Sei sulla pagina 1di 68

AXIS-P

AXIS-FP

Medium pressure axial fans


Axial smoke extraction fans
blaubergventilatoren.de

CONTENTS

Complete solutions for axial fans 2

Medium pressure axial fans Axis-P 4

Axial smoke extraction fans Axis-FP 28

Fan accessories selection table 56

AXIS-P | AXIS-FP 1
AXIS-P | AXIS-FP

Complete solutions for axial fans

Flexible joint Fan Flexible joint Flange Air duct


EVAF-AF Axis-P/Axis-FP EVAF-AF F-AF BlauSpiral
EVAF-AF...400/2 EVAF-AF...400/2

Protective mesh Inlet cone Silencer Carrier Antivibration mounts Backdraft damper
SZ-AF VK-AF SD/SDV O-AF SIF-AF/SIG-AF VRV-AF...400/2

Installation example of axial fans on rooftop

Air pressurisation system Smoke extraction system

Roof hood Z-AF

Backdraft damper VRV1-AF

Fire-resistant backdraft damper VRV-AF...400/2

Axial fan Axis-P

Axial smoke extraction fan Axis-FP

Roof adapter PK-AF

Mounting curb SM-AF

2 blaubergventilatoren.de
blaubergventilatoren.de

4D 2D 4D 2D

D
FAN INSTALLATION INTO AN AIR DUCT SYSTEM CHANGING DIAMETER INSTALLATION
To ensure a uniform air flow the fan should be preceded by a straight When changing from a smaller diameter to a larger one use a connector
duct section with a cross-section area equal to half of that of the fan. diffuser with the maximum opening angle of 12°.
The length of the duct section should be 3 ÷ 4 D (D is the inner diameter
of the fan). The length of the straight duct section downstream of the fan
should be 1.5 ÷ 2 D. max 120

Reduction of the recommended duct length values results in a drop of the 4D 2D


fan pressure and performance. To reduce noise and vibration use the VVGF
flexible joints.

D
4D 2D OBSTRUCTED SPACE INSTALLATION
To ensure normal operation of the fan in an obstructed space make sure
to provide for a sufficient distance between the inlet and outlet flanges
and the floor, walls, bulky equipment and obstacles.
D

H≥D H≥D
H≥D H≥D

FAN INSTALLATION WITH NO UPSTREAM DUCTING


Axial fans without upstream ducting must be equipped with the VK-AF
D
D

inlet cone to improve the air flow parameters.

D
D
max 120
4D 2D
H≥D

H≥D

H≥D

H≥D
D

H≥D H≥D

FAN INSTALLATION WITH NO DOWNSTREAM DUCTING


If the
H≥Daxial fan is a terminal device of the ventilation
H ≥system
D (i.e. there

D
D
is no downstream ducting) the unit must be equipped with a diffuser
to reduce the air flow velocity and the fan dynamic pressure. Reduction
max 120

of the air discharge velocity results in a significant reduction of shock


H≥D

H≥D
losses which are proportional to the square of velocity decrement.
D
D

The fan should not be equipped with a downstream contractor.

2D 2D
H≥D

H≥D

4D H≥D 2D H≥D
D

INSTALLATION NEAR BENDS


D
D

To install the fan directly downstream of a bend (elbow) use a curved


section with a large bending radius or an array of
max internal
12 maxguide
0
12 vanes. 0
H≥D

H≥D

max 120

H≥D H≥D

H≥D H≥D
H≥D

H≥D

D
D
H≥D

H≥D

AXIS-P | AXIS-FP 3
AXIS-P | AXIS-FP

Axis-P
Medium pressure axial fans

Use
The fans are used: Air flow:
as a part of a smoke extraction system for air up to 113 000 m³/h
pressurization to create a positive air pressure
differential in stairway enclosures, airlock
vestibules and lift shafts, to prevent spreading
of smoke in premises, protect people using
evacuation routes from fire hazards and enable
conditions for fire-extinguishing measures.
in general ventilation systems in industrial,
administrative and residential buildings.

