Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
condition and its application for fault location - Part 1: the revised model
Li, Mingzhen; Zhou, Chengke; Wenjun, Zhou
Published in:
IEEE Transactions on Power Delivery
DOI:
10.1109/TPWRD.2019.2918159
Publication date:
2019
Document Version
Peer reviewed version
General rights
Copyright and moral rights for the publications made accessible in the public portal are retained by the authors and/or other copyright owners
and it is a condition of accessing publications that users recognise and abide by the legal requirements associated with these rights.
the relative position between cables. However, short-circuit outer radius. Starting from the centre of the cable, the cable
faults can cause changes in the equivalent circuit of the cable structure is composed of the core conductor, conductor shield,
metal sheath and in the cable impedance per unit length. main insulation, insulation shield, metal sheath, and the jacket.
As shown in Fig.1, the two ends of the metal sheath of a major
dV
Z I (1) section are directly grounded. The equivalent circuit for sheath
dx
dI current calculation is shown in Fig. 3. The formula for
Y V (2) determining sheath current is given in (3), where Im1 is the
dx
sheath current of the circuit made up of elements A1-B2-C3;
Part 1 of the paper presents the revised equivalent circuit of Ua1 is the induced electromotive force (emf) of the sheath
the cable metal sheath under fault conditions. It explains the section A1; Ub2 is the induced emf of the sheath section B2;
changes in the cable impedance per unit length, and proposes a Uc3 is the induced emf of the sheath section C3; Zma1 is the
revised phasor domain mathematical model for calculating equivalent impedance of sheath A1; Zmb2 is the equivalent
cable sheath currents of a cross-bonded cable system under impedance of sheath B1, and Zmc3 is the equivalent impedance
fault conditions. Thereafter, it shows the variation of sheath of sheath C3. Rg1 is the ground resistance at G1 and Rg2 is the
currents with respect to the change in assumed fault location. ground resistance at G2. It is to be noted that Ua1, Ub2, Uc3
Part 2 of the paper proposes a fault location approach via contain the induced emfs from other adjacent cable phases.
sheath current monitoring. The approach includes two steps:
Core
first, the exact cable section where a fault occurs can be
Conductor
determined from changes in current values, as the sheath r2 r3 r4
currents would flow in opposite direction at the two ends of r1
Metal Sheath
the fault section, whilst they would flow in the same direction Semi-conducting
Jacket
in a healthy section; second, the exact fault position in the Shield
fault section can be determined from the phase difference of Main Insulation
the power frequency sheath currents at the two ends of the Fig. 2. The cross-section of a typical HV cable
fault section. Zma1 Ua1
IS
U a U A1S III. THE IMPEDANCE OF THE METAL SHEATH UNDER FAULT
(4)
Z A1S R f Rg1 AND NON-FAULT CONDITIONS
U a U A1R U B 2 U C 3
IR (5) A. The Impedance of the Metal Sheath under Non-Fault
Z A1R Z B 2 ZC 3 R f Rg 2
Condition
If = IS+IR
The longitudinal section of a typical HV cable is shown in
Ua Rf
Core Fig.5, where Im represents the sheath current, and Ic represents
Conductor
UA1R the core current. The magnetic induction of the metal sheath
Metal Sheath
comes from both Im and Ic, represented as Bi2(Im) and Bi2(Ic).
A1
ZB2 UB2 The magnetic induction can be calculated by Ampere’s
UA1S
IS Circuital Law, i.e., the integral of the magnetic induction B
IR
ZC3 UC3 around a closed path C equals the magnetic permeability
Rg1 times the current crossing the area bounded by C. When a
Rg2
IR circle of radius r (r2< r < r3) is chosen to be the closed path,
G1 J1 J2 G2 the current enclosing the circle area is (r2-r22)/(r32-r22)Im. The
Fig. 4. The schematic diagram of the sheath currents when a short circuit fault equation for determining Bi2(Im) is represented as (10).
