Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED TEST DATE & TIME ACTUAL TEST DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
TEST PROCEDURE ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.
How to Test 4 to 20mA Monitoring Devices Using the Transducer Test Meter
1. Connect the meter’s red and black leads to the monitoring pair of
the device being measured. It is not important which leads are
A4 Vendor manual
connected to which conductor - unless you are testing devices on a
Selector Pair Saver™ device circuit
For pressure transducer output, use the values listed below the
curved scale on the gauge face. Reading increments are 0, 10, 20
and 30 PSI. Transducer output that falls between two indicated PSI
A6 values is estimated (Figure 3). Flow readings (numbers on top of Vendor manual
scale) are read as a fraction of the flow range listed on the Flow
Finder to which the transducer is connected. Flow Finder ranges are
0–95, 0–47.5, 0–19 and 0–9.5 SCFH.
1. Connect the meter’s red (positive) lead to the white (tip) conductor
Schedule Q
A10 of the Selector Pair Saver’s outgoing blue/white pair. Connect the
Att. IV
black (negative) lead to the blue (ring) conductor (Figure 4).
ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.
Other Readings: A meter reading in the uncolored region between OPEN and 0 indicates one of the following conditions.
a) If both pneumatic inputs of the device are open to atmosphere, a reading on the left side of this region indicates a possible failed
device.
b) A reading toward the right of this region could indicate that the transducer has a low zero calibration. Low zero calibration can be
verified by placing a pressure transducer under pressure or creating a flow across a flow transducer (at the Flow Finder). If the reading
A16
increases, the transducer is functional but must be recalibrated.
c) If the device is connected to a Flow Finder in a pressurized system, a reading to the left side of the uncolored region can indicate a
reverse flow. Check the Flow Finder pneumatic connections to the transducer for proper orientation. This type of reading could also be
caused by cable pressure that is higher than air pipe pressure. Although this is rare, it is possible in an air-tight system. Test the
transducer with both pneumatic input ports vented to atmosphere to check for this condition
D Test Procedures
ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.
1. Confirm the instrument tag of Relay/contactor/Transducer and that the devices are physically installed as per P & ID and wiring
drawing.
2. Verify proper wiring polarity and that the device is connected to the signal wiring.
3. Verify that the input or output signal is within the device's normal operating range.
4. Measure loop impedance by disconnecting the signal wiring at both the transmitter and rack room ends, shorting the signal wiring at
D1
the transmitter and measuring the loop resistance with an ohmmeter at the termination panel end.
5. With an ohmmeter, verify that there are no shorts to ground in the signal wiring by checking the wiring to ground while the wiring is
still disconnected.
6. Connect the device at the field location and have second technician in the rack room verify the status indication at DCS .
7. Reconnect the wiring to the in the field and the rack room.
0%
25%
50%
75%
100%
75%
25%
0%
F Conclusions
ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.
REMARKS:
REFERENCE DOCUMENTS:
1. Schedule G - Material, Tools and Equipment (Pro Forma MP-IK-LS Contract), March 2006
2. Schedule Q - Quality Requirements (Pro Forma Contract), February 2008
3. SAES-J-700 - Control Valves, 1 January 2018
4. SAEP-16 - Project Execution Guide for Process Automation Systems, 14 March 2017
5. SAEP-1636 - Installation and Checkout Plan, 16 October 2017
6. SAEP-750- Testing Procedures for Process Automation Systems (PAS), 14 November 2016
7. 34-SAMSS-711 - Control Valves - General Services, 12 October 2017
8. 34-SAMSS-718 - Electric Motor Operated Valve Actuators, 12 February 2015
ATTACHMENTS:
1. Attachment 1: Transducer Test Meter - System Studies High Resolution Transducer
NOTES:
1. Approved - Acceptable to the authority having jurisdiction (i.e., Saudi Aramco ID).
2. Identified - Recognizable as suitable for the specific application by a qualified testing laboratory (i.e., listing and/or labeling).
3. Listed - Equipment and materials included in a list published by an approved qualified organization concerned with evaluation of products
or services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose
listing states that the equipment, material or services either meets appropriate designated standards or has been tested and found suitable for
a specified purpose.
4. Labeled - Equipment or materials to which has been attached a label, symbol or other identifying mark of an approved qualified
organization concerned with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by
whose labeling the manufacturer indicates compliance with appropriate standards or performance in a specified manner.
5. Remarks:
*Person Responsible for Implementation of Test and Analysis of Results Y = YES N = NO F = FAILED