Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
DOI 10.1002/suco.201600057
TECHNICAL PAPER
1
CERIS/ICIST, Civil Engineering Department,
Faculty of Sciences & Technology, Universidade The design of anchorage corner blisters for internal continuity posttensioning ten-
NOVA de Lisboa, Caparica, Portugal dons in bridges built using the cantilever method presents some peculiarities
2
Ganz Consulting, Zurich, Switzerland because they are intermediate eccentric anchorages. The simplified formulas for
Correspondence designing the reinforcement required to resist transverse tensile forces due to the
Carla Marchão, CERIS/ICIST, Civil Engineering
application of point loads, as proposed by the current standards, are not sufficient
Department, Faculty of Sciences & Technology,
Universidade NOVA de Lisboa, Campus da because they do not cover all the effects that require reinforcement. The high den-
Caparica, Caparica 2829-516, Portugal. sity of steel reinforcement in anchorage blisters is the most common reason for
Email: c.marchao@fct.unl.pt problems with concrete cast in situ, resulting in zones with low concrete compact-
Funding information ness, which may lead to concrete crushing failures under the anchor plates. The
FCT/MCTES, The Portuguese Foundation for
Science and Technology, Grant/Award number:
solution to this problem may involve reducing the amount of reinforcement by
SFRH/BD/46257/2008. improving the concrete compressive and tensile strengths. An experimental pro-
gram was carried out to study the transmission of prestressing force to the slab
and web of the box girder, to assess the strut-and-tie models used in design and to
investigate the feasibility of using a high-performance fiber-reinforced self-
compacting mix (HPFRC) in the blister only, with either in situ or precast solu-
tions. It can be concluded that the use of HPFRC in anchorage blisters is a very
interesting solution regarding the savings in materials and the reduction in the
steel reinforcement density near the local anchorage zone, with obvious advan-
tages in concrete quality.
KEYWORDS
334 © 2017 fib. International Federation for Structural Concrete wileyonlinelibrary.com/journal/suco Structural Concrete. 2017;18:334–348.
MARCHÃO ET AL. 335
FIGURE 2 The interior of the Lezíria Bridge box girder. FIGURE 4 Typical specimen cross section—section D-D.
336 MARCHÃO ET AL.
FIGURE 5 Elevation. (a) Reference specimen and (b) HPFRC blister specimens.
applied loads at the ultimate limit state. The action of radial of the positions and directions adopted for the ties, it was
forces due to tendon curvature, both in longitudinal necessary to take into account the fact that the ties should
section and on plan, was considered. Regarding the choice coincide with the corresponding reinforcement. The strut-
and-tie models adopted in the longitudinal sections are
shown in Figure 8.
As shown in Figure 8, in the longitudinal sections, due
to the dispersion of the concentrated prestressing force over
the cross section, it was assumed that the reinforcement
needed should be parallel to the front face of the blister
(perpendicular to the applied force). The resultant tie force
(tie 1) was located in the theoretical section where the com-
pression stress field, due to the dispersion of the concen-
trated force, intersects the upper face of the blister.
In the slab between anchorages, the compression was con-
sidered to be uniformly distributed over the slab thickness (for
this purpose, and for simplification, the variation in the slab
thickness at the junction with the web was neglected). There-
fore, two equal struts were adopted located at one-quarter and
three-quarters of the regular slab thickness.
According to Rogowsky and Marti7, and in order to
control cracking, a tieback force amounting to 25% of the
prestressing force was assumed, uniformly distributed over
the slab thickness.
The transverse ties (ties 2) were designed to resist half
of the radial forces due to tendon deviation. The other half
was resisted by the concrete struts that converge at each top
FIGURE 6 Section C-C. (a) Reference specimen and (b) HPFRC blister node. The orientation of the left strut of each node was
specimens. determined by the establishment of equilibrium at the node.
MARCHÃO ET AL. 337
FIGURE 7 Layout of posttensioning tendons—profile. (a) Reference specimen and (b) HPFRC blister specimens.
Corbel and local bending effects (ties 3 and 4 respec- Owing to the fact that the force applied during the test
tively) were also considered. was limited to the failure load of the prestressing tendons
and assuming that concrete failure was not relevant, the steel
reinforcement used in the blister zone was intentionally
2.3 | Specimen design and detailing undersized, the purpose being to try to reach the failure of
The design of the specimen reinforcement was carried out the model during the test. So the reinforcement was designed
based on the tensile forces obtained with the strut-and-tie considering a posttensioning force equal to half the specified
models described above. characteristic value of 0.1% proof force Fp0.1k for seven 0.6-
inch strands (with a nominal area of 150 mm2) and a reinfor-
cing steel tensile strength of 600 MPa, since the reinforcing
steel grade intended for the test would have a characteristic
yield stress fyk = 500 MPa.
