Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
WRITE UP
ON
ELECTROHYDRAULIC TURBINE CONTROLLER ( EHTC )
Reference Documents:
1.MPL for Steam Turbine
Doc. No. :- 41330000488(TAPP3/64110/5516/SCH)
2.Scheme for speed measurement turbine and generator
Doc. No. :- 41330098204(TAPP3/64110/5512/DN)
3.Write up on LRR for MSCV and AEOR
Doc. No. :- 41330000481(TAPP3/64110/5661/DN)
4.OGA of TG control desk 6610 – PL – 9
Doc. No. :- 06560000403(TAPP3/64100/5724/GA)
5.OGA of TG control desk 6610 – PL – 10
Doc. No. :- 06560000404(TAPP3/64100/5725/GA)
6.Turbine controller – CJJ01 – Cubicle & Rack assembly diagram
Doc. No. :- 36560001746(TAPP3/64100/5728/GA)
7.Turbine controller – CJJ01 – Signal Flow Diagram(SFD)
Doc. No. :- ED-031027-SF-S105(TAPP3/64100/5729/WD)
8.Turbine controller – CJJ01 – Functional Diagram(FCD)
Doc. No. :- ED-031027-FC-S105(TAPP3/64100/5729/WD)
1 Introduction 4
1 Introduction
2. A hydraulic system which position the valves to match the valve lift
signal.
- high flexibility
- excellent dynamic response
- simple representation of complex functional interrelationships
3 Hydraulic Controller
If the hydraulic controller is to govern turbine start-up, the set point for the
Electro-hydraulic controller must be set to 100% to allow the hydraulic
controller to implement turbine control over the entire control range. The
speed set point for the hydraulic controller is set to minimum for this.
The set-point for the start-up and load limit device is then increased from
0%. This causes trip fluid pressure to build up and reset the protective
devices of the turbine. Increasing the set point for the start-up and load
limit device further in the open direction causes the turbine stop valves to
open.
After the turbine stop valves have opened, increasing the set point for the
start-up and load limit device further results in gradual opening of the
control valves, admitting steam to the turbine. This runs the turbine up to
about 85 - 90 % rated speed. The hydraulic speed governor then takes over
speed control of the turbine. Actual speed is derived from hydraulic speed
transmitters. After this control takeover has taken place, the set point of the
start-up load limit device has then to be set to the 100 % position..
For synchronization, turbine speed is run further by increasing the set point.
After synchronization, the turbine is loaded by raising the set point further.
As the hydraulic speed governor and the start-up and limit load device are
linked via the downstream hydraulic Min gate, the output of the hydraulic
controller and thereby turbine output can be limited by the start-up and limit
load devices. If turbine start up is to be governed by the Electro-hydraulic
controller, the set point for the start-up and limit load device has to be set to
its max. value of 100% immediately after opening of the turbine stop valves.
The set point for the hydraulic controller likewise has to be set to 100% to
allow the Electro-hydraulic controller to take over speed control of the
turbine above turning speed. The speed set point for the Electro-hydraulic
controller must be set to 0% for this.
The hydraulic amplifier forms the interface between the hydraulic controller
and the hydraulic valve actuation system. The output signal from the
---------------------------------------------------------------------------------------------- Sheet no. 5 of 37
STE, BHEL-HARDWAR
NPC DOC. NO. TAPP-3/64110/5526/DN/R0---------------------------------4 13300 00 486 ----
REV. NO. 01
Two analog electrical output signals are available from the Electro-hydraulic
turbine controller. Each signal acts on a piston via a sleeve of the
independent electro hydraulic converter(EHC). The position of the piston of
each EHC is acquired by linear variable differential transmitters (LVDTs) and
used as actual value for the valve lift controller. The piston acts on a follow-
up piston block, the resulting movement of the follow-up pistons likewise
altering secondary fluid pressure and thereby control valve lift.
The output from the follow-up piston blocks of the hydraulic controller and
Electro-hydraulic are linked via a MIN gate. This means that the system with
the lower pressure output signal sets valve lift.
In the event of failure of the output signal from the Electro-hydraulic
controller to one of the two Electro-hydraulic converters, the other Electro-
hydraulic converter, sets the valve lift if selected though the MIN gate.
