SPPA-T3000 User Guide

Diagnostic System (1/1)


Diagnostic System (1/1) Page: 2 of 126
LKZ:DE AL:N ECCN:4E992

Documenation User Guide

SPPA-T3000 USER GUIDE .............................................................................................................................................. 1

1 DIAGNOSTIC VIEW................................................................................................................................ 4

1.1 General Layout ...................................................................................................................................... 5

1.2 Diagnostic Hierarchy Tree.................................................................................................................... 6


1.2.1 Filter on Diagnostic View......................................................................................................................... 7
1.2.2 Searching in the Diagnostic View ........................................................................................................... 9
1.2.3 Opening Plant Displays ......................................................................................................................... 11
1.2.4 Zoom...................................................................................................................................................... 12
1.2.5 Saving the View..................................................................................................................................... 14

1.3 Containers in the Diagnostic View .................................................................................................... 14


1.3.1 System Diagram Root Node ................................................................................................................. 15
1.3.2 Client Node............................................................................................................................................ 16
1.3.3 Host Computer Node............................................................................................................................. 16
1.3.4 Service Container Node ........................................................................................................................ 17
1.3.5 Alarm Printer Container Node ............................................................................................................... 19
1.3.6 OPC-Client Container Node.................................................................................................................. 21
1.3.7 OPC-Server Container Node ................................................................................................................ 24
1.3.8 Alarm Container Node........................................................................................................................... 27
1.3.9 S7 Runtime Container Node ................................................................................................................. 29
1.3.10 Runtime Container Node....................................................................................................................... 32
1.3.10.1 Diagnostic Information of Automation Functions and Compound Components .................................. 35
1.3.11 CM Runtime Container Node ................................................................................................................ 36
1.3.12 Archive Node ......................................................................................................................................... 39
1.3.13 SIMATIC Communication Container Node ........................................................................................... 41
1.3.14 CFC Chart Container Node................................................................................................................... 43
1.3.15 SIMATIC Fail-Safe Automation Function Container Node ................................................................... 45
1.3.16 SIMATIC S7 FM458 Container Node.................................................................................................... 48
1.3.17 Diagnostic Container Node ................................................................................................................... 49
1.3.18 SIMATIC Hardware Configuration Container Node.............................................................................. 51
1.3.19 IO Tools Container Node ...................................................................................................................... 53
1.3.20 License Server Container Node............................................................................................................ 55
1.3.21 Monitor Container Node ........................................................................................................................ 57
1.3.22 Project Container Node ......................................................................................................................... 59
1.3.23 Plant Display Server Node .................................................................................................................... 61
1.3.24 Report Container ................................................................................................................................... 64
1.3.25 Trend Display Server Node................................................................................................................... 66
1.3.26 Call Home Container Node ................................................................................................................... 68
1.3.27 Technological Calculation Container Node........................................................................................... 71
1.3.28 Plant Monitor Container Node............................................................................................................... 74

1.4 Diagnostic Information Category ...................................................................................................... 75


1.4.1 Status Information ................................................................................................................................. 76
1.4.2 Diagnostic Information........................................................................................................................... 76
1.4.3 Logging Information............................................................................................................................... 81
1.4.3.1 Configuring of Diagnostic Logging Information..................................................................................... 82
1.4.3.2 Adjusting the Location for Diagnostic Logs........................................................................................... 84
1.4.3.3 Client Logging........................................................................................................................................ 86

1.5 Multi Unit .............................................................................................................................................. 88


1.5.1 Starting the View ................................................................................................................................... 89

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 3 of 126
LKZ:DE AL:N ECCN:4E992

2 FAULT TRACKING............................................................................................................................... 91

2.1 Navigation to Connected Ports ......................................................................................................... 91

2.2 Details in Diagnostic View.................................................................................................................. 93


2.2.1 Service Container.................................................................................................................................. 93
2.2.2 Alarm Printer Container......................................................................................................................... 94
2.2.3 OPC-Client Container............................................................................................................................ 95
2.2.4 OPC-Server Container .......................................................................................................................... 96
2.2.5 Alarm Container .................................................................................................................................... 96
2.2.6 Runtime Container ................................................................................................................................ 97
2.2.7 CM Runtime Container........................................................................................................................ 101
2.2.8 S7 Runtime Container ......................................................................................................................... 109
2.2.9 Archive Container................................................................................................................................ 112
2.2.10 SIMATIC Communication Container................................................................................................... 113
2.2.11 CFC Chart Container........................................................................................................................... 114
2.2.12 SIMATIC Failsafe Automation Function Container............................................................................. 114
2.2.13 SIMATIC S7 FM458 Container ........................................................................................................... 116
2.2.14 Diagnostic Container ........................................................................................................................... 116
2.2.15 SIMATIC Hardware Configuration Container...................................................................................... 117
2.2.16 IO-Tools ............................................................................................................................................... 118
2.2.17 License Server..................................................................................................................................... 118
2.2.18 Monitor Container................................................................................................................................ 119
2.2.19 Project Container................................................................................................................................. 120
2.2.20 Plant Display Server............................................................................................................................ 120
2.2.21 Report Container ................................................................................................................................. 122
2.2.22 Trend Display Server........................................................................................................................... 122
2.2.23 Call Home Container ........................................................................................................................... 123
2.2.24 Technological Calculation Container .................................................................................................. 124
2.2.25 Plant Monitor Container ...................................................................................................................... 124

2.3 Quality Codes .................................................................................................................................... 125


2.3.1 List of GOOD Quality Codes ............................................................................................................... 125
2.3.2 List of UNCERTAIN Quality Codes..................................................................................................... 125
2.3.3 List of BAD Quality Codes................................................................................................................... 126

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 4 of 126
LKZ:DE AL:N ECCN:4E992

DIAGNOSTIC SYSTEM
The SPPA-T3000 Diagnostic system supports the user with information collected from different components within the
SPPA-T3000 system for:

• Investigations of failure conditions in cases of disturbances in the system


• Status information on demand
• Maintenance purposes.
• for SPPA-T3000 System Software administration purposes

The diagnostic mechanisms can be divided into

• Event driven diagnostics


• Important events are reported automatically by the diagnostic system. The event driven diagnostic leads to
very fast fault detection, but it also generates the highest system load. Event driven diagnostic is mainly used
for I&C fault detection
• Dialog driven diagnostic
• The dialog driven diagnostic enables the user to access components by selection. Information about system
configuration and releases can be reported. These Reports can support detailed inspections on faults
reported by the event driven diagnostic. Furthermore a trace functionality is available to supervise the data
inside and between the different components.

General Aspects

The SPPA-T3000 Diagnostic System handles the following main functions

• Fault Analysis
• The Fault analysis provides
o Automatic detection and reporting of DCS faults for fault tracking
o Processing of the detected faults with compressed representation in graphical form
o User guidance to the origin of the fault by device structure or by selection of I&C Alarms
o Display of the detected components in graphical and textual representation
• Display of Status Information
o The information is shown in a graphical manner by using the topology, the hierarchical structure and
the configuration of the complete Control System
o Display of the rack disposition and the hardware and software releases
o Online documentation
o Usage of System resources
o Condition of wear and tear parts
• State Report
o Displays lists of component specific information
o Overview of system status like forced signals and availability down to single devices.

1 Diagnostic View
The system diagnostic information is presented in the Diagnostic View.
The Diagnostic View is activated from the Workbench in the menu Application, menu item Diagnostic View .

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 5 of 126
LKZ:DE AL:N ECCN:4E992

Alternatively, the Diagnostic View can be opened in the following ways:

In a Dynamic Function Diagram via the context menu (Select an AF Block, then right mouse click >
Diagnostic View ).

In a Plant Display via the context menu (Select a Pictogram, then right mouse click > Diagnostic View ).

1.1 General Layout


The Diagnostic View has the following structure:

• A menu bar with the following drop down menus:


o File
o Edit
o View
o Help
• The Diagnostics View consists of two Frames:
o The Tree View in the left hand Frame, containing the Diagnostic Hierarchy.
o The detailed information on the right hand part.

The Tree View contains the diagnostic hierarchy. Every possible source of diagnostic information, diagnostic
component of the Automation Function Block, hardware or module proxy or alarm system, is found via the diagnostic
hierarchy.

Field devices are not diagnostic components in this context. However, if they provide diagnostic data by a
proprietary interface, their information is not conveyed through the use of a Container.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 6 of 126
LKZ:DE AL:N ECCN:4E992

The detailed information in the right hand part of the view is automatically updated with the selected diagnostic
component.

Alternatively, the Diagnostic View can be opened in the following ways:

In a Dynamic Function Diagram via the context menu (Select an AF Block, then right mouse click >
Diagnostic View ).

In a Plant Display via the context menu (Select a Pictogram, then right mouse click > Diagnostic View ).

1.2 Diagnostic Hierarchy Tree


After the Diagnostic View is opened in the Workbench, the Tree View appears, displaying the diagnostic hierarchy.

To get more direct access to the necessary information, it is possible to search for a specific component or to
filter according to a defined condition.

The diagnostic hierarchy is designed as part of the engineering process. The diagnostic hierarchy is normally designed
to provide access to information about:

• Proxies: Hardware Proxies and Management Proxies provide diagnostic information about IO devices, bus
communication and server components.
• Containers: Containers running on servers provide diagnostic information and have control functionality via
the Diagnostic View.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 7 of 126
LKZ:DE AL:N ECCN:4E992

The current state of Alarms of a component or a Container. When a symbol appears left of the container the meaning
is as follows:

• Symbol with an exclamation mark in the center


• The Server / Container is down.


• Symbol with a question mark in the center

• The state could not be identified. This state occurs if the monitor on the corresponding server is not running.
• Symbol with a triangle in the center

• The container is currently starting.

After one of the displayed elements is selected, the respective detailed information is displayed in the right hand part of
the Diagnostic View and will be updated automatically if values change.
It is possible to stop the automatic update by pressing the toggle button above the detailed information table in order to
freeze the display for analysis.

1.2.1 Filter on Diagnostic View


A filter Algorithm enables the user to show only the required portion of the tree by use of a search string. Within the
filter string one asterisk (*) is possible as a wildcard to represent an unspecified number of characters.

To open the filter tree dialog

1. Select in the opened Diagnostic View the menu Edit and then the menu item Filter.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 8 of 126
LKZ:DE AL:N ECCN:4E992

The filter dialog appears.


2. Enter the search pattern to be filtered.

3. The drop down list Type further allows the selection to be limited to:
o Containers,
o Function Diagrams or
o Automation Function Blocks
4. Select Match Case if the filter is to be case sensitive.
5. Confirm the selection by pressing the Filter button in the dialog box, or
6. Only the parts matching to the search pattern remain in the Tree View

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 9 of 126
LKZ:DE AL:N ECCN:4E992

To deactivate a filtered display open the filter dialog and press the button Restore.

1.2.2 Searching in the Diagnostic View


The Find option allows the user to search for Nodes in the tree. The first Node which contains an item matching to the
given pattern is selected in the tree.

To open the search tree dialog

1. Select in the opened Diagnostic View the menu Edit and then the menu item Find.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 10 of 126
LKZ:DE AL:N ECCN:4E992

The search dialog appears.

2. Enter the search pattern. The search pattern is not case sensitive. Within the search string one asterisk * is
possible as a wildcard to represent an unspecified number of characters.
3. Select Match Case if the search is to be case sensitive.
4. Confirm the selection by
o clicking the Search button in the dialog box, or
o click the Cancel button to abort the dialog.
Usually the Algorithm starts at the current selected Node and considers all subordinated nodes in the tree.
When a check for Search subordinate nodes of selected node only is applied, than the search Algorithm
starts at the current position and searches subordinated Nodes, only, for the pattern.
5. The first appearance of the Node which matches the pattern is selected in the Tree View and the related
information is displayed.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 11 of 126
LKZ:DE AL:N ECCN:4E992

Depending on the position of the first item in the tree it might be necessary to scroll down the contents of the
tree view.

When the Search Again button is pressed after a successful result, the search will skip to the next
matching Node in the hierarchy.

Alternatively the Search function can be selected over the context menu: (Right Mouse Click : Find)

1.2.3 Opening Plant Displays


Plant Displays can be opened in the Diagnostic View. Plant Displays in the diagnostic hierarchy typically contain the
system configuration, e.g. the layout of IO modules and the bus configuration.

To open a Plant Display in the Diagnostic View proceed as follows:

The Diagnostic View is open.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 12 of 126
LKZ:DE AL:N ECCN:4E992

1. Navigate through the diagnostic hierarchy tree, and find the Plant Display.
2. Select the Plant Display by clicking on it.

The Plant Display will open in the List View of the Diagnostic View.

The Plant Display can be controlled over the View menu:

Zoom to Original Size

Fit to View

Zoom by 200%

Zoom by 50%

1.2.4 Zoom
The zoom functions allow the user to control the magnification of a selected diagram in the Diagram Editor. When
zooming in the objects in the diagram will appear larger, when zooming out they will appear smaller.

The zoom control functions are available in the View menu of the Diagnostic View, or directly on the toolbar.

The options for zoom control are described below:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 13 of 126
LKZ:DE AL:N ECCN:4E992

Fit to View

Select the View menu, then Fit to View from the drop down menu. Alternatively click on the icon on the toolbar:

The diagram is zoomed to a size where every symbol in the diagram is shown. The outermost symbols will be at the
edges of the diagram window. The diagram may appear distorted in this mode.

Zoom by 200%

Select the View menu, then Zoom by 200% from the drop down menu. Alternatively via the context menu (Right
Mouse Click > View > Zoom 200%), or click on the icon on the toolbar:

The diagram is zoomed to double its size.

Zoom by 50%

Select the View menu, then Zoom by 50% from the drop down menu. Alternatively via the context menu (Right Mouse
Click > View > Zoom 50%), or click on the icon on the toolbar:

The diagram is zoomed to half its size.

Zoom to Original Size

Select the View menu, then Zoom Original Size from the drop down menu. Alternatively click on the icon on the
toolbar, or via the context menu (Right Mouse Click > View > Zoom):

The diagram is zoomed to its original size as when it was opened.

Zoom in Rectangle

Click on the icon on the toolbar:

Using the cursor, drag a rectangle around the area to be zoomed in the diagram.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 14 of 126
LKZ:DE AL:N ECCN:4E992

The diagram is zoomed in to the rectangle.

1.2.5 Saving the View


The Save View option controls the default layout that appears when the user activates the Diagnostic View.

The Diagnostic View is open.

Proceed as follows:

Select the View Menu, then Save View.

The relative sizes of the Tree View and detailed information window, window are saved. Any filter settings will
also be saved.

The next time the user logs in, the settings that were stored in the session before are available.

1.3 Containers in the Diagnostic View


After the Diagnostic View is opened in the Workbench, the left hand part of the window displays a Tree View.
The tree starts at the top level with the Project Node.

Below the project node the node Client displays the client computers which are currently connected to SPPA-T3000.

The Host Computer node, which is displayed subordinated to the Project Node, contains further containers. Depending
on the current project configuration more than one host computer may exist. In that case all the Host Computers
assigned to the project node are displayed.
Assigned to the existing Host Computer nodes the user will find the respective Containers. Each container collects the
diagnostic information of the assigned Components. Each existing diagnostic component of the SPPA-T3000 system
is assigned to a container.

Field devices are not diagnostic components in this context. However, if they provide diagnostic data via a
proprietary interface the information is conveyed by other means, and not by a container.

The containers as listed below are available:

• Alarm Printer
• OPC-Client
• OPC-Server
• Alarm Container

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 15 of 126
LKZ:DE AL:N ECCN:4E992

• S7 Runtime Container
• Runtime Container
• CM Runtime Container
• Archive Container
• SIMATIC Communication Container
• Diagnostic Container
• SIMATIC Hardware Communication Container
• CFC Chart Container
• SIMATIC Fail-Safe Automation Function Container
• SIMATIC S7 FM458 Container
• Diagnostic Container
• SIMATIC Hardware Configuration Container
• IO Tools
• License Server Container
• Monitor Container
• Project Container
• Plant Display Server
• Report Container
• Trend Display Container
• Call Home Container

For detailed information refer to the respective description.

1.3.1 System Diagram Root Node


The System Diagram Root Node is the top level Node in the Diagnostic View.

Static Information

The displayed static information consists of:

• The Node name of the System Diagram Root Node


• The ID in the diagnostic system of the Project Node.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 16 of 126
LKZ:DE AL:N ECCN:4E992

• This ID is fixed during the first setup of the project and is needed for system internal identification.
• A description text for this Node.

Dynamic Information

There is no dynamic data available for this Node in the diagnostic system.

1.3.2 Client Node


The Client Node displays the client computers which are currently logged in, with their IP address.

