4010ES IDNAC Main Board


Terminal Block Description
Provides 2 fault isolated loops of IDNet +.
TB1 IDNet Connections
TB1 (1-4) Loop A, TB1 (5-8) Loop B
Each IDNAC circuit has a 4 position terminal block.
TB2 IDNAC Connections
TB2 (1-4) IDNAC 1,TB2 (5-8) IDNAC 2
Provides 2 positions for wiring the aux power and
TB3 Aux/Simple NAC
reverse polarity supervision circuit

TB3
A 32V, 2A relay is provided with
TB4 Relay
both NO and NC contacts

LED Name

TB4
LED 1 IDNet Negative Earth Fault

LEDs 1-6
LED 2 IDNet Positive Earth Fault
LED 3 IDNet Trouble
LED 4 IDNet Com
LED 5 IDNet Loop A Trouble
LED 6 IDNet Loop B Trouble
LED 7 IDNAC 1 Trouble

LEDs 7-15
LED 8 IDNAC 2 Trouble
LED 9 AC
LED 10 Comm Loss
LED 11 E ESS debug LED
LED 12 D ESS debug LED
LED 13 C ESS debug LED
LED 14 B ESS debug LED
LED 15 A ESS debug LED
P2 P3 P4
LED15 LED14 LED13 LED12 LED11 Debug LED P13
A B C D E Description
OFF OFF OFF OFF OFF No Trouble: There are no troubles detected on the ESS.
ON OFF OFF OFF OFF AC Fail: The AC power is disconnected, but the battery is working. P9
OFF ON OFF OFF OFF Low Battery: The battery is under 22V.
P19 SW1
ON ON OFF OFF OFF Battery Cutout: The Battery charge is below 20V. At this point, if Jumper P19
is set to “battery disconnect when depleted” the system shuts down. P18
P7
Depleted/Missing Battery: If jumper P19 is not set to “battery disconnect
OFF OFF ON OFF OFF when depleted”, this trouble appears when the battery charge is below
20V. This code also appears if the system cannot detect the battery.
ON OFF ON OFF OFF Charger Trouble: There is a trouble with the battery charger.
OFF ON ON OFF OFF Card Overcurrent: The module is drawing too much current.
ON ON ON OFF OFF Negative Earth: The circuit is shorted to ground on the negative wire. P Connectors Description
OFF OFF OFF ON OFF Positive Earth: The circuit is shorted to ground on the positive wire. and Switch
City Circuit 1 Trouble: The trouble configured on the City Card’s P2 IDNet 4100 Comms Enable
ON OFF OFF ON OFF
Circuit 1 has been triggered.
P3 and P4 Jumpers select IDNet Class A/B
City Circuit 2 Trouble: The trouble configured on the City Card’s
OFF ON OFF ON OFF P7 City/Relay Card, A 10 position connector is provided for the ribbon harness that goes to a City Card or Relay Card
Circuit 2 has been triggered.
AuxNAC Open: Depending on the chosen configuration,
P9 Positive battery connection
ON ON OFF ON OFF P11 Connection plug for an optional Dual Class A Isolator (DCAI) card
either the Aux circuit or the NAC Circuit is open.
AuxNAC Short: Depending on the chosen configuration, P13 Negative battery connection
OFF OFF ON ON OFF Disables 4100 Communications with the power supply and IDNAC functions
either the Aux circuit or the NAC Circuit is experiencing a short circuit. P18
AuxNAC Overcurrent: Depending on the chosen configuration, P19 Battery Disconnect (Canadian Operation Jumper)
ON OFF ON ON OFF
either the Aux circuit or the NAC circuit is drawing too much current. SW1 Scroll Switch if multiple troubles
4010ES IDNAC CPU Card

LEDs 1-3
TB1
LEDs 5 & 6
SW1 LED 4 P3 SW3 LEDs 7-10 U5 BT1 P8 P5 P9 P10 P11 R23 P1 P2 J7

Switches LEDs Terminal connections


Reset – Momentarily pressing this switch (<2 seconds) generates a Warm Start. 1 ON when a RUI Class A fault (open circuit) or a short
SW1 If the CPU is not responding to the reset, the user can press and hold the switch 2 ON when a RUI Short circuit on the Primary B terminals TB1 Internal RUI Harness
for three seconds causing a Warm Start based on the hardware switch. 3 ON when a RUI Short circuit on the Secondary A terminals RUI A- Black Wire
SW3 Cold Start – Clears Disables, Manual Overrides, and Logs ON when CPU is in reset, flashing when unable to reset, and OFF when the RUI A+ Red Wire
4 Shield Green Wire
P Connectors CPU is running normally
5 Ethernet Activity Status LED, cable is connected Shield
P1 Enables/Disables the RUI circuit
6 Ethernet Linked Status LED, flashes Ethernet activity RUI B- Brown Wire
Connects the RUI shield to earth. For jobs experiencing crosstalk issues,
P2 7 Boot Loader Status A flashes once a second to show the CPU is processing RUI B+ White Wire
changing this jumper connects the shield to 24C.
8 Boot Loader Status B flashes once per polling cycle
P3 Compact Flash connection R23 LCD Contrast Adjust
9 Boot Loader Status C not intended for field use
P5 Ram Battery ON enabled/OFF disabled BT1 Ram Battery – Powers RAM
10 Boot Loader Status D not intended for field use
P8 Keypad Membrane connector memory to save history
P9 & 24V Card Power and Internal Communications. Locking tabs are located UP, on the logs if AC power is lost
P10 top of the connectors. J Connectors U5 Contains the MAC address for
Serial Service Port – for connection to remote services or can be used if Ethernet Service Port – RJ45 connector used to transfer files to or upload reports from the the Ethernet connector and
P11 J7
the Ethernet port is not available. 4010ES IDNAC using the Ethernet port on your laptop. a unique Serial Number.

International Trade Controls and Restrictions


This material may contain information or technology the export or re-export of which is restricted by U.S. laws and regulations. By viewing this material, the recipient agrees to the following: (i) the recipient's use of the contents of this material shall comply with all applicable laws, rules and regulations, including, without limitation,
U.S. international trade laws and regulations, and (ii) the recipient may not transfer or otherwise export or re-export any information or technology contained in this material except in full compliance with the export controls administered by the U.S. and other countries and any applicable import and use restrictions. © 2015 Tyco Fire Protection Products, All Rights Reserved. Rev. A