Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
1. GENERAL
STORAGE BATTERIES
1.1 DEFINITION OF ELECTRICITY
1
10/20/18
2
10/20/18
3
10/20/18
Appliance Circuit
A branch circuit that supplies
current in one or more outlets
specifically intended for
appliances
C3
C3
KIT
20 amp
minimum of 2 - 20 amperes
Range
C2
small appliance outlets in the kitchen, amp circuit loads and on 15 and 20
pantry, dining and family room. amp overcurrent devices respectively.
4
10/20/18
2.2 SINGLE PHASE ELECTRICAL SYSTEMS 2.2 THREE PHASE ELECTRICAL SYSTEMS
For homes and small commercial buildings For industries and large commercial buildings
The Three Phase AC electricity is a Triple
A single phase electrical system can Circuit. The lighting and outlet loads are
either be 2-wire or 3-wire and connected between any phase leg and a
B C
composes two hot legs and a neutral A neutral line. While machineries and other
wire. bigger loads are connected to the phase leg
SWITCH FUSE
A
only.
Three-Wire Three Phase AC
B A-B 220V A-C 220V
MOTOR
110 V
Three-Wire Single Phase DC
(EDISON SYSTEM) Four-Wire Three-Phase AC
220 V
A N B C
Service
The supplying of utilities required
or demanded by the public
Substation
An auxiliary power station
where electrical current is
converted or where voltage
is stepped up or down
Line Drop
The decrease in voltage between
two points on a power line,
usually caused by resistance or Lightning Rod
leakage along the line Any of several conducting rods installed at the
top of a structure and grounded to divert
Service Entrance Conductor Service Drop
lightning away from the structure. Also called air
The portion of a service conductor extending The overhead portion of service terminal
from a service drop or service lateral to the conductors extending from the
service equipment of a building nearest utility pole to a building Lightning Arrester
Watt-Hour Meter
Service Lateral A device for protecting electric equipment from
The underground portion of service damage by lightning or other high-voltage
A meter for measuring and recording the
conductors extending from a main
quantity of electric power consumed with currents, using spark gaps to carry the current
power line or transformer to a
respect to time to the ground without passing through the
building Feeder
Any of the conductors
device
Transformer Vault Switchgear Room
A fire-rated room housing Contains the service extending from the
a transformer and equipment for a large service equipment to Spark Gap
auxiliary equipment for a building various distribution A space between two terminals or electrodes
large building points in a building across which a discharge of electricity may pass
Service Equipment at a prescribed voltage
Equipment necessary for
controlling, metering and
protecting the electric
Standby Generator
power supply to a builidng
For providing emergency power
during a power outage. Switchboard Unit Substation
One or a group of panels on A freestanding enclosure
Uninterruptible Power Supply which are mounted switches, housing a disconnect
An emergency system designed overcurrent devices, switch, a step-down
to provide pwer automatically and metering instruments and transformer and
instantaneously buses switchgear
5
10/20/18
6
10/20/18
Fuse
Service Switch
under the heat produced by
excess current thereby
ELECTRICAL SYSTEM
The main disconnect for the entire interrupting the circuit
electrical system of a building
except for any emergency power
systems
Panel
A board on which are mounted
the switches, fuses and circuit BLOCK DIAGRAM
breakers for controlling and
protecting a number of similar A horizontal single line
branch circuits installed in a diagram of the building’s
cabinet and accessible from
the front only. Also called a Circuit Breaker
electrical system from the
panelboard. A switch that automatically interrupts an electric incoming service to the
Bus
circuit to prevent excess current from damaging
apparatus in the circuit or from causing a fire. A
utilization items at the end
A heavy conductor, usually in the form of a circuit breaker may be reclosed and reused without of the system where the
solid copper bar, used for collecting, carrying
and distributing large electric currents. Also
replacement of any components. Also called a
breaker.
major electrical
called a busbar components are shown as
Grounded Conductor blocks or rectangles.
Any conductor of an electrical system
intentionally connected to a ground
connection
ELEVATORS
PP MACHINE
MR ROOM ROOF
LP
7
10/20/18
8
10/20/18
CONDUCTOR SIZES –
3. ELECTRICAL MATERIALS AND EQUIPMENT AWG/MCM STANDARD
3.1 CONDUCTORS All conductor sizes from No. 16 to
– are materials which allow the free No. 0000 (also designated 4/0) are
flow of electrons through them. expressed in AWG.
Beyond AWG No. 4/0, a different
Wires – are single insulated designation, MCM (or thousand circular mil)
conductors No. 8 AWG (American Wire is used. In this designation, the smallest
Gauge or smaller; for the English MCM size is 250 MCM or ½” and the
System, it is the B & S Gauge or biggest is 500 MCM.
Browne and Sharpe Gauge. The A circular MIL is an artificial area
smallest size of wire permitted is No. measurement, representing the square of
14. the cable diameter (diam2) when the
Cables – are single insulated diameter is expressed in mils (thousands of
conductors No. 6 AWG or larger; or an inch). Thus a solid conductor ½ inch in
they may be several conductors of diameter is 500 mils in diameter, or
any size assembled into a single unit. 250,000 circular mils in area, (500)2 or
250 MCM; thus;
Bus Bars – large conductors which CM/1000 = diam2 = (500)2/1000 =
are not circular in cross section and 250,000/1000 = 250 MCM
usually found only to supply the main In the metric system, conductor sizes are
switch boards. given simply as the diameter in millimeters
(mm).
TYPES OF CABLES
CONDUCTOR AMPACITY Armored Cable (Type AC) – a fabricated
assembly of insulated conductors
enclosed in flexible metal sheath.
