A WARNING A
Where a metallic water service is to be replaced using non
metallic pipe a licensed electrician shall assess affected
property's electricity supply for defects and the likely
effect on earthing adequacy. Work can commence once the
electrician declares in writing that it is safe to proceed.
200 max.
B B
1
GENERAL NOTES
C C
From Water main To Consumer Property 1. All dimensions in millimeters (mm), unless noted otherwise.
2. Installation and fittings schedule is also suitable for DN.25 meter.
1 1 3. All existing metallic service connections should be considered an electrical hazard and electrical
bridging leads (min. 70 Amp rating) and low voltage insulated gloves should be utilised at all times.
4. Reinstate all surfaces to match existing.
DN.20 METER RENEWAL
5. Reinstall property pressure limiting valve where existing.
1:5 6. Installation must comply with Manufacturer's specifications.
7. Connectors and gate valves must be pressure rated PN16. Minimum body dezincification resistant
D D
brass to AS/NZS 2345 and comply with Potable Water Contact to AS/NZS 4020.
8. Provide additional adaptors to suit the existing property connection materials.
9. All products to be in accordance with City West Water's "Approved Products Catalogue".
SCHEDULE OF ITEMS
10. All copper fittings to be 'Viega pro-press' system, or equivalent.
No. DESCRIPTION
11. All pipes and fittings are to be approved by TasWater.
1 Pipe and Fittings (PN 16 minimum)
2 Nut and Tail Connector
ITEMS SUPPLIED BY TASWATER
3 Ball Valve - W/MRK R/A Lockable Quarter Turn Brass DZR,
1. Water meter - complete with inbuilt strainer and dual check valve.
E
Resilient Seated with Extendable Nut and Tail. E
2. Water meter nuts and tails.
4 'Sensus' Water Meter with Dual Check Valve
3. Valves
Drawing
Number
Rev. 5 Date 31/10/2018 Approved G. HENDERSON References HPRM File Ref. T15/82-006-0004
on site by the user prior to construction.
This drawing is produced on an A3 size sheet,
DO NOT SCALE a sheet plotted at any other size.
ABN: 47 162220 653 TWS-W-0002 01 of 19 5
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Limit of Works
200 ( + 30)
Trafficable Proprietary or in-situ meter boxes with trafficable lids to AS/NZS 3996
B B
GENERAL NOTES
1. All dimensions in millimeters (mm), unless noted otherwise.
4 2 2. Installation and fittings schedule is also suitable for DN.25 meter.
1 1 3. All existing metallic service connections should be considered an electrical hazard and electrical
C
bridging leads (min. 70 Amp rating) and low voltage insulated gloves should be utilised at all times. C
From Water main Nominal single size To consumer property 4. Reinstate all surfaces to match existing.
bluestone bedding 5. Footpaths and paved areas are defined as areas with a Class B wheel loading to AS/NZS 3996.
(50mm thick)
In areas with wheel loading greater than Class B then a polyethylene pit is unsuitable.
6. In footpaths and paved areas the Polyethylene meter box must be supported with an insitu N25
DN.20 METER RENEWAL
concrete surround of minimum dimension 50 wide and 100 deep ('Rapidset' not permitted).
1:5 7. Reinstall property pressure limiting valve where existing.
8. Installation must comply with Manufacturer's specifications.
SCHEDULE OF ITEMS
9. Connectors and gate valves must be pressure rated PN16. Minimum body dezincification resistant
D No. DESCRIPTION D
brass to AS/NZS 2345 and comply with Potable Water Contact to AS/NZS 4020.
1 Pipe and Fittings (PN 16 minimum) 10. Provide additional adaptors to suit the existing property connection materials.
2 Nut and Tail Connector 11. All products to be in accordance with City West Water's "Approved Products Catalogue".
3 Ball Valve - W/MRK R/A Lockable Quarter Turn Brass DZR, 12. All copper fittings to be 'Viega pro-press' system, or equivalent.
Resilient Seated with Extendable Nut and Tail.
13. All pipes and fittings are to be approved by TasWater.
4 'Sensus' Water Meter with Dual Check Valve
ITEMS SUPPLIED BY TASWATER
1. Polyethylene meter box
E
WARNING E
Where a metallic water service is to be replaced using non 2. Water meter - complete with inbuilt strainer and dual check valve.
metallic pipe a licensed electrician shall assess affected
3. Water meter nuts and tails.
property's electricity supply for defects and the likely
effect on earthing adequacy. Work can commence once the 4. Valves
electrician declares in writing that it is safe to proceed.