Design Impeller
The metal casing with rolled flanges helps achieve outstanding rigidity Depending on the size and the required air capacity the fans are
and minimum clearances between the casing and the blades. There is equipped with impellers with 6 or 8 blades angled from 20° to 50° with
an inspection hatch in the casing for easy maintenance. from 2.5 up to 5° stepping to ensure precise matching of fans with the
All the casing components are powder coated for improved protection operating point.
against the environmental effects. The specially designed impeller blades ensure high efficiency of the fan
The weight of the fans may differ from the one stated in the catalogue while keeping noise well under control. The impellers are dynamically
and depends on the components used (motor, terminal box, etc.). balanced. Low weight and low moment of the impeller inertia help
reduce the fan start-up time.
The fan blades can be made of the following materials:
Motor
• PAG – fiberglass reinforced polyamide;
The fans are equipped with three-phase (400 V/50 Hz) single-speed 2-, • AL – aluminium.
AXIS-P

4- or 6-pole electric motors. Please confirm the blade material while placing your order..
Motor with energy efficiency class IE3 on request.
Mounting
The fans can be mounted on any flat surface or directly into
a ventilation duct. The units are suitable for both horizontal and vertical
configurations. In-duct installation requires flanges to attach the fan to
the ductwork.
To attach the fan to the floor, a wall or the ceiling use the O-AF carriers
(not included as standard, should be purchased separately).
The units are suitable for installation on rooftops to provide direct
supply of outdoor air to the stairway areas.

Accessories
Carrier Flange Flexible joint Hood Roof adapter Mounting curb Inlet cone

O-AF F-AF EVAF-AF Z-AF PK-AF SM-AF VK-AF

4 blaubergventilatoren.de
blaubergventilatoren.de

Designation key
Casing Motor Impeller Modification

AXIS-P 630 K - 2 D/ 5.5 - 8 /35/AL - U 1 - K


Axis-P: axial pressurisation fan

Standard size (duct diameter) [mm]

Modification:
_: standard casing;
K: shortened casing

Number of the motor poles


Motor phase:
E: single-phase;
D: three-phase

Motor power [kW]

Number of the impeller blades [items]

Blade setting angle [ °]

Blade material
PAG: fiberglass reinforced polyamide
AL: aluminium

Climatic category:
U: moderate climate (-40 ... +40 °C)
HL: cold climate (-60 ... +40 °C)
UHL: moderate and cold climate (-60 ... +40 °C)
T: tropical climate (-10 ... +50 °C)
M: maritime moderately cold climate (-40 ... +40 °C)
O: general climatic modification (except maritime climate) (-60 ... +50 °C)
OM: general maritime climatic modification (-40 ... +40 °C)
V: universal climatic modification (-60 ... +50 °C)

Placement category:
1: outdoors
2: under a shed or indoors with the same conditions as outdoors except solar radiation and precipitation

AXIS-P
3: in closed rooms without artificial climate control
4: in closed rooms with artificial climate control (ventilation, heating)
5: in rooms with high levels of humidity, without climate control
Terminal box:
_: electric connection on the terminal box on the motor
K: external terminal box on the fan casing

Accessories
Backdraft damper Silencer Protective mesh Anti-vibration mount

VRV-AF VRV1-AF SD SDV SZ-AF SIF-AF SIG-AF

AXIS-P | AXIS-FP 5
AXIS-P | AXIS-FP

Technical data
AXIS-P 400-4
Voltage Fan model with Fans model with fiberglass Blade setting Weight Lenght L Curve
Size Number [V / aluminum blades impeller reinforced polyamide blades Installed motor RPM [min⁻¹] Number of number
of poles 50 Hz] (AL) impeller (PAG) power Ny [kW] blades angle [°] [kg] [mm] on graph