The reinforcement detailing is shown in Figure 9. It
should be noted that, in the reference specimen, spiral con-
fining reinforcement was also installed.
The blister volume and total steel reinforcement weight
for the ties considered in the strut-and-tie models are shown
in Table 1 for each specimen.
Comparing both specimens, the volume of the HPFRC
blister is approximately 65% of the volume of the ORC blis-
FIGURE 8 Strut-and tie model—longitudinal section along a tendon. ter. Regarding the steel reinforcement, the difference is
(a) reference specimen and (b) HPFRC blister specimens. smaller, but the adoption of HPFRC results in a reduction
338 MARCHÃO ET AL.
FIGURE 9 Reinforcement in anchorage blister zone. (a) Reference specimen, (b) reference specimen—cross section, (c) HPFRC blister specimens—
longitudinal section, and (d) HPFRC blister specimens—cross section.
of approximately 17% with respect to the value obtained for 2.4 | Reference specimen
the ORC blister. 2.4.1 | Specimen preparation
It can be seen that, in addition to saving materials, the
The specimen was produced by a precast company. The
greatest advantage of adopting HPFRC in the anchorage
blister is the decrease in the steel reinforcement density near strength class requested was C30/37 and a reinforcing
the local anchorage zone, with obvious improvements in the steel with a characteristic yield stress fyk = 500 MPa and
concrete quality. ductility class C was used. The characteristics of the
MARCHÃO ET AL. 339
FIGURE 15 Concrete surface relative displacements versus average load. (a) Relative displacement transducer 3 and (b) relative displacement transducer 5.
It should be noted that the applied load does not corre- • Strain gauges 20 and 22 have the highest strains as they
spond to the measured load because the load cells were are located near the crack that can be seen in
located in the anchorage blister and the posttensioning was Figure 13a.
applied at the opposite end. The difference between the two • Strain gauges 16, 18, 19, and 21 present similar strains
corresponds to the loss of prestressing force by friction because they are located in the legs of the stirrups
(approximately 7% of prestressing force). between the two tendons. Of these, strain gauges 19 and
As can be seen, the measured displacements decrease as 21 have the largest strains, since they are located on the
the transducer gets closer to the web. A residual displace- reinforcement that corresponds to tie 1 of tendon A (see
ment at the end of the first phase of the test can be seen.
Figure 15 presents the evolution of the relative displace-
ments on the concrete surface with the average load for rela-
tive displacement transducers 3 and 5, which recorded crack
openings >0.3 mm (see Figure 16).
The evolution of the strains in the reinforcing steel with
the average measured load is shown in Figure 17 for strain
gauges 16–22, which recorded the larger strain values. Their
locations are shown in Figure 18.
Although the strain values are not directly related to the
tensile force in the ties of the strut-and-tie models used in the
design, the steel reinforcement stresses do reveal the following:
FIGURE 18 Locations of strain gauges on anchorage blister reinforcement. (a) Section C-C, (b) section A-A, and (c) section B-B.
MARCHÃO ET AL. 343
Figure 8), which is the one with the largest tensile force
and smallest ratio between the reinforcement adopted
and the reinforcement required.
2.5 | HPFRC blister specimen FIGURE 20 HPFRC blister specimen before testing.
of the remaining model, its dimensions plus 15 mm were obtain a minimum thickness of 50 mm and avoid
considered corresponding to the concrete cover of the fractures.
web and bottom slab, as shown in Figure 25. Further, the The HPFRC blister was cast upside down, with the sur-
opposite region to the anchorage zone was chamfered to face that will connect to the slab on the top, because it was
FIGURE 23 Concrete surface relative displacements versus average load. (a) Relative displacement transducer 3, (b) relative displacement transducer
4, (c) relative displacement transducer 6, and (d) relative displacement transducer 7.
MARCHÃO ET AL. 345
necessary to leave protruding reinforcement bars, to make TABLE 5 HPFRC precast blister specimen - Concrete characteristics
the subsequent connection to the bottom slab and web of fccm (MPa) fctm (MPa)
the model. OC 49.2 3.4
In the casting of the overall model, it was necessary to HPFRC 126.7 11.3
ensure the complete filling of the area under the anchorage
blister. Thus, vertical pipes were left in the blister so that intentionally roughened with a pneumatic chipping hammer,
any air that accumulated could escape, thus minimizing the as shown in Figure 26.
formation of air pockets at the surface between bottom slab The bottom slab, web, and end block of the specimen
and blister. were cast in ordinary concrete. The strength class requested
The surfaces in contact with the bottom slab and web was C30/37, that is, the same as for the reference specimen.
were a free surface and a surface cast against plywood The reinforcing steel had a characteristic yield stress fyk =
formwork, respectively. To increase the bond at the inter- 500 MPa and ductility class C. The concrete characteristics
face between the two concretes, these surfaces were on the date of the tests are shown in Table 5.
between the anchorage blister and bottom slab, which anchorage zone, with the obvious advantages for concrete
reached a width of approximately 0.3 mm, as can be seen in quality.