The load rejection relay (see Fig.2) assists the electro hydraulic controller to
ensure that the speed of the turbine generator cannot reach the trip setting
for the hydraulic overspeed trips under any circumstances.
Response of the load rejection relay to the load rejection uses the change in
electrical generator load before the subsequent increase in speed which
results. This means that the load rejection relay acts on the turbine control
system before the significant speed increase .
After termination of the electrical pulse the solenoid valves which have
switched to drain close again. At this stage , the electro hydraulic controller
still holds the drain closed due to the speed increase which has occurred in
the meantime. After this speed increase has stabilized , the electro hydraulic
controller opens these valves again. Control fluid pressure then builds up
again and the electro hydraulic controller opens the control valves to a
position corresponding to the new generator load or to the speed set point.
---------------------------------------------------------------------------------------------- Sheet no. 6 of 37
STE, BHEL-HARDWAR
NPC DOC. NO. TAPP-3/64110/5526/DN/R0---------------------------------4 13300 00 486 ----
REV. NO. 01
The settings for the load rejection relay (load step magnitude, pulse
duration) are made during initial commissioning and start-up of the turbine
generator.
The separate loops are completely isolated from one another by means of a
control selection circuit .
The output signal of the control selection circuit sets the positions of the
electro hydraulic converters pistons via the valve lift controllers, thereby
setting turbine control valve lift.
The task of the speed loop is to meet closed-loop control requirements for
the turbine generator during start-up and synchronization with the power
system. During power operation the speed controller serves as an overspeed
limit controller to ensure that speed increases caused by power system
disturbances (such as load rejection) cannot result in speed reaching the trip
setting for the mechanical overspeed trips (set to approx. 115% of rated
speed) under any circumstances.
The speed control loop consists of the set point adjuster, the set point control
and the speed controller.
The speed set point nr is governed by the position of the set point adjuster
(refer Fig. 5). The set point can be adjusted over the range from 0 to 55 rps
from the main control room panel 6610 – PL - 10. To assist in fine
adjustment of the speed set point for synchronization, the rate of change for
the set point adjuster is decreased by a factor of 4 at set points above 47
rps.
Further input are provided for adjustment of the speed set point by a
synchronizing unit and an automatic start - up system. Manual set point
change command take priority.
The speed set point is displayed on two indicators on the turbine control
panel , one for the overall speed range of 0 to 60 rps and the other for the
narrow range from 45 to 55 rps.
The speed setpoint nr forms the input signal for the setpoint control which
determiners the acceleration rate. For this, the setpoint control outputs a
delayed setpoint nr del.
The turbine stress evaluators (TSE) acts via the setpoint control to limit the
speed setpoint rate. Any limitation is based on acquisition and evaluation of
thermal stresses measured at representative locations on the turbine .This
prevents excessive thermal stressing of the turbine and at the same time
allows turbine generators run-up at the maximum permitted acceleration
rate. Depending on the thermal conditions in the turbine , the TSE can cause
the acceleration rate to be reduced to zero or even to become negative (see
Fig.5).
In the event of a fault in the TSE, the momentary output signal of the speed
setpoint control is "frozen" automatically until the fault has been cleared or
the TSE control component has been deactivated using the ON/OFF switch in
the electro hydraulic controller cabinet.
The TSE is provided with a test program to allow checkout of the anolog
calculation channel.
Actual speed is measured digitally .The end of the turbine shaft is fitted with
a digital speed transmitter which consists of 3 Hall probes and a non-
magnetic disk with 120 permanent magnets positioned around its
circumference (See Fig.6).
During turbine operation , the poles of these magnets move past the Hall
sensors separated by a slight air gap only (approx.0.8 mm). When the disk
rotates , the probes output pulses which are converted into an AC voltage
signal with a frequency proportional to rotational speed of the turbine. The
output signal from each Hall probe is transmitted to a dedicated pulse
converter in the vicinity of the turbine .Each of these pulse converters
amplifies the Hall voltage and replicates this to give 3 floating- voltage,
square -wave voltage signals of approx. 20 Vpp.