Metal Clad Cable (Type MC) – a factory
Conductor current carrying capacity or assembled cable of one or more
ampacity is the maximum operating conductors each individually insulated
temperature that its insulation can stand and enclosed in a metallic sheath of
continuously. Heat is generated as a interlocking tape of a smooth or
result of the current flowing and the corrugated tube.
conductor resistance. When conductors Mineral Insulated Cable (Type MI) – a
are placed in an enclosed conduit, the factory assembled conductor/s insulated
heat generated is not as easily with a highly compressed refractory
dissipated as it would be if the conductor mineral insulation enclosed in a liquid and
were free in the air. Thus, the current gas tight continuous copper sheath.
rating of a conductor in free air is much
higher than that for the same were it in Non-Metallic Sheathed Cable (Type NM
a conduit. or NMC) – also known by the trade
name ROMEX, is a factory assembly of
two or more insulated conductors having
a moisture resistant, flame retardant,
and non-metallic material outer sheath.
9
10/20/18
10
10/20/18
To protect the enclosed conductors “Intermediate Metal Conduit” or IMC with
from mechanical injury and chemical thickness of 0.071 mm.
damage.
Thin-wall steel conduits named “Electric
Metal Tubing” or EMT.
To protect people from shock hazards
by providing a grounded enclosure.
RSCs and IMCs use the same fitting, called
condulets, and are threaded alike at the
To provide a system ground path. joints. EMTs are not threaded but use set
screw and pressure fitting and are not
recommended for embedding in concrete
To protect the surroundings against fire nor permitted in hazardous areas. IMCs
hazard as a result of overheating or short yield a larger inside diameter (ID) for
circuiting of the enclosed conductors. easier wire pulling and is lighter than the
RSC.
To support the conductors. Standard length of steel conduits is 3 M or
10 ft.
11
10/20/18
12
10/20/18
13
10/20/18
14
10/20/18
2.2 Poles and transformer supports shall be located not more than
500mm inside from the road right-of-way or property line, and
1. General Locational Requirements in Towns, shall not obstruct the sidewalk, pedestrian path and/or the road
Subdivisions, Human Settlements, Industrial Estates drainage canal or structure, existing or proposed.
and the like.
15
10/20/18
≥5 m
≥150 mm
2.4 Secondary, neutral and service lines shall have a minimum vertical
clearance of 7.5 m from the crown of the road pavement when
crossing the highway and from the top of the shoulder or sidewalk
when installed along the side of the highway or street in highly
urbanized area.
16
10/20/18
4.4 Clearance of wires from building surface shall be not less than
those required Table II. 5. Conductors Passing By or Over Buildings
pole: general
Span and guy wires 75 mm 150 mm 300 mm 300 mm 10 mm
attached to same
pole: when parallel
to line
Lightning protection 75 mm 75 mm 75 mm 75 mm 5 mm
wires parallel to line:
surfaces of cross
arms
Lightning protection 75 mm 125 mm 75 mm 125 mm 5 mm
wires parallel to line:
surfaces of poles
17
10/20/18
Exception No. 2. Service drop conductors of 300 volts or less which do not pass 6.2 Clearance from the Ground. Conductors shall have a clearance of not less
over other than a maximum of 1.2m of the overhang portion of the roof for the than 3m from the ground or from any platform or projection from which they
purpose of terminating at a through-the-roof service raceway or approved might be reached.
conductor
support may be maintained at a minimum of 500mm from any portion of the
roof over which they pass. ≥3m platform
≥500mm
6.3 Clearance from Building Openings. Conductors shall have a horizontal
Service Drop Conductor clearance of not less than 1m from windows, doors, porches, fire escapes, or
similar locations and shall be run at least 500mm above the top level of a
≤ 1.2 m ≤ 300 volts
window or opening.
Highest point
≥ 500mm
window
≥1m
18
10/20/18
6.5 No parts of swimming and wading pools shall be placed under existing service
6.4 Service Drop of communication lines, when crossing a street, shall have a drop conductors or any other over-head wiring; nor shall such wiring be
clearance of not less than 5.5 m from the crown of the street or sidewalk installed above the following:
over which it passes. Service drop of communication line
a. Swimming and wading pools and the area extending 3m
outward horizontally from the inside of the walls of the pool.
≥ 5.50 m ≥5.50 m b. Diving Structures
c. Observation stands, towers or platforms
≥3m
8. Transformers
7. Wiring Methods
8.1 Oil-insulated Transformers Installed Outdoors. Combustible material,
Service entrance conductors extending along the exterior or entering combustible buildings and parts of buildings, fire escapes, door and
buildings or other structures shall be installed in rigid steel conduit or window openings shall be safeguarded from fires originating in oil-
asbestos cement conduit or concrete encased plastic conduit from point of insulated transformers installed on, attached to, or adjacent to a building
service drop to meter socket and from meter socket to the disconnecting or combustible material. Space separations, fire-resistant barriers and
equipment. However, where the service entrance conductors are protected enclosures which confine the oil of a ruptured transformer tank are
by approved fuses or breakers at their outer ends (immediately after the recognized safeguards. One or more of these safeguards shall be applied
service drop or lateral) they may be installed in any of the recognized wiring according to the degree of hazard involved in cases where the transformer
methods. installation presents a fire hazard. Oil enclosures may consist of fire-
resistant dikes, curbed areas or basins, or trenches filled with coarse,
7.1 Abandoned Lines and/or portions of lines no longer required to provide crushed stone. Oil enclosures shall be provided with trapped drains in
shall be removed. cases where the exposure and the quantity of oil involved are such that
removal of oil is important.
7.2 Power or communication poles, lines, service drops and other line
equipment shall be free from any attachment for antennas, signs, Exterior Oil-insulated
streamers and the like. Transformer
Trench all
7.3 Metallic sheaths or jackets of overhead power or communication cables around
shall be grounded at a point as close as possible to ground level
whenever such cables change from overhead to underground
installations.
