DS1012
TECHNICAL Page 1 of 9
SPECIFICATION REV DATE: 07/18
11
CATEGORY
CABLE
SUBJECT
TABLE OF CONTENTS
1 PURPOSE ............................................................................................ 2
2 SCOPE ................................................................................................. 2
3 REFERENCES ..................................................................................... 2
4 DEFINITIONS ....................................................................................... 3
5 SPECIFICATION .................................................................................. 3
5.1 GENERAL ............................................................................................ 3
5.2 SMUD’S INTENDED USE OF CABLE ................................................. 4
5.3 CONDUCTOR ...................................................................................... 4
5.4 CONDUCTOR SHIELDING .................................................................. 5
5.5 INSULATION ........................................................................................ 5
5.6 NON-METALLIC INSULATION SHIELDING ....................................... 5
5.7 METALLIC SHIELDING / CONCENTRIC NEUTRAL .......................... 6
5.8 JACKET ............................................................................................... 6
5.9 LONGITUDINAL WATER BLOCKING ................................................ 6
5.10 CABLE AND FOOTAGE IDENTIFICATION…………………………...6
6 TECHNCIAL DOCUMENTATION SUBMITTED .................................. 7
7 TESTING AND INSPECTION............................................................... 8
8 SHIPPING AND PACKAGING ............................................................. 9
9 DRAWINGS AND MANUALS .............................................................. 9
REV 69KV CROSS LINK POLYETHYLENE SOLID page 2
TECH. SPEC.
11 DIELECTRIC CABLE of 9
DS1012
1 PURPOSE
This Engineering Specification is used to provide the manufacturing requirements
of a single conductor, cross-linked polyethylene insulated, concentric neutral wire
shielded, jacketed cable for use by SMUD on their 69 kV distribution systems.
2 SCOPE
This specification applies to 69 kV class, cross-linked polyethylene insulated
cable used at SMUD. All work and material to design, fabricate, test and deliver
the specified equipment along with any drawings, manuals, or other documents
required shall be provided by the successful contractor.
3.14 ASTM B609M, Standard Specification for Aluminum 1350 Round Wire,
Annealed and Intermediate Tempers, for Electrical Purposes.
3.15 NEMA, WC-26 Binational Wire and Cable Packaging Standard
3.16 ASTM B8, Standard Specification for Concentric Lay-Stranded Copper
Conductors, Hard, Medium-Hard, or Soft.
4 DEFINITIONS
Refer to ICEA S-108-720, The IEEE Dictionary of Electrical and Electronic Terms
and the references defined in section 3.
5 SPECIFICATION
5.1 GENERAL
5.1.1 The cable shall be designed, manufactured and tested in accordance
with ICEA S-108-720, as applicable except as defined otherwise in this
specification.
5.1.2 The cable shall be manufactured by the true triple head extrusion of the
conductor shield, insulation, and insulation shield.
5.1.3 After triple extrusion, the cable shall be dry-cured, utilizing the Maillefer
or Troester dry-curing process.
5.1.4 The manufacturer shall demonstrate contamination protection during all
phases of production. To minimize contamination, the insulation
compound shall be received and unloaded in a closed bulk
handling/transfer system, or when necessary, received and unloaded in
an ultra-clean box and sealed super sack handling/transfer system.
Conductor shield and insulation shield compounds shall be received and
unloaded in an ultra-clean box and sealed super sack handling/transfer
system. All manufacturing rooms and areas where materials for the
insulation system are handled from the sealed containers from the
suppliers shall be Class 6 in accordance ISO 14644-1. All other areas
handling the material shall be classified as an ISO class 7.
5.1.5 Cables shall be manufactured utilizing materials from one supplier for
the entire insulation system, unless approved otherwise by SMUD in
writing and upon provision of qualification test reports. The cable
manufacturer shall use materials in the manufacturing of cables supplied
under this specification identical to the materials used in all applicable
Qualification testing submitted per section 7.1.
5.1.6 All cables (i.e. combinations of cable, cable shield, insulation, insulation
shield, and jacket) provided under this specification must have
successfully met the qualification tests per ICEA S-108-720.
REV 69KV CROSS LINK POLYETHYLENE SOLID page 4
TECH. SPEC.
11 DIELECTRIC CABLE of 9
DS1012
S-108-720.
5.10.2 Sequential Length markings shall also be supplied in accordance with
ICEA S-108-720. The sequential length marking shall be made not less
than every two (2) feet along the length of the cable.
5.10.3 The print legend is to be only Hot Stamp Foil type Printing, or SMUD
approved equal. Surface Ink printing is not allowed.
6.5 Instructions for proper handling and installation of the cable including:
6.5.1 Minimum bending radius of each cable being supplied
6.5.2 The maximum sidewall bearing pressure of each cable being supplied
6.5.3 The maximum pulling tension when pulled by the cable jacket and by the
conductor of each cable being supplied
6.5.4 Recommended splicing and terminating methods and materials.
6.6 The short circuit capability of the conductor, and the shield at 30 cycles
and 9 cycles per ICEA P-32-382, and ICEA P-45-482.
6.7 The ampacity of a single circuit showing method of calculation with
installation assumptions and ratings per section 5.2.
6.8 The cables positive sequence impedance value.
6.9 The emergency 100-hour ampacity rating of the cable with the installation
assumptions and ratings per section 5.2.
6.10 The shipping reel information for each cable being supplied including:
6.10.1 The reel flange diameter, the outside traverse flange-to-flange width, the
drum diameter and the shaft hole dimensions.
6.10.2 The longest expected length of each cable type on the reel along with
the maximum weight of each reel with the longest length without wood
lagging.
7.3 Cable acceptance and payment for the cable may be affected by delays in
receipt of the production test data.
7.4 SMUD shall have the right to witness any or all production or production
tests. The contractor shall notify SMUD at least two (2) weeks prior to any
manufacturing and/or testing of cable supplied under this specification.