Drawing
Number
Rev. 5 Date 31/10/2018 Approved G. HENDERSON References HPRM File Ref. T15/82-006-0004
on site by the user prior to construction.
This drawing is produced on an A3 size sheet,
DO NOT SCALE a sheet plotted at any other size.
ABN: 47 162220 653 TWS-W-0002 02 of 19 5
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Limit of Works
Footpath and Paved areas Standard polyethylene meter box with galvanised non-slip lid
200 ( + 30)
(Class B to AS/NZS 3996) ('Draper' Model DRA 30/5)
Trafficable Proprietary or in-situ meter boxes with trafficable lids to AS/NZS 3996
B B
GENERAL NOTES
1. All dimensions in millimeters (mm), unless noted otherwise.
Insitu concrete nib all 2. Installation and fittings schedule is also suitable for DN.25 meter.
around polyethylene
4 2 3. All existing metallic service connections should be considered an electrical hazard and electrical
meter box frame
C
1 1 bridging leads (min. 70 Amp rating) and low voltage insulated gloves should be utilised at all times. C
4. Reinstate all surfaces to match existing.
From Water main Nominal single size To consumer property 5. Footpaths and paved areas are defined as areas with a Class B wheel loading to AS/NZS 3996.
bluestone bedding In areas with wheel loading greater than Class B then a polyethylene pit is unsuitable.
(50mm thick)
6. In footpaths and paved areas the Polyethylene meter box must be supported with an insitu N25
concrete surround of minimum dimension 50 wide and 100 deep ('Rapidset' not permitted).
DN.20 METER RENEWAL
7. Reinstall property pressure limiting valve where existing.
1:5
8. Installation must comply with Manufacturer's specifications.
SCHEDULE OF ITEMS 9. Connectors and gate valves must be pressure rated PN16. Minimum body dezincification resistant
D D
No. DESCRIPTION brass to AS/NZS 2345 and comply with Potable Water Contact to AS/NZS 4020.
1 Pipe and Fittings (PN 16 minimum) 10. Provide additional adaptors to suit the existing property connection materials.
11. All products to be in accordance with City West Water's "Approved Products Catalogue".
2 Nut and Tail Connector
12. All copper fittings to be 'Viega pro-press' system, or equivalent.
3 Ball Valve - W/MRK R/A Lockable Quarter Turn Brass DZR,
Resilient Seated with Extendable Nut and Tail. 13. All pipes and fittings are to be approved by TasWater.
Drawing
Number
Rev. 5 Date 31/10/2018 Approved G. HENDERSON References HPRM File Ref. T15/82-006-0004
on site by the user prior to construction.
This drawing is produced on an A3 size sheet,
DO NOT SCALE a sheet plotted at any other size.
ABN: 47 162220 653 TWS-W-0002 03 of 19 5
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
A A
Saw-cutting line
after coring holes
87
B B
80
Drill 4 - DN.12 holes for
securing bolts
454
279
120
Drill 4 - DN.75 holes
C C
79
88
D CONCRETE DRILLING TEMPLATE D
1:5
Drawing
Number
Rev. 5 Date 31/10/2018 Approved G. HENDERSON References HPRM File Ref. T15/82-006-0004
on site by the user prior to construction.
This drawing is produced on an A3 size sheet,
DO NOT SCALE a sheet plotted at any other size.
ABN: 47 162220 653 TWS-W-0002 04 of 19 5
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
TABLE 1
TasWater Responsibility Property Owner Responsibility
LOCATION METER BOX TYPE
(incl. meter box)
Connection
Non Trafficable Standard polyethylene meter box with green non-slip lid
Point
A A
Property bdy.
(Class A to AS/NZS 3996 - extra light duty) ('Draper' Model DRA 20/3, or simiar approved)
500 Meter box
Footpath and Paved areas Alluminium alloy meter box with alloy non-slip lid Refer Table 1 Concrete nib in
75
footpath and paved areas
(Class B to AS/NZS 3996 - light duty) ('Bennet & Kingston' box and lid, or similar approved)
Existing surface
65
(+ 25)