19
10/20/18
≥ 1.85 m
≥ 300mm
8.3 Askarel-Insulated Transformers Installed Indoors. Askarel-insulated
transformers rated in excess of 25 KVA shall be furnished with a pressure
relief vent. Where installed in a poorly ventilated place they shall be
furnished with a means for absorbing any gases generated by arcing inside
the case, or the pressure relief vent shall be connected to a chimney or flue
which will carry such gases outside the building. Askarel-insulated
transformers rated more than 35,000 volts shall be installed in a vault.
20
10/20/18
9.4 Doorways. Any doorway leading from the vault into the building shall be
2. ARRANGEMENT. Vaults ventilated by natural circulation of air may have
protected as follows:
roughly half of the total area of openings required or ventilation in one or more
openings near the floor and the remainder in one or more openings in the roof
1. TYPE OF DOOR. Each doorway shall be provided with a tight-fitting
or in the sidewalls near the roof; or all of the area required for ventilation may
door of a type approved for openings in such locations by the authority
be provided in one or more openings in or near the roof.
enforcing this Code.
3. SIZE. In the case of vaults ventilated to an outdoor area without using ducts or
2. SILLS. A door sill or curb of sufficient height to confine within the
flues the combined net area of all ventilating openings after deducting the area
vault, the oil from the largest transformer shall be provided and in no
occupied by screens, grating, or louvers, shall be not less than 0.006 sqmm per
case shall the height be less than 100mm.
KVA of transformer capacity in service, except that the net area shall be not
less than 0.1 sqm for any capacity under 50 KVA.
3. LOCKS. Entrance doors shall be equipped with locks, and doors shall
be kept locked, access being allowed only to qualified persons. Locks
4. COVERING. Ventilation openings shall be covered with durable gratings,
and latches shall be so arranged that the door may be readily and
screens, or louvers, according to the treatment requirement required in order to
quickly opened from the inside.
avoid unsafe conditions.
10.Ventilation. Ventilation shall be adequate to prevent a transformer temperature 5. DAMPERS. Where automatic dampers are used in the ventilation openings of
in excess of the prescribed values. vaults containing oil-insulated transformers, the actuating device should be
made to function at a temperature resulting from fire and not a temperature
1. LOCATION. Ventilation openings shall be located as far away as which might prevail as a result of an overheated transformer or bank of
possible from doors, windows, fire escapes and combustible material. transformers. Automatic dampers should be designed and constructed to
minimize the possibility of accidental closing.
21
10/20/18
11.Capacitors.
6. DUCTS. Ventilating ducts shall be constructed of fire resistant material.
1. Application. This section applies to installation of capacitors on electric
7. DRAINAGE. Where practicable, vaults containing more than 100KVA circuits in or on buildings.
transformer capacity shall be provided with a drain or other means which will Exception No. 1. Capacitors that are components of other apparatus shall
carry off any accumulation of oil or water in the vaults unless local conditions conform to the requirements for such apparatus.
make this impracticable. Exception No. 2. Capacitors in hazardous locations shall comply with
additional requirements in PEC Section 400-415.
8. WATER PIPES AND ACCESSORIES. Any pipe or duct system foreign to the
electrical installation should not enter or pass through a transformer vault. 2. Location. An installation of capacitors in which any single unit contains
Where the presence of such foreign system cannot be avoided, appurtenances more than three gallons of combustible liquid shall be in a vault conforming
thereto which require maintenance at regular intervals shall not be located to part C of PEC Section 319.
inside the vault. Arrangements shall be made where necessary to avoid
possible trouble from compensation, leaks and breaks in such foreign system. 3. Mechanical Protection. Capacitors shall be protected from physical damage
Piping or other facilities provided for fire protection or for water-cooled by location or by suitable fences, barriers or other enclosures.
transformers are not deemed to be foreign to the electrical installation.
4. Cases and Supports. Capacitors shall be protected from physical damage by
location or by suitable fences, barriers or other enclosures.
12.Emergency Systems
1. The provisions of this Section shall apply to the installation, operation and
maintenance of circuits, systems and equipment intended to supply 4. Tests and Maintenance
illumination and power in the event of failure of the normal supply or in the
event of accident to elements of a system supplying power and illumination a. The authority having jurisdiction shall conduct or witness a test on the
essential for safety to life and proper where such systems or circuits are complete system upon completion of installation, and periodically afterwards.
required by the Fire Code, or by any government agency having jurisdiction.
b. Systems shall be tested periodically in accordance with a schedule acceptable
Emergency systems are generally installed in places of assembly where to the authority having jurisdiction to assure that they are maintained in proper
artificial illumination is required, such as buildings subject to occupancy by operating condition.
large numbers of persons, hotels, theaters, sports arenas, hospitals and similar
institutions. Emergency systems provide power for such functions as c. Where the battery systems or unit equipment are involved, including
refrigeration, operation of mechanical breathing apparatus, ventilation batteries used for starting or ignition in auxiliary engines, the authority having
essential to maintain life, illumination and power for hospital room, fire alarm jurisdiction shall require periodic maintenance.
systems, fire pumps, industrial processes where current interruption would
produce serious hazards, public address systems and other similar functions. d. A written record shall be kept of such tests and maintenance.
5. Emergency systems shall have adequate capacity and rating for the emergency
2. All requirements of this Section shall apply to emergency systems. operation of all equipment connected to the system.
3. All equipment for use on emergency systems shall be properly approved.
22
10/20/18
6. Current supply shall be such that in the event of failure of the normal supply to
or within the building or group of buildings concerned, emergency lighting or 8. A generator set driven by some form of prime mover, with sufficient capacity
emergency power, will be immediately available. The supply system for and proper rating to supply circuits carrying emergency lighting or lighting and
emergency purposes may be composed one or more of the types of systems power, equipped with suitable means for automatically starting the prime mover
covered in Section 12.7 to Section 12.10 of this Rule. Unit equipment in on failure of the normal service shall be provided. For hospitals, the transition-
accordance with Section 12.21 shall satisfy the applicable requirements of this time from instant of failure of the normal power source to the emergency
Section. generator source shall not exceed ten seconds. (See Section 12.4)
Consideration must be given to the type of service to be rendered; whether for 9. There shall be two services, each in accordance with Section 200 of the PEC,
short duration, as for exit lights of a theater, or for long duration, as for widely separated electrically and physically to minimize the possibility of
supplying emergency power and lighting during long periods of current failure simultaneous interruption of power supply arising from an occurrence within
from trouble either inside or outside the buildings, as in the case of a hospital. the building or group of buildings served.