Three (3) signals (one each from each pulse converter) of frequency which
corresponds to the Hall voltage frequency (and thereby to turbine speed )
---------------------------------------------------------------------------------------------- Sheet no. 9 of 37
STE, BHEL-HARDWAR
NPC DOC. NO. TAPP-3/64110/5526/DN/R0---------------------------------4 13300 00 486 ----
REV. NO. 01
The 3 output signals from the pulse amplifiers are monitored continuously by
the pulse monitor for failure. This is performed by cyclic scanning of the
input signals, with the signal which is at any time the second in chronological
order being selected as actual speed signal by the channel changeover
circuitry and transmitted to the downstream frequency/ voltage converter.
Failure of a speed channel is detected by the pulse monitor. The actual valve
signal is then selected from the two unaffected channels and this fault
annunciated by an individual alarm in the cabinet as well as by a group
alarm.
The remaining output signals from the three pulse converters is transmitted
to other I&C system, e.g. to the speed measuring unit.
The deviation is derived from the delayed speed setpoint nr delay (output of
the speed setpoint control) and the actual speed signal nact (output by the
frequency/ voltage converter).
The output from the speed controller is applied to the control selection circuit
and, when selected for output, forms the input signal for the valve lift
controller ( see description of control selection circuit, Section 5.4).
The set point output of the lift set point control loop takes over control of the
turbine immediately after synchronization of the turbine generator with the
power system. This function allows valve lift and thereby turbine load to be
The lift setpoint Lr is set by the output of the setpoint adjuster. The setpoint
can be adjusted manually from the main control room panel 6610-PL-10.
During auto mode of operation, the lift setpoint adjuster Lr follows the output
of lift setpoint controller Lr del to enable bumpless transfer during
changeover back to manual. The lift setpoint is displayed on an indicator
located on the turbine control panel in the control room.
In manual mode, the output from the lift setpoint control Lr del follows the
input signal Lr, with the preset rate and the rate of change governed by the
lift setpoint rate adjuster. This set point rate can be adjusted from the main
control room panel. The rate can be adjusted to anywhere between zero and
maximum permitted lift rate (approx. 10% /min). During Auto mode of
operation, the output of the lift setpoint controller is based on the adapted
steam generator pressure controller output. Adapted steam generator
pressure controller output is received in two channel . A minimum selection is
formed of the two channel.
The lift rate adjuster can be activated and deactivated from the main control
room panel 6610 - PL -10. When the lift rate adjuster is deactivated, the
maximum permitted lift rate becomes effective.
The turbine stress evaluator (TSE) also acts on the lift set point controller.
The TSE component acts on setpoint changes in both directions, with the
upper margin acting on valve opening and the lower margin on valve
closing. If the upper margin should become negative valve opening, the
output valve of the setpoint controller is automatically reduced, thus leading
to closure of valves instead of opening.
This ensures loading and unloading at maximum possible rate, but without
exceeding maximum permitted thermal stress limits.
The effective rate of change for the lift setpoint is given by the MIN TSE
component and the set lift setpoint rate.
The output from the lift setpoint controller is automatically set to zero under
the following conditions:
- When the lift setpoint is deactivated for longer than 3 s ( see Section
5.2.6)
- After the speed controller has taken over control of the turbine during
shutdown.
The max. valve lift set point LMAX is set by the output of setpoint adjuster.
The setpoint can be adjusted manually from the main control room panel
6610 –PL -10 to limit the valve lift in case of necessity.
The output signal from the lift setpoint controller is passed on to a MIN gate
and compared with the maximum valve lift set point LMAX . The output of
this MIN gate is passed on to the control transfer circuit via a switch for " Lift
setpoint controller ON / OFF".
Providing that the speed controller is in action, the lift setpoint can be
activated or deactivated manually as required from the main control room
panel 6610-PL-10. The lift setpoint should always be activated in normal
operation, as selection of the controller to take control is implemented by the
control selection circuit. The control selection circuit is described in Section
5.4.
In the event that generator actual load becomes negative due to power
system load swings ( generator synchronized to power system and supplying
more than 2 % reverse power, i.e. generator is motoring ), the lift setpoint is
then immediately reactivated. Such load swings in the power system can
occur on reconnection of loads that were shed during a power system
disturbance.