Axis-P 400-4D/0.12-6/30/AL Axis-P 400-4D/0.12-6/30/PAG 0.12 1440 6 30 19.5 350 


Axis-P 400-4D/0.18-6/35/AL Axis-P 400-4D/0.18-6/35/PAG 0.18 1440 6 35 19.8 350 
400 4 3~400 Axis-P 400-4D/0.18-6/40/AL Axis-P 400-4D/0.18-6/40/PAG 0.18 1440 6 40 19.8 350 
Axis-P 400-4D/0.25-6/45/AL Axis-P 400-4D/0.25-6/45/PAG 0.25 1440 6 45 23.2 350 
Axis-P 400-4D/0.37-8/45/AL Axis-P 400-4D/0.37-8/45/PAG 0.37 1440 8 45 23.9 350 

Aerodynamic characteristics
Air flow [CFM]
1000 1500 2000 2500 3000 3500 L
120
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 400 Ø8
110 Number of poles: 4 12 holes
80
100 77
0.4
77 Pd

490
75 78
90
80
76
80
77
75 0.3
78 79
60
76

450
76 40
70 0
74
79
AXIS-P 400

75 77
50 0.2

76 78
40 72 Axis-P 400-4
74
30
77
70 75
77
0.1
73
20 L

10 dBA Ø8
69 72 74 76 77 12 holes
1 2 3 4 5
1000 2000 3000 4000 5000 6000
Air flow [m3/h]
490

0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 1.3 1.4 1.5 1.6
Air flow [m3/h]
0.4
Power [kW]

0.3
5
450

40
0.2 4 0

3 48
0.1 2 0
1
0
1000 2000 3000 4000 5000 6000
Air flow [m3/h]
Axis-P 400-4...-K

6 blaubergventilatoren.de
blaubergventilatoren.de

Technical data
AXIS-P 400-2
Voltage Fan model with Fans model with fiberglass Blade setting Weight Lenght L Curve
Size Number [V / aluminum blades impeller reinforced polyamide blades Installed motor RPM [min⁻¹] Number of number
of poles 50 Hz] (AL) impeller (PAG) power Ny [kW] blades angle [°] [kg] [mm] on graph

- Axis-P 400-2D/0.55-6/25/PAG 0.55 2880 6 25 23.4 350 


Axis-P 400-2D/0.75-6/30/AL Axis-P 400-2D/0.75-6/30/PAG 0.75 2880 6 30 26.5 350 (450*) 
Axis-P 400-2D/1.1-6/35/AL Axis-P 400-2D/1.1-6/35/PAG 1.1 2880 6 35 27.0 450 
400 2 3~400
Axis-P 400-2D/1.5-6/40/AL Axis-P 400-2D/1.5-6/40/PAG 1.5 2880 6 40 32.5 450 
Axis-P 400-2D/2.2-6/45/AL Axis-P 400-2D/2.2-6/45/PAG 2.2 2880 6 45 34.5 450 
Axis-P 400-2D/2.2-8/45/AL Axis-P 400-2D/2.2-8/45/PAG 2.2 2880 8 45 35.0 450 
* Including a motor with energy efficiency IE3

Aerodynamic characteristics
Air flow [CFM]
2000 3000 4000 5000 6000 7000 L
500 2.0
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 400 Ø8
Number of poles: 2 12 holes
450 1.8
96
90
400 1.6
92 Pd

490
89 95
91
350 90 1.4
88
92
88 91
300 1.2
95
87 92

450
89 40
250 1.0 0
90
87 95
91

AXIS-P 400
200 0.8
85 89
90 Axis-P 400-2
94
150 0.6
86 88
83
91
89
100 0.4
84 87 93
L

50 dBA 0.2 Ø8
90 93
80 82 86 87 12 holes
1 2 3 4 5 6
2000 4000 6000 8000 10000 12000
Air flow [m3/h]
490

0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2
Air flow [m3/h]
2.5
Power [kW]

2.0 6
5
450

1.5 40
0
4
1.0 3
48
2 0
0.5 1
0
2000 4000 6000 8000 10000 12000
Air flow [m3/h]
Axis-P 400-2...-K

