download Utility
USB Connection
TRANSFIX 1.0 and TRANSFIX 1.5 (TX1-A000nnn, TX1-B000nnn or TX1-C000nnn) will use the main
USB connection on the TRANSFIX panel. TRANSFIX 1.6 (Serial No TX1-D000nnn), MULTITRANS,
TAPTRANS and MINITRANS will use a mini-USB connection to the USB port on the circuit board
inside the Kelman units.
40-0147-05 Page 4 of 7
Transfix Download Service Logs
Connect the PC to the USB port. Click Start.
The program will search for Kelman instruments on the COM ports. When the analyser is found a
message will appear on the screen “Kelman TRANSFIX found on COM#”
Network Connection
Input the IP address and port (default 502) or search local network for devices. When search is
complete, select the required Kelman analyser. If the analyser is Transfix type A/B check the box
(serial no. TX1-A000nnn, TX1-B000nnn or TX1-C000nnn).
For other types of analyser (Transfix Serial No TX1-D000nnn, Multitrans, Taptrans, Minitrans)
network connection requires a password – apply to GE Energy M&D representative for the
Pincode of the Month. Enter Pincode type and Pincode in the appropriate boxes.
Click on Start.
40-0147-05 Page 5 of 7
Transfix Download Service Logs
All Connection Types Download
When the instrument is found, the download will start with the measurement records.
40-0147-05 Page 6 of 7
Transfix Download Service Logs
The Download Utility will then create a zip file that contains the measurement data and
the techlog file and place it on the Desktop. You can copy this file and paste it into an e -mail.
Click Exit to close the utility.
Send the zip file to your GE Energy M&D Sales contact and ge4service@ge.com with an
explanation of the problem and the serial number of the Kelman analyser.
40-0147-05 Page 7 of 7
Transfix Download Service Logs