Road surface
200
300 Min.
W.S.A.A. guidelines
B B
Cover as per
Connect to water main Pipework
in accordance with WSA-W111 to property
3 2 1 4
and TasWater Supplement
Flow Mass concrete plinth in Bedding (50 min. thick)
footpath and paved areas. 7 (Nom.) clean, single size metal
SCHEDULE OF ITEMS
DN.100 Sleeve for non-metallic No. DESCRIPTION COMMENTS
pipes in trafficable areas. 1 'Sensus' Water Meter with Dual Check Valve Supplied by TasWater
2 Ball Valve - W/MRK Lockable Quarter Turn Brass DZR, Resilient Seated with Extendable Nut and Tail Supplied by TasWater
3 Pipe and Fittings (PN.16 minimum)
GENERAL NOTES
1. All dimensions in millimeters (mm), unless noted otherwise.
2. Water connection to be located next to driveway entrance.
VALVE & EQUIPMENT SCHEDULE 3. Water connection point to be located between driveway entrance and nearest side boundary,
1. Only use products with watermark certification and approved for use by TasWater and listed within unless otherwise approved.
City West Water's approved products catalogue. 4. Light trafficable areas are defined as areas with Class 'B' wheel loadings to AS/NZS 3996. In areas with wheel
2. Installation must comply with manufacturer's written instructions loadings greater than Class 'B' then an aluminium alloy pit with concrete surround is unsuitable.
E 3. TPFNR ferrule cock, connectors, tapping band and gate valve must be pressure rated PN16 minimum 5. In rural and semi-rural situations the cast iron mains cover may be replaced with a DN.150 PVC end connection E
body dezincification brass to AS/NZS 2345 and comply with potable water contact to AS/NZS 4020. and screw cap where approved by authorised officer.
4. All valves must be resilient seated, clockwise closing to AS 1628 with 316 stainless steel bolts and washers. 6. Refer to TasWater's boundary backflow containment guidelines for hazard ratings.
5. In footpaths and paved areas the meter box must be supported with insitu N25 concrete. 7. Any pressure limiting valves installed under the requirements of clause 3.3.4 of AS.3500.1-2003 are to be installed
outside of and downstream of the meter box.
6. Unless approved otherwise the water meter/s, tails and meter boxes are to be supplied by TasWater.
8. After installation of meter, TasWater must be notified by returning meter sheet to "Development@taswater.com.au"
0 0.2 0.4 0.6 0.8 1.0 metres stating TasWater reference number in subject line.
SCALE - 1 : 10 9. Failure to install or contact TasWater after installation will result in non issue of any compliance certificates.
Drawing
Number
Rev. 5 Date 31/10/2018 Approved G. HENDERSON References HPRM File Ref. T15/82-006-0004
on site by the user prior to construction.
This drawing is produced on an A3 size sheet,
DO NOT SCALE a sheet plotted at any other size.
ABN: 47 162220 653 TWS-W-0002 05 of 19 5
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
SCHEDULE OF ITEMS
A No. DESCRIPTION COMMENTS A
Connection
Point
4 Pipe and Fittings (PN.16 minimum) Meter box
Refer Table 1 Concrete nib in
75
footpath and paved areas
65
B B
(+ 25)
LOCATION METER BOX TYPE
200
300 Min.
Non Trafficable Standard polyethylene meter box with green non-slip lid
300 Min.
(Class A to AS/NZS 3996 - extra light duty) ('Draper' Model DRA 20/3, or simiar approved)
4
Footpath and Paved areas Alluminium alloy meter box with alloy non-slip lid
(Class B to AS/NZS 3996 - light duty) ('Bennet & Kingston' box and lid, or similar approved) Flow
2 1 3 4
Pipework to
C Mass concrete plinth in Bedding (50 min. thick) dwelling C
Pipework from boundary
meter assembly footpath and paved areas. 7 (Nom.) clean, single size metal
METER CONNECTION
1 : 10
D D
VALVE & EQUIPMENT SCHEDULE
1. Only use products with watermark certification and approved for use by GENERAL NOTES
TasWater and listed within City West Water's approved products catalogue. 1. All existing service connections should be considered an electrical hazard and
2. Installation must comply with manufacturer's written instructions electrical bridging leads (min. 70 Amp rating) and low voltage insulated gloves
shall be utilised at all times.
3. All valves must be resilient seated, clockwise closing to AS 1628
with 316 stainless steel bolts and washers. 2. Water meter to be located in common ground in front of dwelling.
4. In footpaths and paved areas the meter box must be supported with 3. Applicant must install water meter within appropriate pit as per these drawings.
insitu N25 concrete. 4. Works to be completed by a competent plumber.
