Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
3 Scope:
4 General Clauses:
PORTABLE MANUAL FIRE EXTINGUISHERS
TOTAL OPERATION
SHORT FIRE
CAPACITY WEIGHT TIME DRAWING REMARKS
DESCRIPTION RATING
(KG) (SECONDS)
Including:
Metallic cabinet with
door and fire luminiscent
6KG DRY signals.
6KG ABC
CHEMICAL 27A-183B-C 9,3 22
EXTINGUISHER
POUDRE
Including:
Metallic cabinet with
door and fire luminiscent
9KG DRY signals.
9KG ABC
CHEMICAL 34A-233B-C 13,3 26
EXTINGUISHER
POUDRE
C. Carbon Dioxide Type Fire Extinguishers: Carbon steel tank, with pressure gage.
1. Class: B:C.
2. Size and classification as scheduled.
Including:
Metallic cabinet with
door and fire luminiscent
signals.
5KG C02
5KG CO2 89B-C 16,8 25
EXTINGUISHER
PORTABLE MANUAL FIRE EXTINGUISHERS
TOTAL OPERATION
SHORT FIRE
CAPACITY WEIGHT TIME DRAWING REMARKS
DESCRIPTION RATING
(KG) (SECONDS)
Including:
TROLLEY FRAME AND
WHEELS.
25KG ABC Fire luminiscent signals.
EXTINGUISHER 25KG ABC 34A-233B-C 42,5 30
TROLLEY
B. CO2 Carbon Dioxide Type Wheeled Trolley Fire Extinguishers: Carbon steel tank, with
pressure gage.
1. Class B C.
2. Size and classification as scheduled.
Including:
TROLLEY FRAME AND
WHEELS.
20KG C02 Fire luminiscent signals.
EXTINGUISHER 20KG CO2 188B-C 80 42
TROLLEY
END OF SECTION
END OF SECTION
END OF SECTION
2. Orifice-Type: Rated 250 psi (1725 kPa). Carbon steel (ASTM A-53) body and carbon
steel (ASTM A-569) plate, brass needle valve conforming to ASTM B-124. Minimum
straight pipe installation of five diameters upstream and two diameters downstream 2-
1/2”(DN65) through 4”(DN100) sizes, and 10 diameters upstream and 4 diameters
downstream in sizes 5”(DN125) and larger. Victaulic Style 734.
a. Victaulic Tooling
F. Tools shall be manufactured and supplied by Victaulic. Use roll sets or cut groovers
compatible with the pipe material and wall thickness.
G. Common wedge shaped AGS groove for pipe sizes 14”(DN350) through 24”(DN600)
requiring one (1) common AGS roll set per tool, for use with approved Victaulic grooving
tools. (VE414MC, VE416 FSD, VE424 MC, or VE436.)
2.12 EXECUTION
2.13 INSTALLATION:
A. Pipe ends shall be clean and free from indentations, projections and roll marks in the area
from pipe end to groove for proper gasket sealing.
B. The gasket style and elastomeric material (grade) shall be verified as suitable for the
intended service as specified.
C. Install the Victaulic AGS piping system in accordance with the latest Victaulic installation
instructions.
D. AGS products shall not be installed with standard grooved end pipe or components.
Installing AGS products in combination with standard grooved end products could result in
joint separation and/or leakage.)
E. Use Victaulic grooving tools with AGS roll sets to groove the pipe. Follow Victaulic
guidelines for tool selection and operation.
E. Flexible Drop System: Stainless steel, multiple use, open gate type.
1. Application: Use to properly locate sprinkler heads.
2. Include all supports and bracing.
3. Provide braided type tube as required for the application.
END OF SECTION
END OF SECTION
IP55
Paint Specifications:
Enclosure Accesories: -Red RAL3002.
-Wall mounting lugs. -Powder coating.
-Glossy texture finish.
Shortcircuit Withstand Rating 100 kA 400V/50Hz 200 kW
Ambient Temperature Rating Min. 5ºC Max. 50ºC
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
C. During storage, geotextile rolls shall be elevated off the ground and adequately covered
to protect them from the following: site construction damage, precipitation, extended
ultraviolet radiation including sunlight, chemicals that are strong acids or strong bases,
flames including welding sparks, temperatures in excess of 160ºF (71ºC), and any other
environmental condition that may damage the property values of the geotextile.
