Sei sulla pagina 1di 12

Effective October 2014

Smart Sensors Supersedes S1150-20-1 June 2014 MN915001EN

GridAdvisor™ Series II smart sensor installation instructions


Note: This document applies to product serial numbers that contain 12 characters
hexadecimal formatting
DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY
The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation’s
(“Eaton”) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales
office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in
appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser.
THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES
OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY
EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE
CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES.
In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other-
wise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or
loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing
power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recom-
mendations and descriptions contained herein. The information contained in this manual is subject to change without notice.

ii GridAdvisor Series II smart sensor installation instructions MN915001EN October 2014 www.cooperpower.com
Contents

SAFETY INFORMATION
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iv

PRODUCT INFORMATION
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Acceptance and Initial Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Handling and Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

INSTALLATION PROCEDURES
Installing SIM Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Forcing Over the Air Service Provision (OTASP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Installing Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Underground Distribution Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Installation of Smart Sensor - Underground Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Installation of Smart Sensor - Overhead Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Device Activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
LED Installation Indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Programming Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

SUPPORT
Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

APPENDIX A: REGULATORY INFORMATION


Compliance Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Important Battery Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

GridAdvisor Series II smart sensor installation instructions MN915001EN October 2014 www.cooperpower.com iii
! !
SAFETY
FOR LIFE Safety for life SAFETY
FOR LIFE

Eaton’s Cooper Power Systems products meet or exceed all applicable industry standards relating to product safety. We
actively promote safe practices in the use and maintenance of our products through our service literature, instructional
training programs, and the continuous efforts of all Eaton’s Cooper Power Systems employees involved in product design,
manufacture, marketing, and service.
We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around
high voltage lines and equipment, and support our “Safety For Life” mission.

Safety information
The instructions in this manual are not intended as a Safety instructions
substitute for proper training or adequate experience in the Following are general caution and warning statements that
safe operation of the equipment described. Only competent apply to this equipment. Additional statements, related to
technicians who are familiar with this equipment should specific tasks and procedures, are located throughout the
install, operate, and service it. manual.
A competent technician has these qualifications:
• Is thoroughly familiar with these instructions. DANGER
• Is trained in industry-accepted high and low-voltage safe Hazardous voltage. Contact with hazardous voltage
operating practices and procedures. will cause death or severe personal injury. Follow all
locally approved safety procedures when working
• Is trained and authorized to energize, de-energize, clear,
around high- and low-voltage lines and equipment.
and ground power distribution equipment.
G103.3

• Is trained in the care and use of protective equipment


such as arc flash clothing, safety glasses, face shield, hard
hat, rubber gloves, clampstick, hotstick, etc. WARNING
Following is important safety information. For safe Before installing, operating, maintaining, or testing
installation and operation of this equipment, be sure to read this equipment, carefully read and understand
and understand all cautions and warnings. the contents of this manual. Improper operation,
handling or maintenance can result in death, severe
personal injury, and equipment damage. G101.0

Hazard Statement Definitions


This manual may contain four types of hazard WARNING
statements:
This equipment is not intended to protect human
DANGER life. Follow all locally approved procedures and
safety practices when installing or operating this
Indicates an imminently hazardous situation which, if equipment. Failure to comply can result in death,
not avoided, will result in death or serious injury. severe personal injury and equipment damage. G102.1

WARNING WARNING
Indicates a potentially hazardous situation which, if Power distribution and transmission equipment must
not avoided, could result in death or serious injury. be properly selected for the intended application.
It must be installed and serviced by competent
CAUTION personnel who have been trained and understand
proper safety procedures. These instructions are
Indicates a potentially hazardous situation which, if written for such personnel and are not a substitute
not avoided, may result in minor or moderate injury. for adequate training and experience in safety
CAUTION: Indicates a potentially hazardous situation procedures. Failure to properly select, install or
which, if not avoided, may result in equipment maintain power distribution and transmission
damage only. equipment can result in death, severe personal
injury, and equipment damage. G122.3

