Electronic timers

Product group picture

1/1 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
Electronic timers
Table of contents

Electronic timers
1
Table of contents 1/2
Overview 1/3
Approvals and marks 1/4
CT-D range 1/5
Table of contents 1/6
Benefits and advantages 1/7
Ordering details 1/8
Function diagrams 1/9
Connection diagrams 1/12
Technical data 1/13
Technical data, Technical diagrams 1/15
Wiring notes, Dimensional drawings 1/16
CT-E range 1/17
Table of contents 1/18
Benefits and advantages 1/19
Ordering details 1/20
Function diagrams 1/22
Connection diagrams 1/27
Connection diagrams, Technical diagrams 1/28
Technical data 1/29
Wiring notes, Dimensional drawings 1/31
CT-S range 1/33
Table of contents 1/34
Benefits and advantages 1/35
Ordering details - multifunctional 1/37
Ordering details - singlefunctional 1/38
Ordering details - Accessories 1/39
Function diagrams 1/41
Connection diagrams 1/49
Technical data 1/52
Technical diagrams 1/55
Wiring notes, Dimensional drawings 1/56

2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 1/2
Electronic timers
Overview

CT-D range CT-E range CT-S range

Timing function multifunctional single-functional multifunctional single-functional multifunctional single-functional

A ON-delay CT-MFD CT-ERD CT-MFE, CT-ERE, CT-MVS, CT-MFS, CT-ERS


CT-MKE CT-EKE CT-MBS, CT-WBS

B OFF-delay CT-MFD CT-AHD CT-MFE CT-AHE, CT-MVS, CT-MFS, CT-APS,


CT-ARE, CT-MBS CT-AHS,
CT-AKE CT-ARS
AB ON- and OFF-delay CT-MVS, CT-MXS,
CT-MFS, CT-MBS
CA Impulse-ON CT-MFD CT-VWD CT-MFE, CT-VWE CT-MVS, CT-MFS,
CT-MKE CT-MBS, CT-WBS
CB Impulse-OFF CT-MFD CT-AWE CT-MVS, CT-MFS,
CT-MBS
CE Impulse-ON and OFF CT-MXS
DA Flasher starting with ON CT-MFD CT-EBD CT-MFE, CT-MFS, CT-MBS,
CT-MKE CT-WBS
DB Flasher staring with OFF CT-MFD CT-MFE, CT-EBE CT-MFS, CT-MBS,
CT-MKE CT-WBS
DE Flasher starting with ON or CT-MVS
OFF
ED Pulse generator starting with CT-TGD CT-MXS
ON or OFF
H Pulse former CT-MFD CT-MFE CT-MVS, CT-MFS,
CT-MBS
F Star-delta change-over CT-SDD, CT-SDS
CT-SAD
FC Star-delta change-over with CT-SDE CT-MVS.2x,
impulse CT-MFS, CT-MBS
FA Star-delta change-over CT-YDE
twice ON-delayed
A+ AC BC G CT-MVS, CT-MXS,
further functions CT-MFS, CT-MBS,
CT-WBS
(depending on device)

Technical data (extract)

Time ranges 7 (0.05 s - 100 h) Multifunction devices: 10 (0.05 s - 300 h)


CT-SDD, CT-SAD: 8 (0.05 s - 100 h) CT-ARS, CT-SDS:
4 (0.05 s - 10 min) Single-function devices: 7 (0.05 s- 10 min)
5 single ranges (0.05-1 s, 0.1-10 s,
0.3-30 s, 3-300 s, 0.3-300 min)
Control supply voltage Wide and multi ranges Wide ranges Single and dual Wide, multi and single ranges
ranges
Type and number of contacts 1 or 2 c/o contacts 1 c/ o contact 1 or 2 c/o contacts
CT-SDD, CT-SAD: 2 n/o contacts CT-SDE: 1 n/o contact and 1 n/c CT-MVS.21, CT-MFS, CT-MBS:
contact 2nd c/o contact selectable as inst.
CT-MKE, CT-EKE, CT-AKE: 1 thyristor contact
CT-SDS: 2 n/o contacts
Control inputs voltage-related triggering, voltage-related triggering, polarized voltage-related triggering, non-
polarized, capable of switching a CT-MFE, CT-AHE, CT-AWE: polarized, capable of switching a
parallel load with auxiliary voltage parallel load
CT-MFS, CT-MBS, CT-AHS:
volt-free triggering

1/3 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
Electronic timers
Approvals and marks

J existing CT-D
j pending 1

CT-ERD .22

CT-VWD.12
CT-MFD.12

CT-MFD.21

CT-AHD.12

CT-AHD.22

CT-SDD.22
CT-TGD.12

CT-TGD.22
CT-ERD.12

CT-EBD.12

CT-SAD.22
Approvals
A UL 508, CAN/CSA C22.2 No.14 J J J J J J J J J J J J
K CB scheme J J J J J J
EAC J J J J J J J J J J J J
E CCC J J J J J J J J J J J J
L RMRS J J J J J J J J J J
Marks
a CE J J J J J J J J J J J J
b RCM J j J j J j J J J j j j

J existing CT-E
j pending
CT-AWE
CT-VWE

CT-MKE
CT-MFE

CT-AHE

CT-SDE
CT-ARE

CT-YDE

CT-AKE
CT-ERE

CT-EBE

CT-EKE
Approvals
A UL 508, CAN/CSA C22.2 No.14 J J J J J J J J J J J J
C GL J J J J J J J J J J J J
K CB scheme J J J J J J J J J
EAC J J J J J J J J J J J J
E CCC J J J J J J J J J
L RMRS J J J J J J J J J J J J
Marks
a CE J J J J J J J J J J J J
b RCM J J J J J J J J J J J J

J existing CT-S
j pending
CT-WBS.22S/P
CT-MBS.22S/P
CT-MVS.12S/P

CT-MXS.22S/P

CT-MFS.21S/P
CT-MVS.2xS/P

CT-AHS.22S/P

CT-ARS.11S/P

CT-ARS.21S/P
CT-ERS.12S/P

CT-APS.12S/P

CT-SDS.2xS/P
CT-ERS.2xS/P

CT-APS.2xS/P

Approvals
A UL 508, CAN/CSA C22.2 No.14 J J J J J J J J J J J J J J
C GL J J J J J J J J J J J j j J
EAC J J J J J J J J J J J J J J
K CB scheme J J J J J J J J J J J J J J
E CCC J J J J J J J J J J J J J J
L RMRS J J J J J J J J J J J J J J
Rail applications 1)
J J J J J J
Marks
a CE J J J J J J J J J J J J J J
b RCM J J J J J J J J J J J J J J
1)
Applicable in rail application following the latest standards for rail applications. Further information are available in our rail segment brochure 2CDC110084B0201.

2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 1/4
CT-D range
Product group picture

1/5 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
CT-D range
Table of contents

CT-D Range
1
Benefits and advantages 1/7
Ordering details 1/8
Function diagrams 1/9
Connection diagrams 1/12
Technical data 1/13
Technical data, Technical diagrams 1/15
Wiring notes, Dimensional drawings 1/16

2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 1/6
CT-D range
Benefits and advantages

Characteristics Benefits
1 –– Diversity:
Direct reading scales 1
–– 2 multifunction timers
Direct setting of the time delay without any additional
–– 10 single-function timers calculation provides accurate time delay adjustment.
–– Control supply voltages:
–– Wide range: 12-240 V AC/DC LEDs for status indication 2
–– Multi range: 24-48 V DC, 24-240 V AC All actual operational states are displayed by front-face LEDs,
–– 7 time ranges from 0.05 s to 100 h or thus simplifying commissioning and troubleshooting.
4 time ranges from 0.05 s to 10 min
–– Width of only 17.5 mm Switching currents
–– Light-grey housing in RAL 7035 The CT-D range timers allow an output load of up to 6 A on
–– Devices with: devices with 1 c/o contact and up to 5 A on devices with
1 c/o contact (250 V / 6 A) or 2 c/o contacts (250 V / 5 A) 2 c/o contacts.
Control input: voltage-related triggering, polarized,
capable of switching parallel loads
Connection terminals 3
–– Approvals / Marks (partly pending, details see page 1/4)
Wide terminal spacing allows connection of wires:
–– A, K1), E, , L / a, b 2 x 1.5 mm² (2 x 16 AWG) with wire end ferrules or 2 x 2.5
mm² (2 x 14 AWG) without ferrules.
1)
Only for devices with 1 c/o (SPDT) contact

Width 17.5 mm 4

With their width of 17.5 mm only, the CT-D range timers are
ideally suited for installation in distribution panels.

Operating controls
1 LEDs for status indication
U - green LED: V control supply voltage applied
3 W timing
R, R1, R2 - yellow LED: V output relay energized
2
2 Time range adjustment
3 Fine adjustment of the time delay
1
4 Preselection of the timing function
3

multifunctional single-functional
2CDC 253 021 F0004
2CDC 253 066 F0006

2CDC 253 132 F0006

2CDC 253 033 F0004

2 3 4
1

17.5 mm

1/7 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
CT-D range
Ordering details

Description
The CT-D range in MDRC design with a width of only 17.5 mm fits into all domestic installation
1
and distribution panels.
The CT-D range represents a link between industry and the installation types. For maximum
flexibility in operation, 10 single-function as well as 2 multifunction devices with 7 timing
functions are available. The devices offer 4 or 7 time ranges from 0.05 seconds up to 100
hours. Their wide input range allows the use in applications worldwide.

Ordering details
Timing Rated Time ranges Con- Output Type Order code Price Weight
function control trol (1 pce)
supply input
voltage 1 pce kg (lb)

Multifunc- 24-240 V AC 7 (0.05 s - 0.060


M 1 c/o CT-MFD.12 1SVR500020R0000
tional1) 24-48 V DC 100 h) (0.132)

Multifunc- 12-240 7 (0.05 s - 0.065


M 2 c/o CT-MFD.21 1SVR500020R1100
tional1) V AC/DC 100 h) (0.143)
2CDC 251 089 F0006

0.060
- 1 c/o CT-ERD.12 1SVR500100R0000
(0.132)
ON-delay
0.065
- 2 c/o CT-ERD.22 1SVR500100R0100
(0.143)
CT-MFD.12 0.060
M 1 c/o CT-AHD.12 1SVR500110R0000
(0.132)
OFF-delay 7 (0.05 s -
100 h) 0.065
M 2 c/o CT-AHD.22 1SVR500110R0100
(0.143)
Impulse-
- CT-VWD.12 1SVR500130R0000
ON 24-240 V AC 0.060
Flasher 24-48 V DC (0.132)
starting - 1 c/o CT-EBD.12 1SVR500150R0000
with ON
2CDC 251 091 F0006

0.060
M CT-TGD.122) 1SVR500160R0000
Pulse 2×7 (0.05 s - (0.132)
generator 100 h) 0.065
M 2 c/o CT-TGD.222) 1SVR500160R0100
(0.143)

CT-ERD.22 Star-delta - CT-SDD.223) 1SVR500211R0100


4 (0.05 s - 0.065
change- 2 c/o
10 min) (0.143)
over - CT-SAD.22 4)
1SVR500210R0100

1)
Functions: ON-delay, OFF-delay with auxiliary voltage, Impulse-ON, Impulse-OFF with auxiliary voltage,
Flasher starting with ON, Flasher starting with OFF, Pulse former
2)
ON and OFF times adjustable independently: 2 x 7 time ranges 0.05 s - 100 h M Control input with voltage-related triggering
3)
Transition time 50 ms fixed - no triggering
4)
Transition time adjustable
A ON-delay
B OFF-delay
CA Impulse-ON
CB Impulse-OFF
DA Flasher starting with ON Synonyms
DB Flasher staring with OFF used expression alternative expression(s) used expression alternative expression(s)
H Pulse former
ED Pulse generator 1 c/o contact SPDT voltage-related wet / non-floating
F Star-delta change-over
2 c/o contacts DPDT volt-free dry / floating

2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 1/8
CT-D range
Function diagrams

1 Remarks
Function of the yellow LED
Legend
The yellow LED R glows as soon as the output relay
G Control supply voltage not applied / Output contact open
B Control supply voltage applied / Output contact closed
energizes and turns off when the output relay de-energizes.
A1-Y1/B1 Control input with voltage-related triggering

Terminal designations on the device and in the diagrams


The 1st c/o contact is always designated 15-16/18.
The 2nd c/o contact is designated 25-26/28.
The n/o contacts of the star-delta timers are designated with
17-18 and 17-28.
Control supply voltage is always applied to terminals A1-A2.

A ON-delay (Delay on make) B OFF-delay with auxiliary voltage (Delay on break)


CT-ERD, CT-MFD CT-AHD, CT-MFD

This function requires continuous control supply voltage for This function requires continuous control supply voltage for
timing. timing. If control input A1-Y1/B1 is closed, the output relay
Timing begins when control supply voltage is applied. energizes immediately. If control input A1-Y1/B1 is opened,
The green LED flashes during timing. When the selected the time delay starts. The green LED flashes during timing.
time delay is complete, the output relay energizes and the When the selected time delay is complete, the output relay
flashing green LED turns steady. de- energizes and the flashing green LED turns steady.
If control supply voltage is interrupted, the output relay de- If control input A1-Y1/B1 recloses before the time delay is
energizes and the time delay is reset. complete, the time delay is reset and the output relay does
Control input A1-Y1/B1 of the CT-MFD is disabled when this not change state. Timing starts again when control input
function is selected. A1-Y1/B1 re-opens.If control supply voltage is interrupted,
the output relay de-energizes and the time delay is reset.
A1-A2
2CDC 252 106 F0206

A1-A2

2CDC 252 107 F0206


15-18, 25-28 A1-Y1/B1
15-16, 25-26
15-18, 25-28
green LED 15-16, 25-26
t <t
green LED
t <t
t = adjusted time delay

t = adjusted time delay

CA Impulse-ON (Interval) CB Impulse-OFF with auxiliary voltage


CT-VWD, CT-MFD (Trailing edge interval)
CT-MFD

This function requires continuous control supply voltage for This function requires continuous control supply voltage for
timing. The output relay energizes immediately when control timing. If control supply voltage is applied, opening con-
supply voltage is applied and de-energizes after the set pulse trol input A1-Y1/B1 energizes the output relay immediately
time is complete. The green LED flashes during timing. When and starts timing. The green LED flashes during timing.
the selected pulse time is complete, the flashing green LED When the selected pulse time is complete, the output relay
turns steady. If control supply voltage is interrupted, the de-energizes and the flashing green LED turns steady.
output relay de-energizes and the time delay is reset. Control Closing control input A1-Y1/B1, before the time delay is
input A1-Y1/B1 of the CT-MFD is disabled when this function complete, de-energizes the output relay and resets the time
is selected. delay. If control supply voltage is interrupted, the output
relay de-energizes and the time delay is reset.
A1-A2
2CDC 252 108 F0206

15-18, 25-28
15-16, 25-26 A1-A2
2CDC 252 109 F0206

green LED A1-Y1/B1


t <t
15-18, 25-28
15-16, 25-26

t = adjusted pulse time green LED


t <t

t = adjusted pulse time

1/9 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
CT-D range
Function diagrams

1
DA Flasher, starting with the ON time DB
Flasher, starting with the OFF time
(Recycling equal times, ON first) (Recycling equal times, OFF first)
CT-EBD, CT-MFD CT-MFD