Assignment of degree of reliability of the recognized emergency supply system 10.Connections on the line side of the main service shall be sufficiently separated
depends upon the careful evaluation of the variables of each particular from said main service to prevent simultaneous interruption of supply through
installation. an occurrence within the building or group of buildings served.
7. A storage battery of suitable rating and capacity shall supply, by means of a 11. The requirements of Section 12.5 and Section 12.6 also apply to installations
service installed according to Section 200 of the PEC and maintained at not where the entire electrical load on a service or sub-service is arranged to be
more than 90 per cent of system voltage, the total load of the circuits supplying supplied from a second source. Current supply from a standby power plant
emergency lighting and emergency power for a period of at least ½ hour. shall satisfy the requirements of availability in Section 12.6.
c. To indicate when a battery charger is properly functioning. b. Two or more separate and complete systems with independent power
supply, each system providing sufficient current for emergency lighting
13. Only appliances and lamps specified as required for emergency use shall be purposes. Unless both systems are used for regular lighting purposes
supplied by emergency lighting circuits. and are both lighted, means shall be provided for automatically
energizing either system upon failure of the other. Either or both
14. Emergency illumination shall be provided for all required exit lights and all systems may be part of the general lighting system of the protected
other lights specified as necessary for sufficient illumination. occupancy if circuits supplying lights for emergency illumination are
Emergency lighting systems should be so designed and installed that the installed in accordance with other Section of this Rule.
failure of any individual lighting element, such as the burning out of a light
bulb, shall not leave any area in total darkness. 16. For branch circuits which supply equipment classed as emergency, there shall
be an emergency supply source to which the load will be transferred
automatically and immediately upon the failure of the normal supply.
23
10/20/18
17. Emergency circuit wiring shall be kept entirely independent of all other wiring and
equipment and shall not enter the same raceway, box or cabinet with other wiring 20. Lights on the exterior of the building which are not required for illumination
except: when there is sufficient daylight may be controlled by an automatic light
a. In transfer switches, or actuated device approved for the purpose.
b. In exit or emergency lighting fixtures supplied from two (2) sources.
21. In hospital corridors, switching arrangements to transfer corridor lighting in
18. The switches installed in emergency lighting circuits shall be so arranged that only patient areas of hospitals from overhead fixtures to fixtures designed to provide
authorized persons have control of emergency lighting, except: night lighting maybe permitted, provided that the switching system is so
a. Where two or more single throw switches are connected in parallel to designed that switches can only select between two sets of fixtures but cannot
control a single circuit, at least one of those switches shall be accessible extinguish both sets at the same time.
only to authorized persons.
b. Additional switches which act only to put emergency lights into operation 22.The branch circuits over current devices in emergency circuits shall be
but not to disconnect them may be permitted. accessible to authorized persons only.
Switches connected in series and three- and four-way switches shall not be 23. Where permitted by the authority having jurisdiction, in lieu of other methods
allowed.
specified elsewhere in this Section, individual unit equipment for emergency
illumination shall consist of:
19. All manual switches for controlling emergency circuits shall be located at the most
accessible place to authorized persons responsible for their actuation. In places of
assembly, such as theaters, a switch for controlling emergency lighting systems a. Battery
shall be located in the lobby or at a place conveniently accessible there from. b. Battery charging means, when a storage battery is used
In no case shall a control switch for emergency lighting in a theater for motion c. One or more lamps, and
picture projection be placed in the projection booth or on the stage. However, d. A relaying device arranged to energize the lamps automatically upon
where multiple switches are provided, one such switch may be installed in such failure of the normal supply to the building
locations and so arranged that it can energize but not disconnect for the circuit.
The batteries shall be of suitable rating and capacity to supply and maintain, at not
less than 90 per cent of rated lamp voltage, the total lamp load associated with the
unit for a period of at least ½ hour. Storage batteries, whether of the acid or alkali
type, shall be designed and constructed to meet the requirements of emergency
service. Lead-acid type storage batteries shall have transparent jars.
Unit equipment shall be permanently fixed in place and shall have all wiring to each
unit installed in accordance with the requirements of any of the wiring methods
discussed in Chapter II of the PEC. They shall not be connected by flexible cord. The
supply circuit between the unit equipment and the service, the feeders or the branch
circuit wiring shall be installed as required by Section 12.17. Emergency illumination
fixtures which obtain power from a unit equipment which are not part of the unit
equipment shall be wired to the unit equipment as required by Rule 5257 of the PEC
and in accordance with the one of the wiring methods described in Chapter II of the
PEC.
13. Effectivity
1. All primary and secondary supply lines already existing shall comply with the
provisions of this Rule within two (2) years from the effectivity of this Rule.
2. Transformers to be installed on, attached to, or in buildings shall comply with the
requirements of this Rule. Transformer installations already existing shall comply with
the requirements within two (2) years from the effectivity of this Rule.
3. Non-compliance with the provisions of this Rule shall be subject to the penal
provisions in Section 213 of PD 1096.
