1. DEGREE OF PROTECTION IP 42.

2. VOLTAGE : 415V ±10% ,50 HZ ±3%


3. CABLE ENTRY FROM BOTTO M.
5. PAINT : POW DER COATING SIEMENS GREY - RAL 7032.
6. THE MAXIMUM HEIGHT OF OPERATING HANDLE AND SWITCHES SHALL NOT EXCEED
1800MM
AND MINIMUM HEIGHT NOT BELOW 300MM.
7. EARTHING : A) EARTH BUS 50X6MM TINNED CU FOR MAIN EARTHING AND
B) DOOR EARTHING : 4 SQ.MM CU.
8. ALL INDICATION LAMPS SHALL BE OF CLUSTER LED TYPE.
9. PANEL SHALL BE METAL ENCLOSED, FLOOR MOUNTED, SINGLE/DOUBLE FRONT OF
MODULAR SECTION (FORM-3B) FREE STANDING, FRONT ACCESS TYPE SUITABLE FOR
INDOOR INSTALLATION.
10. VENDER TO SUBMIT BUSBAR SHORT CIRCUIT CALCULATION FOR 50KA FOR 1 SEC FOR
PANEL.
11. INCOMER ACB SHALL BE WITH THERMAL MAGNETIC BASED RELEASE WITH FOLLOWING
FEATURES. PROTECTION - OVERLOAD, SHORT TIME DELAY, SHORT CIRCUIT, EARTH FAULT
PROTECTION.
12. ACCESSORIES OF ACB SHALL INCLUDE AUXILIARY CONTACT BLOCK (2 NOS. 6N0+6NC),
BUSBAR EXTENSION, EXTENDED TERMINAL COVER, AND OPERATING MECHANISM WITH DOOR
'INTERLOCK', DOOR SEALING FRAME AND U/V RELEASE WITH TIME DELAY ETC.
13. ACCESSORIES OF MCCB SHALL INCLUDE AUXILIARY CONTACT BLOCK, BUSBAR
EXTENSION EXTENDED TERMINAL COVER & OPERATING MECHANISM WITH DOOR I/L.
14. ALL SWITCHGEAR SHALL HAVE SHORT TIME RATING OF MIN. 50KA FOR 1 SEC. (FOR
ACB/MCCB ICS=ICU=ICW=50KA FOR 1 SEC.)
15. ALL METERS SHALL BE DIGITAL TYPE & SHALL HAVE COMMUNICATION CAPABILITY.
16. ADEQUATE NO. (MIN. 2NOS FAN) AND ADEQUATE SIZE (MIN. 6" FAN) OF COOLING/
EXHAUST FAN SHALL BE PROVIDED TO ENSURE THAT OPERATING TEMPERATURE WITHIN
APFC PANEL/CUBICLE SHALL NOT INCREASE 5•C OVER DESIGN AMBIENT TEMPERATURE.
AIR INLET VENT AND EXHAUST FAN SHALL BE PROVIDED WITH WASHABLE FILTER.
17. ALL CTS SHALL BE PROVIDED WITH CT BREAKING TERMINAL BETWEEN CT & METER, CT
& RELAY AND CT & EARTH.
18. THERE WILL BE 15 KVAR FIXED CAPACITOR BANK (1 NO.) WITH 7% DE TUNED
REACTOR AND ON DELAY TIMER INSIDE THIS PANEL WHICH WILL BE CONTINUOUS ON.
19. THERE WILL BE A 14 STAGE MICROPROCESSOR BASED APFC RELAY WITH 7% DE
TUNED REACTORS INSIDE THIS PANEL.
20. ALL CAPACITORS SHALL BE SWITCHED ON/OFF THROUGH THYRISTOR SWITCHING
MODULE.
21. START/STOP BUTTON SHALL BE MOMENTARY TYPE, 1 NO/NC, 10A AT 240V AC.
22. SUITABLE INTERLOCK SHALL BE PROVIDED SUCH THAT POWER FACTOR CORRECTION
SHALL BE OFF WHEN DG INCOMER IS ON.
23. SPACE HEATER SHALL BE PROVIDED IN EACH CABLE ALLEY WITH THERMOSTATE
CONTROL PROTECTED BY DP MCB.
24. CFL LAMP & EXHAUST FAN WITH DOOR SWITCH TO BE PROVIDED IN EACH CABLE
ALLEY OF PANEL.
25. ALL MAINTENANCE PURPOSED INDUSTRIAL 10 SOCKET, CFL LAMP & EXHAUST FAN
SHALL BE PROTECTED WITH ELMCB (30mA).
26. ALL CONTROL VOLTAGE SHALL BE 240V AC.
27. VENDOR TO SUBMIT VA BURDEN CALCULATION FOR CONTROL TRANSFORMER.
28. EACH FEEDER COMPARTMENT SHALL HAVE SEPARATE DP MCB FOR ISOLATION OF CONTROL
SUPPLY.
29. SELECTION OF CAPACITORS FOR DETUNED HARMONIC FILTER APPLICATION SHALL BE AS
PER BELOW TABLE:

EFFECTIVE WITH 7% DETUNED REACTOR


kVAr
OUTPUT CAPACITOR (525 V)
5 kVAr 7.5 kVAr 525 V

10 kVAr 12.5 kVAr 525 V

12.5 kVAr 15 kVAr 525 V

15 kVAr 20 kVAr 525 V

20 kVAr 25 kVAr 525 V

25 kVAr 25 kVAr 525 V + 8.33 kVAr 525 V

30 kVAr 35 KVAr 525 V + 8.33 KVAr 525 V

40 kVAr 2 NOS. OF 25 kVAr 525 V + 8.33 kVAr 525 V

50 kVAr 2 NOS. OF 25 kVAr 525 V + 2 NOS. OF 8.33 kVAr 525 V

75 kVAr 3 NOS. OF 25 kVAr 525 V + 3 NOS. OF 8.33 KVAr 525 V

100 kVAr 4 NOS. OF 25 kVAr 525 V + 4 NOS. OF 8.33 kVAr 525 V