Applying control supply voltage starts timing with symmetrical Applying control supply voltage starts timing with symmetrical
ON & OFF times. The cycle starts with an ON time first. The ON & OFF times. The cycle starts with an OFF time first. The
ON & OFF times are displayed by the flashing green LED, ON & OFF times are displayed by the flashing green LED,
which flashes twice as fast during the OFF time. which flashes twice as fast during the OFF time.
If control supply voltage is interrupted, the output relay If control supply voltage is interrupted, the output relay
de-energizes and the time delay is reset. de-energizes and the time delay is reset.
Control input A1-Y1/B1 of the CT-MFD is disabled when this Control input A1-Y1/B1 of the CT-MFD is disabled when this
function is selected. function is selected.
A1-A2
2CDC 252 029 F0206

15-18, 25-28
15-16, 25-26 A1-A2

2CDC 252 030 F0206


green LED 15-18, 25-28
t t 15-16, 25-26
green LED
t = adjusted flashing time t t

t = adjusted flashing time

H
Pulse former (Single shot) E Pulse generator, starting with the ON or OFF time
CT-MFD (Recycling unequal times, ON or OFF first)
CT-TGD
This function requires continuous control supply voltage for
timing. This function requires continuous control supply voltage for
Closing control input A1-Y1/B1 energizes the output relay timing.
immediately and starts timing. Operating the control contact Applying control supply voltage, with open control input
switch A1-Y1/B1 during the time delay has no effect. The A1-Y1/B1, starts timing with an ON time first. Applying
green LED flashes during timing. When the selected ON time control supply voltage, with closed control input A1-Y1/B1,
is complete, the output relay de-energizes and the flashing starts timing with an OFF time first. The ON & OFF times are
green LED turns steady. After the ON time is complete, it displayed by the flashing green LED, which flashes twice as
can be restarted by closing control input A1-Y1/B1. fast during the OFF time.
If control supply voltage is interrupted, the output relay The ON & OFF times are independently adjustable.
de-energizes and the time delay is reset. If control supply voltage is interrupted, the output relay
A1-A2
de-energizes and the time delay is reset.
2CDC 252 110 F0206

A1-Y1/B1
15-18, 25-28 A1-A2
2CDC 252 111 F0206

15-16, 25-26
A1-Y1/B1
green LED
t t 15-18, 25-28
15-16, 25-26
green LED
t = adjusted pulse time
t1 t2 t2 t1

t1 = adjusted OFF time


t2 = adjusted ON time

2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 1/10
CT-D range
Function diagrams

1 F Star-delta change-over
(Star-delta starting)
CT-SDD, CT-SAD A1-A2

2CDC 252 112 F0206


17-18

This function requires continuous control supply voltage for 17-28

green LED
timing. t1 t2

Applying control supply voltage to terminals A1-A2, t1 = adjusted starting time


energizes the star contactor connected to terminals 17-18 t2 = transition time
CT-SDD: t2 = 50 ms
and begins the set starting time t1. The green LED flashes CT-SAD: t2 adjustable

during timing. When the starting time is complete, the first


output contact de-energizes the star contactor.
Now, the transition time t2 starts. When the transition time
is complete, the second output contact energizes the
delta contactor connected to terminals 17-28. The delta
contactor remains energized as long as control supply
voltage is applied to the unit.

2CDC 252 012 F0b07


L1 L2 L3
2CDC 252 128 F0b06

L1 F3 1 3 5
-F1
95 2 4 6
F2
96
S1 21
0
22

S2 13 53 1 3 5 1 3 5 1 3 5
I K2 -K2 2 4 6
-K3 2 4 6
-K1 2 4 6
14 54

17 17 13 13
K1T K2 K1
18 28 14 14 97 95
1 5 4
-F2 98 96
22 22
3 2 6
K3 21
K1 21
-M1
A1 A1 A1 A1 W1 W2
K1T K1 K3 K2 V1 M V2
A2 A2 A2 A2 U1 3~ U2
N
Y  N
Control circuit diagram Power circuit diagram

1/11 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
CT-D range
Connection diagrams

CT-MFD.21
2CDC 252 113 F0b06
CT-MFD.12 A CT-ERD.22 A CT-ERD.12 1

2CDC 252 115 F0b06

2CDC 252 177 F0b05


2CDC 252 114 F0b06
A1 15 25 A1 15 Y1/B1 A1 15 25 A1 15
Y1/ Y1/
B1 A1 15 25 B1 A1 15 A1 15 25 A1 15

A2 16 18 26 28 A2 16 18 A2 16 18 26 28 A2 16 18
18 16 Y1/B1 18 16
18 16 A2 18 16 A2
28 26 A2 28 26 A2

A1-A2 Supply: A1-A2 Supply: A1-A2 Supply: A1-A2 Supply:


12-240 V AC/DC 24-48 V DC or 24-48 V DC or 24-48 V DC or
A1-Y1/B1 Control input 24-240 V AC 24-240 V AC 24-240 V AC
15-16/18 1. c/o contact A1-Y1/B1 Control input 15-16/18 1. c/o contact 15-16/18 1. c/o contact
25-26/28 2. c/o contact 15-16/18 1. c/o contact 25-26/28 2. c/o contact

B CT-AHD.22 B CT-AHD.12 CA CT-VWD.12 DA CT-EBD.12


2CDC 252 116 F0b06

2CDC 252 117 F0b06

2CDC 252 180 F0b05


2CDC 252 179 F0b05
A1 15 25 A1 15 Y1/B1 A1 15 A1 15
Y1/ Y1/
B1 A1 15 25 B1 A1 15 A1 15 A1 15

A2 16 18 26 28 A2 16 18 A2 16 18 A2 16 18
18 16 Y1/B1
18 16 A2 18 16 A2 18 16 A2
28 26 A2

A1-A2 Supply: A1-A2 Supply: A1-A2 Supply: A1-A2 Supply:


24-48 V DC or 24-48 V DC or 24-48 V DC or 24-48 V DC or
24-240 V AC 24-240 V AC 24-240 V AC 24-240 V AC
A1-Y1/B1 Control input A1-Y1/B1 Control input 15-16/18 1. c/o contact 15-16/18 1. c/o contact
15-16/18 1. c/o contact 15-16/18 1. c/o contact
25-26/28 2. c/o contact

ED CT-TGD.22 ED CT-TGD.12 F CT-SDD.22 F CT-SAD.22


2CDC 252 118 F0b06

2CDC 252 119 F0b06

2CDC 252 160 F0b06

2CDC 252 160 F0b06

A1 15 25 A1 15 Y1/B1 A1 17 A1 17
Y1/ Y1/
B1 A1 15 25 B1 A1 15 A1 17 A1 17

A2 16 18 26 28 A2 16 18 A2 18 28 A2 18 28
18 16 Y1/B1
18 16 A2 28 18 A2 28 18 A2
28 26 A2

A1-A2 Supply: A1-A2 Supply: A1-A2 Supply: A1-A2 Supply:


24-48 V DC or 24-48 V DC or 24-48 V DC or 24-48 V DC or
24-240 V AC 24-240 V AC 24-240 V AC 24-240 V AC
A1-Y1/B1 Control input A1-Y1/B1 Control input 17-18 1. n/o contact 17-18 1. n/o contact
15-16/18 1. c/o contact 15-16/18 1. c/o contact (star contactor) (star contactor)
25-26/28 2. c/o contact 17-28 2. n/o contact 17-28 2. n/o contact
(delta contactor) (delta contactor)

2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 1/12
CT-D range
Technical data

Data at Ta = 25 °C and rated values, unless otherwise indicated


1
CT-D with 1 c/o CT-D with 2 c/o CT-MFD.21
contact contacts
Input circuit - Supply circuit
Rated control supply voltage U s 24-240 V AC / 24-48 V DC 12-240 V AC/DC
Rated control supply voltage U S tolerance -15...+10 %
Rated frequency DC or 50/60 Hz
Frequency range AC 47-63 Hz
Typical current / power consumption see data sheet
Power failure buffering time min. 20 ms
Release voltage > 10 % of the minimum rated control supply voltage U s
Input circuit - Control circuit
Control input, control function A1-Y1/B1 start timing external
Kind of triggering voltage-related triggering
Resistance to reverse polarity yes
Parallel load / polarized yes / yes
Maximum cable length to the control inputs 50 m ‑ 100 pF/m
Minimum control pulse length 20 ms
Control voltage potential see rated control supply voltage
Current consumption of the control input see data sheet
Timing circuit
Time ranges 7 time ranges 0.05 s - 100 h 1.) 0.05-1 s 2.) 0.5-10 s 3.) 5-100 s 4.) 0.5-10 min
5.) 5-100 min 6.) 0.5-10 h 7.) 5-100 h
4 time ranges 0.05 s - 10 min (CT-SDD, CT-SAD) 1.) 0.05-1 s 2.) 0.5-10 s 3.) 5-100 s 4.) 0.5-10 min
Recovery time < 50 ms
Accuracy within the rated control supply voltage tolerance it < 0.005 % / V
Accuracy within the temperature range it < 0.06 % / °C
Repeat accuracy (constant parameters) it < ± 0.5 %
Setting accuracy of time delay IEC/EN 61812-1 ± 10% of full-scale value
Star-delta transition time CT-SDD / CT-SAD fixed 50 ms /
adjustable: 20 ms, 30 ms, 40 ms, 50 ms, 60 ms, 80 ms or 100 ms
Star-delta transition time tolerance CT-SDD / CT-SAD ±3 ms
Indication of operational states
Control supply voltage / timing U: green LED V : control supply voltage applied
W : timing
Relay energized (1 c/o contact / R: yellow LED V : output relay energized
2 c/o contacts or inst. contact)
Operating elements and controls
Adjustment of the time range front-face rotary switch, direct reading scales
Fine adjustment of the time value front-face potentiometer
Preselection of the timing function at multifunction devices front-face rotary switch, direct reading scales
Adjustment of the transition time CT-SAD front-face potentiometer
Output circuit
Kind of output 15-16/18 Relay, 1 c/o contact -
15-16/18; 25-26/28 - Relay, 2 c/o contacts
17-18; 17-28 Relay, 2 n/o contacts (CT-SDD, CT-SAD)
Contact material AgNi alloy, Cd free
Rated operational voltage U e 250 V
Minimum switching voltage / minimum switching current 12 V / 100 mA
Maximum switching voltage / maximum switching current 250 V AC / 6 A 250 V AC / 5 A
Rated operational current I e AC-12 (resistive) at 230 V 6A 5A
(IEC/EN 60947-5-1 ) AC-15 (inductive) at 230 V 3A 3A n/o: 3 A n/c: 0.75 A
DC-12 (resistive) at 24 V 6A 5A
DC-13 (inductive) at 24 V 2A 2A 1A
AC rating (UL 508) utilization category (Control Circuit Rating Code) B 300 n/o: B 300 n/c: C 300
max. rated operational voltage 300 V AC
Maximum continuous thermal current at B300 5A n/o: 5A
Maximum continuous thermal current at C300 - n/c: 2.5 A
max. making/breaking apparent power at B300 3600 VA / 360 VA n/o: 3600/360 VA
max. making/breaking apparent power at C300 - n/c: 1800/180 VA
Mechanical lifetime 30 x 10 6 switching cycles
Electrical lifetime 0.1 x 10 6 switching cycles
Max. fuse rating to achieve short-circuit protection n/c contact 6 A fast-acting
(IEC/EN 60947-5-1) n/o contact 10 A fast-acting 6 A fast-acting

1/13 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
CT-D range
Technical data

1
CT-D with 1 c/o CT-D with 2 c/o CT-MFD.21
contact contacts
General data
Mean time between failures (MTBF) on request
Duty time 100%
Dimensions (W x H x D) 17.5 x 70 x 58 mm 17.5 x 80 x 58 mm
(0.69 x 2.76 x 2.28 in) (0.69 x 3.15 x 2.28 in)
Weight see ordering details
Mounting DIN rail (IEC/EN 60715), snap-mounting without any tool
Mounting position any
Minimum distance to other units horizontal / vertical no / no
Degree of protection housing / terminals IP50 / IP20
Electrical connection
Wire size fine-strand with(out) wire end ferrule 2 x 0.5-1.5 mm 2 (2 x 20-16 AWG)
1 x 0.5-2.5 mm 2 (1 x 20-14 AWG)
rigid 2 x 0.5-1.5 mm 2 (2 x 20-16 AWG)
1 x 0.5-4 mm 2 (1 x 20-12 AWG)
Stripping length 7 mm (0.28 in)
Tightening torque 0.5-0.8 Nm (4.43-7.08 lb.in)
Environmental data
Ambient temperature range operation / storage -20 ... +60 °C / -40 ... +85 °C
Climatic class IEC/EN 60068-2-30 3K3
Relative humidity range 25-85%
Shock (half-sine) IEC/EN 60068-2-27 150 m/s 2, 11 ms
Isolation data
Rated impulse withstand voltage U imp IEC/EN 60664-1 type test: 4 kV; 1.2/50 µs
between all isolated circuits
Pollution category IEC/EN 60664-1 3
Overvoltage category IEC/EN 60664-1 III
Rated insulation voltage U i input circuit / output circuit 300 V
output circuit 1 / output circuit 2 not available 300 V 300 V
Basic insulation (IEC/EN 61140) input circuit / output circuit 300 V
Protective separation input circuit / output circuit 250 V
(IEC/EN 61140, EN 50178)
Power-frequency withstand voltage test between all isolated circuits routine test: 2.5 kV; 50 Hz; 1 s
(test voltage) type test: 2.5 kV; 50 Hz; 60 s
Standards
Product standard IEC/EN 61812-1
Low Voltage Directive 2006/95/EC
EMC Directive 2004/108/EC
RoHS Directive 2011/65/EC
Electromagnetic compatibility
Interference immunity to IEC/EN 61000-6-1, IEC/EN 61000-6-2
electrostatic discharge IEC/EN 61000-4-2 Level 3 (6 kV / 8 kV)
radiated, radio-frequency, electromagnetic field IEC/EN 61000-4-3 Level 3 (10 V / m)
electrical fast transient / burst IEC/EN 61000-4-4 Level 3 (2 kV / 5 kHz)
surge IEC/EN 61000-4-5 Level 4 (2 kV L-L)
conducted disturbances, induced by radio-frequency fields IEC/EN 61000-4-6 Level 3 (10 V)
Interference emission IEC/EN 61000-6-3, IEC/EN 61000-6-4
high-frequency radiated IEC/CISPR 22, EN 55022 Class B
high-frequency conducted IEC/CISPR 22, EN 55022 Class B
„Approvals and marks“ see page 1/4.