iv GridAdvisor Series II smart sensor installation instructions S1150-20-1 June 2014 www.cooperpower.com
Introduction Installation procedures
The GridAdvisor™ Series II smart sensor helps utilities Installing SIM card
improve the efficiency in which they operate their
distribution systems by improving outage management,
capacitor bank maintenance and providing critical system
GSM cellular SIM card installation
information not previously available. This simple yet Smart sensors required to communicate over a GSM cellular
sophisticated product can annunciate directional fault network will require the proper Subscriber Identity Module
targeting, detect capacitor bank fuse failure and provide (SIM) card. A SIM card is a tiny chip that fits into the sensor
a DNP3 scannable line monitoring device at nearly any to provide the required network information for the sensor
location. The ProView™ NXG configuration software to properly connect to the cellular network. If the sensor
allows a single stocked item to be used for many different will be communicating using a CDMA network, no SIM
applications. The smart sensors meet or exceed IEEE card is required. AT&T® is one example of a cellular provider
Std 495™-2007 standard “Guide for Testing Faulted using a GSM network technology. Verizon® is an example of
Circuit Indicators” making them suitable for underground a cellular provider using CDMA technology.
applications. The GridAdvisor Series II smart sensor saves
Inside the battery compartment is a small slot for inserting
both operation and maintenance dollars by reducing drive
the SIM card on the inside wall (Figure 1). This slot is
time, and maximizes energy dollars by keeping capacitors
commonly referred to as a “push-push” receiver. Putting
online, operating at peak efficiency. Being hotstick installable
slight finger pressure on the card will cause it to snap into
with no additional hardware or back office software needed,
place. If inserted properly you will hear a click when the
this is the easiest way to gain SCADA visibility across the
SIM card is properly seated. Pushing the engaged SIM card
power distribution network.
again will cause it to slightly depress with a click and then
eject for removal. Putting SIM card into receiver with wrong
Read this manual first orientation and applying strong pressure may cause damage
to sensor and/or SIM Card, please review instructions for
Read and understand the contents of this manual and follow installation.
all locally approved procedures and safety practices before
installing or operating this equipment. 1. Remove sensor barrel cap to access battery
compartment. Take care not to lose the gasket located
on inside of cover.
Additional information
2. Locate SIM Card Slot on side wall inside sensor shown
These instructions cannot cover all details or variations in in Figure 1.
the equipment, procedures, or process described, nor to
provide directions for meeting every possible contingency 3. With metal strips of SIM card facing outside of barrel
during installation, operation, or maintenance. For additional and the chamfered edge of the SIM card facing
information, contact your Eaton’s Cooper Power Systems downward, push SIM card into place. SIM card should
representative. remain depressed and click into place if properly
installed.

Acceptance and initial inspection 4. Re-tighten cap from 17-22 in-lbs of torque to prevent
any water ingress.
Receiving Inspection In cases where a torque wrench is not available; tighten
the cap until the gasket inside the cap makes contact
Each sensor is in good condition when accepted by the
with the battery, turn another 1/2 turn to ensure proper
carrier for shipment. Upon receipt, inspect the shipping
tightening.
container for signs of damage. Unpack the sensor and
inspect it thoroughly for damage incurred during shipment.
If damage is discovered, file a claim with the carrier Shown with cap
immediately. removed
Battery Connector

Handling
Be careful during handling and storage of the sensor to
minimize the possibility of damage. If the sensor is to be
stored for any length of time prior to installation, provide a
clean, dry storage area.

Quality standards Battery Compartment


ISO 9001 certified quality management system

Figure 1.  Battery and SIM Card Locations

GridAdvisor Series II smart sensor installation instructions MN915001EN October 2014 www.cooperpower.com 1
Forcing over the air service provision (OTASP) Installing battery
(Verizon® only) 1. Remove sensor barrel cap to access battery
If the cellular provider being utilized with GridAdvisor Series compartment. Take care not to lose the gasket located
II smart sensor does not require use of a SIM card as is on inside of cover.
case with Verizon® CDMA network, the user must initiate 2. Locate battery inside sensor and battery connector on
an OTASP (over the air service provision). This specific side wall inside sensor shown in Figure 1.
action will cause the sensor to actively interrogate the
network for a proper IP address from which the device 3. Battery and sensor connectors are keyed to prevent
was activated. Failure to complete this step will result in misalignment. Press connectors together until they
communication failures generally visualized to customer as snap into locking position.
simultaneously red blinking LEDs.
4. Device will begin initialization and attempt cellular
1. Ensure that device is powered up and has completed activation.
initialization as indicated by double green blinking LEDs.
WARNING
2. Reed switch device by placing a strong earth metal
magnet next to the device as indicated by the symbol Leaving sensor activated without proper charging
“R” found on the rear side corner of the upper housing current source will lead to equipment (battery) damage.
opposite of LEDs. G101.0
3. Reed switch will initiate Bluetooth® discovery mode,
but in order for OTASP to complete the sensor must
not be paired with. After a two minute timeout, the 5. Re-tighten cap from 17-22 in-lbs of torque to prevent
sensor will connect to network and receive proper IP any water ingress.
address and preferred roaming list.
In cases where a torque wrench is not available; tighten
4. Alternatively, if the device is Bluetooth® paired and the cap until the gasket inside the cap makes contact
connected to ProView NXG software, the sensor will with the battery, turn another 1/2 turn to ensure proper
complete OTASP upon disconnect of ProView NXG tightening.
software.
5. OTASP may take up to five (5) minutes, with included
retries, so do not remove battery from device within
this time frame.
6. OTASP results can be confirmed in the sensor’s
communication logs with the ProView NXG software.
NNote: If the OTASP process fails and the sensor blinks red
LEDs continuously, check the communication log for
diagnostics. OTASP can fail if sensor is on roaming
network or has poor signal strength.