occurs in section A1
f
· ×
The analysis which follows will present the differences · ×
Core Conductor
in the impedance of the metal sheath between fault conditions
· ×
· × Conductor Shield
and non-fault conditions. The fault condition here implies that ·
·
×
× Main Insulation
there is short-circuit fault in the cable section, while the non- · ×
Insulation Shield
Im · ×
and expression, (4) and (5) can be represented as (6) and (7),
Fig. 5. The longitudinal section of a typical HV cable
and the sheath current Im2 of the loop B1-C2-A3, the sheath
current Im3 of the loop C1-A2-B3 can be represented by (8)
Bi 2 I m
0 r 2 r22 I m
and (9), where E(IS) is the total induced emf in the fault loop (10)
IS; E(IR) is the total induced emf in the fault loop IR; E(Im2) is
2 r32 r22 r
the total induced emf in sheath loop B1-C2-A3; E(Im3) is the
The magnetic flux of the metal sheath i2(Im) is the integral
total induced emf in sheath loop C1-A2-B3; Rs0 is the
of Bi2, which can be expressed as (11).
resistance of the metal sheath per unit length; Rc0 is the
resistance of the conductor per unit length; L1 is the length of r3
0 r 2 r22 I 0 I m 1 r2 r3
sheath loop A1-B2-C3, L2 is the length of sheath loop B1-C2- r
i 2 I m =
2 2 r 2
r22 r m dr 2 2 2 ln
2 2 r3 r2 r2
(11)
A3, and L3 is the length of sheath loop C1-A2-B3. 3
2 r2
r 3r2
2
r24 r3 Ee1 I R j 0 f ln IR (20)
Ei 2 I m j 0 f 3 ln Im (14) r1
2
4 r3 r2
2
r32 r22
2
r2
X i 2 I R 0 f ln
r2
r1
(21)
2 2 4
r 3r2 r2 r3
X i 2 I m 0 f 3 ln (15)
2
4 r3 r2
2
r32 r22
2
r2
Under normal, or non-fault conditions, the induced emf of
the metal sheath per unit length is shown in (14), and the per
Similarly, the induced emf Ei2(Ic) and the mutual impedance unit length self-impedance is shown in (15). Under fault
Xi2(Ic) can be represented by (16) and (17) respectively. condition, the induced emf of the metal sheath per unit length
r3 is given in (20), and the self-impedance of the metal sheath
Ei 2 I c j 0 f ln Ic (16)
r2 per unit length is shown in (21). Comparing (21) with (15), it
r3 can be seen that the per unit length self-impedance of the
X i 2 I c 0 f ln (17)
r2 metal sheath is related to the structure and material of the
cable. During a fault, there are changes in the equation of the
B. The Impedance of the Metal Sheath under Fault Condition self-impedance, and in the induced emf.
The longitudinal section of a typical HV cable under fault Changes to the circuit parameters will become even more
condition is shown in Fig.6. The fault current If (core current) significant when considering the mutual impedance among the
is divided into two parts at the fault position, one part (IS) three phase cables. Fig. 7 presents the equivalent circuit when
flows from the fault position to G1, and the other part (IR) a short-circuit fault occurs in section B2, where Ub is the
flows from the fault position to G2. IS and IR are sheath equivalent voltage source of phase B; UB2S is the equivalent
currents flowing in opposite directions. induced emf on sheath section B2 (between the fault position
f and J1); UB2R is the equivalent induced emf on sheath section
B2 (between the fault position and J2). The fault current If
Core Conductor starts from the power source Ub, flows along the core
Conductor Shield conductor of phase B cable (section B1 and part of section B2)
IR to the fault position, it divides into two parts and flows along
Main Insulation
the metal sheath to the two directly-grounded points. Current
Insulation Shield
Fault IS flows along the core conductor of B1 and the metal sheath
· ×
×
Metal Sheath of A1. The positional relationship between the currents IS and
·
· ×
Jacket IR is shown in Fig. 8, where Im2 is the sheath current of phase
IS · ×
Ia If
r34 r 3r 2 r22
Ei 2 I S j 0 f ln 3 3 IS (18)
2
r3 r2 2 2
r2 4 r32 r22
d
r34 r 3r 2 r22
X i 2 I S 0 f ln 3 3 (19) (a) (b)
r32 r22
2
r2 4 r32 r22
Fig. 8 The mutual impedance between phases under fault condition & the
equivalent circuit
Likewise, the mutual impedance between IS and IR can be
calculated by (20) and (21). According to the positional relationship between the
currents IS and IR, the electromagnetic field connection
between IS and IR can be represented as the connection
5
between an infinitely long straight current-carrying line (IR) As Fig. 4 and Fig. 9 show, the short circuit fault affects the
and a current-carrying coil (IS), as shown in Fig. 8. The core and the sheath directly, combining the original core loop
magnetic field generated by IR links with the magnetic field with the sheath loop. However, the induced emf can still be
generated by IS in the area of the current-carrying coil, i.e., the calculated by Ampere’s Circuit Law and Faraday's law of
area between cable section A1 and cable section B1. The induction. When the parameters related to the cable structure
magnetic induction of this area can be represented as B1e(IR). are available, the changes in magnetic flux can be calculated
Similarly, the induced emf E1e(IR) and the self-impedance layer by layer. To calculate the magnetic flux, a closed path is
X1e(IR) can be represented as in (22) ~ (23) respectively. needed to integrate the magnetic induction intensity. This
paper chose the concentric circle of the cable cross section as
d r3
E1e I R j 0 f ln IR (22) the closed path, of which radius is assumed to be r.
