Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Table of Contents
List of Figures
Figure 5-1 Control Unit Electronic Modules ............................................................................ 5-4
Figure 5-2 Transmit Waveform Generation............................................................................. 5-7
Figure 5-3 Data Transmission Format..................................................................................... 5-7
Figure 5-4 Sensor Module Block diagram............................................................................. 5-11
Figure 5-5 ShortHop Receiver Block Diagram ...................................................................... 5-19
Figure 5-6 Standard SCB map with uniform distribution....................................................... 5-29
Figure 5-7 SCB Map with biased distribution ........................................................................ 5-30
Figure 5-8 Transmission Delay ............................................................................................. 5-32
List of Tables
Table 5-1 Table of Schematics, Upper Torquer module........................................................ 5-2
Table 5-2 Table of Schematics – Communications Module .................................................. 5-8
Table 5-3 Table of Schematics – Lower Torquer Module.................................................... 5-13
Table 5-4 ShortHop Receiver Schematics .......................................................................... 5-18
Table 5-5 Signals Digitised by Comms processor’s eight channel 8-bit ADC ..................... 5-27
Table 5-6 Digitised by Sensor processor’s eight channel 8-bit ADC ................................... 5-27
Table 5-7 Derived values from calculations within the Sensor processor ........................... 5-27
Table 5-8 Logged Slow Data................................................................................................ 5-28
Table 5-9 Pump Flow rates for data transmission to tool .................................................... 5-32
Table 5-10 ShortHop Default Values..................................................................................... 5-35
Table 5-11 V1 ShortHop Dpoint Data (Tool ID=132) ............................................................. 5-36
Table 5-12 V2 ShortHop Dpoint Data (Tool ID=132) ............................................................. 5-36
Table 5-13 V2 ShortHop Dpoint Data (Tool ID=133) ............................................................. 5-37
• Communications
• Sensor
The Upper Torquer Module comprises five printed circuit boards (pcbs) on a central
aluminium bracket (six for ShortHop). The printed circuit boards comprise;
• Three identical phase switch boards, which provide the variable loads to the outputs of the
3-phase generator.
• A switched mode power supply board which converts the 3-phase power into several DC
voltage rails.
When the phase voltage goes negative, a diode conducts and is used to switch a shunt
transistor and FET to discharge C1 and clamp the voltage at IC1A pin 3 to 0 volts. This forces
the comparator (IC1A pin 1) to switch low which in turn causes the power FET to switch off.
The cycle then repeats on the next positive part of the sinewave from the generator.
The Mk2 variant incorporates an additional FET connected across C1 that dumps the charge
on this capacitor when the +12v rail is low, ensuring a controlled start-up sequence.
External zener clamping diodes are fitted to some earlier units to prevent excessive transients
when the generators are first started up.
The VMOD demand signal controls where in the cycle the power FET is switched on and
thus controls the loading on the generator. Three identical phase switch boards are fitted to
each torquer module, one for each phase of the generator.
For test purposes, an ‘AUX PWR’ input is provided, allowing an external DC supply to be
used to apply power for test and repair work. A series diode, D7, is used to prevent this line
from being energised by power from the generator. A logic level signal, via the potential
divider R1/R2, provides an ‘APS’ output signal to the CU when auxiliary power is being
applied. When the APS (auxiliary power supply) line is high, the tool believes it is in surface
mode - allowing downloading of firmware / data logs etc. When the APS signal is low, the
tool believes it is in down-hole mode. It is sometimes useful to short APS to 0V while
powering the CU from an external source to ‘fool’ the CU into down-hole mode for certain
tests.
The rectified DC is used to supply IC1, a current mode switching power supply IC, operating
in a flyback configuration at a frequency of approximately 100KHz. The DC supply to IC1 at
this point is proportional to the speed of the generator, which in turn is proportional to the rate
of mud flow. This DC level can vary from approx. 11VDC to 50VDC (corresponding to
approximately 550RPM to 2500RPM at the generator).