2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 1/14
CT-D range
Technical data, Technical diagrams

Technical diagrams
1
Load limit curves
AC load (resistive) DC load (resistive)

2CDC 252 044 F0207

2CDC 252 045 F0207


DC voltage [V]
AC voltage [V]

resistive load resistive load

AC current [A] DC current [A]


CT-D.1x CT-D.1x
2CDC 252 122 F0206

2CDC 252 121 F0206


DC voltage [V]
AC voltage [V]

resistive load resistive load

AC current [A] DC current [A]


CT-D.2x CT-D.2x

Derating factor F Contact lifetime


for inductive AC load

1.0
2CDC 252 123 F0206
Switching cycles
2CDC 252 124 F0206
Derating factor F

0.9

0.8

0.7 250 V
resistive load
0.6

0.5

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
cos ϕ
Switching current [A]

1/15 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
CT-D range
Wiring notes, Dimensional drawings

Wiring notes for devices with control input


A parallel load to the control input is possible 1
L(+)

2CDC 252 102 F0b06


A1 Y1/B1

A2

N(-)

Dimensional drawings dimensions in mm

58 2.28“ 58 2.28“
0.69“ 0.2“
0.69“ 0.2“
17,5 5 43,4 1.71“
17,5 5 43,4 1.71“

80 3.15“

45 1.77“
70 2.76“

45 1.77“

2CDC 252 131 F0b06

2CDC 252 130 F0b06


CT-D devices with 1 c/o contact or 2 n/o contacts CT-D devices with 2 c/o contacts

2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 1/16
CT-E range
Product group picture

1/17 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
CT-E range
Table of contents

CT-E Range
1
Product group picture 1/17
Table of contents 1/18
Benefits and advantages 1/19
Ordering details 1/20
Function diagrams 1/22
Connection diagrams 1/27
Connection diagrams, Technical diagrams 1/28
Technical data 1/29
Wiring notes, Dimensional drawings 1/31
Notes 1/32

2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 1/18
CT-E range
Benefits and advantages

Characteristics Benefits
1 –– Diversity:
Direct reading scales 1
–– 2 multifunction timers Direct setting of the time delay without any additional
–– 56 single-function timers calculation provides accurate time delay adjustment.
–– Control supply voltages:
–– Dual range: 24 V AC/DC LEDs for status indication 2
–– Single range: 110-130 V AC, 220-240 V AC All actual operational states are displayed by front-face LEDs,
–– Wide range: 24-240 V AC/DC (CT-MFE) thus simplifying commissioning and troubleshooting.
–– Time ranges
–– 5 single ranges: 0.05-1 s, 0.1-10 s, 0.3-30 s, 3-300 s, Connection screws in M3 (Pozidrive 1) 3
0.3-30 min Easy and fast tightening and release of the connection screws
–– 8 time ranges: 0.05 s - 100 h (CT-MFE) with pozidrive, pan- or crosshead screwdriver.
–– Devices with 1 c/o (SPDT) contact (250 V / 4 A) or
solid-state output for high switching frequencies (thyristor Solid-state output 4

0.8 A) Devices with solid-state output are the perfect solution for
–– Approvals / Marks (details see page 1/4) high operation cycles.
–– A, C, R, K, E, L / a, b

Synonyms
used expression alternative expression(s) used expression alternative expression(s)
1 c/o contact SPDT voltage-related wet / non-floating
2 c/o contacts DPDT volt-free dry / floating

Operating controls

1 LEDs for status indication


U - green LED: V control supply voltage applied
1 R2: red LED: V output relay energized

2 Time range adjustment (only multifunctional devices)


2
3 Fine adjustment of the time delay
3 4 Preselection of the timing function (only multifunctional devices)

4
2CDC 252 166 F0005
1SVC 110 000 F0508

1SVC 110 000 F0500

1SVC 110 000 F0506

1 2 3 4
2CDC 252 166 F0005

A1 AL
A1

AL

1/19 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
CT-E range
Ordering details

Description
The CT-E range with its excellent price/performance ratio offers an ideal solution for serial
1
applications. 56 single-function devices with 5 different time ranges as well as 2 multifunction
timers with 6 functions and 8 time ranges offer the highest possible flexibility for almost every
application. For high operating cycles, contact-free CT-E timers with solid-state output are
available.

Ordering details
Timing Rated con- Time Con- Output Type Order code Price Weight
function trol supply ranges trol (1 pce)
voltage Input 1 pce kg (lb)
Multifunc- 8 (0.05 s -
24-240 V AC/DC M 1 c/o CT-MFE 1SVR550029R8100 0.08 (0.18)
tional 1) 100 h)

0.1-10 s 1SVR550107R1100

24 V AC/DC, 0.3-30 s 1SVR550107R4100


-
220-240 V AC 3-300 s 1SVR550107R2100
1SVR 550 029 F8100

0.3-30 min 1SVR550107R5100


ON-delay 1 c/o CT-ERE 0.08 (0.18)
0.1-10 s 1SVR550100R1100
0.3-30 s 1SVR550100R4100
110-130 V AC -
CT-MFE 3-300 s 1SVR550100R2100
0.3-30 min 1SVR550100R5100
0.1-10 s 1SVR550118R1100
24 V AC/DC 0.3-30 s 1SVR550118R4100
3-300 s 1SVR550118R2100
0.1-10 s 1SVR550110R1100
OFF-delay 110-130 V AC 0.3-30 s M 1 c/o CT-AHE 1SVR550110R4100 0.08 (0.18)
3-300 s 1SVR550110R2100
1SVR 550 111 F1100

0.1-10 s 1SVR550111R1100
220-240 V AC 0.3-30 s 1SVR550111R4100
3-300 s 1SVR550111R2100
CT-AHE 0.1-10 s 1SVR550127R1100
24 V AC/DC,
220-240 V AC 0.3-30 s 1SVR550127R4100
OFF-delay2) - 1 c/o CT-ARE 0.08 (0.18)
0.1-10 s 1SVR550120R1100
110-130 V AC
0.3-30 s 1SVR550120R4100
0.1-10 s 1SVR550137R1100
A ON-delay 24 V AC/DC,
B OFF-delay 0.3-30 s 1SVR550137R4100
220-240 V AC
CA Impulse-ON
3-300 s 1SVR550137R2100
CB Impulse-OFF Impulse-ON - 1 c/o CT-VWE 0.08 (0.18)
DA Flasher starting with ON 0.1-10 s 1SVR550130R1100
DB Flasher staring with OFF
H Pulse former 110-130 V AC 0.3-30 s 1SVR550130R4100
3-300 s 1SVR550130R2100
24 V AC/DC 1SVR550158R3100
Impulse-
110-130 V AC 0.05-1 s - 1 c/o CT-AWE 1SVR550150R3100 0.08 (0.18)
OFF2)
220-240 V AC 1SVR550151R3100

1) Functions: ON-delay, OFF-delay with auxiliary voltage, Impulse-ON, Flasher starting with ON, Flasher starting with OFF,
Pulse former
2) without auxiliary voltage, True Off-delay timer
M Control input with voltage-related triggering
- no triggering

2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 1/20
CT-E range
Ordering details

Bestellangaben
1 Timing Rated con- Time Con- Output Type Order code Price Weight
function trol supply- ranges trol (1 pce)
voltage Input
1 pce kg (lb)

0.1-10 s 1SVR550148R1100
24 V AC/DC 0.3-30 s 1SVR550148R4100
3-300 s 1SVR550148R2100
2CDC 251 125 F0004

0.1-10 s 1SVR550140R1100
Impulse- 110-130 V AC 0.3-30 s 1SVR550140R4100
M 1 c/o CT-AWE 0.08 (0.18)
OFF
3-300 s 1SVR550140R2100
CT-AWE 0.1-10 s 1SVR550141R1100
220-240 V AC 0.3-30 s 1SVR550141R4100
3-300 s 1SVR550141R2100

Flasher 24 V AC/DC,
1SVR550167R1100
staring with 220-240 V AC 0.1-10 s - 1 c/o CT-EBE 4) 0.08 (0.18)
OFF
110-130 V AC 1SVR550160R1100
0.1-10 s 1SVR550207R1100
24 V AC/DC,
0.3-30 s 1SVR550207R4100
Star-delta 220-240 V AC
change- 3-300 s CT-YDE 1SVR550207R2100
- 1 c/o 0.08 (0.18)
over twice 0.1-10 s
1) 2)
1SVR550200R1100
ON-delayed
2CDC 251 059 F0003

110-130 V AC 0.3-30 s 1SVR550200R4100


3-300 s 1SVR550200R2100

24 V AC/DC,
1SVR550217R4100
Star-delta 220-240 V AC
CT-SDE 1 n/o + CT-SDE
change-over 0.3-30 s - 0.08 (0.18)
1 n/c 2) 5)
with impuls 110-130 V AC 1SVR550210R4100
380-415 V AC 1SVR550212R4100

Multifunc- 0.1-10 s, CT-MKE


24-240V AC/DC - 1SVR550019R0000 0.08 (0.18)
tional 8) 3-300 s 3) 6)

solide-
0.1-10 s 1SVR550509R1000
state
ON-delay 24-240 V AC/DC 0.3-30 s - CT-EKE 1SVR550509R4000 0.08 (0.18)
A ON-delay
B OFF-delay 3-300 s 1SVR550509R2000
CA Impulse-ON 0.1-10 s 1SVR550519R1000
CB Impulse-OFF
DA Flasher starting with ON OFF-delay 24-240 V AC 0.3-30 s - CT-AKE 1SVR550519R4000 0.08 (0.18)
DB Flasher staring with OFF 3-300 s 1SVR550519R2000
H Pulse former
FA Star-delta change-over twice 1)
without auxiliary voltage M Control input with voltage-related triggering
ON-delayed 2)
with fixed transition time - no triggering
FC Star-delta change-over with 3)
solid-state output, functions and time range selection via external jumpers
impulse 4)
symetric ON & OFF times
DE Pulse generator starting 5)
common contact
with ON or OFF 6)
Functions: ON-delay (AC/DC), Impuls-ON (AC only), Flasher starting with OFF (AC only)

Notice
CT-...KE are solid-state timers with thyristor output for 2-wire applications. They are connected
directly in series with the control coil of contactors or relays. Voltage should not be applied
without a load connected, because there is no current limiting in the unit.

1/21 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
CT-E range
Function diagrams

Remarks
Legend Terminal designations on the device and in the diagrams 1
G Control supply voltage not applied / Output contact open The c/o contact is always designated 15-16/18.
B Control supply voltage applied / Output contact closed The n/o contacts are designated with 15-16 and 15-18.
A1-Y1/B1: Control input with voltage-related triggering Control supply voltage is always applied to terminals
A1-A2/B1.

Function of the red LED


The red LED R glows as soon as the output relay energizes
and turns off when the output relay de-energizes.

A ON-delay (Delay on make) B OFF-delay, with auxiliary voltage (Delay on break)


CT-ERE, CT-MFE CT-AHE, CT-MFE

This function requires continuous control supply voltage for


Applying control supply voltage starts timing. When the timing.
selected time delay is complete, the output relay energizes. Timing is controlled by control input A1-Y1. If the control input
If control supply voltage is interrupted, the output relay is closed, the output relay energizes. If control input A1-Y1 is
de-energizes and the time delay is reset. Interrupting control opened, the selected time delay starts. When the time delay
supply voltage before the time delay is complete, resets the is complete, the output relay de-energizes. If control input A1-
time delay. The output relay does not energize. Y1 is closed before the time delay is complete, the time delay
is reset. Timing starts again when the control input re-opens.

A1-A2/B1 A1-A2
2CDC 252 130 F0205

2CDC 252 132 F0205

15-18 A1-Y1
15-16
15-18
green LED 15-16
red LED green LED
t <t red LED
t
t = adjusted time delay
t = adjusted time delay
Minimum control pulse length: 20 ms

2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 1/22
CT-E range
Function diagrams

B OFF-delay, without auxiliary voltage CA Impulse-ON (Interval)


1 (true delay on break) CT-ARE CT-VWE, CT-MFE
The output relay energizes immediately when control sup-
The OFF-delay function without auxiliary voltage does not
ply voltage is applied and de-energizes after the selected
require continuous control supply voltage for timing.
time delay is complete. If control supply voltage is inter-
Applying control supply voltage, energizes the output relay.
rupted before the time delay is complete, the output relay
If control supply voltage is interrupted, the OFF-delay starts.
de-energizes and the time delay is reset.
When timing is complete, the output relay de-energizes. If
Control input A1-Y1 has to be jumpered, when this timing
control supply voltage is re-applied before the time delay is
function is selected.
complete, the time delay is reset and the output relay remains
energized.
Control supply voltage must be applied for the minimum CT-VWE:
energizing time (200 ms), for proper operation.
A1-A2/B1

2CDC 252 134 F0205


15-18
15-16
green LED
A1-A2/B1 red LED
2CDC 252 133 F0205

15-18 t <t
15-16
green LED t = adjusted pulse time
t
CT-MFE:
t = adjusted time delay A1-A2

2CDC 252 135 F0205


A1-Y1
15-18
15-16
green LED
red LED
t <t

t = adjusted pulse time

CB Impulse-OFF, without auxiliary voltage CB Impulse-OFF, with auxiliary voltage


(True trailing edge interval) CT-AWE (Trailing edge interval) CT-AWE

The Impulse-OFF function without auxiliary voltage does not This function requires continuous control supply voltage
require continuous control supply voltage for timing. for timing. Timing is controlled by control input A1-Y1. If
If control supply voltage is interrupted, the output relay the control input is opened, the output relay energizes and
energizes and the OFF time starts. When timing is complete, timing begins. When the selected time delay is complete,
the output relay de-energizes. If control supply voltage is the output relay de-energizes. Interrupting control supply
re-applied before the time delay is complete, the time delay is voltage or closing control input A1-Y1, before the time delay
reset and the output relay de-energizes. is complete, de-energizes the output relay and resets the time
Control supply voltage must be applied for the minimum delay.
energizing time (200 ms), for proper operation.

A1-A2 A1-A2
2CDC 252 138 F0205

2CDC 252 137 F0205

15-18 A1-Y1
15-16
15-18
green LED 15-16
red LED green LED
t red LED
t
t = adjusted pulse time
t = adjusted pulse time

1/23 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
CT-E range
Function diagrams

DA Flasher starting with ON DB Flasher starting with OFF


(Recycling equal times, ON first) CT-MFE (Recycling equal times, OFF first) CT-EBE, CT-MFE 1
Applying control supply voltage starts timing with symmetrical Applying control supply voltage starts timing with symmetrical
ON & OFF times. The cycle starts with an ON time first. ON & OFF times. The cycle starts with an OFF time first.
If control supply voltage is interrupted, the output relay If control supply voltage is interrupted, the output relay
de-energizes and the time delay is reset. de-energizes and the time delay is reset.
Control input A1-Y1 has to be open, when this timing function Control input A1-Y1 has to be jumpered, when this timing
is selected. function is selected.
CT-EBE:
A1-A2/B1

2CDC 252 140 F0205


15-18
15-16

2CDC 252 026 F0209


A1-A2 green LED
A1-Y1 red LED
15-18 t t
15-16
green LED
t = adjusted flashing time
red LED
t t

CT-MFE:

2CDC 252 023 F0209


A1-A2
t = adjusted flashing time
A1-Y1
15-18
15-16
green LED
red LED
t t

t = adjusted flashing time

H
Pulse former (Single shot)
CT-MFE
Closing the control input A1-Y1, with control supply voltage
applied, energizes the output relay for the selected ON time.
Operating the control input during timing has no effect. When
the ON time is complete, the output relay de-energizes.
Timing can be restarted by re-closing control input A1-Y1. If
control supply voltage is interrupted during timing, the output
relay de-energizes and the ON time is reset.