r1
1) 0< r < r1
d r3
X1e I R 0 f ln (23) By assuming the radius of the closed path to be greater than
r1
0 and less than r1, the magnetic flux in the core conductor is
In conclusion, the equivalent circuits and the cable taken into consideration. The core conductor of a HV cable
impedances per unit length are different between the non-fault normally contains multiple stranded wires, which can limit the
and fault conditions. The values depend on the position of the skin effect. Therefore, the core current can be assumed as
fault section, the cable configuration, the cable materials and surface current. The current inside the closed path is (r2/r12IS).
the relative position between cables of different phases. A According to Ampere’s Circuit Law, the magnetic induction
revised calculation model is needed to study the cable sheath Bi1(IS) at r is presented as (24).
currents under short-circuit fault conditions. 0 r
Bi1 I S IS (24)
2 r12
IV. THE INDUCED EMF IN A CROSS-BONDED HV CABLE
SYSTEM UNDER FAULT CONDITION The magnetic flux i1(IS) of this area can be calculated
This section presents the calculation of the emfs induced by from (24), and be represented as (25).
fault current IS in situations which were described in sections r1 0 r
A ~ C. The calculations of the sheath currents in other loops i1 I S =0 2 r1
I dr 0 I S
2 S
4
(25)
can be carried out in exactly the same way.
Note that the flux linkage i1(IS) linking with the current
A. The Electromotive Forces Induced from Fault Current IS inside the closed path can be represented as (26).
Assuming a short-current fault occurs in cable section A1,
r1 0 r 3
flat laid three phase cables in minor section 1 can be i1 I S = 0 I S dr 0 I S (26)
2 r14 8
represented as in Fig. 9. Ib represents the core current of phase
B; Ic represents the core current of phase C; Im2 represents the According to Faraday's law of induction, the induced emf
sheath current of the B1-C2-A3 loop; Im3 represents the sheath of the core conductor per unit length is given as (27), the
current of the C1-A2-B3 loop; IS represents the fault current phasor form of ei1(IS) can be written as (28).
flowing along the core conductor of phase A to the fault
d i1
position, and then flowing back through the sheath to the ei1 I S (27)
dt
grounding position at G1. j 0 f
Ei1 I S IS (28)
4
f f f
IS IS Im2 Ib Im3 Ic 2) r1< r < r2
r4 r3
r2
When the radius of the closed path is assumed to be greater
r1
than r1 and less than r2, the magnetic flux in the main
Core Conductor
Main Insulation B C insulation is taken into consideration. In this case, the current
Metal Sheath Semi-conducting inside the closed path is IS, which fully links with the magnetic
Jacket A Shield d
flux. Derived from Ampere’s Circuital Law, the induced emf
(a) The schematic diagram of fault current flows in minor section 1 (Between of the main insulation per unit length is represented as (29).