The switched mode supply uses a transformer (TR1) to convert the available DC supply
voltage to four other voltage rails. These are,
• +5V @ 250mA
• +12V @ 50mA
5.1.1.3.1 PWM & F/V Board - Fitted to Mk1 Upper Torquer Modules
A potential divider formed by R18 and R19 reduces a voltage from the stator of one phase of
the generator. This signal is then ac coupled, clipped and filtered before being fed into IC3a at
pin 3. The resultant ac signal from IC3a is rectified and amplified by IC3b. The gain of IC3b
is adjusted by an SIT resistor. The output signal ‘VW’ represents an averaged DC signal of
1.5V when a signal at 50Hz is applied to the input (H). As the generator is a 4-pole device,
this represents a mechanical speed of 750 RPM.
The PWM circuit is designed to take the demand ‘PWM’ signal and convert it to a
proportional DC signal that is sent to the phase switch boards.
The ‘PWM’ signal is first applied to a 2-pole filter configured around IC1b and then fed to a
non-inverting amplifier (gain +1.18x) formed by IC1c. The board has the provision for using
a filtered reference signal ‘VR’ as an offset signal for IC1c, however this is not implemented.
The amplified signal at IC1c pin 10 is filtered by a 3-pole filter formed around IC1d, and
output onto the ‘VMOD’ line. The output at IC1d is offset by +2.5V with the addition of IC2
at pin 15.
The ‘VMOD’ output is approx. +5V at 0% demand on the torquer and 0V for 100% demand.
5.1.1.3.2 PWM & F/V Board - Fitted to Mk2 Upper Torquer Modules
This board incorporates the functionality of the Mk1 board but with improved noise rejection
and fault protection.
Monitoring two of the three voltage phases and using the logic gates U4b and U4d configured
as an R-S latch is used to sense the speed of the generator. The resultant signal is a negative
pulse dependent upon speed and amplitude of the input signal. The negative pulse is used to
trigger a monostable multivibrator formed using U4a and U4b. This has a nominal pulse
width of 5mS. The supply to U4 is accurately set to 7V by the voltage regulator formed by
U1, U3b and Q1. Thus the output of the monostable is controlled in both amplitude and pulse
width and it can accurately track the rotational speed of the generator. The output pulses from
the monostable are filtered by three, cascaded RC sections and buffered by U3a before being
output as the ‘VW’ signal. The SIT resistor, R13, achieves final gain trimming.
The PMW signal is filtered by two, cascaded 2-pole filters formed around U2a and U2b. The
filter, formed by U2b, has an offset of 2.5V achieved using the voltage reference IC, U1. The
output appears as the ‘VMOD’ signal. The ‘VMOD’ output is approx. +5V at 0% demand on
the torquer and 0V for 100% demand.
Figure 5-2 shows the stepped drive waveform to the antenna. Note that the first and last
transmit cycles in a bit sequence will be truncated by 1/16th of a cycle to reduce harmonics
and increase efficiency. Figure 5-3 shows the envelope of the transmitted waveform and the
structure of the transmitted data.
The data format is typically as follows,
• One data memory area is used for ‘slow’ data, which is added to the data memory until
full. When full, no further readings will be added and additional readings will be lost.
• The other data memory is used for ‘fast’ data. The software configures this memory to act
as a cyclic buffer. Data is added to the memory until full. When full, the oldest data will
be overwritten with the new data therefore the memory will contain the latest N readings.
The Mk1 design uses one-time programmable (OTP) electrically programmable read-only
memory (EPROM) for monitor code storage and electrically-erasable read-only memory
EEPROM for the application code. The OTP EPROM is contained in a WSI PSD301 device.
Battery backed RAM is used on the Mk1 design to store the whole data log memory. The
microprocessor’s internal EPROM is not used within either Comms Module.
Due to the complex nature of the Sensor Module and its calibration, it is recommended that
faulty items be returned to SHPC for repair and test. For this reason, the circuit description
will be at a relatively high level.
A block diagram of a Sensor Module is shown in Figure 5-2 .
The Sensor Module contains the sensing elements, interface circuitry and processor that are
used to calculate the position of the Control Unit and send the correct drive levels to the
torquers such that the correct position is maintained. For logging purposes, signals are passed
via the SPI bus to the Communications Module. Command and control signals are passed
back from the Comms. Module to the Sensor Module.
The Sensor Module consists of a 2-part aluminium bracket to which the sensors and pcbs are
attached. The lower part of the bracket (nearest to the drill bit) holds the collar fluxgate
magnetometers, the rate-gyro and the TRAX. These sensors are discrete items within their
own cases, which are securely attached to the bracket.
