Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
1
Optimizing combustion in pulverized Coal fired Boilers
• Diagnostic testing
• Sensor based
• Online Optimization
• Modeling based approach for combustion
control
• Control loop tuning
Diagnostic tests
Combustion optimization based on Diagnostic testing
Optimized Combustion
• Optimum Excess Air (~3%)
• Low Unburnt carbon in ashes
(< 1% in FA)
Residence Time
• Avg CO < 100 ppm at furnace ~ 1-2 seconds
outlet
• Minimum SH/RH Sprays
• No Slagging & Clinkering
33
Issues - Combustion Optimization
34
Off line measurements are done to supplement On line feedback
35
Mill Out Temps measured during Dirty Air Flow Test (210 MW)
36
Mill Outlet Temps Vs Dirty air Temps (250 MW)
170
160
Tem p C
150
140 160.0-170.0
130 S3 150.0-160.0
A B
S2
C 140.0-150.0
D E
S1
Probes F
130.0-140.0
38
Combustion Optimization – Minimize Boiler Air-in-Leakage
• Actual optimal O2 varies from boiler to boiler.
• O2 probes at eco exit are influenced by air infiltration. Air-
in-leak thro’ boiler casing fools the panel operator &
Zirconia probes, triggering reduction in total air. In many
old boilers, O2 reading in control room was much higher
Puffing & slagging in
than actual O2 in furnace. upper furnace
• O2 measurement feedback using orsat is on dry basis
while insitu zirconia reading is on wet basis.
% Oxygen profile across FG path % Air ingress across Flue Gas path
9 40
FG path-A FG path-B
8 35
7 30
6 25
5 20
4 15
3
10
2
FG Path A FG Path B PG Test 5
1
0
0 Eco to AH PAPH SAPH AH to ESP ESP Inlet to Eco to
Eco out AH In AH out ESP In ID fan disch Inlet Inlet ID fan disch ID fan
Air ingress is quantified by the increase in oxygen % & temperature drop in flue gas; It’s
important to monitor & trend the same before ID fan capacity is constrained and combustion is
affected adversely.
39
High Unburnt Carbon in Ashes
• Fly ash is over 80% of total ash; So its important to test for unburnt carbon in fly ash. Routine
bottom ash sampling is not representative. For monitoring bottom ash unburnts, visual
inspection in shift beginning or after mill change over is good enough.
• + 50 fineness fractions of pulverized coal samples should be monitored and should be less
than 1% to ensure low unburnts in bottom ash.
40
High Unburnt in Ash
• Place 20 g fly ash on 200 mesh sieve and shake for • 53% of the ash retained on a 200 mesh sieve
20 minutes
• Retention coarse & high in carbon (8%)
• Determine unburnt of residue on 200 mesh screen
• Pass through - 200 sample was soft, fluffy and had
and in pan
less unburnts (1%)
Higher Unburnt in the pan sample indicates Air • This is indicative of poor fineness & problems in
distribution problems while higher Unburnt in the
milling system.
sieve would indicate milling problems
41
PF Fineness
PF fineness is influenced by
• Coal Quality, Mill settings, mill problems
• PA flows / velocities - Optimum Air /Fuel Ratios
• Sampling Techniques - Cyclone / 64 point rotary
sampler
• Sampling location – vertical pipes near burners
• Testing – Motorized sieve shaker
• Mill loading – Sampling at Nominal / defined
mill loading only
• Sampling for PF fineness should be done only at nominal mill loading by traversing test ports
in straight vertical PF pipes.
• +50 retention of PF samples should be <= 1%; High +50 results in high unburnt both in
bottom ash & fly ash as finer particles (-200) burn out in our boilers.
42
Acoustic Pyrometer - Temperature Mapping at Furnace Exit and Eco outlet
43
Online coal flow measurement in Mill discharge pipes
44
Plant Performance Analysis, Diagnosis & Optimization system (PADO)
45
Modifications in Gas duct internals based on CFD study
VSTPP U#5inFG
FG Flow flow atESP
different different
passesESP passes
(210 MW)
390
• Uniformization of flow in ESP passes (23 to 5%) 370 358 371 Before
Flow in T/hr
• Reduction in pressure drop (13 mmWC) in gas ducts 350 After
330 306
310
287
290 291 296
286
270 269
250
ESP_OUT-A ESP_OUT-B ESP_OUT-C ESP_OUT-D
46
Study of High Unburnt Carbon in ashes at 200 MW Unit
Performance test was conducted to diagnose the problem of high unburnt carbon in
fly ash (~2‐3%). High unburnt in ash is due to the following factors
•Poor PF fineness: Average pass through 200 mesh was 68% & average +50 retention
on 50 mesh was 3.5% during the tests
•Large variations in quality & poor reactivity of coals being fired. Differential Thermo
gravimetric analysis (DTG) analysis of coals was carried out at CIMFR labs & revealed
high burnout temperatures (568 C) indicating delayed burning characteristics
•High burner to burner imbalance in dirty air velocities. Dirty air imbalance between
the four discharge pipes in Mill A, B & D was over 10%.
