Sei sulla pagina 1di 71

INDEX

DESCRIPTION
S.NO. DRG.NO. PAGE NO.
132 KV TOWER FOUNDATIONS

A.1 Foundation Details of 132K.V.-General Arrangement 132KV-TL-G.A. 1


P TYPE

A.2.1 Foundation Details of 132 K.V.-"P"Type Tower 2,3


A.2.2 Foundation Details of 132 K.V.-"P"Type Tower - DRY 132KV-TL-P-DRY 4
A.2.3 Foundation Details of 132 K.V.-"P"Type Tower - WET 132KV-TL-P-WET 5
A.2.4 Foundation Details of 132 K.V.-"P"Type Tower - PS / PBC 132KV-TL-P-P.S. 6
A.2.5 Foundation Details of 132 K.V.-"P"Type Tower - FS / BC 132KV-TL-P-F.S. 7
A.2.6 Foundation Details of 132 K.V.-"P"Type Tower - HARD ROCK 132KV-TL-P-H.R. 8
A.2.7 Foundation Details of 132 K.V.-"P"Type Tower - SOFT ROCK / F&F ROCK 132KV-TL-P-S.R. 9
R TYPE

A.3.1 Foundation Details of 132 K.V.-"R"Type Tower 10,11


A.3.2 Foundation Details of 132 K.V.-"R"Type Tower - DRY 132KV-TL-R-DRY 12
A.3.3 Foundation Details of 132 K.V.-"R"Type Tower - WET 132KV-TL-R-WET 13
A.3.4 Foundation Details of 132 K.V.-"R"Type Tower - PS / PBC 132KV-TL-R-P.S. 14
A.3.5 Foundation Details of 132 K.V.-"R"Type Tower - FS / BC 132KV-TL-R-F.S. 15
A.3.6 Foundation Details of 132 K.V.-"R"Type Tower - HARD ROCK 132KV-TL-R-H.R. 16
A.3.7 Foundation Details of 132 K.V.-"R"Type Tower - SOFT ROCK / F&F ROCK 132KV-TL-R-S.R. 17
S TYPE

A.4.1 Foundation Details of 132 K.V.-"S"Type Tower 18,19


A.4.2 Foundation Details of 132 K.V.-"S"Type Tower - DRY 132KV-TL-S-DRY 20
A.4.3 Foundation Details of 132 K.V.-"S"Type Tower - WET 132KV-TL-S-WET 21
A.4.4 Foundation Details of 132 K.V.-"S"Type Tower - PS / PBC 132KV-TL-S-P.S. 22
A.4.5 Foundation Details of 132 K.V.-"S"Type Tower - FS / BC 132KV-TL-S-F.S. 23
A.4.6 Foundation Details of 132 K.V.-"S"Type Tower - HARD ROCK 132KV-TL-S-H.R. 24
A.4.7 Foundation Details of 132 K.V.-"S"Type Tower - SOFT ROCK / F&F ROCK 132KV-TL-S-S.R. 25
INDEX
S.NO. DESCRIPTION DRG.NO. PAGE NO.
220 KV TOWER FOUNDATIONS
B.1 Foundation Details of 220K.V.-General Arrangement 220KV-TL-G.A. 26
A TYPE
B.2.1 Foundation Details of 220 K.V.-"A"Type Tower 27,28
B.2.2 Foundation Details of 220 K.V.-"A"Type Tower - DRY 220KV-TL-A-DRY 29
B.2.3 Foundation Details of 220 K.V.-"A"Type Tower - WET 220KV-TL-A-WET 30
B.2.4 Foundation Details of 220 K.V.-"A"Type Tower - PS / PBC 220KV-TL-A-P.S. 31
B.2.5 Foundation Details of 220 K.V.-"A"Type Tower - FS / BC 220KV-TL-A-F.S. 32
B.2.6 Foundation Details of 220 K.V.-"A"Type Tower - HARD ROCK 220KV-TL-A-H.R. 33
B.2.7 Foundation Details of 220 K.V.-"A"Type Tower - SOFT ROCK / F&F ROCK 220KV-TL-A-S.R. 34
B TYPE
B.3.1 Foundation Details of 220 K.V.-"B"Type Tower 35,36
B.3.2 Foundation Details of 220 K.V.-"B"Type Tower - DRY 220KV-TL-B-DRY 37
B.3.3 Foundation Details of 220 K.V.-"B"Type Tower - WET 220KV-TL-B-WET 38
B.3.4 Foundation Details of 220 K.V.-"B"Type Tower - PS / PBC 220KV-TL-B-P.S. 39
B.3.5 Foundation Details of 220 K.V.-"B"Type Tower - FS / BC 220KV-TL-B-F.S. 40
B.3.6 Foundation Details of 220 K.V.-"B"Type Tower - HARD ROCK 220KV-TL-B-H.R. 41
B.3.7 Foundation Details of 220 K.V.-"B"Type Tower - SOFT ROCK / F&F ROCK 220KV-TL-B-S.R. 42
C TYPE
B.4.1 Foundation Details of 220 K.V.-"C"Type Tower 43,44
B.4.2 Foundation Details of 220 K.V.-"C"Type Tower - DRY 220KV-TL-C-DRY 45
B.4.3 Foundation Details of 220 K.V.-"C"Type Tower - WET 220KV-TL-C-WET 46
B.4.4 Foundation Details of 220 K.V.-"C"Type Tower - PS / PBC 220KV-TL-C-P.S. 47
B.4.5 Foundation Details of 220 K.V.-"C"Type Tower - FS / BC 220KV-TL-C-F.S. 48
B.4.6 Foundation Details of 220 K.V.-"C"Type Tower - HARD ROCK 220KV-TL-C-H.R. 49
B.4.7 Foundation Details of 220 K.V.-"C"Type Tower - SOFT ROCK / F&F ROCK 220KV-TL-C-S.R. 50
D TYPE
B.5.1 Foundation Details of 220 K.V.-"D"Type Tower 51,52
B.5.2 Foundation Details of 220 K.V.-"D"Type Tower - DRY 220KV-TL-D-DRY 53
B.5.3 Foundation Details of 220 K.V.-"D"Type Tower - WET(+0,+3,+6) 220KV-TL-D-WET 54
B.5.4 Foundation Details of 220 K.V.-"D"Type Tower - WET(+9) 220KV-TL-D-WET+9 55
B.5.5 Foundation Details of 220 K.V.-"D"Type Tower - PS / PBC 220KV-TL-D-P.S. 56
B.5.6 Foundation Details of 220 K.V.-"D"Type Tower - FS / BC 220KV-TL-D-F.S. 57
B.5.7 Foundation Details of 220 K.V.-"D"Type Tower - HARD ROCK 220KV-TL-D-H.R. 58
B.5.8 Foundation Details of 220 K.V.-"D"Type Tower - SOFT ROCK / F&F ROCK 220KV-TL-D-S.R. 59
Back
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004
x Stub
COPING
75
G.L

EXCAVATION LINE GL 225 GL

FxF

C Excavation Line
M

SECTION CL EAT S
W1
G A

G D1 W2

W3 250
D D2
EXCAVATION LINE

C.C. 1:2:4
D3
100 P.C.C. 1:4:8
C
L OF TOWER 150 Sand Filling

M B/2 B/2
K
B
NOTE-2 : For locations of cut point / angle towers, the classification of tower
G foundations shall be at next higher type for ensuring safety of the Transmission
line, which is likely to be subjected to seasonal changes / climatic conditions
G from time to time.
NOTE-3 : In case of highly collapsible & loose soils and river crossings, special
PLAN design for foundations are to be made by Civil Engineering wing for adoption
on case to case basis.
NOTE-4 : All locations subjected to water logging, particularly in paddy fields,
NOTE-1 : While classifying foundations of Wet, Partially submerged / ponds, marshy areas etc., the chimney of all stubs are to be raised to 600 mm
Partially black cotton, Fully submerged / Black cotton foundations over the normal chimney being adopted in other cases. This shall be done
mentioned above, the worst conditions should be considered and not after completion of erection of towers as a separate
necessarily the conditions prevailing at the time of inspection. For item for identified locations.
instance there are areas where subsoil water raised when canal water is
let out in the field raising subsoil water to a considerable degree. TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
Similarly the effect of monsoon or when the nearby reservoirs are full
should be considered and not the conditions prevailing in open season or FOUNDATION DETAILS OF 132 K.V. TYPE TOWER
summer when work is carried out normally.
Drg. No. 132KV-TL-G.A. Scale 1:50 Page

1
FOUNDATION DETAILS FOR 132 KV "P" TYPE TOWER
Basic W1 D1 Vol. Of
Soil A B C D F G M K Vol. Of
Tower W2 D2 Excavation Sand Bed PCC 1:4:8
Type (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) PCC 1:2:4
Extn. W3 D3 M3
300 200
± 0.00 M 2800 1200 2350 350 300 150 150 1700 4607 8919
0 0

Dry ± 3.00 M 2800 1200 2350 350 300 1700 5123 9649 32.37 Cum 0.00 Cum 0.78 Cum 2.47 Cum

± 6.00 M 2800 1200 2350 350 300 1700 5638 10377

350 200
± 0.00 M 2800 1800 2300 400 450 325 200 2300 4607 9768
0 0

Wet ± 3.00 M 2800 1800 2300 400 450 2300 5123 10498 59.25 Cum 0.00 Cum 1.60 Cum 5.76 Cum

± 6.00 M 2800 1800 2300 400 450 2300 5638 11226

350 200
± 0.00 M 2950 2400 2000 700 450 325 200 2900 4607 10617
300 300

P.S. ± 3.00 M 2950 2400 2000 700 450 2900 5123 11346 99.24 Cum 5.05 Cum 2.70 Cum 12.43 Cum