The three fluxgate magnetometers, shock sensors (where fitted) and printed circuit boards are
attached to the upper half of the bracket. Interconnecting wires are used between the two
halves of the module set into pockets machined into the outer surface of the bracket. The two
halves of the bracket are attached with two bolts and fitted within a cover tube.
5.1.3.5 TRAX
The TRAX module consists of a small cylindrical module, which fits into the lower half of
the sensor bracket. The module contains the three axis accelerometers that are used for
positional sensing when the tool z-axis is greater than 5° from vertical. The TRAX module
also includes a temperature sensor whose output is logged for temperature compensation and
log analysis.
For a description of the circuit operation, refer to the Upper Torquer Module section of this
document.
5.2.1 Overview
Bit deviation (turn and/or build) of the drillstring is achieved mechanically by using a Bias
Unit (BU). The BU assembly comprises a Filter Extension Sub and BU inserted in the
drillstring between the PowerDrive Control Unit (CU) Collar and the drill bit. The BHA
therefore comprises CU Collar/Filter Extension Sub/Bias Unit/Bit. The PD675 Filter
Extension Sub being a pin/pin NC50 (PD675) connection both ends. The PD900 Filter
Extension Sub being pin/pin - 7⅝” pin up/NC70 pin down. Connection with the drill bit is
provided by a 4½” IF regular box (PD675), or 6⅝” IF regular box (PD900) and screws
directly into the downhole end of the BU body. A multiple thread recut feature is incorporated
in the design of the drillstring tubulars. The BU provides a timed lateral force to the BHA
such that the direction of the bit is deviated within the hole.
• Collects filtered mud from the Filter Extension Sub to feed to the BU dynamics.
• Provides the mounting mechanism, bearings and lubrication system for the Control Shaft
• When fitted to the Valve Housing (Spider) it creates the chamber within which the valve
upper rotor and its mating valve stator are housed.
• Where the operator wants to run bit pressure drops above 800 Usgpm the KSC can be
configured with a set of chokes.
The Kalsi Series Choke is so named because it is designed to take nozzled chokes to limit the
pressure within the valve chamber in the event of high bit pressures being encountered,
however, this feature is seldom used. Kalsi refers to special seals used to meter lubrication of
the Control Shaft.
Filtered mud flows through the Kalsi Series Choke bores into the valve chamber at the
downhole end of the KSC body. The downhole end of the Control Shaft projects into the
valve chamber and is specially machined to provide an oriented location for the ported Valve
Upper. The Valve Upper has an oriented port which, when fitted to the oriented location on
the lower end of the Control Shaft, gets its orientation relative to tool face from the oriented
mechanical connection with the CU. Thus the CU determines the tool face and therefore the
position of the port in the Valve Upper relative to formation.
5.2.3.4 Pads
From the Stator the filtered mud is directed via individual drillings in the Valve Housing
(Spider) and the BU body to an individual piston and pad sub assembly located on the outside
of the BU body. When assembled in the drillstring the only external BU components are the 3
clamp plates, 3 pads, 3 hinges and 3 upper and lower pad travel restrictors known as kickers
complete with sets of fasteners. The 3 pads are the primary BU contacts with the wellbore.
These pads are equi-spaced around the BU circumference. Junk slots are provided between
the pad facets. Each pad is fitted with a hinge on its’ leading edge such that the major area of
the pad trails the hinge relative to drillstring rotation. Each pad is activated once per
revolution of the drillstring being a fed through the ported valve rotor and stator to feed
pressurised, filtered mud diverted from the bit feed. The energy to activate the pads is
provided by the flow and pressure differential between the annulus pressure and the BHA
internal pressure - the pressure drop across the bit generating the hydraulic force across the
stroke of the pad. The pad is attached to a piston operating in a bore which receives a timed
charge of filtered mud, therefore the design area of the piston determines the magnitude of the
force applied to the pad for a given bit pressure drop. PD675 pads and pistons are separate
entities requiring assembly. PD900 pads have the pistons integrated as one entity.
5.2.3.5 Pistons
Design requirements necessitate that the Piston axis is offset relative to the Hinge Pin axis,
resulting in the Piston motion describing an arc during its stroke. Therefore the bore, in which
the Piston stroke is a sector of a torus, is referred to as a ‘toroidal bore’. The toroidal bore is
held in place on each BU body facet using a Clamp Plate. The Clamp Plate is bolted and
staked to the BU body, where the Clamp Plate mates with the BU body an o-ring seal
prevents the escape of pressurised filtered mud.