Static Information

The displayed static information consists of:

• The IP address of the client computer


• The used Login name (username).
• A description text for the client.

Dynamic Information
• Status page:
• The Status of the client computer and the last access time is displayed in the section Status

1.3.3 Host Computer Node


The Host Computer Node covers the Diagnostic Containers. In the case that more than one Host Computer exists in a
project the Containers might be distributed to the existing Host Computers. The assignment will then be displayed
accordingly.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 17 of 126
LKZ:DE AL:N ECCN:4E992

Static Information

The displayed static information consists of:

• The Node name of the computer


• The ID in the diagnostic system of the Host Computer.
• This ID is fixed during the first setup of the project and is needed for system internal identification.
• A description text for this Node

Dynamic Information

There is no dynamic data available for this Node in the diagnostic system.

It is not possible to change any of the displayed information in the Diagnostic View

1.3.4 Service Container Node


A service container provides a standardized execution environment for application services. Application services are
software components which can be added to the service container and can then run in the system.

The application services are located beneath the service container in the diagnostic hierarchy.

Static Information

The displayed static information consists of:

• The Node name of the Container.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 18 of 126
LKZ:DE AL:N ECCN:4E992

• The ID in the diagnostic system of the Container.


• This ID is fixed.
• A description text for this Node.

Dynamic Information

The displayed dynamic information consists of:

• Status page:
• possible information is
o Started:
The container is starting up.
o Running:
Is indicated after a successful startup. The container is in operation.
o Terminating:
The container is shutting down.
For possible reasons refer to Fault Tracking.
o Stopped:
Is indicated after the terminating process is finished. The container is stopped.
o Failed:
The container is not in operation.
For possible reasons refer to Fault Tracking.
• Diagnostic page:
• There is no dynamic data available for this Node in the diagnostic system.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 19 of 126
LKZ:DE AL:N ECCN:4E992

• Logging page:
• After a click on the tab Logging, the logging page will be opened:

The intention of the logging page is to display very specific information of the SPPA-T3000 System Software.
This page is not needed for engineering or operation purposes
but supports computer administration activities. Details concerning the configuration of the logging function are
described in Logging Information.

1.3.5 Alarm Printer Container Node


The Alarm Printer Container Node displays the diagnostic information for the Alarm Printer.

Static Information

The displayed static information consists of:

• The Node name of the Alarm Printer Container.


• The ID in the diagnostic system of the Alarm Printer Container.
• This ID is fixed and needed for system internal identifications.
• A description text for this Node

Dynamic Information

The displayed dynamic information consists of:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 20 of 126
LKZ:DE AL:N ECCN:4E992

• Status page:
• Possible indications are
o Started:
The Alarm Printer Container is starting up.
o Running:
Is indicated after a successful start up. The Alarm Container is in operation.
o Terminating:
The Alarm Printer Container is shutting down.
For possible reasons refer to Fault Tracking.
o Stopped:
Is indicated after the shutdown process is finished.
o Failed:
The Alarm Printer Container is not in operation.
For possible reasons refer to Fault Tracking.
o Action button:
This button allows starting or stopping the Alarm Container. A stopped container can be restarted
either by using this Action button, or with a SPPA-T3000 system restart.
The operation of this button is restricted by the access rights as described in the chapter Project
Administration.
• Diagnostic page:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 21 of 126
LKZ:DE AL:N ECCN:4E992

• After clicking on the tab Diagnostic the diagnostic page will be opened:

• In the area Diagnostic Ports, the status at several Ports of the Alarm Printer Container is provided. With
buttons above the detail area, the diagnostic information can be filtered for the categories:

It is not possible to change any of the displayed information in the Diagnostic View

A detailed category description is available in Diagnostic Information Category

• Logging page:
• There is no logging information available for this Node in the diagnostic system.

1.3.6 OPC-Client Container Node


The OPC-Client Container Node displays the state of the connected Runtime Containers.

Static Information

The displayed static information consists of:

• The Node name of the OPC-Client Container.


• The ID in the diagnostic system of the OPC-Client Container.
• A description text for this Node.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 22 of 126
LKZ:DE AL:N ECCN:4E992

Dynamic Information

The displayed dynamic information consists of:

• Status page:
• possible indications are
o Started:
The OPC-Client Container is starting up.
o Running:
Is indicated after a successful start up. The OPC-Client Container is in operation.
o Terminating:
The OPC-Client Container is shutting down.
For possible reasons refer to Fault Tracking.
o Stopped:
Is indicated after the shutdown process is finished.
o Failed:
The OPC-Client Container is not in operation.
For possible reasons refer to Fault Tracking.
o Connected AFCS: In this area the status of connections to other Runtime Containers is displayed
for those Runtime Containers which send signals to the OPC-Client Container.
o Action button:
This button allows starting or stopping the OPC-Client Container.
A stopped container, can be restarted ether by using this Action button, or with a SPPA-T3000
system restart.
The operation of this button is restricted by the access rights as described in the chapter Project
Administration.
• Diagnostic page:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 23 of 126
LKZ:DE AL:N ECCN:4E992

• After clicking on the tab Diagnostic the diagnostic page will be opened:

• In the area Diagnostic Ports, the status at several Ports of the OPC-Client Container is provided. With buttons
above the detail area, the diagnostic information can be filtered for the categories:
o Diagnostic Ports
o I&C Ports
o Plant Display Ports
o Signal Ports with values classified as BAD quality
o all other Ports

It is not possible to change any of the displayed information in the Diagnostic View

A detailed category description is available in Diagnostic Information Category

• Logging page:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 24 of 126
LKZ:DE AL:N ECCN:4E992

• After a click on the tabulator Logging the logging page will be opened:

The intention of the logging page is to display very specific information of the SPPA-T3000 System Software.
This page is not needed for engineering or operation purposes
but supports computer administration activities. Details concerning the configuration of the logging function are
described in Logging Information.

1.3.7 OPC-Server Container Node


Information concerning the OPC-Server Container itself is available at the OPC-Server Container node.

Static Information

The displayed static information consists of:

• The Node name of the OPC-Server Container.


• The ID in the diagnostic system of the OPC-Server Container.
• This ID is fixed and needed for system internal identifications.
• A description text for this Node

Dynamic Information

The displayed dynamic information consists of:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 25 of 126
LKZ:DE AL:N ECCN:4E992

• Status page:
• Possible indications are
o Started:
The OPC-Server Container is starting up.
o Running:
Is indicated after a successful start up. The OPC-Server Container is in operation.
o Terminating:
The OPC-Server Container is shutting down.
For possible reasons refer to Fault Tracking.
o Stopped:
Is indicated after the shutdown process has finished.
o Failed:
The OPC-Server Container is not in operation.
For possible reasons refer to Fault Tracking.
o Action button:
This button allows starting or stopping the OPC-Server Container.
A stopped container can be restarted either by using this Action button, or with a SPPA-T3000
system restart.
The operation of this button is restricted by the access rights as described in the chapter Project
Administration.
• Diagnostic page:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 26 of 126
LKZ:DE AL:N ECCN:4E992

• After clicking on the tab Diagnostic the diagnostic page will be opened:

• In the area Diagnostic Ports, the status at several Ports of the OPC-Server Container is provided. With
buttons above the detail area, the diagnostic information can be filtered for the categories:
o Diagnostic Ports
o I&C Ports
o Plant Display Ports
o Signal Ports with values classified as BAD quality
o all other Ports
One or more buttons can be selected, the Port information will be displayed accordingly.

It is not possible to change any of the displayed information in the Diagnostic View

A detailed category description is available in Diagnostic Information Category

• Logging page:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 27 of 126
LKZ:DE AL:N ECCN:4E992

• After a click on the tabulator Logging the logging page will be opened:

The intention of the logging page is to display very specific information of the SPPA-T3000 System Software.
This page is not needed for engineering or operation purposes
but supports computer administration activities. Details concerning the configuration of the logging function are
described in Logging Information.

1.3.8 Alarm Container Node


The Alarm Container Node collects the Alarms, generated in the system, for displaying.

Static Information

The displayed static information consists of:

• The Node name of the Alarm Container.


• The ID in the diagnostic system of the Alarm Container.
• This ID is fixed and needed for system internal identifications.
• A description text for this Node

Dynamic Information

The displayed dynamic information consists of:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 28 of 126
LKZ:DE AL:N ECCN:4E992

• Status page:
• possible indications are
o Started:
The Alarm Container is starting up.
o Running:
Is indicated after a successful start up. The Alarm Container is in operation.
o Terminating:
The Alarm Container is shutting down.
For possible reasons refer to Fault Tracking.
o Stopped:
Is indicated after the shutdown process has finished.
o Failed:
The Alarm Container is not in operation.
For possible reasons refer to Fault Tracking.
o Action button:
This button allows starting or stopping the Alarm Container.
A stopped container can be restarted either by using this Action button, or with a SPPA-T3000
system restart.
The operation of this button is restricted by the access rights as described in the chapter Project
Administration.
• Diagnostic page:
• For the alarm container the diagnostic page is currently not used.
• Logging page:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 29 of 126
LKZ:DE AL:N ECCN:4E992

• After a click on the tabulator Logging the logging page will be opened:

• For the alarm container currently no packages are selectable at the logging page.

1.3.9 S7 Runtime Container Node


The S7 Runtime Container Node displays the diagnostic information of the S7 Runtime Container.

Subordinate to this Node, the diagnostic information of the Automation Functions running in the S7 Runtime Container
is presented.

Static Information

The displayed static information consists of:

• The Node name of the respective Runtime Container.


• This ID is defined during the project setup.
• A description text for this Node

Dynamic Information

The displayed dynamic information consists of:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 30 of 126
LKZ:DE AL:N ECCN:4E992

• Status page:
• possible information is
o Started:
The Runtime Container is starting up.
o Running:
Is indicated after a successful startup. The Runtime Container is in operation.
o Terminating:
The Runtime Container is shutting down.
For possible reasons refer to Fault Tracking.
o Stopped:
Is indicated after the terminating process is finished. The Runtime Container is stopped.
o Failed:
The S7 Runtime Container is not in operation.
For possible reasons refer to Fault Tracking.
o Connected AFCs:
In this area the status of connections to other Runtime Containers is displayed for those Runtime
Containers which send signals to the displayed S7 Runtime Container.

For S7 Runtime Containers the Action Stop is not available.

• Diagnostic page:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 31 of 126
LKZ:DE AL:N ECCN:4E992

• After clicking on the tab Diagnostic the diagnostic page will be opened:

• In the area Diagnostic Ports, the status at several Ports of the Runtime Container is provided. With buttons
above the detail area, the diagnostic information can be filtered for the categories
o Diagnostic Ports
o I&C Ports
o HMI (Plant Display) Ports
o Not GOD Quality Ports
o all other Ports

Details of the possible Port status signals are described in S7 Runtime Container of Fault Tracking
information.

It is not possible to change any of the displayed information in the Diagnostic View

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 32 of 126
LKZ:DE AL:N ECCN:4E992

A detailed category description is available in Diagnostic Information Category

• Logging page: This Container has no logging page.

1.3.10 Runtime Container Node


The Runtime Container Node displays the diagnostic information of the Runtime Container.

Subordinate to this Node, the diagnostic information of the Automation Functions running in the Runtime Container is
presented.

Static Information

The displayed static information consists of:

• The Node name of the respective Runtime Container.


• The ID in the diagnostic system of the Runtime Container.
• This ID is defined during the project setup.
• A description text for this Node

Dynamic Information

The displayed dynamic information consists of:

• Status page:
• possible information is
o Started:
The Runtime Container is starting up.
o Running:
Is indicated after a successful startup. The Runtime Container is in operation.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 33 of 126
LKZ:DE AL:N ECCN:4E992

o Terminating:
The Runtime Container is shutting down.
For possible reasons refer to Fault Tracking.
o Stopped:
Is indicated after the terminating process has finished. The Runtime Container is stopped.
o Failed:
The Runtime Container is not in operation.
For possible reasons refer to Fault Tracking.
o Action button:
This button allows starting or stopping the Runtime Container.
A stopped container can be restarted either by using this Action button, or with a SPPA-T3000
system restart.
The operation of this button is restricted by the access rights as described in chapter Project
Administration
o Connected AFCs:
In this area the status of connections to other Runtime Containers is displayed for those Runtime
Containers which send signals to the displayed Runtime Container.
• Diagnostic page:
• After clicking on the tab Diagnostic the diagnostic page will be opened:

• In the area Diagnostic Ports, the status at several Ports of the Runtime Container is provided. With buttons
above the detail area, the diagnostic information can be filtered for the categories
o Diagnostic Ports
o I&C Ports
o HMI (Plant Display) Ports
o Not GOD Quality Ports
o all other Ports

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 34 of 126
LKZ:DE AL:N ECCN:4E992

Details of the possible Port status signals are described in Runtime Container of Fault Tracking information.

It is not possible to change any of the displayed information in the Diagnostic View

A detailed category description is available in Diagnostic Information Category

• Logging page:
• After clicking on the tab Logging, the logging page will be opened:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 35 of 126
LKZ:DE AL:N ECCN:4E992

The intention of the logging page is to display very specific information of the SPPA-T3000 System Software.
This page is not needed for engineering or operation purposes
but supports computer administration activities. Details concerning the configuration of the logging function are
described in Logging Information.

1.3.10.1 Diagnostic Information of Automation Functions and


Compound Components
The diagnostic information concerning Automation Functions and Compound Components is available subordinated to
the Runtime Container Node.
To display the diagnostic information of an AF or CC, open the Diagnostic View.

1. In the Tree View open the sub tree of the Runtime Container to which the desired AF or CC is assigned.
A list of all Function Diagrams assigned to this Container appears.
2. Within this list of Function Diagrams select the Function Diagram which contains the desired AF or CC.
Detailed information appears in the right hand part of the Diagnostic View.

The user can use the search function or the filter function of the Diagnostic View if the assignment of an AF or
CC to a Runtime Container is not known.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 36 of 126
LKZ:DE AL:N ECCN:4E992

From a Faceplate, the diagnostic page of the respective AF or CC can be opened immediately.

In this case the diagnostic view is shown without the hierarchy. Only the detailed view (the right hand side) of
the complete diagnostic view is shown.

Details concerning the Ports and possible values of any AF or CC are described in the Library, collected in the
tables
Description of input ports
Description of output ports and
Exception handling.

1.3.11 CM Runtime Container Node


The CM Runtime Container Node displays the diagnostic information of the CM Runtime Container.

Subordinate to this Node, the diagnostic information of the Automation Functions running in the Runtime Container is
presented.

Static Information

The displayed static information consists of:

• The Node name of the respective CM Runtime Container.


• The ID in the diagnostic system of the CM Runtime Container.
• This ID is defined during the project setup.
• A description text for this Node

Dynamic Information

The displayed dynamic information consists of:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 37 of 126
LKZ:DE AL:N ECCN:4E992

• Status page:
• possible information is
o Started:
The CM Runtime Container is starting up.
o Running:
Is indicated after a successful startup. The CM Runtime Container is in operation.
o Terminating:
The CM Runtime Container is shutting down.
For possible reasons refer to Fault Tracking.
o Stopped:
Is indicated after the terminating process is finished. The CM Runtime Container is stopped.
o Failed:
The CM Runtime Container is not in operation.
For possible reasons refer to Fault Tracking.
o Action button:
This button allows starting or stopping the CM Runtime Container.
A stopped container, can be restarted ether by using this Action button, or with a SPPA-T3000
system restart.
The operation of this button is restricted by the access rights as described in chapter Project
Administration
o Connected AFCs:
In this area the status of connections to other Runtime Containers is displayed for those Runtime
Containers which send signals to the displayed CM Runtime Container.
• Diagnostic page:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 38 of 126
LKZ:DE AL:N ECCN:4E992

• After clicking on the tab Diagnostic the diagnostic page will be opened:

• In the area Diagnostic Ports, the status at several Ports of the CM Runtime Container is provided. With
buttons above the detail area, the diagnostic information can be filtered for the categories
o Diagnostic Ports
o I&C Ports
o HMI (Plant Display) Ports
o Not GOD Quality Ports
o all other Ports

Details of the possible Port status signals are described in the chapter CM Runtime Container of Fault
Tracking information.

It is not possible to change any of the displayed information in the Diagnostic View

A detailed category description is available in Diagnostic Information Category

• Logging page:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 39 of 126
LKZ:DE AL:N ECCN:4E992

• After clicking on the tab Logging, the logging page will be opened:

The intention of the logging page is to display very specific information of the SPPA-T3000 System Software.
This page is not needed for engineering or operation purposes
but supports computer administration activities. Details concerning the configuration of the logging function are
described in Logging Information.

