Sei sulla pagina 1di 7

SAUDI ARAMCO ID/PIEU - 14- May 2018 - REV. 2018.03.00 (Standards Cutoff -March 31, 2018) Rev. 2018.03.

Rev. 2018.03.00 31-Mar-18


SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
Instrument Loop Outputs - Relay / Contactor / Transducer
SATR-J-6510 14-May-18 INST
Operation and Trip Test
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED TEST DATE & TIME ACTUAL TEST DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
TEST PROCEDURE ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.

A Dual Transducer Test Meter (Flow and Pressure)


Here we have discussed System Studies Transducer Test Meter
A1 (P/N9800-3600). Similar instructions are supplied with other product Vendor manual
to be followed.

It is also important to make sure the meter is zero adjusted before


A2 Vendor manual
taking readings and the battery does not show low battery indication

A3 Flow and pressure measurements must be made separately. Vendor manual

How to Test 4 to 20mA Monitoring Devices Using the Transducer Test Meter
1. Connect the meter’s red and black leads to the monitoring pair of
the device being measured. It is not important which leads are
A4 Vendor manual
connected to which conductor - unless you are testing devices on a
Selector Pair Saver™ device circuit

2. Evaluate the reading as indicated on the pressure or flow scale of


A5 the meter. For readings in the OPEN, 0, and SHORT scale regions, Vendor manual
see “Off-scale Readings.” [Attachment 1]

For pressure transducer output, use the values listed below the
curved scale on the gauge face. Reading increments are 0, 10, 20
and 30 PSI. Transducer output that falls between two indicated PSI
A6 values is estimated (Figure 3). Flow readings (numbers on top of Vendor manual
scale) are read as a fraction of the flow range listed on the Flow
Finder to which the transducer is connected. Flow Finder ranges are
0–95, 0–47.5, 0–19 and 0–9.5 SCFH.

A reading of “FS” (Full Scale), when testing a flow transducer


connected across a 47.5 SCFH Flow Finder, indicates a measured
flow of 47.5 SCFH; a scale reading of “1/2” indicates a flow of 23.75
A7 SCFH (0.5 X 47.5). System Studies’ monitoring devices are also Vendor manual
capable of reading up to twice the rated Flow Finder range. The
Transducer Test Meter will indicate extended ranges as either “1.5 X
FS ” or “2 X FS.”

Testing Selector Pair Saver Installations: System Studies’ Selector


A8 Pair Saver device (P/N 4990) makes it possible to read and monitor Vendor manual
two 4 to 20 mA transducers using only one device pair.

Procedures for testing both transducers at the Selector Pair Saver


A9 Vendor manual
are as follows: (A10 to A12)

1. Connect the meter’s red (positive) lead to the white (tip) conductor
Schedule Q
A10 of the Selector Pair Saver’s outgoing blue/white pair. Connect the
Att. IV
black (negative) lead to the blue (ring) conductor (Figure 4).

Saudi Aramco: Company General Use


2. To test the first transducer (the one connected to the orange/white
pair), move the polarity switch (bottom-right switch) to the “Device #1” Schedule Q
A11
(DOWN) position. To test the second transducer (green/white pair), Att. IV
move the switch to the “Device #2” (UP) position

Saudi Aramco: Company General Use


SAUDI ARAMCO ID/PIEU - 14- May 2018 - REV. 2018.03.00 (Standards Cutoff -March 31, 2018) Rev. 2018.03.00 31-Mar-18
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
Instrument Loop Outputs - Relay / Contactor / Transducer
SATR-J-6510 14-May-18 INST
Operation and Trip Test
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.

3. Readings are evaluated as described in Step 2 of the Transducer Schedule Q


A12
Test Procedure (A4) Att. IV

Off-Scale Readings: “OPEN” Reading. OPEN readings indicate that


insufficient current is flowing in the device loop. Using the previous
test procedures as a reference, verify that the connections to both the Schedule Q
A13
meter and the device are correct. Also check to see that the battery is Att. IV
functioning properly. If all external connections are good, an OPEN
reading means the monitoring device could be faulty.

“0” Reading. A meter reading of 0 indicates a flow of zero, or


atmospheric pressure (0 PSIG). A properly functioning device with Schedule Q
A14
both pneumatic inputs disconnected (vented to atmosphere) will read Att. IV
in this region.

“SHORT” Reading. A SHORT reading indicates an over (excessive)


current condition in the device. If the meter reads SHORT, verify that Schedule Q
A15
the test meter or pair leads are not touching each other. If they are Att. IV
not, the device could be faulty.

Other Readings: A meter reading in the uncolored region between OPEN and 0 indicates one of the following conditions.
a) If both pneumatic inputs of the device are open to atmosphere, a reading on the left side of this region indicates a possible failed
device.
b) A reading toward the right of this region could indicate that the transducer has a low zero calibration. Low zero calibration can be
verified by placing a pressure transducer under pressure or creating a flow across a flow transducer (at the Flow Finder). If the reading
A16
increases, the transducer is functional but must be recalibrated.
c) If the device is connected to a Flow Finder in a pressurized system, a reading to the left side of the uncolored region can indicate a
reverse flow. Check the Flow Finder pneumatic connections to the transducer for proper orientation. This type of reading could also be
caused by cable pressure that is higher than air pipe pressure. Although this is rare, it is possible in an air-tight system. Test the
transducer with both pneumatic input ports vented to atmosphere to check for this condition

Testing the Battery


The Battery Test button and LED indicator on the front cover of the unit are used to verify that the battery charge is sufficient for proper
test meter operation. Simply press the button (with power on or off) to check the battery. If the LED illuminates, the battery charge is
A17
acceptable. Replace the batteries if it does not light (see replacement procedures below).
Note: The battery test is independent of the operating mode of the meter. It neither affects the readings, nor is it affected by being
connected to a transducer.