± 6.00 M 2950 2400 2000 700 450 2900 5638 12075

350 200
± 0.00 M 2950 2850 2000 700 450 325 200 3350 4607 11253
525 300

F.S. ± 3.00 M 2950 2850 2000 700 450 3350 5123 11983 132.43 Cum 6.73 Cum 3.72 Cum 15.26 Cum

± 6.00 M 2950 2850 2000 700 450 3350 5638 12711

2
140 1200
± 0.00
2700 730 1500 1200 450 730 4607 7548
M

Hard ± 0.00
2700 730 1500 1200 450 730 5123 8277 2.56 Cum 0.00 Cum 0.00 Cum 2.80 Cum
Rock M

± 0.00
2700 730 1500 1200 450 730 5638 9006
M

375 500
± 0.00
2700 1200 2200 500 450 1200 4607 8212
M

F&F ± 0.00
2700 1200 2200 500 450 1200 5123 8942 15.55 Cum 0.00 Cum 0.00 Cum 4.91 Cum
ROCK M

± 0.00
2700 1200 2200 500 450 1200 5638 9670
M
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004
Scale 1:50
x
COPING

G.L
Stub 100x100x8
EXCAVATION LINE
75

225
GL GL

300x300
M

SECTION Excavation Line


2350
G
2800
G
CL EAT S

300
EXCAVATION LINE
150 250
200
C.C. 1:2:4
150
100 P.C.C. 1:4:8
C
L OF TOWER 600 600
1200
M 1400
K
1700
SOIL CLASSIFICATION
G Where normal dry cohesive or non-cohesive soils are met.

PLAN Released for Construction

CHIEF ENGINEER/CIVIL

TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED


Constants Volume of
G M K Excavation Concrete P.C.C. Sand
+ 0M 4,607 8,919 FOUNDATION DETAILS OF 132 K.V. - "P" TYPE TOWER
+ 3M 1700 5,123 9,649 32.37 Cum 2.47 Cum 0.78 Cum 0.00 Cum
+ 6M 5,638 10,377 Drg. No. 132KV-TL-P-DRY DRY
Pa g e

4
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004
Scale 1:50
x Stub 100x100x8
COPING
75
G.L

GL 225 GL
EXCAVATION LINE

450x450

Excavation Line
2300
M
2800
SECTION
G CL EAT S

G 350
200 C.C. 1:2:4
325 250
200
EXCAVATION LINE
100 P.C.C. 1:4:8
900 900
1800
2000
C
L OF TOWER
2300
M SOIL CLASSIFICATION
K
a) Where sub soil water is met at 1.5 Mtrs. or more below the ground level in normal
soil. (OR)
G b) Where surface water could stand for long period with water penetration not
exceeding 1 Mtr. Below ground level (example : Paddy fields, Sugarcane fields).
G

PLAN Released for Construction

CHIEF ENGINEER/CIVIL

Constants Volume of TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED


G M K Excavation Concrete P.C.C. Sand
+ 0M 4,607 9,768 FOUNDATION DETAILS OF 132 K.V. - "P" TYPE TOWER
+ 3M 2300 5,123 10,498 59.25 Cum 5.76 Cum 1.60 Cum 0.00 Cum
+ 6M 5,638 11,226 Drg. No. 132KV-TL-P-WET WET
Pa g e

5
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004
Scale 1:50
x Stub 100x100x8
COPING
75
G.L

GL 225 GL
EXCAVATION LINE

450x450

2000 Excavation Line


M
2950
SECTION
G CL EAT S
350

G 200 325
200 300 250

300 C.C. 1:2:4


EXCAVATION LINE
100 P.C.C. 1:4:8
150 Sand Filling
1200 1200
C
L OF TOWER 2400
2600
M
K 2900
SOIL CLASSIFICATION
G a) Where sub soil water is encountered between 0.75 Mtrs. and 1.5 Mtrs. depth
below ground level. (OR)
b) Where top layer of black cotton soil extends up to 50 % of the depth with
G normal soil thereafter. (OR)
NOTE : Where soil is clayey type, not necessarily black in colour,
PLAN which shrinks when dry, swells when wet. Released for Construction

CHIEF ENGINEER/CIVIL
Constants Volume of TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
G M K Excavation Concrete P.C.C. Sand
+ 0M 4,607 10,617 FOUNDATION DETAILS OF 132 K.V. - "P" TYPE TOWER
+ 3M 2900 5,123 11,346 99.24 Cum 12.43 Cum 2.70 Cum 5.05 Cum
+ 6M 5,638 12,075 Drg. No. 132KV-TL-P-P.S. PS / PBC
Page

6
Stub 100x100x8
T.O.O. Dir (Tr. & G.O.) M .S. No. 156 Dated 8-10-2004
75
Scale 1:50
x
GL 225 GL
COPING

G.L
450x450
EXCA VATION LINE

2000 Excavation Line

2950

CL E A T S
350
M
200 325
SECTION
G 200 525 250

300 C.C. 1:2:4


G 100 P.C.C. 1:4:8
150 Sand Filling

EXCA VATION LINE 1425 1425

2850
3050
C
L OF TOW ER
3350
M 8 NOS. 10 TOR SUPPORTING RODS
K TOTAL 32 NOS. PER TOW ER

G 8 TOR @ 300 C/C.


SOIL CLASSIFICATION 10 NOS. 2 W AY (TOTAL 80 NOS. PER TOW ER)
a) W here subsoil water table is within 0.75 Mtrs. depth from ground level. (OR)
G
b) W here top layer of black cotton soil exceeds 50% and extends up to full depth or is
followed by norm al soil. (OR)
PL A N c) W here top layer is norm al soil up to 50% of the Released for Construction
depth but the lower layer is a black cotton soil.
CHIEF ENGINEER/CIVIL
Constants Volume of
Steel TRANSM ISSION CORPORATION OF ANDHRA PRADESH LIM ITED
G M K Excavation Concrete P.C.C. Sand
+ 0M 4,607 11,253
+ 3M 3350 5,123 11,983 132.43 Cum 15.26 Cum 3.72 Cum 6.73 Cum 202.34Kgs FOUNDATION DETAILS OF 132 K.V. - "P" TYPE TOW ER
+ 6M 5,638 12,711
Drg. No. 132KV-TL-P-F.S. FS / BC
Page

7
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004
STUB ANGLE Scale 1:25
x 75
100X100X8
COPING
225 450X450
G.L GL GL
EXCAVATION LINE

EARTH OR SOFT ROCK


0 to 1500

M
2700
SECTION
G C.C. 1:2:4

G 1200

EXCAVATION LINE

730
C
L OF TOWER
SOIL CLASSIFICATION
M a) Where hard rock is encountered at 1.5 Mtrs. or less below ground level. (OR)
K
b) Where hard rock is encountered from 1.5 Mtrs. to 2.5 Mtrs. below ground level
though top layer is of normal soil. (OR)
G c) Where chiseling, drilling and blasting is required for excavation.

PLAN Released for Construction

CHIEF ENGINEER/CIVIL
G M K Excavation Concrete TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
+ 0M 4,607 7,548
2.56 to 5.76 2.80 to
+3M 730 5123 8277 CuM 4.07CuM
FOUNDATION DETAILS OF 132 K.V. - "P" TYPE TOWER
+6M 5638 9006 Drg. No. Pa g e
132KV-TL-P-H.R. HARD ROCK 8
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004
Scale 1:50
x
COPING
75 STUB ANGLE
100X100X8
G.L GL 225 GL
EXCAVATION LINE

450X450

2200
2700
J
SECTION
G

G
500 C.C. 1:2:4

EXCAVATION LINE

1200

C
L OF TOWER
SOIL CLASSIFICATION
M a) Where decomposed or fissured rock, hard gravel, kankar, lime stone, laterite
K or any other soil of similar nature is met. (OR)
b) Where top layer of normal dry soil extends up to 85% of the depth followed
G by fissured rock without presence of water.

PLA N Released for Construction

CHIEF ENGINEER/CIVIL
G M K Volume of
TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
+0 M 4607 8212 Excavation Concrete
+3M 1200 5123 8942 FOUNDATION DETAILS OF 132 K.V. - "P" TYPE TOWER
15.55CuM 4.91CuM
+6M 5638 9670
Drg. No. 132KV-TL-P-S.R. SOFT ROCK/ F&F ROCK
Page

9
FOUNDATION DETAILS FOR 132 KV "R" TYPE TOWER
Basic W1 D1 Vol. Of
Soil A B C D F G M K Vol. Of
Tower W2 D2 Excavation Sand Bed PCC 1:4:8
Type (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) PCC 1:2:4
Extn. W3 D3 M3
200 200
± 0.00 M 2960 1350 2410 450 350 300 250 1850 8192 14202
0 0

Dry ± 3.00 M 2960 1350 2410 450 350 1850 9325 15804 40.52 Cum 0.00 Cum 0.96 Cum 3.60 Cum

± 6.00 M 2960 1350 2410 450 350 1850 10453 17399

575 230
± 0.00 M 2960 2300 2430 430 450 350 200 2800 8192 15545
0 0

Wet ± 3.00 M 2960 2300 2430 430 450 2800 9325 17147 92.83 Cum 0.00 Cum 2.50 Cum 8.80 Cum

± 6.00 M 2960 2300 2430 430 450 2800 10453 18743

575 230
± 0.00 M 3110 2900 2130 730 450 350 200 3400 8192 16394
300 300

P.S. ± 3.00 M 3110 2900 2130 730 450 3400 9325 17996 143.81 Cum 6.94 Cum 3.84 Cum 18.65 Cum

± 6.00 M 3110 2900 2130 730 450 3400 10453 19591

575 230
± 0.00 M 3110 3300 2130 730 450 350 200 3800 8192 16959
500 300
F.S. 179.63 Cum 8.66 Cum 4.90 Cum 21.62 Cum
± 3.00 M 3110 3300 2130 730 450 3800 9325 18562