24
10/20/18
1.0 COMMUNICATIONS & SIGNAL SYSTEMS 1.0 COMMUNICATIONS & SIGNAL SYSTEMS
1.1 General 3. Time Equipment 1.2 Fire Alarm System b) Coded Manual Stations
clock and program equipment Each manual station is coded and
this code is received at the control
1.1 General 1.1.1 Types of 1.1 General 1.2.1 Types of Fire Alarm
panel, processed and transmitted
1.2 Fire Alarm
Communication & Signal 1.1.2 Parts of the 1.2 Fire Alarm
Systems audibly on the system gongs. The
System Systems Communication & Signal System code usually comprises of 3 to 4
1. Automatic System digits; the first number may identify
1.3 Intrusion 1. Surveillance and Signal Systems 1.3 Intrusion uses detectors to trigger the alarm the building number, the second the
(Burglar) Alarm Equipment (Burglar) Alarm system. building floor and the third the
System System
Fire, smoke and intruder detection 1. Detectors individual station.
and alarm systems 2. Manual System
1.4 Sprinkler Alarm 1.4 Sprinkler Alarm
2. Control Unit or Panel uses visual detection and the alarm
1.5 Industrial In general, all signal systems require 1.5 Industrial is triggered by hand.
Building Security a surveillance system to process 3. Alarm Devices Building Security
System information including transmitting it System a) Non-Coded Manual Stations
and a means of indicating the signal, 4. Wiring or Circuitry the station locations are not
1.6 Television 1.6 Television identifiable at the control panel when
either audibly, visually or
Antenna System Antenna System it is manually triggered. An
permanently on “hard copy”.
annunciation panel, however, can be
1.7 Sound 1.7 Sound
Amplifying Systems 2. Audio and Visual Amplifying Systems added to the system, to convert
or Public Address Communication Equipment or Public Address each station as a non-coded
System telephone, intercom, public TV and System indicating zone. Beyond 10 stations,
closed circuit television (CCTV) coding should be considered.
1.8 Telephone and 1.8 Telephone and
Intercommunications Intercommunications
Systems Systems
1.0 COMMUNICATIONS & SIGNAL SYSTEMS 1.0 COMMUNICATIONS & SIGNAL SYSTEMS
1.2.2 Detectors b) Rate-of-Rise Unit 2. Photoelectric Detector 4. Flame Detectors
activates when the rate of ambient These detectors react to the These detectors are of two types;
1. Temperature Detector temperature differential exceeds a obscuration of a light beam by the Infrared (IR) and Ultraviolet (UV)
1.1 General 1.1 General
the most common is the predetermined amount. This unit smoke. They are best applied where Detectors. Applications are generally
1.2 Fire Alarm Temperature Detector called the may be combined with the fixed 1.2 Fire Alarm fires produce considerable quantities industrial and are highly sensitive.
System “thermostat” temperature unit in a single housing System of smoke and gas, such as those
such as in the case of an automatic caused by slow burning plastics.
1.3 Intrusion resetting unit. 1.3 Intrusion
a) Fixed Temperature Unit
(Burglar) Alarm (Burglar) Alarm
System triggers a set of contacts when a System
present temperature is reached.
1.4 Sprinkler Alarm This unit is available in a one-time 1.4 Sprinkler Alarm
non-renewable design that uses a
1.5 Industrial low melting alloy fusible plug. 1.5 Industrial projector sensor
Building Security Building Security
System System
3. Ionization Detector
1.6 Television 1.6 Television These detectors operate by
Antenna System Antenna System detecting ionized particles in the air.
Detectors are rated by temperature They do not detect fires producing
1.7 Sound
and coverage. For example in 1.7 Sound heavy smoke but few particles such
Amplifying Systems ordinary rooms, detectors are rated Amplifying Systems as alcohol and plastic fires.
or Public Address at 135 deg F per 200 sqft. For or Public Address
System kitchens, attics and basements System
Photoelectric and Ionization
where ambient temperature is Detectors are classed respectively
1.8 Telephone and higher, units are rated at 190 deg to 1.8 Telephone and
Intercommunications Intercommunications as early warning smoke and fire
200 deg F. detection devices.
Systems Systems
1
10/20/18
1.0 COMMUNICATIONS & SIGNAL SYSTEMS 1.0 COMMUNICATIONS & SIGNAL SYSTEMS
1.2.3 Control Unit or Panel
1.0 COMMUNICATIONS & SIGNAL SYSTEMS 1.0 COMMUNICATIONS & SIGNAL SYSTEMS
1.2.4 Alarm Devices
2
10/20/18
1.0 COMMUNICATIONS & SIGNAL SYSTEMS 1.0 COMMUNICATIONS & SIGNAL SYSTEMS
1.3 Intrusion (Burglar) 1.4 Sprinkler Alarm 1.5 Industrial Building 2. Personnel Entry Control
Alarm System Security System by use of a card reader
1.1 General Water flow switches are installed to 1.1 General
monitor the flow of water in a a) The first level is by simple
Intrusion detection is similar to the 1. Door and Exit Controls
1.2 Fire Alarm sprinkler head and when triggered 1.2 Fire Alarm insertion of a card by the holder to
fire detection system, except that These cover electrified security door
System will trip a coded transmitter, setting System an electric device which grants entry
instead of thermal detection, devices hardware that triggers an alarm
off a sprinkler code to show up on a when a card is inserted into it for
1.3 Intrusion such as metallic tape and micro- 1.3 Intrusion when a door is opened without
sprinkler annunciator board (called a identification.
(Burglar) Alarm and magnetic- switches are used to (Burglar) Alarm authorization, such as, in exterior
System detect door and window motion and sprinkler alarm panel). System doors and doors to restricted areas.
glass breakage. An eye or a laser
1.4 Sprinkler Alarm light beam may also be used to 1.4 Sprinkler Alarm
detect movement once blocked.
1.5 Industrial 1.5 Industrial
Building Security Building Security
System System
1.0 COMMUNICATIONS & SIGNAL SYSTEMS 1.0 COMMUNICATIONS & SIGNAL SYSTEMS
3. Watchmen’s Tour Equipment 1.6 Television Antenna 1.7 Sound Amplifying
this type of station allows a guard to
System Systems or Public
call in through an intercom and
1.1 General
permits a general alarm to ring
1.1 General Address Systems
The system functions by amplifying
1.2 Fire Alarm through operation of a key. 1.2 Fire Alarm the signal received by the TV Consists of the following:
System System
antenna and by means of a special
1.3 Intrusion 1.3 Intrusion cable, distribute these amplified 1. Microphone
(Burglar) Alarm (Burglar) Alarm signals into the various wall outlets. to pick up the sound and convert it
System System A system with two or more outlets to an alternative electric current.
generally needs a booster amplifier.