G1 and the Fault Position)
A1 Rf A1 r2
Ee1 I S j 0 f ln IS (29)
Metal sheath
r1
Core conductor
Ua UA1S 3) r2< r < r3
IS
When the radius of the closed path is assumed to be greater
than r2 and less than r3, the magnetic flux in the metal sheath
G1 is taken into consideration. The induced emf of the metal
(b) The equivalent circuit diagram of the fault loop in minor section A1 sheath per unit length is provided in (18). Besides the induced
(Between G1 and the Fault Position) emfs from IS itself, there are induced emfs from currents in
Fig. 9. The schematic diagram of fault currents flowing in minor section 1 &
its equivalent circuit diagram other phases.
6
B. The Electromotive Force Induced from Fault Current I R j Idx e jk0 R1 e jk0 R2 u 0 z h
The interaction between IS and IR has been analysed in
a
4 k02 R1
R2
2 0 0 1
e J 0 ru du
(32)
section III.B. The magnetic flux of IR linked with the magnetic j Idx u
0
0 h 1 z
e e J 0 ru du (33)
flux of IS in the area of the main insulation. The induced 4 k02 0 1
electromotive force can be found in (20).
R2 x 2 y 2 h z
2
C. The Induced Electromotive Forces due to Currents of j Idx e jk0 R1 e jk0 R2 u
0 z h
Phase B and Phase C Cables Ea
4 R1
R2
2 0 0 1
e J 0 ru du (34)
When current Ib flows in the core conductor of phase B j Idx u
0
0 h 1 z
cable, the magnetic flux linking with IS cannot be represented Ee e J 0 ru du (35)
4 0 1
directly by Ampere’s Circuit Law as no fully linked loop
exists. However, the theory of electric dipoles [24] and The cables are assumed to be laid in earth when the
Sommerfeld Integral [25] can be used for the calculation. The induced emfs from other phases are calculated. The induced
current element can be treated as an electric dipole, as shown emf EAB due to current Ib can be obtained using (36), and the
in Fig. 10, and the electric dipole is above the ground with a induced emf between phase A and phase C cables EAC can be
height of h, the distance between the electric dipole and the calculated using the same method, as shown in (37). Hence,
observation point P is R1, the distance between the observation the total induced emf in the fault loop IS can be represented as
point P and the mirror of the electric dipole is R2. (38), where Lx is the distance between G1 and the fault
z
position.
P(x,y,z)
j Ib dx u
0
R1 0 hAB 1 z AB
E AB e J 0 ru du (36)
4 0 1
Electric dipole
j I c dx u
0
0 hAC 1 z AC
E AC e J 0 ru du (37)
h
z 4 0 1
R2
E I S U A1S
(38)
O
y Ei1 I S Ee1 I S Ei 2 I S Ee1 I R E AB E AC Lx
r
x h The total induced emf E(IR) in the fault loop IR , the total
induced emf E(Im2) in sheath loop B1-C2-A3, and the total
Fig. 10. The configuration of a horizontal electric dipole with the observation induced emf E(Im3) in sheath loop C1-A2-B3 can be calculated
point P
by the very same method.
In an infinite space of non-conducting medium, the
component of the Hertz electric vector generated at the V. A CASE STUDY OF THE PROPOSED MODEL
observation point P(x, y, z) by the electric dipole in the
orientation shown is represented by (30). A simple example power system is shown in Fig. 11, it
contains a power source, a transformer, a major section of
j Idx e jkR1 cross-bonded cables and a three-phase balanced load. The
(30)
4 k 2 R1 cables are installed in a flat horizontal formation (the distance
R1 x 2 y 2 h z
2 between the neighbouring cables d is 0.3 m), directly buried
into soil at a depth of 1 m. Each minor section of the cable
e jkR1 u u2 k 2 h z
R1 0
=
2
u k 2
e J 0 ru du (31) circuit is 500 m long, hence the total length of the major
section is 1500 m. The ground resistance in each of the sheath
k j j j loops is taken as 0.1 Ω. The resistivity of the soil is 100 ·m.
r x2 y 2 The cross section of the cable is 800 mm2. The structural
parameters are shown in Table I.