AXIS-P | AXIS-FP 7
AXIS-P | AXIS-FP

Technical data
AXIS-P 450-4
Voltage Fan model with Fans model with fiberglass Blade setting Weight Lenght L Curve
Size Number [V / aluminum blades impeller reinforced polyamide blades Installed motor RPM [min⁻¹] Number of number
of poles 50 Hz] (AL) impeller (PAG) power Ny [kW] blades angle [°] [kg] [mm] on graph

- Axis-P 450-4D/0.12-6/25/PAG 0.12 1440 6 25 29.1 350 


Axis-P 450-4D/0.18-6/30/AL Axis-P 450-4D/0.18-6/30/PAG 0.18 1440 6 30 29.4 350 
Axis-P 450-4D/0.25-6/35/AL Axis-P 450-4D/0.25-6/35/PAG 0.25 1440 6 35 32.8 350 
450 4 3~400
Axis-P 450-4D/0.25-6/40/AL Axis-P 450-4D/0.25-6/40/PAG 0.25 1440 6 40 32.8 350 
Axis-P 450-4D/0.37-6/45/AL Axis-P 450-4D/0.37-6/45/PAG 0.37 1440 6 45 33 350 
Axis-P 450-4D/0.55-8/45/AL Axis-P 450-4D/0.55-8/45/PAG 0.55 1440 8 45 36.6 350 (450*) 
* Including a motor with energy efficiency IE3

Aerodynamic characteristics
Air flow [CFM]
1500 2000 2500 3000 3500 4000 4500
L
0.6
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


140 Standard size: 450 Ø8
Number of poles: 4 12 holes

82 0.5
120
78

540
79 80
Pd
77

100 0.4
78 82
76 76
80
79
80

500
0.3 45
0
75 77 81
AXIS-P 450

75
80
60
78
0.2 Axis-P 450-4
72 74
76
40 80
79

72 77
70 75 0.1 L
20
79
dBA Ø8
78
67 70 74 76 12 holes
1 2 3 4 5 6
2000 3000 4000 5000 6000 7000 8000
Air flow [m3/h]
540

0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2


Air flow [m3/h]
0.5
Power [kW]

0.4 6
5
500

0.3 45
0
0.2 4
3 52
0.1 2 5
1
0
2000 3000 4000 5000 6000 7000 8000
Air flow [m3/h]
Axis-P 450-4...-K

8 blaubergventilatoren.de
blaubergventilatoren.de

Technical data
AXIS-P 450-2
Voltage Fan model with Fans model with fiberglass Blade setting Weight Lenght L Curve
Size Number [V / aluminum blades impeller reinforced polyamide blades Installed motor RPM [min⁻¹] Number of number
of poles 50 Hz] (AL) impeller (PAG) power Ny [kW] blades angle [°] [kg] [mm] on graph

- Axis-P 450-2D/0.75-6/25/PAG 0.75 2880 6 25 36.1 350 (450*) 


Axis-P 450-2D/1.1-6/30/AL Axis-P 450-2D/1.1-6/30/PAG 1.1 2880 6 30 36.6 450 
Axis-P 450-2D/1.5-6/35/AL Axis-P 450-2D/1.5-6/35/PAG 1.5 2880 6 35 42.1 450 
450 2 3~400
Axis-P 450-2D/2.2-6/40/AL Axis-P 450-2D/2.2-6/40/PAG 2.2 2880 6 40 44.1 450 
Axis-P 450-2D/3-8/40/AL Axis-P 450-2D/3-8/40/PAG 3 2880 8 40 53.6 450 (550*) 
Axis-P 450-2D/4-8/45/AL Axis-P 450-2D/4-8/45/PAG 4 2880 8 45 63.7 550 
* Including a motor with energy efficiency IE3

Aerodynamic characteristics
Air flow [CFM]
3000 4000 5000 6000 7000 8000 9000 L
600 2.4
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 450 Ø8
Number of poles: 2 2.2 12 holes