The Piston circumference is machined with a profiled form to provide controlled clearance
and free movement of the Piston throughout its stroke. PD675 Pistons are doweled to the pad
to aid orientation of the piston-profiled form relative to the pad and bore. PD900 piston/pad
orientation is not relevant, as it is determined in the design as a single entity. All PowerDrive
Pistons are fitted with an elastomer Seal. The Seal is shaped to give a specific contact
pressure with the bore form and is oriented relative to the piston/pad/bore. The Seal is held
captive on the piston using a clamp ring and circlip fastening. This Seal has to cope with high
temperatures, high pressures and the abrasive mud as it strokes within the toroidal bore.
Relative to demanded toolface and formation each piston chamber is sequentially charged
with timed, pressurised and filtered mud delivered from the valve chamber via the stator and
drillings. As pressurised filtered mud charges the piston chamber, the piston/pad assembly
strokes thereby pushing the hinged pad outwards until the pad face contacts the well bore. The
pads are prevented from overstroking by the Kickers.
When the stator port is closed by the heel of the valve upper, the pressurised filtered mud in
the piston chamber is discharged to the well bore for return to the surface via the an exit
choke and an exhaust port machined each piston body. As the pressure depletes pad contact
with the well bore returns the pad and discharged piston to the retracted position pending
recharging during the next rotation of the BU body when the stator port will be recharged
from the port in the valve upper. The piston exit choke is integral with the Piston assembly,
the choke is small relative to the toroidal bore diameter, but sufficient to allow the pressurised
mud to escape into the well bore.
5.2.3.6 Pads
The pad is a stainless steel substrate coated with tungsten carbide hard facing into which
highly wear resistant PDC buttons are embedded. Tungsten carbide tiles, arranged to provide
protection from impact and erosion, provide further wear resistance. The pad hard facing,
PDC buttons and tiles are the primary BU parts in direct contact with the well bore. The PDC
provides most of the resistance to wear whilst pushing against the hole. Under high wear
conditions lower Kickers with extra hardfacing are available.
Bit Pin Restrictors are also available for PowerDrive, however these have not been used at the
time of writing.
The unit has separate power supply modules for the printer (10.6V), tape drive (16V) and
computer (18.5V). There is a further 24V supply which provides power to the PowerDrive
Control Unit, the IS barrier and to the RS-232 opto-isolator. These are all universal supplies
able to operate over a 100V to 260V range of AC power input voltages.
A rear-panel, 6-way connector provides the interface to the control unit. This interface
provides +24V control unit power, supplied via a dedicated control unit power switch on the
front panel and protected by means of a 500mA fuse on the rear panel. It also provides a two-
wire RS-232 connection (RXD, TXD) from the COM1 port of the laptop, which is connected
via an opto-isolator to protect the computer from any voltage transients induced on the cable
connection.
The IS barrier is also powered by the +24V supply via a separate front panel power switch.
When powered it provides an isolated 4-20mA loop drive on the hazardous side to a well-
head pressure transducer. On the safe side of the barrier the pressure transducer voltage is
sampled by an analog to digital converter. The converter is located on a PC card, inserted in a
slot in the laptop, which connects to a transition PCB via a ribbon cable. The transition PCB
is used for 24V supply distribution and samples the control unit supply voltage and current,
which are also acquired by the analogue to digital converter.
The laptop parallel port is connected to the tape drive, from where it is daisy-chained to the
printer port connection on the rear panel. A printer power connector is also located on the rear
panel. The printer is stowed within the surface unit cabinet for transit, but is removed and
connected to the rear panel when in use. The tape drive is built into the surface unit and
accessed on the front panel.
• CPU board,
The antenna signal is passed through Q13 to a low noise amplifier stage (U9) that has a gain
of x10 (20dB) gain. Q13 will be switched off if the DC level on the antenna signal is greater
than about 1V. This can happen when in transmit mode and prevent overload in R78 and U9.
