Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Planning of
Electric Power
Distribution
Technical Principles
siemens.com/tip-cs
Navigation tips
Con-
Navigation bar
tents
On every page you will find a
navigation bar.
Intro
duction Click on the chapter title/number in
the navigation bar to move to the
1 start page of the relevant chapter.
Click on “Contents” at the top to view
2 the contents page.
Contents page
2.3 Estimation of a Concrete Value for the Power
Demand from the Given Margins 21
2.4 Operating Voltages in Supply and Distribution
Grids 25
2.5 Type of Feed-in 27
2.6 Central or Distributed Installation
of Low-voltage Supply 29
Scroll horizontally to
switch between References to figures and tables
individual pages
… standard EN 15232 can be used for the building
management (see Tab. 2/9). However, note that energy
efficiency class D from EN 15232 must not play any role …
The planning of electric power distribution in buildings and infrastructure facilities is subject to
constant transformation. The search for an assignment-compliant, dependable solution should fulfill
those usual requirements placed on cost optimization, efficiency, and time needs. At the same time,
technical development innovations and findings from the practical world are constantly seeping into
the planning process. Our books on electric power distribution are intended to support you in your
work as a planner and to provide you with a continuously updated and dependable instrument.
Various volumes under the “application manual” term have been compiled over time. To introduce a
form of structuring into the process, we will in future distinguish between planning and application
manuals.
The specific requirements of infrastructure facilities of individual industries and building types on
electric power distribution is worked on in the application manuals. Perhaps you have already made
acquaintances with the editions on high-rise buildings, hospitals, energy transparency, and data
centers. This is the series we intend to continue with at intervals. We would be glad to take up any
suggestions you may have here.
The planning manuals concern themselves more with those subjects generally used in planning
electric power distribution. They are oriented to that fundamental know-how which is at the basis of
all planning work. To this end, we are launching a new series, whereby volume 2 will consist of several
individual modules.
This newly designed first volume, “Planning of Electric Power Distribution – Technical Principles”, looks,
in particular, at the general requirements and characteristics which are of interest in planning electric
power distribution. The subsequent volumes of the series “Planning of Electric Power Distribution –
Products and Systems” are an amendment hereto. They will introduce to you the technical details and
descriptions of specific products and systems so as to fulfill the requirements specified in this volume.
Detlef Lucius
Vice President
Consultant Support for Totally Integrated Power
Con
tents
Intro Contents
duction
2
Integrated Planning – Cost Reduction 6 6 Dimensioning of Power Distribution Systems 102
13
and Distribution Systems 218
4.5 Network Protection Equipment 53
10.1 Parameters and Forms
4.6 Connection of the Neutral Point
of Low-Voltage Switchboards 218
in the Medium-Voltage Cable System 64
10.2 Planning Notes 224
14 5 Supply Quality 72 10.3 Motor Control Centers 229
5.1 Voltage Quality 73 10.4 Distribution Boards 229
15
5.2 Electromagnetic Compatibility 79 10.5 Busbar Trunking Systems 232
5.3 Availability and Redundancy 82
5.4 Reactive Power and Compensation 88
17
Intro
duction
2
11 Low-Voltage Switching and Protection Devices 238 16 Lighting Inside Buildings 306
11.1 Circuits and Device Assignment
11.2 Requirements on the Switching
240 16.1 Basic Data Establishment
16.2 Building Analysis
306
309
3
and Protection Devices in the Three Circuit Types 241 16.3 Normative Specifications 309
11.3 Residual Current and Arc Fault Detection Devices 244 16.4 Normative Specifications as to Energy Efficiency
16.5 Lighting Quality Features
310
312
4
12 Starting, Switching, and Protecting Motors 252
16.6 Design Principles 316
12.1 Protecting Electric Motors 252
12.2 Switching Electric Motors 253
16.7 Lighting Tools for Good Lighting 320 5
16.8 Light Calculation 327
12.3 Comparison of Circuits for Motor Starting 260
16.9 Emergency Lighting 338
12.4 Safety of Machines 262
17 Appendix 348
6
13 Feed-in via Converters and Generators 266
17.1 Characteristics of Network Feed-ins 348
13.1 UPS Systems 267
13.2 Embedded Generation Systems 270
17.2 List of Standards
17.3 List of Abbreviations
349
359
7
14 Energy Management 282 17.4 Bibliography 363
14.1 Measured Variables for Energy Transparency 283 17.5 Conversion Factors and Tables 364
8
14.2 Graphic Representations in Energy Management 285
Imprint 368
14.3 Evaluation Profiles 288
14.4 Characteristic Values 289 9
14.5 Electricity Market Observations 290
14.6 Operational Management 295
14.7 Normative Basis 10
for an Energy Management System 296
14
15
16
17
Intro
duction
10
11
12
13
14
15
16
17
1 Increasingly greater demands are placed on modern build- 1. “Properties” represent buildings, space-enclosing devel-
ings. As early as in the planning phase, demands for a high opments, outdoor facilities, engineering structures,
level of safety, flexibility throughout the entire lifecycle, a transportation installations, load-bearing structures,
2 low level of environmental pollution, the integration of and technical system equipment
renewable energies, and low costs must be taken into 2. “Buildings” represent self-contained, roofed, usable
account in order to exploit the full potential of economic structures which people can enter and which are
3 efficiencies and fulfilling technical demands. A special
challenge is the coordination of the individual installations.
suitable or appointed for providing shelter for humans,
animals, or objects
Basically, the main installations are heating, ventilation, air 3. “New structures and new installations” represent prop-
9
Feed-in
10 Power distribution
11 Short-circuit / overload protection
Power management
12
ology
Building techn
13 Process and
manufacturin
g industry
14
stems
ts, and sy
g, produc
configurin
Planning,
15
16
17 Totally Integrated Power – the future-proof power distribution as a basis for Totally Integrated Automation and Total
Building Solutions
Intro
duction
7. “Modernizations” represent structural steps taken to attain maximum process efficiency and reliability. At the
1
sustainably increase the practical value of a property – same time, costs weighing on building investors, operators,
given they do not fall under items 5, 6, or 9 and users can be reduced by exploiting synergies.
8. “Space-enclosing developments” refer to the inner 2
design or setup of interiors without significant incur- Integrated planning utilizes the synergies of well-matched,
sions made into the substance or structure; they can consistent, and intelligent systems and products from a
come to light in conjunction with work undertaken in
items 3 to 7
single supplier, and implements them in cost-effective solu-
tions. Interfaces and elaborate harmonization of different
3
9. “Renovation” refers to steps for restoring the originally systems and products become obsolete. The expense for
intended condition (designated condition) of a prop-
erty given that they are not covered by item 4 or by
spare parts management and procurement is reduced.
Consistent communication systems can be used to connect 4
steps envisaged under item 7 power supply / distribution systems and products to other
10. “Maintenance work” represents steps taken to retain the installations such as automated process and production
designated condition of a property systems or automated building management systems. The 5
11. “Outdoor facilities” represent planned outdoor areas or wiring expense can be substantially reduced by a well-
spaces and appropriately designed facilities in associa- matched concept and thus the wider utilization of the cable
tion with or in structures. infrastructure for data transmission attained from such a
concept. These are merely some examples of how the
6
Regarding the planning concept for electric power supply, cost-benefit ratio can be crucially improved by integrated
it is not only imperative to observe standards and regula-
tions, it is also important to discuss and clarify economic
planning as compared to conventional planning.
7
and technical interrelations. To this end, electrical equip- The focus of Totally Integrated Power (TIP) lies on all power
ment such as distribution boards and transformers is distribution components as an integrated entity. TIP offers
selected and rated in such a way that an optimum result as everything that can be expected from a future-oriented 8
a whole is achieved rather than focusing on individual power distribution system: openness, consistency, efficient
components. All components must be sufficiently rated to planning tools, manifold options for communication, and,
withstand rated operating conditions as well as fault condi-
tions. In addition, the following important aspects must be
as a result, a substantial improvement in efficiency. When 9
regarding power distribution requirements in terms of the
considered when drawing up the power supply concept: building automation, fire protection, and safety systems
• Type, use, and shape of the building (e.g., high-rise
building, low-rise building, or multi-storey building)
installations, it becomes soon obvious that the better the
individual installations are networked, the greater the
10
• Load centers must be determined, as well as possible rise in savings potential. Cost reductions up to 25 % are
routes for supply lines and locations for transformers and feasible. Investors and building operators can thus provide
main distribution boards a more cost-effective power supply system and boost its 11
• Building-related connection values according to specific efficiency.
area loads that correspond to the building’s type of use
• Statutory provisions and conditions imposed by building As a rule, greater efficiency provides the investor with 12
authorities benefits – arising from approval and financing simplifica-
• Requirements by the distribution system operator (DSO). tions – in assessing the building project. This also enables
Intro
duction
10
11
12
13
14
15
16
17
1 On the one hand, it is up to the planner to win an edge Phase 1 – Establishment of basic data
over his competitors and gain unique selling points by
offering modern, innovative concepts for the layout of • Task clarification
2 power supply systems and the selection of equipment. But • Review of the project situation
on the other hand, he is also responsible for his planning • Site analysis
work, which means that he may be held liable for dam- • Operations planning
3 ages. Therefore, it is important to clarify the project scope
and the economic conditions with the builder at an early
• Preparation of a room concept
• Preparation of a functional concept
stage. • Environmental impact assessment
16
17
Intro
duction
9
Energy management /
Energy transparency
Operation &
monitoring
Load
management
Load curves Forecast Maintenance
Substation
Reporting /
failure
Protocols
DATE:
EMPLOYEE
COST CENTER
Power
quality
Cost center
10
management
PAY PERIOD BEGINNING
PAY PERIOD ENDING
Distribution
DATE
SUN MON TUE WED THUR FRI SAT SUN TOTAL
IN
Maintenance
OUT
IN
OUT
task
OVERTIME
TOTAL HOURS
DATE
SUN MON TUE WED THUR FRI SAT SUN TOTAL
IN
OUT
U IN
11
I
Hall 1 Air conditioning system
OUT
cos o OVERTIME
P
checkup
TOTAL HOURS
W central ON DATE
Process / Building
local ON
OUT
OUT
TOTAL HOURS
PROCESS FIELD
12
Industrial
Products & systems Renewables Medium voltage with Transformer Low voltage with
13
protection technology protection and measuring technology
≤ 110 kV
14
16
TIP04_13_001_EN
17
Fig. 1/1: Totally Integrated Power – integrated solutions for electric power distribution
Intro
duction
13 Sub-targets 1 2 3 4 5 6 7 8 9
16 7
8
Low maintenance and repair expense
Ease of operation ■
■ ● ● ■
■
– ■
–
9 High environmental compatibility ■ –
17 ● Strong competition ■ Competition No or irrelevant competition
Intro
duction
1.4 Some Basic Considerations on conditions such as room ventilation, pressure relief in the
1
Power Distribution event of an arcing fault, ceiling loads, and access ways for
moving items in must also be taken into consideration
With regard to electric power supply, the most important when drawing up room and building plans. Overdimen- 2
task in the stage of establishing basic data is the estimation sioned rooms reduce the profitability of a building (room
of the power required for supply. In order to attain a high utilization). Underdimensioned rooms may prevent that a
level of efficiency, the components should work with a load
of 70 to 80 % of the maximum power output. Undersizing
plant is erected in such a way that it can be approved, or at
least force the use of expensive custom solutions for the
3
causes malfunctions, while oversizing results in excess costs. technology applied. This planning manual contains aids for
15
16
17
Intro
duction
1 regional level. The interrelation of the different standard- gaining importance for the technical planner is the
ization levels is illustrated in Tab. 1/2. A complete list of ISO 29481 standard for building virtualization [3]. Building
IEC members and links to more detailed information can be information models are intended to connect the data of the
2 obtained at different technical installations so that
• Project execution is simplified and accelerated
www.iec.ch/members_experts • Errors are already avoided in the planning phase
3 Besides the technical standards for electrical and electronic
• The cooperation of all parties involved is improved
• Consistent traceability of planning, construction, opera-
systems of IEC, for his work the planner should orientate tion, modification, and removal is enabled throughout
the management processes related to quality, environ- To do this, the standards make stipulations regarding the
ment, and energy. A series of standards that is increasingly data formats, data exchange, and data linking.
5
Overview of standards and standardization bodies
6 Regional America
PAS
Europe
CENELEC
Australia Asia Africa
7 CA: SCC
BR: COBEI
I:
F:
CEI
UTE
NZ: SNZ
…
IND: BIS
J: JISC
… GB: BS …
…
8 ANSI
BIS
American National Standards Institute
Bureau of Indian Standards
BS British Standards
12 SABS
SAC
South African Bureau of Standards
Standardization Administration of China
SCC Standards Council of Canada
14
15
16
17
11
Compilation of boundary conditions
Influencing factors
13
Calculation: • Lists of power consumers
14
– Energy balance • Forecasts of expansions
– Load flow (normal / fault) • Temperatures
– Short-circuit currents • Equipment data
(prospective / influenced) • etc.
15 Dimensioning:
– Selection of equipment, transformers,
• Equipment data
– Electrical data
– Dimensions, etc.
cables, protection, and switching
• Selectivity tables
devices, etc.
16
– Selectivity limit tables
– Requirements regarding selectivity – Characteristic curves, setting data, etc.
and back-up protection • etc.
TIP04_13_002_EN
17
Fig. 2/1: Tasks of network planning and configuration
16 Totally Integrated Power – Basics for Drafting Electric Power Distribution Systems
Con
tents
Intro
duction
16
Medical locations
Good electromagnetic compatibility TN-S system to minimize stray
Intensive care, ECG
(EMC) currents
Local confinement of fault currents IT system
Industrial locations Mainly motor loads High power demand per area Busbar trunking systems
17
Tab. 2/2: Examples for various areas of use and their impact on electrical networks and equipment
Totally Integrated Power – Basics for Drafting Electric Power Distribution Systems 17
Con
tents
Intro
duction
6
Library 20 – 40 0.6 300 – 450 20 – 40
Office 30 – 50 0.6 250 – 400 17 – 40
Shopping center 30 – 60 0.6 150 – 300 12 – 35
9
Cold store 500 – 1,500 0.6 150 – 200 10 – 20
Apartment complex (without night
storage / continuous-flow water 10 – 30 0.4 180 – 350 18 – 35
heater)
11 Museum
Parking garage
60 – 80
3 – 10
0.6
0.6
300 – 450
100 – 200
20 – 40
7 – 15
Production plant 30 – 80 0.6 100 – 200 10 – 40
14
Greenhouse (artificial lighting) 250 – 500 0.6 50 – 100 5 – 20
Laboratory / Research 100 – 200 0.6
Mechanical engineering industry 100 – 200 0.4
margins.
17 *) Per bed approx. 2,000–4,000 W; **) Per seat; ***) Power demand strongly process-dependent
Tab. 2/3: Average power demand of buildings according to their type of use
18 Totally Integrated Power – Basics for Drafting Electric Power Distribution Systems
Con
tents
Intro
duction
in W / m2 g
g
2
Hallway / anteroom, lobby 5 – 15 0.3 Building technologies
Staircase 5 – 15 0.3 Escalator 0.5
Technical equipment, general 5 – 15 0.3 Lift 0.3 3
Foyer 10 – 30 1 Sanitary systems 0.5
Access ways (e.g., tunnel) 10 – 20 1 Sprinklers 0.1
Recreation room / kitchenette 20 – 50 0.3 Heating 0.8 4
Toilet areas 5 – 15 1 Air conditioning 0.8
Travel center 60 – 80 0.8 Cooling water system 0.7
Office areas 20 – 40 0.8 Refrigeration 0.7 5
Press / bookshop 80 – 120 0.8
6
Flower shop 80 – 120 0.8
Bakery / butcher 250 – 350 0.8
Fruit / vegetables 80 – 120 0.8 Functional area / Average power
building area demand 1)
7
Bistro / ice cream parlor 150 – 250 0.8
Snack bar 180 – 220 0.8 in W / m2
Electric floor heating,
Diner / restaurant 180 – 400 0.8 65 – 100
living area
1)
modules)
The values specified here are guidelines for demand estimation and cannot substitute precise power demand analysis.
11
2) he simultaneity factor is a guideline for preliminary planning and must be adapted for individual projects. When dimensioning consumers in the safety power
T
supply system (SPS), their simultaneity factor must be considered separately (empirical value: g ≥ 0.8 for SPS busbar).
12
3) Average usable sun radiation in Germany per day 2.75 kWh / m2
Tab. 2/4: Average power demand of various functional / building areas back to page 18
2.2.1 Special Consideration of the Cost • Differentiation between a self-contained building (data
13
Situation for a Data Center center) or the ICT areas in a building
• Different technologies for air conditioning and power
For a data center, there are a number of factors influenc- supply influence the space requirements and energy 14
ing, among other things, the specific power demand. efficiency
Important aspects which result in a wide bandwidth of the • Requirements as to availability determine the redundancy
estimations of power demand, simultaneity factor, and and safety systems. 15
specific costs are as follows:
16
17
Totally Integrated Power – Basics for Drafting Electric Power Distribution Systems 19
Con
tents
Intro
duction
1 The following assumptions are to be made for data center- • The “Tier” structure (with ascending requirements I to
specific cost estimations: IV) of the Uptime Institute, as described in [4], is used as
• An area-specific power demand of 125 to 1,500 W / m2 a basis in connection with availability and the redun-
2 is assumed for a self-contained data center (DaC in dancy conditions upon which availability is founded.
Tab. 2/5). The low value suggests a large space required (n+1) redundancy of Tier IV results in approximately
for information technology and infrastructure (for exam- 2.5-fold costs for infrastructure components compared
3 ple owing to high redundancies), whereas the high value
suggests a high packing density of servers in the racks,
to Tier I without redundancy. The influence of the
redundancy requirements placed on the specific space
and modern cooling and power supply systems required is already taken into account in the first two
11 DaC
1,500 740 940 1,500 1,900
12 IT room
2,000 900 1,100 1,750 2,300
* The cost share of embedded electricity generating sets (generators and UPS
13
systems) is approx. 70 %, and the cost share for high- and medium-voltage
switchgear, low-voltage switchboards, low-voltage installation systems,
lighting systems, and lightning protection and earthing systems amounts to
approx. 30 % altogether.
15
16
17
20 Totally Integrated Power – Basics for Drafting Electric Power Distribution Systems
Con
tents
Intro
duction
2.3 Estimation of a Concrete Value factors with values between 0 and 1 are introduced. The
1
for the Power Demand from individual factors are added and averaged, providing a total
factor, also between 0 and 1.
the Given Margins 2
For our simple calculation model we will limit ourselves to
The values for the average power demand in Tab. 2/3 and six features considered as equivalent:
Tab. 2/4 cover a vast bandwidth of different prerequisites.
When estimating the total power demand for the project to
• Building placement
• Room structure
3
be planned, the individual margins of building types, • Level of comfort
functional areas, and rooms must be substantiated. For this
purpose, we provide an estimation procedure with various
• Air conditioning option
• Technical characteristics 4
calibration factors below as a simple help. • BAC / TBM.
Note: A similar procedure with efficiency factors is also Of course you can also use your own factors as additional 5
used in EN 15232-1. In this context, a classification takes boundary conditions. In any case, the planner and the
place. The division into classes A, B, C, D (Tab. 2/6), for customer should coordinate procedures, so that the calcu-
example, applies to the systems used for building automa-
tion and control (BAC) and technical building management
lation is verifiable. Six calibration factors corresponding to
the six characterization features identify the power de-
6
(TBM). The individual efficiency factors in EN 15232-1 mand of the building in the model.
(Tab. 2/7) refer to the mean values for the power demand
of the BAC/TBM building systems for the electrical power
• Calibration factor kplc for the building placement
• Calibration factor kstruct for the room structure
7
demand. • Calibration factor kcomf for the level of comfort
• Calibration factor kclim for the air conditioning options
To obtain an estimated value within the power demand • Calibration factor ktech for the technical characteristics 8
intervals given in Tab. 2/3 and Tab. 2/4, six calibration • Calibration factor kBAC / TBM for the BAC / TBM.
10
TGM
Auditoriums 1.06 1 0.94 0.89
• Interconnected room automation with automatic
A demand acquisition Educational facilities 1.07 1 0.93 0.86
• Regular maintenance (schools)
• Power monitoring
• Sustainable energy optimization Hospitals 1.05 1 0.98 0.96
11
Corresponds to advanced BAC systems and some special Hotels 1.07 1 0.95 0.90
TBM functions
Restaurants 1.04 1 0.96 0.92
B • Interconnected room automation without automatic
demand acquisition
• Power monitoring
Buildings for wholesale 1.08 1 0.95 0.91 12
and retail
Corresponds to standard BAC systems 1) D Not energy-efficient
13
• Interconnected building automation of the primary C Standard (reference value, also for other types such as sports facilities,
installations warehouses, industrial premises)
C
• No electronic room automation, thermostat valves at B Higher energy efficiency
heaters A High energy efficiency
• No power monitoring
Corresponds to BAC systems that are not energy-efficient.
Buildings with such systems have to be modernized.
Tab. 2/7: Efficiency factors (electrical) for BAC and TGM
functions of non-residential buildings according to EN 15232-1 14
(standard = class C = 1)
New buildings must not be equipped with such systems
D
• No interconnected building automation functions
• No electronic room automation
• No power monitoring
15
Tab. 2/6: Classification of the building automation/control and
management systems of a building regarding energy efficiency
according to EN 15232-1 16
17
Totally Integrated Power – Basics for Drafting Electric Power Distribution Systems 21
Con
tents
Intro
duction
1 As we do not want to apply any further weighting to the Placement of the building – calibration factor kplc
factors, the mean value of the calibration factors can be
defined as the total value: The location of the building has a fundamental influence
2 (kplc + kstruct + kcomf + kclim + ktech + kBAC / TBM)
on the planning of the power supply. The following ques-
tions can also be used to obtain an estimation:
ktot = ———————————————————————
• Do special conditions with regard to adjacent buildings
6
3 If the special significance of some factors shall be taken
have to be considered?
• Which traffic routes and connections can be used?
into account, additional weighting factors must be added. • Which type of power supply is possible and to which
5 Estimated power demand Note: Without any local particularities, the placement
factor can be set to kplc = 0.5.
The established calibration factor ktot and the two limit
6 values for the specific power demand pmin and pmax
(e.g., values from Tab. 2/3 and Tab. 2/4) allow to determine Room structure – calibration factor kstruct
the mean specific power demand pspec for the entire usable
7 area of a building. Smaller rooms are easier to ventilate and light is distributed
better in the room through reflection on the walls and
pspec = pmin + (pmax – pmin) · ktot ceiling. This calibration factor can also take the intended
room height into account. Our estimations that are dis-
8 To obtain the total power demand of the building, the played in Fig. 2/3 as a curve also take into account that
mean specific power demand is multiplied by the usable small rooms and areas frequently have direct ventilation
area of the building. and not air conditioning.
9
10
Specific power
11
kstruct 1
in W/m2
0.0 ktot 1.0
0.8
pmax
0.6
12 0.4
0.2
TIP05_18_005_EN
13
0
1 2 3 4
pmin
100 – 2,000 m2 500 – 4,000 m2 2,000 – 8,000 m2 > 6,000 m2
1 Smaller, single rooms; hotel rooms, window-ventilated
14
0.0 1.0 0.0 1.0 0.0 1.0 0.0 1.0 0.0 1.0 0.0 1.0 2 Larger offices, window-ventilated
kplc kstruct kcomf kclim ktech kBAC/TBM 3 Retail shops, doctor’s practices, open-plan offices,
air conditioning, standard equipment
Calibration factors
4 Open-plan offices, department stores, …, with upscale equipment
16
17
22 Totally Integrated Power – Basics for Drafting Electric Power Distribution Systems
Con
tents
Intro
duction
Larger rooms and halls generally have a larger calibration Computer rooms, which are better planned without win-
1
factor kstruct. At this point, we would again like to empha- dows, generally require more expensive air conditioning
size that the experience and project knowledge of the – constant temperature and humidity – although there is
planner and the agreement with the customer are decisive little effect from solar radiation. It should also be noted 2
in order to determine the factors and thus estimate the that the air conditioning depends on the room structure
costs. Our Siemens TIP contact partners with their back- and the comfort requirements.
ground knowledge support electrical planners in specific
projects. Technical characteristics – calibration factor ktech
3
Level of comfort and safety equipment – calibration
factor kcomf
Even when the functionality of the technical building
equipment has been defined, the difference in the techni- 4
cal constructions is significant. High-speed lifts require
It is difficult to make general statements about comfort, as higher starting currents than slower lifts, fans with EC
this is largely dependent on how the building is used. motors (electronically controlled) save power, modern light 5
Whereas good lighting, an audio system, and a monitoring fittings reduce the power demand, and the efficiency of
system are considered as standard in a shopping center, many electrical consumers differ greatly from version to
these characteristics may be considered as comfort fea-
tures in office areas. On the other hand, blinds play no role
version. 6
in shop windows, but are important in hotels and offices.
17
Totally Integrated Power – Basics for Drafting Electric Power Distribution Systems 23
Con
tents
Intro
duction
1 A general classification for the energy efficiency of the The advantage of our procedure with scaled calibration
technical equipment according to the EN 15232-1 standard factors is revealed here. Characterization features can be
is listed in Tab. 2/8. The efficiency factors of EN 15232-1 adapted to state-of-the-art technology through the scaling,
2 are transformed in Tab. 2/9 to the desired calibration range and the classification always defined through one's own
between 0 and 1. A distinction is not made for other types current experience.
(such as sports facilities, warehouses, industrial facilities,
3 etc.) so that the factor of 0.5 is selected for all classes. This means that we shift the features of class C of
EN 15232-1 (see Tab. 2/6) to our class D and select a
description for class A which is even more oriented to
4 Building management – calibration factor kBAC / TBM efficiency. In the context of BAC / TBM, additional character-
istics such as remote monitoring, remote diagnostics, and
In the same way as for the technical characteristics, stan- remote control, as well as analysis tools and integration
dard EN 15232-1 can be used for automation and building options as part of the smart grid are requested for the new
5 management systems (see Tab. 2/9). However, note that class A. For the four new classes D, C, B, and A (Tab. 2/10)
energy efficiency class D from EN 15232-1 must not play any we then take over the values of the calibration factors
role for the planning of BAC / TBM systems in new buildings. kBAC/TBM from Tab. 2/9 accordingly.
6
Class Technical characteristics and operation
9
Simple communication and control options
Standard devices and systems that represent state-of-the-
art technology during operation
C
10
No communication options, only mechanical adjustment
possible
Simple devices and systems that only satisfy the required Class Building automation and management
12
• Integration of power generation and energy storage
systems in BAC / TBM
• Analysis and forecast tools for continuous optimization
Class D C B A
Corresponds to highly energy-efficient BAC systems and
13 Offices
Auditoriums
1.0
1.0
0.57
0.65
0.26
0.29
0
0
TBM
• Interconnected room automation with automatic
B demand acquisition
Educational facilities • Regular maintenance
1.0 0.67 0.33 0
14 (schools) • Power monitoring
• Sustainable energy optimization
Hospitals 1.0 0.44 0.22 0 Corresponds to advanced BAC systems and some special
Hotels 1.0 0.59 0.29 0 TBM functions and some special TBM functions
15
C • Interconnected room automation without automatic
Restaurants 1.0 0.67 0.33 0 demand acquisition
Buildings for wholesale • Power monitoring
1.0 0.53 0.24 0 Corresponds to standard BAC systems
and retail
16
• Interconnected building automation of the primary
Further building types installations
(e.g., sports and industrial 0.5 D
• No electronic room automation, thermostat valves at
facilities, warehouses, etc.) heaters
• No power monitoring
17 Tab. 2/9: Calibration factors ktech for the technical equipment of a
building and kBAC/TBM for building automation/control and technical Tab. 2/10: Classification of non-residential buildings adapted to
building management systems, suitable for non-residential buildings new buildings in respect of energy efficiency of BAC/TBM systems
24 Totally Integrated Power – Basics for Drafting Electric Power Distribution Systems
Con
tents
Intro
duction
2.4 Operating Voltages in Supply and Power plant sites are oriented towards the availability of
1
Distribution Grids primary energy sources, cooling systems, and other ambi-
ent conditions, and they are therefore mostly located away
Different voltages are used to fulfill the different tasks of from load centers. Electric transmission and distribution 2
electric power supply and distribution. According to inter- grids connect power plants with electricity consumers. The
national rules, there are initially two voltage groups: grids thus form a supra-regional backbone with reserves to
• Low voltage (LV):
up to and including 1,000 V AC (or 1,500 V DC)
ensure reliability of supply and for balancing load differ-
ences. High operating voltages (and therefore low cur-
3
• High voltage (HV): rents) are preferred for power transmission in order to
above 1 kV AC (or 1.5 kV DC). minimize losses. The voltage is then transformed to the
usual values of the low-voltage grid in the load centers 4
Most electrical appliances used in household, commercial close to the consumer.
and industrial applications work with low voltage. High
voltage is used not only to transmit electrical energy over The boundary conditions for selecting the supply voltage 5
very large distances, but also, finely branched, for regional and the design of the technical connection points are
distribution to the load centers. Different voltage levels are described in the Technical Connection Conditions (TCC) of
common for transport and regional distribution because
the tasks and requirements for switching devices and
the distribution system operator (DSO). In the future, the
TCC will be replaced in Germany by the TAR VDE-AR-N 4100
6
switchgear are very different. This is how the term 'medium and VDE-AR-N-4110 (Technical Application Rules “TAR Low
voltage' emerged for voltages that are used to regionally
distribute electrical energy (Fig. 2/5).
Voltage” and “TAR Medium Voltage” are available as drafts)
as well as by VDE-AR-N 4105 (“TAR Self Generation”).
7
• Medium voltage (MV): Among others, this document considers the connection
above 1 kV AC up to and including 52 kV AC; most line of energy storage units, charging and storage systems
operating voltages are within the range of 3 to 40.5 kV for electromobility, or generating plants. Depending on 8
(Fig. 2/5) the situation of the DSO with regard to supply density,
10
11
12
13
14
15
1 2 1 3
16
1 Medium voltage 2 High voltage 3 Low voltage
17
Fig. 2/5: Voltage levels between the power plant and the consumer
Totally Integrated Power – Basics for Drafting Electric Power Distribution Systems 25
Con
tents
Intro
duction
1 network short-circuit power and supply quality, an installed Apart from the public supply, there are other voltages in
capacity between 150 and 1,000 kW may make the con- industrial plants with medium-voltage grids that depend on
nection to the medium-voltage level seem reasonable. the consumers. In most cases, the operating voltages of
2 Since there is no uniform set of rules, this must be dis- the installed motors are decisive. Operating voltages
cussed with the responsible DSO during planning. between 3 kV and 15 kV are very often used in industrial
networks.
3 Dependent on the DSO, a direct connection of the cus-
tomer to a transformer substation of the DSO (grid level 6 The network configuration is determined by the respective
in Tab. 2/11) may be possible in case of a power demand of supply task, the building dimensions, the number of floors
8 In public power supply, the majority of medium-voltage The following characteristics must be determined for a
grids are operated in the 10 kV to 30 kV range. The values suitable network configuration:
vary greatly from country to country, depending on the • Number of feed-in points
9 historical technological development and the local condi- • Size and type of power sources
tions. In urban environments, the spatial supply radius of a • Central or distributed installation of the power sources
medium-voltage grid with 10 kV operating voltage is at • Type of meshing and size of the power outage reserve
10 approx. 5 to 10 km, and in rural areas with 20 kV operating
voltage at approx. 10 to 20 km. These are merely guide
• Type of connection to earth and neutral-point connection.
13 Grid level 3
Supra-regional distribution
High voltage 110 kV 3~
Medium-size power plants, e.g.,
grid bio and hydro power plants
14
Grid level 4 Main transformer substation High to medium voltage HV / MV
17
26 Totally Integrated Power – Basics for Drafting Electric Power Distribution Systems
Con
tents
Intro
duction
2.5 Type of Feed-in In general, circuits for safety purposes routed through
1
fire-threatened areas must be designed fire-resistant. Never
Electrical energy can be fed into the grid in different ways, must they be routed through explosion-prone areas. Usu-
determined by its primary function (Tab. 2/12). For normal ally, safety-purpose facilities receive an automatic power 2
power supply (NPS): supply, whose activation does not depend on operator
• Direct connection to the public low-voltage grid: in action. According to IEC 60364-1 (VDE 0100-100), auto-
Germany, for example, up to approx. 300 kW (two times
250 A house connection) at 400 / 230 V
matic supply is classified by its maximum change-over
time:
3
• Transfer from the medium-voltage grid (up to 52 kV) via • Without interruption: automatic supply which can ensure
public or in-house transformer substations (in Germany
mostly with transformers from 0.5 to 2.5 MVA).
continuous supply during change-over under defined
conditions, e.g., with regard to voltage and frequency 4
fluctuations
For the emergency standby power system (ESPS), power • Very short interruption: automatic supply which is avail-
sources are selected based on standards and regulations able within 0.15 s 5
and as a function of the permissible interruption time: • Short interruption: automatic supply which is available
• Generators for general standby operation and / or safety within 0.5 s
power supply (SPS)
• Uninterruptible power supply systems
• Mean interruption: automatic supply which is available
within 15 s
6
–– Static UPS comprising a rectifier / inverter unit with • Long interruption: automatic supply which is available
battery or flywheel energy storage for buffering
voltage failures
after more than 15 s.
7
–– Rotating UPS comprising a motor / generator set with In IEC 60364-5-56 (VDE 0100-560), the following examples
of safety installations are given:
flywheel energy storage or a battery plus
rectifier / inverter unit for bridging. • Emergency lighting / safety lighting 8
• Fire extinguishing pumps
The constellation depicted in Fig. 2/6 with the correspond- • Fire fighting lifts
ing description given in Tab. 2/12 has proven itself in
infrastructure projects.
• Alarm systems such as fire alarm systems, carbon mon
oxide (CO) alarm systems, and intruder detection systems
9
• Evacuation systems
Since the circuits for SPS loads must be laid separately, their
placement inside the building is relevant for budget con
• Smoke evacuation systems
• Important medical systems.
10
siderations. In Germany, certain statutory regulations and
specifications are additionally applicable, which demand
the functional endurance of cables and wires in case of fire. 11
17
Totally Integrated Power – Basics for Drafting Electric Power Distribution Systems 27
Con
tents
Intro
duction
7
Process definition /
Task description
8
Definition of the permissible
duration of a power failure
9
Is the process / task No
10
business-critical?
Yes
Consideration of all electricity
11 consumers contributing
to the process
12 Is manual
emergency operation possible
Yes
(maybe partially)?
13 No
Is a short Is a shorter
No bridging time sufficient, No
interruption of the power
e.g., for a shutdown
14
supply permissible?
process?
Yes
Yes
16 Consumers to SPS
Consumers to UPS, which
is supplied from NPS
Consumers to UPS, which
is supplied via ESPS
Consumers to NPS
17
Fig. 2/7: Flowchart for an estimation of NPS, SPS and UPS
28 Totally Integrated Power – Basics for Drafting Electric Power Distribution Systems
Con
tents
Intro
duction
2.6 Central or Distributed Installation formers are placed at load centers, so that they must be
1
of Low-Voltage Supply spread over a larger area. Fig. 2/8 shows the intrinsic
advantages of distributed as compared to central feed-in.
The feed-in design distinguishes between central and 2
distributed feed-in variants in dependency of spatial condi- If separate substation rooms cannot or shall not be built
tions and the associated load requirements. In case of a in an industrial environment, for example, these trans-
central installation, the transformers, which are concen-
trated in one place, feed into the different power distribu-
former load center substations (see Fig. 2/9) provide a
compact and easily installable solution for distributed
3
tion circuits. In case of a distributed installation, the trans power supply.
P1 P2 P5 P6 P1 P2 P5 P6
Transformer
6
P3 P4 P7 P8 P3 P4 P7 P8
Inspection window Inspection window Inspection window
TIP05_18_014_EN
9
Fig. 2/9: Load center transformer substation for industrial applications
10
Distributed power supply Central power supply
T1 PS8 11
PS7
T2 PS6
T1 T2 T3 T4 PS5 12
T3 PS4
PS3
T4 PS2 13
PS1 PS2 PS3 PS4 PS5 PS6 PS7 PS8
PS1
14
I”k I”k
kA kA
∆u
%
∆u
%
15
16
TIP01_11_020_EN
Totally Integrated Power – Basics for Drafting Electric Power Distribution Systems 29
Con
tents
Intro
duction
1 2.7 Network Configurations In combination with a ring line as an extension of the spur
network (Fig. 2/10), a ringed network can be built up.
Starting from the type of feed-in, electric power distribu- Dependent on the spatial structures, the investment to be
2 tion grids or networks can also be distinguished according made for an open-type ringed network can be lower or
to their type of meshing. The following basic configura- higher than for a spur network. A spur network is advanta-
tions are distinguished: geous if individual transformers shall handle low-voltage
3 • Radial networks
• Ringed networks
supply in a confined space. A ringed network can be favor-
able regarding costs of investment if supply is spread out
• Meshed networks. over a larger area with several transformer centers.
4 The spur-line-fed radial network (Fig. 2/10) is the most In terms of space requirements, power demand coverage,
simple form. Its advantages lie in easy network monitoring environmental friendliness, and cable costs, the differ-
and network protection as well as in fast fault localization ences between the two network configurations are small.
5 and simple operational management. When the expense is Although ringed networks more often come with shorter
doubled, the outcome is a double-spur network. Every load cable lengths, the cable cross-section must be higher
center can be reached via two different paths. Switching owing to the transmission of higher capacities from one
6 devices are only closed if necessary. If the requirements
placed on reliability of supply are high, each feed-in can be
ring endpoint to the other.
fed from an independent supply network. Due to the fact With regard to the costs of network losses, the spur net-
7 that the networks are independent from each other, a fault
in one network will not affect the other one.
work and the open-type ringed network only differ insig-
nificantly. There are minimal advantages if the ringed
8
Radial network (spur network) Ringed network normally open (n. o.)
9
Main switchgear Main switchgear
10
11
Substation 1 Substation 4 Substation 1 Substation 4
12
Substation 2 Substation 5 Substation 2 Substation 5
13
15 Feed-in Feed-in
n.o.
TIP05_18_006_EN
16 Fig. 2/10: Radial and ringed network for the connection of distributed load center substations
17
30 Totally Integrated Power – Basics for Drafting Electric Power Distribution Systems
Con
tents
Intro
duction
12
13
14
15
16
17
Totally Integrated Power – Basics for Drafting Electric Power Distribution Systems 31
Con
tents
Intro
duction
1 2.8 Network Systems according to ence, the TN-S system has the best cost-benefit ratio of
their Type of Connection to Earth electricity grids at the low-voltage level.
2 Suitable network systems according to the type of connec- In a TN system, in the event of a short circuit to an exposed
tion to earth are described in IEC 60364-1 (VDE 0100-100). conductive part, the main part of the single-phase short-
The type of connection to earth must be selected carefully circuit current is not fed back to the power source via a
3 for the medium- or low-voltage grid, as it has a major
impact on the expense required for protective measures
connection to earth, but via the protective conductor. The
comparatively high single-phase short-circuit current allows
(Fig. 2/11). On the low-voltage side, it also influences the for the use of simple protection devices such as fuses or
4 system’s electromagnetic compatibility (EMC). From experi- miniature circuit-breakers, which trip in the event of a fault
5 TN system: In the TN system, one operating line is directly earthed; the exposed conductive parts in the electrical installation are connected
to this earthed point via protective conductors. Dependent on the arrangement of the protective (PE) and neutral (N) conductors,
three types are distinguished:
a) TNS system: b) TNC system: c) TNCS system:
6 In the entire system, neutral (N)
and protective (PE) conductors
In the entire system, the functions
of the neutral and protective conductor
In a part of the system, the functions
of the neutral and protective conductor
are laid separately. are combined in one conductor (PEN). are combined in one conductor (PEN).
7
Power Power Power
Electrical installation Electrical installation Electrical installation
source source source
L1 L1 L1
8
L2 L2 L2
L3 L3 L3
N PEN PEN PE
PE N
9 3 3 3
1 1 1 1 1 1
TT system: In the TT system, one operating line is directly IT system: In the IT system, all active operating lines are
10 earthed; the exposed conductive parts in the
electrical installation are connected to earthing
separated from earth or one point is is connected
to earth via an impedance.
electrodes which are electrically independent of the
earthing electrode of the system.
11 Power
source
Electrical installation
Power
source
Electrical installation
L1 L1
12 L2 L2
L3 L3
N N
2
13 RB RA RB RA
3 1 4 3 1 4
Fig. 2/11: Systems according to the type of connection to earth in accordance with IEC 60364-1 (VDE 0100-100)
32 Totally Integrated Power – Basics for Drafting Electric Power Distribution Systems
Con
tents
Intro
duction
within the permissible tripping time. In building technol- over its entire course – this includes the distribution sys-
1
ogy, networks with TN systems are preferably used today. tem. The magnitude of the 1-phase short-circuit current
When using a TN-S system in the entire building, residual directly depends on the position of the CEP.
currents in the building, and thus an electromagnetic 2
interference by galvanic coupling, can be prevented in Caution: In extensive supply networks with more than one
normal operation because the operational currents flow splitter bridge, stray short-circuit currents may occur.
back exclusively via the separately laid isolated N conduc-
tor. In case of a central arrangement of the power sources, 4-pole switching devices must be used if two TN-S subsys-
3
we always recommend the TN system as a rule. In that, the tems are connected to each other. In TN-S systems, only
system earthing is implemented at one central earthing
point (CEP), for example in the low-voltage main distribu-
one earthing bridge may be active (see Fig. 5/9 for coupling
distributed feed-ins and in case of separate distributions). 4
tion system, for all sources (Fig. 2/12). Therefore, it is not permitted that two earthing bridges be
interconnected via two conductors.
Please note that neither the PEN nor the PE must be 5
switched. If a PEN conductor is used, it is to be insulated
7
Source
9
Low-voltage main distribution
L1
L2
L1
L2
10
L3 L3
PEN
11
TIP05_18_007_EN
PE
Central
earthing
point
Main
earthing
12
busbar
Sub-distribution board
L1 L1 13
L2 L2
L3 L3
N
PE
N
PE 14
Fig. 2/12: Multiple feed-in for low-voltage main distribution with central earthing point (CEP) 15
16
17
Totally Integrated Power – Basics for Drafting Electric Power Distribution Systems 33
Con
tents
Intro
duction
1 Today, networks with TT systems are only used in rural upon the first fault, for example in the cable and optical
supply areas and in few countries. In this context, waveguide production. The TT system as well as the IT sys-
the stipulated independence of the earthing systems tem require the use of residual current-operated protective
2 must be observed. In accordance with IEC 60364‑5‑54 devices (RCDs) – previously named FI (fault current inter-
(VDE 0100‑540), a minimum clearance ≥ 15 m is required. rupters) – for almost all circuits.
4 production, where no supply interruption is to take place features can be selected and weighted.
9
Fault currents and impedance conditions in
the network can be calculated • • • • •
Stability of the earthing system • • • • •
10 High degree of operational safety • • • • •
11
High degree of protection • • • • •
High degree of shock hazard protection • • • • •
12 High degree of fire safety • • • • •
13
Automatic disconnection for protection
purposes can be implemented • • • • •
EMC-friendly • • • • •
14 Equipment functions maintained in case of
• • • • •
1st earth or enclosure fault
Tab. 2/13: Exemplary quality rating dependent on the network system according to its type of connection to earth
17
34 Totally Integrated Power – Basics for Drafting Electric Power Distribution Systems
Chapter 3
Network Planning Modules
Con
tents
1 Network planning modules can be used for an easy and The room conditions and the associated load requirements
systematic power distribution design for typical building are essential for the basic concept. The flow diagram
structures. These are schematic solution concepts which Fig. 3/1 shows how a systematic analysis of the boundary
2 clarify the spatial arrangement and connection of import- conditions and the different single decisions lead to a
ant components for electric power distribution. The mod- planning framework which helps the planner find the right
ules shown below are suggestions for the planning of supply concept for his project.
3 various building types and supply options. All modules are
based on a clear radial network and the following goals are The design proposals (Tab. 3/1) and the network planning
aimed at: modules (Fig. 3/2 to Fig. 3/6) help building up the power
8
Building Wiring / Floor Power Transformer
Module Supply Floors Total area Generator UPS
type main route area demand module
9 1
Low-rise 1 supply
Cable ≤ 4 2,500 m2 10,000 m2
1,000 –
2 × 630 kVA,
ukr = 6 %,
400 kVA 200 kVA
building section 2,000 kW (30 %) (15 %)
Ik ≤ 30 kA
2 × 800 kVA,
10 2
Low-rise
building
2 supply
sections
Busbar ≤ 4 2,500 m2
2×
10,000 m2
> 2,000 kW ukr = 6 %,
Ik ≤ 60 kA
730 kVA
(30 %)
400 kVA
(15 %)
1 supply 2 × 630 kVA,
High-rise 400 kVA 200 kVA
11
3 section, Busbar ≤ 10 1,000 m2 10,000 m2 ≤ 1,800 kW ukr = 6 %,
building (30 %) (15 %)
energy center Ik ≤ 30 kA
1 supply
section,
2 (2 + 1) ×
12 4
High-rise
building
energy center
and Cable 10 – 20 1,000 m2 20,000 m2 ≥ 1,500 kW
630 kVA,
ukr = 6 %,
800 kVA
(30 %)
400 kVA
(15 %)
transformers
Ik ≤ 45 kA
at remote
13
location
1 supply
2×3×
section, 2× 2×
High-rise 800 kVA,
5 energy center Busbar > 20 1,000 m2 20,000 m2 ≥ 2,000 kW 630 kVA 300 kVA
building ukr = 6 %,
14 and remote
distribution
Ik ≤ 60 kA
(30 %) (15 %)
15
16
17
Intro
duction
Functional areas:
Offices
Functional 2
building?
Conference rooms
Data center yes
Canteen kitchen with casino
Heating/ventilation/air conditioning
Radial network
3
Fire protection
with partial
Transport
load reserve
4
TN-C-S system,
LVMD with central
earthing point 5
i < 5?
no 6
Tip:
Max. side length: a
7
Floor area A = a2
Height per floor: h Low-rise building High-rise building
Number of floors: i
Max. number of floors
for one supply section:
i ≤ (100 m – 2a) / h
no no
8
A ≤ 2,000 m2? i ≤ 10?
Interlocked load 12
transfer with
4-pole devices
13
Hint:
Select busbar trunking
Low-rise building
Module 1
Low-rise building
Module 2
High-rise building
Module 3
High-rise building
Module 4
High-rise building
Module 5 14
systems if the focus is on
yes yes
comfort requirements such
as easy installation and
good extendibility, or high
yes yes yes
15
TIP04_13_004_EN
17
Fig. 3/1: Overview of the network planning concepts back to page 36
Intro
duction
1
Lowrise building, one supply section per floor, energy center, cable
2
Lifts
3
HVAC
FF lifts
HVAC-SPS
4
NPS4.2
UPS4.2
SPS4.2
5 4th floor
NPS3.2
UPS3.2
SPS3.2
6 3rd floor
NPS2.2
7
UPS2.2
SPS2.2
2nd floor
8
NPS1.2
UPS1.2
SPS1.2
1st floor
10
LVMD
11
NPS SPS
1 2 G
3~ UPS
12 MS
z
Basement
13
TIP04_13_005_EN
from DSO
14 FF
HVAC
Firefighters
Heating – Ventilation – Air conditioning
MS Medium-voltage switchgear
LVMD Low-voltage main distribution
15 SPS
UPS
Safety power supply
Uninterruptible power supply
DSO Distribution system operator
z Measuring equipment
16
17
Fig. 3/2: Module 1: Low-rise building, one supply section per floor, energy center, cable back to page 36
Intro
duction
1
Lowrise building, two supply sections per floor, energy center plus decentralized LV distribution with busbars
2
Lifts
HVAC
3
FF lifts
HVAC-SPS
4
NPS4.1
SPS4.1
UPS4.1
NPS4.2
SPS4.2
UPS4.2
5
4th floor
NPS3.1
SPS3.1
UPS3.1
NPS3.2
SPS3.2
UPS3.2
3rd floor
6
NPS2.1
SPS2.1
UPS2.1
NPS2.2
SPS2.2
UPS2.2
2nd floor
7
NPS1.1
SPS1.1
UPS1.1
NPS1.2
SPS1.2
UPS1.2
1st floor
8
9
LVMD
10
NPS SPS
1 2 G UPS
11
3~
MS
z
Basement
from DSO
TIP04_13_006_EN
12
NPS Normal power supply
FF
HVAC
Firefighters
Heating – Ventilation – Air conditioning 13
MS Medium-voltage switchgear
LVMD Low-voltage main distribution
14
SPS Safety power supply
UPS Uninterruptible power supply
DSO Distribution system operator
z Measuring equipment
15
16
17
Fig. 3/3: Module 2: Low-rise building, two supply sections per floor, energy center plus decentralized LV distribution with busbars
back to page 36
Intro
duction
2 Highrise building, one supply section per floor, energy center plus decentralized LV distribution with busbars
3 Lifts FF lifts
HVAC HVAC-SPS
5
nth floor FD-NPS FD-SPS FD-UPS
6
(n–1)th floor FD-NPS FD-SPS FD-UPS
7
(n–2)th floor FD-NPS FD-SPS FD-UPS
8
2nd floor FD-NPS FD-SPS FD-UPS
9
1st floor FD-NPS FD-SPS FD-UPS
10
LVMD
11 NPS SPS
1 2 G UPS
3~
MS
12 z
Basement
TIP04_13_007_EN
from DSO
13
NPS Normal power supply
FD Floor distribution boards
14
FF Firefighters
HVAC Heating – Ventilation – Air conditioning
MS Medium-voltage switchgear
LVMD Low-voltage main distribution
SPS Safety power supply
15 UPS
DSO
Uninterruptible power supply
Distribution system operator
z Measuring equipment
16
17
Fig. 3/4: Module 3: High-rise building, one supply section per floor, energy center plus decentralized LV distribution with busbars
back to page 36
Intro
duction
Highrise building, one supply section per floor, energy center plus transformers at remote location, cable 2
Lifts FF lifts 3
HVAC HVAC-SPS
3 4
5
nth floor FD-NPS FD-SPS FD-UPS
6
(n–1) floor
th FD-NPS FD-SPS FD-UPS
7
(n–2)th floor FD-NPS FD-SPS FD-UPS
11
4th floor FD-NPS FD-SPS FD-UPS
15
SPS Safety power supply
UPS Uninterruptible NPS SPS
power supply 1 2 G UPS
3~
DSO Distribution system MS
16
operator z
z Measuring Basement
equipment
TIP04_13_008_EN
from DSO
17
Fig. 3/5: Module 4: High-rise building, one supply section per floor, energy center plus transformers at remote location, cable
back to page 36
Intro
duction
2 Highrise building, one supply section per floor, energy center plus remote distribution, plus decentralized LV distribution with busbars
3 Lifts FF lifts
G
4 5 6 3~ UPS
HVAC HVAC-SPS
5
nth floor FD-NPS FD-SPS FD-UPS
6
(n–1)th floor FD-NPS FD-SPS FD-UPS
7 FD-SPS FD-UPS
(n–2)th floor FD-NPS
13
Air conditioning
MS Medium-voltage
switchgear
1st floor FD-NPS FD-SPS FD-UPS
LVMD Low-voltage main
14
distribution
SPS Safety power supply
UPS Uninterruptible
power supply LVMD
15 b 4-pole switching
device for connecting NPS SPS
the LVMDs 1 2 3 G
3~ UPS
DSO Distribution MS
16 system operator z
z Measuring Basement
equipment
TIP04_13_009_EN
from DSO
17
Fig. 3/6: Module 5: High-rise building, one supply section per floor, energy center plus remote distribution, plus decentralized LV
distribution with busbars back to page 36
1 As described in chapter 3, a single medium-voltage sub reasons for this, for example, are the high load concen
station with one transfer feeder from the grid operator and trations in different areas of a large building complex, such
one or more distribution transformers for supply of the as data centers and high-rise buildings used in the infra-
2 low-voltage loads is not sufficient in large infrastructure structure, or also the distribution of loads over large areas,
projects. Instead, an internal, separately operated medium- such as airports, industrial plants, production plants, and
voltage grid with several substations is required. The hospitals.
3
10
11
12
13
14
15
16
17
Intro
duction
1. The configuration of transformer substations and main 2. A load flow-optimized network separation and also the
7
feed-ins should be “intrinsically safe”. This means that if possibility of automation and remote control technology
an HV / MV transformer or an MV feeding line should fail, should be taken into account for the operation of MV
the connected loads have to be transferred to other grids, and also the accessibility of substations in order to 8
transformer substations or other feed-in points. How- minimize the downtimes when a fault occurs.
ever, on the one hand, the power of the transferable
loads is limited to the possibilities of the medium-voltage
grid, and, on the other hand, there is a danger of malop-
3. In order to ensure the supply quality in the distribution
grid, the supply radii must be considered in relation to
9
eration and as a result, failure of parts of the supplied the supply voltage. The rule of thumb is:
network. By keeping the number of switchover opera-
tions as low a possible, the total time until the power is
–– For a high load density,
the supply radius r in km = ⅓ supply voltage in kV
10
restored to the loads is minimized. –– For a low load density,
4. The installation of transformer substations and main 2. For cost reasons, transformers in substations up to 14
feed-ins at the load centers corresponds to a radial 630 kVA are usually connected via switch-disconnectors
supply from the transformer substations and short and HV HRC fuses. With high transformer ratings,
distances to the load centers. This enables losses to be circuit-breakers are used for reasons of selectivity or 15
minimized, a simple and flexible network configuration, when automation is required.
as well as an economic network extension.
16
17
Intro
duction
1 3. The economically useful power range (influence on 5. Use uniform, short-circuit-proof cables such as
voltage drop, power losses, power quality) for energy 120 mm² Cu or 150 mm² Al for distribution cables and
transport in a low-voltage grid of 400 V is between 240 mm² Cu or 300 mm² Al for transport cables.
2 50 kVA (approx. 72 A) and 250 kVA (approx. 360 A;
several low-voltage cables are required in one direction). 6. Avoid routing several cable systems together. If possi-
For a larger power range, the construction of a new ble, distribute the lines over the area. The combination
3 substation should be considered. of distribution cables into cable sections with several
systems over a few routes results in mutual heating and
4. Substations as multiple nodes make fault detection more therefore restricted transmission capacity of the cables.
17
Intro
duction
11
12
13
14
15
16
MVMD
17
TIP04_13_098_EN
Intro
duction
2 = substation, such as
3
or
TIP04_13_099_EN
6 MVMD
Rings start and end in the same transformer substation or Lines start in the transformer substation or in the main
9 in the feed-in, but on different busbar sections. The reserve feed-in and end in the same opposite substation. A reserve
power is guaranteed through the maximum permissible power with 100 % of a line is guaranteed through a reserve
utilization of a half ring of 50 to 60 %. cable (empty line without substations).
10 Lines with load center substation (Fig. 4/5)
Intro
duction
4
Supply cable
5
Supply cable
6
TIP04_13_101_EN
MVMD Opposite substation 8
Fig. 4/5: Network configuration: lines with load center substation back to page 48
9
10
11
Opposite substation 12
13
14
TIP04_13_102_EN
16
Fig. 4/6: Network configuration: coupling of two transformer substation areas back to page 48 17
Intro
duction
can be isolated, and galvanically separated subnetworks As for a line network, a single busbar with bus sectionalizer
can be operated. The busbar in a transformer substation is also possible here if the opposite substation of all lines is
5 can usually be designed according to the connected net- a transformer substation. The rings are then connected to
work configuration. both sides of the bus sectionalizer.
usually a subordinate main feed-in, i.e., not a transformer The bus coupler is highly recommended for a single block
substation. Sectionalizing is recommended if a large num- with rings. A duplex system is also possible for this n
etwork
8 ber of transformers is to be connected. Feed-in from the configuration in order to save costs for the circuit-breakers
upstream network as a ring or double spur should then be in the rings.
connected separately to both halves of the busbar.