1.3.12 Archive Node


The Archive provides a continuous storage for process values which can include analog signal values or binary status
changes. The Archive stores the time stamped values of such process variables.
Only values available in the Archive can be used in trends, logs or reports.

The archive container is the runtime environment for the archive. Information from the archive container itself is
available at the archive container node.

Static Information

The displayed static information consists of:

• The Node name arc


• The ID in the diagnostic system of the host computer.
• This ID is fixed during the first setup of the project and is needed for system internal identification.
• A description text for this Node

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 40 of 126
LKZ:DE AL:N ECCN:4E992

Dynamic Information

The displayed dynamic information consists of:

• Status page:
• Possible information is
o Started:
The archive container is starting up.
o Running:
Is indicated after a successful startup. The archive container is in operation.
o Terminating:
The archive container is shutting down.
For possible reasons refer to Fault Tracking.
o Stopped:
Is indicated after the terminating process has finished. The archive container is stopped.
o Failed:
The archive container is not in operation.
For possible reasons refer to Fault Tracking.
o Action button:
This button allows starting or stopping the archive container.
A stopped container can be restarted either by using this Action button, or with a SPPA-T3000
system restart.
The operation of this button is restricted by the access rights as described in the chapter Project
Administration
• Diagnostic page:
• There is no dynamic data available for this Node in the diagnostic system.
• Logging page:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 41 of 126
LKZ:DE AL:N ECCN:4E992

1.3.13 SIMATIC Communication Container Node


The SIMATIC Communication Container contains all dynamic process values of an S7-CPU.

Information concerning the SIMATIC Communication Container itself is available at the SIMATIC Communication
Container node.

Static Information

The displayed static information consists of:

• The Node name of the SIMATIC Communication Container.


• The ID of the SIMATIC Communication Container.
• A description text for this Node

Dynamic Information

The displayed dynamic information consists of:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 42 of 126
LKZ:DE AL:N ECCN:4E992

• Status page:
• possible information is
o Started:
The SIMATIC Communication Container is starting up.
o Running:
Is indicated after a successful startup. The SIMATIC Communication Container is in operation.
o Terminating:
The SIMATIC Communication Container is shutting down.
For possible reasons refer to Fault Tracking.
o Stopped:
Is indicated after the terminating process has finished. The SIMATIC Communication Container is
stopped.
o Failed:
The SIMATIC Communication Container is not in operation.
For possible reasons refer to Fault Tracking.
o Action button:
This button allows starting or stopping the SIMATIC Communication Container.
A stopped container can be restarted either by using this Action button, or with a SPPA-T3000
system restart.
The operation of this button is restricted by the access rights as described in Project Administration
• Diagnostic page:
• There is no dynamic data available for this Node in the diagnostic system.
• Logging page:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 43 of 126
LKZ:DE AL:N ECCN:4E992

• After a click on the tab Logging, the logging page will be opened:

The intention of the logging page is to display very specific information of the SPPA-T3000 System Software.
This page is not needed for engineering or operation purposes
but supports computer administration activities. Details concerning the configuration of the logging function are
described in Logging Information.

1.3.14 CFC Chart Container Node


The CFC Chart Container contains all dynamic process values of an S7-CPU.

Information concerning the CFC Chart Container itself is available at the CFC Chart Container node.

Static Information

The displayed static information consists of:

• The Node name of the CFC Chart Container.


• The ID of the CFC Chart Container.
• A description text for this Node

Dynamic Information

The displayed dynamic information consists of:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 44 of 126
LKZ:DE AL:N ECCN:4E992

• Status page:
• possible information is
o Started:
The CFC Chart Container is starting up.
o Running:
Is indicated after a successful startup. The CFC Chart Container is in operation.
o Terminating:
The CFC Chart Container is shutting down.
For possible reasons refer to Fault Tracking.
o Stopped:
Is indicated after the terminating process has finished. The CFC Chart Container is stopped.
o Failed:
The CFC Chart Container is not in operation.
For possible reasons refer to Fault Tracking.
o Action button:
This button allows starting or stopping the CFC Chart Container.
A stopped container can be restarted either by using this Action button, or with a SPPA-T3000
system restart.
The operation of this button is restricted by the access rights as described in chapter Project
Administration
• Diagnostic page:
• There is no dynamic data available for this Node in the diagnostic system.
• Logging page:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 45 of 126
LKZ:DE AL:N ECCN:4E992

• After a click on the tab Logging, the logging page will be opened:

The intention of the logging page is to display very specific information of the SPPA-T3000 System Software.
This page is not needed for engineering or operation purposes
but supports computer administration activities. Details concerning the configuration of the logging function are
described in Logging Information.

1.3.15 SIMATIC Fail-Safe Automation Function Container Node


The SIMATIC Fail-Safe Automation Function Container contains all dynamic process values of a Fail-Safe component.

Static Information

The displayed static information consists of:

• The Node name of the SIMATIC Fail-Safe Automation Function Container.


• The ID of the SIMATIC Fail-Safe Automation Function Container.
• A description text for this Node.

Dynamic Information

The displayed dynamic information consists of:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 46 of 126
LKZ:DE AL:N ECCN:4E992

• Status page:
• possible information is
o Started:
The SIMATIC Fail-Safe Automation Function Container is starting up.
o Running:
Is indicated after a successful startup. The SIMATIC Fail-Safe Automation Function Container is in
operation.
o Terminating:
The SIMATIC Fail-Safe Automation Function Container is shutting down.
For possible reasons refer to Fault Tracking.
o Stopped:
Is indicated after the terminating process is finished. The SIMATIC Fail-Safe Automation Function
Container is stopped.
o Failed:
The SIMATIC Fail-Safe Automation Function Container is not in operation.
For possible reasons refer to Fault Tracking.
o Action button:

For SIMATIC Fail-Safe Automation Function Container the Action Stop is not available.

• Diagnostic page:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 47 of 126
LKZ:DE AL:N ECCN:4E992

• After clicking on the tab Diagnostic the diagnostic page will be opened.

• In the area Diagnostic Ports, the status at several Ports of the Runtime Container is provided. With buttons
above the detail area, the diagnostic information can be filtered for the categories:
o Diagnostic Ports
o I&C Ports
o HMI (Plant Display) Ports
o Not GOD Quality Ports
o all other Ports

Details of the possible Port status signals are described in SIMATIC Fail-Safe Automation Function Container
of Fault Tracking information.

It is not possible to change any of the displayed information in the Diagnostic View

A detailed category description is available in Diagnostic Information Category

• Logging page: This Container has no logging page.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 48 of 126
LKZ:DE AL:N ECCN:4E992

1.3.16 SIMATIC S7 FM458 Container Node


The S7_FM458_Container contains all dynamic process values of an FM 458 CPU.

Information concerning the S7_FM458_Container itself is available at the S7_FM458_Container node.

Static Information

The displayed static information consists of:

• The Node name of the S7_FM458_Container.


• The ID of the S7_FM458_Container.
• A description text for this Node

Dynamic Information

The displayed dynamic information consists of:

• Status page:
• possible information is
o Started:
The S7_FM458_Container is starting up.
o Running:
Is indicated after a successful startup. The S7_FM458_Container is in operation.
o Terminating:
The S7_FM458_Container is shutting down.
For possible reasons refer to Fault Tracking.
o Stopped:
Is indicated after the terminating process is finished. The S7_FM458_Container is stopped.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 49 of 126
LKZ:DE AL:N ECCN:4E992

o Failed:
The S7_FM458_Container is not in operation.
For possible reasons refer to Fault Tracking.

For S7_FM458_Container the Action Stop is not available.

• Diagnostic page: This Container has no diagnostic page.


• Logging page: This Container has no logging page.

1.3.17 Diagnostic Container Node


The Diagnostic Container is the basis for the Diagnostic View. It collects the data from other Containers or sources
which have registered themselves for diagnostic information. The Diagnostic Container provides this information in the
Diagnostic View.
Information concerning the Diagnostic Container itself is available at the Diagnostic Container Node.

Static Information

The displayed static information consists of:

• The Node name of the Diagnostic Container.


• The ID in the diagnostic system of the Diagnostic Container.
• This ID is fixed and is needed for system internal identification.
• A description text for this Node

Dynamic Information

The displayed dynamic information consists of:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 50 of 126
LKZ:DE AL:N ECCN:4E992

• Status page:
• possible information is
o Started:
The Diagnostic Container is starting up.
o Running:
Is indicated after a successful startup. The Diagnostic Container is in operation.
o Terminating:
The Diagnostic Container is shutting down.
For possible reasons refer to Fault Tracking.
o Stopped:
Is indicated after the terminating process is finished. The Diagnostic Container is stopped.
o Failed:
The Diagnostic Container is not in operation.
For possible reasons refer to Fault Tracking.

For the Diagnostic Container the Action Stop is not available.

• Diagnostic page:
• There is no dynamic data available for this Node in the diagnostic system.
• Logging page:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 51 of 126
LKZ:DE AL:N ECCN:4E992

• After a click on the tab Logging, the logging page will be opened:

The intention of the logging page is to display very specific information of the SPPA-T3000 System Software.
This page is not needed for engineering or operation purposes
but supports computer administration activities. Details concerning the configuration of the logging function are
described in Logging Information.

1.3.18 SIMATIC Hardware Configuration Container Node


The SIMATIC Hardware Configuration Container manages the data of the S7 Hardware Configuration.

Information concerning the SIMATIC Hardware Configuration Container itself is available at the SIMATIC Hardware
Configuration Container node.

Static Information

The displayed static information consists of:

• The Node name of the SIMATIC Hardware Configuration Container.


• The ID in the diagnostic system of the SIMATIC Hardware Configuration Container.
• This ID is fixed and is needed for system internal identification.
• A description text for this Node

Dynamic Information

The displayed dynamic information consists of:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 52 of 126
LKZ:DE AL:N ECCN:4E992

• Status page:
• Possible information is
o Started:
The SIMATIC Hardware Configuration Container is starting up.
o Running:
Is indicated after a successful startup. The SIMATIC Hardware Configuration Container is in
operation.
o Terminating:
The SIMATIC Hardware Configuration Container is shutting down.
For possible reasons refer to Fault Tracking.
o Stopped:
Is indicated after the terminating process has finished. The Diagnostic Container is stopped.
o Failed:
The SIMATIC Hardware Configuration Container is not in operation.
For possible reasons refer to Fault Tracking.
o Action button:
This button allows starting or stopping the SIMATIC Hardware Configuration Container.
A stopped container can be restarted either by using this Action button, or with a SPPA-T3000
system restart.
The operation of this button is restricted by the access rights as described Project Administration
• Diagnostic page:
• There is no dynamic data available for this Node in the diagnostic system.
• Logging page:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 53 of 126
LKZ:DE AL:N ECCN:4E992

• After a click on the tab Logging, the logging page will be opened:

The intention of the logging page is to display very specific information of the SPPA-T3000 System Software.
This page is not needed for engineering or operation purposes
but supports computer administration activities. Details concerning the configuration of the logging function are
described in Logging Information.

1.3.19 IO Tools Container Node


The IO Tools container includes tools which are used to perform the import of HW configuration data, and IO data
provided by an external tool. The imported data is used to automatically generate suitable I&C functions and diagrams
within the SPPA-T3000 system.

Information concerning the IO tools container itself is available in the IOTOOLS

Static Information

The displayed static information consists of:

• The Node name of the IO tools container.


• The ID in the diagnostic system of the IO tools Container.
• This ID is defined as fixed and is needed for system internal identification.
• A description text for this Node

Dynamic Information

The displayed dynamic information consists of:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 54 of 126
LKZ:DE AL:N ECCN:4E992

• Status page:
• possible information is:
o Started:
The IO tool Container is starting up.
o Running:
Is indicated after a successful startup. The IO tool Container is in operation.
o Terminating:
The IO tool Container is shutting down.
For possible reasons refer to Fault Tracking.
o Stopped:
Is indicated after the terminating process has finished. The IO tool Container is stopped.
o Failed:
The IO tool Container is not in operation.
For possible reasons refer to Fault Tracking.
o Action button:
This button allows starting or stopping the IO tool Container.
A stopped container can be restarted either by using this Action button, or with a SPPA-T3000
system restart.
The operation of this button is restricted by the access rights as described in chapter Project
Administration
• Diagnostic page:
• There is no dynamic data available for this Node in the diagnostic system.
• Logging page:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 55 of 126
LKZ:DE AL:N ECCN:4E992

• After a click on the tab Logging the logging page will be opened:

The intention of the logging page is to display very specific information of the SPPA-T3000 System Software.
This page is not needed for engineering or operation purposes
but supports computer administration activities. Details concerning the configuration of the logging function are
described in Logging Information.

1.3.20 License Server Container Node


The main role of the SPPA-T3000 License Server is the encapsulation of routines for communication with the server
for license verification. The License Server provides the uniform license handling for all licensed SPPA-T3000 parts.
The SPPA-T3000 License Server, as a unit of the SPPA-T3000 Service Portal, must be implemented to create the
environment for license monitoring through HTTP.

Information concerning the license container itself is available at the license container node.

Static Information

The displayed static information consists of:

• The Node name of the license container.


• The ID in the diagnostic system of the license container. This ID is fixed, and is needed for system internal
identification.
• A description text for this Node

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 56 of 126
LKZ:DE AL:N ECCN:4E992

Dynamic Information

The displayed dynamic information consists of:

• Status page:
• possible information is
o Started:
The License Container is starting up.
o Running:
Is indicated after a successful startup. The License Container is in operation.
o Terminating:
The License Container is shutting down.
For possible reasons refer to Fault Tracking.
o Stopped:
Is indicated after the terminating process has finished. The License Container is stopped.
o Failed:
The License Container is not in operation.
For possible reasons refer to Fault Tracking.
o Action button:
This button allows starting or stopping the License Container.
A stopped container can be restarted either by using this Action button, or with a SPPA-T3000
system restart.
The operation of this button is restricted by the access rights as described in chapter Project
Administration
• Diagnostic page:
• There is no dynamic data available for this Node in the diagnostic system.
• Logging page:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 57 of 126
LKZ:DE AL:N ECCN:4E992

• After a click on the tab Logging the logging page will be opened:

The intention of the logging page is to display very specific information of the SPPA-T3000 System Software.
This page is not needed for engineering or operation purposes
but supports computer administration activities. Details concerning the configuration of the logging function are
described in Logging Information.

1.3.21 Monitor Container Node


Usually, the Monitor Container starts and monitors all other Containers in the SPPA-T3000 system such as:

• Runtime Container,
• Project Container,
• Diagnostic Container, etc.

Information concerning the Monitor Container itself is available at the Monitor Container Node MC.

Static Information

The displayed static information consists of:

• The Node name of the Monitor Container.


• The ID in the diagnostic system of the Monitor Container.
• This ID is defined during the project setup.
• A description text for this Node.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 58 of 126
LKZ:DE AL:N ECCN:4E992

Dynamic Information

The displayed dynamic information consists of:

• Status page
• Possible information is:
o Started:
The Monitor Container is starting up.
o Running:
Is indicated after a successful startup. The Monitor Container is in operation.
o Terminating:
The Monitor Container is shutting down.
For possible reasons refer to Fault Tracking.
o Stopped:
Is indicated after the terminating process is finished. The Monitor Container is stopped.
o Failed:
The Monitor Container is not in operation.
For possible reasons refer to Fault Tracking.

For Monitor Containers the Action Stop is not available.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 59 of 126
LKZ:DE AL:N ECCN:4E992

• Diagnostic page:
• There is no dynamic data available for this Node in the diagnostic system.
• Logging page:
• After a click on the tab Logging the logging page will be opened:

The intention of the logging page is to display very specific information of the SPPA-T3000 System Software.
This page is not needed for engineering or operation purposes
but supports computer administration activities. Details concerning the configuration of the logging function are
described in Logging Information.

1.3.22 Project Container Node


The Project Container covers all project data relevant to SPPA-T3000.
Information concerning the Project Container itself is available at the Project Container Node PC.

Static Information

The displayed static information consists of:

• The Node name of the Project Container.


• The ID in the diagnostic system of the Project Container.
• This ID is fixed.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 60 of 126
LKZ:DE AL:N ECCN:4E992

• A description text for this Node.

Dynamic Information

The displayed dynamic information consists of:

• Status page:
• possible information is
o Started:
The Project Container is starting up.
o Running:
Is indicated after a successful startup. The Project Container is in operation.
o Terminating:
The Project Container is shutting down.
For possible reasons refer to Fault Tracking.
o Stopped:
Is indicated after the terminating process is finished. The Project Container is stopped.
o Failed:
The Project Container is not in operation.
For possible reasons refer to Fault Tracking.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 61 of 126
LKZ:DE AL:N ECCN:4E992

The Action Stop is not available for Project Containers.