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
EXIT PASSAGE WAY CORRIDOR STL-1 CL-HVAC-1 2 16400 4556 1950 1950 1,20 37
CL-CAR-1 AND CL-CAR-3
EXIT PASSAGE WAY CORRIDOR
STL-1 CL-HVAC-2 1 16400 4556 1950 1950 1,20 37 Aluminium sand trap
CL-CAR-5
louvre w ith galvanised
STAIR WELL
STL-1 IL-PRS 1 16400 4556 1950 1950 1,20 37 steel bird screen.
PRESSURIZATION STR-5
STAIR WELL
STL-1 CL-PRS 1 16400 4556 1950 1950 1,20 37
PRESSURIZATION CAR-7
MAKE UP AIR CL-CLH STL-1 UL-SMK-2 1 30000 8333 1950 1950 2,19 37
Notes:
END OF SECTION
Fire Class
Fire position Duct orientation
EI 15 EI 30 EI 60 EI 90 EI 120
Fire inside duct
30 40 60 70 80 Horizontal
Inside
35 50 80 90 100 Vertical
Fire outside duct
30 30 30 70 80 Horizontal
Outside
30 30 30 70 80 Vertical
When both fire position are required
30 40 60 70 80 Horizontal
Both
35 50 80 90 100 Vertical
F. Thermal Conductivity:
T ºC 10 50 100 150 200 300 400 500 600 STANDARD
W/mK 0.031 0.035 0.040 0.047 0.054 0.072 0.096 0.120 0.162 EN12667
END OF SECTION
END OF SECTION
END OF SECTION
PRESSURIZED
EMERGENCY STAIR
AND CORRIDOR CL-HVAC-1
FAN: IL-PRS
Soundproofed
CL-CAR-1 CL-HVAC-1
PF-01 ventilation units
IL-STR-5 CL-HVAC-2
- 5 1050 4556 16400 350 3,0 400-III w ith backw ard-
CL-CAR-3 CL-PRS
01/02/03/04/05 facing blades.
CL-CAR-5
CL-STR-7
Notes:
- All fans shall be provided w ith flexible connections to avoid vibrations to ducts in inlet and outlet connection. (must be Fire Rated 400ºC and 120 minutes for smoke exhaust fans)
-All fans shall be provided w ith diferential pressure sw itch betw een inlet and outlet connection for supervisory the start or stop mode of the fan. (must be Fire Rated 400ºC and 120 minutes for smoke exhaust fans)
Soundproofed
SUPPLY FAN FOR
SF-01 ventilation units
MAKE UP AIR TO
- 2 UL-SMK-02 1285 8333 30000 433 11,0 400-III w ith backw ard-
CONCOURSE HALL
01/02 facing blades.
CL-CLH.
Notes:
- All fans shall be provided w ith flexible connections to avoid vibrations to ducts in inlet and outlet connection. (must be Fire Rated 400ºC and 120 minutes for smoke exhaust fans)
-All fans shall be provided w ith diferential pressure sw itch betw een inlet and outlet connection for supervisory the start or stop mode of the fan. (must be Fire Rated 400ºC and 120 minutes for smoke exhaust fans)
Axial extraction
SMOKE EXHAUST units w ith
REMOVAL FAN FOR SEF-01 soundproofed
2 UL-SMK-3 1455 10278 37000 440 15,0 400-III
MAIN ENTRANCE -01/02 box,
AT GRADE LEVEL Fire Rated
400ºC / 2h.
Notes:
- All fans shall be provided w ith flexible connections to avoid vibrations to ducts in inlet and outlet connection. (must be Fire Rated 400ºC and 120 minutes for smoke exhaust fans)
-All fans shall be provided w ith diferential pressure sw itch betw een inlet and outlet connection for supervisory the start or stop mode of the fan. (must be Fire Rated 400ºC and 120 minutes for smoke exhaust fans)
Axial extraction
SMOKE EXHAUST
units w ith
REMOVAL FAN FOR
SEF-02 soundproofed
CONCOURSE AREA 4 UL-SMK-1/4 1455 11000 39600 380 15,0 400-III
-01/02/03/04/ box,
AT CONCOURSE
Fire Rated
LEVEL
400ºC / 2h.