9 Note: A duplex system is a switchgear system with two
Double spurs single busbars installed back-to-back or face-to-face, in
which the cable feeder or respectively the incoming panel
10 Double spurs are used to supply subordinate switchgear
from a transformer substation or main feed-in. A single
are both connected to each busbar, each with a circuit-
breaker. This also provides the function of a double
busbar with bus sectionalizer (with disconnector as switch- busbar.
ing device) is sufficient to ensure the supply. To increase
11 the reliability of supply, the busbar sections can be sepa- A single busbar is sufficient for switchgear without feed-in.
rated spatially. If it is a pure opposite substation, then a bus sectionalizer is
generally not required. However, a bus sectionalizer is
12 Rings recommended for a larger number of lines (≥ 8). A bus
sectionalizer is required for an opposite substation with
If the medium-voltage grid is configured exclusively with attached rings or for a load center substation to keep the
13 rings, a single busbar with bus sectionalizer (with cir-
cuit-breaker as switching device) is sufficient. The rings
rings supplied by opening the bus sectionalizer when a bus-
bar fault occurs.
start on one side of the bus sectionalizer and end on the
other side. To increase the reliability of supply, the busbar Because of the shorter cable lengths in industrial or infra-
14 sections can be separated spatially. structure projects compared to those for the supply in
public grids, rings and lines can be operated with higher
Lines utilization with regard to the voltage drop. To avoid the
15 need of using double cables for rings (two parallel cables
In a line network, the decision between a single or double downstream from a switching device), it is recommended
busbar depends on the respective opposite substation. If that rings are not loaded with more than 300 A, with a
16 the opposite substation is a transformer substation, a
single busbar with bus sectionalizer (with circuit-breaker as
single-sided supply. For double spurs, a load of 500 A
should not be exceeded.
17
Intro
duction
a) 4
DSO feed-in
Boundary of
property
5
4)
1) 3)
2)
6
7
Customer feeders
Transfer *)
Billing **)
8
b)
1) Current transformer for protection
DSO feed-in
2) Current transformer for measuring
Boundary of
property
3)
4)
Voltage transformer for measuring
Voltage transformer for protection 9
3) 3) 5) Current transformer combining
5) Billing ***) 5) 2 cores for measuring and protection
4) 4)
*) The transfer switch could be
also a switch-disconnector
10
(acc. to requirements of DSO)
**) Air-insulated billing metering panel
1)
with standard transformer set of DSO
***) Switchgear-specific “system transformer‟ 11
set for billing
Customer feeders Customer feeders
12
c)
DSO feed-in DSO feed-in 13
Boundary of Boundary of
property property
4) 4)
14
2) 2)
15
1) 3) 1) 3) 1)
TIP05_18_001_EN
16
Transfer *) Billing **) Billing **) Transfer *)
17
a) Power demand up to approx. 5 MVA, without redundancy
b) Power demand above 5 MVA, with redundant feed-in
c) Power demand above 5 MVA, with redundant feed-in and separate billing metering panels
Intro
duction
1 the supply of the customer feeders is disturbed in case of transformers” must be kept as a reserve accordingly. In
failure on one busbar section or in the billing metering this case, the DSO supply rings are still dependent on
panel. Fig. 4/8 shows a planning example with SIMARIS the operation of the customer switchgear. In case of
2 project (see chapter 15.2) for such a switchgear of the failure, redundancy is granted on one busbar section.
8DJH type. As a rule, the two feed-ins are operated in parallel.
ii) Separate billing metering panels for the respective
3 b) Connected power above 5 MVA and redundancy of
feed-ins
feed-in with standard billing instrument transformers
of the DSO (Fig. 4/7c): The supply rings of the DSO are
For redundant supply of a MV grid with several substa- not influenced by the customer feeders. The redun-
6
Feed- Feed- Transfer Billing metering panel Transf. 1 Transf. 2 Transf. 3 Transf. 4 Ring 1.1 Ring 1.2
in 1 in 2
10
2,300
11
12
13
14
890
15
TIP05_18_002_EN
310 310 500 840 430 430 500 500 500 500
4,820
16
Fig. 4/8: Front view of 8DJH from SIMARIS project – typical for the non-redundant connection to a supply network (dimensions in mm)
17
Intro
duction
16
17
Intro
duction
1 4.5.2 Selection of the Network Protection • Specification of the mounting location of the protection
and the Network Protection Concept relay and the circuit-breaker on which the protection
device is to take effect
2 One of the planner's tasks is the preparation of a network • Selection of the protection relay type
and protection concept that matches the customer's • Recommendations for the selection of the transformation
requirements. As described previously, mainly spur, double ratio of the transformers
3 spur, and ring networks are used in the infrastructure. Spur
networks and open-type ringed networks are used when
• Specifications for the protection settings
• Consideration of specifications (for example, Technical
a switchover reserve capacity is sufficient. Double spur Connection Conditions (TCC)) and / or provision of devices
7
n.c.
8
I> 0.6 s
I>> 0.1 s
n.c.
n.c.
9
I>> 0.3 s
I> v 0.1 s
10
n.c.
Main substation
11
I>> 0.3 s
Feedin
12
Substation 1
Substation 2
13
n.c.
n.c.
14
I>> 0.3 s
I> v 0.1 s
n.c.
15
I> 0.6 s
I>> 0.1 s
TIP04_13_103_EN
17
Fig. 4/9: Protection concept for a spur network back to page 55
Intro
duction
For the previously described standard network configura- Spur (Fig. 4/9)
1
tions in the infrastructure, various basic statements can be
made regarding the selection of the protection devices and The transformers connected directly in the spur are either
the time grading. protected with a switch-fuse combination or with the aid of 2
a time-overcurrent protection.
Note: The grading times specified in the following examples
apply to the digital protection devices SIPROTEC 4, SIPROTEC
Compact, and SIPROTEC 5 in conjunction with Siemens Double spur (Fig. 4/10 and Fig. 4/11)
3
switchgear and correctly dimensioned current transformers.
The subordinate switchgear is supplied from two cable
systems operated in parallel. There are two ways to selec- 4
tively trip a fault on one of the cable systems:
n.c.
I> 0.6 s
I>> 0.1 s
8
n.c.
n.c.
n.c.
n.c. 9
I>> 0.6 s I>> 0.3 s I>> 0.3 s
I> v 0.1 s I> v 0.1 s
10
n.c.
n.c.
Main substation
11
Substation
12
13
n.c.
n.c.
n.c.
n.c.
I>> 0.6 s
I> v 0.1 s
I>> 0.3 s I>> 0.3 s
I> v 0.1 s
14
n.c.
15
I> 0.6 s
TIP04_13_104_EN
I>> 0.1 s
n.c. Normally closed 16
I> v Short-circuit tripping in the forward direction; this means in the direction of the cable
17
Fig. 4/10: Protection concept for a double spur with directional time-overcurrent protection
Intro
duction
n.c.
8
I> 0.6 s
I>> 0.1 s
n.c.
n.c.
n.c.
9 n.c.
I>> 0.6 s ΔI 0.0 s ΔI 0.0 s
I> v 0.1 s I>> 0.3 s
10
n.c.
n.c.
Main substation
Substation
11
I>> 0.6 s I>> 0.3 s
Feedin
12
13
n.c.
n.c.
n.c.
n.c.
14
I>> 0.6 s ΔI 0.0 s ΔI 0.0 s
I> v 0.1 s I>> 0.3 s
n.c.
15
I> 0.6 s
I>> 0.1 s
TIP04_13_105_EN
16 n.c.
I> v
Normally closed
Short-circuit tripping in the forward direction; this means in the direction of the cable
Communication link
17
Fig. 4/11: Protection concept for a double spur with line differential protection back to page 55
Intro
duction
6
n.c.
n.c.
n.c.
7
Substation 1
Substation 2
8
n.c.
n.c.
n.c.
n.c.
n.c.
n.c.
I>> 0.5 s
I> v 0.1 s
I>> 0.3 s 9
10
n.c.
Main substation
I>> 0.5 s
Feedin
11
12
n.o.
n.c.
n.c.
n.c.
n.c.
n.c.
13
I>> 0.5 s I>> 0.3 s
I> v 0.1 s
14
Substation 4
Substation 3
n.c.
n.c.
n.c.
I> 0.6 s
I>> 0.1 s
I> 0.6 s
I>> 0.1 s
I> 0.6 s
I>> 0.1 s
15
16
TIP04_13_106_EN
Intro
duction
1 Direction determination and time grading (Fig. 4/13) exclusively through this panel. The small current compo-
nent that flows from the opposite side does not activate
The cables can be disconnected selectively with the aid of the protection devices energized on this side. Only after
2 the direction determination of short-circuit currents when a the fault has been cleared on one side, enough fault cur-
fault occurs, and a time grading. Voltage transformers are rent can flow from the other side so that the fault can be
required for the direction determination. The direction finally cleared. This results in the disconnecting times
3 determination is required so that a fault current is only
cleared when it is in the direction defined in the protection
having to be added, which must be taken into account in
the settings in the upstream t ime-overcurrent protection
device. As can be clearly seen in Fig. 4/13, this method is devices.
6
n.c.
n.c.
n.c.
7
n.c. Substation 1
n.c. Substation 2
8
n.c.
n.c.
n.c.
n.c.
9 I>> 0.3 s I>> 0.9 s I> v 0.1 s I> v 0.7 s I> v 0.3 s I> v 0.5 s
I> v 0.1 s
n.c.
10
Main substation
I>> 1.3 s
Feedin
11
12
n.c.
n.c.
n.c.
n.c.
n.c.
n.c.
13
I>> 1.3 s I>> 0.9 s I> v 0.1 s I> v 0.7 s I> v 0.3 s I> v 0.5 s
14 I> v 0.1 s
n.c.
n.c.
n.c.
Substation 4
Substation 3
16
TIP04_13_107_EN
17
Note: Consider addition of grading times for faults at the start of the ring!
Fig. 4/13: Protection concept for a network with closed ring and time grading
Intro
duction
Directional comparison protection (Fig. 4/14) Note: With the SIPROTEC protection devices from Siemens, this
1
is guaranteed within 100 ms even over longer distances (also
In the directional comparison protection, the direction within 50 ms under certain boundary conditions).
determination is extended so that no time grading is 2
required in the ring. Through the evaluation of the fault Because of the current distribution over the two ends of
current direction and a corresponding blocking of the the ring, this can also result in an addition of the discon-
protection device at the other end of the line or the adja-
cent ring-main panel in the substation, all protection
necting times until the fault is finally cleared within the
cable ring. The advantage of the same disconnecting times
3
devices in the ring can be set to the same delay time. The is noticeable in larger rings (more than three substations in
blocking can be performed via binary inputs / outputs with
copper wiring as well as via a system interface with fi-
one direction).
4
ber-optic cable (FOC). The evaluation and blocking as well
as the resetting of the disconnecting signal must be per-
formed within the set time delay. 5
6
n.c.
n.c.
n.c.
Substation 1
Substation 2
7
8
n.c.
n.c.
n.c.
n.c.
n.c.
n.c.
I>> 0.9 s
I> v 0.1 s
I>> 0.3 s
backward
I>> 0.3 s
backward
I>> 0.3 s
backward
I>> 0.3 s
backward
I>> 0.3 s
backward 9
forward forward forward forward forward
n.c.
10
Main substation
I>> 0.9 s
Feedin
11
n.c.
n.c.
n.c.
n.c.
n.c.
n.c.
12
I>> 0.9 s I>> 0.3 s I>> 0.3 s I>> 0.3 s I>> 0.3 s I>> 0.3 s
I> v 0.1 s backward backward backward backward backward
forward forward forward forward forward 13
n.c.
n.c.
n.c.
Substation 4
Substation 3
I> 0.6 s
I>> 0.1 s
I> 0.6 s
I>> 0.1 s
I> 0.6 s
I>> 0.1 s
14
16
backward Short-circuit direction determination backward; this means in the direction of the busbar
TIP04_13_108_EN
forward Short-circuit direction determination forward; this means in the direction of the cable
Blocking
Note: Consider addition of grading times for faults at the start of the ring!
17
Fig. 4/14: Protection concept for a network with closed ring and directional comparison protection
Intro
duction
1 Line differential protection (Fig. 4/15) In modern devices, the communication between the device
pairs for the line differential protection is generally via FOC,
In line differential protection, each ring-main section is but communication via copper cable is also possible. Be-
2 assigned to a differential protection zone. A fault within cause of the differential principle and the extremely fast
this zone results in a simultaneous disconnection of both communication between the devices, a tripping delay is
ends by the line differential protection. This also eliminates not necessary. A further advantage of the differential
3 the problem of the possible addition of disconnecting times
under unfavorable fault conditions. A fault outside the
protection principle is the simpler configuration compared
with the complex structure for blocking by means of a
differential zone is not recognized as a fault. For this rea- directional comparison.
7
Substation 1
Substation 2
n.c.
n.c.
n.c.
8
9
n.c.
n.c.
n.c.
n.c.
n.c.
n.c.
I>> 0.5 s ΔI 0.0 s ΔI 0.0 s ΔI 0.0 s ΔI 0.0 s ΔI 0.0 s
11
Main substation
I>> 0.5 s
Feedin
12
n.c.
n.c.
n.c.
n.c.
n.c.
n.c.
13
I>> 0.5 s ΔI 0.0 s ΔI 0.0 s ΔI 0.0 s ΔI 0.0 s ΔI 0.0 s
n.c.
n.c.
Substation 4
Substation 3
16
TIP04_13_109_EN
Intro
duction
Busbar protection The busbar differential protection is the faster and more
1
sensitive method, but entails higher costs. Fig. 4/16 shows
Busbar faults within switchgear are very improbable today the possibility of reverse interlocking at a substation, which
because of switchgear construction, but not impossible. is integrated in a closed ring via directional comparison 2
Usually, such faults are detected by an upstream time-over- protection or via line differential protection.
current protection and cleared. However, with this method
the time until disconnection depends on the grading times
that result from the selective configuration of the network.
In order to increase the protection level within metal-
enclosed switchgear, arc-related faults that are associated
3
In order to achieve shorter disconnecting times for busbar with a pressure rise within the enclosed switchgear, can be
faults and therefore reduce the damage as much as possi-
ble, or to reach a higher protection level, either a special
quickly detected and cleared by means of pressure
switches. In such cases, the pressure switch functions as a 4
busbar differential protection can be used or a reverse busbar protection device.
interlocking through the directional time-overcurrent
protection. 5
14
n.c.
I> r
Normally closed
15
Short-circuit tripping in the backward direction; this means in the direction of the busbar
backward Short-circuit direction determination backward; this means in the direction of the busbar
16
TIP04_13_110_EN
forward Short-circuit direction determination forward; this means in the direction of the cable
Blocking
17
Communication link
Intro
duction
1 Setting of the time-overcurrent protection In cable systems, remote terminal units (RTU) as well as
excitation currents short-circuit and earth-fault detectors are used for automa-
tion of ring-main units (RMU). The principle is based on
2 The setting of the overcurrent excitation for the protection 3 steps:
of cable routes depends on:
• The respective operating conditions 1. Fault localization
3 • Current transformer ratios
• Maximum normal currents that occur 2. Disconnecting the fault from the network
• Minimum short-circuit currents that occur.
15
16
17
Intro
duction
(Fig. 4/18) as well as the communication with the central through the blue path, and through the yellow path on the
1
control and protection system (in Fig. 4/18, e.g., SICAM TM) right of the fault.
is implemented by means of a communication and automa-
tion device such as SICAM EMIC and the communication- The maintenance crew can be immediately sent to the 2
related integration of the motor operating mechanisms of affected section of the network. After fault clearing,
the switching devices. reconfiguration can also be automated.
7
Regional Controller
SICAM TM
8
10
Fault Fault
Com Com
Run Run
11
12
14
Fault Fault
TIP05_18_003_EN
Com Com
Run Run
15
Fig. 4/18: Simple “self-healing” automation solution for ring-main cable systems (normally open)
16
17
Intro
duction
1 4.6 Connection of the Neutral Point in Depending on the neutral-point connection, there is a
the Medium-Voltage Cable System difference in the operating behavior of the networks,
which is described in the following sections. The following
2 During normal operation, the connection of the neutral are assessed:
point has no effect on the transmission of the electrical • Size of the single-phase short-circuit current
energy. Only when a fault occurs is the connection of the • Size of the neutral displacement voltage
3 neutral point to earth of importance. The neutral-point
connection is not uniform in medium-voltage grids. The
• Transient overvoltage in the phases not affected
• Type of voltage recovery in the affected phases after
following neutral-point connections can be found in over clearing the short circuit.
7
Isolated neutral point phase-to-neutral voltage U occurs. The earth-fault current
(free neutral point) Ie, which is fed from the fault-free phases via the earth
capacitance C0, flows across the fault location. The size of
the earth-fault current is therefore determined by the earth
8 1
2 capacitance of the phase.
3
ICE The following applies to the earth-fault current:
9 C0
Ie = 3 · U · ω · C0
10 Earth-fault compensation
Only small earth-fault currents occur in spatially limited
cable systems and therefore relatively small earth capaci-
(resonant NE: RNE) tance. The thermal effect at the fault location is small. For
this reason, the cable affected by the fault can usually
11 1
remain in operation until switchovers have been made in
the network, which allow the cable to be isolated without
2
affecting the loads. During the time required for the
12
3
Petersen IRest switchovers in the network, there is a danger that the earth
coil C0 fault develops into a short circuit, or that, as a result of the
increased phase-to-earth voltage, a second earth fault in
13 the network occurs on another phase. Such double earth
faults can affect the consumers much more than single
earth faults or short circuits, because two different cable
Low-resistance neutral earthing
connections can be affected and then two disconnections
14 (LRNE)
are required in the network.
1
15 2
3
Ik1“
Resistance R C0
16
TIP04_13_010_EN
Intro
duction
In larger cable systems, earth faults usually develop very If an earthing reactor is connected at the neutral point of a
1
quickly into short circuits. There is therefore not enough transformer, the neutral displacement voltage drives an
time to make the switchovers. When operating cable inductive current that flows back into the network via the
systems with free neutral point, it is best when the earth- fault location. The capacitive earth-fault current and the 2
fault currents are relatively small. Usually, an earth-fault inductive reactor current are in opposite phase. If the
current range of 10 to 35 A is suitable for this operating reactor is suitably dimensioned, the two currents are
mode. With small currents, there is a risk of intermittent
earth faults with high transient overvoltages. With large
approximately the same size and neutralize one another.
Only the active leakage current resulting from the active
3
currents, there can be major thermal effects through an components flows across the fault location. In cable sys-
earth-fault arc. Small industrial networks and auxiliary
power plant networks are usually operated with an isolated
tems, this current is approximately 2 to 5 % of the capaci-
tive earth-fault current. In practice, a residual reactive 4
neutral point. The costs for the equipment to compensate current resulting from inexact harmonization and a har-
earth-fault currents are eliminated. It is only recommended monic leakage current are superimposed on the active leak-
that the earth-fault windings of the three voltage trans- age current, because the resonant circuit from network 5
former sets that are connected in open delta are equipped capacitances and arc suppression coil are only harmonized
with an ohmic damping resistor. This is to avoid the relax- to the basic frequency of 50 Hz.
ation oscillations that can occur during the earth fault or
during making operations. Even when the fault location is As with the free neutral point, operation can also be main-
6
detected with the aid of earth-fault relays, which can result tained with earth-fault compensation when an earth fault
in the fast disconnection of the faulty line, the danger of
double earth faults through earth-fault overvoltages and
occurs, because the phase voltages are only displaced
against the earth potential. The voltages of the phases to
7
also the voltage increase on faulty phases still remains. one another are maintained. That is the main advantage of
these two types of neutral-point connection. The supply of
4.6.2 Operation with Earth-Fault the consumers connected to the network is not affected by 8
a single-phase fault and operation is also maintained
Compensation during an earth fault.
During operation with earth-fault compensation, the
feeding HV / MV transformers must have an intermediate-
9
Compensation of the earth-fault current is intended to
voltage winding at the neutral point for the connection of automatically clear the earth-fault current and thus elimi-
an arc suppression coil. Otherwise, a neutral-earthing
transformer must be installed. When selecting the trans-
nate the fault in the network. An attempt is made to limit
the fault current to the smallest possible leakage current.
10
former to which the arc suppression coils (Petersen coil) is However, the insulation at the fault location should not be
to be connected, the relevant regulations, as described in damaged after the current is cleared. This is not a problem
standard IEC 60076-6 (VDE 0532-76-6), must be taken into in overhead-line networks. 11
account. The earth-fault current can also be distributed
over several arc suppression coils or transformer neutral On the other hand for cable faults in general, automatic
points. clearance of the current at a fault location is not always 12
desired, because the insulation is often damaged at the
In a network with earth-fault compensation, the same fault location, and this can result in earth faults or double
displacement of the voltage neutral point occurs on an
earth fault as in a network with free neutral point. The
earth faults later. Apart from that, the clearance of earth-
fault currents in cable systems also has the same advan-
13
fault-free phases take the delta voltage to earth. As the tages as described above.
phase-to-earth capacitances in the network are indepen-
dent of the neutral-point connection, the capacitive earth- 14
fault currents also reach the same size as in a network with
free neutral point.
15
16
17
Intro
duction
1 With earth-fault compensation, the transient internal 4.6.3 Operation with Neutral Earthing
overvoltages are smaller than with the free neutral point.
They reach two to three times the phase-to-neutral voltage, With neutral earthing, currents similar to short-circuit
2 whereby factors above 2.5 are relatively seldom. Restrikes currents flow in the network when a single-phase fault
scarcely occur. The danger of double earth faults occurring occurs. They must be detected and selectively isolated as
is therefore less than in networks with isolated neutral quickly as possible by the network protection in order to
3 point. clarify the situation even when a single-phase fault occurs.
This eliminates the possibility of an unclear fault evalua-
The disadvantages of earth-fault current compensation are tion. Fault locating, which can cause problems in the other
4 the additional costs for the reactors and the much more dif-
ficult locating of sustained earth faults compared to net-
neutral-point connection procedures, is omitted.
works with free neutral point. Only the relatively small All three phases must be monitored by the protection
active leakage current can be used for a clear indication of system in medium-voltage grids with earthing of the
5 the earth fault. Generally, only electronic relays with sensi- neutral point. This means that there must be three current
tive earth-fault detection are capable of detecting these in transformers, and the network protection must be
cable systems with an active leakage current, because they equipped with relays effective in all three phases. In exist-
6 are only 2 to 5 % of the capacitive earth-fault current.
Alternatively, transient earth-fault relays can also clearly
ing networks that only have two current transformers,
cable-type current transformers to detect single-phase
locate an earth fault. If these are not available, however, a faults can be retrofitted when converting to neutral
15
16
17
Intro
duction
The high earth-fault currents can cause major damage and 4.6.4 Comparison of Neutral Earthing via 1
potential increases at the fault location and high induction Resistance or via Reactance
voltages in telecommunication cables. This may require
costly protection measures. For this reason, the earth-fault The low-resistance neutral earthing can be performed 2
current in medium-voltage grids is also limited through either by means of resistance or reactance. In the
additional neutral-point impedances in countries where medium-voltage grids of many countries up to 20 kV,
solid neutral earthing is commonly used. resistance earthing dominates, because the attenuation of
the transient overvoltages for earth faults and switching
3
The permissible level for the limitation is determined by the procedures is higher. With the reactance earthing, high
trigger conditions for the network protection. Even with an
unfavorable network configuration and position of the
overvoltages can occur particularly when clearing earth
faults. The neutral earthing via reactance is only recom- 4
earth fault, the assigned relays must trigger reliably. In mended [2] when the ratio of the zero-sequence reactance
medium-voltage grids, a highest earth-fault current of 1 kA X0 to the positive-sequence reactance X1 of the network
to 2 kA is practically always sufficient. In industrial net- remains less than or equal to 10 (X0 / X1 ≤ 10). This means 5
works, this value will be closer to the lower range, because that the earth-fault current must be more than 25 % of the
they are not as large as public distribution grids, and values 3-phase short-circuit current and therefore above the
down to 500 A are also common. The damage at the fault
location is relatively small with such currents. However, the
minimum value required by the network protection. 6
current is also large enough to lead to the low-resistance High overvoltages are to be expected if restrikes of
earth connection required to locate the fault. In pure cable
systems, there is therefore no reason to limit the earth-
circuit-breakers occur when breaking capacitive currents.
The problem does not seem important for circuit-breakers
7
fault current further. However, in networks in which gener- without restrikes. Despite this, the better overvoltage
ators are connected directly, it is better when the current is behavior of the resistance earthing is advantageous partic-
limited as much as possible (stator earth fault). ularly for voltage changes in medium-voltage grids. 8
The insulation stress during an earth fault is determined by There is no uniform guideline for the measurement of
the power-frequency voltage increase during operation
(characterized by the earth-fault factor according to
neutral-point resistances or reactor coils. It is appropriate
that the current measurement is determined by the largest
9
IEC 60071-1, VDE 0111-1) and by the transient earth-fault earth-fault current that was specified for the grid, for
overvoltage (characterized by the overvoltage factor).
Compared with operation with free neutral point or with
example, to meet the requirements of the network protec-
tion. This current is considered to be the rated short-time
10
earth-fault compensation, the low-resistance neutral current. The stressing duration is generally specified be-
earthing has definite advantages with regard to the insula- tween 5 and 10 s taking into account long grading times
tion stress. and earth faults that follow in quick succession. Frequently, 11
the resistance or reactance of the earthing unit can be
With earth faults, it is particularly important that the stress- determined precisely enough by means of the network
ing of the network with increased voltage is significantly phase-to-neutral voltage and the largest earth-fault cur- 12
shorter. The overvoltages are reduced through the low- rent. For an assumed maximum earth-fault current of
resistance neutral earthing not only for earth faults, but 2,000 A, this results, for example, in an earthing resistance
practically for all switching procedures. of 5 to 6 Ω in a 20 kV network. It is recommended, how-
ever, that the attenuation of the earth-fault current is
13
checked through the series impedance. The earthing
devices are isolated in the line voltage range between 10
and 20 kV for the phase-to-neutral voltage of the network. 14
15
16
17
Intro
duction
1 4.6.5 Planning of Neutral Earthing fault power in the transformer substation – has no great
effect due to the generally used high current limiting.
When planning the neutral earthing for a network, a decision However, when a fault occurs in the network, the earth-
2 must first be made as to where the neutral earthing is to be fault current is significantly damped by the cable imped-
performed and for what magnitude the earth-fault current ances. In contrast to multi-phase short circuits, fault cur-
is to be limited. The neutral point should always be earthed rents can occur here that are of the same size as the rated
3 in the feeding substation. If there are several feed-ins, then
neutral earthing must be performed at each feed-in. Only in
cable currents. The main point to be investigated during
the planning is whether all earth faults trigger the assigned
this way is it possible to achieve a simple and safe earth- relays and the relays intended as reserve protection. The
10
TIP04_13_111_EN
Low-resistance neutral earthing
Neutral-point connection Free neutral point Earth-fault compensation
With impedance Solid
11 Connection
1
2
3
1
2
3
1
2
3
1
2
3
ICE Petersen I Rest I k1“ I k1“
C0 Coil C0 Resistance R
12
Objective Continuous operation during a single-phase fault Selective tripping of a single-phase fault
13 1 UnN 1
Rating — XD ≈ R≈ << —
3 · ω · C0 3 · Ik1“ 3 · ω · C0
1/(j · ω · C0)
Z0/Z1 Very high resistance 20 … 100 1…5
14 Z1
IRest ≈ j · ω · C0 · c· 3 · UnN
ICE ≈ j · ω · C0 · 3 · UnN Ik1“ =
Current at the (d + jv) · 3 · UnN 2 · Z1 + Z0
15 fault location
10 A < ICE ≤ 35 A IRest ≤ 60 A Ik1“ ≤ 2 kA Ik1“ ≤ 1,5 · Ik3“
back to page 69
17
Fig. 4/20: Electrical parameters of the various neutral-point connections
Intro
duction
Therefore, during the planning of the neutral earthing, it is Fig. 4/20 shows a summary of the most important electrical
1
recommended that measurements are made to obtain an parameters for the various neutral-point connections.
overview of the cable zero-sequence impedances of the
network. Furthermore, those cables should be investigated The earth-fault currents are detected via the wiring of the 2
where the protection conditions are not clear, for example, protection transformer using a Holmgreen connection (see
extremely long cables or double cables. These measure- Fig. 4/21a) or by means of a cable-type current transformer
ments enable a sufficiently precise calculation of the
earth-fault currents. This calculation is a decisive factor for
(see Fig. 4/21b). The following is recommended: 3
the selection of the current limiting and the specification or
the neutral-point impedance.
4
6
a) Holmgreen connection
L1
b) Earthfault detection with cabletype current transformer
L1
7
L2 L2
L3 L3
8
9
SIPROTEC 7SJ …
UL1
SIPROTEC 7SJ …
UL1
10
UL2 UL2
11
UL3 UL3
U4
I L1 I L1
12
I L2 IL1 > I L2 IL1 >
16
Fig. 4/21: Measurement-based detection of earth faults with
a) Holmgreen connection 17
b) Cable-type current transformer (gray: optional voltage transformers for direction detection)
Intro
duction
1 • Operation with isolated neutral point It is only approximately one tenth of the positive-sequence
–– Use of the Holmgreen connection impedance. With star-star transformers with delta stabiliz-
if ICE sec > 0.05 IN2 ing winding for a third of the output, the zero-sequence
2 –– Use of the cable-type current transformer impedance can be up to 2.4 times larger than the posi-
if ICE sec < 0.05 IN2 tive-sequence impedance related to the rated power.
8 If the direction is also to be detected, additional voltage If earth-fault current compensation or neutral earthing is
transformers must be provided. used, transformers are required on which the connection
to the neutral point of the winding is possible and permissi-
9 4.6.6 Neutral-Point Connection and ble. If this is not the case, so-called earthing transformers
can be used. These are three-phase reactors with zigzag
Transformer Connection Symbol connection that have a large open-circuit impedance, but a
10 The neutral-point resistance or the neutral-point reactance
coil can be connected to the transformer in the feeding
small zero-sequence impedance. An earthing transformer
can also be dimensioned with increased zero-sequence
transformer substation in most cases. Prerequisite is that its reactance to limit the earth-fault current. The installation
zero-sequence impedance is sufficiently small. and connection of an earthing resistance is then no longer
11 required as the earthing transformer can be earthed
With transformers, the size of the zero-sequence imped- directly. In medium-voltage grids, the earthing transformer
ance depends on the connection method. Transformers in can also be equipped with a secondary winding, and can
12 star-delta connection have a zero-sequence impedance therefore also serve as a network transformer.
that corresponds to approximately 0.8 to 1 times the
positive-sequence impedance, whereas star-zigzag trans-
13 formers have a relatively small zero-sequence impedance.
14
15
16
17
1 All in all, the quality of electrical power supply is character- The electrical planner will indirectly factor in the aspect of
ized by the voltage and service quality as well as its avail- service quality by considering the functionality and quality
ability. The basic challenge in planning is to find the opti- aspects of the products and systems involved in the project.
2 mum of investment and operating costs on the one hand
and a risk estimation (the product of frequency and effects In order to specify the required product quality of connected
of failures) on the other hand (see Fig. 5/1). power consumers with regard to their supply voltage, the
3 Supply quality =
curve of the “Information Technology Industry Council“
(ITIC), formerly “Computer and Business Equipment Manu-
voltage quality + availability + service quality facturers Association” (CBEMA), as shown in Fig. 5/2 is
11
12
13
Cost Voltage ratio referred
TIP04_13_011_EN
Optimization range
14 (dependent on the
specific cost situation)
Total cost 400
Voltage
tolerance
Non-permissible range
(damage may occur)
300 ranges with
uninterrupted
15
function
Cost of investment 200
and operation 140
100 110
80 90
70 Range possibly without function,
17 Fig. 5/1: Diagram of cost optimization conditional upon supply Fig. 5/2: ITIC curve for computer power supply units [5]
quality
Intro
duction
5.1 Voltage Quality The fault parameters described in EN 50160 affect the
1
operation of the power supply system and the connected
The voltage quality results from the technical specifications power consumers. Tab. 5/2 assigns potential causes and
linked with the different interests of consumers and suppli- effects to the individual voltage problems. Due to the 2
ers. It is impaired by faults in the power supply on the one current energy policy, this issue is now increasingly becom-
hand and network disturbances caused by the connected ing the focus of the planner's attention. The power genera-
appliances, plants, and equipment on the other hand.
EN 50160 describes the following main characteristics of
tion concept based on controlled power plants in the
vicinity of load centers is being restructured towards de-
3
the supply voltage at the connections of the public grids: centralized power supply dependent on time and local
• Voltage magnitude, slow voltage changes
• Fast voltage changes, flicker
conditions. Consequently, intelligent concepts such as the
smart grid are used, and the efficient use of measuring and 4
• Voltage dips automation technology, storage technologies, energy
• Supply interruptions consumption controls, and energy conversion technologies
• Voltage unbalance such as uninterruptible power supply systems and charging 5
• Harmonic voltage and interharmonic component stations for electric vehicles need to be planned.
• Power-frequency and transient overvoltages
• Frequency variations. EN 50160 does not specify any values for electromagnetic
compatibility (EMC) or limit values for the emission of inter-
6
In many European countries, this standard serves as a ferences. It describes the characteristics of the supply
guideline or reference for parameter adaptation to the
characteristics of national power systems in order to create
voltage and related requirements for general operation.
The D-A-CH-CZ guideline [6] defines EMC as the capacity of
7
national standards. The establishment of such standards is an electrical appliance to function in a satisfactory manner
normally performed on the basis of the experience gained in the given electromagnetic environment without causing
by local initiatives with the implementation of monitoring impermissible electromagnetic disturbances itself. This kind 8
systems for power quality which allow the determination of reciprocal impact in the distribution grid and on the
of appropriate voltage parameters. Tab. 5/1 shows a more distribution grid is called network disturbances.
detailed subdivision with appropriate level and guidance 9
values.
Voltage unbalance
U (negative phase-sequence system) / U (positive phase-sequence
system) < 2 % during ≥ 95 % of a week
10 min average 1 week 13
< limit value in acc. with EN 50160 and THD < 8 % during > 95 % 10 min average of each
Harmonics Un2 … Un25 1 week
of a week harmonic
Subharmonics being discussed 1 week 14
Signal voltages < standard characteristic curve = f(f) during ≥ 99 % of a day 3 s average 1 day
15
Number < 10 … 1,000 / year; there of > 50 % with t < 1 s and 10 ms r.m.s. value
Voltage dips 1 year
∆U10ms < 60 % Urated U10ms = 1 … 90 % Urated
10 ms r.m.s. value
Short voltage interruptions Number < 10 … 1,000 / year; there of > 70 % with a duration of < 1 s 1 year
U10ms ≥ 1 % Urated
Long voltage interruptions Number < 10 … 50 / year; there of > 70 % with a duration of < 3 min
10 ms r.m.s. value
1 year
16
Temporary overvoltage (L-N) Number < 10 … 1,000 / year; there of > 70 % with a duration of < 1 s 1 year
U10ms > 110 % Urated
Transient overvoltage < 6 kV; µs … ms No data
17
Tab. 5/1: Voltage characteristics in public power supply systems according to EN 50160
Intro
duction
1
Problem Description Cause Effect
4 Interruption
time up to
Supply interruption:
Planned or accidental total loss
• Switching operations
attempting to isolate an
• Sensible software process
crashes
three minutes of power in a specific area; electrical problem and • Loss of computer memory
Voltage signal
12
fluctuates with time production shortcomings
17
power supply system by UPS systems, for instance breakers, relays, or fuses
Intro
duction
A classification of different operational environments and data center. Protection by UPS, filters, or surge arresters is
1
the assignment of appropriate characteristic parameters common for this class. The classification in accordance with
and compatibility levels are described in the standard series IEC 61000-2-4 (VDE 0839‑2-4) is shown in Tab. 5/4.
IEC 61000. Tab. 5/3 gives an overview of the contents of 2
the individual standards. According to IEC 61000-2-4 Voltage stability, voltage unbalance, and harmonics play an
(VDE 0839-2-4) equipment and devices must be classified important part in assessing malfunctions and voltage
as electromagnetic environment class 1 when they respond
very sensitively to interference parameters of electrical
quality. 3
power supply, such as the data processing facilities in the
5
IEC 61000 – Electromagnetic compatibility (EMC)
-2 EMC – Ambient conditions
6
EMC – Environment – Compatibility levels for low-frequency conducted disturbances and signaling in public low-
-2 VDE 0839-2-2
-4 VDE 0839-2-4
voltage power supply systems
EMC – Environment – Compatibility level in industrial plants for low-frequency conducted disturbances
7
EMC – Environment – Compatibility levels for low-frequency conducted disturbances and signaling in public
-12 VDE 0839-2-12
8
medium-voltage power supply systems
-3 EMC – Limit values
-2 VDE 0838-2 EMC – Limits – Limits for harmonic current emissions (equipment input current ≤ 16 A per phase)
-3 VDE 0838-3
EMC – Limits – Limitation of voltage changes, voltage fluctuations and flicker in public low-voltage supply systems,
for equipment with rated current ≤ 16 A per phase and not subject to conditional connection
9
EMC – Limits – Limitation of voltage changes, voltage fluctuations and flicker in public low-voltage supply systems
-11 VDE 0838-11
– Equipment with rated current ≤ 75 A and subject to conditional connection
-12 VDE 0838-12
EMC – Limits – Limits for harmonic currents produced by equipment connected to public low-voltage systems with 10
input current > 16 A and ≤ 75 A per phase
-4 EMC – Testing and measuring procedures
-7 VDE 0847-4-7
EMC – Testing and measurement techniques – General guide on harmonics and interharmonics measurements and 11
instrumentation, for power supply systems and equipment connected thereto
-15 VDE 0847-4-15 EMC – Testing and measurement techniques – Flickermeter – Functional and design specifications
-30 VDE 0847-4-30 EMC – Testing and measurement techniques – Power quality measurement methods 12
Tab. 5/3: Structure of the standard series IEC 61000 (VDE 0838, VDE 0839, VDE 0847)
13
This class applies to protected supplies, having compatibility levels which are lower than for public grids. It refers to the
14
Class 1 operation of equipment which responds in a very sensitive manner to disturbances in the power supply, for example, the
electrical equipment of technical laboratories, certain automation and protection gear, certain data processing facilities, etc.
This class generally applies to points of common coupling (PCC) with the public grid and for in-plant points of coupling (IPC)
with industrial and other non-public power supply networks. The compatibility levels for this class are generally identical with
15
Class 2
those applying to public grids. Therefore, components which were developed for use in public grids can also be employed in
this class for industrial environments.
This class only applies to in-plant points of coupling (IPC) in industrial environments. For some disturbances, it comprises
higher compatibility levels than those in Class 2. This class should be considered, for example, if one of the following
Class 3
conditions is true.
• A major load share is fed by the power converters
16
• Welding machines exist
• Large motors are frequently started
• Loads vary quickly
17
Tab. 5/4: Electromagnetic compatibility levels in accordance with IEC 61000-2-4 (VDE 0839-2-4)
Intro
duction
SA Connected load as single-phase or two-phase load Tab. 5/5: Electromagnetic compatibility levels in accordance with
SkV Short-circuit power at the point of common coupling EN 50160 for line voltages up to 35 kV
7
Uneven harmonics Even harmonics
5.1.2 Harmonics No multiples Multiples
8 Harmonics are superimposed oscillations deviating from
Order
of 3
Relative Order
of 3
Relative Order Relative
the 50 Hz fundamental frequency of the power supply voltage voltage voltage
system with an integer multiple of the fundamental. Every h in % h in % h in %
9 periodical oscillation curve can be represented as an 5 6 3 5 2 2
overlay of the sine-shaped basic curve and harmonic
7 5 9 1.5 4 1
oscillations. Harmonics are generated by equipment with
10 non-linear current-voltage characteristics such as trans- 11 3.5 15 0.4 6 0.5
formers, gas-discharge lamps, and power electronic 13 3 21 0.3 8 0.5
devices. 17 ≤ h ≤ 21 ≤ h ≤ 10 ≤ h ≤
0.27 0.2 0.25
11
49 45 50
Important harmonic generators are:
Tab. 5/6: Electromagnetic compatibility levels in accordance with
• Power electronic devices such as converter drives, static
IEC 61000-2-2 (VDE 0839-2-2) up to 1 kV
UPS systems, rectifier systems, dimmers
12 • Fluorescent lamps
• Power supply units for the DC voltage supply of informa-
tion and communication technology components
13 • Motors with non-linear current-voltage characteristics
• Converters in DC chargers
• Problems with the compensation of earth faults
• Overloading of the neutral conductor.
• Converters in photovoltaic systems and wind power
plants. The compatibility levels to be observed by the DSO are
14 defined in EN 50160 (see Tab. 5/5). When connecting to
Harmonics cause, for instance: the public power supply system, the user must ensure that
• Heating of three-phase and alternating current motors compatibility levels in accordance with the D-A-CH-CZ
15 • Fault tripping of circuit-breakers and miniature circuit- guideline [6] corresponding to EN 50160 and IEC 61000-
breakers, and malfunctions of ripple control receivers 2-2 (VDE 0839-2-2) are observed at the points of common
• Overloading and destruction of capacitors as a result of coupling to the public distribution grid see Tab. 5/6. Con-
16 thermal overloading
• Overheating of transformers
cerning the compatibility level of the harmonic voltages of
plant-internal connecting points in the non-public grids,
• Skin effects on cables, resulting in higher temperature reference can be made to IEC 61000-2-4 (VDE 0839-2-4)
loads and a greater voltage drop (see Tab. 5/7 to Tab. 5/9).
17 • Malfunction of electronic devices and control units as a
result of zero-crossing faults
Intro
duction
The compatibility levels specified in the standards are for Uneven harmonics Even harmonics
1
forming a reference level in a defined environment which
No multiples Multiples
exceeds the actual interference level only with a low proba-
bility (< 5 %). They are used for a metrological inspection of
Order
of 3
Relative Order
of 3
Relative Order Relative
2
the user's systems. Monitoring systems can be used for voltage voltage voltage
measuring which provide more extensive options for data h in % h in % h in %
processing and analysis than required by EN 50160. The
SICAM Q100 power quality recorder (see Fig. 5/3) enables
5 3 3 3 2 2 3
7 3 9 1.5 4 1
flexible communication with automation systems and
11 3 15 0.3 6 0.5
monitoring stations via standard protocols such as
IEC 61850 and Modbus TCP. With SICAM PQS, data collec- 13 3 21 0.2 8 0.5 4
tion and event recording is done in accordance with 17 2 10 0.5
IEC 61850. For data exchange, new standard formats such
as PQDIF and COMTRADE (ripple control signal) are used.
17 ≤ h ≤
49
0.27
21 ≤ h ≤
45
0.2
10 ≤ h ≤
50
0.25 5
Tab. 5/7: EMC level up to 35 kV for environment class 1 (Tab. 5/4) in
SICAM Q100 meets the precision requirements of a Class A
measuring device in accordance with IEC 61000-4-30
(VDE 0847-4-30) for measuring the voltage quality. Har-
accordance with IEC 61000-2-4 (VDE 0839-2-4) back to page 76
6
monics (see Fig. 5/4) are detected in accordance with the
Uneven harmonics Even harmonics
specifications made in IEC 61000-4-7 (VDE 0847-4-7) and
flickers are calculated as described in IEC 61000-4-15 No multiples Multiples 7
of 3 of 3
(VDE 0847-4‑15).
Order Relative Order Relative Order Relative
The identification, determination, and profile formation of h
voltage
in % h
voltage
in % h
voltage
in %
8
the measuring points for power quality monitoring play an
5 6 3 5 2 2
important part in project design. Since the power supply
system is a dynamic system in the building infrastructure,
the optimization of the measuring points is based on the
7
11
5
3.5
9
15
1.5
0.4
4
6
1
0.5
9
insights gained in day-to-day operation. Besides the selec- 13 3 21 0.2 8 0.5
tion of measuring points, the determination of power
quality requires a definition and determination of the
17 2 10 0.5 10
evaluation criteria at the individual measuring points. 17 ≤ h ≤ 21 ≤ h ≤ 10 ≤ h ≤
0.27 0,2 0.25
49 45 50
In order to properly estimate harmonic voltage interfer- Tab. 5/8: EMC level up to 35 kV for environment class 2 (Tab. 5/4) in 11
ences in line with the D-A-CH-CZ guideline [6], it is import- accordance with IEC 61000-2-4 (VDE 0839-2-4) back to page 76
ant to consider the functioning principles of the harmonic
generators used. According to [6], two groups are to be
Uneven harmonics Even harmonics
12
differentiated:
No multiples Multiples
Group 1: Equipment with a low emission of harmonic
content (10 % ≤ THDi ≤ 25 %) Order
of 3
Relative Order
of 3
Relative Order Relative
13
voltage voltage voltage
h in % h in % h in %
Group 2: Equipment with medium-range and high emission
of harmonic content (THDi > 25 %) 5 8 3 6 2 3 14
7 7 9 2.5 4 1.5
For example, pumps, ventilators, compressors, air condi- 11 5 15 2 6 1
tioning equipment, DC-controlled fans, and compact
13 4.5 21 1.75 8 1 15
fluorescent lamps with electronic ballast belong to group 2.
Compact fluorescent lamps with inductive ballast and 17 4 10 1
12-pulse converters are typically assigned to group 1. For
self-commutated converters with pulse width modulated
17 ≤ h ≤
49
4.5 ×
(17 / h) –
21 ≤ h ≤
45
1
10 ≤ h ≤
50
1 16
0.5
conversion via power capacitors, the harmonic content is
less than 10 % so that such converters do not need to be
17
Tab. 5/9: EMC level up to 35 kV for environment class 3 (Tab. 5/4) in
considered. However, the same also applies if integrated accordance with IEC 61000-2-4 (VDE 0839-2-4) back to page 76
Intro
duction
6 SOS SkV Fig. 5/3: SICAM Q100 power quality recorder back to page 77
=b·
SA SA
7 (b = 0.082 for low voltage or b = 0.058 for medium voltage)
Information
Harmonics voltage
Process connections
Maximum value
AC operational values
Instantaneous value
Harmonics voltage
If the limit lines of Fig. 5/5 for SOS / SA are exceeded, passive
8
Harmonics current Harmonics voltage L1
Interharmonics voltage
23,90 %
Interharmonics current
harmonic content. While passive filters influence harmon- Modbus slave devices
SICAM subdevices
Load profile
14,34 %
9
9,56 %
Automation functions
10
Memory management
Transient detection 34,40 %
13,76 %
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62
15
range
converter transformers. Under certain conditions, the cost 0.2
of oversizing transformers is balanced by reduced energy
losses during operation.
16
0.1
1 5 10 50 100 500 1,000
LV: Low voltage SkV/SA
MV: Medium voltage
Intro
duction
TIP04_13_014_EN
The so-called EMC Directive of the European Union [7] 10
defines electromagnetic compatibility (EMC) as "the capa- 2
Cable routing and screening Fig. 5/6: Distance dependency of the magnetic flux density for
various conductor arrangements back to page 80
6
The propagation of interference currents and the electric
and magnetic fields linked to them depend both on the
cable type and the arrangement. Generally speaking and in
7
accordance with EN 50174-2 (VDE 0800-174-2), signal and
data cables should be routed well away from power cables
and power supply cables. 8
10
D D D D
worse Configuration:
Sidebyside 1 Cu conductor
2 PVC insulation Singlecore cable
with spacing D
3 Core covering
4 PVC outer sheathing
1 2 3 4
11
Configuration:
Sidebyside 1 Cu conductor
2 PVC insulation Singlecore cable
without spacing
3 Core covering
4 PVC outer sheathing 12
1 2 3 4
Configuration:
In bundles
1 Cu conductor
2 PVC insulation
Singlecore cable 13
3 Core covering
4 PVC outer sheathing
14
1 2 3 4
Configuration:
Multicore cable 1 Cu conductor
2 PVC insulation Multicore cable
L1L2L3NPE
3 Core covering
1 2 3 4 5
4 PVC outer sheathing
15
Multicore Configuration:
1 Cu conductor Multicore
L1L2L3N
with concentric
screening (PE)
2 PVC insulation
3 Core covering
cable with
concentric PE 16
4 Concentric Cu screen
better 5 PVC outer sheathing
braiding
17
TIP04_13_015_EN
Fig. 5/7: Classification of simple cable types and installation with regard to EMC back to page 80
Intro
duction
1 The requirements placed on this separation depend on the loading of conductors leads to a deterioration of EMC
following: conditions. The symmetrical splitting of conductors in the
• EMC characteristics of the IT cables busbar trunking system has significant advantages because
2 • Design, dimensions, and geometrical arrangement of the of the reduced magnetic interference with the environ-
power supply cables ment. The SIVACON 8PS LD busbar trunking system
• Type of circuit supplied (LDA / LDC) with its symmetrical conductor splitting is thus
3 • Possibly existing isolating devices. particularly suitable for the transmission of high currents.
The procedure how to define isolation / separation require- Earthing and equipotential bonding
4 ments is described in EN 50174-2 (VDE 0800-174-2). In
particular for data centers, doubling the value established In particular stray currents may become a severe problem.
for the (isolating) distance between IT cabling and power That is, currents flowing through the protection conductor
supply cables is recommended. and the shielding of data and IT cables can cause failures,
5 malfunctions, and even damage. For this cable-bound EMC,
Bundling into cable groups and twisting phase and the earthing conditions (network system) in the low-volt-
return conductor is beneficial for electric power supply age grid are decisive. The strict separation of the protection
6 (see Fig. 5/6). The different bundlings of conductors and
the use of cable screens are arranged in an EMC-quality-
conductor from the neutral conductor in the TN-S system
helps to avoid such stray currents.
significant manner in Fig. 5/7.
9 Conductor arrangements
100
TIP04_13_016_EN
L1
10 cm L1 = 1,000 A e-j0°
10 L2 L2 = 1,000 A e-j120°
Magnetic flux density B in µT
10 cm L3 = 950 A e-j240°
L3
L1
11 10 cm
L2
L1 = 1,000 A e-j0°
L2 = 1,000 A e-j120°
10
10 cm L3 = 1,000 A e-j240°
L3
12 10 cm
L1
L1 = 200 A e-j0°
L2 L2 = 200 A e-j120° 1
10 cm L3 = 200 A e-j240°
13
L3
Interference limit ECG
L1
L1 = 1,000 A e-j0° Interference limit EEG
3c
L2 = 1,000 A e-j120°
m
3c
14
L3 = 1,000 A e-j240° 0.1 Interference limit EMG
L3 3 cm L2
16 L1 = 2,500 A e-j0°
L2 = 2,500 A e-j120°
Distance to source of interference in m
L3 = 2,500 A e-j240°
17 Fig. 5/8: Cable configuration and suitability with regard to EMC (the interference levels for electromyograms (EMG), electrocardiograms
(ECG), and electroencephalograms (EEG) are specified in the standard IEC 60364-7-710 (VDE 0100-710))
Intro
duction
Splitter
9
bridge
10
Source
Main
Protective equipotential
equipotential bonding 2
bonding –
transformer
Operational
earthing
11
Low-voltage main distribution
L1 L1
U
12
L2 L2
L3 L3
PEN N 13
TIP04_13_017_EN
PE PE
Central
earth
point
14
Main
equipotential
15
bonding 1
Sub-distribution board
L1 L1
L2 L2
L3
N
L3
N
16
PE PE
Intro
duction
Although there are no binding standards with regard to Function can be interrupted, data
2 reliability of supply at the moment, the permissible dura-
AEC-0 Conventional
integrity is not essential.
tion of interruption and corresponding redundancy require- AEC-1 Highly reliable
Function can be interrupted, but data
ments should be considered in the planning phase. integrity must be ensured.
4 one unit than required for maintaining this function (here: Function must be maintained without
AEC-3 Fault-resilient interruption within defined times or
for electric power supply of the critical infrastructure during the main operating time.
components). The DIN standard explicitly notes that main-
Function must be maintained without
tenance, i.e., monitoring, servicing, and restoring (in case
5 of failure) proper functioning, is required for maintaining
AEC-4 Fault-tolerant interruption, 24 / 7 operation (24 hours,
7 days a week) must be ensured.
the redundancy. In particular in the field of ICT and data
Disaster- Function must be available under all
center infrastructure, it is necessary that the planner in- AEC-5
tolerant circumstances.
6 tensely deals with the redundancy issue. Therefore, in the
following, reference will often be made to research, experi-
Tab. 5/10: Availability Environment Classification (AEC)
acc. to HRG [8]
ence, and studies from this field.
7
5.3.1 Availability Classes
As a mathematical term, availability is defined as the
Based on the classification performed by the Harvard quotient from the "mean time between failure“ (MTBF) and
8 Research Group (HRG) in 2002 (see Tab. 5/10), several the sum of all MTBF and the "mean time to repair" (MTTR):
grades of availability have established. In its High Availabil-
ity Compendium [9], the German Federal Office for Infor- Availability A = MTBF / (MTBF+MTTR)
9 mation Security (Bundesamt für Sicherheit in der Informa-
tionstechnik (BSI)) presents a classification quoting down- However, availability only becomes significant if the magni-
times corresponding to the respective status of non-avail- tudes of MTBF and MTTR are known. Tab. 5/12 shows three
10 ability (see Tab. 5/11). estimations of the availability in different fault scenarios.
12 AVC 1
Standard safety based on basic IT protection with
normal demand for availability
99 % 1 % <8h < 88 h
14
AVC 4 Highest availability 99.999 % 0.001 % < 26 s < 6 min
AVC 5 Disaster-tolerant Max. availability 0 0 0
* Supplementary risk analysis acc. to BSI Standard 100-3
15 Tab. 5/11: Typical availability classes according to the High Availability Compendium of the BSI [9]
16 MTBF
1 day
MTTR
1 second
A
86,400 s / 86,401 s = 99.999 %
Operational compatibility
Not acceptable
1 month 30 seconds 2,592,000 s / 2,592,030 s = 99.999 % Still acceptable
Intro
duction
The percentages of availability differ marginally in the sixth • (n+1) concept: One component may fail or be removed to
1
digit after the decimal point. The significance of a long, the extent that “n” components are sufficient for full
uninterrupted phase of operation is obvious, as many functioning (“n+1” items available, “n” items are sufficient).
minor interruptions may impair the work rhythm. Some 2
guidelines can be derived from this: A reliability calculation can be made to quantify the reliabil-
• Preference should be given to high quality of the prod- ity of supply. Using models for the replication of the system
ucts applied
• The number of components used should be kept as small
and the associated reliability characteristics, the weak-
nesses and optimization options in the electric power
3
as possible, since every component must be regarded as distribution grid can be identified. The following models
a potential source of trouble
• Repeated interference and switching operations, in
describing network operation and failure behavior are
known: 4
particular in connection with modularization and load- • Element model
dependent operation, should be avoided • Failure model
• A dependency on single components should be avoided • Resupply model 5
since their failure or switching off such a “single point of • Consumer load model.
failure“ (SPOF) would affect the whole system.
16
17
Intro
duction
1 The factors determining the frequency and duration of Network planning and design
supply interruptions include external influences, technical
condition of the equipment, network planning and design, Given factors such as climatic conditions, geographic
2 product quality, installation and commissioning, as well as structures of the supply area, as well as load and structural
operating conditions and modes of operation. changes have to be considered for the network planning
and design in order to achieve the intended reliability of
3 External influences supply. The following planning criteria must be taken into
account dependent on the probabilities of occurrence and
Supply interruptions can be caused by climatic and atmo- the associated effects of these external influences:
Network configuration
isolation of the equipment, which also involves switchovers It is difficult to design and set protection for complex
in the network. Every switchover in the network involves network configurations such that selective fault tripping is
14 the danger of maloperation, which can lead to supply ensured at any time. Moreover, this requires extensive
interruptions in parts of the network when the network adaptations of the network protection to changes in the
protection responds or equipment is destroyed. network, and the probability of misadjustment (overprotec-
15 tion or undersized protection) increases. The danger of
maloperation or maloperation increases if a large variety of
different makes and product series of protection devices is
16 used. In this case, the product and operational know-how
for the individual device types has to be acquired and kept
up to date.