1.4 Sprinkler Alarm 1.4 Sprinkler Alarm
2. Amplifiers
1.5 Industrial 1.5 Industrial amplifies and controls the current.
Building Security b) The second level requires the Building Security
System encoding of a three-digit number System 3. Loudspeaker
simultaneously with the insertion of converts amplified electric current
1.6 Television 1.6 Television back into sound much louder than
Antenna System a card. This bars the entry of Antenna System
unauthorized card holders. the original sound entering the
microphone.
1.7 Sound 1.7 Sound
Amplifying Systems c) The third level involves an Amplifying Systems
or Public Address attendant who compares card data or Public Address
System through a computer screen with the System
person’s appearance providing a
1.8 Telephone and 1.8 Telephone and
Intercommunications further check. Intercommunications
Systems Systems
3
10/20/18
1.0 COMMUNICATIONS & SIGNAL SYSTEMS 1.0 COMMUNICATIONS & SIGNAL SYSTEMS
1.8 Telephone and 2. The Private Automatic Branch
Intercommunications Exchange or PABX is based on
solid-state technology, thus the
1.1 General Systems 1.1 General
entire system can handle up to
1.2 Fire Alarm 1.2 Fire Alarm 500 lines and trunks, 4 operator
System System consoles, and over 140
1. The intercom
simultaneous conversations plus
1.3 Intrusion
system comprises one 1.3 Intrusion full intercom facilities, all
(Burglar) Alarm or more master (Burglar) Alarm occupying a cabinet 0.60 M x
System stations System
0.70M x 1.8 M. The operational
(administrative) and
1.4 Sprinkler Alarm 1.4 Sprinkler Alarm features of this system include:
several remote
stations (staff), one of • direct internal and external dialing
1.5 Industrial which monitors the 1.5 Industrial
Building Security Building Security • consultation hold ( ability to hold an
System
front door. The master System
outside call while making an inside
station allows call)
• conference call capability for
1.6 Television selective calling while 1.6 Television internal and external units
Antenna System remote stations Antenna System • call transfer and camp-on feature
operating through the • automatic call back
1.7 Sound masters are non- 1.7 Sound • call forwarding
Amplifying Systems Amplifying Systems • distinctive ringing for different
selective.
or Public Address or Public Address functions
System System • paging, executive priority, dictation
access, personnel location and other
1.8 Telephone and 1.8 Telephone and options
Intercommunications Intercommunications
Systems Systems
1.0 COMMUNICATIONS & SIGNAL SYSTEMS 1.0 COMMUNICATIONS & SIGNAL SYSTEMS
1.8.1 Elements of the 2. Protector
generally required in residential
Telephone Installation telephone lines to protect against Protector
1.1 General 1.1 General
lightning. When a conduit entrance
1. Service Entrance and an interior conduit system are to
1.2 Fire Alarm the service connection from a pole 1.2 Fire Alarm
System
be installed, it is desirable to provide a System
or other outside terminal location to cabinet to accommodate the protector
1.3 Intrusion a point of entrance into the building usually a metal box of same type used 1.3 Intrusion
(Burglar) Alarm in electrical work. Located as close as (Burglar) Alarm
System The service entrance may be: possible to the point of entrance, one System
protector is required for each pair of
1.4 Sprinkler Alarm a) Overhead with overhead exposed telephone wires entering the building 1.4 Sprinkler Alarm
wires. OVERHEAD
1.5 Industrial 3. Main Terminal Cabinet or Room 1.5 Industrial
Building Security The serviced wires end at the main Building Security
System b) Underground with concealed System
underground wires in conduits. The terminal cabinet. Small sized wall type
terminals are mounted to metal
1.6 Television service conduit is usually of rigid iron 1.6 Television Protector
cabinets attached to or recessed in
Antenna System same for electrical works. Minimum Antenna System
walls or columns. Large sizes of wall
size of service conduit is ½” round. type terminals and frame type
1.7 Sound There should be a clearance of not 1.7 Sound
Amplifying Systems terminals (terminals mounted in frames Amplifying Systems
less than 6” between telephone accessible from both sides) should be
or Public Address or Public Address
System service conduit and the electric located in rooms which are intended System
conduit. for the purpose and constructed of fire
1.8 Telephone and resisting materials. 1.8 Telephone and
UNDERGROUND
Intercommunications Intercommunications
Systems Systems
4
10/20/18
1.0 COMMUNICATIONS & SIGNAL SYSTEMS 1.0 COMMUNICATIONS & SIGNAL SYSTEMS
4. Vertical Riser Conduits or Riser Risers whether conduits or shafts,
Shafts require central locations in relation
to floor area served. Buildings with
1.1 General 1.1 General
a) Riser Conduits large floor areas or with floors so
1.2 Fire Alarm are used in medium sized planned so as to result in two or 1.2 Fire Alarm RISER
DISTRIBUTION
System installations and consist of a series more distinct areas will probably System CABINET SHAFTS
of metal cabinets called splicing need a separate riser for each area.