± 6.00 M 3110 3300 2130 730 450 3800 10453 20157


215 1400
± 0.00 M 2860 880 1460 1400 450 880 8192 12830

Hard
± 3.00 M 2860 880 1460 1400 450 880 9325 14432 4.34 Cum 5.76 Cum
Rock

± 6.00 M 2860 880 1460 1400 450 880 10453 16027

650 550
± 0.00 M 2860 1750 2310 550 450 1750 8192 14060

F&F
35.04 Cum 8.85 Cum
ROCK ± 3.00 M 2860 1750 2310 550 450 1750 9325 15662

± 6.00 M 2860 1750 2310 550 450 1750 10453 17258


T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004
Scale 1:50
x
COPING

G.L
Stub 130x130x10
EXCAVATION LINE
75

225
GL GL

350x350
M

SECTION Excavation Line


G 2410
2960
G
CL EAT S
200
EXCAVATION LINE
300 250
200
250 C.C. 1:2:4
C
L OF TOWER 100 P.C.C. 1:4:8
675 675
M 1350
K
1550
1850
G
SOIL CLASSIFICATION
Where normal dry cohesive or non-cohesive soils are met.
G

PLAN Released for Construction

CHIEF ENGINEER/CIVIL
Constants Volume of
G M K Excavation Concrete P.C.C. Sand TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
+ 0M 8,192 14,202
+ 3M 1850 9,325 15,804 40.52 Cum 3.60 Cum 0.96 Cum 0.00 Cum FOUNDATION DETAILS OF 132 K.V. - "R" TYPE TOWER
+ 6M 10,453 17,399 Drg. No. 132KV-TL-R-DRY DRY
Pa g e

12
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004
Scale 1:50
x Stub 130x130x10
COPING
75
G.L

GL 225 GL
EXCAVATION LINE

450x450

Excavation Line
M 2430
2960
SECTION
G

CL EAT S 575
G
350 250
230
EXCAVATION LINE
200 C.C. 1:2:4
100 P.C.C. 1:4:8
1150 1150
C
L OF TOWER 2300
2500
m
K
2800
SOIL CLASSIFICATION
G a) Where sub soil water is met at 1.5 Mtrs. or more below the ground level in
normal soil. (OR)
b) Where surface water could stand for long period with water penetration
G
not exceeding 1 Mtr. Below ground level (example : Paddy fields,
Sugarcane fields).
PLAN Released for Construction

CHIEF ENGINEER/CIVIL
Constants Volume of
G M K Excavation Concrete P.C.C. Sand TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
+ 0M 8,192 15,545
+ 3M 2800 9,325 17,147 92.83 Cum 8.80 Cum 2.50 Cum 0.00 Cum FOUNDATION DETAILS OF 132 K.V. - "R" TYPE TOWER
+ 6M 10,453 18,743 Drg. No. Pag e
132KV-TL-R-WET WET 13
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004
Scale 1:50
x Stub 130x130x10
COPING
75
G.L

GL 225 GL
EXCAVATION LINE

450x450

2130
M Excavation Line
SECTION
3110 CL EAT S
G 575

G 350
230
300 250
200
EXCAVATION LINE
300 C.C. 1:2:4
100 P.C.C. 1:4:8
150 Sand Filling
1450 1450
C
L OF TOWER
2900
M 3100
K

3400
G SOIL CLASSIFICATION
a) Where sub soil water is encountered between 0.75 Mtrs. and 1.5 Mtrs. depth
below ground level. (OR)
G
b) Where top layer of black cotton soil extends up to 50% of the depth with normal
soil thereafter.
PLAN NOTE : Where soil is clayey type, not necessarily black in colour, Released for Construction
which shrinks when dry, swells when wet.
CHIEF ENGINEER/CIVIL
Constants Volume of
TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
G M K Excavation Concrete P.C.C. Sand
+ 0M 8,192 16,394
+ 3M 3400 9,325 17,996 143.81 Cum 18.65 Cum 3.84 Cum 6.94 Cum FOUNDATION DETAILS OF 132 K.V. - "R" TYPE TOWER
+ 6M 10,453 19,591
Drg. No. 132KV-TL-R-P.S. PS / PBC
Pa g e

14
Stub 130x130x10
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004
75 Scale 1:50
x 225
GL GL
COPING

G.L
450x450
EXCAVATION LINE

Excavation Line
2130

3110 CL EAT S
575
M
350
SECTION 230
G 500 250
200 C.C. 1:2:4
G 300
100 P.C.C. 1:4:8
150 Sand Filling
EXCAVATION LINE
1650 1650
3300
3500
C
L OF TOWER
3800
M 8 NOS. 10 TOR SUPPORTING RODS/PIT
K TOTAL 32 NOS. /TOWER

G 10 TOR @ 400 C/C. (9 NOS. 2 WAY)


SOIL CLASSIFICATION TOTAL 72 NOS. /TOWER

G a) Where subsoil water table is within 0.75 Mtrs. depth from ground level. (OR)
b) Where top layer of black cotton soil exceeds 50% and extends up to full depth or is
followed by normal soil. (OR)
PLAN Released for Construction
c) Where top layer is normal soil up to 50% of the depth
but the lower layer is a black cotton soil.
CHIEF ENGINEER/CIVIL
Constants Volume of TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
Steel
G M K Excavation Concrete P.C.C. Sand
+ 0M 8,192 16,959
FOUNDATION DETAILS OF 132 K.V. - "R" TYPE TOWER
+ 3M 3800 9,325 18,562 179.63 Cum 21.62 Cum 4.90 Cum 8.66 Cum 336.29 Kgs
+ 6M 10,453 20,157 Drg. No. 132KV-TL-R-F.S. FS / BC
Page

15
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004
STUB ANGLE Scale 1:25
x 75
130X130X10
COPING
450X450
225
G.L GL GL
EXCAVATION LINE

EARTH OR SOFT ROCK


0 to
1460

M 1400 to
2860
SECTION C.C. 1:2:4
G

G 1400

EXCAVATION LINE

880
C
L OF TOWER

SOIL CLASSIFICATION
M
K a) Where hard rock is encountered at 1.5 Mtrs. or less below ground
level.(OR)
b) Where hard rock is encountered from 1.5 Mtrs. to 2.5 Mtrs. below ground
G level though top layer is of normal soil. (OR)
c) Where chiseling, drilling and blasting is required for excavation.
G

PL A N Released for Construction

CHIEF ENGINEER/CIVIL
G M K Excavation Concrete TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
+0M 8,192 12,830
4.34 to 4.82 to
+3M 880 9325 14432
8.86CuM 5.76CuM
FOUNDATION DETAILS OF 132 K.V. - "R" TYPE TOWER
+6M 10453 16027
Drg. No. 132KV-TL-R-H.R. HARD ROCK
Page

16
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004
Scale 1:50
x
COPING
75 STUB ANGLE
130X130X10
G.L GL 225 GL
EXCAVATION LINE

450X450

2310

M 2860
SECTION
G

G
550 C.C. 1:2:4
EXCAVATION LINE

1750

C
L OF TOWER SOIL CLASSIFICATION
a) Where decomposed or fissured rock, hard gravel, kankar, lime stone, laterite or
M any other soil of similar nature is met. (OR)
K
b) Where top layer of normal dry soil extends up to 85% of the depth followed by
fissured rock without presence of water.
G

PLAN Released for Construction

CHIEF ENGINEER/CIVIL
G M K Volume of
TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
+0 M 8192 14060 Excavation Concrete
+3M 2860 9325 15662 FOUNDATION DETAILS OF 132 K.V. - "R" TYPE TOWER
35.04CuM 8.85 CuM
+6M 10453 17258
Drg. No. 132KV-TL-R-S.R. SOFT ROCK/ F&F ROCK
Page

17
FOUNDATION DETAILS FOR 132 KV "S" TYPE TOWER
Basic W1 D1 Vol. Of
Soil A B C D F G M K PCC Vol. Of
Tower W2 D2 Excavation Sand Bed
Type (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) 1:4:8 PCC 1:2:4
Extn. W3 D3 M3
200 250
± 0.00 M 3300 1800 2400 800 350 225 250 2300 8997 15976
300 300

Dry ± 3.00 M 3300 1800 2400 800 350 2300 10213 17696 69.83 Cum 0.00 Cum 1.60 Cum 7.21 Cum

± 6.00 M 3300 1800 2400 800 350 2300 11428 19414

575 420
± 0.00 M 3300 2700 2380 820 450 550 400 3200 8997 17249
0

Wet ± 3.00 M 3300 2700 2380 820 450 3200 10213 18969 135.17 Cum 0.00 Cum 3.36 Cum 18.14 Cum

± 6.00 M 3300 2700 2380 820 450 3200 11428 20687

575 420
± 0.00 M 3450 3600 1950 1250 450 550 400 4100 8997 18522
450 430

P.S. ± 3.00 M 3450 3600 1950 1250 450 4100 10213 20242 231.98 Cum 10.09 Cum 5.78 Cum 40.08 Cum

± 6.00 M 3450 3600 1950 1250 450 4100 11428 21960

575 420
± 0.00 M 3450 3850 1850 1350 450 550 400 4350 8997 18876
575 530
F.S. 261.13 Cum 11.35 Cum 6.56 Cum 49.13 Cum
± 3.00 M 3450 3850 1850 1350 450 4350 10213 20595