E 5. Unless approved otherwise the water meter/s, tails and meter WARNING 5. Installation must meet these requirements, if not TasWater will rectify with all E
boxes are to be supplied by TasWater. Where a metallic water service is to be replaced using non
associated cost to be borne by the applicant / developer.
metallic pipe a licensed electrician shall assess affected
property's electricity supply for defects and the likely 6. Any pressure limiting valves installed under the requirements of clause 3.3.4 of
effect on earthing adequacy. Work can commence once the AS 3500.1-2003 are to be installed outside of and downstream of the meter box.
electrician declares in writing that it is safe to proceed.
7. After installation of meter, TasWater must be notified by returning meter sheet to
Development@taswater.com.au stating TasWater reference number in subject line.
0 0.2 0.4 0.6 0.8 1.0 metres
8. Failure to install or contact TasWater after installation will result in non issue of any
SCALE - 1 : 10 compliance certificates.
Drawing
Number
Rev. 5 Date 31/10/2018 Approved G. HENDERSON References HPRM File Ref. T15/82-006-0004
on site by the user prior to construction.
This drawing is produced on an A3 size sheet,
DO NOT SCALE a sheet plotted at any other size.
ABN: 47 162220 653 TWS-W-0002 06 of 19 5
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
2 2 DN.25 Ball Valve - W/MRK R/A Lockable Quarter Turn Brass DZR,
Resilient Seated with Extendable Nut and Tail
300 min.
1 3 10 6
4 DN.25 'Viega' Pro-press Water Male Line Adaptor Or Approved Equivalent
11 12 11
5 DN.25 Type 'A' Copper Pipework
B 6 DN.25 Brass Nipple B
7 DN.25 Ball Valve - Lockable Quarter Turn brass DZR with brass handle, resilient seated.
ELEVATION 9 Medium Hazard DN.25 'ValvCheQ' DC03 Double Check Valve Owned, operated and
1 : 10 High hazard DN.25 'ValvCheQ' RPZD RP03 Valve Only maintained by Property Owner
3 7 6 8 7 4
Direction of Flow Direction of Flow
GENERAL NOTES
1. All dimensions in millimeters (mm), unless noted otherwise.
0 0.2 0.4 0.6 0.8 1.0 metres 9. The Property Owner is responsible for the ongoing maintenance of the security cage.
SCALE - 1 : 10
Drawing
Number
Rev. 5 Date 31/10/2018 Approved G. HENDERSON References HPRM File Ref. T15/82-006-0004
on site by the user prior to construction.
This drawing is produced on an A3 size sheet,
DO NOT SCALE a sheet plotted at any other size.
ABN: 47 162220 653 TWS-W-0002 07 of 19 5
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
2 7 1 1 SCHEDULE OF ITEMS
A No. DESCRIPTION COMMENTS
4 1 3 Pipe supports
A A
Property bdy.
1 1 'Sensus' Water Meter with Dual Check Valve Supplied by TasWater
2 Brass Nut and Tail Supplied by TasWater
8
6 3 'Viega' Pro-press Water Female Line Adaptor Or Approved Equivalent
(typ.) 9
325
Cover *
DZR, Resilient Seated with Extendable Nut and Tail.
5 Universal Adaptor
SECTION A - A
ABOVE GROUND Length as required
1 : 20
*
Drawing
Number
Rev. 5 Date 31/10/2018 Approved G. HENDERSON References HPRM File Ref. T15/82-006-0004
on site by the user prior to construction.
This drawing is produced on an A3 size sheet,
DO NOT SCALE a sheet plotted at any other size.
ABN: 47 162220 653 TWS-W-0002 08 of 19 5
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
SCHEDULE OF ITEMS
No. DESCRIPTION COMMENTS
A Heavy duty path tap box 1 'Sensus' Water Meter with Dual Check Valve Supplied by TasWater A
Property bdy.
(Refer Sheet 5)
500
2 Brass Nut and Tail Supplied by TasWater
3 11 2
3 Ball Valve - W/MRK Lockable Quarter Turn Brass DZR, Resilient Seated with Extendable Nut and Tail
(+ 25)
Cover *
150
5 'Viega' Pro-press Water Female Line Adaptor Or Approved Equivalent
*
Cover 300 Min. for non-trafficable
450 Min. for trafficable
PROFILE (Refer Table 5.3 of AS3500.1)
11 Meter Pit - Non-Trafficable 'Draper' Model Modular DRA 100, or similar Refer Sheet 5
Length as required
9
(typ.)