Figure 31. The adoption of solutions with HPFRC precast blisters
avoids the need to mix and cast two different concretes on
site. This solution can be advantageous with regard to qual-
ity control in the execution of HPFRC blisters.
3 | CON CLU SION S The use of HPFRC results in numerous advantages,
not only in blisters, but in all anchorage zones for post-
The HPFRC blister specimens showed a very similar behav-
tensioning tendons and also in areas with important point
ior during the test, satisfying all requirements regarding loads.
serviceability and strength. The crack width did not exceed
0.3 mm for the maximum load achieved in the test, which
was 29% higher than the tensioning force of 1,512 kN. ACKNOWLEDGMENTS
Comparing the test results of the HPFRC blister speci-
The cooperation of and supply of materials by VSL, Con-
mens, no significant difference regarding cracking was
cremat, Secil, Comital, MC-Bauchemie, Sika, and Krampe-
observed, except for the crack that formed in the connection
Harex is gratefully acknowledged. The financial support of
between the blister and bottom slab. Measurements by the
FCT/MCTES, the Portuguese Foundation for Science and
relative displacement transducers in that zone showed that
Technology, under Research Grant SFRH/BD/46257/2008,
the relative displacement become higher for the precast blis-
is greatly appreciated.
ter model from a load value of approximately 1,250 kN
onward.
Regarding the steel reinforcement, although the strain REFERENCES
values are not directly related to the tensile force in the 1. Gomes F, Nunes S. Betão auto-compactável reforçado com fibras. Aplicação
ties of the strut-and-tie models used for design but with em zonas de ancoragem de cabos de pré-esforço. Encontro Nacional Betão
Estrutural 2010, 2010; Lisbon, Portugal, 3-20.
the steel reinforcement stress, in most cases the largest
2. Haroon S, Yazdani N, Tawfiq K. Post-tensioned anchorage zone enhance-
strains were measured by the strain gauges located on the ment with fiber-reinforced concrete. J Bridge Eng. 2006;11(5):566-572.
reinforcement that corresponded to ties with the largest 3. Leung CKY, Zhang X, Xia Q. The application of pseudo-ductile cementi-
tensile force. Considering the fact that the reinforcement tious composites in the anchorage zone of post-tensioned concrete members.
Mater Struct. 2009;42:1221-1231.
was undersized, yielding would be expected, which was 4. Ganz HR. Prestressed structural concrete: new developments and applica-
not confirmed (the measured strain values were all below tions. Encontro Nacional Betão Estrutural 2008, 2008; Guimarães, Portu-
the steel yield strain) and was probably due to the exist- gal, 3-20.
5. VSL International. European Technical Approval No. ETA-06/0006, version
ence of other reinforcement for constructional reasons of May 4, 2012, Paris: SETRA, European Organisation for Technical
which can also contribute to the strength, and due to the Approvals; 2012.
fact that the strut-and-tie models do not take into account 6. Marchão C, Lúcio V, Ganz HR. Application of a high performance fiber
reinforced self-compacting concrete in post-tensioning anchorage zones. fib
the tensile strength of the concrete.
Congress, 2014; Mumbai, India.
The use of HPFRC in anchorage corner blisters is a 7. Rogowsky D, Marti P. Detailing for post-tensioning. VSL Report Series
very interesting solution regarding the saving in materials 3. Bern, Switzerland: VSL International Ltd.; 1996.
(35% saving in volume of concrete blister and approxi- 8. European Committee for Standardization. EN 1992-1-1 (Eurocode 2): design
of concrete structures – Part 1.1: general rules and rules for buildings, EN
mately 17% steel reinforcement) and the reduction in the 1992-1-1:2004, Brussels: European Committee for Standardization (CEN);
density of the steel reinforcement near the local 2004.
348 MARCHÃO ET AL.
AUTHOR’S BIOGRAPHIES
Hans Rudolf Ganz
Ganz Consulting
Carla Marchão
Switzerland
Assistant Professor
hganz@sunrise.ch
CERIS/ICIST, Civil Engineering Dept.
Faculty of Sciences & Technology
Universidade NOVA de Lisboa
Caparica, Portugal
c.marchao@fct.unl.pt
Válter Lúcio
Associate Professor
CERIS/ICIST, Civil Engineering Dept.
Faculty of Sciences & Technology
How to cite this article: Marchão C, Lúcio V and
Universidade NOVA de Lisboa
Ganz HR. Optimization of anchorage corner blisters for
Caparica, Portugal
posttensioning tendons. Structural Concrete. 2017;
vjgl@fct.unl.pt
18:334–348. https://doi.org/10.1002/suco.201600057