MEASUREMENTS

iSTAT M2x2
Multifunction Meter & Communicating
Measurement Centre

The M2x2 is a Measurement Centre providing quick,


reliable measurement and monitoring of electrical
quantities in a single or three phase distribution
system. The M2x2 is configurable to meet the
requirements of the medium voltage utility and low
voltage industrial markets throughout the world.

High sampling rate and true RMS measurement give


accurate readings under all harmonic conditions.
Measurement accuracy better than 0.5% and Class 1
Energy are suitable for many applications.

The M232 is fitted with either RS232 or RS485


Figure 1: communications using MODBUS for simple connection
M232 Communicating
Measurement Centre to DCS/SCADA.

The standard 96mm DIN case allows simple retrofitting


in many installations.

> The iSTAT M2x2 has auto-ranging current and voltage (option) inputs, fully programmable input scaling and
connection selection which can be set to match any site application for single and 3-phase installations.
> The iSTAT M2x2 is always supplied with Energy pulse outputs and can be optionally fitted with Tariff inputs
Customer and alarm outputs for use in many applications.
Benefits
> The iSTAT M2x2 has fully programmable input scaling which can be set to match any site application for
single and 3-phase installations.
• Auto-range current
and voltage inputs > The iSTAT M212 can be used as a replacement for the M211.
• Comprehensive set > The iSTAT M232 can be used as a replacement for the M231, using the same MODBUS addresses.
of measurements
> The iSTAT M232 uses the standard QDSP setting software used across the range of programmable
• High speed
measurement products supplied by AREVA T&D.
communications
• Easy integration into
DCS/SCADA THE M2x2 RANGE
• Easily configured
• Tariff input option > M212 Multifunction Meter
> M232 Communicating Measurement Centre

areva t&d
AREVA T&D
Features Benefits
Multifunction configurable Measurement Centre Many site applications can be fulfilled from a single product
Configurable connections for single and 3-phase, Easy to specify the Measurement Centre for any application,
balanced and unbalanced loads including when full details are not available
Auto-range Voltage and Current Inputs, up to 500V Easy to specify the Measurement Centre for any application,
and 5A including when full details are not available
Universal AC/DC Power Supply as standard Power supply suits most site requirements
0.5% measurement accuracy, True RMS Accurate measurements of any electrical network regardless of
distortion
Class 1 Energy Measurement, combined with Tariff Able to perform Energy measurement and functions
inputs and energy pulse outputs
RS232 or RS485 communications using MODBUS Allows connection to most remote energy management, DCS
RTU and SCADA systems
Software and Hardware alarms on M232 Alarms increase the range of applications that the Measurement
Centre can be used for
Configuration using QDSP software on M232 Easy to use software allowing fast configuration of
Measurement Centre

Figure 2

QDSP setting software

The iSTAT M232 uses the same QDSP setting software


that is used across the range of programmable iSTAT
measurement products supplied by AREVA T&D.

Download free-of-charge from:


www.areva-td.com/measurements

iSTAT – THE standard measurement platform


Multifunction Transducer Measurement
Simple to fit, Simple to set, Simple to Connect
Advanced Functionality
2>3
Economical
M2x2 Features