1.3 Intrusion cabinets aligned vertically through 1.3 Intrusion WALL
(Burglar) Alarm the building, one on each floor and 5. Splicing Cabinets or Splicing (Burglar) Alarm OUTLET
System System RISER
connected by a vertical conduit. Closets CONDUITS
1.4 Sprinkler Alarm permit the riser cables in the riser 1.4 Sprinkler Alarm
b) Riser Shafts shaft or conduit to be spliced or
1.5 Industrial are required for very large interconnected to the cables or 1.5 Industrial
Building Security installations and consist of a series telephone wires to the various Building Security
System of individual full length floors. System SPLICING
interconnecting closets called FLOOR CABINET
1.6 Television 1.6 Television CONDUITS
splicing closets which are aligned 6. Floor Conduits
Antenna System Antenna System
vertically one on each floor and each connects the splicing closets or
1.7 Sound fitted with a fire proof access door. cabinets into the distribution terminal 1.7 Sound
Amplifying Systems Slots on the floor, forms a clear and cabinets and to floor ducts, wall Amplifying Systems MAIN TERMINAL
or Public Address broken opening from top to bottom outlets, etc. or Public Address TELEPHONE CABINET
System of the building. System
5
10/20/18
2.4 Air-Conditioning
2.1.2 Functions or to 75 deg F and relative humidity of 30%
2.4 Air-Conditioning
to 35% are found most satisfactory.
Equipment Elements of Air- Equipment
Conditioning 3. Air Motion
2.5 Heating air velocity should average 4.57 to 7.6 2.5 Heating
Systems meters per min measured 36” above the Systems
1. Cooling and de-humidifying of air
2. Heating or humidifying of air floor.
2.6 Provisions in 2.6 Provisions in
the NBC 3. Cleaning of air or filtration the NBC
4. Air Supply
Concerning HVAC 4. Circulation of air Concerning HVAC
a. cuft to 7-1/2 cuft of air per minute per
person (5-71/2 cuft/min/pers). In rooms
where smoking is not allowed
1
10/20/18
2
10/20/18
3
10/20/18
4
10/20/18
5
10/20/18
6
10/20/18
7
10/20/18
TRANSPORTATION SYSTEMS
Bulkhead Hoisting Machinery
3.0 Penthouse Control Panel
3.1 Elevators and 3.1.2 Types of Elevators Top Car Clearance
Dumbwaiters Driving Sheave
3.1 Elevators & 1. Electric elevators
Idle Sheave
Dumbwaiters
3.1.1 Definition of Elevator
Hoistway
3.2 Escalators &
Are generally used in buildings Machine Beam
Conveyors Bank
where several peak periods of traffic
3.3 Chutes occur each day, (ie. In office Hoisting Cable
Landing
buildings, hospitals, apartment Guide Rail
3.4 Provisions in buildings)
the NBC
Concerning Elevator Car Safety
Traveling Cable
Transportation
Rise
Systems
Hoistway Door
Counterweight
Limit Switch
Door Contact
A safety device for preventing the operation of
an elevator car unless its door or gate is fully
closed
1
10/20/18
7. Elevator Machine
turns the sheave that lifts and lowers the
car.
8. Controls
a combination of push buttons, contacts, This usually stops the car, but should
relays, and devices, operated manually or speed still increase, the governor will
automatically to initiate door opening, actuate rail clamps mounted at the bottom
starting acceleration, retardation, leveling of the car one on each side. This will
and stopping of the car. clamp the guide rails bringing the car to a
switch stop.
2
10/20/18
3
10/20/18
4
10/20/18
Typical Specifications
Standard width = 27” and 36”
Speeds = 120 fpm and
180 fpm
5
10/20/18
6
10/20/18
7
Intro Definition and Causes of Fire
2 Intro Classes of Fire
3
oxygen and heat - are Class C: Energized electrical No Water; Use electrically
required to start a fire. non-conductive
equipment extinguishing agents such
as gaseous systems
The oxidation process
will not be possible Class D: Combustible metals such Heat-absorbing
without any one of these as potassium, sodium, medium which is
elements. Oxygen (Ventilation) Heat (Ignition) magnesium and other not reactive with
burning metals
reactive metals
Architectural Intervention
Stages This graph shows where active and passive
1
Intro Behavior of Fire and Smoke
1 Intro Fire Spread
2
2
Intro Fire Spread
2
Aims in
External Fire Spread due to: Fire Safety Design
A To prevent fire
Convection
Ignition of Materials
Currents
B To safeguard the lives of
Ignition of Materials Ignition of Materials occupants and firefighters
Basic
Basic Fire Avoidance 1
Principles 1
3
Basic Basic
Fire Avoidance 1
Principles 1
Fire Avoidance 1
Principles 2
Basic Basic
PrinciplesFire Detection2 PrinciplesFire Detection2
Visual Fire Detection Mechanical Fire Detection
Makes use of manual and automatic (electric/
electronic) methods of informing the occupants in
charge that a fire has occurred in a given location.
4
Basic Basic
Fire Growth Restriction3
Principles Fire Growth Restriction3
Principles
4
Aimed at ensuring that the growing fire is extinguished Rating of Fire Extinguishers :
immediately and at providing adequate time for firemen to Class A Extinguishers will put out fires in ordinary
combustibles, such as wood and paper. The numerical
arrive, control the fire and evacuate the occupants. rating for this class of fire extinguisher refers to the
amount of water the fire extinguisher holds and the
amount of fire it will extinguish
Manual Means of Restricting
5 Class B Extinguishers should be used on fires
Fire Growth involving flammable liquids, such as grease, gasoline,
oil, etc. The numerical rating for this class of fire
extinguisher states the approximate number of square
Actively extinguishing or slowing down feet of a flammable liquid fire that a non-expert person
the development of a fire before the full can expect to extinguish
involvement of the room. This is done
Class C Extinguishers are suitable for use on electrically
by the room’s local occupants. energized fires. This class of fire extinguishers does not
have a numerical rating. The presence of the letter “C”
Means: indicates that the extinguishing agent is non-conductive
1. Fire Extinguisher
Class D Extinguishers are designed for use on
2. Water Supply flammable metals and are often specific for the type of
3. Fire Blanket metal in question. There is no picture designator for
Class D extinguishers. These extinguishers generally
4. Bucket of Sand have no rating nor are they given a multi-purpose rating
for use on other types of fires
Basic Basic
Fire Growth Restriction3
Principles Fire Growth Restriction3
Principles
4
Types of Fire Extinguishers :
Mechanical Means of
6
Restricting Fire Growth
Dry Chemical extinguishers are usually rated for multiple purpose use. Sprinkler Specifications:
They contain an extinguishing agent and use a compressed, non-flammable
gas as a propellant
Halon extinguishers contain a gas that interrupts the chemical reaction that
takes place when fuels burn. These types of extinguishers are often used to
protect valuable electrical equipment since them leave no residue to clean up.