A1-A2
2CDC 252 136 F0205

A1-Y1
15-18
15-16
green LED
red LED
t t

t = adjusted pulse time

2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 1/24
CT-E range
Function diagrams

FA Star-delta change-over L1 F3
1 CT-YDE 95

2CDC 253 002 F0013


Applying control supply voltage energizes the star contactor F2
96

(K1) and the line contactor (K2) and begins the set starting 0
S1 21

time. When the starting time is complete, contact 15-16 22

de-energizes the star contactor (K1) Now, the fix transition I


S2 13

time starts. When the transition time is complete, contact 14

15-16 energizes the delta contactor (K3). K2


21

22
43 13 13
K1 K2 K1
44 14 14

21 21 16
K3 K1 K1T
22 22 15

A1 A1 A1 A1
K1 K1T K3 K2
A1-A2/B1
2CDC 252 133 F0206
A2 A2 A2 A2
15-18 N
15-16
Y  N
green LED
red LED Control circuit diagram
Star contactor
Delta contactor
t1 t2

t1 = adjustable starting time


t2 = fixed transition time of 50 ms

2CDC 253 009 F0012


L1 L2 L3

2CDC 253 009 F0012


1 3 5
-F1
2 4 6

1 3 5 1 3 5 1 3 5
-K2 2 4 6
-K3 2 4 6
-K1 2 4 6

1 5 4 97 95
-F2 98 96
FC Star-delta change-over 3 2 6

CT-SDE -M1
Applying control supply voltage energizes the star contactor W1 W2
V1 M V2
(K1) and the line contactor (K2) and begins the set starting U1 3~ U2

time. When the starting time is complete, contact 15-16


Power circuit diagram
de-energizes the star contactor (K1). Now, the fix transition
time starts. When the transition time is complete, contact
15-18 energizes the delta contactor (K3).
L1 F3

95
F2
2CDC 253 001 F0013

96
S1 21
0
22

A1-A2/B1 S2 13 53
2CDC 252 134 F0206

15-18
I K2
15-16 14 54
green LED 15 15 13 53
red LED K1T K1T K2 K1
16 18 14 54
Star contactor
Delta contactor
t1 t2 22 22
K3 21
K1 21
t1 = adjustable starting time
t2 = fixed transition time of 30 ms
B1 A1 A1 A1 A1
K1T K1 K3 K2
A2 A2 A2 A2
N
Y  N

Control circuit diagram

1/25 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
CT-E range
Function diagrams

Multifunction timer CT-MKE


Functions and time ranges are programmed by simply plugging in external wire jumpers. 1
A ON-delay (Delay on Make)
Without external connection. Timing begins when control supply voltage A1-A2

2CDC 252 146 F0205


is applied to terminal A1 and the load connected in series with A2. When Thyristor A1-A2

the selected time delay is complete, the load energizes. If control supply red LED
t <t
voltage is interrupted, the load de-energizes and the time delay is reset.
Interrupting supply voltage before the time delay is complete, resets the t = adjusted time delay

time delay. The load does not energize.

CA Impulse-ON (Interval)
External connection X1-X4 required. The load energizes and timing A1-A2

2CDC 252 147 F0205


starts when control supply voltage is applied to terminal A1 and the load Thyristor A1-A2

connected in series with A2. When the selected time delay is complete, red LED
t <t
the load de-energizes. Interrupting control supply voltage before the time
delay is complete, de-energizes the load and resets the time delay. t = adjusted pulse time

DA Flasher, starting with ON


External connection X1-X4 and X2-X4 required. When control supply A1-A2

2CDC 252 148 F0205


voltage is applied to terminal A1 and the load connected in series with Thyristor A1-A2

A2, the load energizes and de-energizes with the selected ON & OFF red LED

times. The ON & OFF times are equal. The cycle starts with an ON time t t

first (load energized). If control supply voltage is interrupted, the load t = adjusted flashing time
de-energizes and the time delay is reset.
A1-A2

2CDC 252 149 F0205


DB Flasher, starting with OFF Thyristor A1-A2
red LED
External connection X2-X4 required. When control supply voltage is t t

applied to terminal A1 and the load connected in series with A2, the t = adjusted flashing time
load energizes and de-energizes with the selected ON & OFF times.
The ON & OFF times are equal. The cycle starts with an OFF time first Programming the time ranges
(load de-energized). If control supply voltage is interrupted, the load X3-X4 jumpered: 0.1-10 s
de-energizes and the time delay is reset. X3-X4 open: 3-300 s

A ON-delay (Delay on make) B OFF-delay, with auxiliary voltage (Delay on break)


CT-EKE CT-AKE
Timing begins when control supply voltage is applied to The OFF-delay function with auxiliary voltage requires
terminal A1 and the load connected in series with AL. When continuous control supply voltage at terminal A1, and the
the selected time delay is complete, the load energizes. The load connected in series with AL, for timing.
green LED glows as long as the load is energized. Timing is controlled by control input Y2-A2. When the
If control supply voltage is interrupted, the load de-energizes control input is closed, the load energizes. If the control
and the time delay is reset. Interrupting control supply voltage input is opened, the selected time delay starts (minimum
before the time delay is complete, resets the time delay. The control pulse length is 20 ms). The green LED glows as long
load does not energize. as the load is energized. When the selected time delay is
complete, the load de-energizes. If control input Y2-A2 is
A1-AL
closed before the time delay is complete, the time delay is
2CDC 252 150 F0205

Thyristor A1-AL
green LED
reset and the load remains energized. Timing starts again
t <t when the control input is re-opened. Interrupting control
supply voltage resets the time delay and de-energizes the
t = adjusted time delay
load.
A1-AL
2CDC 252 001 F0213

Y2-A2
Thyristor A1-AL
green LED
t
t = adjusted time delay

Notice:
CT-...KE are solid-state timers with thyristor output for 2-wire applications. They are connected directly in series with the control coil
of contactors or relays. Voltage should not be applied without a load connected, because there is no current limiting in the unit.

2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 1/26
CT-E range
Connection diagrams

CT-MFE A CT-ERE B CT-AHE 1)


B CT-ARE
1

2CDC 252 154 F0005

2CDC 252 155 F0005


2CDC 252 152 F0005

2CDC 252 153 F0005


A1 15 Y1 A1 15 B1 A1 15 Y1 A1 15 B1

A1 15 A1 B1 15 A1 15 A1 B1 15

A2 16 18 A2 16 18 A2 16 18 A2 16 18

16 18 A2 16 18 A2 16 18 A2 16 18 A2

A1-A2 Supply: A1-A2 Supply: 220-240 V AC A1-A2 Supply: 24 V AC/DC A1-A2 Supply: 220-240 V AC or
24-240 V AC/DC or 110-130 V AC or 110-240 V AC or 110-130 V AC
A1-Y1 Control input 220-240 V AC
A1-B1 Supply: 24 V AC/DC A1-B1 Supply: 24 V AC/DC
15-16/18 c/o contact 15-16/18 c/o contact A1-Y1 Control input 15-16/18 c/o contact
15-16/18 c/o contact

CA CT-VWE CB CT-AWE CB CT-AWE 1)


DB CT-EBE
2CDC 252 156 F0b05

2CDC 252 157 F0b05

2CDC 252 159 F0005


2CDC 252 158 F0b05
A1 15 B1 A1 15 A1 15 Y1 A1 15 B1

A1 15 A1 15 A1 15 A1 B1 15

A2 B1 16 18 A2 16 18 A2 16 18 A2 16 18

16 18 A2 16 18 A2 16 18 A2 16 18 A2

Device without aux. voltage Device with aux. voltage

A1-A2 Supply: 220-240 V AC A1(+)-A2(-) Supply: 24 V AC/DC A1-A2 Supply: 24 V AC/DC A1-A2 Supply: 220-240 V AC
or 110-130 V AC or 110-240 V AC or or 110-240 V AC or
220-240 V AC or 110-130 V AC
A1-B1 Supply: 24 V AC/DC 220-240 V AC
A1-B1 Supply: 24 V AC/DC
15-16/18 c/o contact A1-Y1 Control input 15-16/18 c/o contact
15-16/18 c/o contact 15-16/18 c/o contact

FA CT-YDE FC CT-SDE FC CT-SDE CT-MKE


2CDC 252 160 F0005

2CDC 252 161 F0005

2CDC 252 162 F0005

2CDC 252 165 F0005


A1 15 B1 A1 15 B1 A1 15 A1 X1 X2
A1
A1 15 A1 15 A1 15

U
A2
A2 B1 16 18 A2 B1 16 18 A2 16 18

16 18 A2 16 18 A2 16 18 A2 X3 X4 A2

Device: 1SVR 550 217 R4100 Devices: 1SVR 550 210 R4100, A1-A2 Supply: 24-240 V AC/DC
1SVR 550 212 R4100 A1-A2 Thyristor
A1-A2 Supply: 220-240 V AC A1-A2 Supply: 220-240 V AC X1-X4 Timing function adjustment
or 110-130 V AC A1-B1 Supply: 24 V AC/DC A1-A2 Supply: 110-130 V AC X2-X4 Timing function adjustment
A1-B1 Supply: 24 V AC/DC 15-16 n/c contact or 380-415 V AC X3-X4 Time range adjustment
15-16/18 c/o contact 15-18 n/o contact 15-16 n/c contact (Details see function diagrams)
with common contact 15-18 n/o contact
with common contact

1)
“„Wiring notes, Dimensional drawings“ see page 1/31.

1/27 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
CT-E range
Connection diagrams, Technical diagrams

A CT-EKE B CT-AKE
1

2CDC 252 167 F0005


2CDC 252 166 F0005
A1 AL A1 AL
A1 A1
Y2

AL AL
A2

Y2 A2

A1-AL Supply: 24-240 A1-AL Supply: 24-240 V AC


V AC/DC A1-AL Thyristor
A1-AL Thyristor Y2-A2 Control input

Technical diagrams

Load limit curves


AC load (resistive) DC load (resistive)
V V

2CDC 252 193 F0205


2CDC 252 194 F0205

300 300
U 200 U 200

100 100
80 80
60 60
50 50
40 40
30 30
20 20

10 10
0,1 0,2 0,5 1 2 4 6 10 0,1 0,2 0,5 1 2 4 6 10
I A I A

220 V 50 Hz AC1
360 cycles/h

Derating factor F for inductive AC load Contact lifetime


1,0
2CDC 252 192 F0205

106
2CDC 252 034 F0208

0,9 9
8
0,8 N
5
F 4
0,7 3
0,6 2

0,5
105
1 2 3 4 5 6 7 8
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 I A
cos ϕ

2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 1/28
CT-E range
Technical data

Technical data
1 Data at Ta = 25 °C and rated values, unless otherwise indicated
CT-E (relays) CT-E (solid-state)
Input circuit - Supply circuit
Rated control supply voltage U s A1-A2, A1-AL 24-240 V AC/DC
A1-A2, A1-AL 24-240 V AC
A1-A2 110-130 V AC -
A1-A2 220-240 V AC -
A1-A2 380-415 V AC -
A1-B1 24 V AC/DC -
Rated control supply voltage U s tolerance -15...+10 %
Rated frequency AC/DC versions DC or 50/60 Hz
AC versions 50/60 Hz
Typical current / power consumption 24-240 V AC/DC, 24-240 V AC approx. 1.0-2.0 VA/W
110-130 V AC, 220-240 V AC approx. 2.0 VA -
380-415 V AC approx. 3.0 VA -
24 V AC/DC approx. 1.0 VA/W -
Minimum energizing time CT-ARE, CT-AWE w/o aux. voltage 200 ms -
Current consumption while timing - ≤ 2 mA (24-60 V AC/DC)
≤ 8 mA (60-240 V AC/DC)
(CT-AKE only AC)
Input circuit - Control circuit
Kind of triggering voltage-related triggering -
Control input, Control function A1-Y1 start timing external -
Parallel load / polarized no / yes 1) -
Minimum control pulse length 20 ms -
Control voltage potential see rated control supply voltage -
Timing circuit
Time ranges 1 of 5 time ranges per single-function device 0.05-1 s / 0.1-10
s / 0.3-30 s / 3-300 s / 0.3-30 min
8 time ranges 0.05 s - 100 h (CT-MFE) 1.) 0.05-1 s 2.) 0.5-10 s -
3.) 5-100 s4.) 50-1000 s
5.) 0.5-10 min
6.) 5-100 min
7.) 0.5-10 h
8.) 5-100 h
2 time ranges 0.1-300 s (CT-MKE) - 1.) 0.1-10 s
2.) 3-300 s
Recovery time <50 ms CT-EKE: <50 ms
CT-ARE: <200 ms CT-MKE: <100 ms
CT-AWE, CT-SDE: <400 ms CT-AKE: <300 ms
CT-YDE: <500 ms
Accuracy within the rated control supply voltage tolerance it < 0.5 % / V
Accuracy within the temperature range it < 0.1 % / °C
CT-MFE: it <0.06 % / °C -
Repeat accuracy (constant parameters) it < 1 %
Star-delta transition time CT-YDE / CT-SDE 50 ms / 30 ms -
Output circuit
Kind of output 15-16/18 Relay, 1 c/o contact -
CT-SDE: 15-16, 15-18 1 n/c, 1 n/o contact with common
contact
A1-A2. A1-AL - Thyristor
Contact material AgCdO -
Rated operational voltage U e IEC/EN 60947-1 250 V
Maximum switching voltage 250 V AC, 250 V DC
Rated operational current I e AC-12 (resistive) at 230 V 4A -
(IEC/EN 60947-5-1) AC-15 (inductive) at 230 V 3A -
DC-12 (resistive) at 24 V 4A -
DC-13 (inductive) at 24 V 2A -

1)
CT-MFE: yes / no

1/29 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
CT-E range
Technical data

CT-E (relays) CT-E (solid-state)


AC rating (UL 508) Utilization category (Control Circuit Rating Code) B 300 - 1
max. rated operational voltage 300 V AC -
Maximum continuous thermal current at B300 5A -
max. making/breaking apparent power at B300 3600 VA / 360 VA -
Mechanical lifetime 30 x 10 6 switching cycles -
Electrical lifetime at AC-12, 230 V, 4 A 0.1 x 10 6 switching cycles -
Max. fuse rating to achieve short-circuit n/c contact 10 A fast-acting, CT-ARE: 5 A -
protection (IEC/EN 60947-5-1) n/o contact 10 A fast-acting, CT-ARE: 5 A -
Minimum load current - CT-MKE: 20 mA
CT-EKE, CT-AKE: 10 mA
Maximum load current - CT-MKE: 0.8 A at Ta = 20 °C
CT-EKE, CT-AKE: 0.7 A
Load current reduction / Derating - 10 mA/°C
Maximum surge current - CT-MKE: ≤ 20 A for t ≤ 20 ms
CT-EKE, CT-AKE: ≤ 15 A
Voltage drop in connected state - ≤3V
Cable length between solid-state timer at 24 V AC - 220 m / 22 nF
and connected load at 50 Hz and a at 42 V AC - 100 m / 10 nF
cable capacity of 100 pF/m : at 60 V AC - 65 m / 6.5 nF
at 110 V AC - 50 m / 5 nF
at 240 V AC - 22 m / 2.2 nF
General data
Duty time 100%
Dimensions (W x H x D) 22.5 x 78 x 78.5 mm (0.886 x 3.07 x 3.09 in)
Weight approx. 80 g (0.176 lb)
Mounting DIN rail (IEC/EN 60715)
Mounting position any
Minimum distance to other units horizontal / vertical no / no
Degree of protection housing / terminals IP50 / IP20
Electrical connection
Wire size fine-strand with wire end ferrule 2 x 0.75-1.5 mm 2 (2 x 18-16 AWG)
fine-strand without wire end ferrule 2 x 1-1.5 mm 2 (2 x 18-16 AWG)
rigid 2 x 0.75-1.5 mm 2 (2 x 18-16 AWG)
Stripping length 10 mm (0.39 in)
Tightening torque 0.6-0.8 Nm (5.31-7.08 lb.in)
Environmental data
Ambient temperature ranges operation / storage -20...+60 °C / -40...+85 °C
Damp heat IEC/EN 60068-2-30 24 h cycle, 55 °C, 93 % rel., 96 h
Operational reliability IEC/EN 60068-2-6 6g
Mechanical resistance IEC/EN 60068-2-6 10 g
Isolation data
Rated impulse withstand voltage U imp IEC/EN 60664-1 type test: 4 kV; 1.2/50 µs -
between all isolated circuits
Pollution category IEC/EN 60664-1 3
Overvoltage category IEC/EN 60664-1 III
Power-frequency withstand voltage (test routine test: 2.5 kV; 50 Hz; 1 s -
voltage) between all isolated circuits type test: 2.5 kV; 50 Hz; 60 s
Basic insulation (IEC/EN 61140) input circuit / output circuit 300 V -
Rated insulation voltage U i input circuit / output circuit 300 V (supply up to 240 V) -
500 V (supply up to 440 V) -
Test voltage between all isolated circuits routine test 2.5 kV, 50 Hz, 1 s -
Standards
Product standard IEC 61812-1, EN 61812-1 + A11, DIN VDE 0435 Teil 2021
Low Voltage Directive 2006/95/EC
EMC Directive 2004/108/EC
Electromagnetic compatibility
Interference immunity to IEC/EN 61000-6-2
electrostatic discharge IEC/EN 61000-4-2 Level 3 (6 kV / 8 kV)
radiated, radio-frequency IEC/EN 61000-4-3 Level 3 (10 V/m)
electromagnetic field
electrical fast transient / burst IEC/EN 61000-4-4 Level 3 (2 kV / 5 kHz)
surge IEC/EN 61000-4-5 Level 4 (2 kV L-L)
conducted disturbances, induced by radio- IEC/EN 61000-4-6 Level 3 (10 V)
frequency fields
Interference emission IEC/EN 61000-6-4
„Approvals and marks“ see page 1/4.