Equation (31) is the Sommerfeld Integral, where k, J0(ru) Source Transformer Cable Load
A
and r represents the medium propagation constant, the 0-order A1 A2 A3
Bessel function of the first kind, the spatial frequency, and the B B1 B2 B3
200
currents IS and IR can be calculated for any given value of the
independent variable Lx using the calculation model presented 190 MoP
in Section V. The results are presented in Fig. 12 and Fig. 13. Pollaczek
5 180 CIGRE
10
7 WCM
170
6
160
IS (A)
3
0 200 400 600
The phase difference
260
Fault Position (m)
Fig. 12. The relationship between fault current IS and the fault position 240
4 MoP
10
3.62 Pollaczek
220
CIGRE
200 WCM
3.60
IR (A)
180
0 100 200 300 400 500
3.58 Fault Position (m)
(c) The phase difference between fault current IS and fault current IR when the
fault occurs in cable section C3
3.56
0 200 400 600
Fig. 14. The result comparison of the 4 calculation methods (MoP is the
method of this paper; Pollaczek is Pollaczek’s method; CIGRE is the method
Fault Position (m) recommended in a CIGRE technical brochure; WCM is the method without
Fig. 13. The relationship between fault current IR and the fault position considering the mutual impedance under fault conditions)
Fault currents IS and IR change monotonically with fault As shown in Fig. 14, the phase difference between the
position, as shown in Fig. 12 and Fig. 13. It should, therefore, fault current IS and fault current IR obtained using the three
methods are all different. The results of the Pollaczek’s
8
method are the closest to the results of the proposed method in location. The maximum absolute error of each method in each
this paper. The results of the CIGRE method are the second cable section is presented in Table II.
closest. The results for the method which does not consider the
mutual impedance under fault conditions differs significantly
from the other methods. This indicates that the mutual TABLE II
The maximum absolute error* of each method in each cable section
impedance under fault conditions plays an important role in
Method
the model and should not be ignored. Furthermore, the degree Section
Pollaczek CIGRE WCM
of difference in the results is related to the minor section in A1 316.4 889.7 4299.0
which the fault is located. If the phase difference between IS A2 680.3 1110.0 1179.4
and IR is taken as the criterion for fault location, the errors for A3 269.9 3852.6 5398.9
B1 340.7 899.2 4503.2
the fault location of the 4 methods are shown in Fig. 15.
B2 696.2 1211.0 1220.3
B3 285.4 4097.0 5550.7
0 C1 314.8 885.7 4246.1
C2 676.5 1022.6 1154.0
C3 263.6 3965.1 5356.0
-1000
*Note: The unit of the error is m.
Location Error/m
MoP
As shown in Table II, the location error varies with the
-2000 Pollaczek
CIGRE
minor section in which the fault is located. As discussed in
WCM
section IV, the calculation of the mutual impedance under
-3000
fault conditions is dependent on the minor section in which the
fault is located. Except for the method proposed by the paper,
-4000 in which the error is 0 m, the fault location errors of the other
3 methods are too large to be accepted in practical situations.
-5000 As noted earlier, one of the assumptions made in section
0 100 200 300 400 500
Fault Position/m
V is that the fault resistance Rf, the resistance of the
(a) The location errors of the 4 methods when the fault is in cable section A1 breakdown channel, is set to 0 as the value for XLPE is
0 said to be very small. However, there are practical cases [30]
that indicate that the current sensors may be triggered before
the penetrating breakdown event occurs, in which case the
-1000
fault resistance Rf will not be close to 0 There are two
Location Error/m
-2000 MoP
I S2 1 k 2 (39)
Pollaczek 250
-3000
CIGRE
The phase difference (degree)
WCM
240 A1
-4000
230 B2
-5000 C3
220
-6000 210
0 100 200 300 400 500
Fault Position/m 200
(c) The location errors of the 4 methods when the fault is in cable section C3
Fig. 15. The comparison of the location errors for the 4 calculation methods 190
B2 is the fault occurring in minor section B2; C3 is the fault occurring in [6] C. Zhou, Y. Yang, M. Li, W. Zhou, “An integrated cable condition
minor section C3) diagnosis and fault localization system via sheath current monitoring,”
in 2016 International Conference on Condition Monitoring and
Diagnosis, Xi’an, China, 2016, pp. 1-8.