17
Intro
duction
Cable laying The operator can minimize the risk of defective equipment
1
by carefully selecting the manufacturing companies of the
For cost reasons, cables are often routed in large numbers equipment used, and by influencing the proper execution
in one single duct. In this context, it has to be minded that of installation and commissioning works. 2
in the event of an excavator accident, for example, all
cables in the duct would be destroyed, or if a cable was Network operation
destroyed by short-circuit current, the other cables would
also be affected. To increase the reliability of supply, the Productive and economic working and quick responding in
3
number of cables in a cable duct should be limited. In the event of a failure depend on the organization and
particular, redundant systems should be routed in separate
ducts.
structure of the personnel as well as on the available
documents and documentation on the network.
4
Short-circuit power Documents and documentation
5
High short-circuit power is required to ensure good voltage Precise and always up-to-date documentation of switching
and network stability. However, it must not reach too high states in the network, protection settings, and planning
values, as the equipment in the network has to be dimen-
sioned accordingly and short-circuit currents go with
documents which show the correct position of the equip-
ment in the network and include technical data such as
6
greater mechanical and thermal stress as well as higher cable cross-sections or transmission capacities, is the basis
breaking capacities. of reliable network operation. It allows for quick proceed-
ing in the event of a fault, and thus clearly shortens the
7
Automation supply interruption. For example, maloperation is avoided
in the forefront already by precise instructions in the
The degree of automation of the network has great influ- documentation. 8
ence on the number and, most of all, the duration of
supply interruptions. Even in a medium-voltage grid, the Failure and damage statistics can help to comprehend
automation of the central systems is advantageous with failure causes and processes to a certain extent and to 9
regard to the reliability of supply, despite the variety of render visible weak points or defects in the network. This
equipment and the large amount of data. The implementa- allows for early clearing and an improvement of the reli-
tion of simple network automation helps to avoid maloper-
ation, but requires a simple and clear network configura-
ability of supply.
10
tion. Personnel
Production, installation, and commissioning The number of personnel required for reliable operation 11
largely depends on the size of the network, the technology
Supply interruptions are always attributable to the failure used, and the degree of automation of the network. Apart
of single pieces of equipment. The reasons for a failure can from the number of personnel, also its qualification, i.e., 12
be very different. For example, maloperation or external profound training, technical knowledge, and many years of
influences can lead to the tripping of the protection equip- work experience, plays an important part. Not to be ne-
ment, which in turn can cause the deliberate failure of
equipment (load shedding). The destruction of equipment
glected is the ability to work in a team as well as the coop-
eration of the personnel with external companies.
13
usually leads to its failure. However, the actual failure
cause might already have been implied before operation.
Mistakes in the project planning phase or insufficient
Switching operation
14
quality assurance during the production process may If the network protection settings are incorrect, equipment
increase the probability of equipment failure. Mistakes can may be overloaded or destructed due to maloperation,
also be made during installation and commissioning of the which leads to repair costs and an interruption of supply. 15
equipment, which might only become apparent after a Therefore, switching operation also includes the setting of
longer period of use in the network by failure of the equip- the network protection.
ment. This danger can only be averted by good technical
knowledge of the installation and commissioning personnel.
16
17
Intro
duction
The organization of the fault-clearing service is another The availability of a system is influenced by the quality of
2 important factor influencing the duration of the supply its components (the availability of the individual compo-
interruption. Failure detection and indication depend on nents) on the one hand and redundancy configurations on
the degree of automation. After the failure has been de- the other hand. Generally speaking, redundancy character-
3 tected, the fault-clearing service is responsible for the
immediate evaluation of information in order to take
izes the use of multiple technical resources which are
technically identical or at least functionally identical. In the
circuit-related and organizational actions. following, the ICT terminology is used.
4 To ensure quick fault location, the required personnel must In order to avoid complete failure from system-related
be available upon the occurrence of a fault, which can be faults, so-called "diversified" systems (different technology
consulted on the spot as well as on call for fault repair. or design for the same function) are used in a redundant
5 Moreover, the required vehicles and / or special vehicles manner. Electric power distribution may involve consider-
must be available and immediately operational. ation being given to a very diversified range of redundancy
configurations in planning.
6 After fault localization, it depends on the network configu-
ration to what extent resupply of all consumers is possible Attention: The following differentiation of the redundancy
by disconnecting the fault location and switching over to types may easily lead to mix-ups!
12 Maintenance
15
16
17
Intro
duction
TIP04_13_018_EN
ately, we also refer to this as “hot” redundancy.
Primary UPS
3
In the UPS example of Fig. 5/11, two of the three systems
connected in parallel are sufficient to safely supply the
connected load. In the case of maximum utilization of Fig. 5/10: Schematic illustration of the standby redundancy
4
redundancy, each of the connected UPS systems supplies for a single UPS system back to page 86
two-third of the required power.
5
Generalizing, we speak of an (n+1) redundancy if n items
of equipment are sufficient in parallel operation to ensure Communication link
undisturbed operation, so that one device may fail or be
switched off. Thus, no further redundancy exists then.
UPS 1
50 kVA
for parallel operation
6
UPS 2 100
TIP04_13_019_EN
7
50 kVA kVA
System redundancy
UPS 3
The configuration of two parallel supply systems allows sys- 50 kVA
tem redundancy to be obtained. At the same time, parallel-
ism should be maintained as far as possible down to the 8
load be supplied. Ideally, electric power supply of consum- Fig. 5/11: Parallel-redundant UPS system with
ers is ensured by at least two redundantly usable, separate (n+1) equal to (2+1)
power supply units. 9
Isolated-parallel redundancy
10
50 kVA
50 kVA
50 kVA
UPS 12
UPS 11
UPS 10
50 kVA
50 kVA
UPS 5
UPS 6
15
Fig. 5/12: Isolated-parallel UPS system with a link through two
independent power supply units acc. to (m+1)^(n+1) – here:
(3+1)^(2+1)
16
17
Intro
duction
1 5.4 Reactive Power and Compensation Transmission losses and energy consumption are reduced
and expensive expansions become unnecessary as the
The total power, the so-called apparent power, of a same equipment can be used to transmit more active
2 transmission grid is composed of active and reactive power owing to reactive power compensation.
power (Fig. 5/13). While the power consumers connected
to the grid transform the active power into active energy, Determination of capacitor power
3 the reactive energy pertaining to the reactive power is not
consumed. The reactive power at the consumer side is A system with the installed active power P is to be compen-
merely used for building up a magnetic field, for example, sated from a power factor cos φ1 to a power factor cos φ2.
4 for operating electric motors, pumps, or transformers. The capacitor power necessary for this compensation
7 Solution
Reactive power estimation
11
12
TIP04_13_021_EN
Active power
Apparent power
Reactive power
13
14
15
Magnetic field
16
Grid of the utility Motor Drive
17
Fig. 5/13: Composition of the total power of a transmission grid
Intro
duction
Qc = 0.1 to 0.2 · P 2
20 kV
Calculation of the reactive power based on the
electricity bill 3
For installations which are already running, the required
capacitor power can be determined by measuring. If active
and reactive work meters are available, the demand of 400 V
4
capacitor power can be taken from the monthly electricity
TIP04_13_022_EN
bill.
Iw
M
Ib
5
tan φ = reactive energy / active energy
10
P Q2 Residual reactive power
φ1 after compensation
Qc = Q1 – Q2 = P · F φ2
S2 Apparent power
after compensation
In this case,
TIP04_13_023_EN
Qc Connected
capacitor power 11
F = tan φ1 – tan φ2
To simplify the calculation of Qc, Tab. 5/13 states the Fig. 5/15: Power diagram for a non-compensated (1)
and a compensated (2) installation back to page 88 12
conversion factors F when a measured cos φ1 is to be
compensated in order to attain a power factor cos φ2 in
operation.
13
14
15
16
17
Intro
duction
1 Actual value
Conversion factor F
(given)
tan φ1 cos φ1 cos φ2 cos φ2 cos φ2 cos φ2 cos φ2 cos φ2 cos φ2 cos φ2 cos φ2 cos φ2 cos φ2
2 = 0.70 = 0.75 = 0.80 = 0.82 = 0.85 = 0.87 = 0.90 = 0.92 = 0.95 = 0.97 = 1.00
4.90 0.20 3.88 4.02 4.15 4.20 4.28 4.33 4.41 4.47 4.57 4.65 4.90
3.87 0.25 2.85 2.99 3.12 3.17 3.25 3.31 3.39 3.45 3.54 3.62 3.87
3 3.18 0.30 2.16 2.30 2.43 2.48 2.56 2.61 2.70 2.75 2.85 2.93 3.18
2.68 0.35 1.66 1.79 1.93 1.98 2.06 2.11 2.19 2.25 2.35 2.43 2.68
4
2.29 0.40 1.27 1.41 1.54 1.59 1.67 1.72 1.81 1.87 1.96 2.04 2.29
2.16 0.42 1.14 1.28 1.41 1.46 1.54 1.59 1.68 1.74 1.83 1.91 2.16
2.04 0.44 1.02 1.16 1.29 1.34 1.42 1.47 1.56 1.62 1.71 1.79 2.04
5 1.93
1.83
0.46
0.48
0.91
0.81
1.05
0.95
1.18
1.08
1.23
1.13
1.31
1.21
1.36
1.26
1.45
1.34
1.50
1.40
1.60
1.50
1.68
1.58
1.93
1.83
1.73 0.50 0.71 0.85 0.98 1.03 1.11 1.17 1.25 1.31 1.40 1.48 1.73
6 1.64 0.52 0.62 0.76 0.89 0.94 1.02 1.08 1.16 1.22 1.31 1.39 1,64
1.56 0.54 0.54 0.68 0.81 0.86 0.94 0.99 1.07 1.13 1.23 1.31 1.56
1.48 0.56 0.46 0.60 0.73 0.78 0.86 0.91 1.00 1.05 1.15 1.23 1.48
7 1.40 0.58 0.38 0.52 0.65 0.71 0.78 0.84 0.92 0.98 1.08 1.15 1.40
1.33 0.60 0.31 0.45 0.58 0.64 0.71 0.77 0.85 0.91 1.00 1.08 1.33
8 1.27
1.20
0.62
0.64
0.25
0.18
0.38
0.32
0.52
0.45
0.57
0.50
0.65
0.58
0.70
0.63
0.78
0.72
0.84
0.77
0.94
0.87
1.01
0.95
1.27
1.20
1.14 0.66 0.12 0.26 0.39 0.44 0.52 0.57 0.65 0.71 0.81 0.89 1.14
9 1.08 0.68 0.06 0.20 0.33 0.38 0.46 0.51 0.59 0.65 0.75 0.83 1.08
1.02 0.70 – 0.14 0.27 0.32 0.40 0.45 0.54 0.59 0.69 0.77 1.02
0.96 0.72 0.08 0.21 0.27 0.34 0.40 0.48 0.54 0,63 0.71 0.96
10 0.91 0.74 0.03 0.16 0.21 0.29 0.34 0.42 0.48 0.58 0.66 0.91
0.86 0.76 – 0.11 0.16 0.24 0.29 0.37 0.43 0.53 0.60 0.86
11
0.80 0.78 0.05 0.10 0.18 0.24 0.32 0.38 0.47 0.55 0.80
0.75 0.80 – 0.05 0.13 0.18 0.27 0.32 0.42 0.50 0.75
0.70 0.82 – 0.08 0.13 0.21 0.27 0.37 0.45 0.70
14
0.36 0,94 0.03 0.11 0.36
0.29 0.96 – 0.01 0.29
0.20 0.98 – 0.20
15 Tab. 5/13: Conversion factors F for phase angle adjustments back to page 89
16
17
Intro
duction
7
conditions
Single compensation Compensation close to Large consumers with constant Relief of consumer lines Many small capacitors
the power consumer power demand and long ON and reduction of
times transmission losses
Long feeder lines to consumers
(voltage drop, power reduction)
Saving of the switching
device
Higher costs 8
For example, with single No simultaneity factor
induction motors, welding
transformers, discharge lamps 9
Group compensation Compensation in sub- Consumer groups (for example, Relief of the consumer Single interruptions may
distribution boards motors, lamps with electronic lines lead to
ballast) that are very close overcompensation
10
Concurrent ON / OFF switching Consideration of the Reactive current load on
of consumers and capacitors simultaneity factor the consumer lines
11
possible possible
Reduction of the
capacitor costs
12
Central compensation Compensation in main Systems with constantly Improved utilization of Extra costs for control
switchgear or load changing load and / or ON times the capacitor power
center substations
Further reduction of the Transport of reactive
capacitor costs power from the
switchgear / substation in
the LV grid 13
General reduction of the
network losses
Easier extensibility 14
System control possible
16
17
Intro
duction
1 Single compensation
TIP04_13_024
• Constant power demand
• Long ON times.
5
M
Here, load is taken off the feeder lines to the power con-
Fig. 5/16: Single compensation
sumers; a continuous adjustment of the capacitor power to
6 its reactive power demand is not possible, however.
Group compensation
7 With group compensation, each compensation unit is
assigned to a consumer group. Such a consumer group
may consist of motors or discharge lamps, for example,
8 which are connected into the network together through
a contactor or switching device. In this case, special switch-
ing devices for connecting the capacitors are not re-
9 quired either (Fig. 5/17). Group compensation has the
same advantages and disadvantages as single compensa-
tion.
TIP04_13_025
10 Central compensation M M M
Controller
16
TIP04_13_026_EN
17
Intro
duction
TIP04_13_027_EN
age heaters, street lights, etc.). The latter also functions as Ripple control signal
a transmission path. Control commands are transmitted by
means of pulse sequences in the range of 167 to approx.
2,000 Hz which are superimposed on the voltage with an
3
amplitude of approx. 1 – 8 % of the respective rated line
voltage. The audio frequency (AF) 1 is switched on and off
for transmission following a code (pulse grid), which 4
creates a “telegram”. The consumer to be remote-con- Capacitor
trolled is downstream-connected to a special receiver
5
(control unit)
(ripple control receiver) which filters the pulse telegrams
out of the network and deduces the desired control infor-
Fig. 5/19: Schematic diagram of the compensation in a network
mation from them (Fig. 5/19).
6
with an audio frequency ripple control system
10
ϑ=5 ϑ=7 ϑ = 11.13
5.4.3 Compensation in Networks with M
Harmonic Content
Power converter Filter circuits
In contrast to linear loads such as incandescent lamps,
three-phase motors, or resistance heaters, non-linear loads
TIP04_13_028_EN
11
such as power converters, single-phase, clocked power Fig. 5/20: Choked capacitors for reactive power compensation
supplies, or energy-saving lamps, create distortions of the
line voltage as described in chapter 5.1. The harmonic 12
currents connected with the distortions are forced upon
Choked capacitors
the network and influence other power consumers in the
network.
Together with the inductive loads in the network, the
13
If the proportion of harmonic-generating loads is 15 % and capacitors of the reactive power compensation form a
more (referred to the total load), choked capacitors, tuned resonant circuit as described in chapter 5.4.1. When the
filter circuits, or active filters should be used for compensa- resonance frequency of this resonant circuit coincides with 14
tion. Tuned filter circuits are used in particular in low- a harmonic frequency, this causes a resonance increase of
voltage grids with extremely high harmonic loads. Active the harmonic voltage and thus an increase of the harmonic
filters for filtering harmonic loads provide advantages current. This might lead to a capacitor overload and addi- 15
when hardly any reactive power of the fundamental har- tional loads on the network components and the con-
monics has to be compensated. nected consumers. In order to avoid such resonances, it is
necessary to use choked capacitors (Fig. 5/20).
16
1 The ripple control frequency tables for Germany, Austria, Switzerland, etc. are
17
available at: www.rundsteuerung.de
Intro
duction
TIP04_13_029_EN
4 choke reactance XL and capacitor reactance XC at line
frequency. M
XL
XC
1
5 fres = fN ·
p
Non-linear
loads
Linear
loads
Thyristor-switched
compensation
TIP04_13_030_EN
10 AF > 350 Hz: p = 5.67 %
13 Tuned filter circuits are built from series resonant circuits Fig. 5/22: Choked capacitors with thyristor control
which consist of capacitors with upstream-connected
reactors. These resonant circuits are tuned in such a way
14 that they form resistors for the individual harmonic cur-
rents which are near zero and thus smaller than the resis-
tors of the remaining network. Therefore, the harmonic
15 currents originating from power converters are absorbed
by the filter circuits to a large extent. Only a small rest
flows into the higher-level three-phase system, so that the
16 voltage is hardly distorted and a negative influence on
other power consumers is ruled out (Fig. 5/22).
17
Intro
duction
As filter circuits always represent a capacitive resistance for Active filters can very well compensate low-frequency
1
the fundamental component of the three-phase system, harmonics, for example, harmonics of the 5th, 7th, 11th,
they also absorb a capacitive fundamental current besides and 13th order, but due to the switching pulse of the power
the harmonic currents. At the same time, they thus contrib- electronic devices in the kHz range, no harmonics of the 2
ute to reactive power compensation of the power convert- 50th order (which corresponds to 2,5 kHz) and higher.
ers and other power consumers installed in the network.
Active filters 9
If there are high demands on the power quality or if the
harmonics vary considerably with regard to amplitude and
frequency, active filters should be used. For that, self-
10
commutated, high-frequency switching power converters
are used, mostly with insulated gate bipolar transistors
(IGBTs), which can replicate virtually every current or 11
voltage curve. By constantly feeding in the “negative”
(i.e., phase-shifted by 180 °) harmonic range, the network
is impressed an almost sinusoidal waveform. 12
Attention: Filters must not be installed in the PEN
conductor of installation systems.
13
When the active filter is connected in parallel, a current
spectrum that is phased inversely to the harmonic currents
is generated and added to the consumer current, resulting 14
in an almost sinusoidal line current. Accordingly, with a
series connection, the voltage quality for sensitive consum-
ers that are to be protected is improved. 15
16
17
Intro
duction
1 5.5 Protection Against Lightning define the technically and economically optimal protection
Current and Overvoltage measures described in IEC 62305-3 (VDE 0185-305-3) and
IEC 62305-4 (VDE 0185-305-4). To this end, the property to
2 Overvoltages considerably damage electrical and electronic be protected is subdivided into a (or several) lightning
appliances. This includes even small voltage peaks on the protection zone(s) (LPZ) (see Fig. 5/23). For each LPZ, the
supply line. This can be seen from the damage caused to geometrical borders, relevant characteristics, lightning
3 lines, circuit boards, or switching devices. Such damage
can be prevented with suitable protection measures
threat data, and kinds of damage to be considered are
defined. Starting from the unprotected state of the prop-
against surge currents and overvoltages. erty, the assumed risk is reduced by taking (further)
9 LPZ 0 A
LEMP
LPZ 0 B M
10
LPZ 1
LEMP
Room shield
11 Venti-
lation LPZ 2 Terminal
LPZ 3
LEMP
12 LPZ 0 B
LPZ 2
LPZ 0 B
IT
network
13 SEMP
Equipotential bonding as lightning
protection, lightning arrester
14
Power Local equipotential bonding,
grid surge arrester
TIP04_13_031_EN
17
Intro
duction
Zone 1 (LPZ 1)
lightning protection system in addition to any existing
1
Inside the building, high-energy transients caused by: external lightning protection system.
–– Switching operations (SEMP)
–– Lightning currents. Current splitting, insulating interfaces, and / or surge pro- 2
tection devices (SPD) can limit surge currents in the inter-
nal lightning protection. The electromagnetic field of
Zone 2 (LPZ 2)
lightning can be dampened by way of spatial shielding. The
impulse withstand voltage of the insulating interfaces and
3
Inside the building, low-energy transients caused by:
–– Switching operations (SEMP) the protection level of the SPDs must be coordinated with
–– Electrostatic discharge (ESD) the following overvoltage categories in accordance with
IEC 60664-1 (VDE 0110-1) (see Tab. 5/15). 4
–– An LPZ 2 which is larger than 5 m × 5 m must be
subdivided.
5
Zone 3 (LPZ 3)
Direct lightning
Inside the building:
6
strike into the
–– No generation of transient currents or voltages beyond building structure
the interference limit LPS (lightning
–– Protection and separate installation of circuits that protection system)
could interact 100 % 7
–– An LPZ 3 which is larger than 5 m × 5 m must be 50 %
subdivided. HV Transformer LV cable
In accordance with IEC 62305-4 (VDE 0185-305-4), for a
50 %
8
lightning strike it is usually to be assumed that about 50 %
TIP04_13_032_EN
of the lightning current is discharged into earth via the ex-
ternal lightning protection system (lightning arrester). Up
to 50 % of the remaining lightning current flow into the
Earthing system of
the transformer
Earthing system
of the struck
9
building structure
building via electrically conductive systems such as the
main equipotential bonding conductor (see Fig. 5/24).
Therefore, it is always necessary to install an internal
Fig. 5/24: Current splitting for a balanced lightning protection
system 10
Rated voltage of the power Phase-to-neutral voltage derived from Rated impulse withstand voltage
11
supply system (network) in the rated AC or DC voltage up to and
accordance with IEC 60038 including
(VDE 0175-1)
Overvoltage category
12
Three-phase Single-phase I II III IV
in V in V in V in V in V in V in V 13
50 330 500 800 1,500
100 500 800 1,500 2,500
120 – 240 150 800 1,500 2,500 4,000 14
230 / 400 300 1,500 2,500 4,000 6,000
277 / 480
400 / 690 600 2,500 4,000 6,000 8,000 15
1,000 1,000 4,000 6,000 8,000 12,000
Tab. 5/15: Overvoltage categories and rated impulse withstand voltages in accordance with IEC 60664-1 (VDE 0110-1) 16
17
Intro
duction
1 Overvoltage category IV: Equipment for the use at the The system or device to be protected has to be figured
connecting point of the installation. within a protected area. At all points of intersection “line
– protection circuit”, SPDs are to be installed which corre-
2 Example: Equipment such as electricity meters and primary spond to the rated data of the relevant circuit or interface
overcurrent protection modules. of the device to be protected. Thus, the area within the
protection circuit is protected in such a way that cable-
3 Overvoltage category III: Equipment in stationary installa-
tions and for such cases in which special demands are
bound overvoltage induction is no longer possible. Within
the scope of an efficient and comprehensive protection
made on the reliability and availability of the equipment. concept against overvoltages, the power supply has to be
14 1
2
Lightning arrester
Surge arrester
1
2
4 kV
2.5 kV
Main distribution
Sub-distribution board
3 Device protection 3 1.5 kV before the connected device
16
17
Intro
duction
1
I)
2
5
Type 1 Type 2 Type 3
6
II)
7
10
11
Type 1+2 Type 3
III) 12
13
14
15
TIP04_13_033_EN
Type 2 Type 3
16
Intro
duction
10
11
12
13
14
15
16
17
4 Basic rules well as the selection of the connecting line itself (cable / line
or busbar connection) under consideration of the technical
On principle, circuit dimensioning shall be performed features of the corresponding switching and protection
in compliance with the technical rules / standards listed in devices. For feed-in circuits in particular, dimensioning also
5 Fig. 6/1. Details will be explained below. includes rating the power sources.
Cross-circuit dimensioning Depending on the circuit type, there may be different focal
6 When selected network components and systems are
points of dimensioning, as demonstrated below. The
dimensioning target of overload and short-circuit protec-
matched, a cost-efficient overall system can be designed. tion can be attained in correlation to the mounting location
9
Overload protection IEC 60364-4-43 VDE 0100-430
10
11
IEC 60364-4-43/ VDE 0100-430/
Short-circuit protection
IEC 60364-5-54 VDE 0100-540
12
Protection against electric shock IEC 60364-4-41 VDE 0100-410
13
IEC 60364-5-52 VDE 0100-520
14
Voltage drop
IEC 60038 VDE 0175-1
16
Selectivity IEC 60364-7-718 VDE 0100-718
IEC 60947-2 VDE 0660-101
IEC 60898-1 VDE 0641-11-100
17
Fig. 6/1: Standards for dimensioning protection equipment and routing in circuits
Intro
duction
6.1 Circuit Types and Basic Rules ing the best possible selectivity towards all upstream and
1
downstream devices.
The basic dimensioning rules and standards listed in
chapter 6.1 principally apply to all circuit types. In addition, Distribution circuit 2
there are specific requirements for these circuit types
(see chapter 6.2), which will be explained in detail below. Dimensioning of cable routes and devices follows the
maximum load currents to be expected at this distribution
level. As a rule:
3
Feed-in circuits
Σ installed capacity · simultaneity factor
Particularly high requirements apply to the dimensioning of
feed-in circuits. This starts with the rating of the power
Ibmax =
system voltage
4
sources. Power sources are rated according to the maxi-
mum load current to be expected for the entire network, Switching and protection device and connecting line are to
the desired amount of reserve power, and the degree of be matched with regard to overload and short-circuit 5
reliability of supply required in case of a fault (over- protection. In order to ensure overload protection, you
load / short circuit). must also observe the standardized test currents referring
Intro
duction
10
11 Disconnection Signaling
12
TN system TT system IT system IT system
13
Overcurrent Overcurrent Insulation Insulation
15
devices (RCD) devices (RCD)
Residual current-
In special cases: operated protective
fault-voltage-operated devices (RCD)
TIP04_13_035_EN
protection devices
16 In special cases:
fault-voltage-operated
protection devices
17
Fig. 6/2: Dependency of personal protection on network systems back to page 105
Intro
duction
14
15
16
17
Intro
duction
Electrical installations in a network are protected either Full selectivity is achieved with two series-connected
by protection devices allocated to the different parts of protection devices if, when a fault occurs after the down-
8 the installations or by combinations of these protection stream protection device, only the downstream device
devices. disconnects from supply. A distinction is made between
two types of selectivity:
9 Standby protection • Partial selectivity in accordance with IEC 60947-2
(VDE 660‑101): Overcurrent discrimination of two
When a protection device fails, the higher-level device must series-connected overcurrent protection devices, where
10 take over this protection function. the load-side protection device takes over the full protec-
tion task up to a defined overcurrent level without the
Back-up protection other protection device being active
• Full selectivity according to IEC 60947-2 (VDE 660-101):
11 If a short circuit, which is higher than the rated making and Overcurrent discrimination of two series-connected
breaking capacity of the switching and protection device overcurrent protection devices, where the load-side
used and higher than the short-circuit capacity of all down- protection device takes over the full protection task
12 stream parts of the installation, occurs at a particular point without the other protection device being active
in the network, back-up protection must be ensured by
means of an upstream current-limiting protection device. Note: Full selectivity always refers to the maximum
16
17
Intro
duction
4
• HV HRC fuses (IEC 60282-1; VDE 0670-4) time short circuit
Current-limiting HV HRC fuses can only be used for
short-circuit protection. They do not provide overload
protection. A minimum short-circuit current is, therefore,
required for correct operation. HV HRC fuses restrict the HV HRC fuse Medium-voltage circuit-breaker
with time-overcurrent protection
5
TIP04_13_036_EN
peak short-circuit current. The protection characteristic is
determined by the selected rated current (Fig. 6/3) I
• Medium-voltage circuit-breakers (IEC 62271-100;
VDE 0671-100)
Adjustable characteristic
curves or setting ranges 6
Circuit-breakers assume the protection function by means
Fig. 6/3: Protection characteristic of HV HRC fuse and MV time-
of additional protection devices such as time-overcurrent
protection (definite-time and inverse-time), time-overcur-
overcurrent protection 7
rent protection with additional directional function, or
differential protection. So far, distance protection has
rarely been used in infrastructure and industrial networks inverse-time-delay
8
owing to their low spatial extension
t
• Secondary relays
9
I 2 t = constant
As protection equipment in medium-voltage grids, sec-
I 4 t = constant
ondary relays are used, whose characteristic curves are
also determined by the current transformer ratio. Digital
definite-time-delay
protection devices are increasingly preferred.
I 2 t = constant
10
Low-voltage protection equipment
13
for overload and short-circuit protection, or partial-range curves or setting ranges
fuse for short-circuit protection only) and the rated
current (Fig. 6/4) Fig. 6/4: Protection characteristic of LV HRC fuse and low-voltage
• Low-voltage circuit-breakers (IEC 60947-2; circuit-breaker with releases
VDE 0660‑101) 14
circuit-breakers for power distribution switchboards
–– Current limiting (either current limiting = MCCB:
are basically distinguished as follows:
–– Design (open or compact design)
molded-case circuit-breaker, or not current limiting =
ACB: air circuit-breaker) 15
–– Mounting type (fixed mounting, plug-in,
–– Protection functions (see releases)
withdrawable)
–– Rated current (maximum rated current of the
–– Communication capability (capability to transmit data
to and from the circuit-breaker) 16
circuit-breaker)
–– Utilization category (A or B, see IEC 60947-2;
VDE 0660-101).
17
Intro
duction
The protection function of the circuit-breaker in the power The protection characteristic curve is determined by the
2 distribution grid is determined by the selection of the rated circuit-breaker current as well as the setting and the
appropriate release (see Fig. 6/5). Releases can be divided pickup values of the releases.
into thermal-magnetic trip units (TMTU, previously also • Low-voltage circuit-breaker in accordance with
3 called electromechanical releases) and electronic trip units
(ETU).
IEC 60898-1 (VDE 0641-11-100)
Miniature circuit-breakers (MCBs) can be distinguished by
• Overload protection their method of operation:
Intro
duction
1
t in s Overcurrent release ”L“
L
IrN Standard I2t
1,000
Ir Optional I4t
2
S
Shorttimedelayed
tr
shortcircuit release ”S“
100 Standard tsd
Optional I2t
3
Instantaneous
I
4
10 shortcircuit release ”I“
Ig Standard On
Isd Optional Off
1
N
Neutral conductor protection ”N“
Standard 0.5 –1 • Ir
5
0.1 tg Optional Off
6
tsd
Earthfault release
Ii G
TIP04_13_038_EN
Standard tE
0.01 Optional I2t
7
0.5 1 5 10 50 100
I in kA
8
Fig. 6/5: Variants of tripping curves back to page 108
9
6.2.3 Selectivity Criteria • The highest short-circuit current determines the required
Intro
duction
1 • In principle, the highest short-circuit current can be both Tolerance range of tripping curves
the three-phase and the single-phase short-circuit current
• In the vicinity of the feed-in into the low-voltage grid, the • The tripping curves of circuit-breakers given in the manu-
2 single-phase fault current will be greater than the three- facturer catalogs are usually only average values and
phase fault current if transformers with the Dy connec- must be extended to include tolerance ranges
tion are used • With overcurrent releases – instantaneous (I) and
3 • The single-phase short-circuit current will be the lowest
fault current if the damping zero-sequence impedance of
delayed (S) releases – the tolerance of the tripping
current values may be ± 20 % (according to IEC 60947-2 /
the low-voltage cable is active. VDE 0660 Part 101).
4 Since the selectivity response of switching and protection Decisive tripping times
devices made by different manufacturers is not known,
products supplied by one manufacturer only should be For a better overview, only the delay time tsd is plotted for
5 installed throughout the same installation if the planning circuit-breakers with definite-time-delay overcurrent re-
criterion of "selectivity" is to be fulfilled. With larger installa- leases (S), and only the opening time to for circuit-breakers
tions, it is advisable to determine all short-circuit currents with instantaneous overcurrent releases (I).
6 using a special software. Here, our SIMARIS design dimen-
sioning and calculation software comes as the optimum Grading principle
solution.
12
40
t 20
min 10
6.2.4 Preparing Current-Time Diagrams 4
L (cold)
2
(Grading Diagrams)
13
1
15
ms t st 150 ms
by pre-loading. The selected characteristic curve must 40
20
I
t i < 30 ms
therefore be suitable for the motor or transformer at 10
operating temperature 2
Intro
duction
10
Current I
Short-circuit
Protection
Time setting of the overlaid protection
11
current Grading time tst
time setting
12
Command time tk
Pickup
current
Variation time Variation time Variation time
of protection of circuit-breaker of protection 13
Load current
14
Break
time
Release
time
Safety
margin
15
TIP04_13_040_EN
of circuit-breaker
16
Total break time tg
of circuit-breaker
Intro
duction
11
12
Q3
tö1 opening time of circuit-breaker Q1
L
grading time for circuit-breaker Q2
13
tsd3 tst2
S
tsd3 ≈ tst2 + tst3 tst3 grading time for circuit-breaker Q3
tsd2 delay time for circuit-breaker Q2
tsd3 delay time for circuit-breaker Q3
tst3
14 L
Q2
tsd2
L
S
inverse-time-delayed, Ir
definite-time-delayed, Isd, tsd
S Safety I instantaneous, Ii
tsd2 ≈ tst2
margin
15 tö1
Circuit-breaker response time
Q1 Circuit-breaker time to contact separation
L
16 I Safety
margin
Circuit-breaker arc duration
M
17
Time t TIP04_13_041_EN
3
Switching and protection devices used in MV Switch-disconnectors, Circuit-breakers, instrument
HV HRC fuses transformers, time-
4 overcurrent protection
LV Circuit-breakers or Coupling Circuit-breaker
LV HRC fuses circuit-breakers
5 Medium-voltage side
I> I>
6 HV HRC
HV HRC
HV HRC I >> I>
I >>
I >>
7 protection LV MV
LV
LV LV MV
LV
LV
10
11
12
HV HRC or LV HRC fuse HV HRC or LV HRC fuse Circuit-breaker Circuit-breaker
13
HV HRC or LV HRC fuse Circuit-breaker
I> Definite-time
I > overcurrentDefinite-time
protection, overcurrent protection,
I >> two-level II >>>and I >>, two-level
at current
Definite-time >>, at current transformer
> and Iprotection,
I transformer
overcurrent Withdrawable circuit-breaker
Withdrawable circuit-breaker
I>
I >> two-level I > and I >>, at current transformer (with disconnecting (with disconnecting
point)
Withdrawable circuit-breakerpoint)
Reactive-power control Reactive-power
unit control unit
14
(with disconnecting point)
Reactive-power control unit
TIP04_13_044_EN
Switch-disconnector Contactor
16 Tab. 7/1: Overview of protection grading schemes for transformer and LV feeders
17
114 Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution
Con
tents
Intro
duction
5
overload relay IEC 60947-4-1 / VDE 0660-102
Thermistor motor protection devices IEC 60947-8 / VDE 0660-302 – – ×
× Protection ensured – Protection not ensured
Tab. 7/2: Overcurrent protection devices for cables and lines and their protection task back to page 114 6
10
11
12
13
14
15
16
17
Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution 115
Con
tents
Intro
duction
4 In order to increase the protection effect further, circuit- Selective networks can more easily be designed using
breakers can also be equipped with additional releases, for zero-current interrupters than by upstream protection
example, for disconnecting upon undervoltage, or with devices, since zero-current interrupters can work with a
5 supplementary modules for detecting fault / residual cur- tripping time delay across a wider current range (time
rents. They are distinguished according to their protection selectivity). With current-limiting circuit-breakers, this
task as follows: range covers only up to 10 to 12 times the rated current.
6 • Circuit-breakers for system protection according to
IEC 60947-2 / (VDE 0660-101)
Above that, energy selectivity must considered. High
selectivity values for energy selectivity can only be attained
• Circuit-breakers for motor protection according to by using high-quality and technically complex tripping
7 IEC 60947-2 / (VDE 0660-101)
• Circuit-breakers used in motor starters according to
mechanisms. Tab. 7/3 gives an overview of the overcurrent
protection for low-voltage circuit-breakers.
IEC 60947‑4-1 (VDE 0660-102)
• Miniature circuit-breakers for cable and line protection With regard to the tripping function of circuit-breakers, two
8 according to IEC 60898-1 (VDE 0641-11-100). types, with corresponding current-time characteristics, can
be distinguished:
• Thermal-magnetic trip unit, TMTU
9 • Electronic trip unit (ETU) with adjustable I2t or I4t charac-
teristics.
10
Protection function Code Delay type of the release Symbols according to IEC 60617
11
Schematic symbol or Graphic symbol
Overload protection L Inverse-time delay (electronic
LT with I2t or I4t or thermal
(long time) curve of the bimetal,
12 Selective short-circuit S1)
see Fig. 7/1)
Definite-time delay by time
protection (with delay) ST element or I2t-dependent
I>
(short time) delayed
13
Earth-fault protection G1) Definite-time delay or I2t-
GF dependent delayed I
14
(ground fault)
1) For SENTRON 3WL and 3VA / 3VL circuit-breakers by Siemens also with zone-selective interlocking (ZSI according to IEC / TR 61912-2).
In the following sections, combinations of releases will only be referred to by their codes as L, S, and I releases, etc.
17
116 Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution
Con
tents
Intro
duction
1
TMTU ETU
2
inverse-time
L
3
delay
t thermal
L inverse-time
delay
I2t = constant
5
I4t = constant
inverse-time-
S
6
delay
I2t = constant
7
I definite-time I
instantaneous delay instantaneous 8
I
9
Adjustable characteristic curve ranges or setting ranges
10
TIP04_13_168_EN
11
Typical characteristic curves of circuit-breakers with ETU current IR and time tR can be set. Circuit-breakers with
and TMTU are depicted in Fig. 7/1. The different tripping higher-value ETU allow the choice between I2t and I4t 12
functions are described in the following sections. characteristics. Possible setting ranges are schematized in
Fig. 7/1.
Thermal-magnetic trip units have either fixed or adjustable
settings, whereas the electronic trip units used in Siemens Mechanical (thermal), inverse-time-delayed overload
13
circuit-breakers all have adjustable settings. The overcur- releases are not always suitable for networks with a high
rent releases can either be integrated in the circuit-breaker harmonic content. Circuit-breakers with electronic trip
or supplied as separate modules for retrofitting or replace- units must be used in such cases. 14
ment. For exceptions, please refer to the manufacturers'
specifications.
15
Overload protection with long-time delay (L) release
Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution 117
Con
tents
Intro
duction
in mind that the circuit-breakers are designed for a specific The rated operating voltage Ue of a circuit-breaker is the
maximum permissible thermal and dynamic load. If the voltage value to which the rated short-circuit making and
9 time delay causes this load limit to be exceeded in the breaking capacities and the short-circuit performance
event of a short circuit, an instantaneous release (I) must category refer.
also be used to ensure that the circuit-breaker is discon-
10 nected instantaneously in case of very high short-circuit
currents (Fig. 7/2). The information supplied by the manu-
The following must be specified to characterize the require-
ments placed on a circuit-breaker as short-circuit protection
facturer should be consulted when selecting an appropriate device (SCPD):
trip unit. Optionally, an I2t characteristic can be used for
11 the S release of an ETU. The electromagnetic I releases of a Rated short-circuit making capacity Icm1)
TMTU can be set.
The rated short-circuit making capacity characterizes the
12 Reclosing lockout after short-circuit tripping current which an open circuit-breaker is capable of making
at a voltage which corresponds to the rated voltage. It is
Some circuit-breakers can be fitted with a mechanical expressed as the maximum peak value of the solid current.
13 and / or electrical reclosing lockout. It prevents reclosing to
the short circuit after tripping on this fault. Only if the fault
The following applies to Icm for alternating voltage:
was cleared and the lockout was unlatched manually, the Icm ≥ n ∙ Icu (with n from Tab. 7/4)
circuit-breaker can be closed again.
14 For direct voltage:
118 Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution
Con
tents
Intro
duction
Short-circuit Power factor Minimum value for n: Rated current Rated short-time withstand current Icw
1
breaking capacity cos φ Short-circuit In in A Minimum values
Icu
2
making capacity In ≤ 2,500 12 · In, but at least 5 kA
(r.m.s.value in kA) n= ––––––––––––––––––––
Short-circuit 30 kA
In > 2,500
breaking capacity
Tab. 7/5: Minimum requirement for circuit-breakers with regard to
3
4.5 < Icu ≤ 6 0.7 1.5
rated short-time withstand current
6 < Icu ≤ 10 0.5 1.7
10 < Icu ≤ 20 0.3 2.0
20 < Icu ≤ 50 0.25 2.1
4
50 < Icu 0.2 2.2
Rated short-circuit breaking capacity short-circuit release with time delay. According to
6
IEC 60947-2 (VDE 0660-101), Icw must observe the mini-
The short-circuit breaking performance of the circuit-
breaker is verified in accordance with IEC 60947-2
mum values of Tab. 7/5. In product data, the tcw value
for the short-time delay for an Icw value must always be
7
(VDE 0660-101) and can be characterized by two values: indicated.
• Rated ultimate short-circuit breaking capacity (Icu)
test sequence III (operating sequence: O – t – CO with Let-through values 8
O = open, t = time, CO = closing and opening):
–– Verification of overload release (test current = twice For zero-current interrupters, the let-through current ID of
the current set value) the circuit-breaker is equal to the solid short-circuit current.
The current-limiting circuit-breaker reaches the let-through
9
–– Testing of ultimate short-circuit breaking capacity
–– Verification of dielectric strength current as the maximum momentary value while breaking,
–– Verification of tripping on overload
dependent on the solid short-circuit current. The short-
circuit release shall trip within a limit range of ± 20 % of the
10
(test current = 2.5-fold current set value)
set trip value. The manufacturer usually provides character-
Test sequence V applies to circuit-breakers with inte-
istic curves for the different tripping times.
grated fuse (see IEC 60947-2, VDE 0660-101)
11
• Rated service short-circuit breaking capacity (Icu) The Joule integral (I2t while breaking) is referred to as
test sequence II (operating sequence: O – t – CO – t – CO let-through energy. With increasing current, the let-
with O = open, t = time, CO = closing and opening): through energy of the circuit-breaker also rises. In analogy 12
–– Testing of service short-circuit breaking capacity to the let-through current, the let-through energy of a
–– Verification of operating performance current-limiting circuit-breaker is significantly lower than
–– Verification of dielectric strength for the sine halfwave with solid short-circuit current.
13
–– Verification of temperature rise
–– Verification of tripping on overload Rated circuit-breaker currents
(test current = 1.45-fold current set value,
all phases in series or with 3-phase current).
The rated current In of circuit-breakers corresponds to 14
the rated continuous current Iu from IEC 60947-1
(VDE 0660‑100) and is equal to the conventional free-air
Rated short-time withstand current Icw thermal current Ith. The conventional enclosed thermal 15
current Ithe must be specified if it deviates from the rated
The rated short-time withstand current characterizes the current.
permissible thermal fault withstand capability. The device
can carry the specified r.m.s. value of the short-time cur-
16
rent under the test conditions IEC 60947-2 (VDE 0660‑101)
for a given period of time tcw without getting harmed. To
do so, the circuit-breaker must be equipped with a 17
Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution 119
Con
tents
Intro
duction
1 7.2 Fuses
LV HRC (low-voltage high-rupturing-capacity) fuses have a Functional category g (full-range fuses)
2 high short-circuit breaking capacity. They fuse quickly to
limit the short-circuit current. The protection characteristic Functional category g applies to full-range fuses which can
is given by the selection of the utilization category (see interrupt currents from the minimum fusing current up to
3 “Type” in Tab. 7/6). the rated short-circuit breaking current.
8 Classification of LV HRC fuses and comparison of IB Operational current of the circuit
characteristic curves of gG and aM utilization categories IZ Continuous current-carrying capacity of the line
In Rated current of the protection device
9 LV HRC fuses are divided into breaking range (functional (here: fuse)
categories) and utilization categories according to their I2 Current for effective disconnection by the protection
type. They can continuously carry currents up to their rated device within the fixed time
10 current. (conventional fusing current, now If).
11
Type Application (characteristic curve) Breaking Rated voltage V AC Maximum operational
range voltage V AC
15
(back-up)
gR, gS Protection of semiconductor components Full range 230 / 400 / 500 / 690 / 1,000 V 2) 253 / 440 / 550 / 725 / 1,100 V 1)
and lines
gU Full-range fuses for line protection Full range 230 / 400 / 500 / 690 / 1,000 V 253 / 440 / 550 / 725 / 1,100 V
16 gL, gF, gI, gII Previous line protection fuses Full range
(replaced by gG)
1) In North American networks: maximum operational voltage = rated voltage 2) Application-related rated voltages are possible
17 Tab. 7/6: Classification of LV HRC fuses based on their functional characteristics defined in IEC / TR 60269-5 (VDE 0636-5)
120 Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution
Con
tents
Intro
duction
11
ts 103
A
Circuit-
breaker 13
100
A
10-1
Ik 14
I Icu Ik
10-2 15
TIP04_13_043_EN
I
8 Response L release I release Fuse
10-3
4 102 103 104 5
Disconnection Circuit-breaker Fuse + 16
circuit-breaker
I in A
Fig. 7/3: Comparison of characteristic curves pertaining to LV HRC Fig. 7/4: Switchgear assembly comprising fuse and circuit-breaker 17
fuses of utilization categories gG and aM (rated current 200 A)
Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution 121
Con
tents
Intro
duction
1 be selected such that its let-through current ID is less than • Coordination type 2: The overload relay must not be dam-
the rated ultimate short-circuit breaking capacity Icu of the aged. Contact welding at the contactor is, however,
circuit-breaker. permissible, given the contacts can easily be separated or
2 the contactor can easily be replaced.
Fuse, contactor, and thermal inverse-time-delayed
overload relay Protection and operating ranges of equipment
3 The switchgear assembly comprising contactor and over-
load relay is referred to as a motor starter or, if a three- Grading diagram for a motor starter
11
1 Tripping curve of (thermal)
12 t
Module with
LV HRC fuse,
inverse-time-delayed
overload relay
contactor 2 Destruction curve
and thermal of thermal overload relay
13 1
overload relay
(motor starter)
3 Rated breaking capacity
of contactor
1 min 4 Characteristic curve of contactor
for easily separable contact welding
14
2
5 Pre-arcing time-current
characteristic curve of the fuse,
B utilization category aM
A 4 (dependent on 6 Total clearing time curve
15 current limiting
performed by fuse)
of fuse, category aM
TIP04_13_045_EN
16 3 C
6
A, B, C Safety margins
in case of proper
short-circuit protection
1 ms
I
17
Fig. 7/5: Switchgear assembly comprising fuse, contactor, and thermal inverse-time-delayed overload relay
122 Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution
Con
tents
Intro
duction
Protection of contactor 5
In order to protect the contactor against excessively high
breaking currents, the pre-arcing time-current characteristic
of the fuse as of the current value corresponding to the
6
breaking capacity of the contactor (3) must lie in margin B
below the tripping curve of the overload relay (1).
7
In order to protect the contactor against contact welding,
time-current characteristics, up to which load currents can
be applied, can be specified for each contactor, resulting in 8
• No welding or
• Easily separable contact welding
(characteristic curve 4 in Fig. 7/5). 9
In both cases, the fuse must therefore respond in good
time. The total clearing time curve of the fuse (6) must
lie in margin C below the characteristic curve of the
10
contactor for easily separable contact welding (4)
(total clearing time = pre-arcing time + extinction time).
11
12
13
14
15
16
17
Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution 123
Con
tents
Intro
duction
TIP04_13_047_EN
with LI release
current is thereby detected by two series-connected inter-
11
U Ue
UB(1+2)
UB1
12
t
13
TIP04_13_048_EN
124 Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution
Con
tents
Intro
duction
TIP04_13_049_EN
Overload protection is provided by the overload relay in
conjunction with the contactor, while short-circuit protec-
tion is provided by the starter circuit-breaker (“starter
protector”). The pickup current of its I release is set as low
as the making operation will permit, in order to include low
I 6
short-circuit currents in the instantaneous breaking range 1 Rated breaking capacity L Characteristic curve
7
as well (Fig. 7/9). The advantage of this switchgear assem- of contactor of inverse-time-delayed
2 Rated making capacity overload release
bly is that it is possible to determine whether the fault was
of contactor I Characteristic curve
an overload or a short circuit, depending on whether the of instantaneous
3 Characteristic curve of
contactor, triggered by the overload relay, or the starter
8
contactor for easily separable electromagnetic
circuit-breaker has opened. Further advantages of the contact welding overload release
starter circuit-breaker following short-circuit tripping are Icu Rated ultimate short-circuit
breaking capacity of
three-phase circuit disconnection and immediate readiness
9
circuit-breaker
for reclosing. Switchgear assemblies with starter circuit-
breakers are becoming increasingly important in control
units without fuses. Fig. 7/8: Switchgear assembly comprising circuit-breaker and
contactor
10
Circuit-breaker
11
with I release
t for starter assemblies
L
Contactor 12
Inverse-time-delayed
overload relay
I
with L release
13
Setting range
Icu
14
TIP04_13_050_EN
16
L Characteristic curve of I Characteristic curve of
(thermal) inverse time- adjustable instantaneous
delayed overload relay overcurrent release
Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution 125
Con
tents
Intro
duction
4 • Restricted cooling
• Higher ambient temperature.
Motors with thermally critical rotors
10
11
a) b) c) d)
12
Fuse Fuse
Circuit-breakers Circuit-breakers Circuit-breaker
with L and I releases with L and I releases with I releases
14 Thermistor
motor protection
Thermistor
motor protection
Thermistor
motor protection
Thermistor
motor protection
TIP04_13_051_EN
M M M M
15 +ϑ +ϑ +ϑ +ϑ
16
Fig. 7/10: Switchgear assembly comprising thermistor motor protection plus additional overload relay or release
17
(schematic diagram)
126 Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution
Con
tents
Intro
duction
4
other solution. ID
cosφ 0.7
TIP04_13_052_EN
The following should be taken into consideration when 1
comparing the protection characteristics of fuses and 1 10 22 100
circuit-breakers:
• The rated short-circuit breaking capacity, which can vary
Short-circuit current Ik in kA
6
ID Let-through current For example, for Ik = 10 kA:
considerably
ip Peak short-circuit current ID (fuse 100 A) = 7.5 kA
• The level of current limiting, which is always higher with
fuses of up to 400 A than for current-limiting circuit-
ID (circuit-breaker) = 8 kA 7
breakers with the same rated current
• The shape of the pre-arcing time-current characteristics
of fuses and the tripping curves of circuit-breakers Fig. 7/11: Current-limiting characteristics of circuit-breakers (63 A)
and LV HRC fuses (63 A or 100 A)
8
• The disconnection conditions according to IEC 60364-4-41
(VDE 0100-410).
9
Comparison of current-limiting characteristics of LV HRC
fuses and circuit-breakers
Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution 127
Con
tents
Intro
duction
1 • Limit current range (1) Selecting circuit-breakers for circuits with and
The typical test range for fuse currents (A) is, for exam- without fuses
ple, between 1.25 and 1.6 times the rated current, while
2 the test range for the limit tripping currents of the over- Circuits and control units can be designed with or without
load release (B) is between 1.05 and 1.2 times the cur- fuses.
rent setting. The adjustable overload release allows for
3 the current setting and, therefore, the limit tripping
current to be matched more closely to the continuous
Circuits with fuses (fuse-protected design)
current-carrying capacity of the equipment to be pro- The standard design with fuses intended for system protection
14
15
16
17
128 Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution
Con
tents
Intro
duction
Maintenance expense No
f (no. of switching operations 6
and condition)
Selectivity No expense Extra expense required
Replaceability Yes 5) If the same make 7
Short-circuit protection:
Line Very good Good
Motor Very good Good
8
Overload protection:
Line Sufficient Good
Motor Not possible Good
1) Type of construction may be: arc-quenching method, short-circuit strength owing to specific resistance, constructive design 9
2) For example, by means of shock-hazard protected fuse-switch-disconnectors with high-speed closing
3) By means of fuse monitoring and associated circuit-breaker
10
4) By means of fuse monitoring
5) Due to standardization
Tab. 7/7: Test range limits for the tripping performance of protection devices (f(…) denotes a functional dependence of the characteristic
on the quantities and parameters in brackets) back to page 128
11
12
13
14
15
16
17
Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution 129
Con
tents
Intro
duction
2
Fuse
Circuit-breaker
3
Contactor
Protected items
and switching
frequency Overload
protection
4 Thermistor motor
protection M M M M
M M
3~ 3~
5 +ϑ +ϑ +ϑ +ϑ
Overload protection
– Line + + + + + + + + + +
9 Circuit-breaker
Contactor
Protected items
10 and switching
frequency
Overload
protection
Thermistor /
11 SIMOCODE motor
protection
M
3~
M
3~
M M M
3~
M
+ϑ +ϑ +ϑ
12 Overload protection
– Line + + + + + + + + + + +
– Motors (with thermally critical stators) + + 1) + + + + + + + + 1) + +
– Motors (with thermally critical rotors) + + 1) + + + + + + + + 1) + +
13 Short-circuit protection
– Line + + + + + + + + + + + +
– Motor + + + + + + + + + + + +
14 Switching frequency
1)
+ + +
Protection with minor restriction in the event of a phase failure + + very good + good – minor
+ – –
Tab. 7/8: Comparison between the protection characteristics of switchgear assemblies (schematic diagrams) back to page 128
15
16
17
130 Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution
Con
tents
Intro
duction
Fixed setting
Fixed setting
Adjustable
Adjustable
Adjustable
3
Fuse
No. Type of circuit-breaker Tripping curve 1)
S
L
I
Feed-in circuit-breaker
1 Circuit-breaker for ≥ Ik1 × – × – × 4
1 system protection with Icu
selectivity requirement t
Ik1
Ik1 I
5
6
Distribution circuit-breaker
2 Fuse for system ≥ Ik2 – – – – – ×
2 protection Icu
t
Ik2 Ik2
Ik2 I
7
Ik2
8
Load circuit-breaker
3 Fuse and circuit- ≥ Ik3 – – – – – ×
breaker for motor ≤ Ik3 × – – × – – Icu
protection t
Ik3 I
9
3 4 5
14
15
16
17
Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution 131
Con
tents
Intro
duction
Fixed setting
Fixed setting
Adjustable
Adjustable
Adjustable
3
No. Type of circuit-breaker Tripping curve 1)
S
L
I
Feed-in circuit-breaker
4 1 Circuit-breaker for system ≥ Ik1 × – × – ×
protection with selectivity Icu
requirement t
5 1
Ik1 I
Ik1
6
Distribution circuit-breaker
22) Circuit-breaker for system ≥ Ik2 – × – × –
protection without Or Icu
selectivity requirement × – – × – t
7 2 3 × –
Or
– – ×
Ik2 I
8
Ik2 Ik2 3 Circuit-breaker for system ≥ Ik2 × – × – ×
protection with selectivity Icu
requirement t
9 Ik2 I
Load circuit-breaker
11 Ik3 I
4 5
5 Circuit-breaker and ≥ Ik3 – – – × –
Ik3 Ik3 direct-on-line starter for ≥ Ik3 × – – – – Icu
12 motor protection t
M M
3~ 3~ Ik3 I
Tab. 7/10: Power distribution with circuit-breakers without fuses back to page 128
14
15
16
17
132 Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution
Con
tents
Intro
duction
Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution 133
Con
tents
Intro
duction
1 • Combined terminals for simultaneous connection of value. If a certain threshold is exceeded in the event of a
busbars and connecting cables short circuit, however, an electromagnetic overcurrent
• Main switch quality in accordance with IEC 60204-1 release instantaneously trips. The tripping range (time-cur-
2 (VDE 0113-1) rent threshold zone) of the MCBs, following IEC 60898-1
• Separate switch position indicator. (VDE 0641-11-100), is determined by the parameters I1 to
I5 (see Fig. 7/13). Parameters IB and Iz of the line are cor-
3 Alternating-current type MCBs are suitable for all single-
phase and three-phase systems up to a rated voltage of
related to the above.