Notes:
- All fans shall be provided w ith flexible connections to avoid vibrations to ducts in inlet and outlet connection. (must be Fire Rated 400ºC and 120 minutes for smoke exhaust fans)
-All fans shall be provided w ith diferential pressure sw itch betw een inlet and outlet connection for supervisory the start or stop mode of the fan. (must be Fire Rated 400ºC and 120 minutes for smoke exhaust fans)
END OF SECTION
EMERGENCY STAIRCASE STR-5 EG-03 AG-STR-5 2 5227 1451,806 1225 325 0,320 4,54 13,4 30
EMERGENCY STAIRCASE STR-7 EG-03 IL-STR-7 2 5227 1451,806 1225 325 0,320 4,54 13,4 30
CEILING
CL-CAR-1, CL-CAR-3 & CL-CAR-
CL-CAR-1
5 PASSAGE WAY CORRIDOR AT EG-04 3 5110 1419,444 1025 425 0,356 3,99 10,3 25
CL-CAR-3
CONCOURSE LEVEL
CL-CAR-5
CL-CLH EG-05 LIFT 2 500 500
NOTES:
-ALL GRILLES WITH REGULATION DAMPER.
NOTES:
-With w ire mesh screen and insect screen in stainless steel.
END OF SECTION
1.03 Compliance
A. Tested to and in compliance with EN 12101-2, and CE marked.
SMOKE VENT
Width Height
TYPE Qty. Cv
(mm) (mm)
I 1100 600 84 0,64
II 1390 600 4 0,64
III 1323 600 24 0,64
IV 1062 600 48 0,64
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
75 3.2
100 3.4
150 3.6
200 4.2
(d) run cables at least 300 mm clear of other services, whether the
latter run parallel or transversely to cable trench. use pulling
compound, or lubricant to avoid excessive stress on the cable, if
required
(e) run cables below intersecting piped services, unless the cable
would be at a depth exceeding 2 m, in which case seek instructions
(f) ducts shall not be filled with cables to more than 60 % of their capacity.
(g) nylon draw cords shall always be left in ducts
(h) cable duct pits shall be provided at each change in direction and
in any case at distances not exceeding 30 m
(i) ducts shall be suitably sealed with polyurethane foam or
proprietary cable sealing arrangements if specified
(j) empty ducts shall be plugged with removable plugs
(k) ducts shall have a minimum diameter of 50 mm.
END OF SECTION
2. Welding:
a) The welding material shall be supplied identified with the catalogue number and
quantity.
b) The welding material shall be a mixture of copper and aluminium oxide which
shall require more than 870 ° C to ignite. In the other hand there shall be a
silver colour powder, named the INITIATOR or STARTER of the reaction, which
shall be ignited with the spark or lighter.
3. Disc:
a) It may be constructed of ferrous or non-ferrous material
b) It will allow the exothermic reaction in the crucible during the time required for
the resulting slag floats; the heat of the molten copper (liquid) melt the disc and
this flows to the cavity for welding.
4. Pliers:
a) Shall be designed according to the graphite moulds; for welding wire to wire,
wire to wire rods and bars.
b) Pliers shall adjust the mould making pressure between the mould parts. The
pressure can be varied.
2.03 CLAMPS
A. Copper rod coupling material shall be copper alloy containing not less than 80%
copper or bronze, and shall be suitable for direct burial. Hardware material must be
either stainless-steel or minimum 80% copper, suitable for direct burial and
compatible with the coupling material
B. The surface finish of the completed coupling shall be smooth and free of cracks,
burrs and sharp projections. Conformance to no sharp projections shall be tested
using a Technical Engineering Service Company, Sharp Edge Tester, Model SET-50
device.
C. The clamp in the assembled mode shall exhibit no less than 95% of the conductivity
of a soli The joined clamp/grounding conductor/rod electrode assembly must
withstand a pullout force of no less than 500 pounds before separation. This test
shall be performed by pulling on the grounding conductor with the rod held firmly in
place, the clamp providing a securing function only.
D. Bolted Clamp: Assembly torque requirements shall fall the following criteria with the
appropriate thread characteristics:
Document No. Revision Title
M002-RLR-MEP-SPE-27005 3 DD2 - Qatar University Station WP11.2 - MEP Specifications
P. O. Box 23452, Doha, State of Qatar; Ahmad Bin Ali Business Centre, 1st Floor , Room 2, Building 289, St.230, C Ring Road, Doha
Tel: ++974 4471 9853; Fax: ++974 4421 9210; Email: rizzani@qatar.net.qa
Joint Venture: Rizzani de Eccher Spa
Lotte Engineering & Construction Co. Ltd.
Redco International Trading & Contracting W.L.L.Page 426 of 611
a) Standard Duty 350 inch-pounds 3/8-20 UNC
E. Compression Clamp: Hammer-on clamp shall provide sufficient force to facilitate a
compression connection between the clamp and rod electrode. The grounding
conductor shall be in direct contact with the rod electrode to assure a positive
grounding path.