• Diagnostic page:
• There is no dynamic data available for this Node in the diagnostic system.
• Logging page:
• After a click on the tab Logging, the logging page will be opened:

The intention of the logging page is to display very specific information of the SPPA-T3000 System Software.
This page is not needed for engineering or operation purposes
but supports computer administration activities. Details concerning the configuration of the logging function are
described in Logging Information.

1.3.23 Plant Display Server Node


The Plant Display Server is responsible for providing the plant Displays with dynamic data.
Information concerning the Plant Display Server itself is available at the Plant Display Server Node PDS.

Static Information

The displayed static information consists of:

• The Node name of the Plant Display Server.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 62 of 126
LKZ:DE AL:N ECCN:4E992

• The ID in the diagnostic system of the Plant Display Server.


• This ID is fixed.
• A description text for this Node.

Dynamic Information

The displayed dynamic information consists of:

• Status page:
• possible information is
o Started:
The Plant Display Server is starting up.
o Running:
Is indicated after a successful startup. The Plant Display Server is in operation.
o Terminating:
The Plant Display Server is shutting down.
For possible reasons refer to Fault Tracking.
o Stopped:
Is indicated after the terminating process has finished. The Plant Display Server is stopped.
o Failed:
The Plant Display Server is not in operation.
For possible reasons refer to Fault Tracking.
o Action button:
This button allows starting or stopping the Plant Display Server.
A stopped container can be restarted either by using this Action button, or with a SPPA-T3000
system restart.
The operation of this button is restricted by the access rights.
• Diagnostic page:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 63 of 126
LKZ:DE AL:N ECCN:4E992

• After a click on the tab Diagnostic the diagnostic page will be opened:

• This section displays the status of several ports of the Plant Display Server. With buttons above the detail
area, the diagnostic information can be filtered for the categories:
o all Diagnostic Ports
o I&C Ports
o HMI Ports
o signal ports with values classified as BAD quality
o all other Ports
One or more buttons can be selected, the Port information will be displayed accordingly.

Details of the possible Port status signals are described in the Plant Display Server description of the Fault
Tracking information.

It is not possible to change any of the displayed information in the Diagnostic View

A detailed category description is available in Diagnostic Information Category

• Logging page:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 64 of 126
LKZ:DE AL:N ECCN:4E992

• After a click on the tab Logging, the logging page will be opened:

The intention of the logging page is to display very specific information of the SPPA-T3000 System Software.
This page is not needed for engineering or operation purposes
but supports computer administration activities. Details concerning the configuration of the logging function are
described in Logging Information.

1.3.24 Report Container


The Report Container is responsible for providing the SPPA-T3000 Reports.
Information concerning the Report Container itself is available at the Report Container Node.

Static Information

The displayed static information consists of:

• The Node name of the Report Container.


• The ID in the diagnostic system of the Report Container.
• This ID is fixed.
• A description text for this Node.

Dynamic Information

The displayed dynamic information consists of:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 65 of 126
LKZ:DE AL:N ECCN:4E992

• Status page:
• possible information is
o Started:
The Report Container is starting up.
o Running:
Is indicated after a successful startup. The Report Container is in operation.
o Terminating:
The Report Container is shutting down.
For possible reasons refer to Fault Tracking.
o Stopped:
Is indicated after the terminating process has finished. The Report Container is stopped.
o Failed:
The Report Container is not in operation.
For possible reasons refer to Fault Tracking.
o Action button:
This button allows starting or stopping the Report Container.
A stopped container can be restarted either by using this Action button, or with a SPPA-T3000
system restart.
The operation of this button is restricted by the access rights.
• Diagnostic page:
• There is no dynamic data available for this Node in the diagnostic system.
• Logging page:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 66 of 126
LKZ:DE AL:N ECCN:4E992

• After a click on the tab Logging, the logging page will be opened:

The intention of the logging page is to display very specific information of the SPPA-T3000 System Software.
This page is not needed for engineering or operation purposes
but supports computer administration activities. Details concerning the configuration of the logging function are
described in Logging Information.

1.3.25 Trend Display Server Node


The task of the Trend Display Server is to provide the trend displays with archived values for visualization.

Static Information

The displayed static information consists of:

• The Node name of the Trend Display Container.


• The ID in the diagnostic system of the Trend Display Container.
• This ID is fixed.
• A description text for this Node.

Dynamic Information

The displayed dynamic information consists of:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 67 of 126
LKZ:DE AL:N ECCN:4E992

• Status page:
• possible information is
o Started:
The Trend Display Container is starting up.
o Running:
Is indicated after a successful startup. The Trend Display Container is in operation.
o Terminating:
The Trend Display Container is shutting down.
For possible reasons refer to Fault Tracking.
o Stopped:
Is indicated after the terminating process has finished. The Trend Display Container is stopped.
o Failed:
The Trend Display Container is not in operation.
For possible reasons refer to Fault Tracking.
o Action button:
This button allows starting or stopping the Trend Display Container.
A stopped container can be restarted either by using this Action button, or with a SPPA-T3000
system restart.
The operation of this button is restricted by the access rights.
• Diagnostic page:
• There is no dynamic data available for this Node in the diagnostic system.
• Logging page:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 68 of 126
LKZ:DE AL:N ECCN:4E992

• After a click on the tabulator Logging the logging page will be opened:

• For the trend display container currently no packages are selectable at the logging page

1.3.26 Call Home Container Node


Information concerning the Call Home Container itself is available at the Call Home Container node.

Static Information

The displayed static information consists of:

• The Node name of the Call Home Container.


• The ID in the diagnostic system of the Call Home Container.
• This ID is fixed and needed for system internal identifications.
• A description text for this Node

Dynamic Information

The displayed dynamic information consists of:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 69 of 126
LKZ:DE AL:N ECCN:4E992

• Status page:
• possible indications are
o Started:
The Call Home Container is starting up.
o Running:
Is indicated after a successful start up. The Call Home Container is in operation.
o Terminating:
The Call Home Container is shutting down.
For possible reasons refer to Fault Tracking.
o Stopped:
Is indicated after the shutdown process has finished.
o Failed:
The Call Home Container is not in operation.
For possible reasons refer to Fault Tracking.
o Action button:
This button allows starting or stopping the Call Home Container.
A stopped container can be restarted either by using this Action button, or with a SPPA-T3000
system restart.
The operation of this button is restricted by the access rights as described in the chapter Project
Administration.
• Diagnostic page:
• After clicking on the tab Diagnostic the diagnostic page will be opened:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 70 of 126
LKZ:DE AL:N ECCN:4E992

• In the area Diagnostic Ports, the status at several Ports of the Call Home Container is provided. With buttons
above the detail area, the diagnostic information can be filtered for the categories:
o Diagnostic Ports
o I&C Ports
o Plant Display Ports
o Signal Ports with values classified as BAD quality
o all other Ports
One or more buttons can be selected, the Port information will be displayed accordingly.

Details of the possible Port status signals are described in the Call Home Container description of the Fault
Tracking information.

It is not possible to change any of the displayed information in the Diagnostic View

A detailed category description is available in Diagnostic Information Category

• Logging page:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 71 of 126
LKZ:DE AL:N ECCN:4E992

• After a click on the tabulator Logging the logging page will be opened:

The intention of the logging page is to display very specific information of the SPPA-T3000 System Software.
This page is not needed for engineering or operation purposes
but supports computer administration activities. Details concerning the configuration of the logging function are
described in Logging Information.

1.3.27 Technological Calculation Container Node


Information concerning the Technological Calculation Container itself is available at the Technological Calculation
Container node.

Static Information

The displayed static information consists of:

• The Node name of the Technological Calculation Container.


• The ID in the diagnostic system of the Technological Calculation Container.
• A description text for this Node.

Dynamic Information

The displayed dynamic information consists of:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 72 of 126
LKZ:DE AL:N ECCN:4E992

• Status page:
• possible indications are
o Started:
The Technological Calculation Container is starting up.
o Running:
Is indicated after a successful start up. The Technological Calculation Container is in operation.
o Terminating:
The Technological Calculation Container is shutting down.
For possible reasons refer to Fault Tracking.
o Stopped:
Is indicated after the shutdown process has finished.
o Failed:
The Technological Calculation Container is not in operation.
For possible reasons refer to Fault Tracking.
o Connected AFCS: In this area the status of connections to other Runtime Containers is displayed
for those Runtime Containers which send signals to the Technological Calculation Container.
o Action button:
This button allows starting or stopping the Technological Calculation Container.
A stopped container can be restarted either by using this Action button, or with a SPPA-T3000
system restart.
The operation of this button is restricted by the access rights as described in the chapter Project
Administration.
• Diagnostic page:
• After clicking on the tab Diagnostic the diagnostic page will be opened:

• In the area Diagnostic Ports, the status of Ports of the Technological Calculation Container is provided. With
buttons above the detail area, the diagnostic information can be filtered for the categories:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 73 of 126
LKZ:DE AL:N ECCN:4E992

o Diagnostic Ports
o I&C Ports
o Plant Display Ports
o Signal Ports with values classified as BAD quality
o all other Ports

It is not possible to change any of the displayed information in the Diagnostic View

A detailed category description is available in Diagnostic Information Category

• Logging page:
• After a click on the tabulator Logging the logging page will be opened:

The intention of the logging page is to display very specific information of the SPPA-T3000 System Software.
This page is not needed for engineering or operation purposes
but supports computer administration activities. Details concerning the configuration of the logging function are
described in Logging Information.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 74 of 126
LKZ:DE AL:N ECCN:4E992

1.3.28 Plant Monitor Container Node


Information concerning the Plant Monitor Container itself is available at the Plant Monitor Container node.

Static Information

The displayed static information consists of:

• The Node name of the Plant Monitor Container.


• The ID in the diagnostic system of the Plant Monitor Container.
• A description text for this Node.

Dynamic Information

The displayed dynamic information consists of:

• Status page:
• possible indications are
o Started:
The Plant Monitor Container is starting up.
o Running:
Is indicated after a successful start up. The Plant Monitor Container is in operation.
o Terminating:
The Plant Monitor Container is shutting down.
For possible reasons refer to Fault Tracking.
o Stopped:
Is indicated after the shutdown process has finished.
o Failed:
The Plant Monitor Container is not in operation.
For possible reasons refer to Fault Tracking.
o Connected AFCS: In this area the status of connections to other Runtime Containers is displayed
for those Runtime Containers which send signals to the Plant Monitor Container.
o Action button:
This button allows starting or stopping the Plant Monitor Container.
A stopped container can be restarted either by using this Action button, or with a SPPA-T3000
system restart.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 75 of 126
LKZ:DE AL:N ECCN:4E992

The operation of this button is restricted by the access rights as described in the chapter Project
Administration.
• Diagnostic page:
• There is no dynamic data available for this Node in the diagnostic system.
• Logging page:
• After a click on the tabulator Logging the logging page will be opened:

The intention of the logging page is to display very specific information of the SPPA-T3000 System Software.
This page is not needed for engineering or operation purposes
but supports computer administration activities. Details concerning the configuration of the logging function are
described in Logging Information.

1.4 Diagnostic Information Category


After the Diagnostic View is opened, the window displays the diagnostic information separated in a left hand part,
which displays the tree view, and the right hand part which displays the detailed information provided by the diagnostic
system.

The diagnostic information is divided into the categories:

• Status Information
• Diagnostic Information
• Logging Information

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 76 of 126
LKZ:DE AL:N ECCN:4E992

A tab bar is located above the detail area. To display a certain diagnostic information category, select the respective
tabulator.

Refer to the categories above for further details.

1.4.1 Status Information


After the Diagnostic View is opened the status for the SPPA-T3000 components is displayed in the section Status at
the right hand part of the diagnostic view.

For the information displayed at the status page, refer to the respective chapter in fault tracking information for the
individual equipment.

1.4.2 Diagnostic Information


After the Diagnostic View is opened the detailed diagnostic information is selectable with the tab located in the right
hand part of the window.
The diagnostic information shows a table of Ports together with their process values. These are distinguished between:

• Diagnostic Ports:
• for these Ports a Port description is shown in the table,
• Non Diagnostic Ports:
• for these Ports an Alarm description is shown if the Port is used as alarm source, or the Port name is
displayed in the table.

The buttons in the toolbar above the detailed table allow selection of a subgroup of the Ports as:

• Diagnostic Ports:
• The diagnostic Ports are selectable with the icon

• These Ports are especially designed to carry diagnostic information.


• Click this icon to display a sample of diagnostic Ports

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 77 of 126
LKZ:DE AL:N ECCN:4E992

In the Name column, either the Port description is displayed, or if no description exists, then the Port name is
displayed.

• I&C Ports:
• The I&C Ports are selectable with the icon

• These Ports are used to distribute signals within the Automation Functions.
• Click this icon to display a sample of I&C Ports

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 78 of 126
LKZ:DE AL:N ECCN:4E992

• Plant Display Ports:


• The Plant Display Ports are selectable with the icon

• Signals available at these Ports are distributed with the operation and monitoring functions in the Plant
Displays.
• Click this icon to display a sample of Plant Display Ports

• Not GOD Quality Port:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 79 of 126
LKZ:DE AL:N ECCN:4E992

• The Ports with values classified as not good quality are displayed after selection of this icon

• Click this icon to display a sample of Ports with classification BAD or UNC

• Reasons to classify a signal with a quality BAD include:


o binary signals which are not valid due to a short or wire break indication
• Misc:
• Ports which do not belong to one of the above categories are selectable with the icon

• Click this icon to display a sample of remaining Ports


Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 80 of 126
LKZ:DE AL:N ECCN:4E992

• Analyze Mode
• To activate the analyze mode click on the icon

• When the icon is clicked, the displayed values are no longer updated. This allows the user to review the
contents without it changing.
• Additional Diagnostics
• To activate additional diagnostics click on the icon

• When the icon is clicked, a web browser window opens with diagnostic data for the container. This option is
only possible if the internal HTTP server has been configured and the user has the appropriate access rights.

Additional Diagnostics is enabled only for certain devices that have web interfaces providing very detailed
system information for Siemens SPPA-T3000 experts.

Changing settings using Additional Diagnostics web interface may result in the maloperation of the system.

• Plant Manual

• This icon will appear when an Automation Function or proxy is selected that has an entry in the Plant Manual.
• When the icon is clicked, the Plant Manual for the tag will open.
• Linked Documents

• When the icon is clicked, the Linked Document for the tag will open. If more than one document is linked,
then the user can choose which one to open.
• Notes

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 81 of 126
LKZ:DE AL:N ECCN:4E992

• When the icon is clicked, the Notepad for the tag will open. A white Notes icon indicates that the notepad is
empty.

• A yellow icon indicates that notes exist for the tag.

When an Automation Function within a Macro has been selected, the user can navigate to the Macro itself in
the Diagnostic View. Select the function via the context menu (right mouse click > Goto top level macro
component).

Sorting the Diagnostic Information

The Ports displayed in the diagnostic information can be sorted via any column. Click on any column header to sort the
Ports in either ascending or descending order.

The original order (the same as when the diagnostic information was first viewed) can be restored. Select the function
via the context menu (right mouse click > Restore Original Sorting).

1.4.3 Logging Information

To support Siemens SPPA-T3000 experts with very detailed system information, i.e. debugging information, it
is possible to generate log files. The logging page supports the configuration of such logs.
This logging function is not needed for engineering or operation purposes

The logging routine extracts large amounts of data throughout the system and should only be used in rare
cases where detailed investigations are warranted. Because of the extent of the data, overall system
performance might be affected when large logging requests are issued. It is recommended such requests be
made during periods where overall system activity is low.

The generated logs, which can be used for further investigation, contain information provided by the installed Software
Classes or Packages. After opening of the Logging page a configuration dialog as shown below appears:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 82 of 126
LKZ:DE AL:N ECCN:4E992

The decision as to which event is to be included in a log is made by a prioritization of the occurrences. The highest
priority is a FATAL error, the lowest priority is DEBUG information.
All events with at least the requested priority and any event classified with a higher priority is included in the log file.
That means:

The lower the level of the selected logging information, the higher the expected amount of occurrences which
will be reported and the higher the additional load for the related computer.

How to configure and view log files is explained in the following chapters.

1.4.3.1 Configuring of Diagnostic Logging Information

The logging routine extracts large amounts of data throughout the system and should only be used in rare
cases where detailed investigations are warranted. Because of the extent of the data, overall system
performance might be affected when large logging requests are issued. It is recommended such requests be
made during periods where overall system activity is low.

To configure diagnostic logs the Diagnostic View in the Workbench needs to be opened. Then

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 83 of 126
LKZ:DE AL:N ECCN:4E992

1. select the desired Container in the left hand part of the Diagnostic View window, then
2. select the Logging page in the right hand part.