The signal is then passed through an automatic gain control (AGC) stage that attempts to
maintain a constant output level on TP11. Q1 acts as a voltage controlled resistor varying the
gain of U6B and is controlled by the integrator U7B. The gain range of U6B is about x1 to
x400 (0-52dB). U6A is a wide band bandpass filter centred on 575Hz and applies a fixed x32
gain (30dB). The output of U6A (TP11) is half wave rectified by U7A which acts to opposed
a fixed current into the integrator provided through R60. If the output level is too high, U7A
and R58 will supply increased negative current - greater than the positive current through
R60. The excess negative current will cause the integrator to ramp more positive to increase
the effective resistance of Q1. This in turn lowers the gain in U6B to reduce the signal level
on TP11. The reverse effect will occur if the signal level is too low. When in equilibrium,
TP14 will be a half wave rectified signal, at approx. 7.8V peak. The integrator output voltage
is passed to a processor A/D channel to indicate signal strength.
The received signal then is amplitude limited to ±185mV by the precision bi-directional
limiter U5A and U5B. The clipping circuit prevents mixer overload caused by the AGC
circuit transient response. The clipped signal is passed to a differential amplifier that gives
inverted and non-inverted outputs. These outputs drive two mixer circuits in U4 that are
driven by locally generated 575Hz clocks phase shifted by 90°. The mixer outputs will
contain the sum and differences of the incoming signal and the local oscillator frequencies.
Separate 9Hz low pass filters, formed by in U3, pass only the difference frequency
components. Therefore, if the input signal frequency is exactly the same as the local
oscillator, then the mixer output will be a DC signal. Two channels are required, as the phase
of the input frequency is not known. If one channel is exactly in phase with the input signal
then that channel will give a maximum output while the other channel will give no output. As
the phase varies, one output will increase while the other decreases but at no time will both be
at zero.
Both filtered outputs are full wave rectified and summed by U2A, B & D and passed to a
comparator U1. U2C, D1 and C4 form a peak-detect and hold circuit. This captures the peak
level of the signal. Half of this signal is used to generate the comparator’s threshold voltage
(ensuring the comparator switches in the centre of the waveform to preserve the mark-space
ratio). U1B blanks the output if the signal level is too small thus reducing spurious noise
reaching the processor.
The FPGA U8 is fed with a 2300Hz clock from the processor that is divided by four to
generate the quadrature signals for the mixers. The FPGA also contains logic to drive a ‘H’
bridge antenna drive circuit. This is not used at present, as transmission is currently only
simplex (in one direction). In bi-directional communications mode, the FPGA will decode the
two signals from the processor using rising or falling edges of the data line while the clock is
high or low (high for transmission, low for receive). The FPGA mode is set by installing R64
or R66. R66 sets 'receive only' mode and is clocked at 2300Hz, R64 sets transmit and receive
and is clocked at 6900Hz.
At present the system is only configured for simplex operation. Future development may lead
to a half-duplex system.
• Inc, Azi,, BTM, HS, Gtot, Btot, Dip, Qinc, Qazi, CU, Vib (11 types)
The firmware, within the Comms. module, will have modified the raw sensor readings as
follows,
• Scaled each value to 12-bits and added a 4-bit tag (data ID), making 16-bits per measured
value
This is then passed by RS232 link, in ASCII/Hex, to the Upper Torquer Module ShortHop
processor (CPU) board, and through the ShortHop link and receiver to the CPU Board.
The Receiver CPU board receives the TTL level data from the Receiver Analogue Board
(T1022210). The data is input to the processor, a 68HC711 (U2) via R19. Resistor R19 and
diode D3 provide protection to the input line.
U1 is a low voltage detector IC which provides a defined reset level to the processor if the
supply voltage should drop below 4.6V.
The processed data is buffered and converted to RS485 levels by U3, an ultra-low power
driver IC. This data is available on connector J1. Note that data is sent to the PowerPulse
Interface (PPI). No data is received back from that module.
The firmware within the CPU (U2) acts upon the received data in performing the following
functions,
• Samples the TTL levels from the Receiver Analogue Board (the envelope of the 575Hz
signal).
• Validates the checksum bytes. If no data or incorrect data is decoded, the processor adds
default data values. This also applies if the receiver times-out.
• Converts the data to the correct format for transmission to the ARC5 modem board.
The firmware within the CPU is not configurable within the field.