± 6.00 M 3450 3850 1850 1350 450 4350 11428 22313


340 1930
± 0.00 M 3200 1130 1270 1930 450 1130 8997 14322

Hard
± 3.00 M 3200 1130 1270 1930 450 1130 10213 16041 9.86 Cum 11.13 Cum
Rock

± 6.00 M 3200 1130 1270 1930 450 1130 11428 17760

775 1050
± 0.00 M 3200 2000 2150 1050 450 2000 8997 15552

F&F
± 3.00 M 3200 2000 2150 1050 450 2000 10213 17272 51.20 Cum 18.78 Cum
ROCK

± 3.00 M 3200 2000 2150 1050 450 2000 11428 18990


T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004
Scale 1:50
x
COPING

G.L
Stub 150x150x12
EXCAVATION LINE
75

225
GL GL

350x350
M

SECTION
G 2400
Excavation Line
3300
G
CL EAT S

EXCAVATION LINE 200


225
250
300 250
250 C.C. 1:2:4
C
L OF TOWER
300
M 100 P.C.C. 1:4:8
K 900 900
1800

G 2000
2300

G SOIL CLASSIFICATION
Where normal dry cohesive or non-cohesive soils are met.
PLAN Released for Construction

Constants Volume of CHIEF ENGINEER/CIVIL


G M K Excavation Concrete P.C.C. Sand
+ 0M 8,997 15,976 TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
+ 3M 2300 10,213 17,696 69.83 Cum 7.21 Cum 1.60 Cum 0.00 Cum
+ 6M 11,428 19,414 FOUNDATION DETAILS OF 132 K.V. - "S" TYPE TOWER
Drg. No. 132KV-TL-S-DRY DRY
Pag e

20
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004

x
Scale 1:50
Stub 150x150x12
COPING
75
G.L

GL 225 GL
EXCAVATION LINE

450x450

Excavation Line
2380
M
3300
SECTION
G CL EAT S

575
G

420 550 250


EXCAVATION LINE

C.C. 1:2:4
400
100 P.C.C. 1:4:8
C
L OF TOWER
1350 1350
M 2700
K
2900
3200
G SOIL CLASSIFICATION
a) Where sub soil water is met at 1.5 Mtrs. or more below the ground level in
normal soil. (OR)
G
b) Where surface water could stand for long period with water penetration not
exceeding 1 Mtr. Below ground level (example : Paddy fields, Sugarcane
PLAN Released for Construction
fields).

CHIEF ENGINEER/CIVIL
Constants Volume of
TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
G M K Excavation Concrete P.C.C. Sand
+ 0M 8,997 17,249
FOUNDATION DETAILS OF 132 K.V. - "S" TYPE TOWER
+ 3M 3200 10,213 18,969 135.17 Cum 18.14 Cum 3.36 Cum 0.00 Cum
+ 6M 11,428 20,687 Drg. No. 132KV-TL-S-WET WET
Page

21
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004 Stub 150x150x12
Scale 1:50
x 75

COPING
GL 225 GL
G.L

EXCAVATION LINE
450x450

1950 Excavation Line

CL EAT S
575
M
3450
SECTION
420 550
G

450 250
G 400

C.C. 1:2:4
430
EXCAVATION LINE
100 P.C.C. 1:4:8
150 Sand Filling

1800 1800
C
L OF TOWER
3600
M
K 3800
4100
G SOIL CLASSIFICATION
a) Where sub soil water is encountered between 0.75 Mtrs. and 1.5 Mtrs. depth below
G ground level. (OR)
b) Where top layer of black cotton soil extends up to 50% of the depth with normal
soil thereafter.
PLAN Released for Construction
NOTE : Where soil is clayey type, not necessarily black in colour,
which shrinks when dry, swells when wet.
CHIEF ENGINEER/CIVIL
Constants Volume of TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
G M K Excavation Concrete P.C.C. Sand
+ 0M 8,997 18,522 FOUNDATION DETAILS OF 132 K.V. - "S" TYPE TOWER
+ 3M 4100 10,213 20,242 231.98 Cum 40.08 Cum 5.78 Cum 10.09 Cum
+ 6M 11,428 21,960 Drg. No. 132KV-TL-S-P.S. PS / PBC
Page

22
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004 Stub 150x150x12

75 Scale 1:50
x
COPING GL 225 GL

G.L

450x450

1850
Excavation Line
EXCAVATION
LINE

CL EAT S
575

M 3450
420 550
SECTION
G
575 250
400
G

530 C.C. 1:2:4


EXCAVATION LINE
100 P.C.C. 1:4:8
150 Sand Filling
1925 1925
C
L OF TOWER
3850
M 4050
K
4350
8 NOS. 10 TOR SUPPORTING RODS
(32 NOS. /TOWER) 10 TOR @ 375 C/C.
G 11 NOS. 2 WAY
SOIL CLASSIFICATION (TOTAL 88 NOS. /TOWER)
G a) Where subsoil water table is within 0.75 Mtrs. depth from ground level. (OR)
b) Where top layer of black cotton soil exceeds 50% and extends up to full depth or is
PLAN followed by normal soil. (OR) Released for Construction
c) Where top layer is normal soil up to 50% of the
depth but the lower layer is a black cotton soil.
CHIEF ENGINEER/CIVIL

Constants Volume of TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED


Steel
G M K Excavation Concrete P.C.C. Sand
+ 0M 8,997 18,876 FOUNDATION DETAILS OF 132 K.V. - "S" TYPE TOWER
+ 3M 4350 10,213 20,595 261.13 Cum 49.13 Cum 6.56 Cum 11.35 Cum 487.82 Kgs
Drg. No. 132KV-TL-S-F.S. FS / BC
Pa g e

23
+ 6M 11,428 22,313
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004
75 STUB ANGLE Scale 1:25
x
130X130X10
COPING
450X450
225
G.L GL GL
EXCAVATION LINE

EARTH OR SOFT
ROCK
0 to
1270
M 1930 to
3200
SECTION C.C. 1:2:4
G

G 1930

EXCAVATION LINE

1130
C
L OF TOWER SOIL CLASSIFICATION
a) Where hard rock is encountered at 1.5 Mtrs. or less below ground level.(OR)
M
K
b) Where hard rock is encountered from 1.5 Mtrs. to 2.5 Mtrs. below ground
level though top layer is of normal soil.(OR)
c) Where chiseling, drilling and blasting is required for excavation.
G

PLAN Released for Construction

CHIEF ENGINEER/CIVIL
Constants Volume of
TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
G M K Excavation Hard Rock Concrete Sand
+ 0M 8,997 14,322 FOUNDATION DETAILS OF 132 K.V. - "S" TYPE TOWER
9.86 to 10.10 to
+ 3M 1130 10,213 16,041 9.86 Cum 0.00 Cum
16.34CuM 11.13 CuM Drg. No. 132KV-TL-S-H.R. HARD ROCK
Page

+ 6M 11,428 17,760 24
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004

x Scale 1:50
COPING
75 STUB ANGLE
150X150X12
G.L GL 225 GL
EXCAVATION LINE

450X450

2150

M
3200
SECTION
G

G
C.C. 1:2:4
1050
EXCAVATION LINE

C
L OF TOWER 2000

M SOIL CLASSIFICATION
K
a) Where decomposed or fissured rock, hard gravel, kankar, lime stone, laterite or any
other soil of similar nature is met. (OR)
G b) Where top layer of normal dry soil extends up to 85% of the depth followed by
fissured rock without presence of water.
G

PLAN Released for Construction

CHIEF ENGINEER/CIVIL

G M K Volume of TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED


+0 M 8997 15552 Excavation Concrete
FOUNDATION DETAILS OF 132 K.V. - "S" TYPE TOWER
+3M 2000 10213 17272
51.20CuM 18.78CuM
+6M 11428 18990 Drg. No. 132KV-TL-S-S.R. SOFT ROCK/ F&F ROCK
Pag e

25
75 STUB ANGLE
x
COPING
G.L GL 225 GL
EXCAVATION LINE

FxF
C

J
W1
SECTION
G
A W2
D1
G

D W3 250
D2
EXCAVATION LINE

D3 C.C. 1:2:4
100 P.C.C. 1:4:8
C
L OF TOWER
B/2 B/2
J
K
B

G
NOTE-2 : For locations of cut point / angle towers, the classification of tower
foundations shall be at next higher type for ensuring safety of the Transmission
line which is likely to be subjected to seasonal changes / climatic conditions
G from time to time.
NOTE-3 : In case of highly collapsible & loose soils and river crossings, special
PLAN design for foundations are to be made by Civil Engineering wing for adoption on
case to case basis.
NOTE-4 : All locations subjected to water logging, particularly in paddy fields,
NOTE-1 : While classifying foundations of Wet, Partially submerged /
ponds, marshy areas etc., the chimney of all stubs are to be raised to 600 mm
Partially black cotton, Fully submerged / Black cotton foundations
over the normal chimney being adopted in other cases. This shall be done after
mentioned above, the worst conditions should be considered and not
completion of erection of towers as a separate item for identified locations.
necessarily the conditions prevailing at the time of inspection. For
instance there are areas where subsoil water raised when canal water is
let out in the field raising subsoil water to a considerable degree. TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
Similarly the effect of monsoon or when the nearby reservoirs are full
should be considered and not the conditions prevailing in open season or FOUNDATION DETAILS OF 220 K.V. TYPE TOWER -
summer when work is carried out normally. (L&T)
Drg. No. 220KV-TL-G.A. Scale 1:50
Page

26
FOUNDATION DETAILS FOR 220 KV A-TYPE TOWER
Basic W1 D1 Vol. Of Vol. Of
Soil A B C D F X PCC Sand G J K
Tower W2 D2 Excavation PCC M-15
Type (mm) (mm) (mm) (mm) (mm) (mm) 1:4:8 filling (mm) (mm) (mm)
Extension W3 D3 M3 M3
175 200
± 0.00 M 3000 1400 2500 500 300 6251 375 300 6872 12405
0 0
1.02
Dry ± 3.00 M 3000 1400 2500 500 300 6964 44.76 Cum 1900 7585 13414 3.70 Cum
Cum