Halon extinguishers have a limited range, usually 1.2 to 1.8 meters. The initial
application of Halon should be made at the base of the fire, even after the
flames have been extinguished
5
Basic Basic
Fire Containment4
Principles Fire Containment4
Principles
2
Definition and Implication Concepts of Fire Compartmentation
Assumes that measures to control a growing fire Definition Objectives
may not be successful, hence its maximum size -To limit fire and smoke spread
needs to be restricted both to reduce the risk Containing fire- -To allow longer escape time
and to allow effective firefighting. prone areas by -To reduce the maximum potential size of the fire
Extend CHB means of fire-
walls up to This implies:
slab resistive
1. Fire cladding of structural components to ensure stability
enclosures
of structural frames.
Room
2. The use of fire-rated walls and slabs to contain fire in
Sub-Compartment
rooms, sub-compartments and compartments so as to
segregate areas where fire may occur. Compartment
Basic Basic
Fire Containment4
Principles Fire Containment4
Principles
3 3
Fire Rating of Construction Systems Fire Rating of Construction Systems
Concrete Masonry Wall Units Ceiling Systems
2 Hour 4 Hour 1 Hour 2 Hour 3 Hour
4” 6”
6
Basic Basic
Fire Containment4
Principles Fire Containment4
Principles
3
Fire Rating of Construction Systems Load Bearing Capacity, Integrity
2
Door Openings For 1.2m X 3.0m single hollow metal doors (ga.20 steel face), with
labeled single-point or 3-point latching hardware, steel hinges or pivots
and Insulation
1 Hour 2 Hour 3 Hour Load Bearing Capacity Integrity Insulation
125mm
min Passage of
Collapse or Temperature
excessive flame increase
1.370m 0.83m deflection
max max
125mm
min
Structural Performance: Ability to resist the *Insulated building elements will
-Maximum glass area: 0.83 sq.m -Maximum glass area 0.063 sq.m -Flush Metal Door
Building still stands development of crack or not ignite in fire and will ensure
-For openings in walls or partitions -6mm thk Wire glass in a steel frame -No Glass Permitted
between rooms and corridors having a during an emergency perforations so as not passage of human beings
-For openings in enclosures of vertical -3mm clearance at jambs
fire resistance rating of 1 hour or less communications through buildings and to allow passage of without damage on the other
-10mm clearance at non-combustinle
Ability to carry load side of the separating element.
in 2-hour rated partitions providing floor smoke and flame
horizontal fire separations without collapsing
-For openings in fire walls or walls Ability to prevent heat transfer
that divide a single building into fire
areas from one face to the other face.
Basic Basic
Principles Fire Control5 Principles Fire Control5
Site Access for Fire Control8:
Definition and Implication L T-TURN
W
30m> DEAD END
Fire apparatus should have Bollards and fences used for traffic
Access Road control must allow for sufficient Prevent time-consuming, hazardous
unobstructed access to
open road width for fire truck back-ups at dead-ends by using T-
buildings.
turns and cul-de-sacs
MAX. 90 METERS
FIRE HYDRANT
0.3m
SIAMESE
CONNECTION
ensure that all areas inside
and outside the building
Place hydrants at max. 3 meters Hydrant must be Utility poles, kiosks, sculpture,
are covered by reach of unobstructed; Fire hose
from curb. Siamese connection fountains, plant boxes can impede
access road for firetrucks the firehose to standpipes must be visible connection should be at fire rescue operations
and within 60m from hydrant least 0.3m above grade
7
Basic Basic
Principles Fire Control5 Principles Fire Control5
Firetrucks Concept of the Firefighting Shaft
Provides access to a building, especially in high
Aerial Apparatus
rise buildings, for fire brigades.
Specifications:
Elevator
Is fully-equipped with firefighting equipment, shaft Wet and Dry
service elevator, stair and lobby. Risers
25 m.
20 m.
Fire-rated
doors
75 ° (safe 75 ° 75 °
angle)
Basic Basic
Smoke Control6
Principles Smoke Control6
Principles
2 2
Definition and Techniques Definition and Techniques
Measures which can assist to some extent c. PRESSURIZATION – technique whereby air is blown into
occupants in the fire zone but are particularly spaces which are designed to be kept clear of smoke.
needed for others in adjacent areas or
compartments.
High
Venting
Techniques of Smoke Uses barriers including Pressure
Control walls, floors and
doors, to contain Low
Extraction of Smoke Pressure
Ceiling Reservoir a. SMOKE CONTAINMENT/ pressurized air
BARRIER – technique of generated by
Smoke Plume restricting the movement of mechanical means to
smoke by the provision of fire keep smoke away
resisting elements.
Shop from protected areas
b. SMOKE DISPERSAL – such as escape
Mall
Smoke Barrier technique of clearing smoke staircases and
locally by provision of natural corridors.
Make Up Air cross-ventilation or mechanical
venting.
8
Basic Basic
Escape Provisions7
Principles Escape Provisions7
Principles
1
Definition Protected Escape Routes
Cover a range of passive or active systems which To provide safety, This can be Escape Route Leading to:
permit the occupants to move or be moved to a the routes must achieved by:
place of safety within or to the outside of a building. be properly
Protected Escape
Route
- Compartmentation
protected from Place of Safety Place of Safety
Basic Basic
Escape Provisions7
Principles Escape Provisions7
Principles
1
Alternative Means of Escape Primary Considerations in the
Design for FIRE Safety
Place of Place of of Hospitals1
Safety Safety