Sei sulla pagina 1di 25

Wecome

to

Evolution
of

Control
Modes

29-08-2015 Instructor: Narendra Gole 1
Process control

Process control is an extremely important field of engineering.


However, all processes are not controllable. For example
terestial events can only be observed,
observed they can not be
controlled. So, for conceiving any control, the controllability
of the p
process needs to be established first.

Having established the controllability of the process, we have


to identify the parameter to be controlled. For example let
us assume that we wish to control the room temperature.
Then room temperature becomes the controlled
parameter. How can room temperature be controlled? Simple
answer is using g a fan. So,, the fan becomes the final control
element (FCE). The ON/OFF switch or the regulator
becomes the controller.

29-08-2015 Instructor: Narendra Gole 2
Evolution of
control modes-I
1. On/Off Control:
Consider the situation below.

H1 Heater’s
H1- H t ’ h heating
ti ratet can be
b
1, 2 or 3 kws
H2- Heat leak rate of the system,
H2 system
let us say 0.5 kws

Heat energy flow Power KW KW KW


H1 Energy Input Rate in KW 1 2 3
H2 Energy Leakage Rate in 0.5 0.5 0.5
KW at the set point (SP)

29-08-2015 Instructor: Narendra Gole 3
Effective heat rate (H1‐H2) kw 0.5 1.5 2.5
Cycling Period T1 T2 T3
Frequency of oscillation F1 F2 F3

The frequency ‘f’ & amplitude of temp. oscillations depend


on: 1. Heating/Cooling time constant of the system and
2 Rate of energy accumulation (H1-
2. (H1 H2).
H2)

Then T1>T2>T3 and f3 >f2 >f1


29-08-2015 Instructor: Narendra Gole 4
The frequency of energy input devices also depends on
heat rates.

High switching frequency can cause damage to the


energy input switching device.

ON/OFF controls are thus preferred only if the system


capacity to store energy is high.

The amplitude of oscillation can be limited to the


acceptable level by properly choosing H1.
H1 But then there
also we end up in to a contradictory requirement. Namely,
if H1 is increased then the amplitude
p increases and if H1
is decreased then the period increases, making the
system control sluggish.

29-08-2015 Instructor: Narendra Gole 5
Example 1.

Another thermocouple mounted in thermowell, in the tank


as shown, has a time constant of 100 seconds and is used
to measure the tank temperature varying as above. How
much is the amplitude variation of the temperature as
recorded by this thermocouple and what is its phase shift,
shift
compared with the actual temperature variation.

Solution:

Assume that, amplitude A=100°C,


C the Set
S Point SP=400°C
S C
and the signal varies with a frequency of 0.1 Hz. The
attenuation suffered by the recorded signal using the
thermocouple having time constant of 100 seconds can
be g
given as:
29-08-2015 Instructor: Narendra Gole 6
Wr is the signal freq. relative to the corner freq. of the
thermocouple response, in Hz/Hz units. Here
Wr =0.1 Hz/( 1/100s )=10 Hz/Hz. Hence attenuation=0.l,
and the amplitude of the recorded signal would be 10
times reduced. Resulting phase shift: Ф = tan wr = 84.28°.
29-08-2015 Instructor: Narendra Gole 7
2. On/Off control with differential gap:

‘A' is increased by (SPH-SPL)/2, but ‘f' is reduced in the


process. We can adjust the diff.gap and locate it around the
SP at a suitable place so as to meet the process needs.
29-08-2015 Instructor: Narendra Gole 8
3. Two-Step Control

The cost of fabrication increases with ‘n'.


n step control as ‘n'
‘n' n tends to ‘∞'
∞ becomes a proportional
control if the step size is equal, since
((Energy
gy input)
p ) α ((Deviation of
controlled parameter from the SP) .
29-08-2015 Instructor: Narendra Gole 9
• Frequency of switching for each heater element is
reduced.
d d
• Amplitude of temperature oscillations is reduced
because of gradual switching of energy input devices.
devices
• Frequency of temperature oscillations is reduced.
• Temperature
p remains closer to the SP since its
variations are gradual and are of lower peak amplitude.

Th number
The b off steps
t ‘n'
‘ ' can thus
th beb increased
i d to
t achieve
hi

• reduced frequency of switching individual elements of


the energy input device, and
• close control w.r.t. the SP.

29-08-2015 Instructor: Narendra Gole 10
4.

Floating
control
action

29-08-2015 Instructor: Narendra Gole 11
The Final Control Element (FCE) is made to move
towards one of the two extremes, depending upon
whether the controlled parameter is above or below the
SP, with a predetermined speed.

In the modes of control seen earlier, the position of the


C was
FCE as made
ade to vary
a y in acco
accordance
da ce with
t tthe
e de
deviation
at o
in the controlled parameter from the set point. Here in
the floating control mode, it is not the position but the
speed of travel of the FCE which is varied in accordance
with the deviation of the controlled parameter from the
set point
point.