Fig. 16 indicates that the phase difference between the
[7] Hanif Livani, Cansin Yaman Everenosoglu, “A single-ended fault
fault currents IS and IR decreases with the increase of the fault location method for segmented HVDC transmission line,” Electric
resistance. As a result, the larger the fault resistance becomes, Power Systems Research, vol. 107, pp. 190-198, Feb. 2014.
the more difficult it is to distinguish the phase difference. The [8] M. Eissa, “Ground distance relay compensation based on fault resistance
calculation” IEEE Trans. Power Del., vol. 29, no. 4, pp. 1830-1835, Oct.
results also indicate that the accuracy of the current sensors
2006.
should match the value of the fault resistance to ensure ability [9] Z.Xu, S.Jiang, Q.Yang, T.Bi, “Ground distance relaying algorithm for
to distinguish phase difference values effectively. high resistance fault,” IET Gener. Transm. Distrib., vol. 4, no.1, pp. 27-
35, Jan. 2010.
[10] J.Suonan, J. Qi, “An accurate fault location algorithm for transmission
VII. CONCLUSIONS AND DISCUSSIONS lines based on R-L model parameter identification,” Electric Power
This paper proposes a revised numerical model of HV Systems Research, vol. 76, no. 1-3, pp. 17-24, Sep. 2005.
[11] D. Novosel, D.G. Hart, E. Udren, J. Garitty, “Unsynchronized two-
cable sheath current under short-circuit fault condition that is terminal fault location estimation,” IEEE Trans. Power Del., vol. 11, no.
applicable to HV cross-bonded cable systems. The differences 1, pp. 130-138, Jan. 1996.
between fault condition and non-fault condition lie in the [12] A.A. Girgis, C.M. Fallon, “Fault location technique for radial and loop
transmission systems using digital fault recorded data,” IEEE Trans.
equivalent circuit and the cable impedance per unit length.
Power Del., vol. 7, no. 4, pp. 1936-1945, Oct. 1992.
Essentially, the differences result from changes due to the [13] T. Ji ,T. Sun, B. Xu, P. Chen, Y. Xue, “Study on fault location of
presence of a short-circuit fault, i.e. to the electrical distribution mixed feeders based on double terminal method of traveling
connections and coupling between the cable conductors and waves,” Proceedings of the CSEE, vol. 26, no. 12, pp. 89-94, Jun. 2006.
[14] M. Bawart, M. Marzinotto, G. Mazzanti, “Diagnosis and location of
the cable sheaths. The paper demonstrated that it is important faults in submarine power cables”, IEEE Elect. Insul. Mag., Vol. 32, No.
to not ignore the mutual impedance under fault conditions 4, pp. 24-37, Jul./Aug. 2016
when the accuracy of the simulated fault current matters in an [15] H. M.Manesh, G. Lugrin, R. Razzaghi, C. Romero, M. Paolone, F.
Rachidi, “A new method to locate faults in power networks based on
application. electromagnetic time reversal,” in IEEE SPAWC, Cesme, Turkey, 2012,
The method proposed in this paper has been compared with pp. 469-474.
the Pollaczek’s method used in PSCAD, an approximate [16] Reza Razzaghi, Gaspard Lugrin, Hossein Manesh, Carlos Romero,
Mario Paolone, Farhad Rachidi, “An efficient method based on the
calculation method recommended in a CIGRE technical electromagnetic time reversal to locate faults in power networks,” IEEE
brochure and the calculation method without considering the Trans. Power Del., vol. 28, no. 3, pp. 1663-1673, Jul. 2013.
mutual impedance under fault conditions. Results show that [17] G. Lugrin, R. Razzaghi, F. Rachidi and M. Paolone, "Electromagnetic
time reversal applied to fault detection: The issue of losses," 2015 IEEE
the method developed is very accurate and that fault location International Symposium on EMC, Dresden, 2015, pp. 209-212.
errors of the other 3 methods are too large to be acceptable. [18] R. Razzaghi, G. Lugrin, F. Rachidi, M. Paolone, "Assessment of the
The results also indicate that the phase difference is very Influence of Losses on the Performance of the Electromagnetic Time
sensitive to the fault distance: a small error in the phase Reversal Fault Location Method," IEEE Trans. Power Del. , vol. 32, no.
