3.8. The maximum flux density in any part of the core and yoke at the rated MVA,
voltage and frequency shall be such that under 10 % continuous over-voltage
condition it does not exceed 1.9 Tesla at all tap positions.
3.9. Transformers shall withstand without damage, heating due to the combined
voltage and frequency fluctuations which produce the following over fluxing
conditions:
3.10. The air core reactance of HV winding of transformer shall not be less than
20% for 400kV class Transformer.