•Low availability of oxygen in furnace: Unburnt carbon in fly ash reduced from 3.1%
to 1.4% on increasing oxygen from 2.9 to 3.4 %. High air ingress in Boiler & gas ducts is
leading to loss of margins in ID fans. Average Oxygen in flue gas at ID fans outlet was
9.2 & 8.0 % respectively.
Test were carried out in Unit 5 to analyze the reasons for high unburnt under different
test conditions and various reasons are detailed as following.
Study of High Unburnt Carbon in ashes at 200 MW Unit
Normally five mills & at times all six mills need to be run for full load as against four
mills as per design. The mills are run with high PA flows at an average outlet
temperature of 110 C. Pulverized coal samples were collected from the mill discharge
pipes of the running mills & sieved for fineness.
•High burner to burner imbalance in dirty air velocities. Dirty air imbalance
between the four discharge pipes in Mill A, B & D was over 10%.
Study of High Unburnt Carbon in ashes at 200 MW Unit
Test conducted with increased oxygen
Flyash samples were collected separately from left and right side during the tests; Incremental
bottom ash samples were collected from the grinders. Ash samples were collected again at full
load condition with increased oxygen (~3.5%) & analyzed
Table 8: Unburnt carbon % in Fly ash & Bottom ash
FA BA Composite Test Load
With increase in average oxygen % in flue gas from 2.9 to 3.4% in Test 2, Unburnt carbon in Fly ash reduced
to 1.38% from 3.08% in Test 1.
There’re no margins in ID fans at full load and average Oxygen in flue gas at ID fans outlet was 8.0 & 9.2 %
indicating high air‐in‐leak from the ducts between air heater outlet and ID fans. Post overhaul, a value of 5‐6
% Oxygen in flue gas is expected at ID fan outlet.
Study of High Unburnt Carbon in ashes at 200 MW Unit
Recommendations
While there are many contributing factors to high unburnt carbon in ashes, appreciable improvement can be
achieved by improvement in coal fineness. +50 fractions of pulverized coal should be close to 1% and the
same can be achieved mainly by mill internal settings, maintenance &/or up gradations.
•Poor +50 fractions are a major contributor towards high unburnt carbon in both Fly ash & Bottom ash.
a)There’s a need to study & revise mill internal settings like center feed pipe gap, inverted cone gap,
throat gap etc. in consultation with OEM to improve PF fineness.
b)Condition & movement of classifier blades should be inspected and rectified during opportunity
shutdowns.
c)Improvements in coal quality would also lead to reduction in coal quantity and increased fineness.
d)The possibility of mill capacity enhancement by component up gradation may be explored.
•Poor coal reactivity is one of the contributing factors for high unburnt carbon in ashes and its adverse
impact can be partly offset by following.
a)blending with more reactive coals
b)improving PF fineness, + 50 fractions in particular
•High Corner to corner imbalance in Dirty air velocities was observed in Mills A, B & D.
a)It is suggested to inspect Mill A, B & D classifiers & the orifices in PF pipes during next opportunity
shutdown to identify the reasons for imbalance in dirty air velocities.
b)Dirty air tests should be carried out in the mills to ensure PF balance after rectifications.
•Adequate excess air in furnace would help to reduce the impact of any PF imbalance and reduce unburnts
in ashes
OXYGEN SET POINT TO BE REPRESENTATIVE OF
DUCT CONDITIONS & CONDITIONS IN THE
FURNACE
• Oxygen as measured On line using ‘Zirconia Probes”
should represent the process.
• Left & right difference of Oxygen value could be a
realistic statement and not instrument error.
• No of Zirconia probes to be increased to improve the
reliability of feedback. Probes provided at AH outlet to
work out on line leakage.
BOILER TUNING AND COMBUSTION OPTIMIZATION
Many boilers are simply not equipped with monitoring and control
When operating with reduced excess air these imbalances are revealed by local carbon
monoxide (CO) formation.
These local CO areas can be significant and affect the average of the entire furnace. A
correction in combustion of these local CO spikes can allow reduction of excess air
improving emissions and efficiency.
The table below show an example of data collected from the economizer outlet plane of
a wall-fired unit. The grid measurement shows how the a pocket of high CO effected the
overall unit emissions and how elimination of the localized imbalanced improved overall
unit emissions.
Boiler Performance Optimization
• To evolve an optimum operating regime for a boiler; a
set of operating parameters and equipment settings
for safe, reliable and efficient operation.
~ Design
59
THANK YOU