97
500 2.0
98
92 93 Pd

540
1.8
90 97
400 1.6
93 98
92
90 1.4
97

500
89
300 1.2 45
92 97 0

89 91
1.0

AXIS-P 450
96
87 92
200 0.8 Axis-P 450-2
90
88 96
0.6
95
91
84 86
100 0.4 L
89
dBA
0.2 Ø8
81 84 88 90 94 96 12 holes
1 2 3 4 5 6
4000 6000 8000 10000 12000 14000 16000
Air flow [m3/h]
540

1.2 1.6 2.0 2.4 2.8 3.2 3.6 4.0 4.4


Air flow [m3/h]
4.0
Power [kW]

3.0 6
500

5 45
0
2.0
4
3 52
1.0 5
2
1
0
4000 6000 8000 10000 12000 14000 16000
Air flow [m3/h]
Axis-P 450-2...-K

AXIS-P | AXIS-FP 9
AXIS-P | AXIS-FP

Technical data
AXIS-P 500-4
Voltage Fan model with Fans model with fiberglass Blade setting Weight Lenght L Curve
Size Number [V / aluminum blades impeller reinforced polyamide blades Installed motor RPM [min⁻¹] Number of number
of poles 50 Hz] (AL) impeller (PAG) power Ny [kW] blades angle [°] [kg] [mm] on graph

- Axis-P 500-4D/0.18-6/25/PAG 0.18 1440 6 25 61.5 350 


Axis-P 500-4D/0.25-6/30/AL Axis-P 500-4D/0.25-6/30/PAG 0.25 1440 6 30 61.7 350 
Axis-P 500-4D/0.37-6/35/AL Axis-P 500-4D/0.37-6/35/PAG 0.37 1440 6 35 64.8 350 
500 4 3~400
Axis-P 500-4D/0.37-6/40/AL Axis-P 500-4D/0.37-6/40/PAG 0.37 1440 6 40 64.8 350 
Axis-P 500-4D/0.55-6/45/AL Axis-P 500-4D/0.55-6/45/PAG 0.55 1440 6 45 65.6 450 
Axis-P 500-4D/0.75-8/45/AL Axis-P 500-4D/0.75-8/45/PAG 0.75 1440 8 45 71.4 450 
* Including a motor with energy efficiency IE3

Aerodynamic characteristics
Air flow [CFM]
1500 2000 2500 3000 3500 4000 4500 5000 5500
L
0.6
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


140 Standard size: 500 Ø12
Number of poles: 4 12 holes
82
81
80 84 0.5
120
Pd

600
78

77 82 83
100 81 0.4
80

77
80

560
75 83
0.3 50
80 82 0
79
AXIS-P 500

60
75 82
73 Axis-P 500-4
81 0.2
77
79
40
73 82
71 81 dBA
0.1 L
20
75
78 Ø12
71
68 80 81 12 holes
1 2 3 4 5 6
2000 3000 4000 5000 6000 7000 8000 9000 10000
Air flow [m3/h]
600

0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6


Air flow [m3/h]
0.8
Power [kW]

0.6 6
560

5 50
0
0.4
4
3 57
0.2 5
2
1
0
2000 3000 4000 5000 6000 7000 8000 9000 10000
Air flow [m3/h]
Axis-P 500-4...-K

10 blaubergventilatoren.de
blaubergventilatoren.de

Technical data
AXIS-P 500-2
Voltage Fan model with Fans model with fiberglass Blade setting Weight Lenght L Curve
Size Number [V / aluminum blades impeller reinforced polyamide blades Installed motor RPM [min⁻¹] Number of number
of poles 50 Hz] (AL) impeller (PAG) power Ny [kW] blades angle [°] [kg] [mm] on graph