APPLICATIONS

> Energy Monitoring > Demand Calculation


The M2x2 is intended for use on systems where The M2x2 is able to calculate Demand values using
energy monitoring and instrumentation are required, fixed, thermal and sliding window methods.
providing Volts, Amps, Watts, Vars, VA, power Both Present Demand and Demand Since Last
factor, frequency and THD, as well as metering for Reset areletter
available.
ontact combination code
active and reactive energy.
Demand values for current, active, reactive and
> Pulsed Outputs
apparent power are also provided.
The M2x2 is supplied with two pulsed outputs which
can be set to correspond to any two of the four
energy measurements. These are set via the front
FUNCTIONS menu and can be disabled if not required.
On the M232 the pulse outputs can be programmed
> Instantaneous Measurement as alarm outputs.
• Active Power Pa, Pb, Pc, Pt
• Reactive Power Qa, Qb, Qc, Qt > Remote Communications
• Apparent Power Sa, Sb, Sc, St A rear communications port is provided on the
• Power Factor CosΦa, CosΦb, CosΦc, CosΦt M232, which has to be specified as either RS232 or
RS485.
• Phase Voltage Ua, Ub, Uc, Ut
The protocol used is MODBUS RTU.
• Line Voltage Uab, Ubc, Uca, U3
• Current Ia, Ib, Ic, In
> Configuration
• Frequency
Two password controlled access levels are
• Current THD,
available.
%THD Ia, %THD Ib, %THD Ic
The following settings are password protected if
• Phase Voltage THD
required:
%THD Ua, %THD Ub, %THD Uc
• CT ratio
• Line Voltage THD
%THD Uab, %THD Ubc, %THD Uca • VT Primary
• VT secondary

> Energy Measurement • System connection

• Active Energy Wh total, import and export • Communications parameters

• Reactive Energy VArh total, leading and lagging. • Demand calculation mode
• Demand period

> Mand Values • Energy meter operations (communications only)

• Phase currents • Energy meter resetting

• Total active power (Positive & Negative) • Demand resetting

• Total reactive power (Lead & Lag) • Pulse output configuration

• Total apparent power • Alarm configuration


HARDWARE DESCRIPTION

> Case
The M2x2 is housed in a DIN case with maximum dimensions of
96mm by 96mm by 97mm. See Fig 4 for the case outline

> Display
The front panel contains an illuminated dot matrix liquid crystal
display (LCD). Five pushbuttons provide access to the M2x2 menu.
See Fig 3 for typical screen views.

> Rear connections


The auxiliary supply, pulsed output and measured voltage use plug
in M2.5 terminal blocks.
The current measuring circuit connections on the rear are by means
of individual embedded CTs.
The current cables are passed through these CTs.

Figure 3 Typical Displays

Figure 4 Case Outline


TECHNICAL DATA

> Voltage Input > AC/DC Universal Power Supply

• Nominal phase to neutral input voltage (Un): • Input voltage AC: 48 – 276V
63.5, or auto-range 50 – 500V • Frequency range: 40 – 65Hz
• Measuring range 0 …120% Un, Max 600V • Input voltage DC: 20 – 300V
• Burden < 0.1VA per phase • Burden < 5VA
• Rated frequency and range:
50Hz - 60Hz; 16Hz to 400Hz
• Thermal withstand > Communications Port Using Modbus RTU
• 1.2 x Un continuously
• 2 x Un for 10 seconds RS232 RS485
Connection Point to point Multidrop
Cable type Screened Screened
> Current Input multicore twisted pair
Cable length 15M 1000M
• Rated current (In) 5A
• Rating 1A/ 5A (Auto-ranging)
• Measuring range 0 – 12.5A sinusoidal > Pulse Outputs
• Burden < 0.1VA per phase
• Thermal withstand • Maximum ac switching power:
• 3 x In continuously 50VA,

• 25 x In for 3 seconds • Maximum switching voltage:


40Vac / 35Vdc
• 50 x In for 1 second
• Maximum switching current:
1A
• Maximum pulse rate:
> Accuracy 4,000 per hour
• Pulse duration:
• Active energy EN 62053-21 class 1 100msec
• Reactive energy EN 62052-23 class 2 • Isolation:
• Power ± 0.5% 4KV coil to contacts
1KV between open contacts
• Phase/phase voltage ± 0.5%
• Phase/Neutral voltage ± 0.5%
• Phase current ± 0.5%
> Tariff Inputs
• Neutral current ± 1.0%
• Input ranges: 110 or 230 VAC ± 20%
• Power Factor ± 0.5 degree
Specified at time of order
• Phase angle ± 0.5 degree
• MD Values ± 1.0%
• Frequency ± 10mHz
ELECTRICAL ENVIRONMENT CASE

• PC/ABS incombustible, self-extinquishing to UL 94V0


European Legislation • Dimensions 96 x 96 x 97mm
• Enclosure protection IP52 EN60529:1997
> Product safety 2006/95/EEC • Connection terminals IP00 EN60529:1997
Compliance with the European Commission Low • Weight 0.5kg
Voltage Directive.