F. Clamps shall be marked with the manufacturer’s name or trademark, and trade size.
Each clamp package shall be marked with the manufacturer’s name or trademark,
and trade size.
2.04 EQUIPOTENTIAL BARS
A. The equipotential bonding bars shall be of copper.
B. Dimensions
1. Equipotential Bar 16 ways:
Length : 825 mm
Height : 50 mm
Width : 61 mm
Bolts : 12 (M10) + 4 (M6)
END OF SECTION
END OF SECTION
20 1.8
25 1.9
32 2.3
38 2.5
50 3.1
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
9.14 Switchboards:
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
2.03 DESCRIPTION
A. Refer to Contract Drawings for actual layout and location of equipment and
components; current ratings of devices, bus bars, and components; voltage ratings of
devices, components and assemblies; interrupting and withstand ratings of devices,
buses, and components; and other required details.
B. The soft starter shall be microprocessor controlled and shall consist of a power section,
logic board, and field wiring interface terminal board for ease of access to control and
power wiring as well as maintenance requirements. The soft starter shall consist of the
following general components:
1. Three sets of back-to-back phased controlled power semiconductors rated 1400
PIV to 500V, 1600 PIV to 600V and 1800 PIV to 690V.
2. Integral thermal sensor to trip and disengage the soft starter on heat sink over
temperature.
3. Programmable keypad and alphanumerical LCD display that indicates present
mode of operation. The LCD keypad shall display programming and diagnostic
data in full text.
4. LED indicators to show the following: On, Start, Run, Soft Stop, Stop, Save/Slow
Speed, Dual Set/Reverse, & Fault.
5. Modbus RTU communications port.
C. The soft starter input power section shall be designed to operate at either 240Vac,
415Vac three phase input voltages.
D. RVSS panels will include control power that is Vac via a control power transformer.
E. The RVSS panel shall include an input disconnect with a through-the-door handle
Document No. Revision Title
M002-RLR-MEP-SPE-27005 3 DD2 - Qatar University Station WP11.2 - MEP Specifications
P. O. Box 23452, Doha, State of Qatar; Ahmad Bin Ali Business Centre, 1st Floor , Room 2, Building 289, St.230, C Ring Road, Doha
Tel: ++974 4471 9853; Fax: ++974 4421 9210; Email: rizzani@qatar.net.qa
Joint Venture: Rizzani de Eccher Spa
Lotte Engineering & Construction Co. Ltd.
Redco International Trading & Contracting W.L.L.Page 526 of 611
interlocked to the enclosure door to provide a local and lockable means of removing all
input power from the RVSS panel.
F. Branch circuit protection fuses shall be provided to protect the RVSS and bypass
starter. Fuses shall be sized to provide proper branch circuit protection and be
coordinated with other power circuit components.
G. The RVSS panel will include door mounted operator devices and a through the door
keypad to facilitate programming, control functions and diagnostics.
H. The RVSS panel will include a line isolation contactor to remove three phase power
from the starter and motor during stop and fault conditions.
I. An AC3 rated Bypass Starter with Class 10 motor overload relay will be included and
controlled to allow cooler and more efficient operation during run conditions. This will
also allow the RVSS panel to run the motor using a full voltage, non-reversing starter in
the event the RVSS trips.
J. Soft-start controllers shall be housed in a separate cubicle compartment of the relevant
motor control centre.
2.03 PROTECTIVE AND DIAGNOSTIC FEATURES
In the event of a fault, the soft starter will have tripped. Faults must be reset to restart
operation once their cause has been rectified. The soft starter shall offer the following
Faults list:
A. External Fault (by a digital input)
B. Frequency out of Range
C. Heat Sink Over Temperature
D. Long Start Time
E. Overcurrent / Jam
F. Overload
G. Overvoltage
H. Phase Loss
I. Phase Sequence
J. Shorted SCR
K. Slow Speed Time
L. Thermistor Trip
M. Too Many Starts
N. Undercurrent
O. Undervoltage
P. Wrong Motor Connection
Q. Wrong Parameters
R. Wrong Wiring Connection
2.04 FEATURES AND ADJUSTMENTS
A. The RVSS panel will be factory programmed to operate all specified optional
devices.
B. The RVSS will include four (4) user selectable Start (4) user selectable and Stop
curves to match starting characteristics to load.