240 / 415 V and all DC systems up to 60 V (1-phase) and The tripping conditions of the MCBs for characteristics B, C,
8 1st condition 2nd condition IB Operational current to be expected, i.e., current drawn
IB ≤ I n ≤ I z I2 ≤ 1.45 · Iz by the power consumer under normal operating conditions
IB Iz
9 Iz Permissible continuous load current for a conductor,
when the maximum continuously applied temperature
I of the insulation is not exceeded
In I2 1.45 · Iz
10
1,45 · Iz Maximum permissible overload current of limited duration,
Time t
at which a sudden, temporary exceeding of the maximum
Int It continuously applied temperature does not yet result
I1 I2 in a safety-relevant reduction of insulation properties
12 I3
Int Specified non-tripping current (previously conventional
non-fusing current I1), meaning the current which
does not result in disconnection under defined conditions
14 I3
I3 Tolerances narrowed down for tripping time:
1 s ≤ t ≤ 60 s at I = 2,55 ∙ In (≤ 32 A)
1 s ≤ t ≤ 120 s at I = 2,55 ∙ In (> 32 A)
15
I4 Withstand current of the instantaneous electromagnetic
overcurrent release (short-circuit release)
I
17
Fig. 7/13: Schematic reference value diagram of lines and their protection devices
134 Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution
Con
tents
Intro
duction
Resulting from this, an assignment of rated currents for This has to be taken into account in particular for an instal- 4
MCBs to conductor cross-sections can be given (Tab. 7/11), lation in hot rooms, in encapsulated distribution boards
related to an ambient temperature of + 30 °C, as it is con- where, owing to the current-induced heat losses of the
sidered appropriate in IEC 60364-4-43 (VDE 0100-430), built-in devices, higher temperatures may prevail, and for 5
and in relation to the type of installation and accumulation. distribution boards installed outdoors. MCBs can be used at
temperatures ranging from –25 °C to +55 °C. The relative
Example: flat webbed cable, multi-strand cable, on or
in the wall, installation type C 1) at + 30 ºC ambient
humidity may be 95 %. 6
temperature Resistance to climate
Siemens MCBs are available with the tripping characteris- Siemens miniature circuit-breakers are resistant to climate
7
tics B, C, and D, bearing, inter alia, the VDE mark based in accordance with IEC 60068-2-30. They were successfully
upon the CCA procedure (CENELEC Certification Agree- tested in six climatic cycles.
ment). 8
All tripping characteristics are depicted in Fig. 7/14. Due to
9
300 MCB tripping characteristics B, C, D according
the position of the tripping bands, the following applies to IEC 60898-1 / VDE 0641-11-100
from curve A to D: I1 I2
A1) B C D
Time t
12
10
Rated cross- Iz (line) 5
Rated MCB current In permissible continuous 2)
13
section qn
for protection of load current in case of
I3
Seconds
2 3 2 3 1
conductors conductors conductors conductors
under load under load under load under load
14
0.4
in mm2 in A in A in A in A A B C D
4 32 32 36 32 15
6 40 40 46 41 0.01
1 2 3 4 6 8 10 20 30 40 60 80 100
16
10 63 50 63 57
Multiple of rated current In
16 80 63 85 76 1) Meets the requirements of IEC 60364-4-41/ VDE 0100-410
25 100 80 112 96 2) Disconnecting condition acc. to IEC 60364-4-41/ VDE 0100-410
17
for TN systems with Un = 400 V
35 125 100 138 119
Tab. 7/11: MCB and conductor cross-section matrix Fig. 7/14: Time-current limit ranges of MCBs
Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution 135
Con
tents
Intro
duction
1 Degree of protection refers to the I2t characteristic to describe the MCB in gen-
eral terms.
As MCBs are mainly installed in distribution boards, their
2 degree of protection must meet the requirements of the In Germany, the Technical Connection Conditions (TCC) of
respective type of environment. MCBs without an encapsu- the German distribution system operators (DSO) apply. TCC
lation can reach IP30 according to IEC 60529 (VDE 0470-1) stipulates for residential and commercial buildings that
3 provided that they have adequate terminal covers. MCBs
can be equipped with a snap-on fixing for rapid fitting on
only energy limitation class 3 MCBs with a rated short-
circuit capacity of at least 6,000 A be used in distribution
35-mm wide DIN rails. Some versions may additionally be boards connected downstream from the electricity meter,
4 screwed on mounting plates. since the service fuse per residential unit is always ≤ 63 A,
thus ensuring back-up protection.
Installation
Devices must be labelled 6000 .
5 Moreover, some type series are available with a rapid 3
wiring system for manual handling without the use of
tools, which even enables the removal of individual MCBs Selectivity
6 from the busbar system.
Selectivity means that only that protection device will trip
Rated short-circuit capacity Icn in the event of a fault which is closest to the fault location
to upstream fuses, energy limitation can be considered If the short-circuit current exceeds the rated MCB switching
according to the I2t characteristic. Tab. 7/12 lists the I2t capacity at the point where the MCB is installed, another
12 values of energy limitation class 3 for type B and C minia- short-circuit protecting device has to be connected up-
ture circuit-breakers up to a rated current of 63 A, which stream. Without impairing the operability of the MCB in
are permitted in Europe. The basis is amendment A13 of such cases, the switching capacity of such a combination
13 the EN 60898-1 (VDE 0641-1 / A13) standard. IEC 60898-1
does not mention an energy limitation class, and only
will be increased up to 50 kA.
14
Rated short-circuit capacity Permissible I2t values for MCBs (energy limitation class 3) in A2s
in A
In ≤ 16 A In = 20, 25, 32 A In = 40 A In = 50, 63 A
15 Type B Type C Type B Type C Type B Type C Type B Type C
3,000 15,000 17,000 18,000 20,000 21,600 24,000 28,000 30,000
16 4,500
6,000
25,000
35,000
28,000
40,000
32,000
45,000
37,000
52,000
38,400
54,000
45,000
63,000
48,000
65,000
55,000
75,000
10,000 70,000 80,000 90,000 100,000 108,000 120,000 135,000 145,000
136 Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution
Con
tents
Intro
duction
www.siemens.com/sios 5
For searching, please enter:
Back-up_and_protection_tables 3VA
6
10
Transformer Permisssible I2t value of 1.5 mm2 line
11
I2t in A2s
DIAZED 50 A 1 2 3
Fuse
MCB
B 16
12
104
13
Ik i
Ieff
I in A
14
TIP04_13_056_EN
15
B 16 3 2 1 Sine half-wave
103
0 5 10 10-1 0.3 0.6 1 3 6 101
t in ms Ik in kA 16
Fig. 7/15: Selectivity of MCBs with energy limitation classes 1, 2, and 3 towards back-up fuses (curve B16 applies to Siemens MCB 16 A, 17
tripping characteristic B) back to page 136
Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution 137
Con
tents
Intro
duction
138 Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution
Con
tents
Intro
duction
TIP04_13_057_EN
tions when current-limiting protection equipment is used.
The measurements can, however, be very costly and com- ts in s
200 A
plicated, which is why many manufacturers publish selec-
3
(160) 100 A 200 A
tivity tables for their switchgear. For low-voltage protection size 00 size 1
Ik=1,300 A
devices from Siemens – circuit-breakers, motor protecting
switches, miniature circuit-breakers, and fuses –, the latest 1.4
selectivity tables can be downloaded electronically via the
website of the Siemens Industry Online Support:
50 A 50 A 100 A
Ik = 0.03
1.37 s 4
1,300 A
www.siemens.com/sios
K1 101 102 103
1.3
10 4 5
For searching, please enter: I in A
www.siemens.com/tip-cs
8
If SIMARIS design is used, the software automatically takes
all these criteria for Siemens products into account.
Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution 139
Con
tents
Intro
duction
1 Selectivity between series-connected circuit-breakers • Current grading with differently set I releases:
The rated currents, and therefore the I release values of
The different releases of circuit-breakers allow to attain the upstream and downstream circuit-breakers, differ
2 selectivity by proceeding in different ways when grading: accordingly
• Current selectivity • 5-second disconnecting and line-protection conditions:
• Dynamic selectivity (energy selectivity) In consideration of the 5-second disconnecting condition
3 • Time selectivity
• Time-reduced selectivity control for zone-selective inter-
specified in IEC 60364-4-41 (VDE 0100-410) or the
5-second line-protection condition specified in
locking (ZSI). IEC 60364‑4-43 (VDE 0100-430) (if line protection cannot
9
Opening time t in s
Sr = 400 kVA 10 4
10 at 400 V,
50 Hz
102
Q2 Q1
I II
min.
103
11
ukr = 4 % 101
Ir = 577 A
Ik = 15 kA
Ie = 600 A 102
(L release)
12
10 0
Q2
Ie = 4,000 A
Ik = 10 kA L L
(I release)
101
13 II
10 0
Ie = 60 A
(L release)
Q1 I I
14 5.0 kA Ie = 720 A
(I release) 10 -1
I
TIP04_13_058_EN
15 2.1 kA
M
10 -2
3~ 4
5 102 2 5 103 2 5 10 4 2 5
17
Q2 Circuit-breaker (zero-current interrupter)
Fig. 7/17: Current selectivity for two series-connected circuit-breakers at different short-circuit current levels (example)
140 Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution
Con
tents
Intro
duction
Selectivity through circuit-breaker coordination Time grading with virtually identical short-circuit currents
1
(dynamic selectivity)
The upstream circuit-breaker is equipped with shor-time-
With high-speed processes, for example, in the event of a delayed overcurrent releases (S) so that, if a fault occurs, 2
short circuit, and the interaction of series-connected pro- only the downstream circuit-breaker disconnects the
tection devices, the dynamic processes in the circuit and in affected part of the installation from the network. Time
the electromechanical releases have a considerable effect
on selectivity behavior, particularly if current limiters are
grading can be implemented to safeguard selectivity if the
short-circuit currents at the mounting location are almost
3
used. Selectivity is also achieved if the downstream identical. This requires grading of both the tripping delays
current-limiting protection device disconnects so quickly
that, although the let-through current does momentarily
and the pickup currents of the overcurrent releases.
4
exceed the pickup value of the upstream protection device, The example, of Fig. 7/18 shows the single-line diagram
the “mechanically slow” release does not have time to with four series-connected circuit-breakers and the associ-
unlatch. The let-through current is dependent on the ated grading times for selective short-circuit protection. 5
prospective short-circuit current and the current-limiting The necessary grading time, which considers all tolerances,
properties. depends on the operating principle of the release and the
type of circuit-breaker. 6
Selectivity limits of two series-connected circuit-breakers
Fig. 7/18: Required delay time settings for S releases for selective 17
short-circuit protection
Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution 141
Con
tents
Intro
duction
10
Sn = 1,000 kVA Opening time t in s
at 400 V, 10 4
50 Hz
ukr = 6 %
11 In = 1,445 A
Ik = 24.1 kA
103
Q1 Q2 Q3
12 Q3
tsd3 = 200 ms
Ii (20 kA)
102
L L L
Main
13 distribution 101
board
tsd2 = 100 ms
Q2 S S
14
10 0
tsd3 =
Sub- Ik = 17 kA tsd2 = 200 ms
distribution 100 ms
board
15
10 -1
TIP04_13_060_EN
Q1
I
Ik = 10 kA 10 -2
16 M
~
102 2 5 103 2 5 10 4 2 5 10 5
Current I in A
17 Fig. 7/19: Selectivity between three series-connected circuit-breakers with limitation of short-circuit stress by means of an additional
I release in circuit-breaker Q3
142 Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution
Con
tents
Intro
duction
TIP04_13_062_EN
I
In the overload range up to the pickup current Ii of the
instantaneous overcurrent release, partial selectivity is Overcurrent limit
Ii I
5
achieved if the upper tolerance band of the characteristic
curve of the fuse does not touch the tripping curve of the F1 Fuse
fully preloaded, thermally delayed overload release (L). Q1 Circuit-breaker
L Inverse-time-delayed overcurrent release
6
When the circuit-breakers work at "operating temperature", I Instantaneous electromagnetic overcurrent release
a reduction of the tripping time of up to 25 % must be
considered unless specified otherwise by the manufacturer.
Ii Pickup current of I release
The time-current characteristics (scatter bands) do not touch 7
Fig. 7/21: Selectivity between circuit-breaker and downstream fuse
in the overload range back to page 144 8
Opening time t in s 9
10 4
tsd = 200 ms
TIP04_13_061_EN
A t ZSI = 50 ms
10
Q5 E
103 Q1/Q2/Q4 Q3 Q5
K2
102 11
A tsd = 100 ms A
Q3 E t ZSI = 50 ms Q4 E
tsd = 10 ms 101 12
t ZSI = 50 ms
tsd = 200 ms
M
A
3~
t i = 10 ms
10 0 tsd = 100 ms
t ZSI 13
Q1 E Q2
t i = 10 ms
14
t ZSI = 50 ms 10 -1
Icu
K1
M M ti =
3~ 3~ 10 -2
15
10 ms
Fig. 7/20: Schematic diagram of the zone-selective interlocking (ZSI) of series- or parallel-connected circuit-breakers back to page 142 17
Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution 143
Con
tents
Intro
duction
1 Full selectivity is given using circuit-breakers without Selectivity between fuse and downstream
short-time-delayed overcurrent releases (S releases) if the circuit‑breaker
let-through current ID of the fuse does not reach the pickup
2 current of the instantaneous overcurrent release. This is,
Selectivity conditions in the overload range
however, only to be expected for a fuse whose rated
current is very low compared to the rated continuous In order to achieve selectivity in the overload range, a
3 current of the circuit-breaker (Fig. 7/21). safety margin of tA ≥ 1 s is commonly required between the
lower tolerance band of the fuse and the characteristic curve
Selectivity between LS releases and fuses with relatively of the inverse-time-delayed overload release (Fig. 7/23).
10 F1 Q1 Q1 F1
11 L Q1 t t
S L F1
L
tA ≥ 1 s
12
S tA ≥ 100 ms
L Q1 I
F1
13 I
TIP04_13_063_EN
TIP04_13_064_EN
ts tsd
Ik I
14
Isd I Ii I
Overload limit
L Overload release
S Short-time-delayed overcurrent release
F1 Fuse
15 tA
Isd
Safety margin
Operational current of the S release
Q1 Circuit-breaker
L Inverse-time-delayed overload release
ts Pre-arcing time of the fuse
I Instantaneous electromagnetic overcurrent release
tsd Delay time of the S release
16 tA
Ii
Safety margin
Operational current of the I release
The time-current characteristics (scatter bands) do not touch
17 Fig. 7/22: Selectivity between circuit-breaker with LS release and Fig. 7/23: Selectivity between fuse and downstream circuit-breaker
downstream fuse for short-circuit protection for the overload range
144 Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution
Con
tents
Intro
duction
Selectivity conditions in the short-circuit range ing feeder at the busbar center and feeding lines of equal
1
length – each carry only half this current, i.e., ≤ 10 kA.
A reliable and usually relatively high selectivity limit for the
short-circuit range can be determined in the I2t diagram. 2
Here, the maximum value of the let-through I2t value of Additional current selectivity with parallel
the circuit-breaker is compared to the minimum value of transformer operation
the pre-arcing I2t value of the fuse (Fig. 7/24). Since these
values are maximum and minimum values, tolerances are In the grading diagram, the tripping curve of circuit-
3
obsolete. breakers Q2 and Q3 must therefore be considered in
IkΣ
10
F1 M
~
I2t
11
F1
Single Parallel
104
Q1 Q2 Q2+Q3 Base IkΣ
12
t in s L L L
Q1 Ikpart
TIP04_13_129_EN
103
Q1
Miniature 102
13
circuit-
breaker
14
Selectivity limit ISel I 101
S
Q1 Circuit-breaker (max. let-through value) 100
Ii tsd = 100 ms
TIP04_13_065_EN
17
Fig. 7/25: Selectivity with two transformers of the same rating
Fig. 7/24: Selectivity between fuse and downstream circuit-breaker feeding simultaneously; example with outgoing feeder in the
for short-circuit protection busbar center
Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution 145
Con
tents
Intro
duction
1 Q2 and Q3 can be shifted optimally to the right along the Three identical feed-ins
current scale by a characteristic displacement factor of 2
up to the line IkΣ, which represents the base current for this During parallel operation of three transformers, the selec-
2 fault condition. The result of this is selectivity both with tivity conditions are in principle improved more than with
regard to time and current. two units owing to the additionally achieved current selec-
tivity, as the characteristic displacement factor is between
3 If the characteristic curve of the individual circuit-breaker
is used instead of the shifted characteristic, the exact
2 and 3. Here, too, LS releases are required in the feed-ins
to obtain unambiguous selectivity conditions for the circuit-
short-circuit current (distribution) which flows through breaker.
When setting the releases of circuit-breakers Q1, Q2, and Feed-ins connected in parallel through coupling circuit-
Q3, it must be ensured that selectivity is also achieved for
8 operation with one transformer and for all short-circuit
breakers
currents (1- to 3-phase). For cost-related reasons, Coupling circuit-breakers must perform the following
S‑releases for the incoming circuit-breakers must also be protection functions in fault situations:
9 provided for low and medium rated fuse currents, as the • Instantaneous tripping with faults in the vicinity of the
resulting current selectivity of I releases is insufficient. busbar
• Relieving the outgoing feeders of the effects of high total
10 short-circuit currents.
11
12
13 T1 T2 T3
IkPart 1 IkPart 2
14
IkΣ Ik Ik Q1 Q2
< 30 kA < 15 kA < 15 kA Q3
L
Q1 S Q2 Q3
I
15 15 kA 15 kA
IkΣ
TIP04_13_067_EN
TIP04_13_066
16
17 Fig. 7/26: Selectivity with three transformers feeding Fig. 7/27: Short-circuit splitting through the coupling circuit-
simultaneously breaker Q3 with two feeders Q1 and Q2 back to page 147
146 Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution
Con
tents
Intro
duction
10
11
a) Fault in the outgoing feeder b) Fault in the outgoing feeder
at the central busbar section at the outer busbar section
12
13
Ikpart 1 Ikpart 2 Ikpart Ikpart
Q1 Q2 Q3 Q1 Q2 Q3
Q4 Q5 Q4 Q5
14
3 Ikpart 2 Ikpart 15
TIP04_13_068_EN
IkΣ IkΣ
16
Fig. 7/28: Splitting of short-circuit currents for the purpose of setting the overcurrent releases in the coupling circuit-breakers Q4 and Q5 17
in case of three feed-ins and faults a and b in the outgoing branch circuit of different busbar sections
Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution 147
Con
tents
Intro
duction
1 Selectivity and undervoltage protection If a short circuit occurs at K2 (Fig. 7/29 b), the circuit-
breaker Q2 opens. It is equipped with a short-time-
If a short circuit occurs, the line voltage collapses to a delayed overcurrent release (S). The delay time is at least
2 residual voltage at the short-circuit location. The magni- 100 ms. During this time, the rated operational voltage at
tude of the residual voltage depends on the fault resis- the busbar of the main distribution board is reduced to
tance. With a dead short, the fault resistance and, there- 0.13 ∙ Ue. If the rated operational voltage drops to 0.7
3 fore, the voltage at the short-circuit location drop to almost
zero. Generally, however, arcs will be present during short
– 0.35 times this value and voltage reduction takes longer
than approximately 20 ms, all of the circuit-breakers with
circuits that generate arc voltages between approximately an instantaneous undervoltage release will disconnect. All
9
a) Short circuit at the sub-distribution board b) Short circuit at the main distribution board
10
11
Q3 Q3
12 0.5 · Ue 0.13 · Ue
Main
distribution
13 Q2
tv ≥
Q2 board
100 ms
14 80 m
3 × 95 mm2 Cu
K2
0.13 · Ue Sub-distri-
bution
15 board
Q1 Q1
TIP04_13_069_EN
tv = 0
16 K1
Fig. 7/29: Voltage conditions for short-circuited low-voltage switchgear installation with a main and sub-distribution board
148 Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution
Con
tents
Intro
duction
Node fuses
is 0.8 for Siemens LV HRC fuses (400 V, up to 400 A).
4
Incoming circuit-breaker for power transformers in the
The nodes of a meshed low-voltage network are normally
equipped with cables of the same cross-section, and thus
meshed network
5
with LV HRC fuses of utilization category gG of the same In a multi-phase meshed network (Fig. 7/31), which means
type and rated current (Fig. 7/30). feeding several medium-voltage lines and transformers,
10
11
Ik1 F1 F2 Ik2
a
Ik
Ik4
Ik 14
b
15
TIP04_13_070
TIP04_13_071
Ik
16
Fig. 7/30: Short-circuited cable with its two feed-in nodes a and b Fig. 7/31: Example of a meshed network with multi-phase feed-in 17
Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution 149
Con
tents
Intro
duction
10
K3
11
K2
12
a
13 K1
14 b
15
TIP04_13_072_EN
a HV HRC fuses
c
b LV circuit-breaker with I2t
150 Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution
Con
tents
Intro
duction
15
16
17
Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution 151
Con
tents
Intro
duction
7 Protection relays
7.7.1 Dimensioning of Protection
functions required for a medium-voltage feeder. Public 10 kV medium-voltage grids are normally character-
ized by a short-circuit power between 250 and 350 MVA
11 Protection as component of energy automation (20 kV grids up to 500 MVA). The corresponding energy
transmitted at 70 ms (3.5 oscillation periods in the 50 Hz
In addition, digital protection provides the option to ac- grid) for circuit-breakers amounts to about 650 to 900 kWs
12 quire operational and fault data, to store and retrieve them in the 10 kV grid (respectively 1,300 kWs in the 20 kV grid).
through the serial data interfaces. Digital protection can, These values are proportionally lower if the fuse clears the
therefore, be incorporated in substation control and pro- fault – 45 to 65 kWs for the 10 kV grid, respectively 90 kWs
13 tection systems as an autonomous component. for the 20 kV grid.
Current transformer rating for protection purposes These values are below the limit values [10]
• Less or equal to 250 kWs for personal protection in case
14 Specifications in accordance with IEC 60044-1,-2, and -3 of an enclosed switchgear installation
(VDE 0414-44-1, -2, and -3) apply to current transformers. • Less or equal to 100 kWs for system function protection
Current transformers with cores in accuracy class 5P or 10P ("complete functional endurance of all system parts and
15 must be used for the connection of protection devices. The equipment" [10]).
required rated output and dimensioning factor must both
be determined on the basis of the information provided in The anticipated selectivity conditions must be checked
16 the protection relay descriptions. before the protection concept is chosen and details deter-
mined.
17
152 Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution
Con
tents
Intro
duction
Protection by HV HRC fuses without switching device happen under difficult conditions that simultaneous com-
1
pliance with the specifications in IEC/TR 62655 (VDE 0670-
The rated current of the HV HRC fuses specified by the 402) and IEC 62271-105 (VDE 0671‑105) is not possible. In
manufacturers for the rated power of each transformer these cases, the switchgear manufacturer should be con- 2
should be used when dimensioning the HV HRC fuses. sulted, or a circuit-breaker should be used for transformer
According to IEC/TR 62655 (VDE 0670-402), the following protection.
parameters are considered:
• Transformer inrush current
3
Grading of HV HRC with LV HRC fuses in feed-ins
The lowest rated current is dimensioned by the inrush
currents generated when the transformers are energized,
and is 1.5 to 2 times the rated transformer current. In
Grading of HV HRC fuses and LV HRC fuses is mainly applied
for transformers with power ratings of up to 400 kVA, 4
practice, it is normally sufficient if the maximum energiz- when LV HRC fuse-switch-disconnectors or motor fuse-
ing current of the transformer has a selective clearance of disconnectors (maximum rated current is 630 A) are used
20 % from the characteristic curve of the fuse at 0.1 s (example: Fig. 7/34). For power ratings ≥ 500 kVA, circuit- 5
• Minimum breaking current Ia min breakers with overcurrent releases are used on the
In order to determine the maximum rated current, the low-voltage side.
minimum breaking current Ia min of the fuse must be
exceeded in the event of a short circuit on the secondary It is acceptable for the pre-arcing time-current character
6
side of the transformer and up to the busbar area of the istics F2 (LV HRC) and F3 (HV HRC) – referred to 0.4 kV –
switchgear. Actual practice has shown that a 25 % mini-
mum safety margin of Ia min should be established in
to touch or intersect, and the switch-disconnector to be
possibly tripped on the medium-voltage side by the up-
7
relation to the short-circuit current Ik of the transformer stream HV HRC fuse, since both fuses protect the same
between the calculated maximum short-circuit current in network component and interruption will occur in all cases
the vicinity of the busbar on the low-voltage side (con- (limited selectivity). HV HRC fuses with higher rated cur- 8
verted to the medium-voltage side) and the minimum rents (for example, 80 A as shown in Fig. 7/34) would not
breaking current Ia min (the circle in the pre-arcing be suitable here, since their lowest breaking current Ia min
time-current characteristic). does not have a safety margin of at least 25 % below the
short-circuit current Ik which the transformer lets through
9
The fuse-link can be chosen between the specified limits (maximum 10.5 kA).
according to the selectivity requirements (see Fig. 7/33).
A non-selective fuse response, as demonstrated in the
10
Protection by switch-disconnectors and HV HRC fuses example, of the 50 A HV HRC fuse towards the 630 A
LV HRC fuse (Fig. 7/34) may result in damage of unblown
As a switch-disconnector is normally used for transformer fuse-links in case of faults at the low-voltage busbar, so 11
protection when HV HRC fuses are used, the limited break- that the tripping characteristic is changed and the fuse may
ing capacity of the switch-disconnector must be taken into trip at any time under any load – even below its rated
account. According to IEC 62271-105 (VDE 0671-105), the current. In the event of protection tripping by the HV HRC 12
following two conditions must be met, among others: fuse, or the LV HRC fuse, both fuse links should always be
• The transfer current of the HV HRC fuse / switch- replaced altogether. This applies to all descriptions below
disconnector combination must be lower than the
breaking capacity of the switch-disconnector
and the examples given for HV HRC fuses, where non-selec-
tive protection is provided on the low-voltage side of the
13
• A secondary-side transformer short circuit should be transformers (Fig. 7/35 to Fig. 7/37).
cleared by the HV HRC fuse in order to relieve the
switch-disconnector from high transient recovery 14
voltages.
Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution 153
Con
tents
Intro
duction
1 Grading of HV HRC fuses, LV circuit-breakers, and the downstream distributions and protection devices, as
downstream LV HRC fuses well as the short-circuit currents likely to be present at the
fault locations, must then be taken into account.
2 Requirements
Tolerances of HV HRC fuses
Selectivity is to be established between the protection
3 devices of the outgoing feeders and those of the feed-in,
which together form a functional unit; the safety margins
According to EC 60282-1 (VDE 0670-4), the tolerance of
HV HRC fuse-links can be ±20 %. Siemens HV HRC fuse-links
of the protection devices must also be considered have a tolerance of ±10 %.
Grading between LV HRC fuses and L / S releases Protection by circuit-breakers with definite-time
overcurrent protection (DMT)
5 Selectivity is achieved with the 315 A fuse-link used in the
example, (Fig. 7/35). With L and S releases, the excitation
Preconditions
values IR and Isd as well as the delay times tR and tsd must
6 be matched to the transformer rating and the downstream
LV HRC fuse. If a low-voltage circuit-breaker is used with
The two incoming circuit-breakers in Fig. 7/38 to Fig. 7/41
form a functional unit and must be selectively graded
an additional, optional I4t characteristic in the L release, towards the protection devices on the low-voltage side.
tional unit, a restriction in selectivity in the upper short-cir- If DMT protection is applied, whose protection function
cuit current range is accepted today in case of faults in the merely consists of the two I> and I>> (ANSI 50 / 51)
11 vicinity of the busbars (as indicated by the circle in the short-circuit stages, and if no further measures are taken
diagram for the 80 A HV HRC fuse in Fig. 7/35 to Fig. 7/37), for transformer protection, the I> stage is normally used as
because faults inside the switchgear in this short-circuit back-up protection for the low-voltage side. This means the
12 range can virtually be ruled out for Siemens low-voltage I> stage is set to 1.5 up to 2.0 times the transformer’s rated
SIVACON switchboards. current. Consequently, the size of the outgoing feeders in
the main distribution board at the low-voltage level is
13 Even partial selectivity of the low-voltage circuit-breaker in
the outgoing feeder with the HV HRC fuse (Fig. 7/35) in the
limited in order to ensure selectivity there. For example,
with a 630 kVA transformer this means:
upper short-circuit range is often acceptable, as dead • A fuse of a maximum size of 160 A can be used in the
3-phase short-circuit currents can be ruled out in practice, main distribution board (Fig. 7/38). In practice, this
14 and faults will be below the selectivity level just a few roughly corresponds to 20 % of the rated transformer
meters downstream from the protection device (here: the current
intersection of the HV HRC fuse curve and S release curve). • With circuit-breakers, their maximum size depends on the
15 In these cases, the more cost-effective variant, the HV HRC setting ranges of the circuit-breakers’ releases and their
fuse, is preferred to a medium-voltage circuit-breaker, and tolerances, as well as the protection devices in the out
not the fulfillment of 100 % selectivity. going feeders of the downstream sub-distribution board.
16 The requirement of full selectivity and the use of HV HRC
Selective grading using SENTRON 3WL circuit-breakers
(630 A or even 800 A) is possible (Fig. 7/39). Generally
fuses can often be met by implementing zone-selective speaking, circuit-breakers can be used with current ratings
interlocking (ZSI) with low-voltage circuit-breakers. All of of 50 % up to 80 % of the rated transformer current.
17
154 Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution
Con
tents
Intro
duction
Intersection of the characteristics Q2 and Q3 in the middle Authorized information on the precise rating of these
1
short-circuit range is permissible because: current transformers matching the protection relays ap-
• The low-voltage circuit-breaker and the medium-voltage plied and the prevailing boundary conditions can only be
circuit-breaker form a functional unit given by the specialized technical departments of the 2
• The L release of the low-voltage circuit-breaker Q2 pro- equipment manufacturer. In practice, the rated currents of
tects the transformer against overloading, which practi- the current transformers used for DMT protection devices
cally is present in the range of 1.0 – 1.3 times the rated
current of the transformer only
can be determined as follows:
• General use of 1 A current transformers (secondary side)
3
• A safety margin of 50 ms to 100 ms exists between the if numerical protection technology is applied. Usually,
pickup value of the I> tripping of the DMT protection
(lower tolerance band) and the upper tolerance bands
this approach almost completely rules out possible prob-
lems regarding non-saturated transmission of short- 4
of the characteristic curve of the LV HRC fuse (F1) and circuit currents and the burdening of the current trans-
the S release of the circuit-breaker Q1 in the outgoing formers for DMT protection in advance
feeders, which means that selectivity is ensured. • The rated primary current of the current transformer 5
should be 1.2 to 2.0 times the rated transformer current.
2-zone DMT protection with overload protection This protects the current transformer against damage
Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution 155
Con
tents
Intro
duction
Assuming that additional overload protection Ith has also The short-circuit stage I>> is set in such a way that it will
3 been set in the DMT protection device, the short-circuit
stage I> is chosen in such a way that it will excite at a
only detect high-voltage-side faults which are then cleared
as fast as possible. Usually, it is chosen with a safety mar-
safety margin of approximately 20 % towards the minimum gin of approximately 20 % above the maximum 3-phase
15
16
17
156 Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution
Con
tents
Intro
duction
1
1,000
TIP04_13_081_EN
10 kV
3GD 50 A
2
t
3GD
50 A
3
8
Ia min
1
≥ 25 % safety margin 9
10
0.1
IRush
11
ms
≥ 20 % safety margin
12
13
0.01
1,000 10,000 I in A at 0.4 kV 100,000
14
A at 0.4 kV 1,000 2,000 3,000 5,000 7,500 10,000 20,000 50,000
A at 10 kV 40 80 120 2 00 400 800 2,000 15
I
ts Pre-arcing time of fuses
Minimum breaking current Ia min of HV HRC fuse
16
Fig. 7/33: Example for dimensioning a HV HRC fuse according to the minimum breaking current of the HV HRC fuse and the inrush current 17
of the transformer back to page 153
Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution 157
Con
tents
Intro
duction
1
1.000
TIP04_13_082_EN
2 F3
10 kV
3GD 50 A
t
3GD
3 3GD 80 A 50 A
min
F3
F2 (80 A)
3NA 630 A
4 100
Base Ik < 10.5 kA
400 kVA
ukr 6 %
5 F1
3NA 400 A F2 3NA
630 A
6
10 0.4 kV
s
7
3NA
F1
8 400 A
1
9
Ia min Ik< 10.5 kA
≥ 25 % safety margin
is not observed!
10
11 0.1
ms
12
13
0.01
14 1,000 10,000 I in A at 0.4 kV 100,000
17 Fig. 7/34: Example of grading HV HRC fuses – LV HRC fuses in the outgoing feeder with a 400 kVA transformer back to page 153
158 Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution
Con
tents
Intro
duction
1
1,000
TIP04_13_083_EN
10 kV
2
F2
3GD 80 A
t
3GD 3
min
F2 80 A
Q1 Base Ik < 16.4 kA
100 3WL 1,000 A 630 kVA 4
ukr 6 %
3WL
I2t characteristic
Q1 1,000 A 5
tsd 300 ms
0.4 kV
F1 6
10 3NA 315 A
s
3NA
F1 315 A 7
Ik < 16.4 kA 8
1
9
tsd
10
0.1
11
ms
12
0.01
13
1,000 10,000 I in A at 0.4 kV 100,000
16
Fig. 7/35: Example of grading HV HRC fuses F2 with circuit-breaker Q1 and downstream LV HRC fuse F1 in the outgoing feeder 17
back to page 153
Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution 159
Con
tents
Intro
duction
1
1,000
TIP04_13_084_EN
2 10 kV
F2
t
3GD 80 A
3 Q1 3GD
min
F2 80 A
3WL 1,000 A
I4t characteristic Base Ik < 16.4 kA
4 100 630 kVA
ukr 6 %
3WL 1,000 A
5 Q1 Isd 4,000 A
tsd 300 ms
0.4 kV
6 F1
10 3NA 400 A
s
3NA
7 F1 315 A
8 Ik < 16.4 kA
1
9
tsd
10
11 0.1
ms
12
13
0.01
1,000 10,000 I in A at 0.4 kV 100,000
14 A at 0.4 kV 1,000 2,000 3,000 5,000 7,50010,000 20,000 50,000
A at 10 kV 40 80 120 200 400 800 2,000
15 ts Pre-arcing time of fuses
I
tsd Delay time of S release (Q1)
16
17 Fig. 7/36: Example of grading HV HRC fuses F2 with circuit-breaker Q1 (optional I4t characteristic of the L release) and downstream
LV HRC fuse F1 in the outgoing feeder back to page 154
160 Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution
Con
tents
Intro
duction
1
1,000
TIP04_13_085_EN
10 kV
2
F2
t
3GD 80 A
3GD 3
min
F2 80 A
Q2
3WL 1,000 A
Base Ik < 16.4 kA
100 I2t characteristic
630 kVA 4
ukr 6 %
Q1
3WL 630 A 3WL 1,000 A
I2t characteristic Q2 Isd 4,000 A 5
tsd 300 ms
0.4 kV
6
10 3WL 630 A
Q1
Isd 2,500 A
s
tsd 200 ms 7
Ik < 16.4 kA 8
1
9
tsd2
10
tsd1
0.1 11
ms
12
13
0.01
1,000 10,000 I in A at 0.4 kV 100,000
Fig. 7/37: Example of grading HV HRC fuses F2 with circuit-breaker Q2 and downstream circuit-breaker Q1 with an LSI release in the 17
outgoing feeder back to page 154
Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution 161
Con
tents
Intro
duction
1
1,000
TIP04_13_086_EN
2 Q3
10 kV
t
3
I> 66 A/500 ms
60/1 A
min
630 kVA
Base Ik < 16.4 kA
4 100 Q2 ukr 6 %
0.4 kV
3WL 630 A
6
Q1
Isd 1,260 A
10 tsd 200 ms
3NA
s
F1
160 A
7
Ik < 16.4 kA Ik < 16.4 kA
8
Q3
1
I> / t>
9
10 tsd2
F1
11 0.1 3NA 160 A Q3
ms
I>> / t>>
12
13
0.01
1,000 10,000 I in A at 0.4 kV 100,000
14 A at 0.4 kV 1,000 2,000 3,000 5,000 7,500 10,000 20,000 50,000
A at 10 kV 40 80 120 200 400 800 2,000
15 I
ts Pre-arcing time of fuses
tsd2 Delay time of S release (Q2)
16 t> / t>> Delay time of short-circuit tripping stages I> / I>> of the DMT protection (Q3)
17 Fig. 7/38: Example of grading a circuit-breaker with DMT protection (Q3), 3WL circuit-breaker, 1,000 A with LSI release (Q2), and
downstream outgoing feeders, e.g., with LV HRC fuses 160 A (F1), in a 630 kVA transformer feeder back to page 154
162 Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution
Con
tents
Intro
duction
1
1,000
TIP04_13_087_EN
Q3
10 kV
2
t
3
I> 66 A/500 ms
60/1 A
810 A/50 ms
min
I>>
Q1
3WL 630 A 630 kVA
Base Ik < 16.4 kA
100 I2t characteristic ukr 6 %
4
3WL 1,000 A
Q2 Q2 Isd 4,000 A
3WL 1,000 A
I2t characteristic
tsd 300 ms
5
0.4 kV
Q1 3WL 630 A
Isd 1,260 A 6
10 tsd 200 ms
3NA
s
F1
160 A
7
Ik < 16.4 kA Ik < 16.4 kA
8
Q3
1 I> / t>
9
tsd2
10
tsd1
0.1 Q3 11
ms
I>> / t>>
12
13
0.01
1,000 10,000 I in A at 0.4 kV 100,000
Fig. 7/39: Example of grading a circuit-breaker with DMT protection (Q3), 3WL circuit-breaker, 1,000 A with LSI release (Q2), and 17
downstream outgoing feeders with 3WL circuit-breaker, 630 A, LSI release (Q1), in a 630 kVA transformer feeder back to page 154
Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution 163
Con
tents
Intro
duction
1
1,000
TIP04_13_088_EN
2 Q3
Ith
10 kV
Q3
0 % Preload
t
I>
I>>
810 A/50 ms
6 Q1 3WL 630 A
Isd 2,560 A
10 tsd 200 ms
3NA
s
F1
7
315 A
8
Q3
1
9 I> / t>
10 tsd2
11 0.1 Q3
ms
I>> / t>>
12
13
0.01
1,000 10,000 I in A at 0.4 kV 100,000
14 A at 0.4 kV 1,000 2,000 3,000 5,000 7,500 10,000 20,000 50,000
A at 10 kV 40 80 120 200 400 800 2,000
15 I
ts Pre-arcing time of fuses
tsd2 Delay time of S release (Q2)
16 t> / t>> Delay time of short-circuit tripping stages I> / I>> of the DMT protection (Q3)
17 Fig. 7/40: Example of grading a circuit-breaker with DMT protection and overload protection (Q3), 3WL circuit-breaker, 1,000 A with LSI release
(Q2), and downstream outgoing feeders with LV HRC fuses 315 A (F1), in a 630 kVA transformer feeder back to page 155
164 Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution
Con
tents
Intro
duction
1
1,000
TIP04_13_089_EN
Q3
Ith
10 kV
2
Q3
0 % Preload
t
3
100 % Preload Ith 42 A
60/1 A 210 A/500 ms
min
I>
I>>
810 A/50 ms
Q2
3WL 1,000 A Base Ik < 16.4 kA 630 kVA
100
Q1
I2t characteristic
ukr 6 %
4
3WL 1,000 A
3WL 630 A Q2 Isd 4,000 A
I2t characteristic tsd 300 ms
5
0.4 kV
6
Q1 3WL 630 A
Isd 2,560 A
10 tsd 200 ms
3NA
s
F1
7
315 A
8
Q3
1
I> / t>
9
tsd2
10
tsd1
0.1 Q3 11
ms
I>> / t>>
12
13
0.01
1,000 10,000 I in A at 0.4 kV 100,000
Fig. 7/41: Example of grading a circuit-breaker with DMT protection (Q3), 3WL circuit-breaker, 1,000 A with LSI release (Q2), and downstream 17
outgoing feeders with 3WL circuit-breaker, 630 A, LSI release (Q1), in a 630 kVA transformer feeder back to page 154
Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution 165
Con
tents
Intro
duction
4 transformers comprising:
–– Temperature sensors in the low-voltage winding and
–– Signaling and tripping devices in the incoming feeder
5 panel / cubicle.
10
11
12
13
14
15
16
17
166 Totally Integrated Power – Switching and Protection Devices for Low‑Voltage Distribution
Chapter 8
Medium-Voltage Switching Devices
and Switchgear
8.1 Medium-Voltage Switchgear 169
8.2 Medium-Voltage Switching Devices 179
8.3 Medium-Voltage Protection 189
Con
tents
Intro 8 M
edium-Voltage Switching Devices and
duction
Switchgear
1 According to international rules, there are only two voltage The electrical transmission and distribution grids not only
levels: connect power plants and electricity consumers, but also,
• Low voltage (LV): up to and including 1 kV AC with their “meshed networks”, form a nationwide backbone
2 (or 1.5 kV DC) with reserves for reliable supply and for the compensation
• High voltage (HV): above 1 kV AC of load differences. High operating voltages (and therefore
(or 1.5 kV DC). low currents) are preferred for power transmission in order
3 Most electrical appliances used in household, commercial,
to minimize losses. The voltage is then transformed to the
usual values of the low-voltage grid in the load centers
and industrial applications work with low voltage. High close to the consumer.
10
11
12 TIP04_13_090_EN
13
14
220 kV
15 High voltage
52 kV
16 Medium voltage
Medium
voltage
1 kV
Low voltage
17
Fig. 8/1: Voltage levels between the power plant and the consumer
Intro
duction
8.1 Medium-Voltage Switchgear clearly predominates. The currents are lower, and
1
short-circuit protection is often provided by the associ-
When planning switchgear, functions and influencing ated circuit-breaker of the primary distribution level. The
factors must be matched, and a cost-efficient solution must requirements placed on the secondary equipment are 2
be found among the offerings of manufacturers. For this, usually lower. Typical forms are:
there is no simple recipe with an unambiguous solution –– The transfer substation, from which the energy is
because:
• The tasks of a switchgear can vary greatly
distributed at the fed-in grid voltage (medium voltage).
A transfer switch (coupling) in the substation can
3
• Many influencing factors are interdependent establish the property limit between the supply
• Different operators may weight the same influencing
factors and requirements in a different way.
company and the customer if the customer wants to
develop his switchgear part independently. In that 4
case, measuring and metering equipment for billing
Generally, a switchgear assembly shall provide a high level the transferred electrical power are also available
of safety so that both operator protection and trouble-free –– The secondary unit or transformer substation, where 5
network operation are ensured. It must meet the require- the energy is transformed from medium into low
ments of protection against accidental contact and exclude voltage and distributed as such. In industrial plants,
the possibility of maloperation. If a fault occurs neverthe-
less, its impact should be limited to the place of origin
unit substations are often installed in the production
centers, which at the same time are load centers, and
6
location and not entail personal injury. are thus defined as load center substations. Very
Power generation
and high-voltage
G In the following, the metal-enclosed, type-tested medi-
um-voltage switchgear in accordance with IEC 62271-200
13
grid (VDE 0671-200) is described, since both solid-insulation
enclosed and site- or workshop-built switchgear assemblies
Transformer substation are manufactured significantly less frequently. The high 14
Primary manufacturing and testing expenses often amortize only if
distribution level
high quantities are produced and the production is stan-
Medium-voltage Central dardized accordingly. The technical data must be verified 15
grid switching by type tests. The manufacturing quality is monitored by
TIP04_13_091_EN
Low-voltage grid
17
Fig. 8/2: Structure of the voltage and power distribution levels
Intro
duction
5
Selection parameter Determinants
8 • Altitude
Primary rated values
16
Selection parameter Determinants
• Circuit-breaker • Normal current and switching duty
Switching
Intro
duction
• Type of construction
– Extendable panels
• Normal current, switching capacity
• Network protection
2
panel type
• Air (AIS)
• Room climate: temperature cycles, humidity,
pollution, salt, aggressive gases 5
Insulating medium
6
• Place of installation (space requirements)
• Fire protection requirements (fire load)
• Altitude
• Switching rate and service life of switching devices
7
Selection parameter Determinants
• Switching rate
8
• Withdrawable part / truck
Disconnection
• Operational requirements
(access to cable connection, e.g., for cable testing)
9
Selection parameter Determinants
• Degree of protection
(IP according to IEC 60529, VDE 0470-1)
• Ambient conditions
10
• Internal arc classification • Personal safety
Enclosure
11
– A or B (type of accessibility) • Type of service location
– F / L / R (qualified sides) • Building
– IA, tA (arc test current and duration)
• Pressure relief duct
12
Selection parameter Determinants
• Loss of service continuity category
(LSC, compartment classification)
• Operational procedures
13
– LSC 1 – Operating, working
– LSC 2 – Maintenance requirements
14
Compartments and partitions
15
• Accessibility und access control via • Operator specifications
– Interlocking • Qualification of personnel
– Work instruction + lock • Protection against access to hazardous parts while working
– Tool
• Non-accessible compartment
• Space requirements of the switchgear
16
• Partition class
– PM (metallic partitions)
17
– PI (non-metallic partitions)
Intro
duction
2
– Termination: conventional sealing end / plug Switching duty
– Number of cables • Cable / overhead line
– Conductor cross-sections • Altitude
Feeder components
3
• Surge arresters
• Voltage transformers • Network protection
– Earth-fault winding (if required) • Measuring, metering
• Current transformers • Control
4 – Number and data of cores • Neutral earthing
• Summation current transformer
(zero-sequence current transformer)
6
Selection parameter Determinants
• Instrument transformers • Network protection and measurement
components
• Surge arresters
9
Secondary equipment
10
• Equipment for monitoring
and communication
• Motor operating mechanisms
• Voltage detecting system
11 • Damping resistor (for voltage transformers)
Tab. 8/1: Overview of the rated values and selection parameters for the configuration of medium-voltage switchgear
12
8.1.3 Design of the Medium-Voltage • Better lifecycle assessment than air-insulated switchgear
Switchgear referred to the entire lifetime of the switchgear.
13 Gas-insulated switchgear should be used for medium-voltage Personal safety
transfer substations. The advantages of gas-insulated
switchgear are: • The gas-insulated switchgear is safe to touch thanks to its
14 • Lower space requirements (up to approx. 70 % savings at earthed metal enclosure
30 kV) compared to the corresponding air-insulated • HV HRC fuses and cable sealing ends are only accessible
switchgear when outgoing feeders are earthed
15 • Smaller transportation sizes and consequently easier • Operation only possible when enclosure is closed
transport • As a “special cooling system”, a maintenance-free pres-
• Higher operational reliability due to hermetically sealed sure absorber system reduces the pressure-dependent
16 primary part of the switchgear (disturbing influences
such as pollution, small animals, contact, condensation
and thermal effects of internal arcing, and thus protects
people and buildings (Fig. 8/3).
are excluded by the enclosure)
• Maintenance-free primary part (no lubrication and read-
17 justment required)
Intro
duction
1
1 Low-voltage compartment
Switchgear room Switchgear room
1 – Standard for
1 2 circuit-breaker panels
2
≥ 2,400
2
≥ 1,000 – Option for every
3 9 other panel type
≥ 1,000
3
4 10 2 Pressure relief outlet
890
3 Room height
5
≥ 2,400
775 ≥ 1,000
2,300
2,000
4 Panel depth
828
6
5 Control aisle
4
6 Cable compartment cover
7 Cable
5
7 300 11
8 Height of cable basement
corresponding to cable
115 ~200 bending radius
> 600 8 12
6
2 834 9 Direction of pressure relief
Cable basement 9 Cable basement 10 Pressure relief duct
620
10
11
620
≥ 50
≥ 50
TIP04_13_092_EN
Top view Top view
12
Switchgear arrangement with standard panels Switchgear arrangement with rear pressure relief duct (option)
Fig. 8/3: Room planning for switchgear (dimensions in mm) with pressure relief downwards (left) and with pressure relief duct (right)
back to page 172
13
Extensibility Place of installation
14
It should be possible to extend the switchgear with a The switchgear shall be usable as indoor installation in
minimum time expense. A modular system with ordering accordance with IEC 61936-1 (VDE 0101-1). Switchgear is
options for busbar extensions on the right, left, or both differentiated as follows: 15
sides provides the best prerequisites for this: • Outside lockable electrical service locations at places
• Individual panels and panel blocks can be lined up and which are not accessible to the public. Enclosures of
extended at will – without gas work on site
• Low-voltage compartment available in two overall
switchgear can only be removed with tools; operation by
untrained or unskilled persons must be prevented
16
heights, wiring to the panel via plug connectors • In lockable electrical service locations: A lockable electri-
• All panels can be replaced at any time. cal service location is a room or a place that is exclusively
used for operating electrical equipment and which is kept 17
under lock and key. Access is restricted to authorized
Intro
duction
TIP04_13_093_EN
instructed in electrical engineering. Untrained or
≥ 800 mm
≥ 500 mm
unskilled persons may only enter under the supervision of
2 electricians or persons who have been properly instructed
Control aisle
in electrical engineering.
availability of a switchgear. The following aspects play a part when choosing a single or
double busbar:
15 Gas-insulated switchgear is available as a type with • Number of outgoing and incoming feeders
• Non-accessible compartment • Separate operation of parts of the switchgear is required
It must not be opened. Opening such a compartment • Operability of certain parts of the switchgear is required
16 could destroy it and impair functioning of the switchgear. while working in the switchgear
• Transfer of consumers to different incoming feeders
Medium-voltage switchgear assemblies are further differ- • Uninterrupted transfer.
entiated according to three opening types:
17 • Interlock-controlled accessible compartment
An interlock in the panel releases access when live parts
Intro
duction
Loss of service continuity When an accessible compartment of the switchgear Constructional design
1
category is opened…
2
the busbar and therefore the complete switchgear No partitions within the panel, no panel separation
LSC 1
must be isolated walls to the adjacent panels
only the incoming cable must be isolated. The busbar Panel separation walls and isolating distance with
LSC 2A
and the adjacent panels can remain in operation partitioning towards the busbar
3
LSC 2
the incoming cable, the busbar, and the adjacent Panel separation walls and isolating distance with
LSC 2B
panels can remain in operation partitioning towards the busbar
5
Busbar Busbar Busbar
compartment compartment compartment
Disconnector
compartment 6
7
Switching-
device
Busbar, switching- compartment
device, and
connection
compartment Connection
Switching-device
and connection
compartment
Switching-device
and connection
compartment
8
compartment
11
Switching-
Switching-
Switching-
device
compartment
device
compartment 12
device
compartment
Switching-device
13
TIP04_13_094_EN
and connection
Connection compartment Connection Connection
compartment compartment compartment
Intro
duction
1 In case of more intense branching (rule of thumb: more Remark: Medium-voltage switchgear is generally tested
than five outgoing feeders), the single busbar can be according to accessibility type A. Only complete, facto-
subdivided once or several times, with its own incoming ry-assembled substations (transformer / load center sub-
2 feeder in every section. At the points of interruption, bus stations) are tested for type B. Testing normal switchgear
sectionalizers can be implemented with disconnectors or according to type B is not reasonable, since it is always
switch-disconnectors, or with circuit-breakers. A bus sec- installed in an additional substation housing in public
3 tionalizer with circuit-breaker makes sense if the busbar
sections are to be operated as alternately separated or
spaces.
4 Double busbar
internal arc, the following aspects should be observed
when configuring on the basis of the IEC 61936-1
(VDE 0101-1) standard:
Reasons for using a double busbar can be, for example:
5 • Two or more incoming feeders must always be operated 1. Protection against operating error, established, for
separately (for example, due to different suppliers or example, by means of the following:
self-generated power separated from the public grid) –– Switch-disconnectors instead of disconnectors
6 • Separation between consumers with disturbing feed-
backs and consumers placing high requirements on the
–– Short-circuit rated fault-making switches
–– Interlocks
power supply quality –– Non-interchangeable key locks
7 • Classification of consumers according to their impor-
tance, and their corresponding assignment according to 2. Operating aisles as short, high, and wide as possible
the service continuity requirements placed on the grids
• Limited short-circuit strength of already installed equip- 3. Solid covers as an enclosure or protective barrier instead
8 ment requires a division into two subnetworks, whereby of perforated covers or wire mesh
transfers enable load balancing in case of varying power
4. Equipment tested to withstand internal arcing fault
demand.
9 instead of open-type equipment (e.g., equipment in
accordance with IEC 62271-200; VDE 0671-200)
Apart from the first example, a bus coupler can be used in
examples two to four. This bus coupler permits busbar 5. Arc products to be directed away from operating person-
10 transfer without interrupting the energy flow (Fig. 8/6). nel, and vented outside the building, if necessary
11 A successful type test of medium-voltage switchgear also 7. Very short tripping time; achievable by instantaneous
requires an internal arc classification IAC in accordance relays or by devices sensitive to pressure, light, or heat
with IEC 62271-200 (VDE 0671-200). The classification
12 distinguishes the following:
8. Operation of the plant from a safe distance
• Accessibility 9. Prevent of re-energization by use of non-resettable
A Access for authorized personnel only devices which detect internal equipment faults, incorpo-
13 B Public access (meaning a higher test level)
• Qualified, accessible sides of the switchgear
rate pressure relief, and provide an external indication.
F Front (front side) According to this, the switchgear room must always be
L Lateral (side wall) included in the protection measures to be taken against the
14 R Rear (rear wall) effects of an arcing fault:
• Arc test current and duration. • A calculation of the dynamic pressure load on the switch-
gear room, from which an architect or structural engineer
15 Example: Internal arc classification IAC AR BFL 25 kA 1 s may recognize the stress on building structures, is recom-
mended
The specification means that the rear side may only be • The switchgear room must be equipped with pressure
16 accessed by authorized personnel, whereas the front and
lateral sides are freely accessible. The internal arcing test
relief outlets of sufficient cross-section or with a pressure
relief duct.
was made with an arc test current of 25 kA for a duration
of 1 s.
17
Intro
duction
1
Busbar 1
Busbar 2
2
Bus sectionalizer
TIP04_13_095_EN
Bus coupler 5
(BCT = bus coupler transversal)
6
Fig. 8/6: Double busbar with bus sectionalizer and bus coupler back to page 176
Pressure calculation according to Pigler for the 8DJH switchgear type without absorber
7
12
TIP04_13_096_EN
10
8
Overpressure p (in hPa)
6 9
4
10
2
0 100 200 300 400 500 600 700 800 900 1,000
11
Room volume VR (in m3): 50 Time t (in ms)
12
Free relief cross-section Aent (in m2): 1
Short-circuit current IK“ (in kA): 16 Maximum pressure Pmax: 10.9 hPa after 99 ms
Fig. 8/7: Example, for the calculation of stationary overpressures resulting from an internal arc
13
Siemens provides two calculation methods as a service to used. Data on the room volume, the area of the free relief
establish guide values for the calculation of the room size cross-section and the short-circuit current to be tested are
and/or pressure relief outlets during the planning phase. entered into a calculation mask. This supplies a simple 14
characteristic for the overload pressure (Fig. 8/7).
Estimation of pressure effects according to Pigler
15
A simple method provides the estimation according to
F. Pigler [11] for rooms up to 50 m³. The calculation can be
performed by a TIP contact person (www.siemens.com/
tip-cs/contact) when 8DJH medium-voltage switchgear is
16
17
Intro
duction
1 Finite elements simulator of pressure loads in case of arrangement of the pressure relief outlets is taken into
internal arc account. Various pressure load scenarios can be calculated
for specific switchgear types, short-circuit currents, and
2 Although the incidence of an internal fault (internal arc) is places of installation. Thus, the customer benefits from
very unlikely in type-tested air- or gas-insulated switchgear, extended planning security and a cost-optimized solution.
the consequences of such a fault may be severe for the
3 operating personnel as much as for the room itself. For this
reason, appropriate measures in relation to the room
The flow conditions are defined as boundary conditions.
On the one hand, these are the steel sheets of the switch-
situation must be provided for pressure relief, such as gear, and on the other hand, the absorber sheets to be
7 of the switchgear, pressure development, reflection, and Remark: Typically, the overpressure caused by an internal
arc, when assuming the same room volume, is significantly
higher for air-insulated switchgear than for metal-enclosed,
gas-insulated switchgear.
8
1 For any information or requests in this matter, please contact your TIP partner:
www.siemens.com/tip-cs/contact
10
11
12
13
14
15
16
17
Fig. 8/8: Contour plotting of a simulation calculation at 0.1 s
Intro
duction
Intro
duction
10 Circuit-breaker × × × × ×
Switch (disconnector) × × × × ×
11
Disconnector × × ×
Earthing switch × ×
Make-proof earthing
× × ×
switch
12 Contactor × × × × × 1) × 1)
Fuse-link × × ×
13 Fuse-base
Surge arrester*
×
× 2) × 3)
×
× 4) × 5)
Current-limiting reactor × × ×
14 Bushing × × × 6)
Post insulator (insulator) × × 6)
15
× Selection parameter
1) Limited short-circuit breaking capacity
2) Applicable as selection parameter in special cases only, e.g., for exceptional pollution layer
3) For surge arresters with spark gap = rated voltage
4) Rated discharge current for surge arresters
16
5) For surge arresters: short-circuit strength when there is an overload
6) For bushings and insulators: minimum failing loads for tension, bending, and torsion
* Further selection criteria for surge arresters may also be: residual voltage, rated discharge current, energy absorption capability, short-circuit strength (general),
rated and continuous voltage (metal-oxide arrester), rated and response voltage (arrester with spark gap)
17
(Parameters of the secondary equipment for operating mechanisms, control, and monitoring are not taken into consideration in this table.)
