1 Wiring for light point/ fan point/ wall fan point/ exhaust fan/
light sockets etc. with 2.0 sq.mm. PVC insulated 1100 V
Grade copper conductor (FR) wires & 1.0 sq.mm. copper
earth wire in concealed/ surface using 16 SWG MS
conduits, accessories such as bends, tees, saddles, draw
boxes, mounting boxes, inner plates, cover plates, ceiling
rose etc (whereever required) and chromium plates brass
screws/ rowel plug etc. The circuit wiring starting from DB
to point control box/ switch box using 2x2.5 sq.mm PVC
insulated 1100 V grade multi- stranded copper conductor
wire & 1.5 sq.mm. PVC insulated earth wire (color code to
be used). (Flexible conduit/ elbow not allowed). The
conduit to be laid in ceiling with proper clamps/ wall/ floor
and filling the chase with cement mortar and finishing the
same in original form/ wooden partition/ above false ceiling
with proper clamps etc. all complete.
vi) One wall fan/ exhaust fan point with 6 amp 3-pin socket Nos. 2.00
controlled by one 6 amp. Modular switch. The switch
should be at switchboard level.
vii) One light 5 pin socket controlled by one 6 amp. Modular
switch.
a Dependent Nos. 10.00
b Independent Nos. 8.00
2 POWER POINTS
i) Same as serial no.1, but wiring for 6/16 Amp, 6-pin
sockets by using 2 X 4 sq.mm. PVC insulated 1100 V
grade copper conductor wire with independent 2 X 2.5
sq.mm earth wire from D.B. to first point 1 st socket and 1st
to 2nd, socket with 2.5 sq.mm. and 1.5 earth wire including
providing and fixing of 16 Amp, 6 –pin socket
with 16 Amp. Switch (Maximum two points in a circuit).
. 1
PASCHIM VIHAR `BRANCH
ii) Same as serial no.1, but wiring for A/C socket by using 2 X Nos. 8.00
6 sq.mm. PVC insulated 1100 V grade copper conductor
wire and earthing with 2.5 sq.mm. PVC insulated 1100 V
grade copper conductor wire including providing and fixing
32 amp 3 pin (phase, neutral and earth) for 1 phase socket
outlet with 1 No. 32 amp SP MCB. (Only one outlet shall
be connected to each
circuit).
3 LIGHT FITTINGS
Supplying, installation, testing and commissioning of
following light fixtures with electronic Ballasts, electronic
transformer, Tubes, lamps, all fixing materials including
connecting wires etc. all complete as per the directions of
Engineer-in-charge.
ii) 595 X 595, LED 36 W Ultraslim Fixture of make Philips/ Nos. 28.00
Wipro/ CG (Contractor to take approval before
installation ).
i) Wall mounted fans 400 mm dia. HiFlo/ Bajaj Midea/ Nos. 10.00
Usha Mist Air.
ii) Supply & fixing of 230 mm exhaust fan 'Ventilair DX W' Nos. 2.00
with self closing louvers and plastic body with all
accessories etc. complete of make Havells/ Crompton/
Orient.
b) Same as above but looped from the above 1st Point to Nos. 10.00
2nd point and 2nd point to 3rd point (Maximum 3 points
in a circuit).
6 DISTRIBUTION BOARDS
All MCBs are of 'C' Series.
. 2
PASCHIM VIHAR `BRANCH
a Supplying, fixing, on wall, interconnection, factory Nos. 2.00
fabricated for LIGHTING DB 4 way TPN with double door
(metal) for having three phase 40 Amp TPN as incomer
controlling 12 Nos. 10 Amp/ 16 Amp SP MCB.
. 3
PASCHIM VIHAR `BRANCH
9 Supplying, fabrication, fixing, interconnection, testing & Nos. 1.00
commissioning of cubical type main panel made from 2
mm thick CRCA sheet, M.S. channel for fixing on wall
complete with MCCBs, MCBs meters C.T. etc complete in
all respect, double strip aluminium insulated bus bar with
heat shrinkable PVC sleeve in suitable bus-bar chamber,
wiring, name plate, earth-bus etc & comprising of
compartments with hinged doors & rubber gasket, bus bar
chamber with bolted door and rubber gasket etc. The
panel being of dust & vermin proof construction and to
be painted with primer and smoke gray paint (minimum
two coats) to look attractive. The panel should be
comprising with the followings: (Degree of Protection IP-
54).
OUTGOING
63 Amp TPN MCB - 3
40 Amp TPN MCB - 1
40 Amp DP MCB - 2
10 EARTH STATIONS
(i) Supplying and installation of pipe-pipe technology Ashlok Nos. 2.00
Earthing system, Model T-19 with outer diameter of 50
mm, length 2000 mm embedded in the soil with masonry
inspection pit along with cover etc., complete in all respect.
Each pit installation test certificate to be submitted after
measurement of earth resistance as per the provision in
IS: 3043. (Panel earthing).(The contractor has to carry
out the earth station work from
Bank’s authorized vendor.)
12 P/f Telephone point wiring with 2 pair cable and fixing Nos. 11.00
telephone Jack.
. 4