± 6.00 M 3000 1400 2500 500 300 7676 8297 14421

325 350
± 0.00 M 3000 2000 2250 750 450 6251 450 400 6815 13173
0 0
1.94
Wet ± 3.00 M 3000 2000 2250 750 450 6964 77.50 Cum 2500 7528 14182 10.16 Cum
Cum

± 6.00 M 3000 2000 2250 750 450 7676 8240 15189

375 350
± 0.00 M 3000 2550 1950 1050 450 6251 375 400 6750 13859
300 300
3.03 5.58
P.S. ± 3.00 M 3000 2550 1950 1050 450 6964 120.93 Cum 3050 7463 14868 17.73 Cum
Cum Cum

± 6.00 M 3000 2550 1950 1050 450 7676 8175 15875

325 350
± 0.00 M 3000 3000 1800 1200 450 6251 450 400 6679 14395
500 450
4.10 7.35
F.S. ± 3.00 M 3000 3000 1800 1200 450 6964 159.25 Cum 3500 7392 15404 26.00 Cum
Cum Cum

± 6.00 M 3000 3000 1800 1200 450 7676 8104 16411


275 1200
± 0.00 M 1200 1000 0 1200 450 6251 6304 10329

HardRock ± 3.00 M 1200 1000 0 1200 450 6964 4.80 Cum 1000 7017 11338 5.04 Cum

± 6.00 M 1200 1000 0 1200 450 7676 7729 12345

625 650
± 0.00 M 3000 1700 2350 650 450 6251 6815 12042

Soft
± 3.00 M 3000 1700 2350 650 450 6964 34.68 Cum 1700 7528 13050 9.66 Cum
Rock

± 6.00 M 3000 1700 2350 650 450 7676 8240 14057


T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004

x
Scale 1:50
COPING
75 STUB ANGLE
100X100X10

G.L GL 225 GL
EXCAVATION LINE

300X300

2500
J
3100
SECTION
G

175
G
200 375 250

EXCAVATION LINE 300 C.C. 1:2:4


100 P.C.C. 1:4:8
700 700
1400
C
L OF TOWER 1600
1900
J
K
SOIL CLASSIFICATION
G Where normal dry cohesive or non-cohesive soils are met.

PLAN Released for Construction

CHIEF ENGINEER/CIVIL
G J K Volume of TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
+0 M 6872 12405 Excavation Concrete P.C.C.
FOUNDATION DETAILS OF 220 K.V. - "A" TYPE TOWER -
+3M 1900 7585 13414 (L&T)
44.76CuM 3.70CuM 1.02CuM
+6M 8297 14421 Drg. No. 220KV-TL-A-DRY DRY
Page

29
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004

x Scale 1:50
COPING
75 STUB ANGLE
100X100X10

G.L GL 225 GL
EXCAVATION LINE

450X450

2250

J
3100
SECTION
G
325

G 450 250
350

EXCAVATION LINE
400 C.C. 1:2:4
100 P.C.C. 1:4:8
1000 1000
2000
C
L OF TOWER 2200
2500
J
K SOIL CLASSIFICATION
a) Where sub soil water is met at 1.5 Mtrs. or more below the ground level in
normal soil.(OR)
G b) Where surface water could stand for long period with water penetration
not exceeding 1 Mtr. Below ground level (example : Paddy fields, Sugarcane
G fields).

PLAN Released for Construction

CHIEF ENGINEER/CIVIL

G J K Volume of TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED


+0 M 6815 13173 Excavation Concrete P.C.C.
FOUNDATION DETAILS OF 220 K.V. - "A" TYPE TOWER -
+3M 2500 7528 14182
77.50CuM 10.16CuM 1.94CuM (L&T)
+6M 8240 15189
Drg. No. 220KV-TL-A-WET WET
Pa ge

30
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004

x
Scale 1:50
COPING
75 STUB ANGLE
100X100X10

G.L GL 225 GL
EXCAVATION LINE

450X450

1950

J
3250
SECTION 375
G
375
350 C.C. 1:2:4
G 300 250
400

EXCAVATION LINE 300


100 P.C.C. 1:4:8
150 Sand Filling
1275 1275
C
L OF TOWER
2550
J 2750
K
SOIL CLASSIFICATION 3050

G
a) Where sub soil water is encountered between 0.75 Mtrs. and 1.5 Mtrs. depth below
ground level.(OR)
b) Where top layer of black cotton soil extends up to 50 % of the depth with normal soil
G thereafter.
NOTE : Where soil is clayey type, not necessarily
PLAN black in colour, which shrinks when dry, swells when wet. Released for Construction

CHIEF ENGINEER/CIVIL
G J K Volume of TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
+ 0M 6,750 13,859 Excavation Concrete P.C.C. Sand
FOUNDATION DETAILS OF 220 K.V. - "A" TYPE TOWER -
+ 3M 3050 7,463 14,868 (L&T)
120.93 Cum 17.73 Cum 3.03 Cum 5.58 Cum
+ 6M 8,175 15,875
Drg. No. 220KV-TL-A-P.S. PS / PBC
Page

31
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004
Scale 1:50
x
COPING
75 STUB ANGLE
100X100X10

G.L GL 225 GL
EXCAVATION LINE

450X450
1800

J 325
3250
SECTION
450
G 350

500 250 C.C. 1:2:4


G 400

450
EXCAVATION LINE
100 P.C.C. 1:4:8
150 Sand Filling
1500 1500
C
L OF TOWER 3000
3200
J
K 3500
SOIL CLASSIFICATION
a) Where subsoil water table is within 0.75 Mtrs. depth from ground level. (OR)
G b) Where top layer of black cotton soil exceeds 50% and extends up to full depth or is
followed by normal soil. (OR)
G c) Where top layer is normal soil up to 50% of the depth but the lower layer is a black
cotton soil.
PLAN Released for Construction

CHIEF ENGINEER/CIVIL

G J K Volume of TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED


+ 0M 6,679 14,395 Excavation Concrete P.C.C. Sand FOUNDATION DETAILS OF 220 K.V. - "A" TYPE TOWER -
+ 3M 3500 7,392 15,404 (L&T)
159.25 Cum 26.00 Cum 4.10 Cum 7.35 Cum
+ 6M 8,104 16,411
Drg. No. 220KV-TL-A-F.S. FS / BC
Pa g e

32
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004
75 STUB ANGLE Scale 1:25
x
100X100X10
COPING
225 450X450
G.L GL GL
As per field conditions
EXCAVATION LINE
0 to 1800

J
1200
SECTION C.C. 1:2:4
G

EXCAVATION LINE

1000

C
L OF TOWER

J
K
SOIL CLASSIFICATION
a) Where hard rock is encountered at 1.5 Mtrs. or less below ground level.(OR)
b) Where hard rock is encountered from 1.5 Mtrs. to 2.5 Mtrs. below ground
G level though top layer is of normal soil.(OR)
c) Where chiseling, drilling and blasting is required for excavation.
G

PLAN Released for Construction

CHIEF ENGINEER/CIVIL

G J K Volume of TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED


+0 M 6304 10329 Excavation Concrete FOUNDATION DETAILS OF 220 K.V. - "A" TYPE TOWER -
+3M 1000 7017 11338 4.8 to 5.04 to (L&T)
+6M 7729 12345 12.00CuM 6.50 CuM Drg. No. 220KV-TL-A-H.R. HARD ROCK
Page

33
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004

x Scale 1:50
COPING
75 STUB ANGLE
100X100X10
G.L GL 225 GL
EXCAVATION LINE

450X450

2350

J
3000
SECTION
G

G
650
C.C. 1:2:4
EXCAVATION LINE

1700

C
L OF TOWER
SOIL CLASSIFICATION
J a) Where decomposed or fissured rock, hard gravel, kankar, lime stone,
K laterite or any other soil of similar nature is met.(OR)
b) Where top layer of normal dry soil extends up to 85% of the depth followed
G
by fissured rock without presence of water.

PLAN Released for Construction

CHIEF ENGINEER/CIVIL

G J K Volume of TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED


+0 M 6815 12042 Excavation Concrete FOUNDATION DETAILS OF 220 K.V. - "A" TYPE TOWER -
+3M 1700 7528 13050 (L&T)
34.68CuM 9.66CuM
+6M 8240 14057 Drg. No. 220KV-TL-A-S.R. SOFT ROCK/ F&F ROCK
Pa g e

34
FOUNDATION DETAILS FOR 220 KV B-TYPE TOWER
Basic Vol. Of
W1 D1 Vol. Of
Soil Tower A B C D F X PCC Sand G J K PCC M-15
W2 D2 Excavation
Type (mm) (mm) (mm) (mm) (mm) (mm) 3 1:4:8 filling (mm) (mm) (mm) M3 with
W3 D3 M
Extension Steps
200 150
± 0.00 M 3500 1650 2950 550 350 8300 450 400 9301 16194
0 0

1.37
Dry ± 3.00 M 3500 1650 2950 550 350 9301 66.56 Cum 2150 10302 17610 6.29 Cum
Cum

± 6.00 M 3500 1650 2950 550 350 10301 11302 19024

450 450
± 0.00 M 3500 2550 2475 1025 450 8300 325 300 9167 17277
275 275

3.03
Wet ± 3.00 M 3500 2550 2475 1025 450 9301 133.96 Cum 3050 10168 18693 17.48 Cum
Cum

± 6.00 M 3500 2550 2475 1025 450 10301 11168 20107

450 450
± 0.00 M 3500 3000 2270 1230 450 8300 325 300 9092 17808
500 480

4.10 7.35
P.S. ± 3.00 M 3500 3000 2270 1230 450 9301 183.75 Cum 3500 10093 19223 27.44 Cum
Cum Cum

± 6.00 M 3500 3000 2270 1230 450 10301 11093 20638

525 450
± 0.00 M 3500 3500 2200 1300 450 8300 500 300 8992 18373
500 550
5.48 9.60
F.S. 240.00 Cum 4000 40.53 Cum
± 3.00 M 3500 3500 2200 1300 450 9301 Cum Cum 9993 19789