2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 1/30
CT-E range
Wiring notes, Dimensional drawings

Wiring notes
1 for single-function devices with control contact (CT-AHE, CT-AWE with auxiliary voltage)

2CDC 252 200 F0b05

2CDC 252 199 F0b05


I I

A1 Y1
A1 Y1
U I
U

A2
A2
2CDC 252 198 F0b05

2CDC 252 201 F0b05


I

A1 Y1 I
I
U U A1 Y1

A2

A2

Dimensional drawing Dimensions in mm

88,5 3.48“ 22,5


.886“
81 3.19“
2CDC 252 189 F0b05
78 3.07“

78,5 3.09“

1/31 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
CT-E range
Notes

2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 1/32
CT-S range
Product group picture

1/33 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
CT-S range
Table of contents

CT-S Range
1
Product group picture 1/33
Table of contents 1/34
Benefits and advantages 1/35
Ordering details - multifunctional 1/37
Ordering details - singlefunctional 1/38
Ordering details - Accessories 1/39
Ordering details - Accessories 1/40
Function diagrams 1/41
Connection diagrams 1/49
Technical data 1/52
Technical diagrams 1/55
Wiring notes, Dimensional drawings 1/56

2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 1/34
CT-S range
Benefits and advantages

Characteristics
1 –– Diversity:
–– 8 multifunction timers
–– 13 single-function timers
–– Control supply voltages:
–– Multi range: 24-48 V DC, 24-240 V AC
–– Wide range: 24-240 V AC/DC
–– Single range: 380-440 V AC
–– Innovative connection technology
–– Double-chamber cage connection terminals
–– Easy Connect Technology
–– Devices with:
–– 1 or 2 c/o (SPDT) contacts
–– 2nd c/o contact can be selected as instantaneous contact 1)
–– Remote potentiometer connection 1)
–– Control input with volt-free or voltage-related triggering e.g. to start timing, pause timing
–– Extended operating temperature range down to -40 °C 1)
–– Sealable transparent cover for protection against unauthorized changes of time values
–– Integrated marker label
–– Approvals / Marks (partly pending, details see page 1/4)
–– A, C, , E, K, L / a, b
1) selected devices

Operating controls

1 2nd contact as an instantaneous contact


2 Preselection of the time range

3 Indication of operational states


U/T: V control supply voltage applied / W timing
R: V Output relay energized
1
4 Fine adjustment of time delay
4 Preselection of timing function
2
Marker label

1/35 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
CT-S range
Benefits and advantages

Easy Connect Technology 1 LEDs for status indication 5

Tool-free wiring and excellent vibration resistance. Push-in All actual operational states are displayed by front-face LEDs, 1
terminals provide connection of wires up to 2 x 0.5 - 1.5 mm² thus simplifying commissioning and troubleshooting.
(2 x 20 -16 AWG), rigid or fine-strand with or without wire
end ferrules. The extended type designators for products with Integrated marker label 6
push-in terminals are indicated by a P following the extended Integrated marker labels allow the product to be marked
type designator e.g. CT-xxS.xxP. quickly and simply. No additional marker labels are required.

Double-chamber cage connection terminals 2 Sealable transparent cover 7


Double-chamber cage connection terminals provide Protection against unauthorized changes of time and
connection of wires up to 2 x 0.5-2.5 mm² (2 x 20-14 AWG) threshold values. Available as an accessory.
rigid or fine-strand, with or without wire end ferrules. Potential
distribution does not require additional terminals. The Snap-On housing 8
extended type designators for products with double-chamber Tool-free DIN rail installation and deinstallation of the
cage connection terminals are indicated by a S following the electronic timer.
extended type designator e.g. CT-xxS.xxS.

Time range preselection and fine adjustment 3


Direct assignment of the preselected time range to the fine
adjustment potentiometer scale by multicolor scales.

Higher utility class 4

The Easy Connect Technology provides excellent vibra-


tion resistance with gas tight push-in terminals – the right
solution for harsh environment. Selected products of the
electronic timers and measuring and monitoring relays comply
to the latest rail standards NF F 16-101/102, EN 45545, EN
50155 and more standards which are relevant for railway
applications. Find more inforamtion in the rail brochure
2CDC110084B0201.
2CDC 253 026 F0011

2CDC 253 035 F0011

2CDC 252 006 F0012

2CDC 255 006 S0011

1 3 5 7
2CDC 253 007 F0012

2CDC 253 013 F0013


2CDC 253 025 F0011

2 4 6 8

2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 1/36
CT-S range
Ordering details - multifunctional

Description
1 The highly sophisticated CT-S range in ABB’s new S-range housing offers two different
types of connection terminals and is ideally suited for universal use. Two different connection
technologies are available:
–– Double-chamber cage connection terminals
2CDC 251 024 V0011

–– Easy Connect Technology


Accessories:
The CT-S range offers the possibility of using accessories such as a remote potentiometer to
adjust the time delay or a sealable, transparent cover to protect against unauthorized changes.
of time and threshold values.
CT-MVS.21P
Ordering details
Timing Rated Time Control Output Type Order code Price Weight
function control ranges input (1 pce)
supply volt-
age 1 pce kg (lb)
CT-MVS.21S 0.148
1SVR730020R0200
1) 2) 3)
(0.326)
24- 240 V AC/DC
CT-MVS.21P 0.136
1SVR740020R0200
1) 2) 3)
(0.30)
0.142
2CDC 251 023 V0011

CT-MVS.22S 1SVR730020R3300
Multifunc- 24-48 V DC, 10 (0.05 s - (0.313)
M 2 c/o
tional 5) 24-240 V AC 300 h) 0.131
CT-MVS.22P 1SVR740020R3300
(0.289)
0.144
CT-MVS.23S 1SVR730021R2300
(0.317)
380-440 V AC
0.133
CT-MBS.22P CT-MVS.23P 1SVR740021R2300
(0.293)
0.107
CT-MVS.12S 1SVR730020R3100
Multifunc- 24-48 V DC, 10 (0.05 s - (0.236)
M 1 c/o
tional 6) 24-240 V AC 300 h) 0.102
CT-MVS.12P 1SVR740020R3100
(0.225)
0.142
CT- MXS.22S ) 4
1SVR730030R3300
Multifunc- 24-48 V DC, 2×10 (0.05 s - (0.313)
M 2 c/o
tional 7) 24-240 V AC 300 h) 0.131
CT-MXS.22P 4) 1SVR740030R3300
(0.289)
CT-MFS.21S 0.145
1SVR730010R0200
10 (0.05 s - 1) 2) 3)
(0.32)
24- 240 V AC/DC n/n 2 c/o
300 h) CT-MFS.21P 0.133
1SVR740010R0200
Multifunc- 1) 2) 3)
(0.293)
tional 8) 0.14
CT-MBS.22S 2) 3)
1SVR730010R3200
24-48 V DC, 10 (0.05 s - (0.309)
n/n 2 c/o
24-240 V AC 300 h) 0.129
CT-MBS.22P 2) 3) 1SVR740010R3200
(0.284)
0.123
CT-WBS.22S 1SVR730040R3300
Multifunc- 24-48 V DC, 10 (0.05 s - (0.271)
- 2 c/o
tional 9) 24-240 V AC 300 h) 0.115
A(+) ON-delay (accumulative) CT-WBS.22P 1SVR740040R3300
(0.254)
B OFF-delay without aux. voltage
CA Impulse-ON
CB Impulse-OFF M Control input with voltage-related triggering
AB Symmetrical ON-delay and m Control input with volt-free triggering
OFF-delay m / m two control input with volt-free triggering
DA Flasher starting with ON 1)
Extended temperature range -40 °C - no triggering
DB Flasher staring with OFF 2)
Remote potentiometer connection
S: screw connection
DE Pulse generator starting 3)
2nd c/o contact selectable as instantaneous contact
P: push-in / easy connect
FC Star-delta change-over with 4)
2 remote potentiometer connections
impulse 5)
Functions: ON-delay, OFF-delay with auxiliary voltage, Impulse-ON, Impulse-OFF with auxiliary voltage, Symmetrical ON- and
H Pulse former OFF-delay, Flasher starting with ON or OFF, Star-delta change-over with impulse, Pulse former, Accumulative ON-delay, ON/
G ON/OFF-function OFF-function
FA Star-delta change-over twice 6)
Functions: ON-delay, OFF-delay with auxiliary voltage, Impulse-ON, Impulse-OFF with auxiliary voltage, Symmetrical ON- and
ON-delayed OFF-delay, Flasher starting with ON or OFF, Pulse former, Accumulative ON-delay, ON/OFF-function
with ON or OFF 7)
Functions: Select function via DIP switches behind the marker label on the front of the unit, asymmetrical ON- and OFF-delay,
ED Pulse generator starting with Impulse-ON/OFF, Pulse generator starting with ON or OFF, Single pulse generator, ON/OFF-function
ON or OFF 8)
Functions: ON-delay, OFF-delay with auxiliary voltage, Impulse-ON, Impulse-OFF with auxiliary voltage, Symmetrical ON- and
EC Single-pulse generator OFF-delay, Flasher starting with ON, Flasher starting with OFF, Star-delta change-over with impulse, Pulse former, ON/OFF-
CE Impulse-ON/OFF function
DA Flasher starting with ON 9)
Functions: Flasher starting with ON, Flasher starting with OFF, Impulse-ON, ON-delay, fixed impulse with adjustable time delay,
DB Flasher starting with OFF Adjustable impulse with fixed time delay, ON/OFF-function
AC fixed impulse with adjustable
time delay
BC Adjustable impulse with fixed
time delay

1/37 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
CT-S range
Ordering details - singlefunctional

Timing Rated con- Time Con- Output Type Order code Price Weight
function trol supply ranges trol (1 pce) 1
voltage input
1 pce kg (lb)
0.13
2CDC 251 030 V0011

CT-ERS.21S 1) 1SVR730100R0300
(0.287)
24-240 V AC/DC
0.121
CT-ERS.21P 1)
1SVR740100R0300
(0.267)
- 2 c/o
0.121
CT-ERS.22S 1SVR730100R3300
24-48 V DC, 10 (0.05 s - (0.267)
ON-delay
24-240 V AC 300 h) 0.113
CT-ERS.22P 1SVR740100R3300
CT-ERS.21P (0.249)
0.106
CT-ERS.12S 1SVR730100R3100
24-48 V DC, (0.234)
- 1 c/o
24-240 V AC 0.101
CT-ERS.12P 1SVR740100R3100
(0.222)
0.146
CT-APS.21S 1)
1SVR730180R0300
(0.322)
24-240 V AC/DC
0.125
CT-APS.21P1) 1SVR740180R0300
(0.276)
M 2 c/o
0.138
2CDC 251 033 V0011

CT-APS.22S 1SVR730180R3300
10 (0.05 s - (0.304)
300 h) 0.127
CT-APS.22P 1SVR740180R3300
24-48 V DC, (0.28)
OFF-delay
24-240 V AC 0.109
CT-APS.12S 1SVR730180R3100
(0.24)
M 1 c/o
0.103
CT-APS.12P 1SVR740180R3100
(0.227)
CT-AHS.22P 0.136
CT-AHS.22S 1SVR730110R3300
24-48 V DC, 10 (0.05 s - (0.30)
M 2 c/o
24-240 V AC 300 h) 0.125
CT-AHS.22P 1SVR740110R3300
(0.276)
0.106
CT-ARS.11S 1SVR730120R3100
(0.234)
- 1 c/o
0.10
CT-ARS.11P 1SVR740120R3100
24-240  7 (0.05 s - (0.22)
OFF-delay5)
V AC/DC 10 min) 0.124
CT-ARS.21S 1SVR730120R3300
(0.273)
- 2 c/o
2CDC 251 040 V0011

0.115
CT-ARS.21P 1SVR740120R3300
(0.254)
0.114
CT-SDS.22S 1SVR730210R3300
24-48 V DC, (0.251)
24-240 V AC 0.108
CT-SDS.22P 1SVR740210R3300
Star-delta 7 (0.05 s - (0.238)
- 2 n/o
change-over 6) 10 min) 0.118
CT-SDS.23P CT-SDS.23S 1SVR730211R2300
(0.26)
380-440 V AC
0.112
CT-SDS.23P 1SVR740211R2300
(0.247)
1)
Extended temperature range -40 °C M Control input with voltage-related triggering
2)
Remote potentiometer connection m Control input with volt-free triggering
A(+) ON-delay (accumulative) 3)
2nd c/o contact selectable as instantaneous contact m / m two control input with volt-free triggering
B OFF-delay without aux.voltage 4)
2 remote potentiometer connections - no triggering
CA Impulse-ON 5)
Without auxiliary voltage
S: screw connection
DA Flasher starting with ON 6)
50 ms transition time
P: push-in / easy connect
DB Flasher staring with OFF
CE Impulse-ON/OFF
DA Flasher starting with ON
DB Flasher starting with OFF
AC fixed impulse with adjustable
time delay
BC Adjustable impulse with fixed
time delay
F Star-delta change-over

2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 1/38
CT-S range
Ordering details - Accessories

Remote potentiometer
1 50 kq ±20 % - 0.2 q, degree of protection IP66
2CDC 252 041 F0009

Material Diameter Type Order code Price Pack.- Weight


unit 1 piece
in mm 1 piece pieces g / oz
Plastic, black 22.5 MT-150B 1SFA611410R1506 1 0.040
MT-x50B Plastic, chrome 22.5 MT-250B 1SFA611410R2506 1 0.040
Metal, chrome 22.5 MT-350B 1SFA611410R3506 1 0.048
2CDC 252 042 F0009

CT-S time relay Potentiometers

Z1
Z3

2CDC 252 040 F0209


30 mm adapters 2CDC 252 039 F0009

Z2
2CDC 252 043 F0209

Note: The connections of the potentiometer


are not marked.