150
135 470 (min.) FTC
C C
8
10
DN.40 Male DN.40 Type 'A' DN.40 Type 'A' Copper Soldered joints
thread coupling Manifold Joiner
(As Required) DN.40 Female
470 (min.)
thread coupling
D (FTC - DN20 Female thread coupling, typ. 3 places) D
8
DN.40 MANIFOLD
7 6 1:5
(min.)
300
Drawing
Number
Rev. 5 Date 31/10/2018 Approved G. HENDERSON References HPRM File Ref. T15/82-006-0004
on site by the user prior to construction.
This drawing is produced on an A3 size sheet,
DO NOT SCALE a sheet plotted at any other size.
ABN: 47 162220 653 TWS-W-0002 09 of 19 5
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
25 (min.)
2. Where meters are located in a utility room, adequate ventillation must be provided.
The cupboard must not be classified as a confined space for entry purposes.
3. The cabinet shall be marked clearly with the words "Water Meters" on the outside of
the door as shown. Where more than one meter cabinet is installed then each cabinet
shall have a cabinet ID number fixed to the outside of the door as shown.
METER TAG
*
Cover 300 Min. for non-trafficable 4. All cabinets shall be either bunded as shown, or drained to the stormwater system to manage
450 Min. for trafficable seepage from maintenance events. All penetrations shall be sealed.
N.T.S.
C (Refer Table 5.3 of AS3500.1) C
25 5. The cabinet shall have a minimum 100mm bund if it is located inside a building.
Wall
(min.) 6. The cabinet size shall provide for the minimum dimensions shown.
Pipework to Unit
100 7. Water meter cabinets shall allow access to the meter assembly for maintenance and
4 4
customer interactions.
115
3 8. A minimum of 2 sq. metres, or an area of 1.5 x door width (which ever is greater) shall be
2 2 provided for maintenance and customer interaction. The cabinet shall have adequate lighting
during daylight hours and shall not require additional aids such as ladders to maintain meters
1 1 or to obtain meter data.
2 9. There will be sufficient room for the cabinet door(s) to swing open completely and provision
2
1600 (max.)
3
D D
10. The cabinet material shall be either 1mm thick steel, or 1.5mm thick 5251, or 5083 alloy
50 aluminium. Cabinets shall be powder coated to suit building architecture.
4 (min.) 4 11. The cabinet door(s) are to be fabricated from a non-metallic product, preferable to have either
toughened safety glass or perspex viewing port to enable easy viewing of meter assembly
without opening doors.
Cover *
12. The cabinet does not need to be locked, but must be fitted with a latch where a double padlock
can be fitted in the future as required.
13. The meter cabinet shall be strategically located to enable best maximum range for AMR (best
150 150 option is by locating meter cabinet so that the TasWater meter reader can automatically
Pipework to read the meters from the closest road frontage without having to enter the complex.)
E Main connection 14. All external edges are to be rounded. E
(Refer Sheet 5) 5
15. Cabinet door(s) shall have a hand operated one point stainless steel quarter turn latch to close
FRONT VIEW SIDE VIEW the door and shall have lift off type hinges with hinge pins - both stainless steel.
16. The meters may be installed in a fire facility cabinet with shown installation dimensions
CABINET GENERAL ARRANGEMENT to be maintained.
17. The meter tag shall have a hole to allow attachment to meter assembly.
0 0.4 0.8 1.2 1.6 2.0 metres 1 : 20
18. The meter tag needs to be of a material that is water proof and the required
SCALE - 1 : 20 information to be in a legible permanent print to identify the meter.
Drawing
Number
Rev. 5 Date 31/10/2018 Approved G. HENDERSON References HPRM File Ref. T15/82-006-0004
on site by the user prior to construction.
This drawing is produced on an A3 size sheet,
DO NOT SCALE a sheet plotted at any other size.
ABN: 47 162220 653 TWS-W-0002 10 of 19 5
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Connection
Meter box
Concrete nib in
Point
Refer Note 5 75
footpath and paved areas
B B
Finished surface level
65
(+ 25)
200
C C
3 3
1
4 2 5 5 4
Direction of Flow
ELEVATION
1:5
Drawing
Number
Rev. 5 Date 31/10/2018 Approved G. HENDERSON References HPRM File Ref. T15/82-006-0004
on site by the user prior to construction.
This drawing is produced on an A3 size sheet,
DO NOT SCALE a sheet plotted at any other size.