Intro
duction
10
11
12
13
14
15
16
17
Intro
duction
1 Selection according to switching duties The following abbreviations and identifying characters are
used in the tables:
For a useful selection of switching devices, the switching
2 duties occurring during normal operation must be known,
Ima
Isc
rated short-circuit making current
rated short-circuit breaking current
so that the optimal device can be selected in each individ-
ual case. It must be distinguished between Ir rated operating current
3 • undisturbed operation (Tab. 8/4 to Tab. 8/6) and
Ik“ initial short-circuit current
Ian motor starting current
4 • operation under fault conditions (Tab. 8/7 to Tab. 8/9). × component is useful
– component is not useful
7
Switching Load case cos φ Current Main problem Comment
application
Earthing switch
Circuit-breaker
Disconnector
10 Contactor
Switch
Fuse
Transformers Unloaded < 0.3 ≤ 0.03 Ir – – × × × – × – – –
12 During inrush 0.15 ≤ 15 Ir Current breaking up to Protection relay with rush
15 Ir with cos φ ≤ 0.15, stabilization required × – × – – – – –
overvoltage possible
0.2 – 0.9 ≤ 2 Ir High switching rate Overvoltage protective
13
Furnace
circuit must be individually × – – – – – – –
transformers
configured
0.15 ≤ 300 A – Surge arresters are
Earthing reactors × × – – × – – –
commonly used
14 Shunt reactors
0.15 ≤ 2,000 A Transient recovery
voltage with rate of
Overvoltage protective
circuit must be individually × × – – – – – –
rise ≤ 6 kV / ms configured
Operating 0.8 – 0.9 ≤ Ir – –
15
Motors × × × – – – – –
Starting 0.2 – 0.3 ≤ 7 Ir Current breaking up to Normally no protective
× × × – – – – –
7 Ir with cos φ ≤ 0.3 circuit necessary
0.8 – 1.0 ≤ Ir Transient recovery Overvoltage protection is
16 Generators voltage with high rate
of rise
commonly used × – – – – – – –
Intro
duction
7
Switching application cos φ Current Main problem Comment
Earthing switch
Circuit-breaker
Disconnector
Contactor 10
Switch
Fuse
Capacitor banks Capacitive ≤ 1.4 Ir High recovery voltage – × × × – × – – ×
Filter circuits Capacitive ≤ 1,000 A High recovery voltage –
Permissible making
× × – – – – – –
11
current:
High amplitude and ≤ 5 kA: for NXACT
Paralleling of capacitor banks Capacitive ≤ 100 Ir high rate of rise of the
making current
vacuum circuit-breaker
≤ 10 kA: for 3AH vacuum
× × – – – – – –
12
circuit-breaker
> 10 kA: reactor required
Unloaded cables Capacitive ≤ 100 A High recovery voltage – × × – – × – – – 13
Unloaded overhead lines Capacitive ≤ 10 A High recovery voltage – × × – – × – – –
Ripple control systems Capacitive ≤ 20 A High recovery voltage – × × – – – – – –
Tab. 8/5: Switching duties in capacitive circuits during undisturbed operation back to page 180 14
15
16
17
Intro
duction
Earthing switch
Circuit-breaker
Disconnector
Contactor
Switch
4
Fuse
Ring separations 0.3 inductive ≤ Ir – – × × × – × – – –
Transfer to differently loaded 0.7 – 1.0 inductive ≤ Ir – –
× × × – × – – –
5 busbars
Unloaded cables – – – – × – – × × × × –
Unloaded overhead lines – – – – × – – – – – – –
Tab. 8/6: Switching duties in other operational cases back to page 180
7
Switching cos φ Current Main problem Comment
8
application
Switch-disconnector
Earthing switch
Circuit-breaker
Disconnector
10 Contactor
Switch
Fuse
Making 0.15 Ima – –
11
× × – – × – × –
inductive
Terminal short 0.15 Isc – –
× – – – – – – ×
circuit inductive
Generator-fed short 0.15 Transient recovery Overvoltage protection for
12
Isc
circuit inductive voltage with rate of rise generators with Ik“ ≤ 600 A × – – – – – – –
≤ 6 kV / ms
Auto-reclosing 0.15 Isc – –
× – – – – – – –
13
inductive
Transformer-fed 0.15 Isc Transient recovery –
short circuit inductive voltage with rate of rise × – – – – – – ×
≤ 4 kV / ms
14 Short-circuit
current-limiting
0.15
inductive
Isc Transient recovery
voltage with rate of rise
–
× – – – – – – –
coils ≤ 10 kV / ms
Double earth fault 0.15 ≤ 0.87 Isc – –
× – – – – – – ×
15 Stalling motors
inductive
0.2 ≤ 6 Ir Breaking For motors with Ian ≤ 600 A
inductive up to 6 Ir with cos φ ≤ 0.3 3EF surge limiters are suitable as
protective circuit. × × – – – – – –
16 Single-compensated motors do
not need protective circuits.
Phase opposition 0.15 0.25 Isc – –
× – – – – – – –
inductive
17 Tab. 8/7: Switching duties in case of short circuit back to page 180
Intro
duction
Switch-disconnector
3
Earthing switch
Circuit-breaker
Disconnector
Contactor
Switch
Fuse
Unloaded cables / overhead lines Capacitive ≤ 5 A High recovery voltage –
4
× × × – – – – –
(supply-side fault)
Loaded cables / overhead lines Variable ≤ Ir High recovery voltage –
(supply-side fault)
× × × – – – – –
5
Switching of the earth-fault current Variable ≤ Ir – –
× × × – – – – –
(load-side fault)
Tab. 8/8: Switching duties under earth-fault conditions back to page 180
6
Switching application cos φ Current Main problem Comment
7
Switch-disconnector
Earthing switch
Circuit-breaker
Disconnector
9
Contactor
Switch
Fuse
Protective disconnection
(disconnecting under load)
0.7 – 1.0 inductive ≤ Ir High recovery voltage –
– – – – × – – – 10
Rapid load transfer 0.7 – 1.0 inductive ≤ Ir Transfer in < 150 ms – × – – – – – – –
12
13
14
15
16
17
Intro
duction
1 Selection according to endurance and switching rate Class S indicates the network type (cable or overhead line)
for which a circuit-breaker is to be used. Circuit-breakers in
If several devices satisfy the electrical requirements and no indoor switchgear are always categorized as Class S1, this
2 further criteria are more important, the required switching means a cable system. This is also true for overhead line
rate can be used as an additional selection criterion. The feeders, since they are connected to the switchgear by
following tables show the endurance of the switching means of a cable.
3 devices and therefore provide a recommendation for their
appropriate use. The respective device standards distin- Circuit-breakers
guish between classes of mechanical (M) and electrical (E)
banks and filters shall be switched, and also if switching The respective number of switching operations with the
8
Class Description
M1 2,000 operating cycles Normal mechanical endurance
9 M
M2 10,000 operating cycles Extended mechanical endurance, low maintenance
2 × C and 3 × O with 10 %,
E1 Normal electrical endurance (circuit-breaker which is not covered by E2)
30 %, 60 % and 100 % Isc
10 2 × C and 3 × O with 10 %,
Without automatic reclosing
30 %, 60 % and 100 % Isc Extended electrical endurance without
E
maintenance of the switching chamber
E2 26 × C 130 × O 10 % Isc
11 26 × C
4 × C
130 × O
8 × O
30 % Isc
60 % Isc
With automatic reclosing
4 × C 6 × O 100 % Isc
12
24 × O per 10 … 40 % Ilc, Icc, Ibc
C1 Low probability of restrikes
24 × O per 10 … 40 % Ilc, Icc, Ibc Breaking without restrikes
C
24 × O per 10 … 40 % Ilc, Icc, Ibc Very low probability of in 2 out of 3 test series
C2
128 × O per 10 … 40 % Ilc, Icc, Ibc restrikes
15
16
17
Intro
duction
dance with the type tests. Modern vacuum circuit-breakers • SF6 switches
1
can usually make and break the rated normal current with are appropriate when the switching rate is ≤ 1 time per
the number of mechanical operating cycles. month. These switches are usually classified as E3 with
regard to their electrical endurance 2
Switches • Air or hard-gas switches
are only useful with switching rates ≤ once a year. These
IEC 62271-103 (VDE 0671-103) only specifies classes for
the so-called general purpose switches. In addition, there
switches are simpler and usually belong to the E1 class.
Versions belonging to Class E2 are in between in terms of
3
are “special purpose switches” and “limited purpose their switching rate
switches”. General purpose switches must be able to break
different types of normal currents (load currents, ring
• Vacuum switches
Their performance is significantly above that of 4
currents, currents of unloaded transformers, charging classes M2 / E3. They are used for special tasks –
currents of unloaded cables and overhead lines) and make mostly in industrial networks – or when the switching
on short-circuit currents. General purpose switches in- rate is ≥ once a week. 5
tended for use in networks with isolated neutral point or
with earth-fault compensation, must also be able to switch
under earth-fault conditions. Their versatility is r eflected in
the precise specifications that are made for class E, the
6
electrical endurance (Tab. 8/11).
8
Class Description
M1 1,000 operating cycles Mechanical endurance
M
M2 5,000 operating cycles Extended mechanical endurance 9
10 × Iload
E1 10 × Iloop Test currents:
10
20 × 0.05 Iload
2 × Ima Iload rated mainly active load-breaking
10 × Icc
current
30 × Iload
10 × 0.02 to 0.04 Icc Iloop rated closed-loop breaking current
E E2 20 × Iloop
5 × Ima
10 × IIc
10 × Ief1
Icc rated cable-charging breaking current
Ilc rated line-charging breaking current
11
100 × Iload
10 × Ief2 Isb rated single capacitor bank breaking
E3 20 × Iloop current
5 × Ima
10 × Icc Restrikes allowed
Ibb rated back-to-back capacitor bank
breaking current
12
C1
10 × Ilc (number not defined) Ief1 rated earth-fault breaking current
13
10 × Isc Ief2 rated cable- and line-charging breaking
C
10 × Ibb current under earth-fault conditions
C2 No restrikes
Additionally 10 times each Ima rated short-circuit making current
0.1 … 0.4 × Icc, Isb, Ibb
15
16
17
Intro
duction
1 Disconnectors Contactors
Disconnectors do not have any switching capacity. Discon- IEC 62271-106 (VDE 0671‑106) has not defined any endur-
2 nectors up to 52 kV may only switch negligible currents ance classes for contactors yet. Commonly used contactors
up to 500 mA (e.g., voltage transformers) or larger currents today have a mechanical and electrical endurance in the
only when there is an insignificant voltage difference range of 250,000 to 1,000,000 operating cycles. They are
3 (e.g., for a busbar transfer with closed bus coupler).
According to IEC 62271-102 (VDE 0671-102), only the
used wherever switching operations are performed very
frequently, for example, > once an hour. The standard
classes for the number of mechanical operating cycles specifies two classes, C1 and C2, for the probability of
8
Class Description
M0 1,000 operating cycles Standard version for general requirements
9 M M1 2,000 operating cycles Extended mechanical endurance
(M1 and M2 are not intended for individual disconnectors, but for
M2 10,000 operating cycles a combination with circuit-breakers belonging to the same class)
Class Description
11 E0 0 × Ima no short-circuit making capacity For general requirements
E E1 2 × Ima short-circuit making capacity For general requirements
12
E2 5 × Ima short-circuit making capacity Reduced maintenance requirements
13
14
15
16
17
Intro
duction
9
PC interface, control and protection system interface
10
Measuring Input V.24 Fiber- I/O ports Binary
inputs filter Serial optics inputs
11
interfaces
Fault
Current
inputs
Amplifier signaling relay
12
(100 · IN, 1 s)
Command relay 13
14
Voltage A / D signal Processor Memory:
inputs transducer system RAM
(140 V EEPROM I/O devices Displays
TIP04_13_073_EN
0001
continuous) 0101 EPROM
15
0011
17
Fig. 8/9: Block diagram for a digital protection device
Intro
duction
Holistic workflow
3 • Integrated system and device engineering – from the
single-line diagram of the unit all the way to device
4 parameterization
• Easy and intuitive graphical linking of primary and
secondary systems
• Application templates included for frequently-used
5 applications
• Manufacturer-independent tool for easy system
engineering
6 • Libraries for user-created configurations and system parts
• Multi-user concept for parallel engineering
• Open interfaces for seamless integration into your
7 process environment
• User interface developed and tested together with
numerous users
• Integrated tools for testing during engineering, Fig. 8/10: SIPROTEC 5 product family
8 commissioning, and for the simulation of operating
scenarios such as network faults or switching operations.
• Hardware modules decoupled from the communication
9 Perfectly tailored fit protocol applied
• Two independent protocols on one module
• Modular system design in hardware, software, and • Comprehensive routines for testing communication links,
10 communications perfectly tailored to user needs
• Functional integration of a great variety of applications
functions, and operational workflows.
such as protection, control, measuring, power quality, or Safety and security inside
fault recording
11 • Identical extension and communication modules for all Tried and tested functions for system protection and per-
device members in the family sonal safety, continuously further developed over five
• Innovative terminal technology ensures easy mounting generations
12 and replaceability combined with maximum safety • Long-life, robust hardware (housing, assemblies, connec-
• Identical functions throughout the entire system family, tors), and a sophisticated layout of the entire electronics
for example, an identical automatic reclosing function of for maximum strength in terms of voltage, EMC, climate,
13 the 7SD8, 7SA8, 7SL8 line protection devices reduce the
training expense, thus enhancing the safety
and mechanical load
• Sophisticated self-monitoring routines identify and report
• All functions can be individually edited and adapted to device malfunctions immediately and reliably
user requirements • Conforming to the strict cybersecurity requirements on
14 • Innovations are available to all devices at the same time the basis of user guidelines and standards such as the
and can easily be retrofitted via libraries if required. IEC / TS 62351 group of standards, the BDEW White Paper
“Requirements for Secure Control and Telecommunica-
15 Designed to communicate tion Systems” [12] and NERC CIP standards (North Ameri-
can Electric Reliability Corporation – Critical infrastructure
• Adaptation to the topology of a given communication protection)
16 structure (ring, star, network, etc.) through parameters
• Scalable redundancy of hardware and software (proto-
• Encryption of the entire communication path between
DIGSI 5, the device and system engineering tool by
cols) matching application requirements Siemens, and devices according to the recommendations
• Several communication channels to higher-level sys- of the IEC / TS 62351 group of standards
17 tems Pluggable communication modules suitable for • Automatic logging of access attempts and security-critical
retrofitting handling performed at devices and systems.
Intro
duction
Where
• Network configuration
• Neutral-point connection
13
IB,max = Maximum normal current • Type and size of the equipment to be protected
fB,max = Safety factor to allow for influences caused by
operational changes and variations such as load 14
changes, operation under faulted loads, instru-
ment transformer faults, resetting percentage; for
example, fB,max = 1.7 for cables, fB,max = 2.0 for 15
transformers1)
Ik,min = Minimum short-circuit current
fLB = Safety factor for excitation linked to arc damping
(typically between 1.25 and 2)
16
1) When determining the safety factor, the coordination with the subordinate
low-voltage grid must be kept in mind. This may result in higher fB,maxvalues
17
(see chapter 7.7)
Intro
duction
1 Normally, time-overcurrent protection devices acting as Both the high-current stage I>> and the overcurrent
main protection should only be used for high-voltage stage I> always work with a definite-time tripping delay
motor ratings up to 2 MW and for transformer ratings up to time (DMT). Different tripping curves can be set for the
2 10 MVA. Above this, directional comparison protection IDMTL function (Ip level). The characteristic curves
devices should be used as main protection, and time- (Fig. 8/13) are described by characteristic formulas
overcurrent protection as standby protection. Both DMT (Tab. 8/14). The characteristic curve types for the relay
3 (Fig. 8/11a) and IDMTL can be used for the protection of
spur cables and normally open cable rings. With motors,
tripping times required in IEC 60255-151 (VDE 0435-3151)
are identified by the letters A, B, C, D, E, and F.
DMT is used for short-circuit protection (Fig. 8/11b). Mod-
10
0.14
t= · Tp
0.140.02 1
Dependent time response fort overcurrent = (I / Ip)0.02 –relays · Tp
(I / I 0.14
) – 1
t= p · Tp
a) b) c) A: Inverse (I / I 0.14
0.14 )0.02 – 1
ttt== · Tp
p
0.14
= (I/ /13.5 0.02
IIIpp)))0.02 –11· T
· Tpp
11 t =(I
(I / 13.5 0.02 – – ·1T
p p
t = (I / Ip) – 1 · Tp
13.5
t = (I / Ip) – 1 · Tp
B: Greatly inverse /13.5
(I 13.5 I p) – 1 · T
t = 13.5
DMT DMT DMT tt =
= (I/ /I80 Ip)) ––11·· T Tpp
12 t = 600 ms
t = (I
(I / I80 p)2 – 1
p
t = (I / Ip)2 – 1 · Tp
80
· Tpp
19.61 2
t = (I / Ip)2 – 1 + 0.491 · Tp
(I /19.61
I ) – 1
DMT t= p + 0.491 · T
= (I 19.61 Ip)2 – 1 + 0.491 · Tp
/19.61
15 t = 0 ms F: IEEE extremely inverse
ttt=
t=
19.61
= (I(I/ /IIp))22 ––11+ 0.491
(I / Ipp28.2
2
) –1
+ 0.491 ·· T
Tppp
+ 0.1217 · Tp
28.2 2
t = (I / Ip)2 – 1 + 0.1217 · Tp
(I / I28.2) – 1
t= + 0.1217 · Tp
16
p
t Tripping time
= I I (I I28.2
/28.2
Fault 2–1
p)current
Fig. 8/11: Main applications for DMT: ttt= 28.2 + 0.1217 ··TTp
Tp Set value of time multiplicator
= (I(I/ /IIp))22 ––11+ 0.1217
p Current 2 +
set value
0.1217 · Tpp
a) Line protection (I / Ipp) – 1
b) Motor protection Tab. 8/14: Formulas for tripping curves according to IEC 60255-151
c) Transformer protection (VDE 0435-3151)
17
Intro
duction
8
t in s
t in s
TIP04_13_171_EN
TIP04_13_170_EN
5
500 9
2
10
100 200
5
100
2 IDMTL
11
Ip
10 I> tp 50
5
20
12
2
DMT T>
1 I >> 10
13
5
T >>
2
I >> Inverse
0.1 2
14
5 IEEE moderately
1 inverse
2 Greatly inverse
T >> IEEE very inverse
0.01 0.5
5
0.2
Extremely inverse 15
2 IEEE extremely
inverse
16
0.001 0.1
102 2 5 103 2 5 104 1 2 5 10 20 50 100
I in A I / Ip
Fig. 8/12: Typical characteristic curves of DMT and IDMTL Fig. 8/13: Tripping curves according to IEC 60255-151 17
protection devices back to page 192 (VDE 0435‑3151) back to page 192
Intro
duction
1 The line differential protection function (ANSI 87L) of the transformers on the high- and low-voltage sides are usually
7SD6 (SIPROTEC 4) or 7SD8 relays (SIPROTEC 5 or SIPROTEC not too long, the summation current can be formed in one
Compact) detects short circuits – even low-current or device, and not in separate devices as in line differential
2 high-ohmic ones – in the section to be protected by means protection. To this end, secondary-side adaptive circuits are
of a phase-selective comparison of current values mea- no longer required to map current influences caused by the
sured separately at the two ends of the line by separate transformer, since the digital protection device does this by
3 devices (Fig. 8/14a). Owing to the strictly local selectivity
– the protection zone is limited by the current transformers
computation:
• Transformer ratio –
at the two ends of the line section – network topology and by amplitude adjustment
The SIPROTEC differential protection relay of the 7UT6 In switchgear assemblies, busbars are the places where the
9 and 7UT8 series can be used as an autonomous current highest energy levels are concentrated. They are subject
comparison protection device for power transformers to a tremendous short-circuit load, as – for reasons of
(Fig. 8/14b). As the connecting cable lengths of the current selectivity – the high short-circuit and earth-fault currents
10
11 a) b) c) d)
12 87L
ΔI
13
Communication 87M/
ΔI 87T M/G ΔI
link 87G
14 ΔI 87G
ΔI G
15 87L
TIP04_13_172_EN
16
Fig. 8/14: Schematic diagrams for a) line differential protection
Intro
duction
at the busbar result in too long tripping times of the In case of a complex topology, the busbar protection must
1
XDMT protection devices. Faults present too long can also detect the disconnector situation in addition to the
easily cause damage in the primary part. For this reason currents of each outgoing feeder, and determine the selec-
must important busbars be protected quickly – inde- tive zones from this, which makes protection very intricate. 2
pendently of their voltage level.
Distance protection
In the face of the complexity of the busbar system (rang-
ing from single to 5-fold busbars), busbar protection can The short-circuit impedance is a measured quantity which
3
get very complex. The principle of reverse interlocking is proportional to the distance between the mounting
(see chapter 4) is suitable for simpler configurations. Here,
the XDMT protection function of the feed-in trips quickly
location of the protection device and the fault location. For
this reason, the impedances of the six possible fault loops 4
independently of the grading time, unless its instantaneous established from all of the measured current and voltage
tripping stage is not blocked by the short-circuit or earth- values (Fig. 8/16) are compared to the line impedance in
fault excitation in an outgoing feeder. In the outgoing order to provide distance protection. After the delay time 5
feeder devices, this excitation is parametrized to a special defined for each zone has elapsed, the distance protection
contact and all excitation contacts are connected in parallel. function trips and clears the fault.
A protection excitation in outgoing feeder panel (fault Distance protection is a universal short-circuit protection
6
F1 in Fig. 8/15) means that the fault present is not within which is preferrably used for line and cable monitoring. The
the busbar area. Owing to the excitation of the outgoing
feeder protection function, the (almost) instantaneous
distance protection function can be used in combination
with various excitation methods:
7
tripping I>> of the incoming feeder protection (t>> = 50 ms • Overcurrent excitation
in Fig. 8/15) can be blocked by the binary input. Here, • Voltage- and current-dependent excitation
incoming feeder protection acts as back-up protection • Voltage, current-, and phase-angle-dependent excitation 8
which trips with t>. If only the protection device for the • Impedance excitation.
incoming feeder is excited during a busbar fault (fault F2)
with t> and t>>, this blocking is suppressed and the busbar
fault is tripped instantaneously. This instantaneous tripping
The communication possibilities are identical for distance
and line differential protection.
9
reduces the load applied by the fault.
10
Feed-in Earth L1 L2 L3 11
12
Distance protection
14
L3 – Earth
L1 – L2
I> I> I>
t > = 0.3 s t > = 0.3 s t > = 0.3 s L2 – L3
15
F1 L3 / L1
Fig. 8/15: Busbar protection by reverse interlocking for the single Fig. 8/16: Fault loops checked by the distance protection 17
busbar
Intro
duction
10
11
12
13
14
15
16
17
1 Power transformers are an essential component for power 9.1 Electrical Design
transmission and distribution. Their ratings originate from
their area of application, their construction, the rated
2 power, and the ratio. Transformer types range from gener-
Rated power and cooling
ator transformers to distribution transformers. All information about the rating of transformers in this
manual results from the product of the rated voltage
3 The standard series IEC 60076 (VDE 0532-76) describes
power transformers, with the following exceptions:
(no-load voltage multiplied by the phase factor √3 for
three-phase systems) and the rated current of the up-
• Rating < 1 kVA for single-phase transformers stream winding (for a multi-winding transformer at the
14
15
16
17
Intro
duction
9
Ur
3 Ur /3
10
Ur
Ur Ur
3
Ur
11
Ir Ir Ir 13
w Ir Ir
w
w/3
14
3 3 3
w/3
Ir 15
Ir Rated current
Ur Rated voltage 16
w Number of turns TIP04_13_113_EN
17
Fig. 9/1: Connections of three-phase current transformers with vector diagrams
Intro
duction
3
I
Typical connection symbols are (see Fig. 9/2):
i
Yy0 (Yy6), Yz5 (Yz11), Dy5 (Dy11) iii
4 In transformers with these connection symbol, a neutral
ii II
III
point connected at the output side permits the connection
of a neutral conductor in the three-phase distribution grid.
5 In this case, the connection symbol designations are as
follows:
Yz5
6 Yyn0 (Yyn6), Yzn5 (Yzn11), Dyn5 (Dyn11)
15
16
17
Intro
duction
Intro
duction
4 B = 100 °C
F = 120 °C A. Lowcost transformer B. Lossoptimized transformer
H = 145 °C.
11
€ 355,404 / year € 294,403 / year
13
Tab. 9/2: Cost calculation for transformer selection
14
15
16
17
Intro
duction
8
Hermetically sealed tank A = length;
B
H
= width;
= height
9
E = roller-to-roller center spacing
10
8 2 5
7 11
2N 2U 2V 2W
12
H
1U 1V 1W
B
5
6
13
3
1 E E A
14
TIP04_13_115_EN
17
Intro
duction
1 In a TUNORMA transformer (Fig. 9/4), the oil level in the • Ester which does not pollute water and is biodegradable.
tank and in the top-mounted bushing insulators is kept Owing to a fire point of over 300 °C, ester also provides a
constant by means of an oil conservator, which is mounted high level of safety against fires and is also classified as K
2 at the highest point of the transformer. Changes in the oil liquid according to EN 61100 (VDE 0389‑2).
level caused by varying thermal conditions only affect the
oil conservator. Accessories and protection devices
3 The design of the transformers depends on the require- For special applications and the enhancement of opera-
ments. For example, double-tank versions are available for tional safety, oil-immersed transformers can be equipped
11 4
1 5
3 8
12 10
2N 2U 2V 2W
13
H
1U 1V 1W
B
14 8 9
2 6
E E A
15
1 Oil level indicator 6 Adjuster for no-load tap changer
TIP04_13_116_EN
16 3 Thermometer pocket
4 Buchholz relay (on request)
8
9
Earth connections
Pulling lug, Ø 30 mm
5 Dehydrating breather (on request) 10 Lashing lug
17
Fig. 9/4: Oil-immersed distribution transformer with conservator
Intro
duction
9.4 GEAFOL Dry-Type Cast-Resin Requirements for the place of installation in accordance
1
Power Transformers with IEC 61936-1 (VDE 0101-1) (for water protection, fire
protection, and functional endurance, see Tab. 9/3 and
Cast-resin transformers are the solution wherever distribu- Tab. 9/4) suggest the use of cast-resin transformers (for 2
tion transformers in the immediate proximity to people example GEAFOL). Compared to transformers using min-
must guarantee the greatest possible safety. The restric- eral oil, silicone oil, or ester, these transformers place the
tions of liquid-filled transformers have been avoided with
cast-resin transformers, but their proven characteristics
lowest demands on the place of installation while fulfilling
higher requirements in terms of personal safety and low
3
such as operational safety and durability have been re- fire load.
tained.
4
Type of cooling
5
Transformer In closed electrical operating
according to General Outdoor installations
versions areas
IEC 60076-2
Mineral oil * O a Oil sumps and collecting pits Impermeable floors with sills No oil sumps and collecting pits
b Discharge of liquid from the are sufficient as oil sumps under certain circumstances
collecting pit must be
prevented
and collecting pits for up
to 3 transformers, each
(The complete text from
DIN VDE 0101, sections 7.6
6
c Water Resources Act and the transformer with less than and 7.7 must be observed.)
country-specific regulations 1,000 l of liquid
Silicone oil or K
must be observed
As for coolant designation O
7
synth. ester**
Cast-resin dry-type
transformers
A No measures required
8
* Or fire point of the cooling and insulation liquid ≤ 300°C ** Or fire point of the cooling and insulation liquid > 300°C
Tab. 9/3: Measures for water protection in accordance with DIN VDE 0101-1 (1997)
9
10
Coolant General Outdoor installations
designation
O a Rooms: fire-resistant F90A, separated a Adequate clearances
b Doors: fire-retardant T30 or
c Doors to the outside flame-retardant
d Oil sumps and collecting pits are arranged to stop a fire spreading; except for
b Fire-resistant partitions
11
installations in closed electrical operating areas with a maximum of
3 transformers, each transformer with less than 1,000 l of liquid
K
e Fast acting protection equipment
As in coolant designation O; a, b, and c can be omitted when e is present No measures required
12
A As in coolant designation K; but without d No measures required
Tab. 9/4: Measures for fire protection and functional endurance in accordance with DIN VDE 0101-1 (1997) 13
14
15
16
17
Intro
duction
11 Climatic class
13
Class F0 There are no measures to limit the danger of fire
The danger of fire is limited by the properties of
Class F1
the transformer
15
16
17
Intro
duction
9.5 Power Converter Transformers If consumers are connected which generate harmonics of
1
a load current THDi > 5 % – referred to the rated current –
The operation of variable-speed three-phase motors using IEC 60076-1 (VDE 0532-76-1) recommends the use of a
power converter connections requires the use of specially power converter transformer instead of a standard trans- 2
customized GEAFOL transformers. The power converter former.
transformer is the link between network and drive system,
and shall ensure an adaptation to the network configu
ration on the one hand and decoupling from feedbacks of
The use of 12-pulse rectifiers with diodes and thyristors
allows the low-frequency harmonic load (especially the 5th
3
the converter connections on the other (Fig. 9/5). Particu- and 7th harmonic) to be reduced. Besides the use of two
lar attention must be given to the impact of harmonics
produced by the converter, the surge operation, a possible
separate transformers for a 6-pulse rectifier bridge each,
special three-windings transformers can be sized as power 4
DC current pre-magnetization, and unbalanced load in the converter transformers. To attain the desired phase shift of
event of a fault. The 6-pulse or 12-pulse bridge connections 30° in the commutation between the two 6-pulse rectifiers,
armonics in the range of the 5th,
for rectifying generate h a star connection and a delta connection is connected to a 5
7th, 11th and 13th harmonic. 6-pulse bridge each on the low-voltage side.
+
10
L1
R 11
L1
Unetwork U
12
C S
L2 U= 3~ AC
L2
13
L3
L3
TIP04_13_117_EN
N ‒
15
Fig. 9/5: Schematic diagram for a three-phase motor drive with power converter transformer and 6-pulse bridge connection
16
17
Intro
duction
1 9.6 FITformer® REG – Regulated “prosumers” (who are electricity customers and “produc-
Distribution Transformer ers” at the same time), play an important part, because
their load purchases, their electricity feed-in, and their
2 Distributed power generation from regenerative energy storage capacities vary greatly sometimes.
sources is more than a trend of the time, and results in
the fact that the load flow in the power supply system is The regulated FITformer® REG distribution transformer
3 becoming increasingly complex in the future. The more
profitable wind power plants and photovoltaic systems
(Fig. 9/6) is capable of changing its ratio under load. It thus
ensures distributed feed-in of small power generating
are becoming, the more attractive they will be in rural plants, and helps the utility keep within the permissible
10
11
12
13
14
15
16
Intro
duction
14
15
16
17
Intro
duction
1 9.7 Transformer Operation forced flow of the external coolant. However, it must be
kept in mind here that the load losses can also more than
double compared to the load losses at rated load. There-
2 Overtemperatures
fore, additional ventilation is a proven means for covering
Transformers are designed in such a manner that overtem- peak loads as well as providing a reserve in case of a trans-
peratures as permitted by the standards are not exceeded former failure when transformers are operated in parallel.
3 during rated operation. The overtemperature in the wind-
ing, and in liquid-filled transformers also the cooling and Notes for planning the low-voltage main distribution
insulating liquid, is the difference between the part under system (LVMD) and transformers under overload:
former overloading is permitted if the specified values for Parallel operation prevails if transformers are connected
the coolant temperature are undershot. The calculation for to identical network systems both at their input and output
9 oil-immersed transformers is described in IEC 60076-7 side. As a rule, transformers characterized by connection
(VDE 0532-76-7), respectively IEC 60076-12 symbols with identical code numbers are suitable for
(VDE 0532‑76‑12) for GEAFOL transformers. parallel operation. Conductor terminals of the same name
10 A corresponding performance increase can be established
(1U-1U, 2U-2U, 1V-1V, 2V-2V, 1W-1W, 2W-2W) must then
be connected to each other. However, transformers with
for Siemens transformers according to a rule of thumb. It certain connection symbols of different code numbers can
is: also be operated in parallel, provided that the conductor
11 • 1 % per 1 K 1) undershooting the coolant temperature for terminals are changed accordingly. This is shown in Fig. 9/8
oil-immersed transformers for transformers with connection symbols in the common
• 0.6 % per 1 K for GEAFOL transformers. code numbers 5 and 11.
12
Overloading the transformer without exceeding the permit- In case of an identical ratio, the total load is distributed to
ted winding temperature is temporarily possible even if the the transformers connected in parallel proportional to the
13 previous continuous load was below the rated power, and
provided that the permitted overtemperatures have not yet
transformer outputs and inversely proportional to the
impedance voltages. In case of identical input voltages and
been reached despite overload. different output voltages of two transformers connected in
parallel, a circulating current flows through both trans-
14 Another transformer overloading option (performance- formers which is approximated as follows:
dependent up to about 50 %) is fan blowing, this means a
16 to –273.15 °C
17
Intro
duction
7
1L1
1L2
8
1L3
9
High voltage:
1W 1V 1U 1W 1V 1U 1W 1V 1U 1W 1V 1U 1L1, 1L2, 1L3
Low voltage:
5 11 11 11 2L1, 2L2, 2L3
10
Required code number 5
2W 2V 2U 2W 2V 2U 2W 2V 2U 2W 2V 2U
11
2L1
2L2
2L3
12
Possible connections
1L1
13
1L2
1L3
High voltage:
14
1W 1V 1U 1W 1V 1U 1W 1V 1U 1W 1V 1U 1L1, 1L2, 1L3
Low voltage:
11 5 5 5 2L1, 2L2, 2L3
Required code number 11
15
2W 2V 2U 2W 2V 2U 2W 2V 2U 2W 2V 2U
2L1
2L2
2L3 16
Possible connections TIP04_13_119_EN
17
Fig. 9/8: Possible connections for transformers operated in parallel with connection symbols of code numbers 5 and 11 back to page 210
Intro
duction
1 In example 1 (Tab. 9/6), the smaller transformer unfortu- Example 1: Transformers with different secondary no-load
nately happens to carry the higher secondary voltage and voltages
must therefore carry the higher total current. This means
2 for this example that, with a circulating current of 25.6 %,
Output voltage
at no load
Rated power Rated impedance
voltage
only a load current of 74.4 % is permitted in order not to in V in kVA in %
exceed the rated current of the smaller transformer 1 Trans-
3
400 630 6
(corresponding to 100 %). Consequently, the whole set of former 1
transformers can only be operated at 74.4 % of its cumu- Trans-
390 1,000 6
lated power of 630 + 1,000 = 1,630 kVA, which is former 2
4 about 1,213 kVA.
Δu =
400 – 390
· 100 = 2.5 %
400
With a power factor for the load below 0.9, this estimation
Sr1 630
suggests a sufficiently precise guide value. With a power
5
= = 0.63
Sr2 1,000
factor greater than 0.9, the permissible cumulated power
rises due to the then growing vectorial difference value. 2.5
Icomp. tr. 1 ≈ ≈ 25.6 %
6 + 6 · 0.63
If it was possible to set a higher tapping on the high-volt- Example 2: Transformer 2 with a 5 % lower transformation and
correspondingly higher secondary no-load voltage
7 age side in the 630 kVA transformer in our example (for
instance 5 % more windings), this would result in a reduc- Output voltage Rated power Rated impedance
at no load voltage
tion on the low-voltage side by a factor of 1 / 1.05 for the in V in kVA in %
smaller transformer 2 due to the induction decrease, when
8 connected to the same high voltage, meaning 381 V
Trans-
former 1
400 630 6
instead of 400 V. Thus, the larger transformer with the
Trans- 5.7
higher voltage (390 V) would be leading. 411 1,000
9
former 2 (≈ 95 % of 6)
17
Intro
duction
In case of equal transformer ratings, the partial loads are 9.8 Transformer Room 1
inversely proportional to the impedance voltages. The
transformer with the lower impedance voltage is loaded Essential spatial requirements are described in IEC 61936-1
more than the one with the higher impedance voltage. (VDE 0101-1). The propagation of fires, the noise level, 2
ventilation, water pollution, and protection against indirect
In case of a transformer load varying over time for a group contact must be taken into account. Furthermore, the
of several transformers connected in parallel considering a
defined period of time, a minimum of total losses can be
standard refers to the relevant national, regional, and local
provisions and regulations. In addition, product-specific
3
attained by connecting individual transformers into or characteristics as described in the IEC 60076 (VDE 0532‑76)
disconnecting them from supply. Load losses are a square
function of the load. This means, the sum of load losses
series of standards play a role for room planning.
4
plus no-load losses may under certain circumstances be Conditions for installation and room layout
lower when the load is split between several transformers
than if fewer transformers are used. To avoid a complicated Extreme local conditions must be taken into account when 5
loss comparison of the transformers operated in parallel, planning the installation:
the partial load where a connection of an additional, • The paint finish and prevailing temperatures are relevant
identical transformer (the kth transformer) is cost-efficient
can be determined as follows using a partial load factor n:
for use in tropical climates
• For use in altitudes of more than 1,000 m above sea
6
level, a special configuration with regard to temperature
n=
Partial load
Rated power
rise and insulation level is required, see IEC 60076-11
(VDE 0532-76-11)
7
• With increased mechanical demands being made – use in
SGroup = n · Sr
a ship, excavator, earthquake region, etc. – additional
Sgroup Output of the group constructive measures may be required, e.g., supporting 8
S r Rated power of an individual transformer the upper yoke.
n Partial load factor.
n=
k · (k – 1) · P0
Pk
With regard to fire protection of facilities, national or local 11
regulations must usually be observed. For example, in
k Number of transformers to be connected in parallel. Germany, the EltBauVO (Ordinance on the construction of
electrical operating areas) governs that doors in fire resis 12
This means, the ratio of no-load to load losses P0 / Pk plays tance class F30-A and walls in fire resistance class F90-A
an important part for the group output in the parallel separate the electrical operating room (in accordance with
connection of transformers. DIN 4102-2). However, firewalls (24 cm wall thickness) as
for oil-immersed transformers are not required for GEAFOL
13
transformers.
Intro
duction
1
AA
2
Air outlet (nat.)
3,000
4 Guard rail
1U 1V 1W
5
Cable
800
6
basement
Air inlet
7
9 Trans-
former 3
Cable 1
Transformer 3 630
10 Cable 2
11
Trans- Metering
former 2 Transfer
6,000
Transformer 2 630
Trans-
12 former 3
Trans-
Trans-
former 2
13 Transformer 1 630
former 1
Trans-
A former 1 A
14
15
7,500
TIP04_13_120_EN
16
outwards, in fire resistance F 90A (DIN 4102)
class F 30A (DIN 4102)
Intro
duction
The heat loss results from the power loss of the trans-
Qv = Σ Pv 6
former. The power loss of a transformer is:
Note: Our TIP contact person can support the electrical
planner with complex calculations of the heat dissipation
7
for arbitrary parameters and when combining ventilation
measures (refer to the contact pages in this manual or the
web page: siemens.com/tip-cs/contact). 8
10
11
KD
QD
AD, KD Qv Total dissipated losses [kW]
12
Pv Transformer power loss [kW]
Air velocity [m/s]
13
v
A1, 2 Air inlet/outlet cross-section [m2]
AW
Air temperature rise [K], = 2− 1
A2 VL Qv = ∑ Pv H Thermally effective height [m]
V2 KW
14
Q W,D Losses dissipated via walls and ceilings [kW]
H
Intro
duction
1 Calculation of the heat dissipation These simple examples show that the heat dissipation
through walls and ceilings quickly reaches the limits of
The following methods are available for the dissipation the room, and that for large transformer outputs, a
2 of the total power loss Qv in the room: detailed configuration of the forced ventilation may be
Qv1 Dissipation with the natural air flow necessary (also refer to the Siemens publication
Qv2 Dissipation via walls and ceilings “GEAFOL Cast-Resin Transformers”; Planning Guidelines,
3 Qv3 Dissipation with the forced air flow. order no. EMTR-B10008-00-4A00). Our Siemens TIP
contact persons can support electrical planners in
Qv = Pv = Qv1 + Qv2+ Qv3 estimating ventilation conditions in a defined room size
7 Qv1 = approx. 13 kW / m2 ∙ A1,2 m2
www.siemens.com/sitrato
9 Qv3 = approx. 44 kW / m2 ∙ A1,2 m2
(Example: Qv3 = 8 kW for a cross-section of approx. 0.18 m2)
10
▶ Project ▼ Ventilation / Pressure increase ▶ EMC ▶ Harmonics ▶ Efficiency Recalculate Export
11
Room width
3m
+ Transformer GEAFOL Neo, 630 kVA, 10 kV, 0.4 kV, uk 4 %, reduced
A2 0.8 m2
12
B2 1 m2
Room height (incl. ϑ2 45 °C _ Ventilation
double floor) Wall thickness
3m 0.2 m
Effective height
Room height (incl. double fl... Room width Room depth
2m
3 m 3 m 3 m
13 Infeed temperature
25 °C
Outlet temperature
45 °C
Transformer load, maxim...
100 %
Room volume
27 m3
Installed ventilation open... Effective height Outlet temperature ϑB2
14
The transformer
volume is considered
1 m2 2 m 41.7 °C
automatically during
the calculation
Minimum ventilation openi...
A1 0.8 m2
B1 1 m2 0.8 m2
ϑ1 25 °C
15 Room depth
+ Pressure increase
3m
Transformer data
17 Fig. 9/11: Screenshot of SITRATO, the Siemens online tool to estimate the ventilation of transformer rooms
2 of Low-Voltage Switchboards
• Degree of protection in accordance with IEC 60529
Low-voltage switchboards1) and distribution boards form (VDE 0470-1)
the link between the equipment for the generation (gener- • Protection against electric shock (safety class) in
3 ators), transport (cables, overhead lines), and transforma-
tion (transformers) of electrical energy on the one hand
accordance with IEC 60364-4-41 (DIN VDE 0100-410)
• Enclosure material
and the consumers, e.g., motors, solenoid valves, devices • Type of installation (at the wall, stand-alone)
rated voltage is 1,000 V max., for direct voltage it is Type of device installation
1,500 V max.
5 • Fixed-mounted design
Like medium-voltage switchgear, low-voltage switchboards • Plug-in design
are also less often installed with individual cubicle design • Withdrawable design
6 on site, but delivered as factory-assembled, design verified
switchboards. For design verification, testing is to be
• Snap-on fixing on DIN rail.
14
15
16 Consumers
Intro
duction
1
Depending on the type of power distribution, a differentia- buildings, no large switching rates have to be considered
tion is made between point-to-point distribution boards and no major extensions are to be expected. Therefore,
and line distribution systems. In point-to-point distribution performance-optimized technology with high component 2
boards, the electric power is distributed radially from a density can be used. In these cases, mainly fuse-protected
spatially limited switchboard (see Fig. 10/1), whereas in equipment in fixed-mounted design is used.
line distribution systems – today mostly busbar trunking
systems – the individual power tap-offs take place via In a power distribution system or motor control center for
3
spatially separated equipment, and the power is transmit- a production plant, however, replaceability and reliability
ted to these tap-off units by means of enclosed busbars
(see Fig. 10/2).
of supply are the most important criteria in order to keep
downtimes as short as possible. An important basis here is 4
the use of non-fused or fused withdrawable-design sys-
In point-to-point distribution boards, one transformer per tems.
busbar section supplies the main switchboard. The down- 5
stream motor control centers, control units, distribution
boards for lighting, heating, air conditioning, workshops,
etc. – that is, those fed by the main switchboard in turn –
are referred to as sub-distribution boards. The combination
6
of a main switchboard with feeding transformer is referred
to as transformer load center substation, and provides –
due to its compactness – a secure and cost-efficient option
7
of distributed power supply in compliance with the pre
fabricated substations described in IEC 62271-202
(VDE 0671-202). 8
When planning low-voltage switchboards, the prerequisite
for efficient dimensioning is the knowledge of the local
conditions, the switching duty, and the demands on avail-
9
ability. For power distribution systems in functional
10
Consumers
11
12
13
Busbar trunking system
14
15
Consumers
16
Fig. 10/2: Schematic diagram of a line distribution system
17
Intro
duction
6 2b
between
connections
and busbars
7
Separation No separation
between
8 3a between
busbars and connections
and busbars
functional units
9
+
Separation
Separation
between
3b between
10 functional units
connections
and busbars
+
11 Separation Connections
between in the same
4a connections compartment as
12 and functional
units
the connected
functional unit
13 Connections
not in the same
4b compartment as
the connected
14 functional unit
Busbar
15
Functional unit
Legend:
16 Connection
for conductors lead in
from the outside
Enclosure Internal separation
Intro
duction
5
1 2 3 4 5 6
6
1 Circuit-breaker cubicle
2 Fixed-mounted or plug-in
universal mounting design 7
3 Plug-in in-line design
4 Fixed-mounted cubicle with front cover 8
5 Fixed-mounted in-line design
6 Reactive power compensation
9
Fig. 10/3: Mounting designs for SIVACON S8 low-voltage switchboard back to page 220
10
Cubicle type
Circuit-breaker Universal 3NJ6 in-line Fixed-mounted 3NJ4 in-line Reactive power 11
design mounting design design design design compensation
Fixed-mounted
12
Fixed-mounted Fixed-mounted
Mounting design Plug-in Plug-in Fixed-mounted Fixed-mounted
Withdrawable with front covers
Withdrawable
Central
Incoming feeder
Cable feeders compensation of
Function Outgoing feeder
Bus coupler
Motor feeders
Cable feeders Cable feeders Cable feeders
the reactive
power
13
Unchoked
14
Up to 630 A / up to 600 kvar
Rated values Up to 6,300 A Up to 630 A Up to 630 A Up to 630 A
up to 250 kW Choked
up to 500 kvar
Connection Front or rear side Front or rear side Front side Front side Front side Front side
Cubicle width in mm
400 / 600 / 800 /
1,000 / 1,400
600 / 1,000 / 1,200 1,000 / 1,200 1,000 / 1,200 600 / 800 / 1,000 800 15
1, 2b, 3a, 4b, 3b, 4a, 4b,
Internal separation 3b, 4b 1, 2b, 3b, 4a, 4b 1, 2b 1, 2b
4 type 7 (BS) 4 type 7 (BS)
Busbars Rear / top Rear / top Rear / top Rear / top Rear Rear / top / without 16
Tab. 10/2: Various mounting designs according to cubicletypes back to page 220
17
Intro
duction
3 back-to-back
Busbar system 3-phase / 4-phase
4 500
PE
7 PE
800
PE
10
PE
800
PE PE
13
1,200
Device / functional compartment Busbar compartment Cable / busbar connection compartment Cross-wiring compartment Operating fronts
14 Tab. 10/3: Cubicle types and arrangement of the busbars on the cubicles (dimensions in mm) back to page 220
15
16
17
Intro
duction
L1
the top
Busbar system 3-phase / 4-phase
N
L3
4
L2
L1
PE
600
L1 L1
7
L3 L3
L2 L2
L1 L1
PE
800
9
N
L3
bottom
L1
10
L3
L2
L1
PE PE
1,000
12
N N
the top
L2 L2
L1 L1
13
N N
L3 L3
L2 L2
L1 L1
PE PE
1,200
14
Device / functional compartment Busbar compartment Cable / busbar connection compartment Cross-wiring compartment Operating fronts
16
17
Intro
duction
• Device reduction factors must be observed according to When low-voltage switchboards are installed, the mini-
manufacturer specifications! Mounting location, ambient mum clearances between switchboards and obstacles
5 temperature and rated current play an important part as specified by the manufacturer must be observed
(particular attention in case of currents greater than (Fig. 10/4). The minimum dimensions for operating and
2,000 A!) maintenance gangways according to IEC 60364-7-729
6 • The dimensioning of compensation systems is very much
governed by the place of use (office, production, etc.)
must be taken into account when planning the space
required (Fig. 10/5). When using an lift truck for the inser-
and the network conditions (harmonic content, DSO tion of circuit-breakers, the minimum gangway widths
12
14
2,000 mm 1)
Switchboard
15
TIP04_16_002_EN
16 600 mm 600 mm
4) When the switchboard is erected (positioning of the right-hand cubicle),
the projection of the busbar connecting lugs must be paid attention to.
Top busbar position: 90 mm projection -> recommended wall clearance > 150 mm 700 mm 700 mm 700 mm 700 mm
Rear busbar position: 54 mm projection -> recommended wall clearance > 100 mm
Attention: All dimensions refer to the frame dimensions ! (nominal cubicle size) 1) Minimum height of passage under covers or enclosures
17
Fig. 10/4: Clearances to obstacles Fig. 10/5: Maintenance gangway widths and passage heights
Intro
duction
Altitude
1
The site altitude must not be above 2,000 m above
sea level. 2
Minimum
Escape direction
Switchboards and equipment which are to be used in maintenance 600 mm
higher altitudes require that the reduction of dielectric
strength, the equipment switching capacity, and the cool-
gangway width
1) 2)
3
ing effect of the ambient air be considered. Further infor-
mation is available from your Siemens contact.
4
Environmental conditions for switchboards
Intro
duction
1 Single-front and double-front systems One or more double-front units can be combined to a
transport unit. Cubicles within a transport unit have a
In single-front switchboards, the cubicles stand next to horizontal through-busbar. Cubicles cannot be separated.
2 each other in a row (Fig. 10/7 top). One or more cubicles
can be combined to a transport unit. Cubicles within a Apart from the following exceptions, a cubicle composition
transport unit have a horizontal through-busbar. Cubicles within a double-front unit is possible for all designs.
3 cannot be separated. The following cubicles determine the width of the dou-
ble-front unit as cubicle (1) and should only be combined
In double-front switchboards, the cubicles stand in a row with a cubicle for customized solutions without cubicle
unit is determined by the widest cubicle (1) within the Cubicles with a width of 350 mm or 850 mm are not
cles (2), (3), (4) can be placed on the opposite side. The
sum of the cubicle widths (2) to (4) must be equal to the
8 width of the widest cubicle (1).
9 Singlefront switchboards
10 Front
connection
12
With main busbar
13
position at the rear
Doublefront switchboards
14
(1)
16
Doublefront units
Intro
duction
Arc resistance
1
Level 1
Personal safety
As for transformers and medium-voltage switchgear, an
arcing fault occurring in the low-voltage switchboard can
without extensive
limitation of the 2
lead to dangerous interferences with serious consequences arc fault effects
and damage neighboring outgoing feeders, cubicles, or inside the
even the entire switchboard. Arcing faults may arise from
wrong dimensioning, insulation deterioration such as
switchboard.
3
pollution, but also from handling faults. High pressure and
extremely high temperatures can have fatal consequences
for the operator and the switchboard; these consequences Level 2 4
may even extend to the entire building. Personal safety
with extensive
9
or cable connection
dling of withdrawable units or circuit-breakers only when compartment.
the door is closed, and non-return flaps (SIVACON switch-
boards use a patented system that is highly reliable) behind Level 4
front ventilations openings, arc barriers, or an arc fault
detection system in combination with a fast interruption of
Personal safety
with limitation
10
arcing faults. The effectiveness of these measures is proven of the arc fault
effects to the
by numerous elaborate arcing tests under worst case condi-
tions on various cubicle types and functional units.
place of origin.
11
The arc protection levels (Fig. 10/8) describe the classifica- TIP04_16_003_EN
14
15
16
17
Intro
duction
1 Reducing the occurrence probability of an arcing fault Monitoring of the outgoing feeder areas of the switch-
board is not recommended for active systems for reasons
In the intensive discussion about arc fault detection or of reliability of supply, as arcing faults in these areas
2 interruption, technically elaborate and expensive solu- should be interrupted by the upstream protection device.
tions are readily propagated. Siemens, however, has for Otherwise, such a fault would lead to a complete shut-
a long time preferred the prevention of arcing faults by down of the switchboard.
3 means of complete insulation (see Fig. 10/9) of all con-
ductive parts inside the switchboard (busbars, connec- For feed-in monitoring (connection compartment), the
tions, transfers, etc.). Such passive precautions ensure system must act on the upstream protection device. Thus,
10
11
12
13
14
15
16 Fig. 10/9: Passive system to prevent arcing faults with insulated busbar, cubicle connector, incoming and outgoing feeder
17
Intro
duction
17
IEC 61439-3 (VDE 0660-600-3)
Intro
duction
1 The following aspects are particularly important for the Selection of the electrical equipment
configuration:
The following has to be considered for the equipment to be
2 Environmental and installation conditions, mechanical installed in switchgear and controlgear assemblies:
stress • The applicable device specifications
• The suitability with regard to rated data, in particular
3 • Degree of protection in accordance with EN 60529
(VDE 0470-1) protection against against access to hazard-
short-circuit strength and breaking capacity
• The installation of current-limiting protection equipment
ous parts, dust and water protection might be necessary.
17
Intro
duction
13
14
15
16
17
Intro
duction
1 10.5 Busbar Trunking Systems Planning is based on the incoming power (for example,
rated and short-circuit currents of the feeding transform-
As line distribution systems (see Fig. 10/11), busbar trunk- ers) and connection values of the BTS, and additionally on
2 ing systems (BTS) also belong to the group of switchgear the following data:
and controlgear assemblies documented in the standard • Permissible voltage drop
series IEC 61439 (VDE 0660-600). Apart from the general • Required degree of protection
3 requirements of IEC 61439-1 (VDE 0660-600-1), the
required product features of BTS are described in
• Network configuration
• Weighing of the supply concepts as cable system or
IEC 61439-6 (VDE 0660-600-6) in particular. The rated busbar trunking system
of electric power and with the control of power consumers. Depending on the project conditions, different busbar
Excluded from IEC 61439-6 (VDE 0660-600-6) are, among trunking systems can be selected:
6 others, electrical busbar systems for luminaires (in accor-
dance with IEC 60570; VDE 0711-300). However, lighting
• Sandwich design for compact dimensions
• Ventilated busbar design for excellent heat dissipation
systems can be connected to BTS, and communication- (attention: In the case of rising main busbars, the stack
8
Profibus ASInterface Industrial Ethernet BACnet KNX DALI ...
9
10 LI system LD system
11 BD2 system
12
BD2 system
13
LI system
14 LR system
BD2 system
15
TIP05_18_010_EN
16
BD01 system BD01 system
17
Fig. 10/11: Busbar trunking systems for different requirements and loads
Intro
duction
17
Intro
duction
5 For reasons of circuit integrity, it may be necessary to pro- Circuit integrity with 4-sided compartmentalization 1)
vide additional protection housing for the busbar trunking
line towards the room. Depending on the required circuit
6 integrity class and the planned carrier / support system,
different design variants are offered with PROMATECT
1
2
boards (enclosed on 2, 3 or 4 sides, refer to Fig. 10/12). 3
7 Because of the poorer ventilation and heat dissipation
through the protection housing, the reduction factors
4
16
6 Bracket in compliance with the statics
TIP04_13_137_EN
Intro
duction
Verification by ...