± 6.00 M 3500 3500 2200 1300 450 10301 10993 21203


425 1300
± 0.00 M 1300 1300 0 1300 450 8300 8375 13683

HardRock ± 3.00 M 1300 1300 0 1300 450 9301 8.79 Cum 1300 9376 15098 9.03 Cum

± 6.00 M 1300 1300 0 1300 450 10301 10376 16512

950 1125
± 0.00 M 3500 2350 2375 1125 450 8300 9167 16287

Soft
± 3.00 M 3500 2350 2375 1125 450 9301 77.32 Cum 2350 10168 17703 27.02 Cum
Rock

± 6.00 M 3500 2350 2375 1125 450 10301 11168 19117


T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004

x Scale 1:50
STUB ANGLE
COPING
75 130X130X10

G.L GL 225
GL

EXCAVATION LINE

350X350

J 2950
SECTION
G
3600
G

200
EXCAVATION LINE
150 450 250

400 C.C. 1:2:4


100 P.C.C. 1:4:8
C
L OF TOWER 825 825
J 1650
K
1850
2150
G
SOIL CLASSIFICATION
Where normal dry cohesive or non-cohesive soils are met.
G

PLAN Released for Construction

CHIEF ENGINEER/CIVIL

G J K Volume of TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED


+0 M 9301 16194 Excavation Concrete P.C.C. FOUNDATION DETAILS OF 220 K.V. - "B" TYPE TOWER -
+3M 2150 10302 17610 (L&T)
66.56CuM 6.29CuM 1.37CuM
+6M 11302 19024 Drg. No. 220KV-TL-B-DRY DRY
Pa g e

37
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004
Scale 1:50
x
STUB ANGLE
COPING
75 130X130X10

G.L GL 225 GL
EXCAVATION LINE

450X450

2475
J
SECTION
G
3600
450
G

450 325 275 250


EXCAVATION LINE
300

275 C.C. 1:2:4


100 P.C.C. 1:4:8
C
L OF TOWER
1275 1275
J 2550
K
2750
3050
G SOIL CLASSIFICATION
a) Where sub soil water is met at 1.5 Mtrs. or more below the ground level in
normal soil.(OR)
G
b) Where surface water could stand for long period with water penetration
not exceeding 1 Mtr. Below ground level (example : Paddy fields,
PLAN Sugarcane fields). Released for Construction

CHIEF ENGINEER/CIVIL

G J K Volume of TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED


+0 M 9167 17277 Excavation Concrete P.C.C. FOUNDATION DETAILS OF 220 K.V. - "B" TYPE TOWER -
+3M 3050 10168 18693 (L&T)
133.96CuM 17.48CuM 3.03CuM
+6M 11168 20107 Drg. No. 220KV-TL-B-WET WET
Pa g e

38
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004 75 STUB ANGLE
130X130X10
Scale 1:50
GL 225 GL

x
COPING

G.L 450X450

EXCAVATION LINE
2270

450
3750
J
325 500 250
SECTION 450
G
300
G
480 C.C. 1:2:4
EXCAVATION LINE
100 P.C.C. 1:4:8
150 SAND FILLING
1500 1500

3000
C
L OF TOWER
3200
J
K
3500
SOIL CLASSIFICATION
G a) Where sub soil water is encountered between 0.75 Mtrs. and 1.5 Mtrs. depth
below ground level.(OR)
b) Where top layer of black cotton soil extends up to 50% of the depth with
G
normal soil thereafter.
NOTE : Where soil is clayey type, not necessarily
PLAN black in colour, which shrinks when dry, swells when wet. Released for Construction

CHIEF ENGINEER/CIVIL
G J K Volume of TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
+0 M 9092 17808 Excavation Concrete P.C.C. Sand filling FOUNDATION DETAILS OF 220 K.V. - "B" TYPE TOWER -
+3M 3500 10093 19223 (L&T)
183.75CuM 27.44CuM 4.10CuM 7.35CuM
+6M 11093 20638 Drg. No. 220KV-TL-B-P.S. PS /PBC
Pa g e

39
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004 75 STUB ANGLE
130X130X10
Scale 1:50
GL 225 GL

x
COPING

G.L 450X450

EXCAVATION LINE 2200

525
3750
J
450 500 500 250
SECTION
G
300
G
550 C.C. 1:2:4
100 P.C.C. 1:4:8
EXCAVATION LINE
150 SAND FILLING

1750 1750

C
L OF TOWER
3500
J 3700
K
4000
SOIL CLASSIFICATION
G
a) Where subsoil water table is within 0.75 Mtrs. depth from ground level.(OR)
b) Where top layer of black cotton soil exceeds 50% and extends up to full depth or is
G followed by normal soil.(OR)
c) Where top layer is normal soil up to 50% of the
PLAN depth but the lower layer is a black cotton soil. Released for Construction

CHIEF ENGINEER/CIVIL

G J K Volume of TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED


+0 M 8992 18373 Excavation Concrete P.C.C. Sand filling FOUNDATION DETAILS OF 220 K.V. - "B" TYPE TOWER -
+3M 4000 9993 19789 (L&T)
240.00CuM 40.53CuM 5.48CuM 9.60CuM
+6M 10993 21203 Drg. No. 220KV-TL-B-F.S. FS / BC
Page

40
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004
75 STUB ANGLE Scale 1:25
x
130X130X10
COPING
225 450X450
G.L GL GL
EXCAVATION LINE

As per field conditions


0 to 2200

J
SECTION C.C. 1:2:4
G
1300
G

EXCAVATION LINE

C
L OF TOWER
1300
SOIL CLASSIFICATION
J
K a) Where hard rock is encountered at 1.5 Mtrs. or less below ground level.(OR)
b) Where hard rock is encountered from 1.5 Mtrs. to 2.5 Mtrs. below ground
level though top layer is of normal soil.(OR)
G c) Where chiseling, drilling and blasting is required for excavation.

PLAN Released for Construction

CHIEF ENGINEER/CIVIL

G J K Volume of TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED


+0 M 8375 13683 Excavation Concrete FOUNDATION DETAILS OF 220 K.V. - "B" TYPE TOWER -
+3M 1300 9376 15098 8.79 to 9.03 to (L&T)
+6M 10376 16512 23.66 CuM 10.82 CuM Drg. No. 220KV-TL-B-H.R. HARD ROCK
Pag e

41
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004

x
Scale 1:50
COPING
75 STUB ANGLE
130X130X10

G.L GL 225 GL
EXCAVATION LINE

450X450

2375
J
SECTION 3500
G

EXCAVATION LINE
1125
C.C. 1:2:4

C
L OF TOWER

J 2350
K SOIL CLASSIFICATION
a) Where decomposed or fissured rock, hard gravel, kankar, lime stone, laterite or
G any other soil of similar nature is met.(OR)
b) Where top layer of normal dry soil extends up to 85% of the depth followed by
fissured rock without presence of water.
G

PLAN Released for Construction

CHIEF ENGINEER/CIVIL
G J K Volume of TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
+0 M 9167 16287 Excavation Concrete FOUNDATION DETAILS OF 220 K.V. - "B" TYPE TOWER -
+3M 2350 10168 17703 (L&T)
77.32CuM 27.02CuM
+6M 11168 19117 Drg. No. 220KV-TL-B-S.R. SOFT ROCK/ F&F ROCK
Page

42
FOUNDATION DETAILS FOR 220 KV C-TYPE TOWER
Basic Vol. Of
W1 D1 Vol. Of
Soil Tower A B C D F X G J K PCC M-15
W2 D2 Excavation PCC 1:4:8 Sand filling
Type (mm) (mm) (mm) (mm) (mm) (mm) 3 (mm) (mm) (mm) M3 with
W3 D3 M
Extension Steps
475 450
± 0.00 M 3500 2000 2800 700 350 8574 350 250 9533 17017
0 0

± 3.00 M 3500 2000 2800 700 350 9574 10533 18431


Dry 90.00 Cum 1.94 Cum 2500 8.56 Cum
± 6.00 M 3500 2000 2800 700 350 10574 11533 19846

± 9.00 M 3500 2000 2800 700 350 11524 12533 21260

275 250
± 0.00 M 3500 3000 2400 1100 450 8574 500 450 9383 18219
500 400

± 3.00 M 3500 3000 2400 1100 450 9574 10383 19634


176.40
Wet 4.10 Cum 3500 24.79 Cum
Cum
± 6.00 M 3500 3000 2400 1100 450 10574 11383 21048

± 9.00 M 3500 3000 2400 1100 450 11574 12345 22408

525 250
± 0.00 M 3500 3500 2350 1150 450 8574 500 450 9282 18784
500 450

± 3.00 M 3500 3500 2350 1150 450 9574 10282 20198


240.00
P.S. 5.48 Cum 9.60 Cum 4000 37.70 Cum
Cum
± 6.00 M 3500 3500 2350 1150 450 10574 11282 21612

± 9.00 M 3500 3500 2350 1150 450 11574 12275 23016

± 12.00 M 3500 3500 2350 1150 450 12574 13275 24431


1075 200
± 0.00 M 3525 4050 2925 500 450 9574 725 300 9625 20046

± 3.00 M 3525 4050 2925 500 450 10574 10625 21461

F.S. 304.33 Cum 7.23 Cum 12.42 Cum 4550 27.70 Cum

± 6.00 M 3525 4050 2925 500 450 11574 11625 22875

± 9.00 M 3525 4050 2925 500 450 11574 12625 24289


RCC
425 1500
± 0.00 M 1500 1300 0 1500 450 10574 0 0 8649 14070
0 0

± 3.00 M 1500 1300 0 1500 450 11574 9649 15484


Hard
10.14 Cum 1300 10.38 Cum
Rock
± 6.00 M 1500 1300 0 1500 450 12574 10649 16898

± 9.00 M 1500 1300 0 1500 450 11574 12533 17724

1075 1300
± 0.00 M 3500 2600 2200 1300 450 11574 0 0 9383 16947
0 0

± 3.00 M 3500 2600 2200 1300 450 11574 10383 18361


Soft
94.64 Cum 2600 37.18 Cum
Rock
± 6.00 M 3500 2600 2200 1300 450 11574! 11383 19775

± 9.00 M 3500 2600 2200 1300 450 11574 12345 21135


T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004
Scale 1:50
x
STUB ANGLE
COPING 75 150X150X12

G.L GL 225
GL

EXCAVATION LINE

350X350

2800
J
SECTION
G 3600
G
475

EXCAVATION LINE
450 350 250

250 C.C. 1:2:4


100 P.C.C. 1:4:8
C
L OF TOWER
1000 1000
J
K 2000
2200
2500
G
SOIL CLASSIFICATION
G Where normal dry cohesive or non-cohesive soils are met.