5, pp. 2303-2312, Oct. 2017.
difference could cause a large error in the fault location. [19] M. Marzinotto, G. Mazzanti, “The Feasibility of Cable Sheath Fault
The phase difference between the fault currents IS and IR Detection by Monitoring Sheath-to-Ground Currents at the Ends of
decreases with increasing fault resistance. A large fault Cross-Bonding Sections,” IEEE Trans. Ind. Appl., vol. 51, no. 6, pp.
5376-5384, Nov. 2015.
resistance, if not considered correctly, could affect the ability [20] Schelkunoff, S. A. “The Electromagnetic Theory of Coaxial
to distinguish the phase difference. To overcome this Transmission Lines and Cylindrical Shields,” Bell Labs Technical
challenge, it is suggested that the current sensors be set to Journal. vol. 13, no. 4, pp. 532-579, Oct. 1934.
trigger when a penetrating breakdown forms, or the accuracy [21] L. M. Wedepohl, D. J. Wilcox, “Transient analysis of underground
power-transmission systems. System-model and wave-propagation
of the current sensors should be matched to the fault characteristics,” Proceedings of the Institution of Electrical Engineers,
resistance. The details of the location method, utilizing the vol. 120, no. 2, pp. 253-260, Feb. 1973.
modelling results, will be presented in part 2 of the paper. [22] L. M. Wedepohl, H.V. Nguyen, G.D. Irwin, “Frequency-Dependent
Transformation Matrices for Untransposed Transmission Lines using
Newton-Raphson Method,” IEEE Trans. Power Syst., vol. 11, no. 3, pp.
VIII. REFERENCES 1538-1546, Aug. 1996.
[1] B. Sheng, W. Zhou, J. Yu, S. Meng, C. Zhou, D. M. Hepburn, “On-line [23] IEEE Guide for Bonding Shields and Sheaths of Single-Conductor
PD detection and localization in cross-bonded HV cable system,” IEEE Power Cables Rated 5 kV through 500 kV, IEEE Standard, 2014.
Trans. Dielectr. Electr. Insul., vol. 21, no. 5, pp. 2217-2224, Oct. 2014. [24] R. Vaughan, J. Bach Anderson, “Channels, propagation and antennas for
[2] X. Zhang, “Estimation of the Lifetime of the Electrical Components in mobile communications”. IET Electromagnetic Waves Series, London, 0
Distribution Networks,” IEEE Trans. Power Del., vol. 22, no.1, pp. 515- 85296 084 0, 2006.
522, Jan. 2007. [25] Sommerfeld A., “Partial differential equations in physics,” New York:
[3] Z. Tang, C. Zhou, W. Jiang, W. Zhou, X. Jing, J. Yu, et al. “Analysis of Academic Press Inc., 1949.
Significant Factors on Cable Failure Using the Cox Proportional Hazard [26] A.S. Vaughan, I.L. Hosier, S.J. Dodd, S.J. Sutton, “On the structure and
Model,” IEEE Trans. Power Del., vol. 29, no. 2, pp. 951-957, Apr. 2014. chemistry of electrical trees in polyethylene”, J. Phys. D: Appl. Phys.,
[4] X. Dong, Y. Yuan, Z. Gao, C. Zhou, B. Sheng, H. Zhao, “Analysis of vol. 39, no. 3, pp.962-978, Jun. 2006.
cable failure modes and cable joint failure detection via sheath
[27] F. Pollaczek, “Sur le champ produit par un conducteur simple infiniment
circulating current”, in EIC, Philadelphia, 2014, pp. 294-298.
long parcouru par un courant alternatif”, Revue Gén, Elec., vol. 29, pp.
[5] A. R. Almeida, O. M. Almeida, B. F. S. Junior, L.H.S.C. Barreto, A. K.
851-867, 1931.
Barros, “ICA feature extraction for the location and classification of
faults in high-voltage transmission lines,” Electric Power Systems [28] EMTDC User's Guide v4.6, Available: https://hvdc.ca/knowledge-
Research, vol. 148, pp. 254-263, Jul. 2017. base/read,article/163/emtdc-user-s-guide-v4-6/v:.
10
IX. BIOGRAPHIES