Currently logging is supported for SPPA-T3000 Containers, only.

Configuring Logs for a Certain Package or Class

To prepare a log for one certain package or class proceed as follows:

1. Open the package tree until the desired package or class to be monitored is visible.
A single package or class is marked by a dot on the left of the Package or class name.
2. Select the package or class and open a context menu with the right mouse click on the selected item

3. Select the desired logging level for the selected package or class.
4. After the selection the color which indicates the logging level, is adjusted accordingly for this package or
class.

A summary of all activated logging states in the subordinated packages or classes are displayed in
the nodes of the tree view.

5. Depending on the selected check boxes, the log will be started after pressing the Submit button on either
o the local computer, i.e. the computer where the selected container resides, or
o remote, i.e. the computer where the Diagnostic Container is resides.
More information concerning remote logging is explained in Adjusting the location for diagnostic logs

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 84 of 126
LKZ:DE AL:N ECCN:4E992

Preparing Logs for All Packages and Classes Which are Subordinated to a Certain Node

If a log for all packages and classes, and further nodes if they exist, subordinated to a certain node is to be prepared,
proceed as follows:

1. Select the desired node and open a context menu with the right mouse click on the selected item

2. Select the desired logging level for the Node.


3. After the selection the color, coding the logging level, is adjusted accordingly.
4. Depending of the selected check boxes, the log will be started after pressing the Submit button on either
o the local computer, i.e. the computer where the selected container resides, or
o remote, i.e. the computer where the Diagnostic Container is resides.

The logging level for all packages and classes subordinated to the selected node will be adjusted to the same
level.

Displaying Logging Information

After the button View Log File was pressed, a window will be opened which displays the log file for the selected
container.

1.4.3.2 Adjusting the Location for Diagnostic Logs


The Containers of the SPPA-T3000 system are usually located on different computers, e.g. the PC, DC, PDS, ARC
etc. reside on the Application Server, and the RTCs may reside on one or more Automation Servers. Because of this
there are several possibilities for storing the log files.

• Local means, the log file is stored on that computer where the selected Container resides

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 85 of 126
LKZ:DE AL:N ECCN:4E992

• Remote means, the log file for the selected container is stored on the computer where the Diagnostic
Container resides.

Whereas for a local logging no further adjustments are necessary (just click Submit, then View for displaying), there
are a few parameters which might be changed for Remote logging.

Remote Logging Options Settings

To open the remote options dialogs the Remote check box must be selected.

1. If it is not selected, select the check box. The Options button becomes selectable.
2. After a click on this button the Logging Options dialog as shown below will be opened.

o File Size (MByte): This value determines the maximum size for log files.
o Max. Backup Index: Determines how many history files will be kept for this container.
Explanation:
The log files will be created sequentially. e.g. with the settings above the logging will start with the first file.
After the maximum file size of 2 MByte has been reached it is renamed to "*.1" and the logging is continued to
a new file with the original name. This procedure will be continued until the 10th file is reached. The maximum
backup index gives the maximum index of those file names before the oldest file is overwritten.

Unless you know the result you should not change the following settings. Otherwise the log files
might be not readable.

o Format determines the output format of the files.


o Format String determines the structure of any string in the log file.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 86 of 126
LKZ:DE AL:N ECCN:4E992

In principle the logging activities can not be stopped completely.


It is possible the remove both checks for remote and local logging. Then no log files will be created. This will
reduce the CPU load but not completely terminate the logging activities.
Another option to reduce the load is to set the logging for all packages and classes in the container to FATAL.
This also will minimize the events to be logged.

After the options have been set satisfactorily terminate the dialog with OK or abort with Cancel.

Finally press the Submit button to activate the logging.

1.4.3.3 Client Logging

Unauthorized persons are highly advised against requesting these log files because of the heavy impact on
the runtime behavior of the SPPA-T3000 system.

The Client Logging function must be used when debug information of the Graphical User Interface is needed. The log
files are generated in the local environment. Access to the Application Server and Automation Server log files is gained
using the standard Logging Information described elsewhere. To start the configuration dialog for the Client Logging

1. Open the Diagnostic View in the Workbench


2. From the menu Edit select the menu item Client Logging.

3. The configuration dialog in the window below appears

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 87 of 126
LKZ:DE AL:N ECCN:4E992

Since the principles of adjusting the desired logging levels are the same as for the SPPA-T3000 containers
refer to the description in Configuring of Diagnostic Logging Information

To prepare a log for one certain package or class proceed as follows:

Output of Client logging Information

The logging request always refers to that client where the client logging was started. In these terms, the output is sent
either to the (Java) - console of that client or into a file.

If the Java Console is not visible on your monitor, double click the button below in the task bar of the client
monitor.

If it is not available at that position it should be available via the web browser.

To prepare an output file on the client proceed as follows:

1. Click the option for Log to file in the window Client Logging.
2. Now the button Options can be selected to open the Logging Options Dialog

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 88 of 126
LKZ:DE AL:N ECCN:4E992

3. Enter the destination for the log file in the field File.
Preferably press the Browse button to open the explorer window of your computer.

Since the same explanations apply here as for the SPPA-T3000 containers refer to the description in
Adjusting the location of diagnostic logs

Further Functions in the Client Logging Dialog


• To display the logging levels which are currently valid at the logging server select the menu item Refresh
from the View menu of the Client logging window.

• To close the Client logging window select the menu item Exit from the File menu.

1.5 Multi Unit


The Multi Unit Workbench offers the user Diagnostic Views of attached units in the Multi Unit. Local Unit and Remote
Unit Diagnostic views are opened in separate windows.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 89 of 126
LKZ:DE AL:N ECCN:4E992

The Local Unit Diagnostic View has the full functionality of the Diagnostic View in the Single Unit Workbench.

In the Remote Unit Diagnostic View the user has only viewing rights. The user will not be permitted to stop and start
containers in the Remote Unit. The logging function is also disabled on Remote Unit containers. But Client Logging is
available from the Remote Unit Diagnostic View.

The Client Logging menu item in the Local and Remote Unit Diagnostic Views actually all open the same
Client Logging window.

1.5.1 Starting the View


In the Multi Unit Workbench, the Diagnostic Views for the Local Unit and Remote Units are opened in separate
windows.

Local Unit Diagnostic View

To start the Diagnostic View of the Local Unit:

The user must be logged into the Multi Unit Workbench.

• Select the Applications menu from the Workbench menu bar, then Diagnostic View from the drop down
menu.

A window displaying the Diagnostic View of the Local Unit will open.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 90 of 126
LKZ:DE AL:N ECCN:4E992

Alternatively, in the Applications menu, select Multi Unit , under Diagnostic View . Then select the Unit
Name of the Local Unit.

Remote Unit Diagnostic View

To start the PDH of a Remote Unit:

The user must be logged into the Multi Unit Workbench and logged into the Remote Unit.

1. Select the Applications menu then select Multi Unit under the Diagnostic View item menu.
2. The Unit Names of the logged in units will appear in a drop down list.
3. Select the desired Remote Unit.

A window displaying the Diagnostic View of the Remote Unit will open.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 91 of 126
LKZ:DE AL:N ECCN:4E992

2 Fault Tracking
Fault tracking is supported by the Diagnostic View in two ways:

• if a Port has invalid data, the source can be found by navigating to the connected Port.
• This principle is described in Navigation to Connected Ports
• by analyzing the detail information provided in the diagnostic pages for the Container.
• The chapter Details in Diagnostic View describes the diagnostic Port information together with the possible
conditions, a classification and a comment providing possible reasons for a malfunction, to aid in trouble
shooting the problem. The classifications are:
o o.k
there is no further remark, no action required
o fault
indicates a malfunction. Information to remedy condition is given in the comments
o transient
indicates that this condition is temporary and should result in a final state. That state is mentioned in
the comments.

Before starting any investigation on malfunction details ensure that the


Monitor Container , the
Project Container and the
Diagnostic Container
are working properly, this verifies the Diagnostic View information is reliable.

2.1 Navigation to Connected Ports


When an Automation Function is selected in the Diagnostic View, details for any port data is displayed in the right hand
part of the window.
An example is given in the picture below.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 92 of 126
LKZ:DE AL:N ECCN:4E992

To support investigations in the Diagnostic View, it is possible to navigate between connected Ports, i.e. to select one
Port of the actual displayed AF Block and navigate to the connected Port of the referring AF Block.

One of the modes described below can be used:

• display the connected AF Block in the detail display


• open the connected AF Block in an additional window

Select Connected AF Block

To display the connected AF Block in the detail window, proceed as follows:

1. Place the cursor over a connected Port.


2. Open the context menu with a right mouse click
3. Select Select connected AF from the context menu.

If the Port is not connected, the menu option will not be available.

4. If there is only one Port connected, the respective AF Block is displayed immediately.
5. If there is more than one Port connected, proceed as follows:
1. A dialog box will open, listing all the connected Ports.

2. Select the desired Port in the dialog box which appears and confirm with OK or abort with Cancel.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 93 of 126
LKZ:DE AL:N ECCN:4E992

3. The connected AF Block will be displayed.

Open Connected AF Block in a New Window

This mode allows simultaneous opening of one additional diagnostic window displaying detail information of an AF
Block.

2.2 Details in Diagnostic View


Diagnostic information supplied by the different Containers and other non SPPA-T3000 components (which provide
diagnostic information) to the diagnostic view is described in this chapter. Follow the descriptions below to get the
respective information for:

• Alarm Printer Container


• OPC-Client Container
• OPC-Server Container
• Alarm Container
• Runtime Container
• CM Runtime Container
• S7 Runtime Container
• Archive Container
• SIMATIC Communication Container
• CFC Chart Container
• SIMATIC Failsafe Automation Function Container
• SIMATIC S7 FM458 Container
• Diagnostic Container
• SIMATIC Hardware Configuration Container
• IO-Tools
• License Server
• Monitor Container
• Project Container
• Plant Display Server
• Report Container
• Trend Display Server
• Call Home Container

2.2.1 Service Container


To start the fault tracking for the Service Container proceed as follows:

1. The Diagnostic View has to be opened in the Workbench


2. Open the Nodes until the Service Container is visible in the Tree View

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 94 of 126
LKZ:DE AL:N ECCN:4E992

The Service Container Node name is sc

3. Select the Service Container


4. Compare the displayed status signals with the information below

Status Page
Column possible fault / o possible reason in case of fault
Value k
Status starting transient The starting procedure for this Container is not finished
Status running o.k.

Status terminating transient The shut down procedure for this Container is not finished
Status stopped fault The shut down procedure for this Container is finished. Service services are
currently not performed.
Status failed fault A malfunction was detected. Further investigation is necessary to ensure that
the Service Container is functioning properly.

Diagnostic Page

There is no dynamic data available for this Node in the diagnostic system.

2.2.2 Alarm Printer Container


To start the fault tracking for the Alarm Printer Container proceed as follows:

1. The Diagnostic View has to be opened in the Workbench


2. Open the Nodes until the Alarm Printer Container is visible in the Tree View

The Runtime Container Node name is AlarmPrinter

3. Select the desired Alarm Printer Container


4. Compare the displayed status signals with the information below

Status Page
Column possible fault / o possible reason in case of fault
Value k
Status starting transient The starting procedure of this Container is not finished.
Status running o.k. no comment
Status terminating transient The shut down procedure of this Container is not finished.
Status stopped fault The shut down procedure of this Container is finished. This Container needs to
be started to proceed with processing.
Status failed fault A malfunction was detected. Probably some or all tasks assigned to the
Container are stopped. Further investigation is needed to ensure the Runtime
Container in functioning properly.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 95 of 126
LKZ:DE AL:N ECCN:4E992

Diagnostic Page
Diagnostic port I/O ID Type Description
CONTAINER_ST O 1000 int Container State:
ATE
Stop, Start, Run-Master, Run-Slave
LAST_PRINT O 1030 int Time of the last printed alarm
PARTNER_CON O 1040 int Connection to partner container
_STATE
PRINT_SERVIC O 1050 long integer State of the print service
E_STOP
ERR_PRINTER_ O 1060 bool Server connection is missing
SERVER
ERR_PRINTER O 1070 bool General printer error
ERR_PAPER_O O 1080 bool Printer is out of paper
UT
ERR_INK_OUT O 1090 bool Printer is out of ink

2.2.3 OPC-Client Container


To start the fault tracking for the OPC-Client Container proceed as follows:

1. The Diagnostic View is open in the Workbench


2. Open the Nodes until the OPC-Client Container is visible in the Tree View

The Runtime Container Node name is OPC_Client

3. Select the OPC-Client Container.


4. Compare the displayed status signals with the information below

Status Page
Column possible fault / o possible reason in case of fault
Value k
Status starting transient The starting procedure of this Container is not finished.
Status running o.k. no comment
Status terminating transient The shut down procedure of this Container is not finished.
Status stopped fault The shut down procedure of this Container is finished. This Container
needs to be started to proceed with processing.
Status failed fault A malfunction was detected. Probably some or all tasks assigned to the
Container are stopped. Further investigation is needed to ensure the
Runtime Container in functioning properly.
connection Quality_good o.k. no comment
state
connection Quality_bad fault This Runtime Container does not receive signals from at least one other
state Runtime Container. The concerned Runtime Container is displayed.
Check whether this connected Runtime Container is running or not.
Check whether the signal exchange is designed properly.

Diagnostic Page

The diagnostic page is the same as for Runtime Containers.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 96 of 126
LKZ:DE AL:N ECCN:4E992

2.2.4 OPC-Server Container


To start the fault tracking for the OPC-Server Container proceed as follows:

1. The Diagnostic View has been opened in the Workbench.


2. Open the Nodes until the OPC-Server Container is visible in the Tree View.

The OPC-Server Container Node name is OPC-Server

3. Select the OPC-Server Container


4. Compare the displayed status signals with the information below

Status Page
Column possible fault / o possible reason in case of fault
Value k
Status starting transient Startup procedure for this Container is not finished
Status running o.k.

Status terminating transient Shutdown procedure for this Container is not being performed
Status stopped fault Shutdown procedure for this Container is finished. Alarm monitoring is not
performed actually.
Status failed fault A malfunction was detected. Some or all tasks of the Container are not working
properly. Further investigation is necessary to put the OPC-Server Container in
proper operation.

Diagnostic Page
Diagnostic port Type Values Fault possible reason in case of fault
default min max indication
SUB_CNT I n/a *) *) none Number of Subscriber:
Count of automation function
containers, that are currently
accessed by the OPC-Server.
CLT_CNT I n/a *) *) none Number of Clients:
Count of visualization clients
(plant displays) that are
currently connected to the OPC-
Server.
VAL_CNT I n/a *) *) none Number of subscribed values:
Overall count of all subscribed
process values ( i.e. size of the
internal process image)
RES_TIME I n/a *) *) none Response Time:
update time of the OPC-Server
process image.

*) these values are continuously updated.

2.2.5 Alarm Container


To start the fault tracking for the Alarm Container proceed as follows:

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 97 of 126
LKZ:DE AL:N ECCN:4E992

1. The Diagnostic View has to be opened in the Workbench


2. Open the Nodes until the Alarm Container is visible in the Tree View

The Alarm Container Node name is ac

3. Select the Alarm Container


4. Compare the displayed status signals with the information below

Status Page
Column possible fault / o possible reason in case of fault
Value k
Status starting transient Startup procedure for this Container is not finished
Status running o.k.

Status terminating transient Shutdown procedure for this Container is not being performed
Status stopped fault Shutdown procedure for this Container is finished. Alarm monitoring is not
performed actually.
Status failed fault A malfunction was detected. Some or all tasks of the Alarm Container are not
working properly. Further investigation is necessary to put the Alarm Container in
proper operation. The alarm functions are most likely at fault.

Diagnostic Page

There is no dynamic data available for this Node in the diagnostic system.

2.2.6 Runtime Container


To start the fault tracking for the Runtime Container proceed as follows:

1. The Diagnostic View has to be opened in the Workbench


2. Open the Nodes until the Runtime Container is visible in the Tree View

The Runtime Container Node name starts with rtc, e.g. rtc201

3. Select the desired Runtime Container


4. Compare the displayed status signals with the information below

Status Page
Column Possible Value Fault / o Possible reason in case of fault
k
Status starting transient The starting procedure of this Container is not finished.
Status running o.k. no comment
Status terminating transient The shut down procedure of this Container is not finished.
Status stopped fault The shut down procedure of this Container is finished. This Container
needs to be started to proceed with processing.
Status failed fault A malfunction was detected. Probably some or all tasks assigned to
the Container are stopped. Further investigation is needed to ensure
the Runtime Container is functioning properly.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 98 of 126
LKZ:DE AL:N ECCN:4E992

Column Possible Value Fault / o Possible reason in case of fault


k
Status additional - Indicates that the Runtime Container is disconnected.
disconnected
Connection GOD o.k. no comment
State
Connection BAD fault This Runtime Container is not receiving the signals from the Source
State Container. Only the status of input signals from other Runtime
Containers or CM Runtime Containers are monitored.
Check whether this connected Runtime Container is running or not.
Check whether the signal exchange is designed properly.