Note: Technical specifications see data sheet

Marker label 29.6 x 44.5 mm

30 mm adapter for attaching the potentiometer 22 mm in 30 mm mounting hole


Material Type Order code Price Pack.- Weight
2CDC 252 044 F0209

unit 1 piece
1 piece pieces g / oz
Plastic, black KA1-8029 1SFA616920R8029 1
Marker label with scale 0-10 Metal, chrome KA1-8030 1SFA616920R8030 1
48.5 x 44.5 mm

12 15
18
Marker label
2CDC 252 045 F0209

9 21 Caption Type Order code Price Pack.- Weight


6 24 unit 1 piece
3 27
1 piece pieces g / oz
0 30 Symbol (see illustration) SK 615 562-87 GJD6155620R0087 1 0.002
Marker label with scale 0-30
Scale 0 - 10 SK 615 562-88 GJD6155620R0088 1 0.002
48.5 x 44.5 mm
Scale 0 - 30 MA16-1060 1SFA611940R1060 1 0.002

1/39 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
CT-S range
Ordering details - Accessories

Accessories for CT-S in new housing (1SVR7...)


Description Type Order code Price Pack.- Weight 1
0.453”

2CDC 252 008 F0010


11.5

unit 1 piece
0.256”

62.5 2.461” 1 piece pieces g / oz


6.5

Adapter for screw mounting ADP.01 1SVR430029R0100 1 0.018 (0.040)


0.394”

0.787”
10

20

Sealable transparent cover COV.11 1SVR730005R0100 1 0.004 (0.009)


60 2.362”
70 2.756” Marker label for devices w/o DIP switches MAR.01 1SVR366017R0100 10 0.001 (0.002)
Marker label for devices with DIP switches MAR.12 1SVR730006R0000 10 0.001 (0.002)
ADP.01

7 .275”
2CDC 252 185 F0005

22,5
3,5 .138”
.886”
68,5 2.70 ”

Accessories for CT-S in old housing (1SVR4...)


Description Type Order code Price Pack.- Weight
unit 1 piece
1 piece pieces g / oz
front-to-back
size 107 Adapter for screw mounting ADP.01 1SVR430029R0100 1 0.018 (0.040)
COV.01
Sealable transparent cover COV.01 1SVR430005R0100 1 0.004 (0.009)
Marker label for devices w/o DIP switches MAR.01 1SVR366017R0100 10 0.001 (0.002)
0.315”
2CDC 252 186 F0005

3A11
8

Marker label for devices with DIP switches MAR.02 1SVR430043R0000 10 0.001 (0.002)
20
0.787”
MAR.01

8 0.32”
22.5 0.89” 4.8 0.19”
68 2.68”

2CDC 252 010 F0011

front to back
110.5 4.31”
COV.11

4T22
0.314“
8

2CDC 252 010 F0010

18 0.709“
21 0.827“

MAR.02

22.2
0.874”

4T22
2CDC 252 020 F0010
0.309”
7.85

19.9
0.783”

MAR.12

2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 1/40
CT-S range
Function diagrams

Remarks
1 Legend Terminal designations on the device and in the diagrams:
G Control supply voltage not applied / Output contact open The 1st c/o contact is always designated 15-16/18.
B Control supply voltage applied / Output contact closed The 2nd c/o contact is designated 25-26/28, if it responds to
the time delay.
A1-Y1/B1 Control input with voltage-related triggering
If the 2nd c/o contact is selected as an instantaneous con-
Y1-Z2 Control input with volt-free triggering
X1-Z2 Control input with volt-free triggering
tact, the designation 25-26/28 is replaced by 21-22/24.
Control supply voltage is always applied to terminals A1-A2.
Remote potentiometer connection:
When an external potentiometer is connected to the remote Function of the yellow LEDs:
potentiometer connection (terminals Z1-Z2, Z3-Z2 respective- On devices without the function ‘2nd c/o contact selectable
ly), the internal, front-face potentiometer is disabled and the as instantaneous contact’, the yellow LED R glows as soon as
time adjustment is made via the external potentiometer. the output relay energizes and turns off when the output relay
de-energizes.
2nd c/o contact selectable as instantaneous contact:
Devices with the function ‘2nd c/o contact selectable as
When switch position Inst. “I” is selected, the functionality of
instantaneous contact’ have two yellow LEDs, designated R1
the 2nd c/o contact changes to an instantaneous contact.
and R2. LED R1 shows the status of the 1st c/o contact (15-
It acts like the c/o contacts of a switching relay, i.e. apply-
16/18) and LED R2 shows the status of the 2nd c/o contact
ing or interrupting the control supply voltage energizes or
(25-26/28, 21-22/24 resp.). LED R1 or R2 glow as soon as
de-energizes the c/o contact. The designation of the 2nd c/o
the corresponding output relay energizes and turns off when
contact changes from 25-26/28 to 21-22/24, when selected
the corresponding output relay de-energizes.
as instantaneous contact.

A ON-delay A ON-delay
(Delay on make) (Delay on make)
CT-MVS, CT-ERS, CT-WBS CT-MFS, CT-MBS

This function requires continuous control supply voltage for This function requires continuous control supply voltage for
timing. timing.
Timing begins when control supply voltage is applied. The If control input Y1-Z2 is open, timing begins when control
green LED flashes during timing. When the selected time supply voltage is applied. Or, if control supply voltage is
delay is complete, the output relay energizes and the flash- already applied, opening control input Y1-Z2 also starts tim-
ing green LED turns steady. ing. The green LED flashes during timing. When the selected
If control supply voltage is interrupted, the output relay de- time delay is complete, the output relay energizes and the
energizes and the time delay is reset. flashing green LED turns steady.
If control input Y1-Z2 closes before the time delay is com-
A1-A2 plete, the time delay is reset and the output relay remains
2CDC 252 017 F0206

15-18, 25-28
15-16, 25-26 de-energized.
21-24
21-22
Pause timing / Accumulative ON-delay (CT-MFS):
green LED Timing can be paused by closing control input X1-Z2. The
t <t
elapsed time t1 is stored and continues from this time value
t = adjusted time delay when X1-Z2 is re-opened. This can be repeated as often as
required.
If control supply voltage is interrupted, the output relay de-
energizes and the time delay is reset.
A1-A2
2CDC 252 018 F0206

Y1-Z2
15-18, 25-28
15-16, 25-26
21-24
21-22
X1-Z2
green LED
t t1 t3 t2

t = adjusted time delay t1 + t2 = t


t3 = pause timing

1/41 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
CT-S range
Function diagrams

A+
Accumulative ON-delay B OFF-delay with auxiliary voltage
(Accumulative delay on make) (Delay on break) 1
CT-MVS CT-MFS, CT-MBS, CT-AHS

This function requires continuous control supply voltage for This function requires continuous control supply voltage for
timing. timing.
Timing begins when control supply voltage is applied. The If control input Y1-Z2 is closed, the output relay energizes
green LED flashes during timing. When the selected time immediately. If control input Y1-Z2 is opened, the time delay
delay is complete, the output relay energizes and the flashing starts. The green LED flashes during timing. When the se-
green LED turns steady. lected time delay is complete, the output relay de- energizes
Timing can be paused by closing control input A1-Y1/B1. The and the flashing green LED turns steady.
elapsed time t1 is stored and continues from this time value If control input Y1-Z2 closes before the time delay is com-
when A1-Y1/B1 is re-opened. plete, the time delay is reset and the output relay does not
This can be repeated as often as required. change state. Timing starts again when control input Y1-Z2
If control supply voltage is interrupted, the output relay de- re-opens.
energizes and the time delay is reset. Pause timing / Accumulative OFF-delay (CT-MFS):
Timing can be paused by closing control input X1-Z2. The
A1-A2 elapsed time t1 is stored and continues from this time value
2CDC 252 043 F0206

A1-Y1/B1 when X1-Z2 is re-opened.


15-18, 25-28
15-16, 25-26 This can be repeated as often as required.
21-24
21-22
If control supply voltage is interrupted, the output relay de-
green LED energizes and the time delay is reset.
t t1 t3 t2
A1-A2

2CDC 252 019 F0206


t = adjusted time delay t1 + t2 = t Y1-Z2
t3 = pause timing
15-18, 25-28
15-16, 25-26
21-24
21-22
X1-Z2
green LED
t t1 t3 t2

t = adjusted time delay t1 + t2 = t


t3 = pause timing

B OFF-delay with auxiliary voltage B OFF-delay without auxiliary voltage


(Delay on break) (True delay on break)
CT-MVS, CT-APS CT-ARS

This function requires continuous control supply voltage for The OFF-delay function without auxiliary voltage does not
timing. require continuous control supply voltage for timing. After a
If control input A1-Y1/B1 is closed, the output relay energizes storage time of several months without any voltage, a format-
immediately. If control input A1-Y1/B1 is opened, the time ting time of about 5 minutes is necessary.
delay starts. The green LED flashes during timing. When the Applying control supply voltage energizes the output relay
selected time delay is complete, the output relay de-energizes immediately. Applied control supply voltage is displayed by
and the flashing green LED turns steady. the glowing green LED. If control supply voltage is interrupted,
If control input A1-Y1/B1 recloses before the time delay is the OFF-delay starts and the LED turns off. When timing is
complete, the time delay is reset and the output relay does complete, the output relay de-energizes.
not change state. Timing starts again when control input A1- For correct operation of the unit, it is necessary to complete
Y1/B1 re-opens. the minimum energizing time. As soon as timing starts, the
If control supply voltage is interrupted, the output relay de- LED turns off.
energizes and the time delay is reset.

A1-A2
2CDC 252 020 F0206

A1-A2
2CDC 252 021 F0206

A1-Y1/B1
15-18, 25-28
15-18, 25-28 15-16, 25-26
15-16, 25-26
green LED
21-24
21-22 t

green LED
t <t t = adjusted time delay

t = adjusted time delay

2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 1/42
CT-S range
Function diagrams

AB Symmetrical ON-delay and OFF-delay AB


Symmetrical ON-delay and OFF-delay
1 (Symmetrical delay on make and delay on break) (Symmetrical delay on make and delay on break)
CT-MFS, CT-MBS CT-MVS

This function requires continuous control supply voltage for This function requires continuous control supply voltage for
timing. timing.
Closing control input Y1-Z2 starts the ON-delay t1. When tim- Closing control input A1-Y1/B1 starts the ON-delay t1. When
ing is complete, the output relay energizes. Opening control timing is complete, the output relay energizes. Opening
input Y1-Z2 starts the OFF-delay t2. Both timing functions are control input A1-Y1/B1 starts the OFF-delay t2. Both timing
displayed by the flashing green LED. When the OFF-delay t2 is functions are displayed by the flashing green LED. When the
complete, the output relay de-energizes. OFF-delay t2 is complete, the output relay de-energizes.
If control input Y1-Z2 opens before the ON-delay t1 is com- If control input A1-Y1/B1 opens before the ON-delay t1 is
plete, the time delay is reset and the output relay remains de- complete, the time delay is reset and the output relay re-
energized. If control input Y1-Z2 closes before the OFF-delay mains de-energized. If control input A1-Y1/B1 closes before
t2 is complete, the time delay is reset and the output relay the OFF-delay t2 is complete, the time delay is reset and the
remains energized. output relay remains energized.
Pause timing / Accumulative, symmetrical ON-delay and If control supply voltage is interrupted, the output relay de-
OFF-delay (CT-MFS): Timing can be paused by closing control energizes and the time delay is reset.
input X1-Z2. The elapsed time t1a or t2a is stored and contin-
ues from this time value when X1-Z2 is re-opened. This can
be repeated as often as required. A1-A2

2CDC 252 023 F0206


If control supply voltage is interrupted, the output relay de- A1-Y1/B1

energizes and the time delay is reset. 15-18, 25-28


15-16, 25-26
21-24
21-22
A1-A2
2CDC 252 022 F0206

green LED
Y1-Z2 t1 t2 t1 < t2
15-18, 25-28
15-16, 25-26
t1 = adjusted ON-delay
21-24 t2 = adjusted OFF-delay
21-22
t1 = t2
X1-Z2
green LED
t1 t2 t1a t3 t1b t2a t3 t2b

t1 = adjusted ON-delay t1a + t1b = t1


t2 = adjusted OFF-delay t2a + t2b = t2
t1 = t2 t3 = pause timing

1/43 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
CT-S range
Function diagrams

AB
Asymmetrical ON-delay and OFF-delay CA Impulse-ON
(Asymmetrical delay on make and delay on break) (Interval) 1
CT-MXS CT-MVS, CT-WBS
This function requires continuous control supply voltage for
timing. This function requires continuous control supply voltage for
Closing control input A1-Y1/B1 starts the ON-delay t1. When timing.
timing is complete, the output relay energizes. Opening The output relay energizes immediately when control supply
control input A1-Y1/B1 starts the OFF-delay t2. When the voltage is applied and de-energizes after the set pulse time
OFF-delay is complete, the output relay de-energizes. Both is complete. The green LED flashes during timing. When
timing functions are displayed by the flashing green LED. The the selected pulse time is complete, the flashing green LED
ON-delay and OFF-delay are independently adjustable. turns steady.
If control input A1-Y1/B1 opens before the ON-delay is com- If control supply voltage is interrupted, the output relay de-
plete (<t1), the time delay is reset and the output relay remains energizes and the time delay is reset.
de-energized.
If control input A1-Y1/B1 closes before the OFF-delay is com- A1-A2

2CDC 252 024 F0206


15-18, 25-28
plete (<t2), the time delay is reset and the output relay remains 15-16, 25-26

energized. 21-24
21-22

If control supply voltage is interrupted, the output relay de- green LED
t <t
energizes and the time delay is reset.
t = adjusted pulse time

A1-A2
2CDC 252 038 F0206

A1-Y1/B1
15-18, 25-28
15-16, 25-26
green LED
t1 t2 t1 < t2

t1 = adjusted ON-delay
t2 = adjusted OFF-delay
t1 and t2 independently adjustable

CA Impulse-ON CB Impulse-OFF with auxiliary voltage


(Interval) (Trailing edge interval)
CT-MFS, CT-MBS CT-MFS, CT-MBS

This function requires continuous control supply voltage for This function requires continuous control supply voltage for
timing. timing.
The output relay energizes immediately when control supply If control supply voltage is applied, opening control input Y1-
voltage is applied and de-energizes after the set pulse time is Z2 energizes the output relay immediately and starts timing.
complete. If control input Y1-Z2 is open, timing begins when The green LED flashes during timing. When the selected pulse
control supply voltage is applied. Or, if control supply voltage time is complete, the output relay de-energizes and the flash-
is already applied, opening control input Y1-Z2 starts timing. ing green LED turns steady.
The green LED flashes during timing. When the selected pulse Closing control input Y1-Z2, before the pulse time is com-
time is complete, the output relay de-energizes and the flash- plete, de-energizes the output relay and resets the pulse time.
ing green LED turns steady. Pause timing / Accumulative impulse-OFF (CT-MFS):
Closing control input Y1-Z2, before the pulse time is com- Timing can be paused by closing control input X1-Z2. The
plete, de-energizes the output relay and resets the pulse time. elapsed time t1 is stored and continues from this time value
Pause timing / Accumulative impulse-ON (CT-MFS): when X1-Z2 is re-opened.
Timing can be paused by closing control input X1-Z2. The This can be repeated as often as required.
elapsed time t1 is stored and continues from this time value If control supply voltage is interrupted, the output relay de-
when X1-Z2 is re-opened. energizes and the time delay is reset.
This can be repeated as often as required.
If control supply voltage is interrupted, the output relay de-
A1-A2
2CDC 252 026 F0206

energizes and the time delay is reset. Y1-Z2


15-18, 25-28
A1-A2
2CDC 252 025 F0206

15-16, 25-26
Y1-Z2 21-24
21-22
15-18, 25-28
15-16, 25-26 X1-Z2
21-24 green LED
21-22
t t1 t3 t2
X1-Z2
green LED t = adjusted pulse time t1 + t2 = t
t t1 t3 t2 t3 = pause timing

t = adjusted pulse time t1 + t2 = t


t3 = pause timing

2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 1/44
CT-S range
Function diagrams