• +5V @ 250mA
• +6V @ 50mA
5.4.1.6 Antennas
In order to transmit the data across the link, the ShortHop system utilises a magnetic
induction link. Passing current through a multi-turn coil achieves the magnetic field. The coil
is designed to produce a large magnetic field, proportional to the product of the energising
current and the number of turns. Unfortunately, the material forming the outer cover of the
antenna and the proximity of the stabilizer have a pronounced effect on the magnetic
waveform. The effect of the ferrous materials is to act as both a shorted turn around the
antenna coil and a shield. This reduces the efficiency of the system and affects the distance
over which the link will be effective.
Both the transmit and receive antennas are of a similar design. The units are encapsulated
within their housings and cannot be dismantled.
5.5 Software
There are a number of software components within the PowerDrive system. As might be
expected, the current release of software may change between updates of this manual
therefore it is recommended that the current release is checked on the PowerDrive website,
http://www.stonehouse.oilfield.slb.com/website/download_now.htm
The software items used with the PowerDrive System are.
5.5.1.1.1 Control
High and Low torquer RPM levels used in overspeed protection. If either torquer exceeds the
upper level, both torquers are progressively braked to attempt to reduce the speed (and hence
the generated voltage) until both torquers are below the lower level. Then the additional
braking is gradually reduced. (Default torquer limits are 2207 and 2002 RPM)
5.5.1.1.2 Logging
This specifies the fast data logging rate (fast data is acquired through the processor ADC at 5
msec intervals (min). To log at this rate would choke the system – so 100 msec is typically
used)
Memory partitions for logging memory are expressed as percentages. For Mk I Comms, the
memory is a 4Mbyte block of battery-backed static RAM which holds all the partitions.
Fast and Slow logs are single-pass (logging stops when full).
Telemetry and diagnostic are rollover logs (diagnostic is analogous to a black-box recorder of
fast data).
For Mk II Comms, Fast and Slow data is logged to a 2 Mbyte block of flash RAM, again
single-pass. Telemetry and diagnostic data are logged to 0.5 Mbyte of battery-backed RAM.
• All subsequent surveys - second survey starts when the first drilling cycle starts (end of
‘Bit’ period). Thereafter, this field defines the interval.
• Slow log period - duration of each survey (logging of 5Hz hi-res Gxyz & Bxyz signals at
5Hz).
• Fast log delay - time delay from start of slow log period to start of fast log period.
• Fast log period - duration of logging fast data channels (acquired at 200 Hz, logged at 10
Hz typically).
As an example, the fast log period may be 3 seconds, delay 10 seconds and slow log period
30 seconds. In this way, there is a mid-survey view of all fast and slow data concurrently.
5.5.1.1.2.2 Acquisition
This determines the order in which slow (high-resolution survey) data channels are acquired.
5.5.1.1.3 Navigation
This section defines aspects of the repeating drilling cycle and the initial steering setting for
the tool. After the start-up sequence, the ‘cycle time’ period repeats until power-off. Within
each ‘cycle time’ period, the Control unit stabilises for ‘Proportion’ percent of the cycle time
at an angle depending on the Toolface setting. Toolface is the desired angle of departure of
the borehole relative to highside in gravitational mode or relative to magnetic north in
magnetic mode. In each case, the frame of reference is to be looking downhole along the
tool’s longitudinal axis. The steering setting may alternatively be specified in cartesian terms
of build and turn, although this is rarely used.
On entering a toolface and proportion pair, the ‘Validate’ button is used to find the nearest
point in the steering map – itself viewable via the ‘Map’ button.
Telemetry may be set to 3-pulse or 4-pulse operation. If it is known that the tool will be
steering exclusively under Gravity or Magnetic control for the duration of the run, then the
mode can be pre-defined in the SCB and all telemetry sequences will be 3-pulse, defining
build and turn only. In all other cases 4-pulse telemetry should be specified, in which case the
build, turn and mode are redefined completely in each telemetry sequence.
Typically, magnetic steering mode is used within about ten degrees of vertical, gravitational
at higher inclinations. The steering mode is entirely under the control of the user. There is no
automatic change between modes. (The Control Unit’s angle relative to highside bears no
relationship to its angle relative to magnetic north).
The Toolface Phase Shift is an angle that relates to the Bias Unit. It signifies the angular
difference between the Control Shaft, which mates with the CU/BU Connector, and the
ultimate departure direction of the hole relative to highside (or magnetic north). This is
largely based on drillings within the Bias Unit body between the disk valve ports and their
corresponding actuators.