1
Characteristics to be verified Construction
Testing Calculation
2
rules
Strength of materials and parts:
Corrosion resistance Yes No No
Insulation material properties:
3
Resistance of insulation material to heat No No Yes
Heat resistance Yes No No
Resistance to extraordinary heat and fire due to internal electrical effects Yes No Yes 4
Resistance to UV radiation Yes No Yes
5
Impact test Yes No No
Labels Yes No No
Resistance to mechanical load Yes No No
Tests with thermal cycles Yes No No
6
Degree of protection of enclosures Yes No Yes
Clearances in air Yes No Yes
Creepage distances No No Yes 7
Protection against electric shock and continuity of protective conductor circuits:
8
Continuity of the connection between bodies of the BTS and the protective
Yes No No
circuit
Short-circuit strength of the protective conductor circuit Yes No No
9
Installation of equipment No No Yes
Internal electric circuits and connections No No Yes
Connections for conductors entered from the outside No No Yes
Insulation properties:
10
Power-frequency withstand voltage Yes No No
Impulse withstand voltage Yes No Yes
Temperature-rise limits Yes Yes No 11
Short-circuit strength Yes Yes No
12
Electromagnetic compatibility (EMC) Yes No Yes
Mechanical function Yes No No
Resistance to fire spreading Yes No No
Fire resistance time of busbar trunking units with fire barriers Yes No No
13
Tab. 10/5: Design verification for BTS in accordance with IEC 61439-6 (VDE 0660-6) back to page 234
14
15
16
17
Intro
duction
5
Current-carrying Type of routing, accumulation, and operating conditions
High current-carrying capacity
capacity determine limit values
Freedom from Standard cables are not halogen- / PVC-free; halogen-free
Trunking units are always halogen-free
halogen / PVC cables are expensive
6 Space
requirements
Compact design due to high current-carrying capacity;
standard angle and offset elements
Large space requirements due to bending radii, type of
routing, accumulation, and current-carrying capacity
Compared to cable, weight reduction to the half or even one
Weight Weight up to 3 times higher than that of a comparable BTS
7 third
Uncomplicated installation possible with simple auxiliary Laborious installation only possible with numerous auxiliary
Installation
tools and short installation times tools; considerably longer installation times
8 Tab. 10/6: Comparison of characteristics of BTS and conventional cable installation back to page 233
9
Decentralized power distribution
10 with busbar
11
12
13
Centralized power distribution
with cable
14
15
TIP04_13_138_EN
16
17
Fig. 10/13: Comparison of routings for cable installation and BTS back to page 234
4 –– Overload protection
• Overtemperature protection.
In the ‘open’ position, they meet the requirements
defined for the disconnecting function
• Well-matched combinations of circuit-breakers, fuses,
Device selection must correspond to the widely varying miniature circuit-breakers, and residual current operated
5 protection tasks the devices have to fulfill, such as line circuit-breakers ensure comprehensive system protection
protection, personal safety, fire protection, lightning in terms of short circuit, overload, and fire protection.
current, and overvoltage protection, as well as equipment Above that, the electrical installation can be protected
6 and system protection (Fig. 11/1):
• Circuit-breakers protect systems, motors, generators, and
against overvoltages as a result of electrostatic discharges,
switching overvoltages, and lightning strikes by the
transformers against overload and short circuit in the coordinated use of lightning and surge arresters. Optimal
16
17
Intro
duction
1
Siemens switching and protection devices (portfolio excerpt)
Circuit-breakers 2
3
3WL air circuit-breaker
4
3RV circuit-breaker for motor protection
6
5SL miniature circuit-breaker
7
5SD7 surge arrester
Fuse systems 11
NEOZED fuse system
12
DIAZED fuse system
16
TIP05_18_015_EN
17
Fig. 11/1: Overview of switching and protection devices back to page 238
Intro
duction
4
Motor starter protection
protection
(MSP)
The most important criteria for switching and protection
device selection are: Tab. 11/1: Distribution of switching and protection devices in the
• Type of application low-voltage power distribution system
5 For example, equipment, motor, disconnector
• 3- or 4-phase design
• Mounting design
6 For example, fixed mounting, plug-in or with-
drawable design
• Type of release
For example, L, S or I (see chapter 6); electronic or
• Rated current In thermal-magnetic; this influences selectivity and
9
ACB
Incoming circuit
10
11
ACB MCCB Si-LT LT-Si
12 Distribution circuit
13
MCCB Si-LT MSP
14
15 Final circuit
16
TIP04_13_124_EN
M M M
17
Fig. 11/2: Distribution of switching and protection devices according to circuit type
Intro
duction
11.2 R
equirements on the Switching maximum short-circuit current, meaning the energy con-
1
and Protection Devices in the tained therein, until the circuit-breaker is tripped. This
requirement is met by circuit-breakers of utilization cate-
Three Circuit Types gory B according to IEC 60947-2 (VDE 0660-101) (for 2
example, air circuit-breakers, ACB). Current-limiting circuit
11.2.1 Use in the Incoming Circuit breakers molded-case circuit breakers, MCCB) trip during
Intro
duction
1 Utilization category
Releases
3 Partial shutdown with the couplers must be taken into
consideration for the reliability of supply. As the coupler
16
17
Intro
duction
16
current is limited)
1) ETU: electronic trip unit 2) TMTU: thermal-magnetic trip unit
Tab. 11/2: Selection criteria for switching and protection devices back to page 242
17
Intro
duction
1 11.3 R
esidual Current and Arc Fault risk of hazardous physiological effects on the human
Detection Devices body. In dependency of the different requirements of
IEC 60364 4-41 (VDE 0100-410) for TN and TT systems,
2 Protection systems for the electrical installations of a appropriate protection devices must be selected
building must also provide for fault and fire protection to (Tab. 11/3).
ensure personal and system protection. Protection against
3 electric shock under fault conditions is referred to as fault
protection (previously: protection against indirect contact).
In everday practice, RCDs of type A (alternating current
and pulsating direct currents) are mainly used. Owing to
To protect a person who is in contact with a live part which the increased use of equipment accommodating power
TIP04_13_125_EN
t in ms
cable bending radii, etc.), as well as on improper handling
9 and lack of maintenance. The use of RCDs and arc fault 2,000
10 200
100
AC-4.2
11.3.1 Residual Current-operated 50 AC-4.1
Protective Devices
11
20
0.1 0.2 0.5 1 2 5 10 20 50 100 200 500 1,000 10,000
Protection measures against electric shock are described
2,000 5,000
in IEC 60364-4-41 (VDE 0100-410). RCDs can be used in
IM: Shock current IM in mA
all network systems (TN, TT, IT system) of a single-phase
12
t: Duration of exposure
or three-phase network. In such networks, RCDs are
superior to other permitted protection devices in their
Range AC-1:
protection effect, since they provide additional protection Perception is possible,
13
but generally no shock reaction.
(protection against direct contact) besides mere fault
protection (protection against indirect contact) if they are Range AC-2:
Perception and involuntary muscle contractions probable,
used with IΔn ≤ 30 mA, and they also effectively prevent but generally no harmful physiological effects.
electrically ignited fires caused by earth-fault currents
14 through IΔn ≤ 300 mA.
Range AC-3:
Strong involuntary muscle contractions.
Breathing difficulties. Reversible impairment of the heart function.
Immobilization (muscle spasm) may occur.
Fig. 11/3 demonstrates the physiological reactions of the
15
Effects increasing with amperage and duration of current flow.
human body to current flow subsumed in amperage Generally, organic damage is not to be expected.
17 In the IT system, a disconnection upon the first fault is not Fig. 11/3: Scope of effects of alternating current (50 / 60 Hz) on the
required, but precautions have to be made that prevent the human body
Intro
duction
TN system TT system
1
Maximum permissible disconnecting 0.4 s (120 V < U0 ≤ 230 V) 0.2 s (120 V < U0 ≤ 230 V)
time according to IEC 60364-4-41
(VDE 0100-410) 2
Ia ≤ U0 / Zs Ia ≤ U0 / Zs
5
Ia ≤ U0 / Zs IΔn ≤ 50 V / RA
Fault currents IF are substantially higher With U0 = 230 V, the following applies
than 5 IΔn in the TN system to the tripping current Ia in case of fault:
Disconnect conditions of RCDs for Ia = (230 V / 50 V) ∙ IΔn = 4.6 IΔn
ensuring the required disconnecting
time ta Type Ia ta1) Type Ia ta1) 6
RCD general > 5 IΔn ≤ 0.04 s RCD general > 2 IΔn ≤ 0.15 s
1)
RCD selective > 5 IΔn
The values for ta refer to the specifications in the relevant product standards.
≤ 0.15 s RCD selective > 2 IΔn ≤ 0.2 s
7
IΔn Rated residual current of RCD in A
RA Sum of resistances of the earth electrode and the protective conductor of the exposed conductive parts
U0 Rated AC voltage of phase to earth
Zs Fault loop impedance 8
Tab. 11/3: Selection of protection equipment in the TN and TT system with rated voltages of 230 / 400 V AC back to page 244
10
Type Type
Current type Current AC A F B B+ Tripping
11
shape current
Half-wave current
overlaid with smooth
up to 1.4 IΔn 14
direct current + 6 mA + 10 mA + 0.4 IΔn + 0.4 IΔn + DC
17
Tab. 11/4: Types of residual RCDs and their tripping ranges back to page 244
Intro
duction
1
Suitable RCD type Circuit Load current Fault current
2
iL iL iF1
B F A AC
iF1 t t
3
iL iL iF1
B+ iF1 t t
α α
4 iL iL iF1
iF1 t t
5 iL iL iF1
6
iF1 t t
iL iL iF1
iF1
7 t t
α α
iL iL iF1
8 iF1
t t
iL iF1 iF2
iL
9 iF1 iF2
M
t t t
10
iL iL iF1
iF1
t t
11 iL iL iF1
iF1 t t
12 iL
iL iF1
iF1
13
t t
iL iL iF1 iF2
14
M
11 iF1 iF2
t t t
iL iL iF1
15 12 iF1
t t
16 iL iL iF1 iF2
TIP04_13_127_EN
13 M
iF1 iF2 t
t t
17
Tab. 11/5: RCD types and possible shapes of fault currents back to page 244
Intro
duction
9
RCD Residual currentoperated protective device
In connection with circuit-breakers
(usually for rated currents > 125 A) 10
MRCD CBR RCCB RCBO
Modular residual Circuit-breakers Residual current Residual current PRCD SRCD 11
current device incorporating residual operated circuit- operated circuit-
(without integral current protection breaker without breaker with over- Portable residual Socket-outlet
12
current breaking integrated overcurrent current protector1) current protective residual current
device) protector1) device, e.g., integrated device (stationary)
in plugs and multiple
socket outlets
Residual current units
(RCU), to be combined
with MCB1)
13
IEC 60947-2
Appendix M
IEC 60947-2
Appendix B
IEC 61008-1
(VDE 0664-10)
IEC 61009-1
(VDE 0664-20)
HD 639 S1/A2
(VDE 0661-10/A2)
Draft VDE 0662
14
(VDE 0660-101 (VDE 0660-101
Appendix M) Appendix B)
15
According to the above standards
16
TIP04_13_151_EN
Protective measure in case of indirect contact, plus direct contact not suitable as protective measure
in accordance with IEC 60364-4-41
with IΔn ≤ 30 mA; additionally fire protection (VDE 0100-410); only local increase
of protection level
17
1) Linevoltageindependent fault detection and tripping
Intro
duction
1 • CBRs are circuit-breakers with residual current protec- Harmless sources of interference, such as drills or hoovers
tion in accordance with IEC 60947-2 (VDE 0660-101) which are operated at the moment, can be distinguished
Appendix B. Here, the residual current detection unit from dangerous arcs by the arc fault detection device. As a
2 is fixed-mounted to a circuit-breaker, thus ensuring complement to residual current operated circuit-breakers
residual current protection and miniature circuit-breakers, the 5SM6 arc fault detec-
• MRCDs are devices in modular design, which means tion device (Fig. 11/7) increases personal safety, protects
3 residual current detection (using current transformers),
evaluation, and tripping (through circuit-breakers) is
material assets, and closes a gap in the protection against
electrically ignited fires. The general requirements for arc
performed in separate modules (in accordance with fault detection devices (AFDD) are specified in IEC 62606
CBRs and MRCDs are intended for applications with The arc fault detection device responds to the following
higher rated currents (> 125 A) in particular. faults:
5 • PRCDs in accordance with HD 639 S1 / A2 • Serial fault with arcing fault
(VDE 0661‑10 / A2) are portable residual current • Parallel fault with arcing fault
devices which are integrated in plugs or in multiple • Overvoltage (however, self-protection in the event of a
6 socket outlets, for example
• SRCDs in accordance with VDE 0662 (draft) are
voltage higher than 275 V).
stationary residual current devices integrated in a If such a fault is detected, the arc fault detection device
7 socket outlet or forming a unit with a socket outlet. trips the mounted miniature circuit-breaker or combined
RCBO. The status LED of the AFDD indicates the detected
PRCDs and SRCDs can be used to increase the protection fault. The fault indication can be reset by switching the
level in applications where the required protective mea- device on-off-on.
8 sure is ensured by other means. They are not permitted
to implement a protective measure with disconnection. In IEC 60364-4-42 the application of AFDD’s is
recommended in:
9 11.3.2 Arc Fault Detection Devices • Premises with sleeping accommodation
• Locations with risk of fire (due to the nature of processed
Over a hundred thousand fires are detected every year in or stored materials)
10 Europe. The shocking outcome: many casualties and
injured, as well as material damage amounting to billions
• Locations with combustible constructional material
• Fire propagating structures
of euros. More than one fourth of these fires can be at- • Locations with endangering of irreplaceable goods.
tributed to arcing faults – frequently caused by defects in
11 the electrical installation. An arcing fault can, among other According to the German implementation VDE 0100-420 of
things, be caused by damaged cable insulation, squeezed the international standard IEC 60364-4-42, the usage of
leads, kinked plugs, or loose contact points in the electrical AFDD must be provided for such applications.
12 installation. The result is heavy heating which may eventu-
ally result in a cable fire and finally a fire of the whole More information: siemens.com/sentron
building.
13 Glowing connections or arcing faults cannot be detected
by conventional protection devices, as they have little
influence on the load current. In order to detect such
14 faults, the arc fault detection device permanently measures
the high-frequency noise (Fig. 11/6) of voltage and current
as well as their intensity, duration, and the gaps in between.
15 Integrated filters with intelligent software analyze these
signals and initiate the disconnection of the connected
circuit within fractures of a second in case of abnormal
16 conditions.
17
Intro
duction
1
Covering the protection gap in the IEC market by using
2
wellproven technology from the UL scope of standards
Fault condition Protection acc. to IEC standard
Serial
L New
Load AFDD 3
N
4
Parallel
Phase-to- L New
neutral/ Load MCB AFDD
phase-to-
phase N
Parallel
Phase-to- L New 5
protective Load RCD AFDD
conductor
N
AFDD Arc fault detection device
MCB Miniature circuit-breaker
6
RCD Residual current-operated protective device
TIP04_13_128_EN
10
11
12
13
14
15
16
17
Fig. 11/7: 5SM6 arc fault detection device back to page 248
Intro
duction
10
11
12
13
14
15
16
17
1 When planning and selecting the control and protection of The trip classes of the motor protection (IEC 60947‑4‑1;
motors, the relevant standards and regulations must be VDE 0660-102) are based on the tripping times at
taken into account. Essentially, these are the standards 7.2 times the current setting Ie in the cold state. The
2 IEC 60947-4-1 (VDE 0660-102) and IEC 60947-4-2 tripping times are:
(VDE 0660-117) as well as the IEC 60364 (VDE 0100) series • Class 5 between 0.5 and 5 s
of standards and the EMC-relevant IEC 61000 (VDE 0839) • Class 10A between 2 and 10 s
3 series of standards. The protection devices must ensure the
protection of the cable and the motor in a motor feeder.
• Class 10 between 4 and 10 s
• Class 20 between 6 and 20 s
This can be achieved with separate devices or through a • Class 30 between 9 and 30 s.
16
17
Intro
duction
12.2 Switching Electric Motors • Continuous running duty S1 and duty with separate
1
constant loads S10
The starting and operating behavior of the three-phase • S2, S3, S6 are duty types that permit an increase in
induction motor is determined by two physical variables: output compared to continuous running duty S1; the 2
the torque and the consumed current. To switch electric result is that the motor is not overloaded
motors, there are electromechanical solutions (direct • S4, S5, S7, S8, S9 are duty types that require a decrease
starter, star-delta starter) and electronic solutions (soft
starter, frequency starters, frequency converters, semi
in output compared to continuous running duty S1; the
result is that the motor will probably be overloaded and
3
conductor switching devices). therefore, a more powerful motor must be configured.
t
Θ
t 8
S2 – short-time duty P
• Constant load state
t
9
• Thermal steady state is not reached
Pv
• Pause long enough for the system cooling until (Θ – Θ0) < 2K
• Temperature limit of the components is not reached ➝ tB,
Θ
t
10
is selected accordingly for only a short time
• (Load current ≥ load time ) t
➝
11
S3 – intermittent periodic duty P
• Constant load state
12
TC t
• Sequence of identical operating cycles
Pv
(load and pause times can vary)
• Thermal steady state is not reached t
13
Θ
• Thermal balance of the system components
is not achieved during heating or cooling t
t
15
Θ
t
16
P load PV electrical losses Θ temperature t time TC cycle time
17
Tab. 12/1: Duty types according to IEC 60034-1 (VDE 0530-1)
Intro
duction
2
t
with long starting time tA, constant load and pause TC
3
Θ
TC t
• Operation time at constant load tP
Pv
6 t
Pv
• No pause
8 Θ
t
14
• Mixture of short-time duty, intermittent periodic duty,
and continuous duty t
16 Θ
t
t
17 P load PV electrical losses Θ temperature t time TC cycle time
Intro
duction
Direct and reversing starters malfunctions may occur during switching under certain
1
circumstances. In this case, contactors may not close or
These devices are a cost-effective solution for switching open.
motors. They ensure a short acceleration time and a high 2
starting torque. Closing:
Intro
duction
1 In the worst case, this results in the following problems: Tab. 12/2 lists typical settings and device dimensions; they
• Short-circuit devices trip are for information purposes only and are not binding. The
• The delta contactor is welded or is subject to high contact settings are application-dependent and must be optimized
2 erosion during commissioning. The load torque (the curve could be
• The motor is subject to a high dynamic stress. constant, linear, square, or inversely proportional like for
mills) and the motor torque curve influences selection and
3 Current peaks can be minimized through a preferred con-
nection during the switchover.
parameterization of the soft starter. These tasks are simpli-
fied by the software “STS”.
12 The motor feeder between the soft starter and the motor
must not contain any capacitive elements (e.g., no reactive
power compensation system). In order to avoid faults in
13 the compensation system and / or soft starter, neither static
systems for reactive power compensation not a dynamic
power factor correction (PFC) may be operated during the
starting and stopping of the soft starter.
14
When selecting a soft starter, it is important that the appli-
cation and the starting time of the motor are considered
15 closely. Long starting times mean a thermal load on the
soft starter. The software “STS” (Simulation Tool for Soft
Starters) can be used to simulate and select Siemens soft
16 starters, taking into account various parameters such as the
network conditions, motor data, load data, and special
application requirements.
17
Intro
duction
6
Stopping method Soft stopping Soft stopping Free stopping Free stopping Free stopping Free stopping
8
Starting parameters
• Voltage ramp and current
limiting
– Starting voltage % 30 30 30
– Starting time
– Current-limiting value
s 30
·
4 IM
30
·
4 IM
10
·
4 IM 9
• Torque ramp
10
– Starting torque % 30 30 30
– Final torque % 150 150 150
– Starting time s 30 30 30
• Break-away pulse Deactivated (0 ms) Deactivated (0 ms) Deactivated (0 ms)
Stopping method Free stopping Free stopping Free stopping of DC braking 11
15
• Torque ramp
– Starting torque % 20 50 50 20
– Final torque % 150 150 150 150
– Starting time s 60 60 60 60
• Break-away pulse Deactivated (0 ms) 80 %, 300 ms 80 %, 300 ms Deactivated (0 ms)
16
Stopping method Free stopping Free stopping Free stopping Free stopping
Tab. 12/2: Examples of starting methods and settings for different applications back to page 256
17
Intro
duction
1 As the soft starter has a reduced starting torque, it is not Because of the increasing use of variable-speed drives, the
suitable for all applications. The starting torque of the load assessment of network disturbances is also increasingly
must be less than or at the most equal to the starting important. Not only the operators of supply networks, but
2 torque of the motor. Typical applications are: also the operators of variable-speed drives are demanding
• Conveyor belts, transport systems: more information from the manufacturers about the
–– Jerk-free starting response of the drives to harmonic effects, so that they can
3 –– Jerk-free braking already check during the planning and configuration
phases whether the limit values of the standards will be
• Rotary pumps, piston pumps
–– Avoidance of pressure surges adhered to. Line reactors or active filters must be provided
14 Note: Frequency converters are also available for 1- and The IEC 61800-3 (VDE 0160-103) standard “Adjustable
2-phase alternating current motors. speed electrical power drive systems – Part 3: EMC require-
ments and specific test methods” defines the EMC require-
15 Particularities of frequency converters are network dis ments for variable-speed electric drives. A variable-speed
turbances and the effect on the EMC. As described in electric drive system (PDS, power drive system) as defined
chapter 5, converters produce harmonic currents and in this standard comprises a drive converter and the electric
16 voltages. As the other equipment in the network is
designed for sinusoidal voltages, a distortion of the
motor including the connection cables. The driven machine
is not part of the drive system.
voltage can have negative effects or even destroy the
consumers and electrical equipment.
17
Intro
duction
Torque ramp
The free stopping is extended by the torque ramp. This function is used to prevent the load stopping suddenly. This
is typical of applications with a small moment of inertia or high counter torque (for example, conveyor belts).
8
Pump stop is used to prevent water hammer when the pump is switched off. This reduces noise and the stressing of
Pump stop
9
the pipes and any flaps contained therein.
Free stopping is shortened by DC braking. DC braking should be used for applications with large moments of inertia.
DC braking The moments of inertia of the load should not be more than 5 times the moments of inertia of the motor:
·
JLoad ≤ 5 JMotor
Dynamic DC braking /
Compound braking
Free stopping is shortened by DC braking. Compound braking is recommended for applications with small moments
of inertia: 10
JLoad ≤ JMotor
Tab. 12/4: Stopping methods for soft starters and their meaning back to page 258
11
Line filters are used to reduce the radiation. These also limit • Pulse frequency fP of the inverter
the network disturbances. An electromagnetic-compatible • Converter output with or without motor reactor of 12
installation is required so that the line filters can achieve motor filter
their maximum effect. A shielded cable is required between • Impedance ZW (cable impedance) or capacitance C of the
the converter and the motor so that the parasitic currents
can flow back to the converter along a low-inductance
motor cable
• Inductance of the earthing system and all earthing and
13
path. The motor cables should have a symmetric conductor shield connections.
structure.
The length of the motor cable must also be taken into 14
The most important factors with regard to high-frequency account. Particularly with shielded cables, the cable capaci-
leakage currents are: tance increases with the cable length and causes additional
• Size of the DC-link voltage current peaks. This current must also be supplied by the 15
• DC-link voltage UZK of the converter frequency converter which may result in overload and
• Rate of voltage rise du / dt when switching therefore the shutdown of the converter.
16
17
Intro
duction
• Lay the cables close to the earthed plates and not freely With a direct starter, the motors are stressed thermally and
4 in the cabinet
• Always install RFI suppression filters close to the sources
mechanically by the high current that is applied immedi-
ately. Voltage changes are also induced in the feeding
of interference network. In order to limit these disturbances in the net-
• Connect the shields of the digital signal leads at both work, apparent power limit values are specified for the
5 ends and with good conductivity over a large area to direct start in the Technical Connection Conditions (TCC)
earth (if required, several times) of the German distribution system operators (DSO). The
• Connect the shields of the analog signal leads with good following are permitted for motors that start occasionally
6 equal potential bonding at both ends to earth. If low-fre-
quency interference occurs, connect the shield at one
(twice a day):
• Alternating current motors with an apparent power of
end to the converter. The other end of the shield should not more than 1.7 kVA or
• Connect contactors, relays, etc. in the control cabinet The soft starter increases the motor voltage within a speci-
with RC elements, diodes, and varistors. fied starting time. The starting voltage should be selected
11 according to the break-away torque for the motor starting.
For example, the break-away pulse can be set for the
SIRIUS 3RW44 soft starter. With the inside-delta circuit
12 (Fig. 12/2) for soft starters, the rated current can be limited
to 1 / √3 = 0.58 times the value of the rated motor current.
17
Intro
duction
1
Direct Star-delta Soft starter Frequency converter
U
100 %
U
100 %
U
100 %
U
100 % 2
Terminal 70 % UBoost
58 %
3
voltage
30 %
4
I I I I
Starting 5
current
TIP04_13_139_EN
Motor speed Motor speed Motor speed Motor speed
Fig. 12/1: Characteristic behavior of the various circuits during motor starting back to page 260
9
10
L1 L1
L2 L2
L3
N
L3
N
11
PE PE
12
U2 L2
U1
T1 T2
V1
13
L1 V2
W2 W1 T3 L3 14
TIP04_13_140_EN
Fig. 12/2: Comparison of circuits for soft starters between standard circuit and inside-delta circuit back to page 260
16
17
Intro
duction
1 12.4 Safety of Machines • Better chances in the worldwide market through compli-
ance with the required approvals and conformance with
Manufacturers and operators of machines are legally the EU directives
2 obligated to guarantee the safety of people and the envi- • Simplified maintenance and plant expansion thanks to
ronment. In other words: machines that are manufactured long-term product and system availability.
or operated in Europe must be safe – irrespective of
3 whether they are new or used. Also for economic reasons,
any risk that may emanate from a machine, should be
In Europe, machine manufacturers (product safety) and
machine operators are legally obligated to guarantee the
avoided from the start. The safety of machines and plants safety of people and the environment. Lots of other coun-
8 Greater cost-efficiency
Compliance with the Machinery Directive can be guaran-
• Minimization of the number of types teed in different ways:
• Minimization of the costs due to only one bus and one • In the form of a machine acceptance through a certifica-
9 engineering system tion office
• More easily reproducible series machines through intelli- • By satisfying the harmonized standards
gent software solutions. • Through a separate safety certificate with increased test
10 Greater standardization
and documentation work.
Intro
duction
1
Basic safety requirements Basics standards
in the manufacturing industry for safetyrelated control functions
"Occupational Safety and Health" Design and implementation of safetyrelated control units 4
e.g., machines Framework Directive
(89/391/EEC) IEC 62061 (VDE 0113-50) ISO 138491
Harmonized standards
Safety of machines Safety of machines
Individual
(presumption of
conformity)
Functional safety of safety-related
electric, electronic and programmable
control systems
Safety-related components
of control units,
Part 1: General design guidelines
5
Low-Voltage Machinery
Directive "Use of Successor to EN 954-1
Directive Directive
Work Equipment"
(2014/35/EU) (2006/42/EU)
(2009/104/EC) General architectures
Safety integrity level (SIL)
Intended architectures (categories)
Performance level (PL)
6
SIL 1, SIL 2, SIL 3 PL a, PL b, PL c, PL d, PL e
Harmonized European National statutory provisions
7
standards
TIP04_13_122_EN
Manufacturer User Electrical safety aspects
IEC 602041 Safety of machines Electrical equipment of machines,
(VDE 01131) Part 1: General requirements
8
Fig. 12/3: Directives and standards for the functional safety of machines back to page 262
10
11
12
13
14
15
16
17
Intro
duction
10
11
12
13
14
15
16
17
1
In the guidelines for the connection of embedded or dis- The VDEW guideline “Emergency generators – Guideline for
tributed generation systems, emergency generators are the planning, installation, and operation of systems with
2 considered as such and a distinction is made according to emergency generators” (2004 edition) describes the con-
the connection to the supply network. The following are nection conditions for UPS installations and explains the
defined as power sources for safety purposes according to methods of operation of emergency generators in different
3 IEC 60364-5-56 (VDE 0100-560):
• Storage batteries
system configurations (for further information on emer-
gency standby power systems and uninterruptible power
• Primary cells supply systems (UPS systems), refer to chapter 13.1 and
• A separate feed-in (for Germany, supplemented by Electronic components do not only play a part as power
a “dual system”) from the supply network that is really consumers (for soft starters and frequency converters, see
5 independent of the normal supply. chapter 14) but also as a source of energy. In wind power
plants and photovoltaic systems, the generated power is
fed in using network-conforming converters whose distur-
6 bances can affect the network environment.
10
11
12
13
14
15
16
17
Intro
duction
1
13.1 UPS Systems
Dynamic UPS systems
The use of a UPS system is for the protection of sensitive 2
consumers in the normal power supply system (NPS) and to Dynamic UPS systems Dynamic UPS systems
ensure their safe, continual operation during power failures as machine unit as machine unit with
TIP02_12_019_EN
additional reciprocating
(see Fig. 2/6). The proper integration of the UPS system internal combustion
into the network concept is of vital importance for the engine
availability of the entire power supply system. The follow-
ing general aspects concerning UPS should be considered
in the planning:
Dynamic UPS
systems with
Dynamic UPS
systems with
Dynamic UPS
systems as
Dynamic UPS
systems as
4
directly coupled storage battery or no-break standby quick-starting
• Selectivity for the switching and protection function in kinetic storage cell equivalent kinetic generating set standby generating
conjunction with the UPS system storage cell (without set (with short-time
TIP02_12_020_EN
a static UPS system.
Diesel
engine
Electro-
magnetic
Flywheel Synchro-
nization
10
coupling machine
13.1.1 Dynamic UPS Systems
DIN 6280-12 describes the different types of dynamic UPS Fig. 13/2: Schematic view of a dynamic UPS system using
a combination of diesel engine, flywheel, and generator power
11
systems (Fig. 13/1). The two main components of a dynamic
UPS system are the electric motor and the generator,
synchronized as a machine unit. Following the standard, 12
the critical consumers are supplied by the generator.
The operating modes of dynamic UPS systems in accor-
Although the machine unit has a low kinetic energy for
bridging voltage failures in the millisecond range, this very
dance with DIN 6280-12 permit further distinctions to be
made:
13
short period can be extended to a limited time, mostly in • Standby active mode (quick starting: 2 to 500 ms
the range of seconds or minutes, by using flywheel energy interruption time)
storage and / or battery systems. The bridging time can be • Continuous operation mode (electrically isolated load 14
extended by connecting a diesel engine. Then, the interme- supply through UPS: no break)
diate storage systems must supply the generator with • Active following mode (uninterruptible transfers between
energy for so long until the diesel engine has run up to load supply from the normal network and load supply 15
speed (Fig. 13/2). from the synchronized UPS: no break).
16
17
Intro
duction
1 Please note that this classification does not correlate with frequency-independent) provides an independent supply
the classification of static UPS systems (see Fig. 13/3). quality for the consumers. In the voltage-independent (VI)
Even in the continuous mode, the dynamic UPS may be UPS, the voltage is set independently of the UPS input
2 frequency-dependent if the line voltage is not transformed voltage, whereas in an off-line circuit (VFD, voltage- and
into a so-to-speak independent supply voltage for the frequency-dependent) both the voltage and the frequency
motor using a converter. at the UPS output depend on the conditions at the input. In
3 An active standby mode, for example, is not feasible for the
any case, planning must take into account that network
disturbances and the consumers’ load requirements have
IT components in the data center, since manufacturers of an influence on the supply at the UPS input.
17
10. Frequency variations sporadic –
Tab. 13/1: Types of line faults and matching UPS solutions based on IEC 62040-3 (VDE 0558-530) [13]
Intro
duction
A current trend which may be important for the planning In this context, it must be kept in mind that initially an
1
of reliable power supply is the extendibility and redesign investment must be made in oversizing parts of the modu-
capability gained from modular UPS systems. A modular lar system, which is often worthwhile only if the factual
UPS system allows the integration of extension modules extension corresponds to the planned scope of extension. 2
into an existing system when performance demands are Above that, the system operator binds himself to a specific
rising. To this end, a possible final brown field scenario UPS model so that the framework parameters for subse-
should already be on hand when operation starts. It is
frequently argued that although the initial cost of invest-
quent purchases of modules may best be considered prior
to the first purchase. Model changes make subsequent
3
ment is somewhat higher, the investment total can be purchases much more difficult and expensive in most
reduced by the lower cost for the extension modules.
Moreover, easy extendibility and fast swapping of modules
cases.
4
shall reduce the UPS failure period in case of a fault –
thus increasing availability as against a conventional UPS
solution. 5
7
a) 1
Supply
network
Load
Normal mode 1 Switching device 8
without influencing
2 Rectifier / charger
2 3 4
3 Battery 9
4 Inverter
5 4-quadrant inverter
10
b) 7 6 Static bypass switch
Supply
network
Normal mode
using 4-quadrant
7 Manual bypass switch
11
inverter (5)
Load
12
3 5
13
c) 7
Normal mode
14
TIP02_12_021_EN
15
network
2 3 4 6
Fig. 13/3: UPS systems with energy flow during normal operation: back to page 268
16
a) Off-line UPS system (VFD)
b) Line-interactive UPS system (VI)
c) On-line UPS system (VFI) 17
Intro
duction
Intro
duction
The power generating station also includes the auxiliary Medium voltage has the following advantages:
1
equipment such as exhaust system, fuel system, switch- • Larger loads can be transmitted more easily over longer
gear, and the installation room (Fig. 13/4). This then con- distances
stitutes a complete emergency standby power system. The • Better power quality in extensive networks (voltage drop) 2
purpose of use and the design have not been taken into • More favorable energy purchase price for power
account yet. consumption (clue: approx. 20 % advantage over low
voltage)
• In case of “Protection through disconnection” as
3
Integration into the network concept
protective measure in the TN-S system, the required
The following selection criteria for the emergency standby
power system must be taken into account because of the
short-circuit current is much more easy to attain.
4
consumer-dependent boundary conditions of the SPS such Medium voltage has the following disadvantages:
as power requirements, power distribution concept, simul- • Cost-efficiency should be checked when the power
taneity factor, and reserves for expansions: requirement is less than approximately 400 kVA 5
• Supply at the medium-voltage or low-voltage level • Expenses for the protection concept rise with the size of
• Distribution of the SPS load over several ESPSs connected the networks
in parallel or supply via one large ESPS
• Central installation or distribution of the individual power
• (Additional) transformers with the associated switchgear
and appropriate protection are also required in the
6
supplies close to the SPS consumers. network for the safety power supply
13
14
Exhaust air Supply air
muffler muffler
15
TIP04_13_141_EN
Switchgear
16
17
A
Intro
duction
1 Switch-on and operating behavior of consumers Room planning and system components
The starting or switch-on behavior of electric motors, When planning the generator unit room, the local building
2 transformers, large lighting systems with incandescent regulations must be taken into account. The planning of
lamps, or similar, has a major effect on the generator unit the generator unit room can also have a significant influ-
output. Especially when there is a large proportion of ence on the acquisition costs of an emergency standby
3 critical consumers in relation to the generator unit output,
an individual test must be performed. The possibility of
power system. The installation room should be selected
according to the following criteria:
staggering the connection of loads or load groups signifi- • Short cable routes to the feed-in point (low-voltage main
160
Dynamic response
TIP01_11_015_EN
8
140
The dynamic response of the generator unit at full-load
Spatial volume in in m3
120
connection and for the load changes to be expected must
100
be adapted to the permissible values of the consumers. The
9 design class of the generator unit in accordance with 80
400
If no particular measures are taken, the unit generators
14
350
Fuel consumption in l/h
Intro
duction
10
11
12
13
14
15
16
17
Intro
duction
1 13.2.2 Wind Turbine • The phase asymmetry (ratio of the voltage’s negative-
sequence component to the positive-sequence compo-
A wind turbine basically consists of the rotor system, the nent) shall not exceed 2 % (15 % for small wind turbines
2 nacelle with the generator (directly driven or geared), the in extreme conditions)
frequency converter, and the tower. A certified monitoring • Automatic reconnection period(s) must be within 0.1 s
and control system is crucial for the continuous adjustment and 0.5 s for the first reconnection (between 0.2 s and
3 of operating parameters to the actual wind conditions.
Every wind turbine requires reliable auxiliary power supply
0.5 s for small wind turbines) and for a second reconnec-
tion between 10 s and 90 s.
in order to supply the many auxiliary circuits (for example,
Intro
duction
1
Increasing performance and cost – higher risk
2
Rotor diameter
3
5
Rotor hub height
TIP04_13_143_EN
7
1990 2012
Rating
Rotor diameter
250 kW
30 m
1,500 kW
70 m
3,000 kW
90 m
6,000 kW
126 m
8
Rotor hub height 50 m 100 m 105 m 135 m
9
Annual output 400,000 kWh 3,500,000 kWh 6,900,000 kWh approx. 20,000,000 kWh
Fig. 13/8: Technical development of wind turbines from 1990 until 2012 back to page 274
10
1 Wind turbine Wind farm
– Automation / SCADA / HMI
– Busbar trunking systems
11
– Circuit protection systems
– Electric drives
– Generator / inverter
– Video surveillance
4
12
2 Medium-voltage
13
transformer
5
3 Medium-voltage switchgear
– Circuit-breakers
7
– Switchgear panels
4 Control center
– Automation 3
14
– Monitoring
– Control
5 Feed-in meter 2
15
6 Operation and servicing
– Preventive maintenance
16
TIP04_13_144_EN
– Repair 6
7 Transformer substation and 1
high-voltage overhead lines
17
Fig. 13/9: Embedding wind turbines into the electric power distribution grid back to page 274
Intro
duction
1 13.2.3 SIESTORAGE Energy Storage System of production plants. Such a failure means an enormous
loss of quality and time, along with noticeable financial
Electric power generation based on renewable energies is damage.
2 a key element for restructuring a strongly fuel-oriented
energy business towards more sustainability. Besides Storage characteristics
water power, wind and solar energy play the crucial part
3 in this context. The use of renewables on a large scale,
however, leads to new challenges for grid stability: Pro-
Traditional energy storage systems (Fig. 13/10) cannot
necessarily ensure stable grid operation in the lower distri-
ducers of wind and solar energy are usually not capable of bution grid levels today. A storage solution is called for
Technology
Chemical storage systems
Li-ion
batteries SIESTORAGE Electro-chemical storage systems
14
NaS
Minutes
15 Electrical double
Maturity
TIP04_13_145_EN
Power
1) CAES: Compressed Air Energy Storage
17
Source: Study by DNK/WEC: "Energie für Deutschland 2011"; Bloomberg technologies Q2 2011
Intro
duction
12
Transformer System control
13
Filters
AC/DC
Converter control 14
=
Data logging 15
TIP05_18_011_EN
Liion
Series
connection
battery
module
Battery management
16
17
Fig. 13/11: Schematic design of SIESTORAGE
Intro
duction
1 If the customer takes over the risk of such fluctuations, this power and simultaneously achieve a good forecastability of
will become noticeable in a better pricing. This energy de- the power drawn from the distribution grid operator
mand forecast, known as schedule clause in ¼ h electricity (Fig. 13/13).
2 supply contracts, is gaining increasingly more importance
in this context (Fig. 13/12). The customer submits to his Two vital factors which are to be observed when planning
distribution system operator (DSO) a forecast of his energy a combined system are the size relations between power
3 demand (EU-wide always on Thursdays), in which optimiza-
tions at 24 h notice are permitted. The procurement of
generation and storage plus the so-called C factor for the
charging / discharging characteristic of the storage system.
these forecast energy quantities is up to the electricity The C factor is defined as the quotient from the current and
± 10 %, for example. So far, forecasts are optional for the C factor = current / charge
customer and result in more favorable price conditions, but = 1 / time (output / accumulator capacity in h-1)
5 in the long run, they will become mandatory with smart
grids paving their way. Example: When a storage system with a capacity of 400 Ah
is discharged, a C factor of 2 C means that a current of
6 Example for the interaction of power generation from 800 A can be output. Vice versa, with a C factor of 6 C,
a continuous charging current of about 2,400 A can be
a photovoltaic system and energy storage systems
assumed for recharging. To establish the charging
Forecast optimization
10 150
kWh
Energy purchase
100
50
Dependencies
11
0
between power
generation, use,
-50
0:15 6:15 0:15
12
generation and kWh
9,000
storage behavior 8,000
7,000
6,000
5,000
4,000
13
3,000
2,000
1,000
0
Monday Tuesday Wednesday Thursday Friday Saturday Sunday
Smart meter
15
800
Controlling/
1,800
700 1,600
600 Limit
regulating
1,400
500
Schedule
1,200
TIP04_13_147_EN
400
300 - Consumption 1,000
800
200
100 Consumption - Generation 600
- Storage
0 400
16
11:00 11:05 11:10 11:15 200
0
17
Fig. 13/12: Transparency of the energy flows
Intro
duction
In our example, we assume a sunny weekly load curve for The evaluated scenario assumes a forecast for sun radia-
1
power deployment by a PV system with a power peak of tion. The peak value for the feed-in curve is then calculated
1,000 kWp (index p for peak) as shown in Fig. 13/14. A day-specifically in such a way that it yields the forecast
possibly feasible scenario assumes feed-in with an ideal PV energy quantity together with the ideal PV curve shape, 2
curve whose output peak is adapted daily to the forecast which is equal to the energy quantity from the PV output
noon peak for sun radiation. The difference between power curve for the individual day. Though the peak of the ideal
generation from the PV system and the feed-in load curve
of the scenario defines the sizing of the SIESTORAGE en-
PV curve thus varies in amplitude (Fig. 13/14), the energy
balance at midnight is always equalized (Fig. 13/15).
3
ergy storage system. It is expected that the storage system
is completely discharged at the beginning of the assess-
ment period (storage content 0 kWh).
In this case, the storage capacity needed amounts to about
900 kWh, so that two standard storage containers with 4
a total capacity of 1 MWh will be sufficient. The maximum
For the evaluation, the difference quantities between charging power per hour which will be fed into the storage
power generation and hourly mean feed-in are formed. A container from the PV system is 350 kW, and the maximum 5
positive difference means that the storage system is being power drawn is 200 kW. Hence a C factor of 3 C is suffi-
charged during the hour under assessment, whereas it is cient. In this scenario, the investment required is within
discharged in case of a negative result. The required stor-
age capacity of the SIESTORAGE results from the difference
acceptable limits so that a business assessment could be
worthwhile.
6
between the maximum and minimum value of this weekly
curve in each case. No statement is made about costs and
C factors, since this is always a project-specific task.
7
8
PV system SIESTORAGE
9
1,200 kW 600 kW
10
1,000 kW 400 kW
11
800 kW 200 kW
600 kW 0 kW
400 kW -200 kW
200 kW -400 kW
0 kW
08/02 08/03 08/04 08/05 08/06 08/07 08/08 08/09
-600 kW
08/02 08/03 08/04 08/05 08/06 08/07 08/08 08/09
12
13
1,000 kW
Power distribution
14
800 kW
600 kW
400 kW
200 kW
0 kW
08/02 08/03 08/04 08/05 08/06 08/07 08/08 08/09
15
TIP04_13_148_EN
Consumers
16
back to page 278
17
Fig. 13/13: Power supply concept integrating photovoltaics and a SIESTORAGE energy storage system
Intro
duction
7 1,000 kW PV system
Feed-in load curve
800 kW
8 600 kW
400 kW
9
200 kW
TIP04_13_149_EN
10 0 kW
08/02 08/03 08/04 08/05 08/06 08/07 08/08 08/09
11 Fig. 13/14: Weekly curve of PV power and the desired feed-in power according to the forecast about sun radiation provided the day before
back to page 279
12
13
600 kWh
Storage load
min
400 kWh max
14
0.9 MWh
200 kWh
0 kWh
15
08/02 08/03 08/04 08/05 08/06 08/07 08/08 08/09
-200 kWh
TIP04_13_150_EN
-400 kWh
16
-600 kWh
17 Fig. 13/15: Weekly curve of the energy required which a storage system is to supply, respectively take in, based on the power ratios
from Fig. 13/14 back to page 279
Energy efficiency Even during the planning process, electrical planners are
9 increasingly expected to consider the lifecycle costs. How-
Energy efficiency specifies the relationship of benefit to ever, the limits established when dimensioning the electric
cost. Differing efficiency considerations are possible such as power distribution are unsuitable for determining the cost
10 energy consumption, time, overall costs, operating costs,
environmental burdens, and many more. Often, individual
for losses which reflect actual operating conditions. The
power losses of transformers, busbar trunking systems, and
criteria are consciously combined in efficiency consider- cables figure prominently in lifecycle cost calculations
ations to substantiate a conclusion reached. Relations under the envisaged operating conditions. Current is
11 between differing factors can also be drawn. For instance, factored in with its square value.
consideration can be given in an eco-balance to the rela-
tionship between material deployment at the manufactur- For an ohmic load, power loss Pv is calculated
12 ing stage and energy consumption under operations. As the from (current I, specific resistance R):
degree of efficiency is physically clearly defined as the
relationship between active power for use and the total Pv = I2 · R
13 active power to be applied, it must not be put on the same
footing as energy efficiency. The loss costs are the product of electricity price and energy
losses. However, without a realistic load curve for the
period under review, it is not possible to obtain an estima-
14 Energy transparency
tion of energy consumption that reflects operating condi-
Energy transparency creates the data basis for actions, tions. After all to establish the energy losses, the time-
reactions, handling instructions, and improvement mea- specific power losses characterized by the load curve are
15 sures. Basically, energy transparency is part of operational integrated over the period under consideration and – in
management, since energy flows can only be analyzed with connection with the electricity prices – the contribution
precision in practice. Even so, it is often overlooked that to the lifecycle costs is defined.
16 the measuring, evaluation, and data management systems
are the basis for energy transparency. On average, 5 % of the energy procured is dissipated into
heat as energy losses within an electric power distribution
system. Owing to consumption-optimized dimensioning of
17 individual distribution system components, such as trans-
formers, busbar trunking systems, and cables according to
Intro
duction
7
Distribution
Electricity Supplier
System Operator
8
Power Management Power Distribution
9
- Coordination of procurement
- Coverage of energy Feed-in
application requirements
- Focus on economic /
10
ecological goals Transformer Generator
G
(in-plant power generation)
11
Energy Transparency
- Documentation and
evaluation of energy flows
12
UPS
Distribution
13
14
Intro
duction
1 To ensure transparency of system operation, it is useful Leased or tenant areas are billed on the basis of energy
to measure voltage U in V, current I in A, the power consumption W in kWh. A power meter records the con-
factor cos φ, and total harmonic distortion THD as the sumption. Here, it must already be clarified in the planning
2 sum of all harmonics (separately for the voltage and stage, whether this meter must be a calibrated meter
current) at the transformer in addition to the above-men- for billing purposes. A non-certified meter is sufficient if
tioned apparent power S (Fig. 14/2). A generator is invoicing is only done internally via cost centers. For billing
3 treated like a transformer, but in addition, the produced
energy W must be measured in kWh.
purposes, it is essential that an MID-conforming instrument
is used in accordance with the European 2004/22/EC
Measuring Instruments Directive (MID).
6 Recommended Measurements
Transfer meter of
8 Transformer G Generator U
I
U, I, S of all 3 phases
Power factor
G U
I
U, I, P, W of all
3 phases
S P
cos of all 3 phases W Power factor
Distribution THD THD of all 3 phases cos of all 3 phases
9
I I of all 3 phases
I or
10 cos cos φ of all 3 phases
12 P
Leased equipment P
W Billing meter
Wtotal over all 3 phases
TIP04_14_153_EN
14
Permissible voltage drop for lighting for other electrical equipment
Low-voltage installation supplied directly 3 % 5 %
15 from the public grid
Low-voltage installation supplied 6 % 8 %
from a private power supply system*)
16
*) The voltage drop is preferably not to exceed the values for public grids
Tab. 14/1: Permitted voltage drop in accordance with IEC 60364-5-52 (VDE 0100-520) from the distribution grid – consumer installation
interface to the connection point of a consumer (main wiring system up to 100 m in length)
17
Intro
duction
14.2 G
raphic Representations in 1
Energy Management 8,000 kW
TIP04_13_154_EN
2
7,000 kW
The measured values as rows of figures constitute the basis 6,000 kW
for various graphics in an energy management system. 5,000 kW
Normally, users can only understand the response of
3
4,000 kW
individual system components and the interconnection
3,000 kW
between energy usage and corresponding energy demand
by analyzing the graphs of the measured values. 2,000 kW
4
1,000 kW
TIP04_13_155_EN
at 15-minute intervals
7
5,000 kW
Mean active power P = E / 0.25 h. Load curve
Maximum
4,000 kW
–5%
Load curves 3,000 kW
– 10 %
17
Intro
duction
1 The weekly load curve (Fig. 14/5) brings out clear day- 6,000 kW
specific differences:
TIP04_13_156_EN
• Daily demand
2
5,000 kW
• Daily variations
4,000 kW
• Typical work-shift patterns
• Demand peaks. 3,000 kW
curve (Fig. 14/6) so that, for instance, the following points 1,000 kW
4 can be recognized:
• Precise representation of the daily demand and moments
1 kW
Monday Tuesday Wednesday Thursday Friday Saturday Sunday
of change
• Breaks Fig. 14/5: Weekly load curves for a measuring point
5 • Work-shift changes.
TIP04_13_157_EN
Early Shift Late Shift
5,000 kWh
Even during building planning phases, statements as to
the lifecycle costs – lying well into the future from the 4,000 kWh
13 Office building with ventilation Office building with air conditioning system
2.40 2.20
2.23 2.03
2.20 2.00
14 2.00
1.80
Mon - Thurs
1.80
1.60
Mon - Thurs
Factor
Factor
1.60 Fr 1.40 Fr
Sat + Sun Sat + Sun
1.40 1.20
15
Mean value Mean value
1.20 Peak factor
1.00 Peak factor
1.00 0.80
0.80 0.60
0.60 0.40
16
1:00
2:00
3:00
4:00
5:00
6:00
7:00
8:00
9:00
0:00
1:00
2:00
3:00
4:00
5:00
6:00
7:00
8:00
9:00
0:00
10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00
18:00
19:00
20:00
21:00
22:00
23:00
10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00
18:00
19:00
20:00
21:00
22:00
23:00
Time Time
TIP04_13_158_EN
17 Fig. 14/7: Examples of synthetic load curves for specifying the energy consumption in offices back to page 287
Intro
duction
Note: For the lifecycle costs, it is also necessary to plan The Siemens TIP Consultant Support contact partner
1
both the depreciation or reinvestments for replacement provides personal planning assistance in the analysis of
of components and the service and maintenance losses for transformers and busbar trunking systems.
expenses. In this context, technical as well as economic With the aid of given synthetic load curves, they can – 2
aspects have a major role to play. by using the values established in SIMARIS and the
selected products – carry out a loss and cost analysis.
To estimate energy losses in the planning process, the
loss can be integrated across the service life through the
The TIP Consultant Support contact partner can then
compare energy and costs with the Siemens portfolio
3
synthetic load curves. The prerequisite here is the cyclic products. To illustrate the matter, the power losses of
repetition of the curve progression, e.g., for a day during
the planned operating behavior. Conditional upon the use
selected GEAFOL transformers are entered in Fig. 14/8.
This permits a direct comparison to be made between 4
patterns, consideration can, of course, be given to differ- different power outputs. The synthetic load profiles (with
ent, day-specific load curves as, for instance, the differ- the number of operating hours shown at a certain power
ences between office working days and weekends and demand above the related load value, see chapter 14.3) 5
public holidays, as well as possibly the vacation period. for an identical power range, which result from the syn-
thetic load curves for the various building types, serve to
The modelling for building use can, of course, also be
elaborated upon. For example, the synthetic day load
make it clear that raising the power by forced ventilation
of the transformer is sometimes appropriate, or that
6
curves of an office with air conditioning differ from those selecting a larger transformer involving a greater invest-
of a ventilated office (see Fig. 14/7). At the same time,
various curves can be drawn and evaluated for rooms of
ment provides for benefits in operation.
7
different uses in the building, such as those solely fitted Note: If a larger transformer is established and a new
out with desks, or for canteens and kitchens in office calculation is performed in Simaris design, then other,
buildings. Process-specific cycles such as shift, charge, or usually larger appliances can be dimensioned. 8
batch operation periods can be chosen for industrial
processes.
17
building types
Intro
duction
4 Load profile
frequency distributions are:
• Load peak characteristics
• Continuity of procurement
In terms of the load profile, the power values are shown on • Shift models
5 the X-axis, and the number of hours in which the respec- • Base load.
tive value was measured are shown on the Y-axis. The
power profile, which is based on the power values measured Evaluation of maxima
6 every 15 minutes, starts with the base load and ends with
the maximum procured power. The load profile allows to In the maxima representation (Fig. 14/11), the highest
identify the main power areas, meaning the most fre- measured power values including the time stamp are
12 300 h 8,000 kW
TIP04_13_160_EN
TIP04_13_161_EN
7,000 kW
250 h
13 200 h
6,000 kW
Frequency distribution
Mean curve progression
5,000 kW
150 h 4,000 kW
14 100 h 3,000 kW
2,000 kW
5h
1,000 kW
16 Fig. 14/9: Load profile of a measuring point over one year Fig. 14/10: Frequency distribution over one year and mean curve
progression
17
Intro
duction
4,000 kW 8
TIP04_13_162_EN
3,900 kW
3,800 kW
9
10
3,700 kW
3,600 kW
3,500 kW
11
3,400 kW
3,300 kW
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
12
15 min. value
3,904 kW
Date/Time 15 min. value
12.1.10 9:00 3,816 kW
Date/Time 15 min. value
12.1.10 8:45 3,792 kW
Date/Time
11.1.10 10:45
Peak cutting • by 5 % 3,709 kW
• by 10 % 3,514 kW 13
3,856 kW 12.1.10 10:30 3,816 kW 12.1.10 8:45 3,792 kW 11.1.10 10:45
3,848 kW 13.1.10 8:30 3,808 kW 12.1.10 9:00 3,784 kW 11.1.10 8:15
3,848 kW 13.1.10 8:30 3,800 kW 12.1.10 11:45 3,784 kW 11.1.10 8:15 Difference between highest
3,832 kW
3,824 kW
12.1.10 11:00
12.1.10 9:15
3,792 kW
3,792 kW
11.1.10 10:45
11.1.10 10:45
3,776 kW
3,776 kW
13.1.10 8:15
13.1.10 8:15
and 20th value: 3 %
14
15
Fig. 14/11: Maxima view as a ranking of peak load values back to page 288
16
17
Intro
duction
9
Lower consumption Present Lower power peak
–10 % AEP –10 %
10 21,160,000 kWh 23,511,492 kWh 23,511,492 kWh
15.5 7,086 kW 7,086 kW 6,400 kW
3,178,000 € 3,436,500 € 3,351,500 €
11
15.02 kWh
Ct
14.62 kWh
Ct
14.25 kWh
Ct
15.0
AEP in Ct/kWh
12 14.5
14.0 Price
13 negotiations
13.5 Reduced kilowatt-hour
charge –10 % to 9.9 Ct/kWh
14
Ct
13.52 kWh
Lower demand charge
13.0 –10 % to 108 €/kW
15
Ct
12.83 kWh
TIP04_13_163_EN
12.5
2,800 2,900 3,000 3,100 3,200 3,300 3,400 3,500 3,600 3,700 3,800
16 Usage period in h
Intro
duction
The development of the electricity price as a function of Today’s still usual flow of energy from large power plants to
1
the usage period can be graphically represented. The the consumer by way of the transmission and distribution
different options for optimization as a result of kilowatt- grids is increasingly being replaced by a distributed power
hour charge and demand charge variations as well as generation in small units within the distribution grid. The 2
specific time limits can thus be illustrated. flow of energy may even be reversed with it being fed from
the distribution grid into the transmission grid. In Germany,
Shown in Fig. 14/12 on the X-axis is the usage period as
a quotient from kWh consumed per year and maximum
97 % of the regenerative energy generated in a distributed
fashion was fed into the distribution grids at the end of
3
15-minute procured power within the year and on the 2012. The capacity installed was 83 GW. The capacity
Y-axis the AEP. In so doing, the following key points are
definable:
generated in a distributed fashion is likely to rise substan-
tially as the energy turnaround gathers pace. 4
• Current AEP
• Possible energy savings while maintaining the maxi- Within the smart grid, consideration is being given to
mum procured power directly controlling consumer equipment and guiding 5
• Possible saving of procured power while keeping to the consumer attitudes by applying special tariffs so as to
same amount of energy consumption match consumption to power generation. A considerable
• Possible revised kilowatt-hour charge
• Possible revised demand charge.
planning outlay is required for generating power in a host
of small to medium-sized plants, most of which are sup-
6
plied from regenerative energy sources. The vital regenera-
The assumption for the dashed curve in the view is a price
reduction of kilowatt-hour charge and demand charge
tive power generators are weather-dependent (PV systems
from solar radiation which, in turn, is conditional upon
7
of 10 % each. In the three tabs above the “optimization locality and time, wind turbines from wind conditions
window”, the demand charge (120 € / kW) and kilowatt- dependent on locality and time). No generating forecasts
hour charge (11 cent / kWh) are fixed prices. Variations are possible here without a detailed weather forecast. In 8
of the consumption or required power peak result in addition, one needs to have forecasts of the consumption
changes to the usage period and AEP respectively. Please of the many electricity customers within the distribution
note that it is not the absolute cost of electricity that can
be read from the “optimization window”, but a mean
grid. Without them, a balance between generation and
consumption is impossible. What is absolutely needed is
9
electricity price per kilowatt-hour consumed. effective communication between the parties involved.