CB
Impulse-OFF with auxiliary voltage Impulse-ON and impulse-OFF
CE
1 (Trailing edge interval) (Interval and trailing edge interval)
CT-MVS CT-MXS
This function requires continuous control supply voltage for This function requires continuous control supply voltage for
timing. timing. If control supply voltage is applied, closing control
If control supply voltage is applied, opening control input A1- input A1-Y1/B1 energizes the output relay immediately and
Y1/B1 energizes the output relay immediately and starts tim- starts the pulse time t1. The green LED flashes during timing.
ing. The green LED flashes during timing. When the selected When t1 is complete, the output relay de-energizes and the
pulse time is complete, the output relay de-energizes and the flashing green LED turns steady. Re-opening control input
flashing green LED turns steady. A1-Y1/B1 energizes the output relay immediately and starts
Closing control input A1-Y1/B1, before the pulse time is com- the pulse time t2. The green LED flashes during timing. When
plete, de-energizes the output relay and resets the pulse time. t2 is complete, the output relay de-energizes and the flashing
If control supply voltage is interrupted, the output relay de- green LED turns steady. t1 and t2 are independently adjust-
energizes and the time delay is reset. able. If control input A1-Y1/B1 changes state before the pulse
time is complete, the output relay de-energizes and the pulse
A1-A2
time is reset. If control input A1-Y1/B1 changes state again,
2CDC 252 027 F0206

A1-Y1/B1
15-18, 25-28
the interrupted pulse time restarts. If control supply voltage is
15-16, 25-26
21-24
interrupted, the output relay de-energizes and the time delay
21-22
is reset. A1-A2

2CDC 252 028 F0206


green LED
t <t A1-Y1/B1
15-18, 25-28
15-16, 25-26
t = adjusted pulse time
green LED
t1 t2 < t1

t1 = adjusted pulse time 1


t2 = adjusted pulse time 2

DA Flasher, starting with the ON time DB Flasher, starting with the OFF time
(Recycling equal times, ON first) (Recycling equal times, OFF first)
CT-WBS CT-WBS
Applying control supply voltage starts timing with symmetrical Applying control supply voltage starts timing with symmetri-
ON & OFF times. The cycle starts with an ON time first. The cal ON & OFF times. The cycle starts with an OFF time first.
ON & OFF times are displayed by the flashing green LED, The ON & OFF times are displayed by the flashing green
which flashes twice as fast during the OFF time. LED, which flashes twice as fast during the OFF time.
If control supply voltage is interrupted, the output relay de- If control supply voltage is interrupted, the output relay de-
energizes and the time delay is reset. energizes and the time delay is reset.
A1-A2 A1-A2
2CDC 252 029 F0206

15-18, 25-28
15-16, 25-26
15-18, 25-28
15-16, 25-26 2CDC 252 030 F0206

green LED green LED


t t t t

t = adjusted flashing time t = adjusted flashing time

DA Flasher with reset, starting with the ON time DB Flasher with reset, starting with the OFF time
(Recycling equal times with reset, ON first) (Recycling equal times with reset, OFF first)
CT-MFS, CT-MBS CT-MFS, CT-MBS
Applying control supply voltage starts timing with symmetrical Applying control supply voltage starts timing with symmetri-
ON & OFF times. The cycle starts with an ON time first. The cal ON & OFF times. The cycle starts with an OFF time first.
ON & OFF times are displayed by the flashing green LED, The ON & OFF times are displayed by the flashing green LED,
which flashes twice as fast during the OFF time. which flashes twice as fast during the OFF time.
The time delay can be reset by closing control input Y1-Z2. The time delay can be reset by closing control input Y1-Z2.
Opening control input Y1-Z2 starts the timer pulsing again Opening control input Y1-Z2 starts the timer pulsing again
with symmetrical ON & OFF times. with symmetrical ON & OFF times.
If control supply voltage is interrupted, the output relay de- If control supply voltage is interrupted, the output relay de-
energizes and the time delay is reset. energizes and the time delay is reset.
A1-A2
2CDC 252 031 F0206

A1-A2
2CDC 252 032 F0206

Y1-Z2
15-18, 25-28 Y1-Z2
15-16, 25-26 15-18, 25-28
15-16, 25-26
21-24
21-22 21-24
21-22
green LED
t t t t green LED
t t t t
t = adjusted flashing time
t = adjusted flashing time

1/45 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
CT-S range
Function diagrams

DE
Flasher, starting with the ON or OFF time H Pulse former
(Recycling equal times, ON or OFF first) (Single shot) 1
CT-MVS CT-MFS, CT-MBS
Applying control supply voltage starts timing with symmetri- This function requires continuous control supply voltage for
cal ON & OFF times. The cycle starts with an ON time first. timing.
Closing control input A1-Y1/B1, with control supply voltage Closing control input Y1-Z2 energizes the output relay im-
applied, starts the cycle with an OFF time first. The ON & mediately and starts timing. Operating the control contact
OFF times are displayed by the flashing green LED, which switch Y1-Z2 during the time delay has no effect. The green
flashes twice as fast during the OFF time. LED flashes during timing. When the selected ON time is
If control supply voltage is interrupted, the output relay de- complete, the output relay de-energizes and the flashing
energizes and the time delay is reset. green LED turns steady. After the ON time is complete, it
can be restarted by closing control input Y1-Z2.
A1-A2
If control supply voltage is interrupted, the output relay de-
2CDC 252 033 F0206
A1-Y1/B1 energizes and the time delay is reset.
15-18, 25-28
15-16, 25-26
A1-A2

2CDC 252 034 F0206


21-24
21-22 Y1-Z2
green LED 15-18, 25-28
t t t t 15-16, 25-26
21-24
t = adjusted flashing time 21-22
green LED
t t

t = adjusted pulse time

H Pulse former ED Pulse generator, starting with the ON or OFF time


(Single shot) (Recycling unequal times, ON or OFF first)
CT-MVS CT-MXS
This function requires continuous control supply voltage for This function requires continuous control supply voltage for
timing. timing.
Closing control input A1-Y1/B1 energizes the output relay Applying control supply voltage, with open control input
immediately and starts timing. Operating the control contact A1-Y1/B1, starts timing with an ON time t2 first. Applying
switch A1-Y1/B1 during the time delay has no effect. The control supply voltage, with closed control input A1-Y1/B1,
green LED flashes during timing. When the selected ON time starts timing with an OFF time t1 first. The ON & OFF times
is complete, the output relay de-energizes and the flashing are displayed by the flashing green LED, which flashes twice
green LED turns steady. After the ON time is complete, it as fast during the OFF time.
can be restarted by closing control input A1-Y1/B1. The ON & OFF times are independently adjustable.
If control supply voltage is interrupted, the output relay de- If control supply voltage is interrupted, the output relay de-
energizes and the time delay is reset. energizes and the time delay is reset.

A1-A2
2CDC 252 035 F0206

A1-A2
2CDC 252 075 F0207

A1-Y1/B1
A1-Y1/B1
15-18, 25-28
15-16, 25-26 15-18, 25-28
15-16, 25-26
21-24
21-22 green LED
t1 t2 t2 t1
green LED
t t
t1 = adjusted OFF time
t2 = adjusted ON time
t = adjusted pulse time

2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 1/46
CT-S range
Function diagrams

EC
Single-pulse generator, starting with the OFF time AC
Fixed impulse with adjustable time delay
1 (Delay on make with interval output) (Delayed pulse output)
CT-MXS CT-WBS
This function requires continuous control supply voltage for This function requires continuous control supply voltage for
timing. timing.
Applying control supply voltage, or, if control supply voltage is The time delay t1 starts when control supply voltage is ap-
already applied, opening control input A1-Y1/B1 energizes the plied. The green LED flashes during timing. When t1 is com-
output relay after the OFF time t1 is complete. When the fol- plete, the output relay energizes for the fixed impulse time t2
lowing ON time t2 is complete, the output relay de-energizes. of 500 ms and the flashing green LED turns steady.
The ON & OFF times are displayed by the flashing green LED, If control supply voltage is interrupted, the time delay is reset.
which flashes twice as fast during the OFF time. The output relay does not change state.
The ON & OFF times are independently adjustable.
Closing control input A1-Y1/B1, with control supply voltage
applied, de-energizes the output relay and resets the time A1-A2

2CDC 252 041 F0206


delay. 15-18, 25-28
15-16, 25-26

If control supply voltage is interrupted, the output relay de- green LED
t1 t2 < t1
energizes and the time delay is reset.
t1 = adjusted time delay
t2 = pulse time fixed 500 ms

A1-A2
2CDC 252 037 F0206

A1-Y1/B1
15-18, 25-28
15-16, 25-26
green LED
t1 t2 t1 t2

t1 = adjusted OFF time


t2 = adjusted ON time
t1 and t2 independently adjustable

BC Adjustable impulse with fixed time delay G ON/OFF-Function


(Delayed Interval) CT-WBS CT-MFS, CT-MBS, CT-MVS, CT-MXS, CT-WBS
This function requires continuous control supply voltage for This function is used for test purposes during commissioning
timing. and troubleshooting.
Applying control supply voltage starts the fixed time delay t2 of If the selected max. value of the time range is smaller than
500 ms. When t2 is complete, the output relay energizes and 300 h (front-face potentiometer “Time sector” ≠ 300 h), apply-
the selected pulse time t1 starts. The green LED flashes dur- ing control supply voltage energizes the output relay imme-
ing timing. When t 1 is complete, the output relay de-energizes diately and the green LED glows. Interrupting control supply
and the flashing green LED turns steady. voltage, de-energizes the output relay.
If control supply voltage is interrupted, the pulse time is reset. If the selected max. value of the time range is 300 h (front-
The output relay does not change state. face potentiometer “Time sector” = 300 h) and control supply
voltage is applied, the green LED glows, but the output relay
A1-A2
2CDC 252 042 F0206

15-18, 25-28
does not energize.
15-16, 25-26
Time settings and operating of the control inputs have no ef-
green LED
t2 t1 t2 < t1 fect on the operation.
t1 = adjusted pulse time
t2 = time delay fixed 500 ms
A1-A2
2CDC 252 044 F0206

15-18, 25-28
15-16, 25-26
green LED

Time sector ≠ 300 h Time sector = 300 h

1/47 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
CT-S range
Function diagrams

FC Star-delta change-over with impulse function


(Star-delta starting, interval/delay on make) 1
CT-MFS, CT-MBS, CT-MVS.2x

2CDC 252 129 F0b06


L1 F3
This function requires continuous control supply voltage for timing.
Applying control supply voltage to terminals A1-A2, energizes the 95
F2
star contactor connected to terminals 15-18 and begins the set 96
S1 21
starting time t1. The green LED flashes during timing. When the 0
22
starting time is complete, the first c/o contact de-energizes the star
S2
contactor. I
13
K2
53
14 54
Now, the fixed transition time t2 of 50 ms starts. When the transition
15 25 13 13
time is complete, the second c/o contact energizes the delta con- K1T
18 28
K2
14
K1
14
tactor connected to terminals 25-28. The delta contactor remains
22 22
energized as long as control supply voltage is applied to the unit. K3 K1
21 21

A1-A2
2CDC 252 039 F0206

A1 A1 A1 A1
15-18
15-16 K1T K1 K3 K2
A2 A2 A2 A2
25-28
25-26 N
green LED Y  N
t1 t2
Control circuit diagram
t1 = adjusted starting time
t2 = transition time (50 ms)

2CDC 253 009 F0012


L1 L2 L3

1 3 5
-F1
2 4 6

F Star-delta change-over
(Star-delta starting)
CT-SDS 1 3 5 1 3 5 1 3 5
-K2 -K3 -K1
This function requires continuous control supply voltage for timing. 2 4 6 2 4 6 2 4 6

Applying control supply voltage to terminals A1-A2, energizes the


star contactor connected to terminals 17-18 and begins the set 1 5 4 97 95
-F2
starting time t1. The green LED flashes during timing. When the 3 2 6
98 96

starting time is complete, the first output contact de-energizes the


-M1
star contactor.
Now, the fixed transition time t2 of 50 ms starts. When the transi- W1
V1 M
W2
V2

tion time is complete, the second output contact energizes the U1 3~ U2

delta contactor connected to terminals 17-28. The delta contactor


Power circuit diagram
remains energized as long as control supply voltage is applied to
the unit.
A1-A2
2CDC 252 040 F0206

17-18
2CDC 252 128 F0b06

17-28
L1 F3
green LED
t1 t2 95
F2
96
t1 = adjusted starting time
t2 = transition time (50 ms) S1 21
0
22

S2 13 53
I K2
14 54

17 17 13 13
K1T K2 K1
18 28 14 14

22 22
K3 21
K1 21

A1 A1 A1 A1
K1T K1 K3 K2
A2 A2 A2 A2
N
Y  N

Control circuit diagram

2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 1/48
CT-S range
Connection diagrams

CT-MVS.21 CT-MVS.22 CT-MVS.23 CT-MVS.12


1 A1 15 25 21 A1 15 25 A1 15 25 A1 15 Y1/B1
2CDC 252 002 F0b06

2CDC 252 003 F0b06

2CDC 252 003 F0b06

2CDC 252 004 F0b06


Y1/B1 Z2 Z1 Y1/B1 Y1/B1
Y1/ 25 Y1/ Y1/ Y1/
B1 A1 15 21 B1 A1 15 25 B1 A1 15 25 B1 A1 15

A2 16 18 26 28 A2 16 18 26 28 A2 16 18 26 28 A2 16 18
22 24
28 24 26 22 28 26 28 26
18 16 A2 18 16 A2 18 16 A2 18 16 A2

A1-A2 Supply: 24-240 V AC/DC A1-A2 Supply: 224-48 V DC A1-A2 Supply: 380-440V AC A1-A2 Supply: 24-48 V DC
A1-Y1/B1 Control input or 24-240 V AC A1-Y1/B1 Control input or 24-240 V AC
A1-Y1/B1 Control input A1-Y1/B1 Control input
15-16/18 1. c/o contact 15-16/18 1. c/o contact
15-16/18 1. c/o contact 15-16/18 1. c/o contact
25-26/28 2. c/o contact 25-26/28 2. c/o contact
25-26/28 2. c/o contact
21-22/24 2. c/o contact as
instantaneous contact
Z1-Z2 Remote potentiometer
connection

CT-MXS.22 CT-MFS.21 CT-MBS.22 CT-WBS.22


A1 15 25 A1 15 A1 15 A1 15 25
2CDC 252 005 F0b06

2CDC 252 006 F0b06

2CDC 252 007 F0b06

2CDC 252 008 F0b06


25 21 25 21
Z3 Z2 Z1 X1 Z2 Z1 Z2 Z1
Y1/ 25 25
B1 A1 15 25 A1 15 21 A1 15 21 A1 15 25

A2 16 18 26 28 A2 16 18 26 28 A2 16 18 26 28 A2 16 18 26 28
22 24 22 24
28 26 Y1/B1 28 24 26 22 Y1 28 24 26 22 Y1 28 26
18 16 A2 18 16 A2 18 16 A2 18 16 A2