PLAN Released for Construction

CHIEF ENGINEER/CIVIL
G J K Volume of
+0 M 9533 17017 Excavation Concrete P.C.C. TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
+3M
2500
10533 18431 FOUNDATION DETAILS OF 220 K.V. - "C" TYPE TOWER -
+6M 11533 19846 90.00CuM 8.56CuM 1.94CuM (L&T)
+9M 12533 21260 Drg. No. Page
220KV-TL-C-DRY DRY 45
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004
Scale 1:50
x
STUB ANGLE
COPING 75 150X150X12

G.L GL 225 GL
EXCAVATION LINE

450X450

2400

J
SECTION
G 275
3600
G 250 500 500 250

EXCAVATION LINE
450

400 C.C. 1:2:4


100 P.C.C. 1:4:8
C
L OF TOWER
1500 1500
J 3000
K
3200
SOIL CLASSIFICATION 3500
G a) Where sub soil water is met at 1.5 Mtrs. or more below the ground level in
normal soil.(OR)
b) Where surface water could stand for long period with water penetration not
G
exceeding 1 Mtr. Below ground level (example : Paddy fields, Sugarcane
fields).
PLAN Released for Construction

CHIEF ENGINEER/CIVIL
G J K Volume of
+0 M 9383 18219 Excavation Concrete P.C.C.
TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
+3M
3500
10383 19634 FOUNDATION DETAILS OF 220 K.V. - "C" TYPE TOWER -
+6M 11383 21048 176.40CuM 24.79CuM 4.10CuM (L&T)
+9M 12345 22048
Drg. No. 220KV-TL-C-WET WET
Pa g e

46
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004 75
STUB ANGLE
150X150X12 Scale 1:50
GL 225 GL

COPING
x
G.L 450X450
EXCAVATION LINE
2350

3750
525
J 500 500 250
SECTION 250

G 450
G
450 C.C. 1:2:4
100 P.C.C. 1:4:8
EXCAVATION LINE 150 SAND FILLING
1750 1750
3500
3700
C
L OF TOWER 4000
SOIL CLASSIFICATION
J
K a) Where sub soil water is encountered between 0.75 Mtrs. and 1.5 Mtrs. depth
below ground level.(OR)
b) Where top layer of black cotton soil extends up to 50% of the depth with normal
G soil thereafter.
NOTE : Where soil is clayey type, not necessarily black in colour, which shrinks when
G dry, swells when wet.

PLAN Released for Construction

CHIEF ENGINEER/CIVIL
G J K Volume of
+0 M 9282 18784 Excavation Concrete P.C.C. Sand filling
TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
+3M 10282 20198
+6M 4000 11282 21612
FOUNDATION DETAILS OF 220 K.V. - "C" TYPE TOWER -
240.00CuM 37.70CuM 5.48CuM 9.60CuM (L&T)
+9M 12275 23016
+12M 13275 24431 Drg. No. 220KV-TL-C-P.S. PS / PBC
Pa g e

47
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004 STUB ANGLE Scale 1:50
75 150X150X12
GL 225 GL

16 # @ 2 00 c / c AT
X BOT HWAYS
65 ST UB ANGL E (
COPI NG
C/C OF PEDASTAL ) 150( C- T YPE F .S. SOI L ) .
15 0X15 0X16 L PL I NT H LV L 450X450

FXF 12 mm dia - 8 Nos.


C EXCAV AT I ON L I NE
2925
A 6 mm dia - 200 c/c
R.C.C. M15 R.C.C. M15
D
58 3675
E
22
43 B 43 B
43

R.C.C. 1:2:4
12 mm dia - 170 c/c both ways
200 16 mm dia - 200 c/c both ways
Alternate bars are cranked
300 P.C.C. 1:4:8
100
150 SAND FILLING

2600
4050
J X X 4250
4550
SOIL CLASSIFICATION
a) Where subsoil water table is within 0.75 Mtrs. depth from ground level.(OR)
b) Where top layer of black cotton soil exceeds 50% and extends up to full depth or is
followed by normal soil.(OR)
F
c) Where top layer is normal soil up to 50% of the depth but the lower layer is a black
cotton soil.
J

Released for Construction


PLAN

CHIEF ENGINEER/CIVIL

G J K Volume of Steel (Kgs) TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED


+0 M 9625 20046 Excavation Concrete P.C.C. Sand filling
+3M 10625 21461
FOUNDATION DETAILS OF 220 K.V. - "C" TYPE TOWER -
4550 1974.86 (L&T)
+6M 11625 22875 304.33CuM 27.70CuM 7.23CuM 12.42CuM
+9M 12625 24289 Drg. No. 220KV-TL-C-F.S. FS / BC
Pa g e

48
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004
STUB ANGLE Scale 1:25
75
x 150X150X12
COPING
225 450X450
G.L GL GL
EXCAVATION LINE

As per field conditions


0 to 2000

J
SECTION C.C. 1:2:4
G

G
1500

EXCAVATION LINE

C
L OF TOWER

J
K
1300
SOIL CLASSIFICATION
a) Where hard rock is encountered at 1.5 Mtrs. or less below ground level.(OR)
G
b) Where hard rock is encountered from 1.5 Mtrs. to 2.5 Mtrs. below ground level
though top layer is of normal soil.(OR)
G
c) Where chiseling, drilling and blasting is required for excavation.

PLAN Released for Construction

CHIEF ENGINEER/CIVIL
G J K Volume of
TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
+0 M 8649 14070 Excavation Concrete
+3M
1300
9649 15484
10.14 to 10.40 to
FOUNDATION DETAILS OF 220 K.V. - "C" TYPE TOWER -
+6M 10649 16898 (L&T)
23.66CuM 12.04CuM
+*9M 11649 17724 Pa g e

Drg. No. 220KV-TL-C-H.R. HARD ROCK 49


T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004
Scale 1:50
x
STUB ANGLE
COPING 75 150X150X12

G.L GL 225 GL
EXCAVATION LINE

450X450

2200

J
SECTION 3500
G

EXCAVATION LINE 1300


C.C. 1:2:4

C
L OF TOWER

J 2600
K
SOIL CLASSIFICATION
a) Where decomposed or fissured rock, hard gravel, kankar, lime stone, laterite or
G
any other soil of similar nature is met.(OR)
b) Where top layer of normal dry soil extends up to 85% of the depth followed by
G
fissured rock without presence of water.

PLAN Released for Construction

CHIEF ENGINEER/CIVIL
G J K Volume of TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
+0 M 9383 16947 Excavation Concrete
+3M
2600
10383 18361 FOUNDATION DETAILS OF 220 K.V. - "C" TYPE TOWER -
+6M 11383 19775 94.64CuM 37.18CuM (L&T)
+9M 12345 21135 Drg. No. Pa g e
220KV-TL-C-S.R. SOFT ROCK/ F&F ROCK 50
220 KV TOWERS L&T DESIGN OF FOUNDATION FOR TYPE-D TOWER
Basic Vol. Of
W1 D1 Vol. Of
Soil Tower A B C D F X PCC Sand G J K PCC M-15
W2 D2 Excavation
Type (mm) (mm) (mm) (mm) (mm) (mm) 3 1:4:8 filling (mm) (mm) (mm) M3 with
W3 D3 M
Extension Steps
400 450
± 0.00 M 3500 2450 2450 1050 450 10734 300 300 11833 20906
300 300

± 3.00 M 3500 2450 2450 1050 450 11990 13093 22688


Dry 125.32 Cum 2.81 Cum 2950 16.35 Cum
± 6.00 M 3500 2450 2450 1050 450 13250 14353 24470

± 9.00 M 3500 2450 2450 1050 450 14500 15613 26252

625 600
± 0.00 M 3500 3700 2000 1500 450 10734 500 450 11581 22318
500 450

± 3.00 M 3500 3700 2000 1500 450 11990 254.02 Cum 6.08 Cum 4200 12841 24100 46.56 Cum
Wet
± 6.00 M 3500 3700 2000 1500 450 13250 14101 25882

675 600
± 9.00 M 3500 3800 1950 1550 450 11574 500 500 266.26 Cum 6.40 Cum 4300 15340 27775 51.27 Cum
500 450
1150 200
± 0.00 M 3425 4300 2775 550 450 10734 775 350 12032 23804
0 0

± 3.00 M 3425 4300 2775 550 450 11990 13292 25586


P.S. 329.47 Cum 8.10 Cum 13.82 Cum 4800 34.43 Cum

± 6.00 M 3425 4300 2775 550 450 13250 14552 27368

± 9.00 M 3425 4300 2775 550 450 11574 15812 29150


RCC
1375 200
± 0.00 M 3425 4800 2775 550 450 10734 800 350 12032 24511
0 0

± 3.00 M 3425 4800 2775 550 450 11990 13292 26293


F.S. 401.69 Cum 10.00 Cum 16.85 Cum 5300 42.94 Cum
± 6.00 M 3425 4800 2775 550 450 13250 14552 28075