17
Intro
duction
2
Biomass power plant
system Billing
5 Communication Network
CHP
Weather service
6
Concentrator
7
Wind power Influenceable
8 PV system plant
Remote meter reading loads
9 Communications
unit
TIP04_13_164_EN
10 Distributed
miniCHPs and
Fuel cell PV systems Distributed loads
11
Fig. 14/13: Energy management in the smart grid through communication effected across all energy networks back to page 291
12
13
14
15
16
17
Intro
duction
Intro
duction
12
13
14
15
16
17
Intro
duction
M P P
P
• Measuring
8
9
4.000 kW
8,000 kW 300 h Maximum value
3.500 kW
7,000 kW 250 h Mean value
3.000 kW
6,000 kW
200 h Minimum value
5,000 kW 2.500 kW
150 h
Controlling:
4,000 kW 2.000 kW
3,000 kW 100 h 1.500 kW
2,000 kW
6,000 kW 5h 8.000 kW 1.000 kW
1,000 kW
7.000 kW 500 kW
1 kW 5,000 kW
1 5 10 15 20 25Lastgang
30 35 40 45 50 KW 0 kW 1.000 6.000 kW
2.000 3.000 4.000 5.000 6.000 7.000
0 kW
Current
3,000 kW 4.000 kW
6,000 kW Monday
3.000 kW 3.500 kW
2,000 kW Tuesday
2.000 kW 3.000 kW
5,000 kW Wednesday
2.500 kW
10
1,000 kW 1.000 kW
2.000 kW Thursday
4,000 kW
• ISO 50001
1 kW 0 kW 1.500 kW Friday
KW 53 KW 1 KW 2 KW 3 KW 4 0 1.000 2.000 3.000 4.000 5.000 6.000 7.000 8.000 9.000 h 1.000 kW
3,000 kW
500 kW 20 %
Maximum value
2,000 kW 12. Januar 2010 0 kW 15 %
6,000 kWh 0:15 3:15 6:15 9:15 12:15 15:15 18:15 21:15
Frühschicht Spätschicht Mean value
1,000 kW 10 %
5,000 kWh Minimum value
5%
1 kW
Monday
4,000 kWh
Tuesday Wednesday Thursday Friday Saturday Sunday
0%
0:15 3:15 6:15 9:15 12:15 15:15 18:15 21:15
-5 %
3,000 kWh
-10 %
2,000 kWh
-15 %
1,000 kWh -20 %
-25 %
1 kWh
0 2 4 6 8 10 12 14 16 18 20 22 24 -30 %
6,000 kW
5,000 kW
11
4,000 kW
Forecast:
• Power procurement forecasts
Current
12
3,000 kW
1 kW
13
Monday Tuesday Wednesday Thursday Friday Saturday Sunday
Current
Utility
Heat
14
Primary energy
District
Operational management:
Current
Current
Gas, oil, coal
heating
Emission CO2 • Procurement forecasts
Biomass
kWh
CO2
kWh
CO2
m3
CO2
Biogas m3
CO2 Heat • Generation forecasts
In-house generation
15
Energy conversion
Boiler CHP Solar Wind Geothermy • Consumption forecasts
Cold
Fossil Fossil Thermal, photovoltaics Heat pump
Regenerative Regenerative
Storage cell
• Cross-commodity optimization
Energy application
Consumption
Current Heat Cold
TIP04_13_196_EN
16
17
Fig. 14/15: Operational view of electric power distribution and incorporation into the operational management
Intro
duction
1 14.7 N
ormative Basis for an Energy ISO 50001 also features the requirements placed on energy
Management System management systems and an introduction for their applica-
tion. In the standard, the term “organization” is used gener-
2 To remain commercially competitive, companies need to ally to include undertakings, companies, and institutions.
continually subject their competitive position and thus their As early as 2008, the American National Standards Institute
energy consumption to critical examination and optimiza- (ANSI) in conjunction with Brazilian associate ABNT was
3 tion. A further incentive here comes from governments
which increasingly have and want to ensure a cut in the
involved in developing ISO 50001:2011. Experts from over
40 countries were rendering assistance. Thanks to close
greenhouse gas emissions of their country. The result is an cooperation with the European ISO member states, a lot of
Intro
duction
14.7.3 Management Process aids, training courses, and information are to be provided.
1
A documentation on the key EnMS elements and their
ISO 50001 describes a continuous improvement process for interaction must be present. Controlling of documents and
a more efficient use, monitoring, and analysis of energy. processes is oriented to the corresponding specifications 2
The principal setup follows the PDCA cycle as applied, for for other management processes, such as that of quality or
instance, to the ISO 9001 standard, and which is to be environment management, and needs to conform to
adapted to the daily operation of an organization: Plan, Do,
Check, Act. Proceeding on the basis of this cycle, a model
management standards. 3
for the EnMS is described (Fig. 14/16) followed by specifi- Demanded by ISO 50001 is the monitoring, testing, and
cation of the requirements. In particular, the responsibility
of the manager of an organization is gone into.
analysis of the main energy-relevant operations of an
organization at scheduled intervals. The improvement of 4
energy-related performance needs to be taken into account
The energy policy specifies the energy framework and when designing new, modified, or renovated buildings,
establishes the strategic goals to be aspired to by the systems, plants, facilities, and processes. This also applies 5
organization regarding energy utilization. A description is to energy metering and the attendant scope for evaluation
also given of the communication on this and the reaction and analysis.
to be expected of those employed in the organization. The
obvious goal of the energy policy must be towards continu- A supplier assessment can be carried out when purchasing
6
ously improving energy handling. energy and energy services as well as products and facili-
Monitoring,
metering, and
Management
14
analysis
systems Checking
ct Ch
ec
k
ISO 50001 15
A
TIP04_13_167_EN
Internal auditing of
the EnMS
Nonconformities,
corrections, corrective and 16
preventive actions
17
Fig. 14/16: Implementation of the PDCA management cycle for EnMS in ISO 50001
Intro
duction
12
13
14
15
16
17
6 siemens.com/simaris/help
10
11
Fig. 15/1: Power losses of the network configured with SIMARIS design professional
12
back to page 301
13
14
15
16
Fig. 15/2: Defining the longest fire section for a busbar trunking system in SIMARIS design
back to page 301
17
300 Totally Integrated Power – Planning Tools for the Efficient Planning of Power Distribution
Con
tents
Intro
duction
15.1 Dimensioning with Prior to dimensioning, the electrical planner defines the
1
SIMARIS design operating modes required for the project. This definition
can be more or less complex, depending on the project size
Based on specifications resulting from the project require- and the type and amount of system feed-ins and couplings 2
ments, SIMARIS design can be used to dimension the equip- used. However, with SIMARIS design this definition is quite
ment according to the accepted rules of good installation simple, since the relevant devices and their switching
practice and all applicable standards (VDE, IEC), from the
medium-voltage feed-in to the power consumers. SIMARIS
conditions required for the respective operating modes are
presented graphically in a clear and well-structured man-
3
design supports the calculation of short-circuit currents, load ner. All common switching modes can be mapped and
flow and distribution, voltage drop, and energy balance.
Moreover, SIMARIS design assists in the selection of actually
calculated thanks to the option of representing directional
and non-directional couplings, feed-in at sub-distribution 4
required equipment, for example, medium-voltage switching level, and isolated networks. Sizing of the complete
and protection devices, transformers, generators, low- network or subnetworks is done automatically according to
voltage switching and protection devices, and in conductor the dimensioning target of “selectivity” or “back-up protec- 5
sizing, meaning the sizing of cables, wires, and busbar tion”, and the calculation results can be documented with
trunking systems. In addition, the lightning and overvoltage various output options. With the “professional” version of
protection can be included in the dimensioning process. The
“professional” version of SIMARIS design also allows deter-
the software, it is possible, among other things, to perform
a selectivity evaluation of the complete network.
6
mining the power losses of equipment during network
calculations. To this end, an overview is created in SIMARIS
which shows where the greatest losses occur in the network.
From experience, planning an electric power distribution
system is always subject to considerable changes and adapta-
7
Suitable adjustments in equipment selection then allow tions both in the planning and in the implementation stage, for
reducing such power losses, thus optimizing the energy example also due to concept changes on part of the customer
efficiency of the network (Fig. 15/1). The network to be forwarded at short notice. With the help of the software, adapta- 8
planned can be designed graphically in a quick, easy, and tions of the voltage level, load capacities, or the technical
clear way with the help of the elements stored in the library. settings for medium or low voltage can be quickly and reliably
12
13
14
15
16
17
Fig. 15/3: Network planning with SIMARIS design
Totally Integrated Power – Planning Tools for the Efficient Planning of Power Distribution 301
Con
tents
Intro
duction
12
13
14
15
16
17
Fig. 15/4: System planning with SIMARIS project
302 Totally Integrated Power – Planning Tools for the Efficient Planning of Power Distribution
Con
tents
Intro
duction
siemens.com/simariscurves
6
10
11
12
Fig. 15/5: Characteristic curves (fuse, molded-case circuit-breaker, air circuit-breaker) in SIMARIS curves
13
14
15
16
17
Totally Integrated Power – Planning Tools for the Efficient Planning of Power Distribution 303
Con
tents
Intro
duction
10
11
12
13
14
15
16
17
304 Totally Integrated Power – Planning Tools for the Efficient Planning of Power Distribution
Chapter 16
Lighting Inside Buildings
16.1 Basic Data Establishment 306
16.2 Building Analysis 309
16.3 Normative Specifications 309
16.4 Normative Specifications
as to Energy Efficiency 310
16.5 Lighting Quality Features 312
16.6 Design Principles 316
16.7 Lighting Tools for Good Lighting 320
16.8 Light Calculation 327
16.9 Emergency Lighting 338
Con
tents
1 People stay in buildings and perform various activities The basis of planning is the synchronization with the users'
there. Visual perception is the most frequently used human requirements profile and the architectural requirements. As
sensory impression inside buildings. Therefore, specific a reference for interior rooms, EN 12464-1 specifies rated
2 lighting is required which reflects the correlations between illuminances. Numerous brochures state typical characteris-
architecture, daylight, visual task, biological effect, energy tic values that refer specifically to this standard.
efficiency, and required light sources in buildings. In the
3 end, light is the form of energy that brings together people
and building including the equipment. The planner faces
The data for the illuminance maintenance value ( m), the
maximum unified glare rating limit value (UGRL) for dis-
a versatile organizational task that goes far beyond consid- comfort glare assessment, the minimum uniformity ratio of
4 ering lighting merely as part of the architecture. illuminance (U0), and the minimum value of the color
rendering index (Ra) should be agreed with the customer.
In view of an increasing consideration of the biological
effect of light, these parameters have to be regarded
5 16.1 Basic Data Establishment intensely in the planning phase.
The basic requirement for a good lighting solution is the For the purpose of integrated planning, the planner should
6 compilation of constructional and technical conditions and
a founded establishment of all parameters against which
know the basic task of lighting planners and architects and
be able to synchronize with them. Therefore, crucial points
the lighting is pitted. Therefore, no lighting task equals in the creation of a lighting concept will be dealt with in
17
Intro
duction
1
16.1 Basic data • Creation of the users' requirements specification
establishment • Creation of the architect's requirements specification 2
16.2 Building • Project analysis
analysis • Zoning in detail 3
• First technology concept for technical building
equipment is available (control system, bus systems etc.)
• Façade details are known (daylight factor) 4
• Ceiling system is known
5
16.3/4 Normative specifications
Lighting of Biological 6
Energy efficiency
workplaces effect
7
European level European level
EN 12464-1 Directive 2012/27/EU 1)
Directive 2010/31/EU 2)
8
Germany Germany Germany
DIN 5035-8 EnEV 2014 / DIN Spec 67600
DIN EN 12464-1 Sheet 1 3)
ASR A3.4
DIN V 18599-1, -4, -10, -11 (see also VDI 6008
Sheet 1 and Sheet 3)
9
16
TIP05_18_012_EN
1) Directive 2012/27/EU on energy efficiency; to the revision of 2009/125/EC and 2010/30/EU as well as
to the withdrawal of 2004/8/EC and 2006/32/EC
2) Directive 2010/31/EU on the energy performance of buildings; to the withdrawal of 2002/91/EC
3) This supplement serves for interpretation of the German edition of DIN EN 12464-1:2011-08
17
Fig. 16/1: Flow diagram for light planning back to page 306
Intro
duction
2
Furnishings:
Tables, desks
3
Chairs
Building: Cabinets
Climate Shelves
Building orientation High desks
Surroundings Accessories:
4 Building/light management
Network/data management
Pictures, boards, calendars
Curtains
Light:
Room: Luminaire Plants
Windows/doors
5
Mounting position
Walls/ceilings/floors
Sun protection
Colors
Reflections
8
People
Brightness
Safety: Working appliances:
9 Personal safety
Occupational health and safety
Light distribution
Daylight utilization
Monitor, computer,
Keyboard
Light color
Orientation ability Writing materials
Dynamics
Feeling: Projector/screen
10
Energy efficiency
Natural vision Control panel
Well-being Working equipment:
Concentration/attentiveness Treatment chair
Work task Writing desk/work area
11 Workflows
Communication needs
Workbench
Conveyor belt
Test facility TIP05_18_017_EN
12
14
15
16
17
Intro
duction
16.2 Building Analysis With regard to energy efficiency and ecological framework
1
conditions for lighting, the EU directives form a framework
The architectural surroundings and design of the building that is to be implemented in the national legislation of the
structure have a great influence on the light planning. After Member States of the European Union: 2
clarification of the basic specifications, a building analysis is • Directive 2009 / 125 / EC:
conducted to emphasize the correlations. This analysis Establishing a framework for the setting of ecodesign
comprises the following:
• Analysis of the existing lighting system (if any) including
requirements for energy-related products (replaces
Directive 2005 / 32 / EC)
3
the recording of positive and negative experiences • Regulation 244 / 2009 of the European Commission (plus
• Analysis of the determined basic information, the archi-
tecture, the customer’s wishes, and the user’s
modifications in accordance with EU regulation
859 / 2009): 4
requirements Implementing Directive 2005 / 32 / EC to define ecodesign
• Analysis of the first plans (floor plans and sectional views) requirements for non-directional household lamps
• Zoning of floors, rooms and areas into traffic routes, • Regulation 245 / 2009 of the European Commission (plus 5
workplaces, common zones, etc. modifications in accordance with EU regulation
• Analysis of an existing technology concept (light 347 / 2010):
management concept, building management system,
digitalization, etc.)
Implementing Directive 2005 / 32 / EC to define ecodesign
requirements for fluorescent lamps without integrated
6
• Recording of the technical requirements (the building ballast, for high intensity discharge lamps, and for bal-
control system to be considered, integration of further
components, requirements for control systems, data
lasts and luminaires able to operate such lamps
• Regulation no. 1194 / 2012 of the European Commission:
7
technology options) Implementing Directive 2009 / 125 / EC with regard to
• Analysis of the ceiling system ecodesign requirements for directional lamps, light
• Analysis of the mounting options and restrictions emitting diode lamps and related equipment 8
(beams, recessed ceiling installations) • Directive 2010 / 30 / EU:
• Definition of possible mounting positions based on the On the indication by labelling and standard product
structural conditions. information of the consumption of energy and other
resources by energy-related products (replaces
9
92 / 75 / EEC)
17
Intro
duction
not dealt with in the EN 12464-1 itself EnEV 2009 [18] is the implementation of the repealed
• EN 12464-1 Directives 2002/91/EC and 2006/32/EC in a German regula-
5 Lighting of indoor work places (in areas close to buildings tion in accordance with the specifications of the European
such as service roads, parking areas, and pedestrian Union. In compliance with that, the energy consumption in
ways, the lighting requirements according to the appli non-residential buildings is to be determined for the in-
6 cable standards for the lighting of outdoor work places
according to EN 12464-2 or the standard series EN 13201
stalled lighting and stated in kWh per year and square
meter of the net floor area. The target value is the annual
in the area of street lighting to be observed) primary energy consumption of a building per square
concepts and lighting types for artificial lighting With regard to the calculation of the energy demand of the
Remark: Explanations to the application of the DIN EN lighting, EnEV 2009 refers to DIN V18599-4: 2007-02 and
8 12464-1 in Germany; does not include any standardized provides different methods for the planning of a lighting
specifications to the EN 12464-1 system taking into account a specific type of lighting and
• EN 15193-1 a use-specific maintenance value of the illuminance.
9 Energy performance of buildings – Energy requirements As a requirement basis for non-residential buildings,
for lighting – Part 1 EnEV 2009 states specific component and system designs
• CEN/TR 15193-2 of a reference building, among them also for the lighting:
10 Energy performance of buildings – Energy requirements
for lighting, Part 2: Technical report to EN 15193-1
• Glass roofs, lighting trunking systems, skylight domes
• Windows, French doors, skylights
• Pre-standard DIN V18599-1, -4, -10, -11 • Daylight supply in the case of sun and/or glare protection,
Energy efficiency of buildings shading
11 Part 1: General balancing procedures, terms and defini- • Type of lighting, lighting control.
tions, zoning and evaluation of energy sources
Part 4: Net and final energy demand for lighting In particular for lighting control, EnEV 2009 provides
12 Part 10: Boundary conditions of use, climatic data specifications for the different types of use of a building in
Part 11: Building automation accordance with DIN V18599-10:2007-02 (see Tab. 16/2).
• DIN SPEC 67600
13 Biologically effective illumination – Design guidelines. EnEV 2009 has been revised to EnEV 2014 for two reasons:
1. Transposition of Directive 2012/27/EU with higher
Based on the flow diagram depicted in Fig. 16/2, the nor- requirements into German law
mative bases with regard to technology, energy consump- 2. Reference to the new pre-standard series DIN V18599.
14 tion and the biological effect of lighting inside buildings For the lighting, DIN V18599-4:2011-12 replaces
will be touched in the following. DIN V18599-4:2007-02 to which EnEV 2009 refers
(new pre-standard DIN V18599-4:2016-10 is available).
15
Publication of EnEV 2014 was in November 2013 [19].
16
17
Intro
duction
not available
server room, data center, gym (without grandstand)
otherwise
4
Tab. 16/1: Lighting control in accordance with EnEV 2009
5
Lighting control for types of use in accordance with DIN V18599-10:2011-12
Presence control effected by presence detector Cellular office and group office, meeting, conference, seminar, class
room (school), group room (kindergarten), lecture hall, auditorium,
6
hotel room, kitchen (preparation, storage), lavatories and sanitary
facilities in non-residential buildings, other common rooms, circulation
areas, server room, data center, sports hall / gym (without grandstand),
car parks (office or private use), laboratory, examination and treatment 7
rooms, doctor's surgeries and therapeutic surgeries
effected manually otherwise
Constant light control / daylight- Constant light control effected Counter area, lecture hall, auditorium, wards, kitchens in non-residential 8
dependent control in accordance with buildings, commercial and industrial halls, library – open access section,
DIN V18599-4:2011-12 car parks (public use), fitness room, examination and treatment rooms,
9
Section 5.4.6 special nursing areas, corridors of the general nursing area, doctor's
surgeries and therapeutic surgeries
Daylight-dependent control in Cellular office, group office (two to six workplaces), open-plan office
combination with constant light
control is effected in accordance
(from seven workplaces on), conference room, meeting room, seminar,
class room (school), group room (kindergarten), cafeteria, library – 10
with DIN V18599-4:2011-12 reading room, sports hall / gym (without grandstand), laboratory
Section 5.5.4
effected manually otherwise
11
Tab. 16/2: Lighting control in accordance with EnEV 2014 back to page 310
12
This also results in a change of Tab. 16/1 to Tab. 16/2 Software-based tools considering all installations are
according to current DIN V18599‑4: 2011-12 and for provided for the calculation. The electrical and lighting
lighting control a daylight-dependent control is considered.
A new edition of the EnEV is pending.
planning engineer can use, for example, the lighting
calculation programs DIALux or RELUX to calculate the
13
reference value to be observed for the energy demand. The
For the planning of energy-efficient lighting in compliance light planning applications are able to calculate the value
with EnEV, DIN V18599-4 is applied. In that, the different for the net energy demand of the lighting by applying the 14
utilization zones of the building, the specific electrical formulas described in DIN V18599-4.
efficiency of artificial light, the consideration of the day-
light utilization and the influence of presence detection More information about DIALux and RELUX can be obtained 15
systems are determined. In the future, DIN V18599-11 for on the Internet at:
building automation will influence the EnEV.
Intro
duction
1 16.5 Lighting Quality Features With its recommendations, EN 12464-1 emphasizes the
importance of light and lighting quality, and identifies
The normative specifications for the requirements imposed visual comfort, visual performance, and security as the
2 on the state of the art that have to be met at the minimum main components of good lighting for workplaces. The
are described in EN 12464-1 on the European level. For the following lighting quality features are considered:
first time, uniform characteristic values apply for the spe- • Luminance distribution
3 cific requirements imposed on the lighting of different
buildings, rooms, and usages.
• Illuminance
• Visual atmosphere
• Spatial illumination
12
Background
13
Immediate surroundings
14 Visual task
Illuminance Illuminance
“visual task” “immediate surroundings”
15 in lx in lx
≥ 750 500
500 300
16 TIP04_13_177_EN
300 200
≤ 200 = E”visual task”
17 Fig. 16/3: The visual task area with immediate surroundings (strip
of 0.5 m beyond the visual field) and background area (within the
Tab. 16/3: Correlations between the illuminance levels
Intro
duction
10
11
12
13
14
15
16
17
Intro
duction
7
Illuminance Power demand
in lx in W
TIP04_13_178_EN
Maintenance value
Maintenance factor
Maintenance
Maintenance
Maintenance
Maintenance
Maintenance
Maintenance
ΔE ΔE ΔE
9
Maintenance
value Em
10 Controlled lighting Controlled lighting
Time Time
11 Fig. 16/4: Operation-dependence of illuminance, power demand, and energy saving ΔE back to page 315
(dark grey areas in the right-hand diagram) for controlled lighting with constant illuminance
12
13
14
15
16
17
Intro
duction
16.5.4 Maintenance Factor LSF Lamp survival factor: corresponds to the C-value 1
of an LED luminaire (considers the total failure of
a luminaire within the expected service life;
EN 12464-1 specifies the illuminances as maintenance
values, that is, as minimum values that must not be under-
usually equal to 1 at rated service life for LED
luminaires)
2
shot even after several years of operation. When the light-
ing system is planned, a maintenance factor is determined LMF Luminaire maintenance factor: identifies the
which is applied for software-based light calculation, thus
granting a standard-compliant illumination of the applica-
disposition to dust accumulation / pollution in
luminaires as well as the dust and smoke expo-
3
tion until the end of the system’s service life. The mainte- sure of luminaires due to the room utilization and
4
nance factor MF takes into account operational influences environmental influences (may lead to discolor-
(e.g., ageing of LED modules and possible failure of single ing/yellowing)
luminaires) and pollution of room and luminaire. RSMF Room surface maintenance factor: considers the
disposition of reflecting surfaces to pollution, as
When these minimum values are reached, the lighting has well as the accessibility to these surfaces and the 5
to be maintained (Fig. 16/4). The planner must state the cleaning/ maintenance intervals.
maintenance factor and assumptions for value determina-
tion, determine the lighting system dependent on the
operating conditions, and attach a comprehensive mainte-
The maintenance factor directly influences a system’s
energy efficiency. High-quality luminaires assume a key
6
nance plan. This maintenance plan should describe the function in that. In combination with luminous flux adjust-
cleaning and replacement of lamps and luminaires as well
as the cleaning and modification of the rooms.
ment (constant light control), the energy consumption can
be positively influenced. Since the power requirement is
7
proportional to the illuminance, this can be additionally
For the determination of the maintenance factor, reduced by modern building managements systems.
EN 12464-1 refers to the international standard 8
CIE 97-2005 (International Commission on Illumination, The LED’s performance is defined by the system of LED
French: Commission Internationale de l’Éclairage). module, operating device, and optical cover – und also
There, it is described as a product of single components: decisively influenced by the LMS. The decline in luminous 9
flux depends on the respective current load, the thermal
MF = LLMF ∙ LSF ∙ LMF ∙ RSMF management, and the ambient temperature of the lumi-
where
naire. The better the luminaire’s thermal management, the
lower the decline in luminous flux of the luminaire over
10
LLMF Lamp lumen maintenance factor: considers the time in the respective surroundings. The luminous flux and
the endurance performance of LED modules is described in
reduction of the luminous flux depending on the
rated service life and the annual utilization / the IEC 62717 standard. 11
service life of the installation (e.g.: LLWF = 0.8 for
“L80 50,000 h” = 80 % luminous flux after expiry The luminaire manufacturers are committed to publish
of the mean service life of 50,000 h); the mean information on their luminaires. Detailed explanations and 12
service life is extended, in particular, if a light planning instructions, particularly for LED lighting, can be
management system (LMS) is considered found in the ZVEI “Guide to Reliable Planning with LED
Lighting” [22] as well as brochures of the LiTG [20].
13
14
15
16
17
Intro
duction
1 16.6 Design Principles Light direction (top, bottom, lateral, vertical, horizontal,
etc.) and light distribution (punctiform, wide-area, accen-
In addition to the general or basic lighting, it is reasonable tuated etc.)
2 to use lighting for visual focussing or emphasizing. In that, • How do I want to achieve the effect?
architecture, design elements in the room, forms, materi- For example, through color contrasts, different illumi-
als, and surface properties are immersed in light. This can nances, color temperatures, light density beam focusing
3 also be used to draw the viewer’s attention to something or
to foreground the light itself as an object of viewing (catch-
or scattering, and adjustable light effects (time-, environ-
ment-, event-dependent)
word: light sculpture). • Which design functions are to be assumed by lamps and
7
Light
8
10
11
Visual path Nonvisual path
• Relaxation, tension
15 • Concentration, unrest
• Well-being, discomfort
TIP04_13_179_EN
• Activity, restraint
16 • Security, unease
• Confidence, caution
Intro
duction
Structural conditions and the desired light moods provide • Preference of daylight in the planning; artificial light
1
the required light distribution curve (LDC), which is charac- should be a supplement and only a substitute where
terized by the spatial distribution (for example, a symmet- daylight is not sufficiently available
ric, asymmetric, wide-angle, or narrow beam LDC). The • Visual requirements on the lighting design are described 2
selection of the required LDCs leads to the selection of the in EN 12464-1 (for Europe) and, especially for work-
corresponding luminaires, taking into account the lighting places, in ASR A3.4 (binding for Germany)
task, design intention, and mounting options. • Integral planning taking into account the biological
effect of light is structured according to the HOAI phases
3
Finally, the mounting positions are checked and tailored to (German Fees Ordinance for Architects and Engineers):
the space requirements of the lighting system. Also to be
considered is any additional equipment and cooling ele-
requirements planning – basic evaluation – preliminary
planning, etc. 4
ments for the luminaire, or stipulated clearances.
As criteria for biologically effective lighting,
16.6.1 Biological Effect of Light DIN SPEC 67600 explicitly describes the following aspects: 5
• Spectral composition of the light
For a long time, the biological effect of light on the human The natural circadian rhythm of the human body
being had been regarded as a mainly medical topic. This
changed when another photoreceptor was discovered in
(chronobiological effect of the so-called “internal clock”)
is determined by the increased red component at sun-
6
the human eye (in 2001). Light is perceived with these rise or sunset on the one hand, and the high illuminance
light-sensitive sensory cells (most intensely, the blue-wave
light) and passed on to the body in biological signals. This
during the day with increased blue components on the
other hand. These spectral correlations can also be used
7
regulates the production of the wake and sleep hormones for artificial light. To be considered for that is that
cortisol and melatonin. These hormones control the body’s reflections and transmissions as well as the spectral
circadian rhythm. properties of materials may have considerable influence 8
on the light. The correlation between color temperature
Light influences physiological and psychological states such and biological effect is shown schematically in
as moods, emotions, and also attention. Thus, light has a DIN SPEC 67600 (Fig. 16/6). 9
controlling impact on people’s health and well-being.
Integral light planning is not just restrained to the technical
aspects of lighting, but also considers the biological and
emotional factors connected with the “human light re-
10
ceiver” – thus, not only the visual factors, but also the
non-visual factors (Fig. 16/5). For artificial light, this means
that a targeted broadening of the spectrum by the propor- Melanopic factor in accordance with DIN SPEC 5031-100 1) 11
tion of blue can have a positive effect. From the biological
view, the highest efficiency lies in the range between 1.6
12
TIP05_18_013_EN
6,500 K and 8,500 K. However, it has to be noted that the 1.4
17,000 K
user’s acceptance decreases with increasing proportion of 14,000 K
1.2
blue. Today, 6,500 K are established as a “standard”. A
medium-term towards higher color temperatures can be
13
D75
1.0
D65 8,000 K
recognized. D55
0.8
D50
F10
DIN SPEC 67600 is not a standard in the conventional sense
14
0.6
F11
of light planning, but a recommendation to consider for 0.4
the planning the biological effect of light on the human F12
0.2
eye and body. Some notes in DIN SPEC 67600 are
important: 0
0 5,000 10,000 15,000 20,000
15
Correlated color
Planckian radiator Standard illuminants
temperature
Daylight spectrum Fluorescent lamps
16
in K
Halogen lamps
LED
1)
The melanopic effect of light is the part of the biologic effect
generated by the photopigment melanopsin.
Intro
duction
7 • Light dynamics
The adaptation of the light to the time of day and time of
Mood
Health
+75 %
+50 %
year or even to the weather plays an important part. The
circadian rhythm is stabilized with biologically effective See
8 light. When the daylight has only low illuminance, it may www.osram.com/ls/press/hcl-case-cbre-amsterdam/index.jsp
be desirable to supplement it with biologically effective
artificial light. Since the human biological system The 10 guidelines of a HCL concept:
9 responds relatively slowly, the duration of the light • Use of daylight
exposure is an important factor for the biological effect, Due to evolution, daylight is our most important time/
which means, in the ideal case, that biologically effective clock. Daylight offers maximum light quality referred to
10 lighting solutions should extend throughout entire
sequences of rooms
the spectral distribution and color quality in the visible
spectrum. In the non-visible spectrum, sunlight contains
• Energy efficiency of biologically effective lighting many health enhancing contents. For this reason, natural
Wide-area light from above makes for a distinct biological daylight should be used as much as possible for your
11 effect, as the receptor cells in the eye’s retina are reached lighting concept. To this end, it has to be observed that
better and more uniformly. These receptors are located in disturbing effects such as glare or too high heat input by
the lower half-space of the eye. However, this usually direct sunlight are avoided
12 requires more power installed to achieve the desired • The right lighting at the right time
illuminance in the case of spatial distribution of the light. The chosen solution concept must be suitable both for
According to experience values – as noted in DIN SPEC visual and non-visual perception. Biologically effective
13 67600 – the installed power increases by factor 3. How-
ever, in a conversion to biologically effective lighting, an
light is particularly effective in the morning, after preced-
ing darkness. Warm white light in the evening fosters
efficient new system with modern LED luminaires can at relaxing and coming to rest. Recommendations related to
the same time make for a relative decrease of the energy “use of the right lighting at the right time” are indispens-
14 consumption. Due to the use of light management able for a good concept. The effects of all light sources
systems, the increase of energy consumption in a conver- shall be considered as far as possible, also of those
sion to biologically effective lighting is limited to about sources which are no directly intended for illumination,
15 25 %. such as computer monitors
16
17
Intro
duction
• Ecological and sustainable planning • Considering more than one light color – planning
1
Light shall only be provided where necessary and dynamic light
required for well-being. This is wherever people stay for a Daylight, as the conceptual example, is characterized by a
longer time. A suitable and dynamic LMS as well as the local and timely distribution of warm and cold white light 2
utilization of daylight resources are an important factor colors and brightness. Therefore, cool light colors with
for HCL concepts. For this reason, the HCL concept should high illuminances should be combined with warm white
already be observed during room design, and it should
also be checked whether the LMS can be connected to
light colors featuring a lower brightness. Cold white light
leads to biological activation; warm white light has a
3
the possible existing building systems technology positive effect on relaxing and slowing-down. Light
• User-related planning
User-specific information must be observed during the
patterns with a circadian effect support the daily human
rhythm; short-time “light showers” can punctually con- 4
creation and design of the concept (e.g., elderly people tribute to specific activation
need more light that younger people). Different working • Planning the right components
rhythms are to be observed (chronotypes). The lighting The type of luminaire supports the biological effect (e.g., 5
solution shall have a positive effect of the room directly and indirectly radiating pendant luminaires, wall
perception floodlights, free-standing luminaires, or light ceilings for
• Application-related planning
The desired effect of a HCL concept on the person must
wide-area, cool, or dynamically white lighting resp.
downlights or spotlights for warm white accent lighting).
6
be defined specifically for the application. During the The combination of dynamic light management and
analysis, the positive effect on well-being, concentration,
and motivation of the person is in the focus
luminaires, as well as the use of components with docu-
mented melanopic data, simplifies the implementation of
7
• Architectural planning an HCL planning approach
“Material-conforming” light is a part of the concept, and • Standard-compliant planning
the lighting solution must be a part of the architecture Workplace illumination in accordance with the standards 8
(and support it). The visual effect of light has to be forms the basis for all HCL lighting concepts. Recommen-
observed (light opens up areas, directs the view, designs, dations for correct planning with biologically active light
and enacts). It has to be taken into account that surfaces
absorb light and just reflect it to a certain degree. As
can be found, for example, in DIN SPEC 67600 and
DIN SPEC 5031-100. Additionally, activating lighting
9
melanopic effects are mainly provided by blue light, concepts are to be created, based the standards.
strong colors towards red, brown, yellow can dramati-
cally reduce the effect, as they absorb the blue
10
• Brig the sky indoors
The light quality of daylight must be considered at least
as a reference; i.e., large-surface light (either widely 11
radiating indirect light or light ceilings) for cold white
lighting during the day following the sky view factor, and
warm white light following the lighting quality by the sun 12
in the evening hours
13
14
15
16
17
Intro
duction
1 16.7 Lighting Tools for Good Lighting Glare can considerably impair the sight. It diminishes the
visual performance (disability glare) and visual comfort
To obtain a good lighting, the requirements described in (discomfort glare). A differentiation is to be made between
2 EN 12464-1 must be implemented project-specifically as a direct and indirect glare. Direct glare comes from lumi-
minimum. For that, the rooms are divided into the visual naires or other areas with excessive luminance, for exam-
task area(s), the respective immediate surroundings, and ple, the incidence of light through windows. Reflected
3 the background (Fig. 16/7). glare acts indirectly, caused by reflections on shining
surfaces.
Room structuring serves for the planning of a balanced
10
Minimum 0.5 m
11
EU EU EU
12
Minimum 3 m
13
EH = 1/3 · EU
14 EU
TIP04_13_181_EN
15
Size and position of the
EU surrounding and background area
should be defined and documented
16 Visual task EH
EU
Mean illuminance in the background
Background
17
Fig. 16/7: Room structuring for the lighting concept
Intro
duction
even rod-shaped lamps will be affected thereby. Specific The term “luminaire” describes the entire lighting appliance
1
properties such as light color, efficiency, dimming behav- including all components required for operation and pro-
ior, and dimensions must be considered for the selection of tection. Luminaires are differentiated by:
illuminants. During the regular maintenance of existing • The magnitude of the luminous flux 2
systems, the traditional illuminants are frequently replaced • The number of separate switching groups (e.g. by direct/
by LED retrofit solutions. The selection of the luminaires indirect)
including the modules installed should take into account
specific properties such as the light color, color rendering,
• The spectrum (e.g., from 2,700 K to 6,500 K)
• The field of application (interior luminaires, exterior
3
efficiency, dimming behavior, and dimensions. luminaires)
17
Intro
duction
1 The luminaire’s light output ratio describes how effectively • Protection against the ingress of foreign bodies and
a luminaire distributes the light of an illuminant. The moisture with the degrees of protection in accordance
higher the light output ratio is, the less energy has to be with IEC 60529 (VDI 0470-1, see Tab. 16/5)
2 spent to achieve the desired illuminance. In modern LED • Electromagnetic compatibility (EMC in accordance with
systems, the LED modules are installed as fixed part of the EN 55015/VDE 0875-15-1, IEC 61000-3-2/VDE 0838-2
luminaire, and the specification is referred to the system. and IEC 61000-3-3/VDE 0838-3)
3 This normally results in an output ratio of 1 = 100 %, and
loses importance.
• Immunity to interference in accordance with IEC 61547
(VDE 0875-15-2)
• Exposition of persons to electromagnetic fields
These electrical properties are generally regarded as To meet the safety requirements on lighting, the luminaires
6 important:
• Protection against excessively high touch voltage with
must comply with the standard series IEC 60598
(VDE 0711). As a prerequisite for that, also the associated
safety classes in accordance with IEC 61140 (VDE 0140-1, electrical components must comply with the relevant
7 see Tab. 16/4) safety regulations (for example, the standard series
IEC 61347/VDE 0712 for equipment). Moreover, also the
Safety class I Luminaires for connection to the so-called performance requirements for the equipment’s
principle of operation should be considered and observed.
8
line-side protective conductor.
The symbol is applied at the To indicate conformity with the standards, the luminaires
connecting point. should carry the ENEC approval mark (European Norms
Safety class II Luminaires with additional or Electrical Certification).
9 reinforced insulation. They do
not provide a protective To ensure standard-compliant performance also for the
conductor connection.
luminaires, and in particular LED luminaires, the standards
10 III
Safety class III Luminaires for operation with
safety extra-low voltage.
IEC 62722-1 and IEC 62722-2-1 were published. The re-
quirements are already met in the development of LED
III luminaires, which is of great importance for the planning
of lighting systems [22].
11 Tab. 16/4: Symbols for safety classes in accordance with IEC 61140
(VDE 0140-1)
14 4 Protected against solid objects of 1.0 mm diameter and greater 4 Protected against splashing water
5 Dust-protected 5 Protected against water jets
6 Dust-tight 6 Protected against powerful water jets
15 7 Protected against the effects of temporary immersion in water
8 Protected against the effects of continuous immersion in water
16 Tab. 16/5: Degrees of protection in accordance with IEC 60529 (VDE 0470-1)
17
Intro
duction
Degrees of protection
1
The degree of protection of a luminaire indicates whether
it is suitable for the desired lighting application and can 2
be operated safely. The luminaires must be constructed
such that no foreign bodies or moisture can ingress
according to the criteria of IEC 60529. The degree of
protection is indicated on the luminaire; the IP code is
3
applied for marking. The first characteristic numeral after
the abbreviation “IP” (international protection) describes
the protection against the ingress of foreign bodies, the 4
second characteristic numeral the protection against the
ingress of water (see Tab. 16/5).
5
Constructional properties
10
11
12
13
14
15
16
17
Intro
duction
1 • Recessed ceiling luminaires such as Taris and Apollon • Surface-mounted luminaires such as Scriptus Taris and
are suitable for mounting in cavities or ceiling voids. Most ARKTIKA are mounted visibly on the ceiling. They are thus
of the luminaire is put into the ceiling out of sight. The part of the room impression and a means of architectural
2 luminaire face is often flush with the ceiling. As “tunable designing.
white” versions, they are perfectly appropriate for the
implementation of biologically effective lighting concepts.
3
7
• Pendant luminaires such as Scriptus Taris and ARKTIKA
are suspended from the ceiling. They are thus also design
8 • Downlights such as Lunis® are special recessed ceiling elements and optionally available with directly/indirectly
luminaires (round or square), which are fitted with radiating light distribution. In separate circuits of indirect
reflectors and lenses for a clearly directed light distribu- and direct component of the “tunable white” versions
9 tion (symmetrical or asymmetrical) with good glare (TCP from 2,700 K to 6,500 K), they are suitable for
suppression. Projectors and wall floodlights for accentua- biologically effective lighting concepts.
tion complete this downlight family as well as “tunable
10 white versions” adequate for biologically effective light-
ing concepts. Surface-mounted versions round out a
downlight family.
11
12
13
14
15
16
17
Intro
duction
• Free-standing luminaires such as Futurel® are lighting • Moisture-proof luminaires such as the Monsun® fami-
1
systems that are individually dimmable and locally adjust- lies comply at least with degree of protection IP 65. They
able. Lighting control systems such as Lightify Pro facili- are primarily used in dusty and humid environments such
tate grouping despite changeable locations, which is as industrial plants, logistic areas, parking garages, and 2
becoming increasingly important both in new systems up to simple and cellar and secondary rooms, as well as
and for refurbishing projects. In separate circuits of in covered outdoor areas. Furthermore, the high degree
indirect and direct component, they are suitable for
biologically effective lighting concepts.
of protection makes the luminaires extremely easy to
maintain.
3
8
• Lighting trunking systems such as Modario® are modu- • Mirror reflector systems, such as Mirrortec®, can be
lar systems with two main components: supporting bars
(enabling suspended o surface-mounted installation) and
used for uniform and directed wide-area lighting. Light is
directed from a very tightly bundled lamp to a multi-facet
9
module inserts (to adjust the light distribution to the mirror and there reflected either symmetrically or asym-
specific application requirements). Sensors are provided
to save resources, and the high IP protection up to IP 64
metrically, depending on the properties of these mirror
facets. Compared to conventional luminaires, the light
10
allows them to be used in areas with higher dust density, source is fractionalized into single light points with low
for example, in workshops. intensity via the multi-facets system. Glare is minimized
by that. At the same time, the many facets provide for 11
very uniform lighting. Due to the lamp’s low mounting
position, maintenance is also facilitated. Under normal
conditions, the mirror remains maintenance-free. 12
13
14
15
16
17
Intro
duction
1 • Point-type hall luminaires such as NJ 700 are predomi- • Floodlights and projectors such as the FL luminaire
nantly suitable for high halls. The luminaires have a family are suitable for a wide range of connected loads
rotation-symmetric and narrow-angle light distribution. (in watts) and for many different light distributions.
2 Versions with asymmetrical distribution enable the ideal Other than in the case of large-surface hall luminaires,
illumination over inaccessible locations or the border of the complete room is illuminated, which provides an
the hall. optimal recognizability of the complete playing surface in
3 halls or outdoors, as in the case of ball sports, for exam-
ple. Smaller versions are often used for theaters and
show stages. In outdoor lighting, projectors are suitable,
10
11
12
13
For more information, see:
14 www.siteco.com/en/products/indoor-luminaires-catalogue.html
15
16
17
Intro
duction
16.8 Light Calculation For this equation, the following correlations apply with
1
regard to the luminous fluxes:
In the next step of professional light planning, the lighting
concept is reviewed on the basis of the specifications for ΦN 2
the simplified efficiency factor method as described in the ηB · ηR =
standard DIN V18599-4. The electrical efficiency referred to
Φtot
a floor area can be determined for a calculation area with
the following formula:
En · A 3
ΦN =
MF
pj =
kA · Em
Φtot = n · z · Φ 4
MF · ηS · ηLB · ηR
Where
Where
5
ΦN Usable luminous flux
pj Electrical efficiency Φtot Total luminous flux of lamps
referred to the floor area considered
kA Reduction factor, considering the boundaries
of the visual task
6
Em Maintenance value of illuminance in accordance
The room efficiency factor ηR is dependent on the luminous
with DIN V 18599-10
ηS
ηLB
System luminous efficacy of illuminant plus equipment
Light output ratio of the luminaire applied
flux distribution of the luminaire, the room geometry, and
the reflection conditions in the room. The relevant data are
7
ηR Room efficiency factor stated in the LiTG publication no. 3.5 [24].
8
MF Maintenance factor
To simplify distinctions, DIN V18599-4 introduces three
types of lighting: “direct”, “direct / indirect”, and “indirect”,
This formula is an adaptation of the equation presented by and specifies corresponding room efficiency factors
the Deutsche Lichttechnische Gesellschaft e. V. (LiTG
– German Light Engineering Society) for a simple
dependent on the room index k in a table. The room
index k is calculated as follows:
9
estimation of the required number of luminaires or lamps
referred to the desired illuminance [23]:
a·b 10
k=
hN · (a + b)
En · A
n·z=
Φ · ηB · ηR · MF 11
Where
Where
12
a Room depth
b Room width
n Number of luminaires
hN For "direct" or mainly "direct" lighting: difference
z Number of lamps per luminaire in height between luminaire plane and working plane
En Rated illuminance
A
Φ
Floor area of the room
Luminous flux of lamp
For "indirect" or mainly "indirect" lighting: difference
in height between ceiling and working plane 13
ηB Total luminous efficacy
14
ηR Room efficiency factor
MF Maintenance factor The table values for the room efficiency factor can be
interpolated. For simplification, Fig. 16/8 shows three
interpolated curves for the correlation between room index
and room efficiency factor. 15
16
17
Intro
duction
TIP04_13_182_EN
a lighting system. With the efficiency factor method, the
100 number of luminaires required for a given illuminance can
be determined simply with paper and pencil. The illumi-
3
90
nances at relevant points in the room are calculated by the
80 computer. The lighting engineering result is output in
various display forms (mean value, iso-illuminance curves,
7
10
0 1 2 3 4 5
Room index k
10
11
N
12
12 m
10
13 8
14 4
15
2
0
TIP04_13_183_EN
16
0 2 4 6 8 10 12 m
17
Illuminance in lx
Intro
duction
www.siteco.com/en/planning-guide/lighting-calculation.html
• Luminaire solutions:
Time-dependent, daylight- and presence-dependent
6
luminaire control, for example, a free-standing luminaire
with an integrated brightness and presence sensor to
switch off the luminaire automatically with a time delay
7
as soon as there is nobody in the room any more
10
Course of daylight
11
Rated illuminance
12
13
14
Power consumption
15
Time
Person entering
16
Person leaving
17
TIP04_13_184_EN
Fig. 16/10: Daylight- and presence-dependent lighting requirements for an assembly facility
Intro
duction
1 • Room and building solutions: –– The selection of the mains phase is independent of the
Luminaire groups are set to different switching and control line
dimming states, which can be called via the LMS as –– The DALI control line is protected against reverse
2 defined light scenes. polarity; a special bus cable is not required
–– One control line is sufficient for a maximum of 64 EB in
As an additional application, LMS allow for dynamic color up to 16 groups
3 solutions which are easy to integrate and operate. Light
intensity and color for effect light can then be selected
–– Switching of the luminaires can be effected through
the control line
dynamically or at the push of a button. Application exam- –– A relay is not required
4 ples for so-called ambience lighting are: shops, showrooms
and points of sale (PoS), fitness and wellness areas, restau-
–– Feedbacks like “Lamp status” and “EB status” are
possible
rants, bars, hotel lobbies, conference rooms, schools, –– Synchronous scene transitions, all relevant light values
universities, further education institutions, façade illumina- are saved in the EB
5 tion. For so-called scene-based lighting, moods can be –– Group allocation can be changed without rewiring
enhanced or a biological effect can be caused, for example,
activation through a high blue component in the light • DMX for effect lighting:
6 spectrum with high illuminance. DMX stands for “digital multiplex” and is another digital
communication protocol for lighting control. DMX allows
Typically, one of the following interfaces is used for LMS for the simultaneous control of up to 512 light channels.
7 control:
• Dimming EB with 1...10 V interface:
The data rate is rapid 250 kB / s. Especially lighting scenar-
ios in which a large number of RGB light points and
In this standard solution, ballasts and control unit are numerous dynamic, quick color changes are required can
connected via a poled 2-core control line. The control thus be illuminated excellently
8 voltage level determines the dimming position of the • EnOcean – wireless in buildings:
connected ballasts. This analog control unit is increasingly EnOcean is a battery-free radio technology. The compo-
losing importance due to the unidirectional communica- nents get their energy from piezo crystals, for example,
9 tion, as no feedback can be transmitted from the ballast which transform motion into electrical pulses – tiny
to the controller changes in movement, pressure, light, temperature, or
• DALI for general lighting: vibration are sufficient to transfer radio signals. EnOcean
10 Lighting control, sensors, operating units, electronic
control gear and lamps communicate via the professional
transmits the signals on the licence-free 868 MHz fre-
quency band. Customers benefit from EnOcean radio
interface standard DALI (digital addressable lighting products in terms of planning flexibility and low installa-
interface). The DALI protocol is a bidirectional commu- tion costs. There is no wiring expense. This is a significant
11 nication standard with information exchange between advantage not only in the planning phase but also in the
the controller and the lamp. DALI is a manufacturer- later usage of the rooms. Adaptation of the wireless
independent interface standard for dimmable electronic components to the room usage is straightforward.
12 ballasts and provides high functionality as well as easy EnOcean light and presence sensors or wall pushbuttons
handling. Via a 2-core control line, a maximum of 64 DALI can be relocated without disturbing operational work-
control gears can be flexibly controlled either individually flows and without causing any dirt or noise
13 or together and in up to 16 groups. Switching and dimming
of the lighting is effected via the control line. A relay is
not required. Important information such as the lamp
status is saved in the control gear and forwarded to the
14 control unit as information. Advantages as opposed to
the 1…10 V interface (see Fig. 16/11):
15
16
17
Intro
duction
1
e. g., L1 L2 L3
1...10V
KNX/EIB
2
1...10V
3
1...10V
4
1...10V
1...10V
5
1...10 V
1...10V
6
1...10V
7
1...10V
9
e. g., L1 L2 L3
10
KNX/EIB
11
12
13
14
15
TIP04_13_185_EN
17
Fig. 16/11: Comparison of the system design between 1…10 V and DALI back to page 330
Intro
duction
1 • 3DIM:
3DIM can be used to implement three different con-
trol and dimming functions in one electronic ballast.
2 Tab. 16/6 shows a simple comparison of the different
scope of functions
• StepDIM:
3 In DALI mode, bidirectional communication takes place
between the EB and LMS, as described above. StepDIM is
used if a special control line (switched phase) is available
10
11
12 Operating modes
DALI
DALI
DALI
DALI StepDIM
StepDIM
StepDIM
StepDIM AstroDIM
AstroDIM
AstroDIM
AstroDIM
13
15
Flexibility to control different light points ✔
16 Autonomous dimming
Use of the existing bi-power approach with
✔
✔ 1)
conventional ballasts (half-night switching)
17
1) In mixed installations, special precautions have to be taken when installing the luminaire
2) DALI must already be available in the existing installation
Intro
duction
16.8.3 Efficiency Comparison for a (in particular Table 5.11.5) for the usage profile “Industrial
1
Refurbishing Example activities and crafts – Electrical and electronic industry
Rough assembly work”.
In the configuration and planning of lighting systems, 2
the operating costs are usually an important criterion. In In the example, no local restriction of the visual task is
existing installations, new technologies from time to time assumed. Therefore, the lighting must be designed as
raise the question: further operation, refurbishing, or
purchasing a new system?
general lighting so that the visual conditions are equally
good at all places in the room. For test stations and other
3
activities with higher visual requirements, additional
Various concepts should be compared to point out possible
differences with regard to the energy consumption as well
lighting with workplace luminaires is required. Sufficient
vertical illuminance must be ensured for workplaces 4
as investment and maintenance costs. Generally it is to be intended for handling large equipment.
expected that – by using energy-efficient lighting – savings
can be achieved compared to existing solutions. Possible mounting positions for the lighting systems are 5
defined on the basis of the structural conditions. Due to the
Apart from the selection of luminaires, the use of light beams in the room, the light point height is 5 m, resulting
management systems plays an important part for usage-
based planning. However, for the following comparison of
in a rather wide-angle radiation characteristic (LDC) for the
lighting system.
6
different lighting systems, assumptions and specifications
are applied for different mounting positions, illuminants,
and luminaires. The lighting solutions resulting from that
7
can be compared and evaluated. For holistic system com- Parameter Data for the considered example
parisons, it is essential that the quality, service life, service
performance, spare parts supply, and maintenance proper-
Room geometry (L × W × H) 50 m × 30 m × 6.5 m 8
ties of the luminaires as well as the compliance with the Reflectance values 70 × 50 × 20
(C × W × F)
quality characteristics are comparable. In the following, (Ceiling x Walls x Floor)
various lighting systems for the refurbishment of an indus-
trial hall are compared (Fig. 16/12).
Maintenance factor 0.67 (normal rooms and 9
a maintenance interval of 3 years)
Working plane h 0.75 m
The base data such as hall dimensions, working plane,
operating hours, lighting conditions, etc. for the determi-
Operating hours per year 5,000 h / a 10
nation of the lighting system are stated in Tab. 16/7. The ≥ 300 Ix
m
planning requirements for the illuminance maintenance
11
UGRL < 25
value m, the maximum glare (UGRL), the uniformity U0 ≥ 0.6
ratio of illuminance (U0), and the color rendering index
Color rendering index 80
Tab. 16/7 are selected in compliance with EN 12464-1
Tab. 16/7: System and lighting data for an industrial hall 12
13
14
15
16
17
Fig. 16/12: Lighting concept finding for the refurbishment of an industrial hall (left: 3D view; right: floor plan)
Intro
duction
1 As a result of the European Directive 2009/244/EC (so-called For the sample calculations, an existing lighting system
“light bulb decree”) and the Amendment 2015/1428/EU, with lighting trunking systems on the basis of fluorescent
just LED technology can be used for planning today as a lamps (T8 and T5) are compared with a moden LED system:
2 general rule. Particularly in case of refurbishment, the • SiTECO DUS lighting trunking system – T26 2 × 58 W – LLB
higher efficiency in operation can be a decisive advantage (low-loss ballast LLB, fluorescent lamp T26)
of LED technology compared to traditional lamp systems. Luminous flux 2 × 5,200 lm
3 Moreover, LEDs are suitable for all applications. By select-
ing and combining suitable LEDs, specific requirements are
Luminaire efficiency factor 71.9 %
• SiTECO Modario lighting trunking system – T16 2 × 35 W – EB
met. LEDs have a long service life, are highly efficient, have (electronic ballast EB, fluorescent lamp T16)
and spotlights can be applied at any position on the bar Efficiency factor method
with the aid of adapters.