5.5.1.1.4 Downlink
The downlink parameters specify the physical characteristics of each telemetry pulse. Given
normal and low (in-pulse) flow rates and the falling and rising time constants of the mud
system (by observation), the characteristics of pulses as seen downhole are calculated.
5.5.1.1.5 Uplink
5.5.1.1.6 Mechanical
This details the calibration of the radial position of the Control Unit Connector (Mule Shoe)
relative to the Control Unit’s X-axis.
The actual angle at which the Control Unit stabilises for steering is computed in the Control
Unit software as the sum of three angles;
• The intended steering direction relative to highside (or magnetic north) which is the basic
demand angle from the user’s point of view as initially set in the SCB or telemetered to
the tool.
5.5.1.1.7 Ancillary
• Servo Gains – alteration is likely to seriously upset the behaviour of the Control Unit.
• Basic ‘Terminal Mode’ for querying software versions, log sizes, RTC setting and
checking, initialisation of log memory
Select file type, then file, then up to 4 curves (some curve-pairs are available, e.g. quadrature
signals). There are facilities for panning, zooming, scaling, time-correlation, X-Y plots, etc.
plus an option of a direct hardcopy of screen display. Displayed curves may be deleted and
replaced by others, more than one log can be open simultaneously.
Table 5-5 Signals Digitised by Comms processor’s eight channel 8-bit ADC
Table 5-7 Derived values from calculations within the Sensor processor
Figure 5-3 shows the standard distribution of points where the requirement for any vector is
likely. Figure 5-7 shows a biased distribution as might be used when the dominant
requirement is to build and turn right.
In both maps there are 49 points, each of which is the end of a vector whose origin is at the
centre. Despite the circular distribution, the points can be conveniently mapped onto a
rectilinear 7 * 7 matrix in the SCB.
The centre point in each map represents the straight-ahead case. The periphery of the circle
represents deviation at the tool’s full capability.
A point at 90°and at half-radius represents right turn at half the maximum capability of the
tool. Points along the 180° radius represent drop, and so on.
Any given point is uniquely defined by its two indices in the matrix.
5.5.2.5 Telemetry
To command the tool to steer according to a new vector, the Field Engineer selects the closest
available point to satisfy the continuing requirements of the well bore. The Surface Unit
software identifies the selected point by its indices in its copy of the navigation table and
encodes a sequence of pulse modulation.
The pulses are periods of departure from normal flow rate, generally a reduction of twenty
percent. The PowerDrive Control Unit detects flow rate variation by observing the rotational
speed of its upper torquer/generator.
Each pulse must be of sufficient duration and amplitude to be detected by the Control Unit.
Pulses as detected by the Control Unit can be heavily distorted versions of the step change
applied to the pump controls. The pump control system may slew at a constrained rate to
prevent damage to the pump - the inertial effects of varying the momentum of approximately
one ton of mud per hundred feet of borehole must also be considered. The resultant time
constant is typically in the order of 2.5 seconds per thousand feet of borehole.
A pulse is therefore taken to be a reduction in flow rate for a nominal period followed by a
similar period to allow for recovery to the normal flow rate.
The pulse sequence is encoded on a timebase of a Digit Time parameter, which is a part of the
SCB.
A pulse is separated from its neighbour by a time period, which is the product of the Digit
Time and the encoded value (in addition to the Digit Time for pulse recovery).
The matrix is numbered 0, 0 for the top left point, 6, 6 for the bottom right. The first index is
the row (vertical) and the second is the column (horizontal).
Either three or four pulses may be sent. The time between the first and second pulses
represents the first (vertical) index and the time between the second and third pulses
represents the second (horizontal) index. If a fourth pulse is sent it represents value 0 or 1
indicating magnetic or gravitational steering mode.
The Control Unit is receptive to telemetry pulses at a specifiable time after powering up.
The encoding of a new steering setting by the surface software is best demonstrated with an
example.
• The point 332°, 75%, shown ringed in Figure 5-3 , is in the second row and third column
of the matrix. This encodes as point 1, 2 as numbering starts at zero.
• Suppose that four pulses will be sent, and that gravitational steering is required.
• Given a Digit Time of 20 seconds and that the sequence starts two minutes after power-
up, the modulation sequence is as shown in Table 5-9.