2 GridAdvisor Series II smart sensor installation instructions MN915001EN October 2014 www.cooperpower.com
Underground distribution circuits Method 2 (refer to Figure 3B)

Primary cable preparation 1. Attach one or two strands of the concentric neutral
wrapped around the cable to the tie-off tab on the elbow.
Proper primary cable preparation is necessary for the
GridAdvisor Series II smart sensor acting as a faulted 2. Terminate all of the remaining neutral wires
circuit indicator to work reliably on underground distribution just below the elbow. The balance of the neutral wires
circuits. The sensor can be used on concentric neutral, tape should be gathered together and “double backed”
shield, or drain wire cable. If the cable does not provide a down the cable and grounded.
return path for the fault current, the sensor can be installed
directly over the cable. If used on concentric neutral cable, NNote: The sensor is installed over the “double back”
or if the cable shield provides a return path for the fault neutral wires to cancel the effect of current in the
current, the sensor will not reliably detect a fault and will neutral. The exact trip value is dependent on the
require the use of a tape shield or drain wire adapter. When overall diameter of the “double back” neutral wires.
used, the adapter must be installed approximately 3.5”
Method 3 (refer to Figure 3C)
below the elbow to allow space for mounting the sensor on
the cable. 1. Attach one or two strands of the concentric neutral
wrapped around the cable to the tie-off tab on the
One of the following four methods is preferred for
elbow.
installation on concentric neutral primary cable:
2. Terminate and ground all of the remaining neutral wires
Method 1 (refer to Figure 3A)
approximately 6” below the elbow.
1. Attach one or two strands of the concentric neutral
Method 4 (refer to Figure 3D)
wrapped around the cable to the tie-off tab on the
elbow. 1. Arch one or two strands of the concentric neutral
wrapped around the cable and attach it to the tie-off tab
2. Terminate all of the remaining neutral wires
on the elbow. The arch should be large enough to go
approximately 6” below the elbow.
around the outside sensor when the sensor is installed.
3. Pull the neutral wires straight up and terminate them
In some installations, improper preparation of the primary
again just below the elbow. The wires should then be
cable will result in an inoperable sensor as a faulted circuit
bent back down the cable (commonly referred to as
indicator (FCI) (Figure 2). The magnetic field, due to current
“double back.”)
in the center conductor, will be cancelled by the current in
4. Terminate the ground wires approximately 6”below the the concentric neutral wires.
elbow.
IMPORTANT
NNote: The sensor is installed over the “double back”
neutral wires to cancel the effect of current in the Do not place the fault indicator as shown in Figure 2. Doing
neutral. The exact trip value is dependent on the so will prevent the sensor from working properly.
overall diameter of the “double back” neutral wires.

ELBOW
TIE-OFF
TAB

ELBOW

TERMINATED
NEUTRAL
LOCATE WIRES
THE SENSOR
PORTION OF
THE FAULTED
CIRCUIT
INDICATOR
(in the outlined
area)

NEUTRAL
WIRES
A B C D
c d
A B

Figure 2.  Incorrect methods of concentric Figure 3.  Recommended methods of concentric neutral primary cable
neutral primary cable preparation preparation

GridAdvisor Series II smart sensor installation instructions MN915001EN October 2014 www.cooperpower.com 3
. 9 60 15.2/26.3 kV
0-
200 A

IN
. 83
LE225
D LOADBREAK

21.

m
08
-24.38

m
. 9 60 15.2/26.3 kV
. 9 60 0-
0- 15.2/26.3 kV 200 A

IN
. 83
200 A
IN
. 83

LE225
LE225 D LOADBREAK

21.
LOADBREAK

m
D 08
21.

-24.38
m

08

m
-24.38
m

Figure 4.  Proper installation of smart sensor on prepared conductor is shown in Figures A (left) and B (middle).
Figure C (right) shows the incorrect placement for installation.