8 In the simplified efficiency factor method, the data from
Remark: In high halls (with a height as from 6 m), Tab. 16/7 are used to determine the room index for direct
special ”Compact High Bay LED” luminaires are a suitable lighting (height difference between luminaire plane and
9 alternative. In the often dirty environments of industry and working plane):
handicrafts, it is reasonable to use luminaires with
a higher degree of protection. The luminaires remain clean a·b
k=
10 for a longer period, which extends their service life and
maintenance interval.
hN · (a + b)
50 m · 30 m
k=
11 (5 m – 0.75 m) · (50 m + 30 m)
k = 4.4
12
From Fig. 16/8 (in accordance with DIN V18599-4), a room
efficiency factor of 100 % can be read for a direct lighting
13 with k = 4.4 (in accordance with DIN V18599-4, the value is
to be interpolated between 1.03 and 1.05; limitation of the
room efficiency factor to 100 %). Using the formula
14
Em · A
n=
z · Φ · ηLB · ηR · MF
15
Intro
duction
13
14
15
TIP05_18_018
16
DUS, T26 2 × 58 W Modario, T16 2 × 35 W Modario, LED
17
Fig. 16/13: Radiation characteristics for the three sample lighting systems
Intro
duction
1
m N
2 30.0
27.5
25.0
3 22.5
20.0
4 17.5
15.0
12.5
5 10.0
7.5
6 5.0
2.5
0.0
7
TIP05_18_016_EN
0 5 10 15 20 25 30 35 40 45 50 m
10 User profile: industrial activities and crafts – electrical and electronic industry 5.11.5 (EN 12464-1, 8.2011)
rough assembly work, e.g., large transformers (Ra > 80.00)
11 Em
Horizontal
320 lx (≥ 300 lx)
Emin 252 lx
Emin/Em (U0) 0.76 (≥ 0.60)
13
SiTECO
2 80 Order no.: 5TR21271V4080
Luminaire name: Modario RS
Equipment: 1 × LED 4,000 K / CRI ≥ 80 / 52.3 W / 8,100 lm
14
Fig. 16/14: Excerpt of the results of a software calculation for the LED lighting system back to page 335
15
16
17
Intro
duction
4
Efficiency factor of the luminaire 71.9 % 93.4 % 100 %
Luminous flux of the luminaire 7,478 lm 6,164 lm 8,100 lm
Maintenance factor calculation 0.67 0.67 0.67
Illuminance
Uniformity
322
0.74
315
0.76
320
0.76
5
Costs (energy, maintenance)
Power consumption of the luminaire 145 W 79 W 52.3 W 6
Total efficiency of the luminaire 52 lm/W 78 lm/W 155 lm/W
Number of luminaires in the room 95 110 80
Specific power demand per surface 9.2 W/m2 5.8 W/m2 2.8 W/m2 7
Useful life of the system 20 a 20 a 20 a
Annual operating time
Energy consumption per year
7,300 h/a
100,557 kWh/a
7,300 h/a
63,437 kWh/a
7,300 h/a
30,543 kWh/a
8
Maintenance cycles in the useful life 14 8 2
Tab. 16/8: Result overview for the calculations with a software tool and basic data for energy cost considerations back to page 335 9
10
11
12
13
14
15
16
17
Intro
duction
TIP04_13_188_EN
safety lighting has to maintain the following functions
during a failure of the normal power supply:
11 • Lighting or back-lighting of the safety signs for emer- Safety lighting for high-risk workplaces
gency escape routes
• Lighting of emergency escape routes
12 • Lighting of fire fighting and alarm stations Fig. 16/15: Types of emergency lighting in accordance with
EN 1838
• Facilitating rescue actions.
16 EN 1838
EN 15193-1
BetrSichV
BGV A3
MLAR
EltBauVo
17 Tab. 16/9: Statutory bases, standards, and guidelines around safety lighting
Intro
duction
Self-contained system
back-lit safety sign
Illuminance (lx)
limitation (LPS)
4
(≤ 0.5 s)
(≤ 15 s)
people
8
High-rise buildings b) 15 3 d) × × × × × × × –
Emergency escape routes at b) 15 × × × × × × × ×
workplaces
9
Workplaces involving special hazards b) 0.5 c) × × × × × × – ×
a) Depending on the panic risk from 1 s to15 s and risk assessment.
b) Illuminance of safety lighting in accordance with EN 1838.
c) The period entailing danger for people.
10
d) 8 h for residential buildings if the lighting is not switched as detailed under g).
e) 3 h are sufficient if the lighting is switched as detailed under g).
f) 1 h is also permissible for overground areas in railway stations depending on the evacuation concept.
g) Rated operating time of 3 h if the safety lighting is continually operated together with the general lighting; it must be possible to identify at least one luminous
pushbutton as local switching device from any place even if the general lighting fails. Safety lighting is automatically switched off after a settable time if it is
11
supplied from a power source for safety purposes.
× = permissible – = not permissible
Tab. 16/10: Safety lighting requirements of physical structures for the gathering of people based on the pre-standard
VDE V 0108-100:2010 (Note: EN 50172:2004 correlates with VDE 0108-100:2005 and deviates from the newer pre-standard
VDE V 0108-100:2010 in some parts) 12
VDE V 0108-100 states the requirements placed on safety
lighting for the different rooms and buildings (see also
The German pre-standard VDE V 0108-100, which is based
on the older European standard EN 50172 for safety light-
13
Tab. 16/10). Standby lighting is used to enable people to ing systems, requires the following – among other things –
continue economically and / or technically important work for electrical installations, circuits, control and bus systems:
during the failure of normal lighting. For this reason, the • Along the course of emergency escape routes, two or 14
provisions applicable to safety lighting have to be fulfilled more lamps must be installed in every area for reasons of
and the wattage of standby lighting has to correspond to system integrity
that of normal lighting. At a low illuminance level, safety • If more than one safety luminaire is required in a room, 15
lighting may only be used for shutting down or terminating the number of luminaires must alternate between two
work processes. circuits. A maximum of 20 luminaires may be connected
into one circuit. Their load may not exceed 60 % of the
rated current of the overcurrent protection device
16
17
Intro
duction
Intro
duction
A disadvantage of battery power for safety lighting is that supply must comply with the requirements of MLAR 2005
1
self-contained luminaires become economically inefficient and the model building code EltBauVo 01 / 2009. In particu-
if more than about 15 to 25 luminaires are used. The lar, it must be ensured that the distribution boards for
boundary conditions for ageing-related luminaire replace- safety power supply are kept separate from the distribution 2
ment should always be looked into, too, when considering boards for normal power supply in functional endurance
the use of self-contained luminaires. class E30. This also applies in cases where these batteries
10
11
12
13
TIP04_13_189_EN
17
Intro
duction
1 The luminaires for safety lighting must be installed: When assessing the budget for emergency lighting, you
• At least 2 m above the ground should not only look into the pure investment costs, but
• Close to every exit door to be used in case of emergency 2) you should also factor in the expense for inspection, moni-
2 • At mandatory emergency exits and safety signs 2) toring, replacement, and power consumption (Fig. 16/17).
• Close to stairways 2), in order to have direct light on each Emergency lighting is to be installed, monitored, and
step maintained in accordance with VDE V 0108‑100 or the
3 • Close to every change of level 2)
• At every change of direction of the gangways/corridors 3)
older EN 50172. IEC 62034 (VDI 0711-400) describes the
requirements on automatic testing options in case these
• At every change of direction of the gangways/corridors 3) are to be provided. Safety luminaires have to comply
7 locations with fire fighting equipment that are not near the
emergency escape route or inside the area of anti-panic For an initial power estimation of the required emergency
lighting must be especially well lit (5 lx vertical illuminance lighting system, a correlation of the installation height of
measured on the equipment). Signs at emergency exits and the luminaires and the required power per area can be
8 exits along an emergency escape route must be lit or stated in the form of a straight line (Fig. 16/18). For a more
back-lit. detailed determination, the ratio 40 : 1 has to be adhered
to for the uniformity between the maximum and minimum
9 illuminance (Emax / Emin) in accordance with EN 1838 along
2 Usually a horizontal distance of 2 m as a maximum the center line of the emergency escape route. In that,
3 All directions must be illuminated emergency escape routes broader than 2 m are to be
10
12
BT *
13
Labor cost Luminaire Labor
Cost of Cost of Cost share
for visual and battery cost for
14 investment electricity
inspection
FT/BT *
replacement maintenance
Operating
cost
16
TIP04_13_190_EN
Time
* FT = Functional test
Cost of emergency lighting system
BT = Battery test
17
Fig. 16/17: Cost factors of emergency lighting
Intro
duction
divided into multiple strips of 2 m or equipped with anti- The illuminance control described before can also prolong
1
panic lighting. For workplaces involving special hazards, an the service life of the LED emergency lighting in continuous
illuminance of 15 lx (or 10 % of the illuminance of the operation and help reducing the operating costs, as LEDs
general lighting) and a ratio Emax / Emin of 10 : 1 must be have very good dimming properties. This is because the 2
adhered to. LEDs' efficiency diminishes with the operating current
increasing, so that the losses and thus the operating costs
Use of LEDs 3
In the past few years, the luminance of commercially
available LEDs has been increasing considerably. With more
than 100 lm / W, high-power diodes supply ten times the
Required output [W/m2]
0.7
4
luminous efficacy value of the first LEDs. At the same time,
LEDs provide their full light output immediately after 0.6
switch-on, which is a decisive criterion in particular for
0.5
5
emergency lighting. In IEC 60598-2-22 (VDE 0711-2-22),
emergency luminaires with fluorescent lamps in combina-
6
0.4
tion with neon starters are explicitly excluded from the use
in emergency lighting. 0.3
TIP04_13_191_EN
possible service life of 50,000 hours and more. To be
0.1
minded is that the degradation in the LED's semiconductor
material results in a decrease of the luminous flux in the
course of operation. The manufacturers declare the LED 0 2.5 5.0 7.5 10 8
service life as the time when the luminous intensity is still Room height [m]
50 % (sometimes the value is given for a luminous intensity
of 70 %) of the measured initial value. The LEDs' service life
is considerably influenced by the operating and ambient
Fig. 16/18: Power estimation for emergency lighting systems with
a central battery, based on experience gained with fluorescent
9
lamps at an illuminance of 1 lx back to page 342
temperature.
10
Requirements Safety lighting for emergency escape Anti-panic lighting Safety lighting for workplaces
for ... routes involving special hazards 11
Illuminance In 2 m wide strips, the horizontal The horizontal illuminance on the free The maintenance value of the
illuminance along the center line of an floor area (except for 0.5 m wide border illuminance on the working surface
emergency escape route must be 1 lx areas) must be 0.5 lx minimum. must be at least 10 % of the task-related
minimum maintenance value for the illuminance
or 15 lx minimum
12
The middle section of the emergency
escape route (at least 50 % of the route
width or a 1 m wide strip) must be lit
with 0.5 lx minimum 13
Duration Operating time 1 h min. Operating time 1 h min. Operating time corresponds at least to
the hazard duration for persons at the
17
Intro
duction
1 as well as the operating temperature increase. Therefore, LEDs, the battery volumes can be reduced (see Fig. 16/19)
the service life of a controlled LED is longer than that of an and the advantages of lithium ion accumulators can be
LED operated with permanently high current. Moreover, utilized. Compared to conventional nickel-metal-hydride
2 LEDs are virtually maintenance-free, which is an additional and nickel-cadmium batteries, lithium-ion accumulators
advantage as to the operating costs compared to conven- provide the following advantages:
tional lamps. Due to the low energy consumption of the
3
5
3m
100 %
6
2m
8
3m
50 %
9
2m
11
3m
10 %
12
2m
15 lx 1.5 lx 15 lx 1.5 lx
13 Emergency operation
14
Emin
Control mains emergency emergency Emin Emax
Ud = per luminaire consumption Energy
Variant Luminaire gear operation operation operation [lx] [lx] Emax [A] [A] demand
EVG +
Louvre luminaire,
No. 1 CEAG 5 3 100 % 4 113 1:28 0.250 0.750 100 %
white, 1 × 58 W
15
V-CG-S
Louvre luminaire, CEAG
No. 2 5 3 30 % 1.2 34 1:28 0.110 0.330 44.0 %
TIP04_13_192_EN
white, 1 × 58 W N-EVG
CEAG GuideLed SL CEAG
No. 3 with asymmetrical V-CG- 0 3 100 % 1.5 15 1:10 0.022 0.065 8.6 %
16 optics SLS500
Intro
duction
Ud = Emin / Emax greater than 1 : 40 For central battery systems, functional endurance must be
7
complied with in accordance with the requirements for the
As an intermediate stage, the use of controllable electronic installations to be supplied. MLAR for Germany and
ballasts (CEAG E-EB in Fig. 16/19) can already reduce the ÖVE / ÖNORM E8002-1 for Austria request a functional 8
energy demand considerably, and thus halve the size of the endurance of at least 30 minutes for safety lighting sys-
required accumulator. tems. Therefore, the battery systems, distributors, and lines
between the distributors, too, must comply with this
functional endurance.
9
Functional endurance
13
a) b) c)
14
MDNP MDNP MDNP
15
TIP04_13_193_EN
Fig. 16/20: Functional endurance for the distribution boards of a safety lighting system (MDSP = main distribution board for safety power 17
supply; MDNP = main distribution board for normal power supply) back to page 346
Intro
duction
4 (Fig. 16/20b)
• Use of fire-retardant components (non-combustible
materials) and covers for the enclosures of the distribu-
tion boards (Fig. 16/20c)
5 a) Fire-retardant room (except for outer walls)
b) Fire-retardant housing E30
Fire section II
c) Fire-retardant enclosure.
6 The floor space of each fire section is to be limited to
1,600 m2 at most. The functional endurance requirement
11
F30
12 Door
T30
MDSP
TIP04_13_194_EN
13
15
16
17
Intro 17 Appendix
duction
4
Requirements • High reliability of supply • Covering the energy demand for • Stable output voltage
• Overload capability standby power supply • Availability of sufficient continuous
• Low power loss • For turbocharger motors: load short-circuit power to ensure
• Low noise transfer in steps disconnect conditions
• No restrictions as to installation • Availability of sufficient continuous • Low-maintenance buffer batteries
5 • Compliance with the environment,
climate and fire safety categories
short-circuit power to ensure
disconnect conditions
for power supply, compliance with
noise level limits
• Low harmonic load for the
upstream network
6 Rated current
SN SN SN
IN = IN = IN =
3 · UN 3 · UN 3 · UN
7
Short-circuit currents • Sustained short-circuit current • Sustained short-circuit current • Sustained short-circuit current
3-phase: 3-phase: 3-phase:
8 IK3 =
IN · 100 % IK3 ≈ 2.1 · IN (for 0.02 s)
IK3, D ≈ 3 · IN
UK IK3 ≈ 1.5 · IN (for 0.02 – 5 s)
9 • Sustained short-circuit current
2-phase:
3
10 IK2 ≈ IK3 ·
2
13 current:
IN · 100 %
IK“ =
Xd“
14
Advantages • High transmission capacities • Distributed availability • Low losses
• Stable short-circuit currents • Self-contained power supply • Voltage stability
15
• Electrical isolation • Electrical isolation
Disadvantages • High inrush currents • Grid instability in case of power • Very low short-circuit currents
• Dependency on the public grid fluctuations
• Low short-circuit currents
16 IN Rated current, UN Rated voltage, UK Rated short-circuit voltage, SN Rated apparent power, Xd“ Subtransient reactance
17
Intro
duction
7
Elektrizitätsbinnenmarkt und zur Aufhebung der internal market in electricity and repealing Directive
Richtlinie 2003/54/EG 2003/54/EC
2014/32/EU EU-Richtlinie zur Harmonisierung der EU Directive on the harmonization of the laws of
Rechtsvorschriften der Mitgliedstaaten über die the Member States relating to the making available
2006/32/EC
Bereitstellung von Messgeräten auf dem Markt
EG-Richtlinie über Endenergieeffizienz und
on the market of measuring instruments
EC Directive on energy end-use efficiency and
8
Energiedienstleistungen und zur Aufhebung der energy services and repealing Council Directive
Richtlinie 93/76/EWG 93/76/EEC
2006/42/EC EG-Richtlinie über Maschinen und zur Änderung der EC Directive on machinery, and amending Directive 9
Richtlinie 95/16/EG 95/16/EC
2014/35/EU EU-Richtlinie zur Harmonisierung der EU Directive on the harmonization of the laws of
Rechtsvorschriften der Mitgliedstaaten über die
Bereitstellung elektrischer Betriebsmittel zur
the Member States relating to the making available
on the market of electrical equipment designed for
10
Verwendung innerhalb bestimmter Spannungen use within certain voltage limits
(„Niederspannungsrichtlinie“)
2009/125/EC EG-Richtlinie zur Schaffung eines Rahmens für die EC Directive establishing a framework for the 11
Festlegung von Anforderungen an die setting of ecodesign requirements for energy-
umweltgerechte Gestaltung related products
12
energieverbrauchsrelevanter Produkte
2010/30/EU EU-Richtlinie über die Angabe des Verbrauchs an EU Directive on the indication by labelling and
Energie und anderen Ressourcen durch standard product information of the consumption
energieverbrauchsrelevante Produkte mittels of energy and other resources by energy-related
2010/31/EU
einheitlicher Etiketten und Produktinformationen
EU-Richtlinie über die Gesamteffizienz von
products
EU Directive on the energy performance of
13
Gebäuden buildings
2012/27/EU EU-Richtlinie zur Energieeffizienz, zur Änderung der
Richtlinien 2009/125/EG und 2010/30/EU und zur
EU Directive on energy efficiency, amending
Directives 2009/125/EC and 2010/30/EU and 14
Aufhebung der Richtlinien 2004/8/EG und 2006/32/ repealing Directives 2004/8/EC and 2006/32/EC
EG
2014/30/EU EU-Richtlinie zur Harmonisierung der
Rechtsvorschriften der Mitgliedstaaten über die
EU Directive on the harmonization of the laws of
the Member States relating to electromagnetic
15
elektromagnetische Verträglichkeit compatibility
16
244/2009 + EG-Verordnung zur Durchführung der Richtlinie EC Regulation implementing Directive 2005/32/EC
859/2009 2005/32/EG für die Anforderungen an die with regard to ecodesign requirements for non-
umweltgerechte Gestaltung von Haushaltslampen directional household lamps – ecodesign
mit ungebündeltem Licht + Anforderungen an die requirements on ultraviolet radiation of non-
Ultraviolettstrahlung von Haushaltslampen mit directional household lamps
ungebündeltem Licht 17
4 EU treaties
(2009)
safety and health)
Article 154 Titel VII – Gemeinsame Regeln betreffend Title VII – Common Rules on Competition, Taxation
EU treaties Wettbewerb, Steuerfragen und Angleichung der and Approximation of Laws (relating to the free
5 (2009) Rechtsvorschriften (zum freien Warenverkehr) movement of goods)
CIE 97:2005 Leitfaden zur Wartung von elektrischen Guide on the Maintenance of Indoor Electric
Beleuchtungsanlagen im Innenraum Lighting Systems
6 IEC/TR
60269‑5
VDE 0636‑5 Niederspannungssicherungen – Teil 5: Leitfaden für
die Anwendung von Niederspannungssicherungen
Low-voltage fuses – Part 5: Guidance for the
application of low-voltage fuses
D‑A‑CH‑CZ- Technische Regeln zur Beurteilung von Technical rules for the assessment of network
directive Netzrückwirkungen disturbances
7 EN 12193 Licht und Beleuchtung – Sportstättenbeleuchtung Light and lighting – Sports lighting
EN 12464‑1 additional Licht und Beleuchtung – Beleuchtung von Light and lighting – Lighting of work places –
DIN EN 12464-1 Arbeitsstätten – Teil 1: Arbeitsstätten in Part 1: Indoor work places
8 supplement 1 Innenräumen
EN 12464‑2 Licht und Beleuchtung – Beleuchtung von Light and lighting – Lighting of work places –
Arbeitsstätten – Teil 2: Arbeitsplätze im Freien Part 2: Outdoor work places
13 EN 50172 VDE
0108‑100:2005
Sicherheitsbeleuchtungsanlagen Emergency escape lighting systems
EN 50174‑2 VDE 0800‑174‑2 Informationstechnik – Installation von Information technology – Cabling installation –
Kommunikationsverkabelung – Teil 2: Part 2: Installation planning and practices inside
14 Installationsplanung und Installationspraktiken in
Gebäuden
buildings
EN 50272 ‑1 VDE 0510‑1 Sicherheitsanforderungen an Batterien und Safety requirements for secondary batteries and
17
5
60050‑601 Erzeugung, Übertragung und Verteilung elektrischer Chapter 601 : Generation, transmission and
Energie – Allgemeines distribution of electricity – General
IEC Umgebungseinflüsse – Teil 2-30: Prüfverfahren – Environmental testing – Part 2-30: Tests – Test Db:
60068‑2‑30 Prüfung Db: Feuchte Wärme, zyklisch (12 + 12 Damp heat, cyclic (12 h + 12 h cycle)
10
Kurzschlussfestigkeit short circuit
IEC 60076‑6 VDE 0532‑76‑6 Leistungstransformatoren – Teil 6: Drosselspulen Power transformers – Part 6: Reactors
IEC 60076‑7 VDE 0532‑76‑7 Leistungstransformatoren – Teil 7: Power transformers – Part 7: Loading guide for oil-
11
Belastungsrichtlinie für ölgefüllte immersed power transformers
Leistungstransformatoren
IEC 60204‑1 VDE 0113‑1 Sicherheit von Maschinen – Elektrische Ausrüstung Safety of machinery – Electrical equipment of
von Maschinen – Teil 1: Allgemeine Anforderungen machines – Part 1: General requirements
IEC 60204‑11 VDE 0113‑11 Sicherheit von Maschinen – Elektrische Ausrüstung
von Maschinen – Teil 11: Anforderungen an
Safety of machinery – Electrical equipment of
machines – Part 11: Requirements for HV
12
Hochspannungsausrüstung für Spannungen über equipment for voltages above 1000 V a.c. or 1500
1000 V Wechselspannung oder 1500 V V d.c. and not exceeding 36 kV
Gleichspannung aber nicht über 36 kV 13
IEC VDE 0435‑3151 Messrelais und Schutzeinrichtungen – Teil 151: Measuring relays and protection equipment –
60255‑151 Funktionsanforderungen für Über-/ Part 151: Functional requirements for over/under
17
Neue Isolieröle auf Mineralölbasis für mineral insulating oils for transformers and
Transformatoren und Schaltgeräte switchgear
1 IEC
60364‑4‑41
VDE 0100‑410 Elektrische Anlagen von Gebäuden – Teil 4-41:
Schutzmassnahmen – Schutz gegen elektrischen
Low-voltage electrical installations – Part 4-41:
Protection for safety – Protection against electric
Schlag shock
2
IEC VDE 0100‑430 Errichten von Niederspannungsanlagen – Teil 4-43: Low-voltage electrical installations – Part 4-43:
60364‑4‑43 Schutzmaßnahmen – Schutz bei Überstrom Protection for safety – Protection against
overcurrent
IEC VDE 0100‑520 Errichten von Niederspannungsanlagen – Teil 5-52: Low-voltage electrical installations – Part 5-52:
5
– Erdungsanlagen, Schutzleiter und Earthing arrangements and protective conductors
Schutzpotentialausgleichsleiter
IEC VDE 0100‑560 Errichten von Niederspannungseinrichtungen – Low-voltage electrical installations – Part 5-56:
60364‑5‑56 Teil 5-56: Auswahl und Errichtung elektrischer Selection and erection of electrical equipment –
7 IEC
60364‑7‑710
VDE 0100‑710 Elektrische Anlagen von Gebäuden – Teil 7-710:
Anforderungen für Betriebsstätten, Räume und
Electrical installations of buildings – Part 7-710:
Requirements for special installations or locations;
Anlagen besonderer Art; Medizinisch genutzte Medical locations
Bereiche
8 IEC
60364‑7‑718
VDE 0100‑718 Errichten von Niederspannungsanlagen –
Teil 7-718: Anforderungen für Betriebsstätten,
Low-voltage electrical installations – Part 7-718:
Requirements for special installations or locations –
Räume und Anlagen besonderer Art – Öffentliche Communal facilities and workplaces
Einrichtungen und Arbeitsstätten
9 IEC
60364‑7‑729
VDE 0100‑729 Errichten von Niederspannungsanlagen –
Anforderungen für Betriebsstätten, Räume und
Low-voltage electrical installations – Part 7-729:
Requirements for special installations or locations –
Anlagen besonderer Art – Teil 7-729: Operating or maintenance gangways
Bedienungsgänge und Wartungsgänge
10 IEC 60529 VDE 0470‑1 Schutzarten durch Gehäuse (IP-Code) Degrees of protection provided by enclosures (IP
Code)
IEC 60570 VDE 0711‑300 Elektrische Stromschienensysteme für Leuchten Electrical supply track systems for luminaires
11 IEC 60598‑1 VDE 0711‑1 Leuchten – Teil 1: Allgemeine Anforderungen und
Prüfungen
Luminaires – Part 1: General requirements and
tests
IEC VDE 0711‑2‑22 Leuchten – Teil 2-22: Besondere Anforderungen – Luminaires – Part 2-22: Particular requirements –
12 60598‑2‑22 Leuchten für Notbeleuchtung Luminaires for emergency lighting
IEC 60617‑DB Graphische Symbole für Schaltpläne (Schaltzeichen) Graphical symbols for diagrams / Online-Database –
/ Online-Datenbank – Die Datenbank ersetzt IEC The database replaces part 2 to 13 of IEC 60617
60617-2 bis -13
13 IEC 60664‑1 VDE 0110‑1 Isolationskoordination für elektrische Betriebsmittel Insulation coordination for equipment within low-
in Niederspannungsanlagen – Teil 1: Grundsätze, voltage systems – Part 1: Principles, requirements
Anforderungen und Prüfungen and tests
15 IEC
rungen; Anleitung für Errichtung und Betrieb
Fernwirkeinrichtungen und -systeme – Teil 5-101:
installation and operation
Telecontrol equipment and systems – Part 5-101:
60870‑5‑101 Übertragungsprotokolle; Anwendungsbezogene Transmission protocols; Companion standard for
Norm für grundlegende Fernwirkaufgaben basic telecontrol tasks
16 IEC Fernwirkeinrichtungen und -systeme – Teil 5-104: Telecontrol equipment and systems – Part 5-104:
60870‑5‑104 Übertragungsprotokolle – Zugriff für IEC 60870-5- Transmission protocols – Network access for IEC
101 auf Netze mit genormten Transportprofilen 60870-5-101 using standard transport profiles
2
Leitungsschutzschalter für Wechselstrom (AC) lations – Part 1: Circuit-breakers for a.c. operation
IEC 60898‑2 VDE 0641‑12 Leitungsschutzschalter für Hausinstallationen und Circuit-breakers for overcurrent protection for
ähnliche Zwecke – Teil 2: Leitungsschutzschalter für household an similar installations – Part 2: Circuit-
Wechsel- und Gleichstrom breakers for a.c. and d.c. operation
IEC 60947‑1 VDE 0660‑100 Niederspannungsschaltgeräte – Teil 1: Allgemeine Low-voltage switchgear and controlgear – Part 1: 3
Festlegungen General rules
4
IEC 60947‑2 VDE 0660‑101 Niederspannungsschaltgeräte – Teil 2: Low-voltage switchgear and controlgear – Part 2:
Leistungsschalter Circuit-breakers
IEC 60947‑3 VDE 0660‑107 Niederspannungsschaltgeräte – Teil 3: Lastschalter, Low-voltage switchgear and controlgear – Part 3:
Trennschalter, Lasttrennschalter und Schalter- Switches, disconnectors, switch-disconnectors and
Sicherungs-Einheiten fuse-combination units 5
IEC 60947‑4‑1 VDE 0660‑102 Niederspannungsschaltgeräte – Teil 4-1: Schütze Low-voltage switchgear and controlgear – Part 4-1:
und Motorstarter – Elektromechanische Schütze und Contactors and motor-starters – Electromechanical
Motorstarter contactors and motor-starters
6
IEC 60947‑4‑2 VDE 0660‑117 Niederspannungsschaltgeräte – Teil 4-2: Schütze Low-voltage switchgear and controlgear – Part 4-2:
und Motorstarter – Halbleiter-Motor-Steuergeräte Contactors and motor-starters – AC semiconductor
7
und -Starter für Wechselspannungen motor controllers and starters
IEC 60947‑8 VDE 0660‑302 Niederspannungsschaltgeräte – Teil 8: Low-voltage switchgear and controlgear – Part 8:
Auslösegeräte für den eingebauten thermischen Control units for built-in thermal protection (PTC)
Schutz (PTC) von rotierenden elektrischen for rotating electrical machines
Maschinen
8
IEC VDE 0839‑2‑12 Elektromagnetische Verträglichkeit (EMV) – Electromagnetic compatibility (EMC) – Part 2-12:
61000‑2‑12 Teil 2-12: Umgebungsbedingungen; Environment; Compatibility levels for low-
Verträglichkeitspegel für niederfrequente
leitungsgeführte Störgrößen und Signalübertragung
frequency conducted disturbances and signaling in
public medium-voltage power supply systems; 9
in öffentlichen Mittelspannungsnetzen; EMV- Basic EMC Publication
Grundnorm
13
61000‑3‑11 Teil 3-11: Grenzwerte; Begrenzung von Spannungs Limits – Limitation of voltage changes,
änderungen, Spannungsschwankungen und Flicker voltage fluctuations and flicker in public
in öffentlichen Niederspannungs- low-voltage supply systems – Equipment with rated
Versorgungsnetzen; Geräte und Einrichtungen mit current ≤ 75 A and subject to
einem Bemessungsstrom ≤ 75 A, die einer conditional connection
Sonderanschlussbedingung unterliegen 14
IEC VDE 0838‑12 Elektromagnetische Verträglichkeit (EMV) – Electromagnetic compatibility (EMC) – Part 3-12:
61000‑3‑12 Teil 3-12: Grenzwerte für Oberschwingungsströme, Limits – Limits for harmonic currents produced by
verursacht von Geräten und Einrichtungen mit
einem Eingangsstrom > 16 A und ≤ 75 A je Leiter,
equipment connected to public low-voltage
systems with input current > 16 A und ≤ 75 A per 15
die zum Anschluss an öffentliche phase
Niederspannungsnetze vorgesehen sind
2 IEC
61000‑4‑15
VDE 0847‑4‑15 Elektromagnetische Verträglichkeit (EMV) –
Teil 4-15: Prüf- und Messverfahren – Flickermeter –
Electromagnetic compatibility (EMC) – Part 4-15:
Testing and measurement techniques –
Funktionsbeschreibung und Auslegungsspezifikation Flickermeter – Functional and design specifications
3
IEC VDE 0847‑4‑30 Elektromagnetische Verträglichkeit (EMV) – Electromagnetic compatibility (EMC) – Testing and
61000‑4‑30 Teil 4-30: Prüf- und Messverfahren – Verfahren zur measurement techniques – Power quality
Messung der Spannungsqualität measurement methods
IEC 61000‑4‑7 VDE 0847‑4‑7 Elektromagnetische Verträglichkeit (EMV) – Teil 4-7: Electromagnetic compatibility (EMC) – Part 4-7:
4 Prüf- und Messverfahren; Allgemeiner Leitfaden für
Verfahren und Geräte zur Messung von
Testing and measurement techniques; General
guide on harmonics and interharmonics
Oberschwingungen und Zwischenharmonischen in measurements and instrumentation, for power
Stromversorgungsnetzen und supply systems and equipment connected thereto
IEC 61439‑1 VDE 0660‑600‑1 Niederspannungs-Schaltgerätekombinationen – Low-voltage switchgear and controlgear assemblies
Teil 1: Allgemeine Festlegungen – Part 1: General rules
10 IEC 61439‑2 VDE 0660‑600‑2 Niederspannungs-Schaltgerätekombinationen – Low-voltage switchgear and controlgear assemblies
Teil 2: Energie-Schaltgerätekombinationen – Part 2: Power switchgear and controlgear
assemblies
12
IEC 61439‑6 VDE 0660‑600‑6 Niederspannungs-Schaltgerätekombinationen – Low-voltage switchgear and controlgear assemblies
Teil 6: Schienenverteilersysteme (busways) – Part 6: Busbar trunking systems (busways)
IEC 61547 VDE 0875‑15‑2 Einrichtungen für allgemeine Beleuchtungszwecke – Equipment for general lighting purposes – EMC
EMV-Störfestigkeitsanforderungen immunity requirements
13 IEC 61800‑3 VDE 0160‑103 Drehzahlveränderbare elektrische Antriebe – Teil 3: Adjustable speed electrical power drive systems –
Anforderungen einschließlich spezieller Part 3: EMC requirements and specific test methods
Prüfverfahren
14 IEC 61869‑1 VDE 0414‑9‑1 Messwandler – Teil 1: Allgemeine Anforderungen Instrument transformers – Part 1: General
requirements
IEC 61869‑2 VDE 0414‑9‑2 Messwandler – Teil 2: Zusätzliche Anforderungen Instrument transformers – Part 2: Additional
15
für Stromwandler requirements for current transformers
IEC 61869‑3 VDE 0414‑9‑3 Messwandler – Teil 3: Zusätzliche Anforderungen Instrument transformers – Part 3: Additional
für induktive Spannungswandler requirements for inductive voltage transformers
16
IEC 61869‑4 VDE 0414‑9‑4 Messwandler – Teil 4: Zusätzliche Anforderungen Instrument transformers – Part 4: Additional
für kombinierte Wandler requirements for combined transformers
IEC 61936‑1 VDE 0101‑1 Starkstromanlagen mit Nennwechselspannungen Power installations exceeding 1 kV a.c. – Part 1:
über 1 kV – Teil 1: Allgemeine Bestimmungen Common rules
17
4
und programmierbarer elektronischer electronic control systems
Steuerungssysteme
IEC VDE 0671‑100 Hochspannungs-Schaltgeräte und -Schaltanlagen – High-voltage switchgear and controlgear –
62271‑100 Teil 100: Wechselstrom-Leistungsschalter Part 100: Alternating-current circuit-breakers
IEC
62271‑102
VDE 0671‑102 Hochspannungs-Schaltgeräte und -Schaltanlagen –
Teil 102: Wechselstrom-Trennschalter und
High-voltage switchgear and controlgear –
Part 102: Alternating current disconnectors and
5
-Erdungsschalter earthing switches
IEC
62271‑103
VDE 0671‑103 Hochspannungs-Schaltgeräte und -Schaltanlagen –
Teil 103: Lastschalter für Bemessungsspannungen
High-voltage switchgear and controlgear –
Part 103: Switches for rated voltages above 1 kV up 6
über 1 kV bis einschliesslich 52 kV to and including 52 kV
IEC VDE 0671‑105 Hochspannungs-Schaltgeräte und -Schaltanlagen – High-voltage switchgear and controlgear –
62271‑105 Teil 105: Wechselstrom-Lastschalter-Sicherungs-
Kombinationen für Bemessungsspannungen über 1
Part 105: Alternating current switch-fuse
combinations for rated voltages above 1 kV up to
7
kV bis einschliesslich 52 kV and including 52 kV
8
IEC VDE 0671‑106 Hochspannungs-Schaltgeräte und -Schaltanlagen – High-voltage switchgear and controlgear –
62271‑106 Teil 106: Wechselstrom-Schütze, Part 106: Alternating current contactors, contactor-
Kombinationsstarter und Motorstarter mit Schützen based controllers and motor-starters
IEC VDE 0671‑200 Hochspannungs-Schaltgeräte und -Schaltanlagen – High-voltage switchgear and controlgear –
62271‑200 Teil 200: Metallgekapselte Wechselstrom-
Schaltanlagen für Bemessungsspannungen über 1
Part 200: AC metal-enclosed switchgear and
controlgear for rated voltages above 1 kV and up to
9
kV bis einschliesslich 52 kV and including 52 kV
10
IEC VDE 0671‑201 Hochspannungs-Schaltgeräte und -Schaltanlagen – High-voltage switchgear and controlgear –
62271‑201 Teil 201: Isolierstoffgekapselte Wechselstrom- Part 201: AC insulation-enclosed switchgear and
Schaltanlagen für Bemessungsspannungen über 1 controlgear for rated voltages above 1 kV and up to
kV bis einschliesslich 52 kV and including 52 kV
IEC
62271‑202
VDE 0671‑202 Hochspannungs-Schaltgeräte und -Schaltanlagen –
Teil 202: Fabrikfertige Stationen für Hochspannung/
High-voltage switchgear and controlgear –
Part 202: High voltage/low voltage prefabricated 11
Niederspannung substation
IEC 62305‑2 VDE 0185‑305‑2 Blitzschutz – Teil 2: Risiko-Management Protection against lightning – Part 2: Risk
management 12
IEC 62305‑3 VDE 0185‑305‑3 Blitzschutz – Teil 3: Schutz von baulichen Anlagen Protection against lightning – Part 3: Physical
und Personen damage to structures and life hazard
IEC 62305‑4 VDE 0185‑305‑4 Blitzschutz – Teil 4: Elektrische und elektronische
Systeme in baulichen Anlagen
Protection against lightning – Part 4: Electrical and
electronic systems within structures
13
IEC 62471 VDE 0837‑471 Photobiologische Sicherheit von Lampen und Photobiological safety of lamps and lamp systems
14
Lampensystemen
IEC 62493 VDE 0848‑493 Beurteilung von Beleuchtungseinrichtungen Assessment of lighting equipment related to
bezüglich der Exposition von Personen gegenüber human exposure to electromagnetic fields
elektromagnetischen Feldern
IEC 62722-1 Arbeitsweise von Leuchten – Teil 1: Allgemeine Luminaire performance – Part 1: General 15
Anforderungen Requirements
IEC 62722-2-1 Arbeitsweise von Leuchten – Teil 2-1: Besondere Luminaire performance – Part 2-1: Particular
4
IEEE 446 Empfohlene Praxis für Not- und Reservestromnetze Recommended Practice for Emergency and Standby
für industrielle und gewerbliche Zwecke Power Systems for Industrial and Commercial
Applications (Orange book)
ISO 12100 Sicherheit von Maschinen – Allgemeine Safety of machinery – General principles for design
5 Gestaltungsleitsätze – Risikobeurteilung und
Risikominderung
– Risk assessment and risk reduction
ISO 13849‑1 Sicherheit von Maschinen – Sicherheitsbezogene Safety of machinery – Safety-related parts of
Teile von Steuerungen – Teil 1: Allgemeine control systems – Part 1: General principles for
6 Gestaltungsleitsätze design
ISO 14001 Umweltmanagementsysteme. Anforderungen mit Environmental Management Systems –
Anleitung zur Anwendung Specification with Guidance for Use
11
ISO 3864 Normenreihe graphische Symbole – Group of standards for graphical symbols – Safety
Sicherheitsfarben und Sicherheitszeichen colors and safety signs
ISO 50001 Energiemanagementsysteme – Anforderungen mit Energy management systems – Requirements with
Anleitung zur Anwendung guidance for use
12 ISO 9001 Qualitätsmanagementsysteme – Anforderungen Quality management systems – Requirements
VDE 0710‑13 Leuchten mit Betriebsspannungen unter 1000 V; Luminaires with operating voltages below 1000 V;
Ballwurfsichere Leuchten VDE-Bestimmung luminaires safety to ball throwing VDE Specification
13 DIN 4102‑2 Brandverhalten von Baustoffen und Bauteilen; Fire Behavior of Building Materials and Building
Bauteile, Begriffe, Anforderungen und Prüfungen Components; Building Components; Definitions,
Requirements and Tests
15
EltBauVO Verordnung über den Bau von Betriebsräumen für Regulation for the construction of operation rooms
elektrische Anlagen for electrical equipment
HOAI 2013 Deutsche Honorarordnung für Architekten und German fee structure imposed on architects and
Ingenieure engineers
11
DIN V 18599‑10 Energetische Bewertung von Gebäuden – Energy efficiency of buildings – Calculation of the
Berechnung des Nutz-, End- und net, final and primary energy demand for heating,
Primärenergiebedarfs für Heizung, Kühlung, cooling, ventilation, domestic hot water and
Lüftung, Trinkwarmwasser und Beleuchtung – lighting – Part 10: Boundary conditions of use,
Teil 10: Nutzungsrandbedingungen, Klimadaten climatic data
DIN V 18599‑11 Energetische Bewertung von Gebäuden – Energy efficiency of buildings – Calculation of the 12
Berechnung des Nutz-, End- und net, final and primary energy demand for heating,
Primärenergiebedarfs für Heizung, Kühlung, cooling, ventilation, domestic hot water and
Lüftung, Trinkwarmwasser und Beleuchtung – Teil
11: Gebäudeautomation
lighting – Part 11: Building automation
13
DIN Spec 67600 Biologisch wirksame Beleuchtung – Biologically effective illumination – Design
Planungsempfehlungen guidelines
ASR Technische Regeln für Arbeitsstätten Technical workplace regulation 14
ASR A3.4 Technische Regeln für Arbeitsstätten in Bezug auf Technical workplace regulation on lighting systems
Beleuchtung
DGUV 215-410 Bildschirm- und Büroarbeitsplätze – Leitfaden für die Monitor and office workplaces – Design guidelines 15
Gestaltung
VDI 6011‑1 Lichttechnik – Optimierung von Tageslichtnutzung Lighting technology – Optimization of daylight use
und künstlicher Beleuchtung – Grundlagen und
allgemeine Anforderungen
and artificial lighting – Fundamentals and basic
requirements 16
DIN SPEC Strahlungsphysik im optischen Bereich und Optical radiation physics and illuminating
5031‑100 Lichttechnik – Teil 100: Über das Auge vermittelte, engineering – Part 100: Non-visual effects of ocular
nichtvisuelle Wirkung des Lichts auf den Menschen
– Grössen, Formelzeichen und Wirkungsspektren
light on human beings – Quantities, symbols and
action spectra
17
Intro
duction
2 MBO
Gesundheit bei der Arbeit
Musterbauordnung Standard building code
LBO Landesbauordnung Building regulation of the state ("Land")
5
ASchG ArbeitnehmerInnenschutzgesetz Occupational Safety and Health at Work for
Employees
VDE V 0108‑100 Sicherheitsbeleuchtungsanlagen Emergency escape lighting systems
6
DIN 4844‑1 Graphische Symbole – Sicherheitsfarben und Graphical symbols – Safety colors and safety signs
Sicherheitszeichen – Teil 1: Erkennungsweiten und – Part 1: Observation distances and colorimetric
farb- und photometrische Anforderungen and photometric requirements
DIN 4844‑2 Graphische Symbole – Sicherheitsfarben und Graphical symbols – Safety colors and safety signs
ÖVE/ÖNORM Normenreihe zu Starkstromanlagen und Series of standards about power installation and
E8002 Sicherheitsstromversorgung in baulichen Anlagen safety power supply in communal facilities
8 für Menschenansammlungen
DIN 4102‑12 Brandverhalten von Baustoffen und Bauteilen – Fire behavior of building materials and building
Teil 12: Funktionserhalt von elektrischen components – Part 12: Circuit integrity
9
Kabelanlagen; Anforderungen und Prüfungen maintenance of electric cable systems;
requirements and testing
VDE‑AR‑N 4105 Erzeugungsanlagen am Niederspannungsnetz – Generators connected to the low-voltage
Technische Mindestanforderungen für Anschluss distribution network – Technical requirements for
10 und Parallelbetrieb von Erzeugungsanlagen am
Niederspannungsnetz
the connection to and parallel operation with low-
voltage distribution networks
VDE-AR-N 4100 Technische Regeln für den Anschluss von Technical requirements for the connection and
draft Kundenanlagen an das Niederspannungsnetz und operation of customer installations to the low
11 deren Betrieb (TAR Niederspannung) voltage network (TAR low voltage)
VDE-AR-N 4110 Technische Regeln für den Anschluss von Technical requirements for the connection and
draft Kundenanlagen an das Mittelspannungsnetz und operation of customer installations to the medium
12 GL 2010
deren Betrieb (TAR Mittelspannung) voltage network (TAR medium voltage)
Guideline for the Certification of Wind Turbines
Edition 2010
13
GL 2012 Guideline for the Certification of Offshore Wind
Turbines Edition 2012
14
15
16
17
Intro
duction
A C
2
A/D Analog/digital CAES Compressed-air energy storage
AC Alternating current CB Conventional ballast 3
ACB Air circuit-breaker CBEMA Computer and Business Equipment
Manufacturing Association
AEC Availability environment classification
AEP Average electricity price
CBR Circuit-breaker incorporating residual 4
current protection
AF Audio frequency CCA CENELEC Certification Agreement
AFDD Arc fault detection device CEN Comité européen de normalisation; 5
AFE Active front end European Committee for Standardization
CENELEC Comité Européen de Normalisation
AIS Air-insulated switchgear
ANSI American National Standards Institute
Électrotechnique; European Committee 6
for Electrotechnical Standardization
AS Auxiliary switch CEP Central earthing point
ASR Technical workplace regulation (Germany) CFHC Chlorofluorohydrocarbon 7
AVC Availability class CHP Combined heat and power station
AWG American Wire Gauge CIE Commission Internationale de l’Éclairage;
International Commission on Illumination 8
B CO Carbon monoxide
BAC/TBM Building automation and control / CPS Central power supply system 9
Technical building management CSA CSA Group (former Canadian Standards
BDEW Bundesverband der Energie- und Wasser Association)
wirtschaft e.V. (Registered Federal
Association of the Energy and Water
10
D
Industry, Germany)
DaC Data center
BGR/GUV Berufsgenossenschaftliche Regeln /
Gesetzliche Unfallversicherung (German DALI Digital adressable lighting interface 11
Rules for Social Accident Insurance) DBO Distribution boards intended to be operated
by ordinary persons
BGV Berufsgenossenschaftliche Vorschriften
(German Standards for Social Accident DC Direct current
12
Insurance) DGUV Deutsche Gesetzliche Unfallversicherung
BIM Building information models (German Social Accident Insurance)
DI Differential current protection device
13
BSI Bundesamt für Sicherheit in der
Informationstechnik (Federal Office (in conjunction with FI, now RCD =
residual current-operated protective device)
for Information Security, Germany)
BT Battery test, continuous DIAZED Diametrically graded two-part Edison fuse 14
BTS Busbar trunking system DIN VDE Deutsches Institut für Normung / Verband der
Elektrotechnik Elektronik Informationstechnik
(German Institute for Standardization / German 15
Association for Electrical, Electronic &
Information Technologies)
DMT Definite minimum time 16
(overcurrent protection)
DMX Digital multiplex, digital communication
protocol for lighting control 17
DSO Distribution system operator
Intro
duction
1 E I
EB Electronic ballast I&C Instrumentation and control
2
EC, ECC European Community, ICT Information and communication technology
European Economic Community
IDMTL Inverse definite minimum time leakage
ECG Electrocardiogram (overcurrent protection)
safety standards
K
EnEV Energieeinsparverordnung (German Energy
7 Saving Ordinance) Kcmil 1,000 circular mil (circular mil means area
EnMS Energy management system of a circle with a diameter of 1/1,000 inch;
1 kcmil = 0,5067 mm2)
8 EPROM Erasable, programmable read-only-memory
ESD Electrostatic discharge
L
ESPS Emergency standby power system
LDC Light distribution curve
9 ETU Electronic trip unit
LED Light emitting diode
LEMP Lightning electromagnetic pulse
F
10 FC Fault signal contact
LiTG Lichttechnische Gesellschaft e. V.
(German Light Engineering Society)
FGW Fördergesellschaft Windenergie e. V. (German
Society for the Promotion of Wind Energy) LLB Low-loss ballast
11 FI Fault current interrupter LLMF Lamp lumen maintenance factor
Intro
duction
M R 1
MCB Miniature circuit-breaker RAM Random access memory
MCC Motor control center
MCCB Molded-case circuit-breaker
RCBO Residual current operated circuit-breaker
with integrated overcurrent protection 2
MDNP Main distribution board for normal power RCCB Residual current operated circuit-breaker
(without integral overcurrent protection)
supply
RCD Residual current-operated protective device
3
MDSP Main distribution board for safety power
supply (previously FI)
17
Intro
duction
1 T X
TAR Technical application rule (Germany) XDMT General for either DMT or IDTML protection
4 U
UCTE Union for the Co-ordination of Transmission
5 of Electricity
UGR Unified glare rating
UL Underwriters Laboratories
6 UPS Uninterruptible power supply
UR Undervoltage release
7 UV Ultraviolet
V
8 VDN Verband der Netzbetreiber e. V.
(German Association of Network Operators)
VFD Voltage and frequency dependent,
9 off-line UPS
VFI Voltage and frequency independent,
on-line UPS
10 VI Voltage independent, line-interactive UPS
11
12
13
14
15
16
17
Intro
duction
17.4 Bibliography 1
2 2011
and Technology
Kiank / Fruth
(HOAI)
Planning Guide for Power Distribution Plants
3
3 2016 Boston Consulting Group Digital in Engineering & Construction: The Transformative Power of
6 2007
Council TC3
VEÖ, VSE, CSRES, VDN, VWEW D-A-CH-CZ – Technische Regeln zur Beurteilung von Netzrückwirkungen
5
(Technical Rules for the Assessment of Network Disturbances)
7 2014 Official Journal of the European Union “L96/79 Directive 2014/30/EC of the European Parliament and of the
Council on the harmonization of the laws of the Member States relating to 6
electromagnetic compatibility”
8 2005 A. Held Oracle 10g Hochverfügbarkeit
9 2013 Bundesamt für Sicherheit in der HV-Kompendium Band G (high availability compendium volume G): 7
Informationstechnik (German Federal Introduction and methodological bases
Office for Information Security)
10 2005 H. Schau Schutz vor Störlichtbögen – II. Workshop Elektrische Sicherungen, Ilmenau
8
11 1976 F. Pigler Druckbeanspruchung der Schaltanlagenräume durch Störlichtbögen,
Energiewirtschaftliche Tagesfragen Vol. 26, No. 3
12 2008 BDEW Whitepaper „Anforderungen an sichere Steuerungs- und
Telekommunikationssysteme“ 9
13 2003 ZVEI Unterbrechungsfreie Stromversorgung, 2nd edition
14 2016 Fördergesellschaft Windenergie (Society
for the Promotion of Wind Energy)
Technical Guidelines for Generator Units and Plants, Part 3 (TR3):
Determination of the electrical properties of generator units and plants 10
connected to the medium-, high-, and extra-high-voltage grid
15 2010 Germanischer Lloyd Guideline for the Certification of Wind Turbines, Edition 2010 (GL 2010)
16 2012 Germanischer Lloyd Guideline for the Certification of Wind Turbines, Edition 2012 (GL 2012) 11
17 2010 M. Weiß Datenauswertung von Energiemanagementsystemen
18 2009 Federal Law Gazette (Germany) 2009
Part I No. 23 (BGBl I 2009 Nr. 23)
Ordinance on the Amendment of the Energy Saving Ordinance
(EnEV 2009) 12
19 2013 Federal Law Gazette (Germany) 2013 Second Ordinance on the Amendment of the Energy Saving Ordinance
Part I No. 67 (BGBl I 2013 Nr. 67) (EnEV 2014)
20 2013 licht.de Guide for DIN EN 12464-1 13
21 2014 ZVEI “Photobiological Safety of Lighting Products – Blue Light Hazard”
14
22 2016 ZVEI Guide to Reliable Planning with LED Lighting
23 2016 licht.de licht.wissen 01 – Lighting with Artificial Light
24 1988 LiTG Publication No. 3.5 Projektierung von Beleuchtungsanlagen nach dem Wirkungsgradverfahren
15
16
17
Intro
duction
3
Conductor crosssections in metric and US system Temperature
8m
Conductor Equivalent crosssection 160 320
5 crosssection
15 m
3m
305
150
in mm2 in mm2 AWG / in kcmil 290
6
7m
140
275
13 m
130
0.653 19 AWG 260
0.75
7 0.832
1.040
18
17
120
245
6m
1.310 16
1.50 110 230
8 1.650 15
11 m
2.080 14 100 212
2.50 2.620 13 200
2m
5m
9 3.310 12 90
4.00 185
4.170 11
9m
80
5.260 10 170
10
6.00
6.630 9 70 155
4m
8.370 8
10.00 10.550 7 60 140
11
7m
13.300 6
125
16.00 16.770 5 50
21.150 4 110
3m
12 25.00 40
26.670 3
95
33.630 2
35.00
5m
1m
30
42.410 1 80
14
3m
107.200 4/0
120.00 0 32
126.680 250 in kcmil
150.00 152.000 300 20
1m
185.00 –10
15 240.00
202.680
253.350 500
400
5
1m
–20
M 1 : 100
300.00 600
M 1 : 20
M 1 : 50
304.000 –10
354.710 700
16 400.00
500.00
405.350
506.710
800
1000
–30 –25
17
Intro
duction
2
Volume
3
Linear measure
1 mm
1 cm
39.37 mil
0.394 in
1 cm3
1 dm3
0.061 in3 = 0.034 fl. oz
61.024 in3 =
4
1m 3.281 ft = 39.370 in =1l 0.035 ft3 = 1.057 quart =
2.114 pint = 0.264 gallon
5
= 1.094 yd
15 m
9
9m
11
7m
13
1 in2 6.452 cm2 = 645.16 mm2 1 gallon/min 0.227 m3/h = 227 l/h
1 ft2 0.093 m2 = 929 cm2 1 ft3/s 101.941 m3/h
1 yd2 0.836 m2 1 ft3/min 1.699 m3/h
14
3m
1 acre 4,046.9 m2
1 mile2 2.59 km2
15
1m
Intro
duction
2
SI unit Non-metric unit SI unit Non-metric unit SI unit
1N 0.225 lbf = 0.102 kgf
1 bar 29.53 in Hg = 1 kWh 1.
1 kN 0.100 tonf = 105 Pa 14.504 psi = 1J =
3
= 102 kPa 2,088.54 lbf/ft2 = 3.
Non-metric unit SI unit
14.504 lbf/in2 = 0.
1 lbf 4.448 N 0.932 tonf/ft2 1 kgf m 9.
6.457 × 10–3 tonf/in2 (=
1 kgf 9.807 N
4 1 tonf 9.807 kN
(= 1.02 kgf/cm2)
3.
7.
Non-metric unit SI unit
11 ft2 m2
1 lbf 0.04214 kg 1 oz 28.35 g 1 hp 0.
1 lb 0.454 kg = 453.6 g 76
1 sh ton 0.907 t = 907.2 kg 1 ft lbf/s (=
12
1 kcal/h 1.
Velocity
1 Btu/h 1.
SI unit Non-metric unit 0.
Specific steam consumption
13 1 m/s
1 km/h
3.281 ft/s = 2.237 mile/h
0.911 ft/s = 0.621 mile/h SI unit Non-metric unit
15
16
17
Intro
duction
Temperature
1
Energy, work, heat content
2
ric unit SI unit Non-metric unit SI unit Non-metric unit
3
/ft2 = K °F 9
– · T – 459,67 = ∂F
3.725 × 10–7 hp h = 5
n2 = 0.738 ft lbf =
t2 1 kgf m 9.478 × 10–4 Btu Non-metric unit SI unit
3 tonf/in2
(= 2.388 × 10–4 kcal
4
m2) °F °C 5 (∂ – 32) = ∂
–
3.653 × 10–6 hp h = 9 F C
7.233 ft lbf 5
SI unit °F K – (∂F + 459.67) = T
9
5
Non-metric unit SI unit Note:
Quantity Symbol Unit
1 hp h 0.746 kWh = 2.684 × 106 J
Temperature
4 bar = ∂F °F
4 1 ft lbf = 2.737 × 105 kgf m in degrees Fahrenheit
kgf/cm2
0.070 kgf/cm2 1 Btu 0.138 kgf m
1.055 kJ = 1,055.06 J
Temperature
in degrees Celsius
∂C °C 6
1.093 kgf/cm2 (= 0.252 kcal) Thermodynamic
T K
= temperature in Kelvin
/cm2
7
Examples of decimal multiples
Electrical power
and fractions of metric units
9
ric unit 101.972 kgf m/s 1 m2 = 10,000 cm2;
(= 1.36 PS) 1 cm2 = 100 mm2
1W 0.738 ft lbf/s = 0.86 kcal/h = 1 m3 = 1,000,000 cm3;
5.27 oz 3.412 Btu 1 cm3 = 1,000 mm3
= 2,205 lb (= 0.102 kgf m/s)
1 t = 1,000 kg; 1 kg = 1,000 g 10
SI unit Non-metric unit SI unit 1 kW = 1,000 W
53.6 g
1 hp 0.746 kW = 745.70 W =
76.040 kgf m/s
11
7.2 kg 1 ft lbf/s (= 1.014 PS) Btu = British thermal unit
Btu/h = British thermal unit/hour
12
1 kcal/h 1.356 W (= 0.138 kgf in/s)
kgf = kilogram force
1 Btu/h 1.163 W
lbf = pound force
0.293 W
on tonf = ton force
ric unit
13
ph
SI unit 14
Wh
15
16
17
10 Imprint
Totally Integrated Power – Consultant Support
Planning of Electric Power Distribution
11 Technical Principles
Published by
12 Siemens AG
Energy Management
Medium Voltage & Systems
13 Editor
Siemens AG
14 Dr. Siegbert Hopf
E-Mail: siegbert.hopf@siemens.com
15 Publishing House
Publicis Pixelpark
Nägelsbachstr. 33
16 D-91052 Erlangen
Image Rights
17
page 5: Siemens Historical Institute
page 324-326: Osram AG
All other images and graphics © Siemens AG
E-Mail: consultant-support.tip@siemens.com
© 2018 Siemens AG
Berlin and Munich