Diagnostic Page
Diagnostic port Type Values Fault indication possible reason in case of fault
default min max
Base cycle I 0 0 10000 Indicates the target cycle time that
time was set for this Runtime Container.
This value is preset and does not
change during the runtime
Measured I 0 0 10000 Indicates the cycle duration of the
cycle time last finished cycle.
Number of ipc I 0 0 100 Indicates the number of incoming
connections connections from other Runtime
Containers.
Imported data I 0 0 10000 Indicates the total number of signals
items count which are received from other
Runtime Containers.
Free memory I 0 1000000 Indicates the currently available
(kb) memory of a Runtime Container.
Free memory I 0 1000000 Indicates the minimum available
minimum (kb) memory of a Runtime Container.
Measured O 0 0 10000 NOT AVAILABLE will be displayed
cycle time of since this type of Runtime Container
Standby does not support redundancy.
Health Status O 0 0 100 NOT AVAILABLE will be displayed
of Master since this type of Runtime Container
does not support redundancy.
Health Status O 0 0 100 NOT AVAILABLE will be displayed
of Standby since this type of Runtime Container
does not support redundancy.
Health O 0 0 3 NOT AVAILABLE will be displayed
Redundant since this type of Runtime Container
Connection does not support redundancy.
Health status O 0 0 1 NOT AVAILABLE will be displayed
Automation since this type of Runtime Container
Highway does not support redundancy.
Master
Health status O 0 0 1 NOT AVAILABLE will be displayed
Automation since this type of Runtime Container
Highway does not support redundancy.
Standby
Redundancy O false false true ture NOT AVAILABLE will be displayed
Health Status since this type of Runtime Container
Low does not support redundancy.
Number of I 0 0 20 NOT AVAILABLE will be displayed
Elements in since this type of Runtime Container
Synchronizatio does not support redundancy.
n Data Queue
Number of Af I 0 0 10000 Indicates number of activated Af
Instance instances in container.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 99 of 126
LKZ:DE AL:N ECCN:4E992

Diagnostic port Type Values Fault indication possible reason in case of fault
default min max
Health Status O 0 0 1 NOT AVAILABLE will be displayed
of Master since this type of Runtime Container
Communicatio does not support redundancy.
n Interface 0
Health Status O 0 0 1 NOT AVAILABLE will be displayed
of Master since this type of Runtime Container
Communicatio does not support redundancy.
n Interface 1
Health Status O 0 0 1 NOT AVAILABLE will be displayed
of Master since this type of Runtime Container
Communicatio does not support redundancy.
n Interface 2
Health Status O 0 0 1 NOT AVAILABLE will be displayed
of Standby since this type of Runtime Container
Communicatio does not support redundancy.
n Interface 0
Health Status O 0 0 1 NOT AVAILABLE will be displayed
of Standby since this type of Runtime Container
Communicatio does not support redundancy.
n Interface 1
Health Status O 0 0 1 NOT AVAILABLE will be displayed
of Standby since this type of Runtime Container
Communicatio does not support redundancy.
n Interface 2
Wake-up fault O false false true true Indicates that the next new runtime
container cycle could not be started
in time.
Cycle time O false false true true Indicates that a cycle has needed
exceeded more time than scheduled
Pool overflow O 0 1000000 Indicates that one of the Runtime
Containers' internal resources
exceeded. (Details are available via
the xxx_PoolSize ports, which are
currently not used.)
Memory low O 0 1000000 Indicates that the maximum
warning available memory of a Runtime
Container has nearly reached.
Maximum O 0 0 10000 Indicates the maximum cycle
cycle time duration of the last 100 cycles.
System fault in O false false true true Indicates an internal error in the
ipc module communication module of the
Runtime Container
Average cycle O 0 0 10000 Indicates the average cycle duration
time of the last 100 cycles.
System fault in O false false true true Indicates an internal error in the real
realtime time module of the Runtime
module Container.
System fault in O false false true true Indicates an internal error in the
engineering engineering module of the Runtime
module Container.
System fault O false false true true Group Alarm of detected system
faults. It is raised if at least one of
the Runtime Containers' sub
modules indicates an internal error.
In this case, the logs should contain
detailed information about the state
within the Runtime Container
Redundancy O false false true true Indicates whether redundancy has
Lost been lost.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 100 of 126
LKZ:DE AL:N ECCN:4E992

Diagnostic port Type Values Fault indication possible reason in case of fault
default min max
Switch over is O false false true Indicates whether a mastership
in process switch over is in progress.
Connection O false false true Indicates whether the connection
between between runtime container and
runtime Redundancy Monitor has been lost.
container and
Redundancy
Monitor is lost
Communicatio O false false true true Indicates that at least one failure in
n fault the communication subsystem has
occurred (refer to IPC_CNT below,
also).
Investigations into the connected
Containers should give a reason for
the disturbances.
InputPortPoolS O 0 1000000 Indicates the resource usage of one
ize of the Runtime Containers' internal
resources. Currently not used.
OutputPortPoo O 0 1000000 Indicates the resource usage of one
lSize of the Runtime Containers' internal
resources. Currently not used.
ImportPortPool O 0 1000000 Indicates the resource usage of one
Size of the Runtime Containers' internal
resources. Currently not used.
ExportPortPool O 0 1000000 Indicates the resource usage of one
Size of the Runtime Containers' internal
resources. Currently not used.
BinaryValuePo O 0 1000000 Indicates the resource usage of one
olSize of the Runtime Containers' internal
resources. Currently not used.
FloatValuePool O 0 1000000 Indicates the resource usage of one
Size of the Runtime Containers' internal
resources. Currently not used.
IntegerValueP O 0 1000000 Indicates the resource usage of one
oolSize of the Runtime Containers' internal
resources. Currently not used.
IP Address of O (IP Address) IP Address of Master
Master
IP Address of O (IP Address) IP Address of Standby
Standby
LongValuePool O 0 1000000 Indicates the resource usage of one
Size of the Runtime Containers' internal
resources. Currently not used.
AlarmEventPo O 0 1000000 Indicates the resource usage of one
olSize of the Runtime Containers' internal
resources. Currently not used.
ByteArrayValu O 0 1000000 Indicates the resource usage of one
eSmallPoolSiz of the Runtime Containers' internal
e resources. Currently not used.
ByteArrayValu O 0 1000000 Indicates the resource usage of one
eMediumPoolS of the Runtime Containers' internal
ize resources. Currently not used.
ByteArrayValu O 0 1000000 Indicates the resource usage of one
eLargePoolSiz of the Runtime Containers' internal
e resources. Currently not used.
StringValueSm O 0 1000000 Indicates the resource usage of one
allPoolSize of the Runtime Containers' internal
resources. Currently not used.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 101 of 126
LKZ:DE AL:N ECCN:4E992

Diagnostic port Type Values Fault indication possible reason in case of fault
default min max
StringValueMe O 0 1000000 Indicates the resource usage of one
diumPoolSize of the Runtime Containers' internal
resources. Currently not used.
StringValueLar O 0 1000000 Indicates the resource usage of one
gePoolSize of the Runtime Containers' internal
resources. Currently not used.
AlarmInfoPool O 0 1000000 Indicates the resource usage of one
Size of the Runtime Containers' internal
resources. Currently not used.
ProcessDataId O 0 1000000 Indicates the resource usage of one
PoolSize of the Runtime Containers' internal
resources. Currently not used.
ProcessDataId O 0 1000000 Indicates the resource usage of one
HysPoolSize of the Runtime Containers' internal
resources. Currently not used.
ConnectionInfo O 0 1000000 Indicates the resource usage of one
DataPoolSize of the Runtime Containers' internal
resources. Currently not used.
SubscriptionDa O 0 1000000 Indicates the resource usage of one
taPoolSize of the Runtime Containers' internal
resources. Currently not used.
PvDataPoolSiz O 0 1000000 Indicates the resource usage of one
e of the Runtime Containers' internal
resources. Currently not used.
PvDataSeqPo O 0 1000000 Indicates the resource usage of one
olSize of the Runtime Containers' internal
resources. Currently not used.
SetPvDataPool O 0 1000000 Indicates the resource usage of one
Size of the Runtime Containers' internal
resources. Currently not used.
InputValueCha O 0 1000000 Indicates the resource usage of one
ngedWrapperP of the Runtime Containers' internal
oolSize resources. Currently not used.
InputValueCha O 0 1000000 Indicates the resource usage of one
ngedProxyPool of the Runtime Containers' internal
Size resources. Currently not used.
AlarmMachine O 0 1000000 Indicates the resource usage of one
PoolSize of the Runtime Containers' internal
resources. Currently not used.
WrapperObject O 0 1000000 Indicates the resource usage of one
PoolSize of the Runtime Containers' internal
resources. Currently not used.
Supported O -- -- Indicates the communication
Communicatio protocols supported by the
n Protocols container.
Synchronizatio O 0 0 100000 Indicates the size of the
n Buffer Size synchronization buffer
Small=20000
Medium=40000
Large=100000

2.2.7 CM Runtime Container


To start the fault tracking for the CM Runtime Container proceed as follows:

1. The Diagnostic View has to be opened in the Workbench


2. Open the Nodes until the CM Runtime Container is visible in the Tree View

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 102 of 126
LKZ:DE AL:N ECCN:4E992

3. Select the desired CM Runtime Container


4. Compare the displayed status signals with the information below

Status Page
Column Possible Fault / o Possible reason in case of fault
Value k
Status starting transient The starting procedure of this Container is not finished.
Status running o.k. no comment
Status terminating transient The shut down procedure of this Container is not finished.
Status stopped fault The shut down procedure of this Container is finished. This Container
needs to be started to proceed with processing.
Status failed fault A malfunction was detected. Probably some or all tasks assigned to the
Container are stopped. Further investigation is needed to ensure the
Runtime Container is functioning properly.
Connection GOD o.k. no comment
State
Connection BAD fault This Runtime Container is not receiving the signals from the Source
State Container. Only the status of input signals from other Runtime Containers
or CM Runtime Containers are monitored.
Check whether this connected Runtime Container is running or not.
Check whether the signal exchange is designed properly.

Diagnostic Page
Diagnostic port Type Values Fault possible reason in case of fault
default min max indication
Base cycle I 0 0 10000 Indicates the target cycle time that
time was set for this Runtime
Container. This value is preset and
does not change during the
runtime
Measured I 0 0 10000 Indicates the cycle duration of the
cycle time last finished cycle.
Number of ipc I 0 0 100 Indicates the number of incoming
connections connections from other Runtime
Containers.
Imported data I 0 0 10000 Indicates the total number of
items count signals which are received from
other Runtime Containers.
Free memory I 0 1000000 Indicates the currently available
(kb) memory of a Runtime Container.
Free memory I 0 1000000 Indicates the minimum available
minimum (kb) memory of a Runtime Container.
Measured I 0 0 10000 Indicates the measured cycle time
cycle time of of the standby partner.
Standby
If the CM is nonredundant then
NOT AVAILABLE will be
displayed.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 103 of 126
LKZ:DE AL:N ECCN:4E992

Diagnostic port Type Values Fault possible reason in case of fault


default min max indication
Health Status O 0 0 100 Indicates health of the Master
of Master 0 to 49=FAILED
50 to 100=OK

where

at 51, Standby is started, but not


fully synchronized;

from 52 to 60, the role change is


triggered if Master's health is in
this range and Standby's health
value is greater than 60.

(see below for more information).

If the CM is nonredundant then


NOT AVAILABLE will be
displayed.
Health Status O 0 0 100 Indicates health of the Standby
of Standby 0 to 49=FAILED
50 to 100=OK

where

at 51, Standby is started, but not


fully synchronized;

from 52 to 60, the role change is


triggered if Master's health is in
this range and Standby's health
value is greater than 60.

(see below for more information).

If the CM is nonredundant then


NOT AVAILABLE will be
displayed.
Redundancy O false false true true Indicates that the health status of
Health Status the Automation Highways
Low connection for either the Master or
Standby is not OK.

If the CM is nonredundant then


NOT AVAILABLE will be
displayed.
Health O 0 0 3 Indicates heath of redundant
Redundant connection
Connection 0=OK
1=Link A Down
2=Link B Down
3=Both Links Are Down

If the CM is nonredundant then


NOT AVAILABLE will be
displayed.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 104 of 126
LKZ:DE AL:N ECCN:4E992

Diagnostic port Type Values Fault possible reason in case of fault


default min max indication
Health status O 0 0 1 Indicates health status of
Automation Automation Highway connection of
Highway master
Master 0=OK
1=ERROR

If the CM is nonredundant then


NOT AVAILABLE will be
displayed.
Health status O 0 0 1 Indicates health status of
Automation Automation Highway connection of
Highway standby
Standby 0=OK
1=ERROR

If the CM is nonredundant then


NOT AVAILABLE will be
displayed.
Number of I 0 0 20 Indicates number of elements in
Elements in synchronization data queue. When
Synchronizatio there isn't enough time in the cycle
n Data Queue to complete the synchronization
the elements in the queue
increase. Therefore a lower
number is desirable.

If the CM is nonredundant then


NOT AVAILABLE will be
displayed.
Number of Af I 0 0 10000 Indicates number of activated Af
Instance instances in container.
Health Status O 0 0 1 Indicates status of Master
of Master Communication Interface 0
Communicatio 0=OK
n Interface 0 1=ERROR

If the CM is nonredundant then


NOT AVAILABLE will be
displayed.
Health Status O 0 0 1 Indicates status of Master
of Master Communication Interface 1
Communicatio 0=OK
n Interface 1 1=ERROR

If the CM is nonredundant then


NOT AVAILABLE will be
displayed.
Health Status O 0 0 1 Indicates status of Master
of Master Communication Interface 2
Communicatio 0=OK
n Interface 2 1=ERROR

If the CM is nonredundant then


NOT AVAILABLE will be
displayed.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 105 of 126
LKZ:DE AL:N ECCN:4E992

Diagnostic port Type Values Fault possible reason in case of fault


default min max indication
Health Status O 0 0 1 Indicates status of Standby
of Standby Communication Interface 0
Communicatio 0=OK
n Interface 0 1=ERROR

If the CM is nonredundant then


NOT AVAILABLE will be
displayed.
Health Status O 0 0 1 Indicates status of Standby
of Standby Communication Interface 1
Communicatio 0=OK
n Interface 1 1=ERROR

If the CM is nonredundant then


NOT AVAILABLE will be
displayed.
Health Status O 0 0 1 Indicates status of Standby
of Standby Communication Interface 2
Communicatio 0=OK
n Interface 2 1=ERROR

If the CM is nonredundant then


NOT AVAILABLE will be
displayed.
Wake-up fault O false false true true Indicates that the next new runtime
container cycle could not be
started in time.
Cycle time O false false true true Indicates that a cycle has needed
exceeded more time than scheduled
Pool overflow O 0 1000000 Indicates that one of the Runtime
Containers' internal resources
exceeded. (Details are available
via the xxx_PoolSize ports, which
are currently not used.)
Memory low O 0 1000000 Indicates that the maximum
warning available memory of a Runtime
Container has nearly reached.
Maximum O 0 0 10000 Indicates the maximum cycle
cycle time duration of the last 100 cycles.
System fault in O false false true true Indicates an internal error in the
ipc module communication module of the
Runtime Container
Average cycle O 0 0 10000 Indicates the average cycle
time duration of the last 100 cycles.
System fault in O false false true true Indicates an internal error in the
realtime real time module of the Runtime
module Container.
System fault in O false false true true Indicates an internal error in the
engineering engineering module of the
module Runtime Container.
System fault in O false false true true Indicates an internal error in the
ipc module communication module of the
Runtime Container.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 106 of 126
LKZ:DE AL:N ECCN:4E992

