NATIONAL INSTITUTE OF TECHNOLOGY, ROURKELA

Department of Electrical Engineering


End-Semester Supplementary Examination, 2019 (Spring)
Program: B.Tech./ B.Tech & M.Tech Dual Degree
Semester: 4th
Subject Name: Electrical Machines
Subject Code: EE 3011

Number of Pages: 2 Full Marks: 50 Duration: 3 Hours


Figures at the right hand margin indicate marks.
All symbols carry usual meaning. Assume standard value for any missing data.

Q.No. Instruction regarding questions Marks


Answer all questions
1 The following test results were obtained on a 20 kVA, 2500/250V, 50 Hz single 5
phase transformer,
OC test (LV side): 250 V, 1.4 A, 105 W
SC test (HV side): 104 V, 8 A, 320 W
Compute the parameters of the approximate equivalent circuit referred to the low
voltage side and draw the circuit

2 Two 100 kW transformers each has a maximum efficiency of 98% but in one, 5
the maximum efficiency occurs at full load while in the other, it occurs at half
load. Each transformer is on full load for 4 hours, on half load for 6 hours and
on one tenth load for 14 hours per day. Determine the all-day efficiency of each
transformer

3 A d.c. series motor, with an unsaturated field and negligible resistance when 5
running at a certain speed on a given load takes 45 A at 450 V. If the load torque
varies as the cube of the speed, calculate the resistance required to reduce the
speed by 25%.

4 A dc shunt motor rated at 12.5 kW output runs at no load at 1000 rpm from a 5
250 V supply, containing an input current of 4 A. The armature resistance is 0.5
Ω and shunt field resistance 250 Ω. Calculate the efficiency of the machine when
delivering full load output of 12.5 kW, while operating at 250 V.

5 Draw and explain the starting of 3-phase slip ring Induction Motor. 5
6 A 4 - pole, 50 Hz, 20 kW, 3-ph induction motor has friction and windage loss of 5
2.5 % of the output. The full load slip is 4%. Compute for full load (a) the rotor
P.T.O.
copper loss (b) the rotor input (c) the shaft torque (d) the gross electromagnetic
torque.

7 5
The following test results are obtained from a 3 phase 6000 kVA, 6600 V, star
connected, 2-pole, 50 Hz turbo-alternator:

With a field current of 125 A, the open-circuit voltage is 8000 V at the rated
speed; with the same field current and rated speed, the short circuit current is 800
A. At the rated full-load, the resistance drop is 3 %. Find the regulation of the
alternator on full-load and at a power factor of 0.8 lagging.

8 A 75 kW, three phase, Y-connected, 50-Hz, 400 V cylindrical rotor synchronous 5


motor operates at rated condition with 0.85 p.f. leading. The motor efficiency
excluding field and stator losses, is 90% and Xs = 2 Ω. Calculate (i) mechanical
power developed (ii) armature current (iii) back emf (iv) power angle and (v)
maximum or pull-out torque of the motor.

9 5x2
Answer any two

a). Explain three phase transformer connections and phasor groups.

b). Explain different methods of speed control of three phase induction motor.

c). Voltage regulation of alternator using Synchronous Impedance Method.

Wish you all the Best

--------------------**------------------