A1-A2 Supply: 24-48 V DC A1-A2 Supply: 24-240 V AC/DC A1-A2 Supply: 24-48 V DC A1-A2 Supply: 24-48 V DC
or 24-240 V AC or 24-240 V AC or 24-240 V AC
A1-Y1/B1 Control input 15-16/18 1. c/o contact 15-16/18 1. c/o contact 15-16/18 1. c/o contact
15-16/18 1. c/o contact 25-26/28 2. c/o contact 25-26/28 2. c/o contact 25-26/28 2. c/o contact
25-26/28 2. c/o contact 21-22/24 2. c/o contact as 21-22/24 2. c/o contact as
Z1-Z2 Remote instantaneous contact instantaneous
potentiometer contact
connection Y1-Z2 Control input Y1-Z2 Control input
Z3-Z2 Remote X1-Z2 Control input Z1-Z2 Remote
potentiometer Z1-Z2 Remote potentiometer potentiometer
connection connection connection

A CT-ERS.21 A CT-ERS.22 A CT-ERS.12


A1 15 25 A1 15 25 A1 15
2CDC 252 009 F0b06

2CDC 252 009 F0b06

2CDC 252 010 F0b06

A1 15 25 A1 15 25 A1 15

A2 16 18 26 28 A2 16 18 26 28 A2 16 18
28 26 28 26
18 16 A2 18 16 A2 18 16 A2

A1-A2 Supply: 24-240 V AC/DC A1-A2 Supply: 24-48 V DC A1-A2 Supply: 24-48 V DC
or 24-240 V AC or 24-240 V AC
15-16/18 1. c/o contact 15-16/18 1. c/o contact 15-16/18 1. c/o contact
25-26/28 2. c/o contact 25-26/28 2. c/o contact

1/49 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
CT-S range
Connection diagrams

B CT-APS.21 B CT-APS.22 B CT-APS.12 B CT-AHS.22


A1 15 25
2CDC 252 011 F0b06
A1 15 25 A1 15 Y1/B1 A1 15 25 1

2CDC 252 011 F0b06

2CDC 252 012 F0b06

2CDC 252 013 F0b06


Y1/B1 Y1/B1 Z2
Y1/ Y1/ Y1/
B1 A1 15 25 B1 A1 15 25 B1 A1 15 A1 15 25

A2 16 18 26 28 A2 16 18 26 28 A2 16 18 A2 16 18 26 28
28 26 28 26 28 26 Y1
18 16 A2 18 16 A2 18 16 A2 18 16 A2

A1-A2 Supply: 24-240 V AC/DC A1-A2 Supply: 24-48 V DC or A1-A2 Supply: 24-48 V DC or A1-A2 Supply: 24-48 V DC or
A1-Y1/B1 Control input 24-240 V AC 24-240 V AC 24-240 V AC
A1-Y1/B1 Control input A1-Y1/B1 Control input Y1-Z2 Control input
15-16/18 1. c/o contact
15-16/18 1. c/o contact 15-16/18 1. c/o contact 15-16/18 1. c/o contact
25-26/28 2. c/o contact
25-26/28 2. c/o contact 25-26/28 2. c/o contact

B CT-ARS.11 B CT-ARS.21 F CT-SDS.22 F CT-SDS.23


A1 15 A1 15 25
2CDC 252 014 F0b06

2CDC 252 015 F0b06

A1 17 A1 17

2CDC 252 016 F0b06

2CDC 252 016 F0b06


A1 15 A1 15 25 A1 17 A1 17

A2 16 18 A2 16 18 26 28 A2 18 28 A2 18 28
28 26
18 16 A2 18 16 A2 18 28 A2 18 28 A2

A1-A2 Supply: 24-240 V AC/DC A1-A2 Supply: 24-240 V AC/DC


15-16/18 1. c/o contact 15-16/18 1. c/o contact A1-A2 Supply: 24-48 V DC or A1-A2 Supply: 380-440 V AC
24-240 V AC 17-18 1. n/o contact
25-26/28 2. c/o contact 17-18 1. n/o contact
17-28 2. n/o contact
17-28 2. n/o contact

2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 1/50
CT-S range
Technical data

Data at Ta = 25 °C and rated values, unless otherwise indicated


1 CT-S
Input circuit - Supply circuit
Rated control supply voltage U s CT-xxx.x1 24-240 V AC/DC
CT-xxx.x2 24-48 V DC, 24-240 V AC
CT-xxx.x3 380-440 V AC
CT-xxx.x4 110-240 V AC
CT-xxx.x5 220-240 V AC
CT-xxx.x6 24 V AC/DC
CT-xxx.x7 100-127 V AC or 110 V DC
CT-xxx.x8 200-240V AC/DC
Rated control supply voltage U S tolerance -15...+10 %
Rated frequency DC or 50/60 Hz
Frequency range AC 47-63 Hz
Typical current / power consumption depending on device, see data sheet
Power failure buffering time 24 V DC min. 15 ms
230/400 V AC min. 20 ms
Minimum energizing time 100 ms (CT-ARS)
Formatting time 1) 5 min (CT-ARS)
Input circuit - Control circuit
Kind of triggering CT-MVS, CT-MXS, CT-APS voltage-related triggering
Control input, Control function A1-Y1/B1 start timing external
Parallel load / polarized yes / no
Maximum cable length to the control input 50 m - 100 pF/m
Minimum control pulse length 20 ms
Control voltage potential see rated control supply voltage
Current consumption of the control input 24 V DC 1.2 mA
230 V AC 8 mA
400 V AC 6 mA
Kind of triggering CT-MFS, CT-MBS, CT-AHS volt-free triggering
Control input, Control function Y1-Z2 start timing external
X1-Z2 pause timing / accumulative functions (CT-MFS)
Maximum switching current in the control circuit 1 mA
Maximum cable length to the control input 50 m - 100 pF/m
Minimum control pulse length 20 ms
No-load voltage at the control inputs 10-40 V DC
Remote potentiometer
Remote potentiometer connections, Resistance value Z1-Z2 50 kΩ (CT-MFS, CT-MBS, CT-MVS.21, CT-MXS)
Z3-Z2 50 kΩ (CT-MXS)
Maximum cable length to remote potentiometer 2 x 25 m, shielded with 100 pF/m
Shield connection Z2
Timing circuit
Time ranges 10 time ranges 0.05 s - 300 h 1.) 0.05-1 s 2.) 0.15-3 s 3.) 0.5-10 s 4.) 1.5-30 s 5.) 5-100 s
6.) 15-300 s 7.) 1.5-30 min 8.) 15-300 min 9.) 1.5-30 h 10.) 15-300 h

7 time ranges 0.05 s - 10 min (CT-SDS, 1.) 0.05-1 s 2.) 0.15-3 s 3.) 0.5-10 s
CT-ARS) 4.) 1.5-30 s 5.) 5-100 s 6.) 15-300 s 7.) 0.5-10 min
Recovery time 24-240 V AC/DC < 50 ms
24-48 V DC, 24-240 V AC < 80 ms
380-440 V AC < 60 ms
Accuracy within the rated control supply voltage tolerance it < 0.004 % / V
Accuracy within the temperature range it < 0.03 % / °C
Repeat accuracy (constant parameters) < ±0.2 %
Star-delta transition time fixed 50 ms (CT-SDS, CT-MBS, CT-MFS, CT-MVS.2x)
Star-delta transition time tolerance ±2 ms

1)
prior to first commisioning and after a six-month stop in operation

1/51 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
CT-S range
Technical data

Indication of operational states


Control supply voltage / timing U/T: green LED V : control supply voltage applied / W : timing 1
Control supply voltage U: green LED V : control supply voltage applied
Relay state R, R1, R2: yellow LED V : output relay energized
Output circuit
Kind of output 15-16/18 relay, 1 c/o contact
15-16/18; 25-26/28 relay, 2 c/o contacts
15-16/18; 25(21)-26(22)/28(24) relay, 2 c/o contacts, 2nd c/o contact selectable as inst. contact
17-18; 17-28 relay, 2 n/o contacts (CT-SDS)
Contact material Cd-free, on request
Rated operational voltage U e IEC/EN 60947-1 250 V
Minimum switching voltage / minimum switching current 12 V / 10 mA
Maximum switching voltage / maximum switching current see load limit curves
Rated operational current I e AC-12 (resistive) at 230 V 4 A
(IEC/EN 60947-5-1 ) AC-15 (inductive) at 230 V 3 A
DC-12 (resistive) at 24 V 4 A
DC-13 (inductive) at 24 V 2 A (CT-ARS; 1.5 A)
AC rating (UL 508) Utilization category (Control Circuit Rating Code)
B 300
max. rated operational voltage 300 V AC
Maximum continuous thermal current at B300 5 A
max. making/breaking apparent power at B300 3600 VA / 360 VA
Mechanical lifetime 30 x 10 6 switching cycles
Electrical lifetime at AC-12, 230 V, 4 A 0.1 x 10 6 switching cycles
Max. fuse rating to achieve short-circuit protection n/c contact 6 A fast-acting
(IEC/EN 60947-5-1)
n/o contact 10 A fast-acting
General data 2)
MTBF on request
Duty time 100%
Dimensions (W x H x D) product dimensions 22.5 x 85.6 x 103.7 mm (0.89 x 3.37 x 4.08 in)
packaging dimensions 97 x 109 x 30 mm (3.82 x 4.29 x 1.18 in)
Weight depending on device, see ordering details
Mounting DIN rail (IEC/EN 60715), snap-on mounting without any tool
Mounting position any
Minimum distance to other units vertical / horizontal not necessary / not necessary
Material of housing UL 94 V-0
Degree of protection housing / terminals IP50 / IP20
Electrical connection 2)
Screw connection technology Easy Connect Technology
(Push-in)
Wire size fine-strand with(out) wire end 1 x 0.5-2.5 mm 2 (1 x 20-14 AWG) 2 x 0.5-1.5 mm 2 (2 x 20-16 AWG)
ferrule 2 x 0.5-1.5 mm 2 (2 x 20-16 AWG)
rigid 1 x 0.5-4 mm 2 (1 x 20-12 AWG) 2 x 0.5-1.5 mm 2 (2 x 20-16 AWG)
2 x 0.5-2.5 mm 2 (2 x 20-14 AWG)
Stripping length 8 mm (0.32 in)
Tightening torque 0.6-0.8 Nm (5.31-7.08 lb.in) -

2)
Data for all references 1SVR 730 xxx xxx and 1SVR 740 xxx xxx. For devices with 1SVR 430 xxx xxx please refer to the data sheet.

2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 1/52
CT-S range
Technical data

Environmental data
1 Ambient temperature ranges operation / storage -25...+60 °C / -40...+85 °C,
-40...+60 °C / -40...+85 °C (CT-MVS.21, CT-MFS.21, CT-ERS.21,
CT-APS.21)

Damp heat (cyclic) (IEC/EN 60068-2-30) 6 x 24 h cycle, 55 °C, 95 % RH


Vibration, sinusoidal (IEC/EN 60068-2-6) functioning 40 m/s 2, 10-58/60-150 Hz
resistance 60 m/s 2, 10-58/60-150 Hz, 20 cycles
Vibration, seismic (IEC/EN 60068-3-3) functioning 20 m/s 2
Shock, half-sine (IEC/EN 60068-2-27) functioning 100 m/s 2, 11 ms, 3 shocks/direction
resistance 300 m/s 2 , 11 ms, 3 shocks/direction
Isolation data CT-S with 1 c/o CT-S with 2 c/o
Rated insulation voltage U i input circuit / output circuit 500 V
output circuit 1 / output circuit 2 not available 300 V
Rated impulse withstand voltage U imp between all isolated circuits type test: 4 kV; 1.2/50 µs
(IEC/EN 60664-1)
Power-frequency withstand voltage (test voltage) between all isolated routine test: 2.0 kV; 50 Hz; 1 s
circuits type test: 2.0 kV; 50 Hz; 60 s

Basic insulation (IEC/EN 61140) input circuit / output circuit 500 V


Protective separation input circuit / output circuit 250 V
(IEC/EN 61140; EN 50178)
Pollution degree IEC/EN 60664-1 3
Overvoltage category IEC/EN 60664-1 III
Standards
Product standard IEC 61812-1, EN 61812-1 + A11, DIN VDE 0435 part 2021
Low Voltage Directive 2006/95/EC
EMC Directive 2004/108/EC
RoHS Directive 2011/65/EC
Electromagnetic compatibility
Interference immunity to IEC/EN 61000-6-1, IEC/EN 61000-6-2
electrostatic discharge IEC/EN 61000-4-2 Level 3, 6 kV / 8 kV
radiated, radio-frequency IEC/EN 61000-4-3 Level 3, 10 V/m (1 GHz) 3 V/m (2 GHz) 1 V/m (2.7 GHz)
electromagnetic field
electrical fast transient / burst IEC/EN 61000-4-4 Level 3, 2 kV / 5 kHz
surge IEC/EN 61000-4-5 Level 4, 2 kV A1-A2
conducted disturbances, induced by IEC/EN 61000-4-6 Level 3, 10 V
radio-frequency fields
harmonics and interharmonics IEC/EN 61000-4-13 Class 3
Interference emission IEC/EN 61000-6-3, IEC/EN 61000-6-4
high-frequency radiated IEC/CISPR 22, EN 55022 Class B
high-frequency conducted IEC/CISPR 22, EN 55022 Class B
„Approvals and marks“ see page 1/4.

1/53 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
CT-S range
Technical diagrams

Technical diagrams
Load limit curves
1
AC load (resistive) DC load (resistive)

2CDC 252 149 F0206

2CDC 252 150 F0206


AC voltage [V]

DC voltage [V]
resistive load

resistive load

AC current [A] DC current [A]

Derating factor F for inductive AC load Contact lifetime

1.0

2CDC 252 148 F0206


Switching cycles
2CDC 252 124 F0206
Derating factor F

0.9

0.8

0.7 250 V
resistive load
0.6

0.5

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
cos ϕ
Switching current [A]

2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 1/54
CT-S range
Wiring notes, Dimensional drawings

Wiring notes
1
Control inputs Triggering of the control inputs (volt-free)
(volt-free triggering) with a proximity switch (3 wire)
L(+) L(+) +V
2CDC 252 101 F0b06

2CDC 252 105 F0b06


A1 X1 Y1 A1 Y1

A2 Z2 A2 Z2

N(-) N(-) 0V

Control inputs
(voltage-related triggering)
L(+) L(+) L(+)

2CDC 252 103 F0b06


2CDC 252 102 F0b06

A1 Y1/B1 A1 Y1/B1

A2 A2

N(-) N(-) L(-)

The control input Y1/B1 is triggered with electric potential against A2. It is pos-
sible to use the control supply voltage from terminal A1 or any other voltage
within the rated control supply voltage range.

Remote potentiometer
L(+)
2CDC 252 104 F0b06

A1 Z3 Z1

A2 Z2

N(-)

Dimensional drawing Dimensions in mm

113.4 4.47”
105.9 4.17” 22.5 0.89”
109,5 4.31“ 22,5
.886“
102 4.02“
85.6 3.37”
2CDC 252 188 F0b05
78 3.07“

2CDC 252 009 F0011

100 3.94“
103.7 4.08”

1SVR 430 xxx xxx 1SVR 730 xxx xxx, 1SVR 740 xxx xxx

1/55 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
Electronic timers
Notes