0 : 00 Pumps up
2 : 00 Lower flow by 20% Start first pulse
2 : 20 Restore normal flow End first pulse20 sec recovery + 1 * 20 secs
3 : 00 Lower flow by 20% Start second pulse
3 : 20 Restore normal flow End second pulse20 sec recovery + 2 * 20 secs
4 : 20 Lower flow by 20% Start third pulse
4 : 40 Restore normal flow End third pulse20 sec recovery + 1 * 20 secs
5 : 20 Lower flow by 20% Start fourth pulse
5 : 40 Restore normal flow End fourth pulse
The effects of transmission delay on a pulse through the transmission medium (mud) are
shown in figure Figure 5-8.
The three lines within the figure represent;
The Control Unit observes flow rate indirectly from its effect on the RPM of the upper
torquer/generator’s rotor. This signal is averaged, as a noise reduction measure, and filtered,
revealing the relative times of the leading and trailing edges of each pulse.
Due to dispersive effects in the transmission of a pulse, the length of the pulse as detected
downhole may be up to 50% longer than the nominal pulse as sent.
The interval between the trailing edge of one pulse and the leading edge of the next is
therefore not sufficiently reliable. However, the interval between detection of two successive
falling edges can be determined with much greater accuracy. From this is subtracted the
nominal pulse width to reveal the interval from trailing edge of one pulse to the falling edge
of the next. Thus the represented numbers are determined. The Control Unit software looks
up the new toolface and proportion values using these indices into its copy of the navigation
table.
• Stage 0 - Idle period (time to first survey): Control Unit is inert for 10 to 255 seconds,
zero rotation by roll-rate gyro sensor. Its purpose is to allow other BHA components to
perform necessary activities without risk of CU interference.
• Stage 1 - Survey: CU takes a standard survey, still non-rotating. Typically the collar will
be non-rotating, or only slowly rotating, with the bit off-bottom, leading to a good quality
survey.
• Stage 2 - Diagnostic: Control Unit rotates at a fixed (specifiable) rate with the Upper
torquer hard-wired to half-load. During this period, the average flow rate (as Upper
Torquer rpm) is established as a reference for the Telemetry Window.
• Stage 3 - Telemetry window: CU continues under the same conditions and a software
filter runs, looking for a falling edge in the flowrate which signifies the start of the first
pulse in a sequence for re-defining the tool’s steering setting. If no pulses are sent, the
window times-out after four nominal pulse-widths - otherwise, the window remains active
until the sequence is complete (subject to further timeout constraints).
The Control Unit rotates at a constant speed relative to space during the Diagnostic and
telemetry periods. During a shallow-hole test, when the drillstring should be static, the
rotation of the CU drives the Bias Unit valve that should cause uniform pressure dips
when each port is opened in turn.
• Stage 4 - Bit period indicates whether telemetry has been received. Different rotation
rates are defined for the cases of successful receipt of telemetry and no telemetry (or
failed transmission / interpretation).
The start-up sequence is now complete and the drilling phase starts. Until power-off the
Control Unit alternates periods at fixed angle relative to space (to achieve maximum turn in
the required direction) with periods of collar-relative rotation (to achieve straight drilling).
These are stages 5 and 6 respectively. For 100% proportion, stage 6 never occurs (continuous
maximum turn). For 0% proportion, stage 5 never occurs (continuous slew).
5.5.3.2 Defaults
There are a number of defaults that are transmitted if any element of the system is unable to
see other elements within the data flow chain. These defaults, as seen on IDEAL, are;
Table 5-13 defines the PowerDrive Dpoints that are embedded into IDEAL 7 and
HSPM 7. Note that a ShortHop receiver sub modem software change to V7.0 is also
required to implement this change. A Mod Recap will be issued to cover this change
when appropriate.
Table 5-13 V2 ShortHop Dpoint Data (Tool ID=133)
1. AZI available in two resolutions, normal (0.1 deg) and LO (0.4 deg). The same source data is
available.
2. Control Unit tool face will be available in two resolutions, normal and LO resolution (6.4 deg) -
for use where bandwidth is limited.
3. SIG_LO, SIG_HI (Signal Strength) is also available in two resolutions, 12 and 6-bit. The 6-bit
version cuts off at approx. 50% receiver input saturation.
Next Chapter