Installation of smart sensor - underground application


1. Arm the sensor clamping mechanism by carefully
grasping both clamping arms, pulling them apart until
the trigger mechanism drops into place. Stops have
been built into the clamping arms such that they can
only be opened to the point where the trigger will latch
(Figure 5).
2. For applications where the cable diameter is less than
1”, leave the clamp pads attached to the clamp arms.
On installations where the cable diameter exceeds 1”,
remove the pads that are attached to each clamping
arm. Removing the pads will allow the clamping
mechanism to properly attach to larger diameter cables
(Figure 6).
3. Attach the sensor to a hotstick using the pulling eye.
4. Push the sensor onto the cable below the elbow at a
location shown in Figure 3 while holding the hotstick Figure 5.  Smart Sensor clamping arms in the latched
horizontal. The triggering mechanism will release the position.
clamping arms and securely attach the device to the cable.

NNote: Only the closed core current transformer (CT) need


be applied over the region of the cable where the
concentric neutral has been removed or double-
backed (Figure 5).
• For installation on tape shield cable, the closed-core CT
of the sensor should be placed above the location on the
cable where the tape shield has been removed or trained
back as part of the cable termination. Location of the
sensor must be similar to Figure 2 (C or D), or Figure 4 (A
or B), for proper operation of the sensor as an FCI.
5. Remove the hotstick. Figure 6.  Remove clamp pads attached to each
clamping arm on a mechanism where cable diameter
exceeds 1”.

4 GridAdvisor Series II smart sensor installation instructions MN915001EN October 2014 www.cooperpower.com
2. For applications where the cable diameter is less than
1”, leave the clamp pads attached to the clamp arms.
On installations where the cable diameter exceeds 1”,
remove the pads that are attached to each clamping
arm. Removing the pads will allow the clamping
mechanism to properly attach to larger diameter cables
Load LED (Figure 4, Figure 6).
3. Attach the sensor to a hotstick using the pulling eye.
4. Push the sensor onto the cable conductor. Ensure
that the CT is around the conductor and good contact
is made between the ends of the CT. The triggering
mechanism will release the clamping arms from the
latched position, to securely attach the device to the
cable.
Source LED

Sensor display operation


The GridAdvisor Series II smart sensor has two multicolor
Figure 7.  Smart Sensor LED designations. light emitting diodes (LEDs) used for annunciating functional
tasks and the status of the smart sensor. Each LED will be
NNote: On 200 A loadbreak elbows, the preferred installation referred to as Source and Load LED in the context of the
is demonstrated in Figure 4 (A), where the closed labels found on sensor per Figure 7.
core CT is located directly below the test point.

Device activation
Installation of smart sensor - overhead application The LEDs provided on the GridAdvisor Series II smart
sensor provide annunciation during the activation process of
IMPORTANT the sensor onto the cellular network at time the battery is
installed.
Install the sensor a minimum of ten (10) feet from any
structure on the conductor including any poles.

1. Arm the FCI clamping mechanism by carefully grasping


both clamping arms, pulling them apart until the trigger
mechanism drops into place. Stops have been built into
the clamping arms such that they can only be opened
to the point where the trigger will latch (Figure 5).

Table 1.  LED Annunciation During Cellular Activation


Sequence step (in order) Source LED Load LED
Initialization A single pulse green LED. A single pulse green LED.
Bluetooth® and cellular modules are unavailable Bluetooth® and cellular modules are unavailable
and device will not respond to reed switch. and device will not respond to reed switch.
Initialization Failure LED will blink red continuously. LED will blink red continuously.
Contact Factory for assistance after attempting Contact Factory for assistance after attempting
to force an OTASP or inserting a new SIM card. to force an OTASP or inserting a new SIM card.
Initialization Complete A double pulse green LED. A double pulse green LED.
Bluetooth® module is available for Bluetooth® module is available for
programming sensor by reed switching device. programming sensor by reed switching device.
Successful Cellular Three yellow LED flashes in succession ten Three yellow LED flashes in succession ten
Activation times. times.
Indicates sensor has received IP address from Indicates sensor has received IP address from
network network
Failed Cellular Activation Three (3) red LED flashes in succession ten Three (3) red LED flashes in succession ten
(10) times. (10) times.
Contact utility network administrator to verify Contact utility network administrator to verify
proper configuration of cellular account. proper configuration of cellular account.

GridAdvisor Series II smart sensor installation instructions MN915001EN October 2014 www.cooperpower.com 5
LED installation indication
The LEDs provided on the GridAdvisor Series II smart
sensor provide annunciation during the installation of device
to verify proper load current is present.

Table 2.  GridAdvisor Series II Smart Sensor LEDs Provided


Sequence Step (in order) Source LED Load LED
Current present below 10 Amps RED Moving Bar Sequence for Direction RED Moving Bar Sequence for Direction
Current present below 50 Amps AMBER Moving Bar Sequence for Direction AMBER Moving Bar Sequence for Direction
Current present above 50 Amps Green Moving Bar Sequence for Direction Green Moving Bar Sequence for Direction

Programming sensor
Please refer to Programming Guide S1150-20-2 for
instructions on connecting to sensor with Bluetooth®
module and/or programming device with ProView NXG
software.

Support
Eaton’s Cooper Power Systems is proud to offer a
comprehensive collection of support resources for users
requiring additional information or assistance in the setup,
operation, and troubleshooting of GridAdvisor Series II
smart sensor and other equipment from Eaton’s Cooper
Power Systems.

6 GridAdvisor Series II smart sensor installation instructions MN915001EN October 2014 www.cooperpower.com
Appendix A: regulatory information Important battery information
• Do not disassemble or open crush, bend or deform,
puncture or shred
Compliance information • Do not modify or remanufacture, attempt to insert foreign
GridAdvisor objects into the battery, immerse or expose to water or
other liquids, expose to fire, explosion or other hazard.
Model: GCVT3G
Contains FCCID: QIPPXS8 and QOQWT12
• Only use the battery for the system for which it is
specified
Contains IC: 7830A-PXS8 and 5123A-BGTWT12A
• Only use the battery with a charging system that has
Federal Communications Commission (FCC): been qualified with the system per this standard. Use of
an unqualified battery or charger may present a risk of
NNote: This equipment has been tested and found to comply fire, explosion, leakage, or other hazard.
with the limits for a Class B digital device, pursuant
to Part 15 and 24 of the FCC rules. These limits are • Do not short circuit a battery or allow metallic conductive
designed to provide reasonable protection against objects to contact battery terminals.
harmful interference in a residential installation. This • Replace the battery only with another battery that has
equipment generates, uses, and can radiate radio been qualified with the system per this standard, IEEE
frequency energy and, if not installed and used in Std 1725™-2006 standard. Use of an unqualified battery
accordance with the instructions, may cause harmful may present a risk of fire, explosion, leakage or other
interference to radio communications. However, hazard.
there is no guarantee that interference will not occur
in a particular installation. If this equipment does • Promptly dispose of used batteries in accordance with
cause harmful interference to radio or television local regulations
reception, which can be determined by turning the • Battery usage by children should be supervised.
equipment off and on, the user is encouraged to try
to correct the interference by one or more of the • Avoid dropping the phone or battery. If the phone or
following measures: battery is dropped, especially on a hard surface, and the
user suspects damage, take it to a service center for
• Reorient or relocate the receiving antenna. inspection.
• Increase the separation between the equipment and • Improper battery use may result in a fire, explosion or
receiver. other hazard.
• Connect the equipment into an outlet or circuit different
from that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician
for help.

Industry Canada:
This Class B digital apparatus meets all requirements of
the Canadian Interference Causing Equipment Regulations.
Operation is subject to the following two conditions: (1)
this device may not cause harmful interference, and (2) this
device must accept any interference received, including
interference that may cause undesired operation.

Radio frequency (RF) exposure:


In accordance with FCC requirements of human exposure
to radio frequency fields, the radiating element shall be
installed such that a minimum separation distance of 20 cm
is maintained.

GridAdvisor Series II smart sensor installation instructions MN915001EN October 2014 www.cooperpower.com 7
SAFETY
!
FOR LIFE

Eaton, Cooper Power Systems,


Eaton GridAdvisor and ProView are valuable
1000 Eaton Boulevard trademarks of Eaton, in the U.S. and other
Cleveland, OH 44122 countries. You are not permitted to use
United States these trademarks without the prior
Eaton.com written consent of Eaton.
IEEE Std 495™-2007 and IEEE Std
Eaton’s Cooper Power Systems 1725™-2006 standards are trademarks of
Business the Institute of Electrical and Electronics
2300 Badger Drive Engineers, Inc., (IEEE). This publication/
Waukesha, WI 53188 product is not endorsed or approved by For Eaton’s Cooper Power
Cooperpower.com the IEEE. Systems GridAdvisor
Bluetooth© is a registered trademark of
© 2014 Eaton Bluetooth SIG, Inc. Series II smart sensor
All Rights Reserved AT&T® is registered trademark of AT&T product information call
Printed in USA Intellectual Property.
Publication No. MN915001EN October 2014 Verizon® is a registered trademark of
1-877-277-4636 or visit:
(Supersedes S1150-20-1 / June 2014) Verizon Wireless. www.cooperpower.com.

Potrebbero piacerti anche