Zero Adjusting the Meter:


To verify that the meter is properly zeroed, turn the power switch on. If necessary, using a flat-blade screwdriver, turn the zero-adjust
A18 screw located on the gauge face in either direction until the meter’s needle lines up with the “meter zero” line. Because the meter is
slightly position sensitive, it is recommended that you both zero adjust and take readings holding the meter in the same orientation
(either vertical or horizontal).

B Test Equipment Serial Numbers: (a) Digital Multimeter

C General Test Routines


C1 Manufacturer's test routines to be followed and calibrations to be confirmed within tolerance limits

D Test Procedures

Saudi Aramco: Company General Use


SAUDI ARAMCO ID/PIEU - 14- May 2018 - REV. 2018.03.00 (Standards Cutoff -March 31, 2018) Rev. 2018.03.00 31-Mar-18
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
Instrument Loop Outputs - Relay / Contactor / Transducer
SATR-J-6510 14-May-18 INST
Operation and Trip Test
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.

1. Confirm the instrument tag of Relay/contactor/Transducer and that the devices are physically installed as per P & ID and wiring
drawing.
2. Verify proper wiring polarity and that the device is connected to the signal wiring.
3. Verify that the input or output signal is within the device's normal operating range.
4. Measure loop impedance by disconnecting the signal wiring at both the transmitter and rack room ends, shorting the signal wiring at
D1
the transmitter and measuring the loop resistance with an ohmmeter at the termination panel end.
5. With an ohmmeter, verify that there are no shorts to ground in the signal wiring by checking the wiring to ground while the wiring is
still disconnected.
6. Connect the device at the field location and have second technician in the rack room verify the status indication at DCS .
7. Reconnect the wiring to the in the field and the rack room.

E Results (The Table to be Modified Based on Requirements)


ITEM
PASS FAIL N/A RE-INSP DATE
No.
Measured Actual
% span Input Error
output output

0%
25%
50%
75%
100%
75%
25%
0%
F Conclusions

G Loop Continuity Check Sheet (Pre-Loop Check)


Unit No. System No. Loop No. Loop Drawing No
From To Checks per Section Name-sign/
Remarks and
Tag / Item no Area Cable Number Tag no Area Continuity Test Termination Date

Saudi Aramco: Company General Use


SAUDI ARAMCO ID/PIEU - 14- May 2018 - REV. 2018.03.00 (Standards Cutoff -March 31, 2018) Rev. 2018.03.00 31-Mar-18
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
Instrument Loop Outputs - Relay / Contactor / Transducer
SATR-J-6510 14-May-18 INST
Operation and Trip Test
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.

REMARKS:

REFERENCE DOCUMENTS:
1. Schedule G - Material, Tools and Equipment (Pro Forma MP-IK-LS Contract), March 2006
2. Schedule Q - Quality Requirements (Pro Forma Contract), February 2008
3. SAES-J-700 - Control Valves, 1 January 2018
4. SAEP-16 - Project Execution Guide for Process Automation Systems, 14 March 2017
5. SAEP-1636 - Installation and Checkout Plan, 16 October 2017
6. SAEP-750- Testing Procedures for Process Automation Systems (PAS), 14 November 2016
7. 34-SAMSS-711 - Control Valves - General Services, 12 October 2017
8. 34-SAMSS-718 - Electric Motor Operated Valve Actuators, 12 February 2015
ATTACHMENTS:
1. Attachment 1: Transducer Test Meter - System Studies High Resolution Transducer

NOTES:
1. Approved - Acceptable to the authority having jurisdiction (i.e., Saudi Aramco ID).
2. Identified - Recognizable as suitable for the specific application by a qualified testing laboratory (i.e., listing and/or labeling).

3. Listed - Equipment and materials included in a list published by an approved qualified organization concerned with evaluation of products
or services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose
listing states that the equipment, material or services either meets appropriate designated standards or has been tested and found suitable for
a specified purpose.

4. Labeled - Equipment or materials to which has been attached a label, symbol or other identifying mark of an approved qualified
organization concerned with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by
whose labeling the manufacturer indicates compliance with appropriate standards or performance in a specified manner.
5. Remarks:

Contractor / Third-Party Saudi Aramco


Technician Performing Test* PMT Representative
Name, Title, Department, Test Performed Successfully and Results are Acceptable: T&I Witnessed QC Record Reviewed Work Verified
Company, Initials and Name, Initials and Date:
Date:
QC Inspector PID Representative
Witnessed Test Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Supervisor Proponent and Others


Quality Record Approved: T&I Witnessed QC Record Reviewed Work Verified
Name, Organization,
Name, Sign and Date:
Initials and Date:

*Person Responsible for Implementation of Test and Analysis of Results Y = YES N = NO F = FAILED

Saudi Aramco: Company General Use


SAUDI ARAMCO ID/PIEU - 14- May 2018 - REV. 2018.03.00 (Standards Cutoff -March 31, 2018) Rev. 2018.03.00 31-Mar-18
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
Instrument Loop Outputs - Relay / Contactor / Transducer
SATR-J-6510 14-May-18 INST
Operation and Trip Test
Attachment 1: Transducer Test Meter - System Studies High Resolution Transducer

Saudi Aramco: Company General Use


Saudi Aramco: Company General Use

Potrebbero piacerti anche