± 9.00 M 3425 4800 2775 550 450 11574 15812 29857


RCC
425 1600
± 0.00 M 1600 1300 0 1600 450 10734 0 0 10825 17147
0 0

± 3.00 M 1600 1300 0 1600 450 11990 12085 18929


Hard
10.82 Cum 1300 11.06 Cum
rock
± 6.00 M 1600 1300 0 1600 450 13250 13345 20711

± 9.00 M 1600 1300 0 1600 450 11574 14605 22493

1225 1700
± 0.00 M 3500 2900 1800 1700 450 10734 0 0 11581 20479
0 0

± 3.00 M 3500 2900 1800 1700 450 11990 12841 22261


Soft
117.74 Cum 2900 58.89 Cum
rock
± 6.00 M 3500 2900 1800 1700 450 13250 14101 24043

± 9.00 M 3500 2900 1800 1700 450 11574 15340 25795


T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004

x
Scale 1:50
COPING
75 STUB ANGLE
150X150X16

G.L GL 225 GL
EXCAVATION LINE

450X450

2450
J
SECTION
G
3600
400
G

450 300
EXCAVATION LINE
300 250
300
C.C. 1:2:4
300
100 P.C.C. 1:4:8
C
L OF TOWER

J 1225 1225
K
2450
2650
G
2950

G SOIL CLASSIFICATION
Where normal dry cohesive or non-cohesive soils are met.
PLAN Released for Construction

CHIEF ENGINEER/CIVIL
G J K Volume of
TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
+0 M 11833 20906 Excavation Concrete P.C.C.
+3M
2950
13093 22688 FOUNDATION DETAILS OF 220 K.V. - "D" TYPE TOWER -
+6M 14353 24470 125.32CuM 16.35CuM 2.81CuM (L&T)
+9M 15613 26252 Drg. No. Pa ge
220KV-TL-D-DRY DRY 53
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004 Scale 1:50
75 STUB ANGLE
150X150X16
x
GL 225 GL
COPING

G.L
EXCAVATION LINE 450X450

2000

625
J
SECTION 3600
500
G 600

G 250
500
450

EXCAVATION LINE 450 C.C. 1:2:4


100 P.C.C. 1:4:8
1850 1850
3700
C
L OF TOWER
3900
J
K 4200
SOIL CLASSIFICATION
G a) Where sub soil water is met at 1.5 Mtrs. or more below the ground level in
normal soil.(OR)
b) Where surface water could stand for long period with water penetration not
G exceeding 1 Mtr. Below ground level (example : Paddy fields, Sugarcane fields).

PLAN Released for Construction

CHIEF ENGINEER/CIVIL

G J K Volume of TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED


+0 M 11581 22318 Excavation Concrete P.C.C.
+3M 4200 12841 24100
FOUNDATION DETAILS OF 220 K.V. - "D" TYPE TOWER -
254.02CuM 46.56CuM 6.08CuM (L&T)
+6M 14101 25882
Drg. No. 220KV-TL-D-WET WET(+0, +3, +6M) Pa g e

54
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004
Scale 1:50
x
COPING
75 STUB ANGLE
150X150X16

G.L GL 225 GL
EXCAVATION LINE

450X450
1950

J
675
SECTION
G
3600 500
600
G

500 500 250


EXCAVATION LINE

450 C.C. 1:2:4


100 P.C.C. 1:4:8
C
L OF TOWER 1900 1900
J 3800
K 4000
4300
G SOIL CLASSIFICATION
a) Where sub soil water is met at 1.5 Mtrs. or more below the ground level in
normal soil.(OR)
G
b) Where surface water could stand for long period with water penetration not
exceeding 1 Mtr. Below ground level
PLAN (example : Paddy fields, Sugarcane fields). Released for Construction

CHIEF ENGINEER/CIVIL
G J K Volume of TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
+0 M Excavation Concrete P.C.C.
+3M FOUNDATION DETAILS OF 220 K.V. - "D" TYPE TOWER -
4250 15340 27704
+6M 266.26CuM 51.27CuM 6.40CuM (L&T)
+9M Drg. No. 220KV-TL-D-WET+9 WET (+9M) Pa g e

55
75 STUB ANGLE
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004 150X150X16 Scale 1:50
GL 225 GL
X
16 # @ 2 00 c / c AT
( C/C OF PEDASTAL ) BOTHWAYS
65 STUB ANGL E 150( C- TYPE F.S. SOI L ) .
15 0X15 0X16 L COPI NG PL I NTH LV L

FXF 450X450
C EXCAV ATI ON L I NE
A
R.C.C. M15 R.C.C. M15
D 12 mm dia - 8 Nos.
58 2875 6 mm dia - 200 c/c
E
43 B 43 B
22 43
3675

R.C.C. 1:2:4
12 mm dia - 170 c/c both ways

200 16 mm dia - 175 c/c both ways


Alternate bars are cranked
350 P.C.C. 1:4:8
100
150 Sand filling
X 2750
J X
4300
4500
4800
SOIL CLASSIFICATION
a) Where sub soil water is encountered between 0.75 Mtrs. and 1.5 Mtrs. depth below
F ground level.(OR)
J b) Where top layer of black cotton soil extends up to 50% of the depth with normal soil
thereafter.
NOTE : Where soil is clayey type, not necessarily black in colour, which shrinks when
PLAN dry, swells when wet.
Released for Construction

CHIEF ENGINEER/CIVIL
G J K Volume of Steel (Kgs) TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
+0 M 12032 23804 Excavation Concrete P.C.C. Sand filling
+3M 13292 25586 FOUNDATION DETAILS OF 220 K.V. - "D" TYPE TOWER -
4800 2248.13 (L&T)
+6M 14552 27368 338.69CuM 34.51CuM 8.10CuM 13.82CuM
+9M 15812 29150 Drg. No. 220KV-TL-D-P.S. PS / PBC
Page

56
75 STUB ANGLE Scale 1:50
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004 150X150X16
GL 225 GL
X
16 # @ 2 00 c / c AT
( C/C OF PEDASTAL ) BOT HWAYS
65 ST UB ANGL E 150( C- T YPE F .S. SOI L ) .
15 0X15 0X16 L COPI NG PL I NT H LV L

FXF 450X450
C EXCAV AT I ON L I NE
A
R.C.C. M15 R.C.C. M15
D 12 mm dia - 8 Nos.
58 2875
E B B 6 mm dia - 200 c/c
43 43
22 43
3675

R.C.C. 1:2:4
12 mm dia - 170 c/c both ways
200 16 mm dia - 175 c/c both ways
Alternate bars are cranked
350 P.C.C. 1:4:8
100
150 Sand filling
X 3200
J X
4800
5000
5300

SOIL CLASSIFICATION
a) Where subsoil water table is within 0.75 Mtrs. depth from ground level.(OR)
F b) Where top layer of black cotton soil exceeds 50% and extends up to full depth or is
J followed by normal soil.(OR)
c) Where top layer is normal soil up to 50% of the depth but the lower layer is a black
PLAN
cotton soil.

Released for Construction

CHIEF ENGINEER/CIVIL
G J K Volume of Steel (Kgs) TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
+0 M 12032 24511 Excavation Concrete P.C.C. Sand filling
+3M 13292 26293 FOUNDATION DETAILS OF 220 K.V. - "D" TYPE TOWER -
5300 2876.45
+6M 14552 28075 412.92CuM 43.02CuM 10.00CuM 16.85CuM (L&T)
+9M 15812 29857 Drg. No. Page
220KV-TL-D-F.S. FS / BC 57
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004
STUB ANGLE
Scale 1:25
x 75
150X150X16
COPING
225 450X450
G.L GL GL
EXCAVATION LINE

As per field conditions


0 to 1900

J
SECTION
G

1600
EXCAVATION LINE
C.C. 1:2:4

C
L OF TOWER

J
K

G 1300
SOIL CLASSIFICATION
a) Where hard rock is encountered at 1.5 Mtrs. or less below ground level.(OR)
G
b) Where hard rock is encountered from 1.5 Mtrs. to 2.5 Mtrs. below ground level
though top layer is of normal soil.(OR)
PLAN c) Where chiseling, drilling and blasting is Released for Construction
required for excavation.
CHIEF ENGINEER/CIVIL
G J K Volume of
TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
+0 M 10825 17147 Excavation Concrete
+3M 12085 18929 FOUNDATION DETAILS OF 220 K.V. - "D" TYPE TOWER -
1300 10.82 to 11.06 to (L&T)
+6M 13345 20711
23.66CuM 12.60CuM
+*9M 14605 22491 Drg. No. 220KV-TL-D-H.R. HARD ROCK
Pa g e

58
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004
Scale 1:50
x
COPING
75 STUB ANGLE
150X150X16

G.L GL 225 GL
EXCAVATION LINE

450X450
1800

J
SECTION 3500
G

1700
EXCAVATION LINE

C.C. 1:2:4

C
L OF TOWER

J 2900
K
SOIL CLASSIFICATION
a) Where decomposed or fissured rock, hard gravel, kankar, lime stone, laterite
G or any other soil of similar nature is met.(OR)
b) Where top layer of normal dry soil extends up to 85% of the depth followed by
G fissured rock without presence of water.

PLAN Released for Construction

CHIEF ENGINEER/CIVIL
G J K Volume of TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
+0 M 11581 20479 Excavation Concrete
+3M 12841 22261 FOUNDATION DETAILS OF 220 K.V. - "D" TYPE TOWER -
2900 (L&T)
+6M 14101 24043 117.74CuM 58.89CuM
+9M 15340 25795 Drg. No. 220KV-TL-D-S.R. SOFT ROCK/ F&F ROCK
Pa g e

59

Potrebbero piacerti anche