The adapted pressure deviation signal from steam generator pressure control
system is received in two channels. These two signals are compared in a
MAX gate and fed to a pressure controller. The output of the pressure
controller is fed to the control selection circuit and has got highest priority
(see fig.12)
The pressure controller tolerates small size deviations from the pressure
setpoint. It does not take action until actual pressure drops more than a
---------------------------------------------------------------------------------------------- Sheet no. 13 of 37
STE, BHEL-HARDWAR
NPC DOC. NO. TAPP-3/64110/5526/DN/R0---------------------------------4 13300 00 486 ----
REV. NO. 01
certain limit value below the setpoint. The controller then throttles the
turbine control valves.
The control selection circuit (see fig.12), a logic circuit comprising a MAX
gate with downstream MIN gate, determines which of the three types of
loop- speed control loop,lift set point control loop or minimum pressure
control loop - takes over control of the turbine generator. This control
selection circuit also ensures that only one of these 3 controllers will be
active.
The output signals from the speed controller and the lift setpoint controller
are inputted to the MAX gate, i.e the higher signal value is always output by
this gate, thereby setting turbine valve lift if this is also the lower signal
valve present at the downstream MIN gate. During turbine generator start-
up, the output signal from lift setpoint formation is deactivated (as the
generator breaker is not closed), so that the signal from the speed controller
will be output by this logic and the speed controller will take control of the
turbine generator. Minimum pressure controller output has got more priority
and will takeover control to throttle valves if actual pressure drops more than
a certain limit from set pressure valve.
Once the generator is synchronized with the power system and the generator
breaker is closed and lift setpoint control loop is activated, the lift setpoint
control in line with the set lift set point. During this operation with the output
signal from the speed controller set to a valve lift corresponding to about 10
% load by appropriate automatic adjustment of the speed setpoint.
This setting for the speed controller output signal ensures that if the lift
setpoint signal is deactivated in the event of power system disturbance,
turbine generator speed is prevented from rising due to the setpoint set for
the speed controller.
The minimum pressure controller takes over control via the MIN gate when
this is lowest input signal to this gate.
The control loop that is in control of the turbine generator at any moment is
signalled on main control room panel 6610-PL-10 by one of the following
status indications:
With a droop setting for the speed controller of 5%, this results in a speed
rise of
From this diagram it can be seen that lift setpoint controller is in control of
the turbine up to time t1 . After this load is reduced to 50% of rated load by
the negative speed controller output signal.
The turbine then operates at an actual speed of 51.5 rps to match the new
load demand of 50% only. Turbine speed can be returned to rated speed by
lowering the lift setpoint to match the new power system load demand.
Two valve position control loops are provided for the turbine control valves.
To improve the stability and dynamic response of the overall control system,
the valve position controllers are implemented as slave control loops to the
master controllers (speed controller, minimum pressure controller, lift
setpoint controller). Both valve position control loops are operative normally
but in case of fault in actual lift derivation of one loop, the valve position is
decided by other loop which will now always remain operational .
The signal by the control selection circuit is outputted in two sets of three
channels. Middle of the three signals is selected by voting module. This acts
as set point for both valve lift controllers.
These two control loops do not differ so that the description which follows
applies for both.
The lift of the servo piston in the electrophydraulic converter sets the lift of
the turbine control valves.
As a result, this can be used to derive control valve lift. Although this is an
indirect measurement it is linear and accurate enough for this purpose. This
is usually a more reliable method than direct measurement on the control
valves. Even in the event of turbine trip with the resulting drop in trip fluid
pressure, the servo piston moves in the "close valves" direction so that valve
lift is correctly registered under these conditions.
The output signals act on the plunger coil system of the electrohydraulic
converters, thereby acting on control fluid pressure of the hydraulic valve
actuation system. These converters thereby set the lift for the control
valves. For further details see turbine manual.
In the event of an open circuit for the plunger coil of one electrohydraulic
converter, the valve position is determined by other valve position controller
which is always operative as back up.
As can be seen from fig. 1, the downstream MIN gate means that the
controller with the lower output signal will take control under any condition.