Diagnostic port Type Values Fault possible reason in case of fault


default min max indication
System fault O false false true true Group Alarm of detected system
faults. It is raised if at least one of
the Runtime Containers' sub
modules indicates an internal
error. In this case, the logs should
contain detailed information about
the state within the Runtime
Container
Redundancy O false false true true Indicates whether redundancy has
Lost been lost.
Switch over is O false false true Indicates whether a mastership
in process switch over is in progress.
Connection O false false true Indicates whether the connection
between between runtime container and
runtime Redundancy Manager has been
container and lost.
Redundancy
Manager is lost
Communicatio O false false true true Indicates that at least one failure in
n fault the communication subsystem has
occurred (refer to IPC_CNT below,
also).
Investigations into the connected
Containers should give a reason
for the disturbances.
InputPortPoolS O 0 1000000 Indicates the resource usage of
ize one of the Runtime Containers'
internal resources. Currently not
used.
OutputPortPoo O 0 1000000 Indicates the resource usage of
lSize one of the Runtime Containers'
internal resources. Currently not
used.
ImportPortPool O 0 1000000 Indicates the resource usage of
Size one of the Runtime Containers'
internal resources. Currently not
used.
ExportPortPool O 0 1000000 Indicates the resource usage of
Size one of the Runtime Containers'
internal resources. Currently not
used.
BinaryValuePo O 0 1000000 Indicates the resource usage of
olSize one of the Runtime Containers'
internal resources. Currently not
used.
FloatValuePool O 0 1000000 Indicates the resource usage of
Size one of the Runtime Containers'
internal resources. Currently not
used.
IntegerValueP O 0 1000000 Indicates the resource usage of
oolSize one of the Runtime Containers'
internal resources. Currently not
used.
IP Address of O (IP Address) IP Address of Master
Master
If the CM is nonredundant then
NOT AVAILABLE will be
displayed.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 107 of 126
LKZ:DE AL:N ECCN:4E992

Diagnostic port Type Values Fault possible reason in case of fault


default min max indication
IP Address of O (IP Address) IP Address of Standby
Standby
If the CM is nonredundant then
NOT AVAILABLE will be
displayed.
LongValuePool O 0 1000000 Indicates the resource usage of
Size one of the Runtime Containers'
internal resources. Currently not
used.
AlarmEventPo O 0 1000000 Indicates the resource usage of
olSize one of the Runtime Containers'
internal resources. Currently not
used.
ByteArrayValu O 0 1000000 Indicates the resource usage of
eSmallPoolSiz one of the Runtime Containers'
e internal resources. Currently not
used.
ByteArrayValu O 0 1000000 Indicates the resource usage of
eMediumPoolS one of the Runtime Containers'
ize internal resources. Currently not
used.
ByteArrayValu O 0 1000000 Indicates the resource usage of
eLargePoolSiz one of the Runtime Containers'
e internal resources. Currently not
used.
StringValueSm O 0 1000000 Indicates the resource usage of
allPoolSize one of the Runtime Containers'
internal resources. Currently not
used.
StringValueMe O 0 1000000 Indicates the resource usage of
diumPoolSize one of the Runtime Containers'
internal resources. Currently not
used.
StringValueLar O 0 1000000 Indicates the resource usage of
gePoolSize one of the Runtime Containers'
internal resources. Currently not
used.
AlarmInfoPool O 0 1000000 Indicates the resource usage of
Size one of the Runtime Containers'
internal resources. Currently not
used.
ProcessDataId O 0 1000000 Indicates the resource usage of
PoolSize one of the Runtime Containers'
internal resources. Currently not
used.
ProcessDataId O 0 1000000 Indicates the resource usage of
HysPoolSize one of the Runtime Containers'
internal resources. Currently not
used.
ConnectionInfo O 0 1000000 Indicates the resource usage of
DataPoolSize one of the Runtime Containers'
internal resources. Currently not
used.
SubscriptionDa O 0 1000000 Indicates the resource usage of
taPoolSize one of the Runtime Containers'
internal resources. Currently not
used.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 108 of 126
LKZ:DE AL:N ECCN:4E992

Diagnostic port Type Values Fault possible reason in case of fault


default min max indication
PvDataPoolSiz O 0 1000000 Indicates the resource usage of
e one of the Runtime Containers'
internal resources. Currently not
used.
PvDataSeqPo O 0 1000000 Indicates the resource usage of
olSize one of the Runtime Containers'
internal resources. Currently not
used.
SetPvDataPool O 0 1000000 Indicates the resource usage of
Size one of the Runtime Containers'
internal resources. Currently not
used.
InputValueCha O 0 1000000 Indicates the resource usage of
ngedWrapperP one of the Runtime Containers'
oolSize internal resources. Currently not
used.
InputValueCha O 0 1000000 Indicates the resource usage of
ngedProxyPool one of the Runtime Containers'
Size internal resources. Currently not
used.
AlarmMachine O 0 1000000 Indicates the resource usage of
PoolSize one of the Runtime Containers'
internal resources. Currently not
used.
WrapperObject O 0 1000000 Indicates the resource usage of
PoolSize one of the Runtime Containers'
internal resources. Currently not
used.
Supported O -- -- Indicates the communication
Communicatio protocols supported by the
n Protocols container.
Synchronizatio O 0 0 100000 Indicates the size of the
n Buffer Size synchronization buffer
Small=20000
Medium=40000
Large=100000

Health Status of Master and Standby

The health status of the Master and Standby redundancy partners is indicated by a value from 0 to 100. The following
table provides the impact of various faults to this health value:

Fault Scenario State Impact (in %) Resulting Health Status


Synchronization Fault

a. Master FAULT 5 (100 - 5) = 95


b. Standby FAULT 100 (100 - 100) = 0
Communication Fault

a. Hpi Connection 0 (100 - 0) = 100

b. Communication Interface DEVICE_FAULT 20 (100 - 20) = 80


b. Communication Interface INTERFACE_FAULT 50 (100 - 50) = 50
c. IPC (Unbundler/Subscriber) FAULT 10 (100 - 10) = 90
Runtime Fault

FAULT 70 (100 - 70) = 30

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 109 of 126
LKZ:DE AL:N ECCN:4E992

Multiple concurrent faults are subtracted from 100% (e.g. 100 - 70 - 20 = 10).

2.2.8 S7 Runtime Container


To start the fault tracking for the S7 Runtime Container proceed as follows:

1. The Diagnostic View has to be opened in the Workbench


2. Open the Nodes until the S7 Runtime Container is visible in the Tree View

The Runtime Container Node name begins with afc, i.e. afc701

3. Select the desired S7 Runtime Container


4. Compare the displayed status signals with the information below

Status Page
Column possible fault / o possible reason in case of fault
Value k
Status starting transient The starting procedure of this Container is not finished.
Status running o.k. no comment
Status terminating transient The shut down procedure of this Container is not finished.
Status stopped fault The shut down procedure of this Container is finished. This Container needs
to be started to proceed with processing.
Status failed fault A malfunction was detected. Probably some or all tasks assigned to the
Container are stopped. Further investigation is needed to ensure the
Runtime Container is functioning properly.
connection GOD o.k. no comment
state
connection BAD fault This Runtime Container does not receive signals from at least one other
state Runtime Container. The concerned Runtime Container is displayed.
Check whether this connected Runtime Container is running or not.
Check whether the signal exchange is designed properly.

Diagnostic Page
Diagnostic port Type Values Fault possible reason in case of fault
default min max indication

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 110 of 126
LKZ:DE AL:N ECCN:4E992

Diagnostic port Type Values Fault possible reason in case of fault


default min max indication
base cycle C1 O 0 0 10000 Indicates the cycle time that was
set for this S7 Runtime Container.
This value is preset and does not
change during the runtime.
maximum O 0 0 10000 Indicates the maximum cycle
cycle time C1 duration of the S7 Runtime
Container. This is the maximum
value monitored since the last
configuration change to the
container.
average cycle O 0 0 10000 Indicates the average cycle
time C1 duration of the S7 Runtime
Container. This is the average
value monitored since the last
configuration change to the
container.
measured O 0 0 10000 Indicates the average system
system cycle cycle duration of the S7 Runtime
time Container. The system cycle time
is the amount of time left over in
the cycle after the user program
has been executed. This is the
value monitored since the last
configuration change to the
container.
maximum O 0 0 10000 Indicates the maximum system
system cycle cycle duration of the S7 Runtime
time Container. The system cycle time
is the amount of time left over in
the cycle after the user program
has been executed. This is the
value monitored since the last
configuration change to the
container.
minimum O 0 0 10000 Indicates the minimum system
system cycle cycle duration of the S7 Runtime
time Container. The system cycle time
is the amount of time left over in
the cycle after the user program
has been executed. This is the
value monitored since the last
configuration change to the
container.
maximum O 0 0 10000 Indicates the maximum number of
subscription dynamic values from the S7 CPU
size that can be displayed
simultaneously at User Interfaces
(in addition to alarms and archived
values).
current O 0 0 10000 Indicates the current number of
subscription dynamic values from the S7 CPU
size that are displayed simultaneously
at User Interfaces.
hmi buffer O 0 0 1 1 Indicates the buffer used for the
overflow transmission of HMI signals is full.
alarm buffer O 0 0 1 1 Indicates the buffer used for the
overflow transmission of alarms is full.
CP1 error O 0 0 1 1 Indicates Communication
Processor 1 error

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 111 of 126
LKZ:DE AL:N ECCN:4E992

Diagnostic port Type Values Fault possible reason in case of fault


default min max indication
CP2 error O 0 0 1 1 Indicates Communication
Processor 2 error
Bus1 error O 0 0 1 1 Indicates Bus1 has an error
Bus2 error O 0 0 1 1 Indicates Bus2 has an error
CPU0 error O 0 0 1 1 Indicates CPU 0 has an error
CPU1 error O 0 0 1 1 Indicates CPU 1 has an error
Communicatio O 0 0 1 1 Indicates that at least one failure in
n fault the communication subsystem has
occurred. These failures can occur
as HMI Buffer Overflow or Alarm
Buffer Overflow, CP1 or CP2 Error
or Bus1 or Bus2 Error.
System fault O 0 0 1 1 Indicates that at least one failure in
the system has occurred. These
failures occur as CPU errors or
also in the case where the internal
error index is greater than 0.
internal error O 0 0 10 Indicates information about the
index nature of a fault. To be used by
specialized service staff.
archive sync O 0 0 1 1 Indicates successful
event resynchronization with the archive
successful following a communication
interruption.
archive sync O 0 0 1 1 Indicates a failed
event failed resynchronization with the archive
following a communication
interruption.
alarm sync O 0 0 1 1 Indicates successful
event resynchronization with the alarm
successful system following a communication
interruption.
alarm sync O 0 0 1 1 Indicates a failed
event failed resynchronization with the alarm
system following a communication
interruption.
Adaptive O 0 0 1 1 Indicates that the current amount
Archiving of analog signals being archived
requires that the generation of the
archive signals is automatically
adapted.
The following diagnostic Ports correspond to the indication lamp status of the CPU modules. Each Port exists for CPU0 and
CPU1, e.g. CPU0 INTF and CPU1 INTF.
INTF O 0 0 1 1 Internal fault. "INTF" LED lights up
until the fault is acknowledged.
EXTF O 0 0 1 1 External fault. "EXTF" LED lights
up until the fault is acknowledged.
BUS1F O 0 0 1 1 An error has been detected at the
MPI / PROFIBUS DP interface 1.
BUS2F O 0 0 1 1 An error has been detected at the
PROFIBUS DP interface 2.
RUN O 0 0 1 1 CPU is in RUN mode.
STOP O 0 0 1 1 CPU is in STOP mode. The user
program is not processed. Restart
and warm restart / reboot is
possible. If the STOP status was
triggered by an error, the error
indication (INTF or EXTF) is also
set.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 112 of 126
LKZ:DE AL:N ECCN:4E992

Diagnostic port Type Values Fault possible reason in case of fault


default min max indication
REDF O 0 0 1 1 There is an IO redundancy error:
Failure of a DP master or partial or
complete failure of a DP master
system
Loss of redundancy on the DP
slave.
IFM1F O 0 0 1 1 An error has been detected at
module interface 1.
IFM2F O 0 0 1 1 An error has been detected at
module interface 2.
MSTR O 0 0 1 1 CPU has the process control for
the switched IO.
RACK0 O 0 0 1 1 CPU on rack number 0.
RACK1 O 0 0 1 1 CPU on rack number 1.
The following diagnostic Ports correspond to the indication lamp status of the power supply modules. Each Port exists for
rack 0 and rack 1, e.g. Power supply rack 0 error 24V and Power supply rack 1 error 24V.
Power supply O 0 0 1 1 DC24V LED: The 24 V DC voltage
rack (0 or 1) for rack is outside the tolerance
error 24V limits.
Power supply O 0 0 1 1 BAF LED: The battery voltage on
rack (0 or 1) the rack backplane bus is too low.
error battery
fault

2.2.9 Archive Container


To start the fault tracking for the Archive Container proceed as follows:

1. The Diagnostic View has to be opened in the Workbench


2. Open the Nodes until the Archive Container is visible in the Tree View

The Archive Container Node name is arc

3. Select the Archive Container


4. Compare the displayed status signals with the information below

Status Page
Column possible fault / o possible reason in case of fault
Value k
Status starting transient The starting procedure for this Container is not finished
Status running o.k.

Status terminating transient The shut down procedure for this Container is not finished
Status stopped fault The shut down procedure for this Container is finished. Archive services are
currently not performed.
Status failed fault A malfunction was detected. Probably the archive functions are particularly not
working. Further investigation is necessary to ensure that the Archive Container
is functioning properly.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 113 of 126
LKZ:DE AL:N ECCN:4E992

Diagnostic Page
Diagnostic port Type Values Fault possible reason in case of fault
default min max indication
Analog tag O 0 0 1 1 Archive overflow impending. Less
overflow than 100 tags are available.
Event tag O 0 0 1 1 Archive overflow impending. Less
overflow than 100 tags are available.
Long tag O 0 0 1 1 Archive overflow impending. Less
overflow than 100 tags are available.
Operation tag O 0 0 1 1 Archive overflow impending. Less
overflow than 100 tags are available.
Used analog O 0 0 65536 The number of analog tags
tag ids currently used in the archive.
Used event tag O 0 0 262144 The number of analog tags
ids currently used in the archive.
Used long tag O 0 0 32768 The number of long tags currently
ids used in the archive.
Used operation O 0 0 32768 The number of operation tags
tag ids currently used in the archive.
Maximal O 0 0 65536 The maximum number of analog
allowed analog tags currently allowed in the
tag ids archive.
Maximal O 0 0 262144 The maximum number of event
allowed event tags currently allowed in the
tag ids archive.
Maximal O 0 0 32768 The maximum number of long tags
allowed long currently allowed in the archive.
tag ids
Maximal O 0 0 32768 The maximum number of
allowed operation tags currently allowed in
operation tag the archive.
ids

2.2.10 SIMATIC Communication Container


To start the fault tracking for the SIMATIC Communication Container proceed as follows:

1. The Diagnostic View has to be opened in the Workbench


2. Open the Nodes until the SIMATIC Communication Container is visible in the Tree View

The SIMATIC Communication Container Node name is cc

3. Select the SIMATIC Communication Container


4. Compare the displayed status signals with the information below

Status Page
Column possible fault / o possible reason in case of fault
Value k
Status starting transient Startup procedure for this Container is not finished
Status running o.k.

Status terminating transient Shutdown procedure for this Container is not being performed
Status stopped fault Shutdown procedure for this Container is finished.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 114 of 126
LKZ:DE AL:N ECCN:4E992

Column possible fault / o possible reason in case of fault


Value k
Status failed fault A malfunction was detected. Some or all tasks of the Container is not working
properly. Further investigation is necessary to put the Container in proper
operation.

Diagnostic Page

There is no dynamic data available for this Node in the diagnostic system.

2.2.11 CFC Chart Container


To start the fault tracking for the CFC Chart Container proceed as follows:

1. The Diagnostic View has to be opened in the Workbench


2. Open the Nodes until the CFC Chart Container is visible in the Tree View

The CFC Chart Container Node name is cfc

3. Select the CFC Chart Container


4. Compare the displayed status signals with the information below

Status Page
Column possible fault / o possible reason in case of fault
Value k
Status starting transient Startup procedure for this Container is not finished
Status running o.k.

Status terminating transient Shutdown procedure for this Container is not being performed
Status stopped fault Shutdown procedure for this Container is finished.
Status failed fault A malfunction was detected. Some or all tasks of the Container are not working
properly. Further investigation is necessary to put the Container in proper
operation.

Diagnostic Page

There is no dynamic data available for this Node in the diagnostic system.