With the introduction of the neutral zone,, the FCE can be


made motionless at or near the set point (i.e. its rate of
travel is made zero). This scheme can reduce deviation
almost to zero and can, if correctly adjusted, eliminate
FCE motion, except following
29-08-2015 load or set point changes.
Instructor: Narendra Gole 12
5. Proportional Control

dl 1
 ( fi  fo )
dt A
Where A - Area of tank.,
So, sL(s)-Lo = [Fi(s)-Fo(s)]/A ------------ (1)
and L (s) = [Fi(s)-Fo(s)]/sA + Lo/s ------------ (2)
Also fi = bKv + (LR-l)KpKv
H
Hence Fi( ) = bKv/s
Fi(s) / +[ LR/s-L(s)]
/ L( )] KpKv ------------ (3)
29-08-2015 Instructor: Narendra Gole 13
Therefore from (1) and (3) we get
L(s) = ( Lo + [bKv + LR KpKv - Fo(s)]/sA )/( s+ KpKv/A)
------------- (4)
Assume that the initial value of level is set at SP, i.e. Lo=LR

Thus Lss = Lim ss->0


>0 sL(s) = Steady state value of level
= LR + [b/Kp - Fo(s)/ KpKv ]

This clearly shows that level settles at the SP only for the
initial load value. For any other value of the load, there will
be a steady state error (offset).

This error is observed to be inversely proportional to the gain

29-08-2015 Instructor: Narendra Gole 14
The proportional controller characteristic is shown below.

29-08-2015 Instructor: Narendra Gole 15
From eq
eq. (1) and (3) discussed earlier
earlier, of level control system
can be represented, block diagram as follows:

LO=LR is adjusted manually and then auto-control is put ‘ON'.

A K → ∞, offset
As ff t → 0.
0

But this is impossible to achieve


achieve.

Hence to reduce offset, either bias is adjusted


j or ‘LR' is
adjusted such that the output with the offset is equal to SP.

Thi iis a manuall reset.


This t

29-08-2015 Instructor: Narendra Gole 16
6. Proportional plus reset control
Automatic reset can be achieved by integrating the error
signal
g over time and proportionately y add a component in
the controller output. This is a proportional plus reset control
mode. Where:

Co = Kp (e + [1/TI]∫e dt) or
Co(s) = Kp(1 + 1/TIs)e(s) becomes the controller equation
equation.

Putting Kp (1+1/TIs)=Kp (TIs+1)/TIs for Kp in equation (4)


we get:

Lss = lim
li sL(s)
L( ) as s →0
0 = LR

Thus it is clear that integral action totally removes "offset"


offset .
29-08-2015 Instructor: Narendra Gole 17
Integral time ‘TI‘ is the time required for the reset action to
produce the output that would be produced by proportional
action for a step disturbance. However, the ‘reset' action has
t accumulate
to l t error for
f quite
it some titime tto force
f the
th ‘offset'
‘ ff t' to
t
zero. Hence this is an inherently slow process.
Therefore an action proportional to the rate of change of error
(slope of error curve) is added. This anticipates the correction
required in future and corrects controlled parameter in the
present, causing it to quickly converge to the steady state.
29-08-2015 Instructor: Narendra Gole 18
7. Proportional + reset + rate control
Which is Co = Kp e + (Kp/TI) ∫e dt) + (Kp TI) de/dt
Thus Co(s) = Kp(1 + 1/TIs+ TIs) e(s)
becomes the controller equation. 3-mode controller overcomes
1.instability (proportional)
2.offset (reset action) as well as
3 l
3.sluggish
i h response (rate
( t action)
ti )

29-08-2015 Instructor: Narendra Gole 19
8. Various types of process time lags
S Instantaneous Distance- Capacity T
Transfer
f Lag
L
response Velocity Lag Lag
1

2 Output follows Output is Output Output rises


the input delayed slowly rises sluggishly
3 E
Example:l Example:
E l Example:
E l Control
C t l action
ti
Pressure Process with Liquid level passes through
control of liquid dead time control resistive network
filled vessels
4 Use wide Use wide PB Use narrow Use PD or PID
Proportional and slow reset PB or on/off modes of control
Band (PB) and Do not use rate control with
slow reset action diff gap
diff.
29-08-2015 Instructor: Narendra Gole 20
Examples
Instantaneous Distance- Capacity Lag Transfer
response Velocity Lag Lag

After you press 
y p Water storage 
g Keep a ketle full 
p 2 adjacant 
j
a button an  tank located on a  of water on the  rooms are 
incandescent  hill 10 km away  gas stove. The  cooled by a 
lamp starts  from a township  water  desert 
glowing almost  receiving the  temperature  cooler 
instantaneously
instantaneously. water After
water. After  starts rising
starts rising  placed in
placed in 
opening the  slowly, untill  one room. 
outlet at the tank, , the whole  The other 
water reaches the  capacityful  room  cools 
town after this  water heats up. only after 
delay. this dalay.
29-08-2015 Instructor: Narendra Gole 21
9. Various types of control systems
(1) Feed Back Control System (FBCS)
1. Corrective control
2 Corrects for load changes on sensing their effect
2.
3. Closed loop control
Controlled parameter is fed back for correcting deviations.

29-08-2015 Instructor: Narendra Gole 22
(2) Feed Forward Control System (FFCS)
a)) P
Preventive
i controll
b) Takes care of known incoming loads before they affect
the process
c) Open loop control & so cannot consider unknown
loads
Load variation is fed to the controller before it affects the
process.

29-08-2015 Instructor: Narendra Gole 23
(3) Cascade control system (CCS)

Set point of one system (shown by dotted rectangle)


is controlled by another controller
controller.

29-08-2015 Instructor: Narendra Gole 24
(4) Adaptive control system (ACS)

Parameters of controller are varied


to meet environmental effects

29-08-2015 Instructor: Narendra Gole 25

Potrebbero piacerti anche