C. The RVSS will include an 80% Kickstart voltage with adjustable Kickstart time.
D. The RVSS will include user programmable Starting Voltage.
Document No. Revision Title
M002-RLR-MEP-SPE-27005 3 DD2 - Qatar University Station WP11.2 - MEP Specifications
P. O. Box 23452, Doha, State of Qatar; Ahmad Bin Ali Business Centre, 1st Floor , Room 2, Building 289, St.230, C Ring Road, Doha
Tel: ++974 4471 9853; Fax: ++974 4421 9210; Email: rizzani@qatar.net.qa
Joint Venture: Rizzani de Eccher Spa
Lotte Engineering & Construction Co. Ltd.
Redco International Trading & Contracting W.L.L.Page 527 of 611
E. The RVSS will include user programmable Starting Current.
F. The RVSS will include user programmable Current Limit.
G. The RVSS will include user programmable Acceleration and Deceleration times.
H. The RVSS will include user programmable Auto Reset for Phase Loss and
Undervoltage Fault.
I. The RVSS will include Dual Setting functionality to allow setting a second set of basic
motor parameters.
J. For diagnostic assistance, the RVSS shall record and store in its memory run status
and fault type of the past 10 faults and provided detailed information on soft starter
operating conditions at the time of fault.
K. The RVSS shall contain an energy savings function that when selected, automatically
reduces the RVSS output voltage at steady state operation to the level only required to
meet the torque requirement of the load. This function is not available with bypass
style panels.
L. Three user programmable inputs with the following functions:
1. Energy Savings Mode, Slow Speed or Reset.
2. Dual Adjust, Reversing or Reset.
3. External Fault
M. The Soft Starter shall have one (1) dedicated thermistor input that is programmable for
PTC or NTC type thermistors.
N. The RVSS shall provide an adjustable 4-20ma analog output signal that is proportional
the motor current.
O. Multiple configurations and all parameters can be save to a computer file via a PC
communication kit.
2.05 OPERATOR CONTROLS
A. All ASTAT XTs will include pull a-part terminals for its control connections.
B. The RVSS panel shall have a control terminal strip for field I/O wiring.
C. The RVSS will include four (4) customer safety interlocks.
D. The RVSS will include an Auto Run Input.
E. The RVSS will include fault relay outputs.
F. The RVSS will include auxiliary run relay outputs.
G. The RVSS will include three (3) programmable logic inputs.
H. The RVSS will include one (1) scalable analog output.
I. All RVSS panel door mounted operators will be 22mm industrial rated devices.
1. Operator controls and indicating devices shall include: RVSS Keypad, Fault Light.
2.06 KEYPAD INTERFACE AND STATUS LEDS
A. The Soft Starter shall be supplied with a backlit alphanumeric Liquid Crystal Display
(LCD) Multi-Function Keypad. The Keypad shall be capable of programming and
monitoring the Soft starter.
B. Keypad shall be divided into 3 functional groups:
1. Graphical display shall two lines of 16 alphanumeric characters each with full text
programming. Codes are not accepted.
2. LED’s – To display soft starter functions.
3. Navigation keys to program soft starter, display operational data, and faults.
C. The Soft Starter shall have Indication LED’s as follows:
1. Green – The soft starter is “On”.
Document No. Revision Title
M002-RLR-MEP-SPE-27005 3 DD2 - Qatar University Station WP11.2 - MEP Specifications
P. O. Box 23452, Doha, State of Qatar; Ahmad Bin Ali Business Centre, 1st Floor , Room 2, Building 289, St.230, C Ring Road, Doha
Tel: ++974 4471 9853; Fax: ++974 4421 9210; Email: rizzani@qatar.net.qa
Joint Venture: Rizzani de Eccher Spa
Lotte Engineering & Construction Co. Ltd.
Redco International Trading & Contracting W.L.L.Page 528 of 611
2. Red – The soft starter is in “Stop” mode.
3. Yellow – The soft starter is in “Start” mode.
4. Yellow – The soft starter is in “Save” or “Slow Speed” mode.
5. Green – The soft starter is in “Run” mode.
6. Green – The soft starter is in “Reverse” mode.
7. Yellow – The soft starter is in “Soft Stop” mode.
8. Red – The soft starter is in “Fault” mode.
D. The Soft Starter shall display operating data, fault information, and programming
parameters in English with other languages - Spanish, German and Italian available by
parameter setting.
E. The keypad shall display the last 10 faults and provides detailed information on soft
starter operating conditions at the time of fault occurrence.
2.06 NETWORK COMMUNICATIONS
A. The RVSS shall include Modbus RTU communication protocol.
END OF SECTION
END OF SECTION
B. Batteries:
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF SECTION
END OF DOCUMENT