DETAILED DESIGN REPORT

ON
G+5 RESIDENTIAL BUILDING- BANGALORE

By
V. ANIL KUMAR

1
CONTENTS

1. Superstructure 3
2. Substructure 7

2
1. Superstructure

Structure Information:
No. of Floors 8 (G+5+Terrace+OHT)
Total Height 24 m
Plan Dimensions 14.055x22.532 m
Typical Floor Height 3m
PLAN aspect Ratio 0.623

Architectural plan

Structure Layout

3
Materials:
Concrete M25,M30
Steel HYSD500

Sections:
Columns 300x600 mm,230x600
Primary Beams 230x600 mm
Secondary beam 150x300 mm
Slabs 125mm, 150mm, 200mm

Shell Loads:
Load Set Dead Load (kN/m2) Live Load (kN/m2)
Habitual 1.5 2
Wash 3 2
Terrace 3 1.5
OHT 12 0.75
LMR 6 0.75
Stair Case 3 3
Lobby 1.5 3

Frame Loads:
Primary Beam 5.52 kN/m2
Secondary Beam 4.05 kN/m2
Parapet 1.5 kN/m2

Earthquake Load: As per IS 1893:2016 part 1


Zone Factor II
Importance Factor 1.0
Response Reduction Factor 5
Soil Type II (Medium)
Mass Source DL-1, LL-0.25
Time Period Tx-0.5682s, Ty-0.455s
Base Shear Vbx-551.94 kN, Vby-576.5 kN

Wind Load: As per IS 875:2015 part 3


Basic Wind Speed 33
Class Type B
Terrain Category II
Probability Factor, k1 1.0
Terrain, height, structure size factor, k2 1.07
Topography factor, k3 1.0
Shear Wx-269.1 kN, Wy-494.27 kN

4
P-Delta: P-Delta with 1.5DL is considered for Analysis.

Property Modifiers:
Section Unfactored Loads (Service) Factored Loads (Strength)
Columns 1.0Ig 0.7Ig
Beams 0.5Ig 0.35Ig
Slabs 0.35Ig 0.25Ig
Walls 1.0Ig 0.7Ig

Stability Checks:
Check Load OBSERVED ALLOWABLE
Case
Inter Story Drift ( Service) (mm) Spec X 0.002 0.012 SAFE
Spec Y 0.005 0.012
Max. Def. against EQ (Service) Spec X 14.18 96 SAFE
(mm) Spec Y 17.98 96
Max. Def. against Wind (mm) Wx 2.70 42 SAFE
Wy 4.96 42
Vertical deflection (mm) DL+LL 6.429 9.85 SAFE

Modal Analysis:

a) Guideline for Fundamental time period = 0.1 x N =0.1 X 8 = 0.8


Time period = 1.078s

b) No. of modes given should be given in such a way that around 95% to 98% modal
mass participation ratio shall be achieved.
Sum UX=96%
Sum UY=97.8%

c) 1st mode of vibration is performed to be translation mode


RZ = 2% which is less than 5 %
d) Difference between translation and rotation mode should be 10% of translation
mode time period
Translation mode time period=1.078 sec
Rotation mode time period=0.951 sec
Difference=0.127>0.1078

5
Vibration Analysis: the demand to capacity ratio is less than 1. Hence the building is safe
against vibration.

Torsional Irregularity: Torsion Irregularity observed.

6
2. Substructure Details:
Structure Information:

SBC 100 kN/m2


Nature of Foundation PILE FOOTING
Depth of Foundation 475mm, 650mm, 700mm, 800mm,975mm
Spring Type Point Spring
Spring Constant 95.2KN/mm
Depth of Water Table 3m

Materials:

Grade of Concrete M30


Grade of Steel HYSD500

Checks:

Check Load Case Allowable Observed


Settlement DL+LL 5 mm 4.91 mm SAFE
Punching Shear Service Envlp 1 0.907 SAFE
0.537(S.W) 0.49
Crack Width Service Envlp 0.2 mm 0.16 mm SAFE
Flotation 0.9DL+1.4WL Not observed SAFE

7
Reinforcement Cover: As per IS 456:2000

Slabs 25 mm
Beams 30 mm
Columns 40 mm
Walls 40 mm
Foundation Top-50, Bottom-60 mm

Load Combinations:

For Strength

 1.5DL + 1.5LL
 1.2DL + 1.2LL + SPEC X/Y
 0.9DL + 1.2LL + SPEC X/Y
 0.9DL + 1.5SPEC X/Y
 1.5DL +/- 1.5W X/Y
 1.2DL +1.2LL +/-1.2W X/Y
 1.5DL +/- 1.5W X/Y
 1.2 DL +/- 1.2LL +/- 1.2W X/Y
 0.9 DL +/- 1.5W X/Y

For Service

 1DL + 1LL
 1DL + 1SPEC X/Y
 1DL + 0.8LL + 0.8SPEC X/Y

List of Codes used:

Code Details
IS-456 2000 For RCC Design
IS-1893 Part-1, 2016 For Earthquake Loads
IS-875 Part-1, 1987 For Dead Loads
IS-875 Part-2, 1987 For Live Loads
IS-875 Part-3, 2015 For Wind Loads
IS-13920 2016 For Ductile Detailing

Softwares used:

Superstructure ETABS 2016


Substructure SAFE 2016