ABN: 47 162220 653 TWS-W-0002 11 of 19 5
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
4 4 3 Medium Hazard DN.32 'ValvCheQ' DC03 Double Check Valve Owned, operated and
High hazard DN.32 'ValvCheQ' RPZD RP03 Valve Only maintained by Property Owner
300 min.
8 2 10 10 12 7 13 12 6 Pipe Wrapped where Concrete will contact Pipe (Refer Note 5)
B 6 9 5 6 B
7 DN.32 Strainer Owned, operated and
maintained by Property Owner
TasWater Responsibilty Property Owner Responsibility DZR with brass handle, resilient seated
11 9 12 11 7 12 8
D GENERAL NOTES D
Drawing
Number
Rev. 5 Date 31/10/2018 Approved G. HENDERSON References HPRM File Ref. T15/82-006-0004
on site by the user prior to construction.
This drawing is produced on an A3 size sheet,
DO NOT SCALE a sheet plotted at any other size.
ABN: 47 162220 653 TWS-W-0002 12 of 19 5
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
10 10
BOUNDARY CONNECTION PARTS LIST
No. DESCRIPTION COMMENTS
A 5 5 A
1 DN.50 'Sensus' Meistream Plus Water Meter Supplied by TasWater
2 DN.50 'Sensus' WP-F Dirt Box Supplied by TasWater
3 DN.50 Gate Valve Supplied by TasWater
4 Low Hazard DN.50 'ValvCheQ' DCO3U Double Check Valve Owned, operated and
300 min.
9 3 11 2 1 6 11 4 9 Non-Testable maintained by Property Owner
5 DN.50 "Type A" Copper Water Pipe
8 7 Pipe Support Bracket 8
6 DN.50 x 200mm Hydrant Riser with 25mm Tapping for Supplied by TasWater
Refer Sheet 18
B Pressure Testing, 20mm Valve and Plug B
Drawing
Number
Rev. 5 Date 31/10/2018 Approved G. HENDERSON References HPRM File Ref. T15/82-006-0004
on site by the user prior to construction.
This drawing is produced on an A3 size sheet,
DO NOT SCALE a sheet plotted at any other size.
ABN: 47 162220 653 TWS-W-0002 13 of 19 5
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
11 11 12 4
GENERAL NOTES
5 5 1. All dimensions in millimeters (mm), unless noted otherwise.
A A
2. A 3mm clearance has been added where a gasket is required.
3. All metallic pipe work to be 'Denso' wrapped, or equivalent where it comes in contact
with concrete - to protect it from corrosion.
4. Install and locate the meter assembly so that the meter can be easily read.
300 min.
10 3 12 2 1 7 12 13 9 14 13 10 5. Where a vented back flow prevention device is required such as a
Reduced Pressure Zone Device (RPZD) it shall:
8 6 8 - Comply with AS 3500 and AS 2845; and shall
- Have free ventilation to the atmosphere for the relief valve at all times.
B - Not be in an area that may be subject to ponding; B
- Have the relief drain outlet not less than 300mm above the surrounding surface.
6. Install the meter assembly in cage in accordance with TWS-W-0003.
Pipe Support Bracket 7. The Property Owner is responsible for the ongoing maintenance of the security cage.
Refer Sheet 18
ELEVATION VALVE & EQUIPMENT SCHEDULE
1 : 10
1. Only use products with watermark certification and approved for use by TasWater
TasWater Responsibility Property Owner Responsibility and listed within City West Water's approved products catalogue.
C 2. Installation must comply with manufacturer's written instructions. C
1590
3. All valves must be resilient seated, clockwise closing to AS 1628 with 316 stainless
13 13 steel bolts and washers.
Direction of Flow Direction of Flow 4. Unless approved otherwise the water meter/s, tails and meter boxes are to be
supplied by TasWater.
12
5 10 3 2 1 7 11 12 9 4 10 5
D 12 11 D
PLAN
1 : 10
Drawing
Number
Rev. 5 Date 31/10/2018 Approved G. HENDERSON References HPRM File Ref. T15/82-006-0004
on site by the user prior to construction.
This drawing is produced on an A3 size sheet,
DO NOT SCALE a sheet plotted at any other size.
ABN: 47 162220 653 TWS-W-0002 14 of 19 5
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
5 4 Low Hazard DN.65 'ValvCheQ' DCO3U Double Check Owned, operated and
5
Valve Non-Testable maintained by Property Owner
5 DN.65 PN16 Metallic Water Pipe Copper not to be used for DN.100
6 DN.65 x 200mm Hydrant Riser with 25mm Tapping for Supplied by TasWater
B Pressure Testing, 20mm Valve and Plug B
300 min.
3 2 1 6 4
7 100mm (minimum) Reinforced Concrete Slab SL72 placed central
8 7 8 8 Pipe Wrapped where Concrete will contact Pipe (Refer Note 5)
ELEVATION
1 : 10 VALVE & EQUIPMENT SCHEDULE
1. Only use products with watermark certification and approved for use by TasWater
TasWater Responsibility Property Owner Responsibility and listed within City West Water's approved products catalogue.
2. Installation must comply with manufacturer's written instructions.
3. All valves must be resilient seated, clockwise closing to AS 1628 with 316 stainless
(752 / 827 / 858) (403 / 403 / 541) steel bolts and washers.
D D
4. Unless approved otherwise the water meter/s, tails and meter boxes are to be
Direction of Flow Direction of Flow
supplied by TasWater.
GENERAL NOTES
1. All dimensions in millimeters (mm), unless noted otherwise.
5 3 2 1 6 4 5 2. Installation and fittings schedule is also suitable for DN.80 and DN.100 meters.
3. Dimensions shown in brackets apply to (DN.65 / DN.80 / DN.100).
E E
PLAN 4. A 3mm clearance has been added where a gasket is required.
1 : 10
5. All metallic pipe work to be 'Denso' wrapped, or equivalent where it comes in contact
with concrete - to protect it from corrosion.
6. Install and locate the meter assembly so that the meter can be easily read.
7. Install the meter assembly in cage in accordance with TWS-W-0003.
0 0.2 0.4 0.6 0.8 1.0 metres
8. The Property Owner is responsible for the ongoing maintenance of the security cage.
SCALE - 1 : 10
Drawing
Number
Rev. 5 Date 31/10/2018 Approved G. HENDERSON References HPRM File Ref. T15/82-006-0004
on site by the user prior to construction.
This drawing is produced on an A3 size sheet,
DO NOT SCALE a sheet plotted at any other size.
ABN: 47 162220 653 TWS-W-0002 15 of 19 5
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
GENERAL NOTES
1. All dimensions in millimeters (mm), unless noted otherwise.
A
2. Installation and fittings schedule is also suitable for DN.80 and DN.100 meters. A
5 5 3. Dimensions shown in brackets apply to (DN.65 / DN.80 / DN.100).
4. A 3mm clearance has been added where a gasket is required.
5. All metallic pipe work to be 'Denso' wrapped, or equivalent where it comes in contact
with concrete - to protect it from corrosion.
6. Install and locate the meter assembly so that the meter can be easily read.
7. Where a vented back flow prevention device is required such as a
3 2 1 6 3 9 10 4 3
300 min.
Reduced Pressure Zone Device (RPZD) it shall:
- Comply with AS 3500 and AS 2845; and shall
B - Have free ventilation to the atmosphere for the relief valve at all times. B
8 7 Pipe Support Bracket 8
Refer Sheet 18 - Not be in an area that may be subject to ponding;
- Have the relief drain outlet not less than 300mm above the surrounding surface.
8. Install the meter assembly in cage in accordance with TWS-W-0003.
9. The Property Owner is responsible for the ongoing maintenance of the security cage.
0 0.2 0.4 0.6 0.8 1.0 metres 10 Vent only applies on High Hazard installations where
SCALE - 1 : 10 a RPZD is used
Drawing
Number
Rev. 5 Date 31/10/2018 Approved G. HENDERSON References HPRM File Ref. T15/82-006-0004
on site by the user prior to construction.
This drawing is produced on an A3 size sheet,
DO NOT SCALE a sheet plotted at any other size.
ABN: 47 162220 653 TWS-W-0002 16 of 19 5
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
2 Low Hazard 'ValvCheQ' DN.100 SDCT03 Single Check Valve Owned, operated and
3 maintained by Property Owner
3
3 DN.100 PN16 Metallic Water Pipe Copper not to be used
4 Metered Bypass Supplied by TasWater
5 100mm (minimum) Reinforced Concrete Slab SL72 placed central
6 Pipe Wrapped where Concrete will contact Pipe (Refer Note 3)
330
300 min.