EN 61010-1: 2002 CONNECTIONS


Safety requirements for electrical equipment for
measurement, control and laboratory use, Part 1: Permissible cross section of connection leads:
General requirements.
Connection Max. conductor cross-
sections
> EMC Compliance 2004/108/EEC
Voltage inputs (4) ≤ 2.5 mm2; one conductor
EN62052-11:2003 Part 11 Metering equipment
Current inputs (3) ≤ Ø 6 mm; one conductor
general requirements, tests and test conditions
with insulation
Electricity Metering Equipment (AC)
Power supply (2) ≤ 2.5 mm2; one conductor
Modules (2 x 3) ≤ 2.5 mm2; one conductor

Design

> Connection Tables


> Protection
Compliance is demonstrated by reference to generic Inputs / Quantities Terminals
safety standards. IL1 TT1
Protection class II AC current IL2 TT2
600V installation category II IL3 TT3
300V installation category III Measuring
UL1 2
inputs
Pollution degree 2 UL2 5
AC voltage
UL3 8
> Test voltage N 11
3.7kV rms to EN61010-1:2004 + / AC 13
Auxiliary power supply
– / AC 14
Out −1 15
Environmental Withstand Output C−12 16
Input / Out −2 17
> Climatic rating Output
T - 1/2 18
modules
EN 62052−11: 2004
Tariff input C - 12 19
EN 62052−21: 2005
T - 3/4 21
> Reference range of operation
-10°C…23… 55°C
Comms Terminals Description
> Nominal range of operation
21 Data transmission (Tx)
-10°C to 55°C
RS232 22 Grounding ( )
> Transit and storage
23 Data reception (Rx)
-40°C to 70°C
21 A
> Humidity
RS485 22 Do not connect!
≤75% Average annual relative humidity
23 B
ORDERING GUIDE

Model type M2?2 X A R ? U ? 2 ? ? 0 A


iSTAT M212 Multifunction Meter M212
iSTAT M232 Communicating Measurement Centre M232
Electrical Network
Menu configurable X
Accuracy
0.5% measured values (energy class 1) A
Secondary Current
Auto-Range 1 & 5A R
Secondary Voltage
63.5V (57.7 to 69.3V L-N or 100V to 120V L-L) B
Auto-range 50….500V R
Auxiliary Voltage
Universal Power Supply (40-276Vac and 24-300Vdc) U
Communications
No communication (M212 only) 0
Serial RS232 (M232 only) 2
Serial RS485 (M232 only) 4
Rear Module configuration
Module 1
2 x Pulse (Alarm) contacts (Always fitted) 2
Module 2
Not fitted N
2 x Tariff inputs 230 VAC T
2 x Tariff inputs 110 VAC U
Finish
Standard 0
IP54 1
Factory defaults 0 A
MiCOM and iSTAT are registered trademarks of AREVA. All trade names or trademarks mentioned herein whether registered or not, are the property of their owners. - 389191982 RCS PARIS - Printed in France - SONOVISION-ITEP
AUTOMATION-L3-iSTATM2x2-BR-10.09-2179-EN - © - AREVA - 2009. AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA.

Our policy is one of continuous development. Accordingly


AREVA T&D Worldwide Contact Centre: the design of our products may change at any time. Whilst
http://www.areva-td.com/contactcentre/ every effort is made to produce up to date literature, this
brochure should only be regarded as a guide and is intended for
Tel.: +44 (0) 1785 250 070 information purposes only. Its contents do not constitute an
offer for sale or advise on the application of any product referred
to in it. We cannot be held responsible for any reliance on any
www.areva-td.com decisions taken on its contents without specific advice.
www.areva-td.com/measurements