As a result, to make a controller take over control it is necessary to adjust
the setpoint appropriatly for the two controllers.
To transfer control to the hydraulic controller, the setpoint for this controller
only needs to be set lower than that for the electrohydraulic controller. The
lift setpoint for the electrohydraulic controller then has to be set to 100% to
allow the hydraulic controller to exercise control over the entire control
range.
The operator control devices for operation of the turbine controller are
intergrated into the main control room. The panel section for the
electrohydraulic controller is shown in fig.17.
The turbine generator must be in turning operation, with the start-up and
load limit device, hydraulic speed governor setpoint and electrical speed
setpoint set to zero.
After the turbine stop valves have been opened using the start-up and load
limit device, hydraulic speed governor as well as the start-up and limit load
device are then set to their upper limit positions ( 100% position).
As the turbine has already been run up to a low speed (approx. 200 rpm )
by the hydraulic turning gear, the electrical speed measurement system
supplies a voltage signal proportional to speed as actual speed.
The speed setpoint nr is raised to make the speed controller take control, the
turbine is then run up to rated speed by increasing the speed setpoint further
and the generator synchronized with the power system. The TSE component
ensures run-up of the turbine at an optimum rate and without exceeding
permitted thermal stress limits.
The lift setpoint controls the turbine generator unit once the generator has
been synchronized with the power system.
After this, control valve lift is set by adjusting the lift setpoint manually to
the appropriate level in manual mode.
The output signal from the lift setpoint controller is increased and at the
same time the speed setpoint is reduced to a value corresponding to approx.
10% unit load. In auto mode, the output of lift setpoint controller is
determined by the adapted pressure deviation signal from steam generator
pressure control system and lift setpoint Lr tracks the lift setpoint controller
output. The speed controller is inactive but is kept on stand-by to take over
control of the turbine generator and maintain speed close to rated speed on
full load rejection down to station load. The TSE ensures optimum power
increase rates on turbine generator loading, but without exceeding permitted
thermal stress limits.
The lift setpoint rate dL/dt is set on the main control room panel 6610-PL-10
to give the max. permitted rate of change for lift.
If valve opening is limited for any reason, the lift setpoint is lowered. This
results in take-over of turbine generator control by the lift setpoint controller
via the control selection circuit
8.3 Shutdown
The lift setpoint is set to zero on turbine generator shutdown. This causes
unloading of the turbine generator in line with the set rates.
The lift set point is lowered until all control valves are throttled such that the
generator breaker opens via the anti-motoring protection ( this responding
when the generator motors and takes up more than 2 or 3 % reverse power
from the power system ) and the generator is de-excited.
The turbine trip pushbutton is then pressed to initiate turbine trip, this
resulting in closure of the turbine stop valves.
The above operating procedure ensures that the turbine generator is not
disconnected from the power system until the control valves have closed fully
( to avoid the risk of turbine overspeed).
During rundown of the turbine generator after turbine trip push button is
pressed, the speed setpoint nr is tracked to actual speed. This means that
the speed setpoint adjuster is already set to the correct value for restart.
On load rejection to station load or zero load (i.e., in the event of sudden
disconnection of the loaded turbine generator from the power system), the
lift setpoint signal is immediately deactivated. This results in a large
magnitude deviation in the control valves in close direction for the lift
---------------------------------------------------------------------------------------------- Sheet no. 19 of 37
STE, BHEL-HARDWAR
NPC DOC. NO. TAPP-3/64110/5526/DN/R0---------------------------------4 13300 00 486 ----
REV. NO. 01
controller. The speed controller takes over control of the turbine generator
unit. This results in closure of the turbine control valves at maximum speed,
as the speed setpoint was set to a level equivalent to 10% load on turbine
generator start-up and this signal now takes effect as input signal for the lift
controller.
The only difference between a load rejection to station load and a load
rejection to zero load is in the magnitude of the resulting transient speed
rise. The speed rise is less for load rejection to station load due to the load
which remains.
The electro hydraulic controller or hydraulic controller hold the speed of the
turbine generator below the trip setting for the overspeed trips under all
operating conditions.
9 Alarms