7 'Sensus' Meter size for Low Flow Bypass DN.25 Bypass for DN.100 - DN.150
B B
5 440 DN.32 Bypass for DN.200
6 6
DN.40 Bypass for >DN.200
Tee
Direction of Flow Domestic Assembly 25mm and above
ELEVATION (Refer separate sheets)
C 1 : 10 C
Drawing
Number
Rev. 5 Date 31/10/2018 Approved G. HENDERSON References HPRM File Ref. T15/82-006-0004
on site by the user prior to construction.
This drawing is produced on an A3 size sheet,
DO NOT SCALE a sheet plotted at any other size.
ABN: 47 162220 653 TWS-W-0002 17 of 19 5
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
3 DN.100 Lug Type Butterfly Valve with Worm Gear Actuator 1 x Supplied by TasWater 8 DN.100 x 200mm Hydrant Riser with 25mm Tapping Supplied by TasWater
for Pressure Testing, 20mm Valve and Plug
4 DN.100 Lug Type Butterfly Valve with Worm Gear Actuator or Approved Equivalent
- Not Required for Non-Testable Backflow Devices 9 100mm (minimum) Reinforced Concrete Slab SL72 placed central
5 DN.100 PN16 Metallic Water Pipe Copper not to be used 10 Concrete Thrust Block made to WSAA Standard (Refer MRWA-W-205)
C Direction of Flow C
GENERAL NOTES 3 4
(3 x DN)
effect on earthing adequacy. Work can commence once the
300
electrician declares in writing that it is safe to proceed. 5 8 2 6
4. Where a vented back flow prevention device is required such as a 5
300 min.
Reduced Pressure Zone Device (RPZD) it shall:
- Comply with AS 3500 and AS 2845; and shall
D 1 D
- Have free ventilation to the atmosphere for the relief valve at all times.
9
- Not be in an area that may be subject to ponding;
- Have the relief drain outlet not less than 300mm above the surrounding surface.
5. Install the meter assembly in cage in accordance with TWS-W-0003.
500 (min.)
(5 x DN)
6. The Property Owner is responsible for the ongoing maintenance of the security cage.
7. Install and locate the meter assembly so that the meter can be easily read. 11 11
12 7
8. The Magflow Meter requires a straight length of pipe measured from the centre of the meter:
- To an upstream length of 5 times the Nominal diameter; and
Direction of Flow
- To a downstream length of 3 times the Nominal diameter to minimize turbulance.
E 9. Earth the meter as per manufacturer's specifications. E
ELEVATION
0 0.4 0.8 1.2 1.6 2.0 metres
1 : 20
SCALE - 1 : 20
Revision Notes Scale 1 : 10 DRAWING ISSUE
5. AMENDMENTS TO SHEETS 7, 12 AND 17 Datum N/A Drawn R. HAWLEY
TASWATER STANDARD DRAWING
F 07/02/2017
F
Sheet Size A3 Designed R. CAMERON 08/02/2017 PROPERTY SERVICE CONNECTIONS
Verified R. JAMES 20/03/2017 This drawing and the information it contains is, and DN.100 WATER METER
remains the property of TasWater and must not be
Project No. JR16982-035 Discipline W disclosed to third parties, or copied or reproduced wholly
or in part or in any format without the written consent
ELECTROMAGNETIC FLOW METER
of the owners. The information contained herein is also
Vault Folder STANDARDS C 2018 correct and up-to-date, but all details should be verified Sheet Number REVISION
TASMANIAN WATER & SEWAGE CORPORATION PTY LTD
Drawing
Number
Rev. 5 Date 31/10/2018 Approved G. HENDERSON References HPRM File Ref. T15/82-006-0004
on site by the user prior to construction.
This drawing is produced on an A3 size sheet,
DO NOT SCALE a sheet plotted at any other size.
ABN: 47 162220 653 TWS-W-0002 18 of 19 5
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
140
= =
30 30
Fillet weld DN15 pipe 140 x 60 x 10
to pipe clamp Plate
B M8 Locking Bolt B
50
250
=
Height adjustable Stand
60
Refer Note 5
=
250
BASE PLATE
FRONT VIEW SIDE VIEW 1:2
D D
Drawing
Number
Rev. 5 Date 31/10/2018 Approved G. HENDERSON References HPRM File Ref. T15/82-006-0004
on site by the user prior to construction.
This drawing is produced on an A3 size sheet,
DO NOT SCALE a sheet plotted at any other size.
ABN: 47 162220 653 TWS-W-0002 19 of 19 5
1 2 3 4 5 6 7 8