2.2.12 SIMATIC Failsafe Automation Function Container


To start the fault tracking for the SIMATIC Failsafe Automation Function Container proceed as follows:

1. The Diagnostic View has to be opened in the Workbench


2. Open the Nodes until the SIMATIC Failsafe Automation Function Container is visible in the Tree View

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 115 of 126
LKZ:DE AL:N ECCN:4E992

The Runtime Container Node name is afc_F

3. Select the desired SIMATIC Failsafe Automation Function Container


4. Compare the displayed status signals with the information below

Status Page
Column possible fault / o possible reason in case of fault
Value k
Status starting transient The starting procedure of this Container is not finished.
Status running o.k. no comment
Status terminating transient The shut down procedure of this Container is not finished.
Status stopped fault The shut down procedure of this Container is finished. This Container needs
to be started to proceed with processing.
Status failed fault A malfunction was detected. Probably some or all tasks assigned to the
Container are stopped. Further investigation is needed to ensure the
Runtime Container in functioning properly.
connection GOD o.k. no comment
state
connection BAD fault This Runtime Container does not receive signals from at least one other
state Runtime Container. The concerned Runtime Container is displayed.
Check whether this connected Runtime Container is running or not.
Check whether the signal exchange is designed properly.

Diagnostic Page
Diagnostic port Type Values possible reason in case of fault
default min max
Monitoring f_cfc_ 0 0 10000 The monitoring time
time Failsafe- timer is set in ms. It is set at AF:
Cycle 1 F_CYC_CO at the Port:
MAX_CYC

Monitoring of the F cycle time of


the cyclic interrupt Order Blocks
Monitoring f_cfc_ 0 0 10000 The monitoring time
time Failsafe- timer is set in ms. It is set at AF:
Cycle 2 F_CYC_CO at the Port:
MAX_CYC

Monitoring of the F cycle time of


the cyclic interrupt Order Blocks
Safety mode bool 1 1 0 Indicates that Safety Mode is
active = 0
inactive 0 1
Shutdown of bool 0 0 1 Indicates the current operating
Safety status of the system.
program
The failsafe program is
shutdown = 1

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 116 of 126
LKZ:DE AL:N ECCN:4E992

2.2.13 SIMATIC S7 FM458 Container


S7_FM458_Container

To start the fault tracking for the S7_FM458_Container proceed as follows:

1. The Diagnostic View has to be opened in the Workbench


2. Open the Nodes until the S7_FM458_Container is visible in the Tree View

The Runtime Container Node name is afc_FM

3. Select the desired S7_FM458_Container


4. Compare the displayed status signals with the information below

Status Page
Column possible fault / o possible reason in case of fault
Value k
Status starting transient The starting procedure of this Container is not finished.
Status running o.k. no comment
Status terminating transient The shut down procedure of this Container is not finished.
Status stopped fault The shut down procedure of this Container is finished. This Container needs
to be started to proceed with processing.
Status failed fault A malfunction was detected. Probably some or all tasks assigned to the
Container are stopped. Further investigation is needed to ensure the
Runtime Container in functioning properly.
connection GOD o.k. no comment
state
connection BAD fault This Runtime Container does not receive signals from at least one other
state Runtime Container. The concerned Runtime Container is displayed.
Check whether this connected Runtime Container is running or not.
Check whether the signal exchange is designed properly.

2.2.14 Diagnostic Container


To start the fault tracking for the Diagnostic Container proceed as follows:

1. The Diagnostic View has to be opened in the Workbench


2. Open the Nodes until the Diagnostic Container is visible in the Tree View

The Diagnostic Container Node name is dc

3. Select the Diagnostic Container


4. Compare the displayed status signals with the information below

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 117 of 126
LKZ:DE AL:N ECCN:4E992

Status Page
Column possible fault / possible reason in case of fault
Value ok
Status running o.k.

Status unknown fault This status information provided by the Monitor Container. The Diagnostic
Container itself is not working properly and needs to be restarted.

Since the Diagnostic Container is responsible for most of the information displayed in the Diagnostic View, a
lack of displayed information would indicate that the Diagnostic Container, itself, is not working properly.

The Action Stop for the Diagnostic Container is disabled.

Diagnostic Page

There is no dynamic data available for this Node in the diagnostic system.

2.2.15 SIMATIC Hardware Configuration Container


To start the fault tracking for the SIMATIC Hardware Configuration Container proceed as follows:

1. The Diagnostic View has been opened in the Workbench.


2. Open the Nodes until the SIMATIC Hardware Configuration Container is visible in the Tree View

The SIMATIC Hardware Configuration Container Node name is hc

3. Select the SIMATIC Hardware Configuration Container


4. Compare the displayed status signals with the information below

Status Page
Column possible fault / o possible reason in case of fault
Value k
Status starting transient Startup procedure for this Container is not finished
Status running o.k.

Status terminating transient Shutdown procedure for this Container is not being performed
Status stopped fault Shutdown procedure for this Container is finished. Alarm monitoring is not
performed actually.
Status failed fault A malfunction was detected. Some or all tasks of the Alarm Container is not
working properly. Further investigation is necessary to put the Alarm Container in
proper operation. The alarm functions are most likely at fault.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 118 of 126
LKZ:DE AL:N ECCN:4E992

Diagnostic Page

There is no dynamic data available for this Node in the diagnostic system.

2.2.16 IO-Tools
To start the fault tracking for the IO-Tools Container proceed as follows:

1. The Diagnostic View has to be opened in the Workbench


2. Open the Nodes until the IO-Tools Container is visible in the Tree View

The IO-Tools Container Node name is iotools

3. Select the IO-Tools Container


4. Compare the displayed status signals with the information below

Status Page
Column possible fault / o possible reason in case of fault
Value k
Status starting transient The starting procedure for this Container is not finished.
Status running o.k.

Status terminating transient The shut down procedure for this Container is not finished.
Status stopped fault The shut down procedure for this Container is finished. IO-Tools services are
currently not performed.
Status failed fault A malfunction was detected. The IO-Tools functions are probably not working.
Further investigation is needed to ensure the IO-Tools Container is functioning
properly.

Diagnostic Page

There is no dynamic data available for this Node in the diagnostic system.

2.2.17 License Server


To start the fault tracking for the License Server proceed as follows:

1. The Diagnostic View has to be opened in the Workbench


2. Open the Nodes until the License Server is visible in the Tree View

The License Server Node name is ls

3. Select the License Server


4. Compare the displayed status signals with the information below

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 119 of 126
LKZ:DE AL:N ECCN:4E992

Status Page
Column possible fault / o possible reason in case of fault
Value k
Status starting transient The starting procedure for this Container is not finished.
Status running o.k.

Status terminating transient The shut down procedure for this Container is not finished.
Status stopped fault The shut down procedure for this Container is finished. License services are not
performed.
Status failed fault A malfunction was detected. The License functions are probably not working.
Further investigation is necessary to ensure the License Container is functioning
properly.

Diagnostic Page

There is no dynamic data available for this Node in the diagnostic system.

2.2.18 Monitor Container


To start the fault tracking for the Monitor Container proceed as follows:

1. The Diagnostic View has to be opened in the Workbench


2. Open the Nodes until the Monitor Container is visible in the Tree View

The Monitor Container Node name is mc

3. Select the Monitor Container


4. Compare the displayed status signals with the information below

Status Page
Column possible Value fault / o k possible reason in case of fault
Status running o.k.

Since the Monitor Container is a key component of the system management which also monitors the other
Containers, a malfunction of the Monitor Container will result in a very limited function of the Diagnostic View.
In such cases, ensure that the Monitor Container works properly before starting investigations on malfunctions
of the other Containers.

Diagnostic Page

There is no dynamic data available for this Node in the diagnostic system.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 120 of 126
LKZ:DE AL:N ECCN:4E992

2.2.19 Project Container


To start the fault tracking for the Project Container proceed as follows:

1. The Diagnostic View has to be opened in the Workbench


2. Open the Nodes until the Project Container is visible in the Tree View

The Project Container Node name is pc

3. Select the Project Container


4. Compare the displayed status signals with the information below

Status Page
Column possible fault / o possible reason in case of fault
Value k
Status starting transient Startup of this Container is not finished
Status running o.k.

Status terminating transient Shutdown of this Container is not finished


Status stopped fault This Container is shutdown.

Since the Project Container contains all the static project information a proper
plant or unit operation is not possible in this case.
Status failed fault A malfunction was detected. Some or all tasks of the Project Container are not
working properly. Further investigation is necessary to put the Project Container
in proper operation.

Since the Project Container contains all the static project information a proper
plant or unit operation is not possible in this case.

Diagnostic Page

There is no dynamic data available for this Node in the diagnostic system.

2.2.20 Plant Display Server


To start the fault tracking for the Plant Display server proceed as follows:

1. The Diagnostic View has to be opened in the Workbench


2. Open the Nodes until the Plant Display server is visible in the Tree View

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 121 of 126
LKZ:DE AL:N ECCN:4E992

The Plant Display server Node name is pds

3. Select the Plant Display Container


4. Compare the displayed status signals with the information below

Status Page
Column possible fault / o possible reason in case of fault
Value k
Status starting transient Startup for this Container is not finished
Status running o.k.

Status terminating transient Shutdown for this Container is not finished


Status stopped fault This Container is shutdown. The Plant Display server is not operating.

The Plant Displays will not be provided with actual process data.
Status failed fault A malfunction was detected. Some or all tasks of the Plant Display Container are
not working properly. Further investigation is necessary to put the Plant Display
Container in proper operation. Alarm function issues are the most probable
causes of this condition.

The Plant Displays will not be provided with actual process data.

Diagnostic Page
Diagnostic port Type Values Fault possible reason in case of fault
default min max indication
Number of I n/a *) *) none Number of Subscriber:
Subscriber Count of automation function
containers, that are currently
accessed by the plant display
server.
Number of I n/a *) *) none Number of Clients:
Clients Count of visualization clients
(plant displays) that are
currently connected to the plant
display server.
Number of I n/a *) *) none Number of subscribed values:
subscribed Overall count of all subscribed
values process values ( i.e. size of the
internal process image)
Response I n/a *) *) none Response Time:
Time update time of the plant display
server process image.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 122 of 126
LKZ:DE AL:N ECCN:4E992

*) these values are continuously updated.

2.2.21 Report Container


To start the fault tracking for the Report Container proceed as follows:

1. The Diagnostic View has to be opened in the Workbench


2. Open the Nodes until the Report Container is visible in the Tree View

The Report Container Node name is rc

3. Select the Report Container node


4. Compare the displayed status signals with the information below

Status Page
Column possible fault / o possible reason in case of fault
Value k
Status starting transient Startup of this Container is not finished
Status running o.k.

Status terminating transient Shutdown of this Container is not finished


Status stopped fault This Container is shutdown. The Report Container is not operating.
Status failed fault A malfunction was detected. Probably the Report Container functions are
particularly or completely not working. Further investigation is necessary to put
the Report Container in proper operation.

Diagnostic Page

There is no dynamic data available for this Node in the diagnostic system.

2.2.22 Trend Display Server


To start the fault tracking for the Trend Display Server proceed as follows:

1. The Diagnostic View has to be opened in the Workbench


2. Open the Nodes until the Trend Display Server is visible in the Tree View

The Trend Display Server Node name is tds

3. Select the Trend Display Server node


4. Compare the displayed status signals with the information below

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 123 of 126
LKZ:DE AL:N ECCN:4E992

Status Page
Column possible fault / o possible reason in case of fault
Value k
Status starting transient Startup of this Container is not finished
Status running o.k.

Status terminating transient Shutdown of this Container is not finished


Status stopped fault This Container is shutdown. The Trend Display Server is not operating.
Status failed fault A malfunction was detected. Probably the Trend Display Server functions are
particularly or completely not working. Further investigation is necessary to put
the Trend Display Server in proper operation.

Diagnostic Page

There is no dynamic data available for this Node in the diagnostic system.

2.2.23 Call Home Container


To start the fault tracking for the Call Home Container proceed as follows:

1. The Diagnostic View has to be opened in the Workbench.


2. Open the Nodes until the Call Home Container is visible in the Tree View.
3. Select the Call Home Container.
4. Compare the displayed status signals with the information below.

Status Page
Column Possible Fault / o Possible reason in case of fault
Value k
Status starting transient The starting procedure of this Container is not finished.
Status running o.k. no comment
Status terminating transient The shut down procedure of this Container is not finished.
Status stopped fault The shut down procedure of this Container is finished. This Container
needs to be started to proceed with processing.
Status failed fault A malfunction was detected. Probably some or all tasks assigned to the
Container are stopped. Further investigation is needed to ensure the Call
Home Container is functioning properly.
connection GOD o.k. no comment
state

Diagnostic Page
Diagnostic port Type Values Fault possible reason in case of fault
default min max indication
smtp server O 0 0 1 1 Communication to the message
connection server failed.
error
buffer overrun O 0 0 1 1 Indicates that some alarm
notifications could not be sent due
to buffer overrun. Buffer size is set
in the administration console.
trouble alarm O 0 0 1 1 Raised if at least one of the
diagnostic ports is activated.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 124 of 126
LKZ:DE AL:N ECCN:4E992

2.2.24 Technological Calculation Container


To start the fault tracking for the Technological Calculation Container proceed as follows:

1. The Diagnostic View has to be opened in the Workbench.


2. Open the Nodes until the Technological Calculation Container is visible in the Tree View.
3. Select the Technological Calculation Container.
4. Compare the displayed status signals with the information below.

Status Page
Column Possible Fault / o Possible reason in case of fault
Value k
Status starting transient The starting procedure of this Container is not finished.
Status running o.k. no comment
Status terminating transient The shut down procedure of this Container is not finished.
Status stopped fault The shut down procedure of this Container is finished. This Container needs
to be started to proceed with processing.
Status failed fault A malfunction was detected. Probably some or all tasks assigned to the
Container are stopped. Further investigation is needed to ensure the
Technological Calculation Container is functioning properly.
connection GOD o.k. no comment
state

Diagnostic Page
Diagnostic port Type Values Fault possible reason in case of fault
default min max indication
TCC Status O 0 0 1 1 An error has occurred in the FMS.

2.2.25 Plant Monitor Container


To start the fault tracking for the Plant Monitor Container proceed as follows:

1. The Diagnostic View has to be opened in the Workbench


2. Open the Nodes until the Plant Monitor Container is visible in the Tree View

The Plant Monitor Container Node is located under the service container node, sc.

3. Select the Plant Monitor Container


4. Compare the displayed status signals with the information below

Status Page
Column possible fault / o possible reason in case of fault
Value k
Status starting transient The starting procedure for this Container is not finished
Status running o.k.

Status terminating transient The shut down procedure for this Container is not finished
Status stopped fault The shut down procedure for this Container is finished. Plant Monitor services
are currently not performed.
Status failed fault A malfunction was detected. Further investigation is necessary to ensure that
the Plant Monitor Container is functioning properly.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 125 of 126
LKZ:DE AL:N ECCN:4E992

Diagnostic Page

There is no dynamic data available for this Node in the diagnostic system.

2.3 Quality Codes


In SPPA-T3000 each signal is assigned a quality code. The OPC Data Access Custom Interface Specification is
used to establish a common base, which uses flags to convey the quality state for an items data value.

The quality codes are divided into 3 groups:

• Good, all good status indications start with G.


• Uncertain, all uncertain status indications start with U.
• Bad, all bad status indications start with B.

2.3.1 List of GOOD Quality Codes


The Good quality codes are listed below:

Abbreviation Denotation
GOD Value is GOOD, i.e. in normal state
GFO Value is GOOD but manually FORCED/SIMULATED
GNC Value is GOOD but port is Not Connected (e.g. visible Parameter)

2.3.2 List of UNCERTAIN Quality Codes


The UNCERTAIN quality codes are listed below:

Abbreviation Denotation
UNC Value is UNC ERTAIN since a substitute value is used
ULV Value is UNCERTAIN and the Last Usable Value is held, e.g. during parameter reconfiguration of
Hardware Proxies

ULV differs from BLV specifically on how the value is input.

In ULV a value which is supposed to be written to SPPA-T3000 has unexpectedly stopped updating.

In BLV a detectable communication error has prevented a value from being read.

In both cases the last usable value is maintained.

Copyright © Siemens AG 2005 Version:


All Rights Reserved Date: 2008_07_21 CFrel_4.41_en_2008_07_18_13_42
Diagnostic System (1/1) Page: 126 of 126
LKZ:DE AL:N ECCN:4E992

2.3.3 List of BAD Quality Codes


The BAD quality codes are listed below:

Abbreviation Denotation
BAD Value is BAD with non-specific reason
BAD-LL Value is BAD since a proper Limit Low is exceeded
BAD-LH Value is BAD since a proper Limit High is exceeded
BCE Value is BAD due to a Configuration Error
BNC Value is BAD since it is Not Connected to a data source
BLV Value is BAD and Last Known (good) Value is processed
BOS Value is BAD since the module channel is Out of Service
BCF Value is BAD due to a Communication Failure
BDF Value is BAD due to a Device Failure
BSF Value is BAD due to a Sensor Failure

Copyright © Siemens AG 2005 Version: