ECON-4

Order code: ECON-4

Digital Speed Governor


Datasheet
Product description
Stand-alone digital speed governor for gas gen- PWM signal, 12 - 32 V, 0 - 6000 Hz
sets 0-5V
0 - 20 mA
Key features
Wide range of supported actuators within one Example of supported
hardware
actuators
Precise throttle position control, with optional
Heinzmann actuators – STG6, STG10, STG30,
position feedback utilization
STG2010, STG2040, etc.
Different modes of control – over Binary signals,
Woodward actuators – ITB PWM, ITB 0-200mA,
over Analogue signals, over CAN line (with
specific ComAp controllers and firmwares) F-series, etc.

Load dependent PID adjustment possibility for GAC actuators – ATB552, etc.

variable load applications (e.g. Oil&Gas


Certifications and standards
industry)
This product is CE compliant.
Droop operation function
EN 60068-2-6 ed.2:2008
Overspeed protection
EN 60068-2-27
Configurable with ComAp PC tool (WinScope) ed.2:2010

Data Interface with InteliSys Gas controller over EN 60068-2-30, May


2000
CAN line
EN 60068-2-64

Supported interface to EN 61010-1:2003

All certificates and standards are available on:


actuators https://webstore.iec.ch/publication/4243

0 - 200 mA
0 - 8 A continuous, 10 A peak

|ECON-4 Datasheet |Related HW ver: 1.0.0 |Related SW ver: 1.0.0 |Date of issue: 8.2.2016 1
Technical data
Power supply Speed pick-up inputs
Power supply range 12-36 V DC Active or magnetic pick-up
0,5 – 10 A, depends on Type of sensor (connection by shielded cable

Consumption supply voltage and used is strongly recommended)


actuator Minimum input
2 Vpk-pk (from 4 Hz to 4 kHz)
voltage
Operating conditions Maximum input
50 Veff
Operating voltage
- 30 to +70 ˚C
temperature Minimum measured
4 Hz
Storage frequency
-30 to +80˚C
temperature Maximum measured 10 kHz (min. input voltage
Humidity 95% without condensation frequency 6Vpk-pk)

Low voltage Frequency


EN 61010-1:95 +A1:97
directive measurement 0,2 %
tolerance
Electromagnetic EN 50081-1:94, EN 50081-2:96
compatibility EN 50082-1:99, EN 50082-2:97
CAN bus interface
5 - 25 Hz, ± 1,6mm 25 - 100 Hz, a =
Vibrations 200 m galvanically
4g Maximal CAN bus length
separated
Shocks a = 200 m/s2
Speed 250 kBd
Binary inputs Nominal impedance 120 Ω

Number 8 Cable type twisted pair (shielded)

Input resistance 4.4 kΩ


General information
Input range 0 - 36 V DC
Weight 600 g
Switching voltage level
for close contact 0 -2 V Protection IP20

indication
Max voltage level for Dimensions, terminals and
8 - 36 V
open contact indication
mounting
Analog inputs
2 non electrically
Number
separated

Resolution 10 bits
0 - 10 V; input resistance
11 kΩ
Range
0 - 20 mA; load resistor 50

Analog measurement
1%
tolerance

Actuator feedback input


Resolution 10 bits non electrically separated

RS232 interface
Note: The unit is mounted on DIN rail (35
Maximal distance 10 m mm/1.38 in).
Speed 19 200 bps

Manufacturer:
ComAp a.s. Fax: +420 266 316 647
Czech Republic E-mail: info@comap.cz
Phone: +420 246 012 111 Internet: www.comap.cz

ECON-4 Datasheet 2