- Axis-P 500-2D/1.1-6/25/PAG 1.1 2880 6 25 48.2 450 


Axis-P 500-2D/1.5-6/30/AL Axis-P 500-2D/1.5-6/30/PAG 1.5 2880 6 30 53.7 450 
Axis-P 500-2D/2.2-6/35/AL Axis-P 500-2D/2.2-6/35/PAG 2.2 2880 6 35 55.7 450 
500 2 3~400
Axis-P 500-2D/3-8/35/AL Axis-P 500-2D/3-8/35/PAG 3 2880 8 35 65.3 450 (550*) 
Axis-P 500-2D/4-8/40/AL Axis-P 500-2D/4-8/40/PAG 4 2880 8 40 75.4 550 
Axis-P 500-2D/5.5-8/45/AL Axis-P 500-2D/5.5-8/45/PAG 5.5 2880 8 45 96.8 550 
* Including a motor with energy efficiency IE3

Aerodynamic characteristics
Air flow [CFM]
3000 4000 5000 6000 7000 8000 9000 10000 11000
L
700 2.8
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 500 Ø12
98 99 Number of poles: 2 12 holes
600 2.4

99 100

600
94 Pd
500 92 98 2.0

90
94 100
400 98 1.6
91

560
97 50
0
90 93 99
300 1.2

AXIS-P 500
97
90 Axis-P 500-2
88 95
200 99 0.8
92

94 96 dBA
88
85 L
100 0.4
98
90 93 Ø12
82 86 95 12 holes
1 2 3 4 5 6
4000 6000 8000 10000 12000 14000 16000 18000 20000
Air flow [m3/h]
600

1.2 1.6 2 2.4 2.8 3.2 3.8 4 4.4 4.8 5.2


Air flow [m3/h]
6.0
Power [kW]

5.0
6
4.0
560

50
3.0
5 0
4
2.0 3 57
5
2
1.0 1
0
4000 6000 8000 10000 12000 14000 16000 18000 20000
Air flow [m3/h]
Axis-P 500-2...-K

AXIS-P | AXIS-FP 11
AXIS-P | AXIS-FP

Technical data
AXIS-P 560-4
Voltage Fan model with Fans model with fiberglass Blade setting Weight Lenght L Curve
Size Number [V / aluminum blades impeller reinforced polyamide blades Installed motor RPM [min⁻¹] Number of number
of poles 50 Hz] (AL) impeller (PAG) power Ny [kW] blades angle [°] [kg] [mm] on graph

- Axis-P 560-4D/0.25-6/25/PAG 0.25 1440 6 25 61.5 350 


Axis-P 560-4D/0.37-6/30/AL Axis-P 560-4D/0.37-6/30/PAG 0.37 1440 6 30 61.7 350 
Axis-P 560-4D/0.55-6/35/AL Axis-P 560-4D/0.55-6/35/PAG 0.55 1440 6 35 64.8 350 (450*) 
560 4 3~400
Axis-P 560-4D/0.55-6/40/AL Axis-P 560-4D/0.55-6/40/PAG 0.55 1440 6 40 64.8 350 (450*) 
Axis-P 560-4D/0.75-6/45/AL Axis-P 560-4D/0.75-6/45/PAG 0.75 1440 6 45 65.6 450 
Axis-P 560-4D/1.1-8/45/AL Axis-P 560-4D/1.1-8/45/PAG 1.1 1440 8 45 71.4 450 
* Including a motor with energy efficiency IE3

Aerodynamic characteristics
Air flow [CFM]
2000 3000 4000 5000 6000 7000 L
200 0.8
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 560 Ø12
Number of poles: 4 12 holes
180
0.7

160
82 84 85

660
0.6
81
140 80
Pd
82 85
84 0.5
120
78

620
81
100 56
79 0.4 0
82 84
76 85
AXIS-P 560

80
80 0.3
Axis-P 560-4
77
60
74 81 83

84
0.2
79
40 dBA
72 80
75 L
0.1
20 77 Ø12
82 83
69 73 79 12 holes
1 2 3 4 5 6
3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000
Air flow [m3/h]
660

1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4
Air flow [m3/h]
1.0
Power [kW]

6
0.75
5
620

56
0
0.5 4
3 59
0.25 2 0
1
0
3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000
Air flow [m3/h]
Axis-P 560-4 ...-K

12 blaubergventilatoren.de
blaubergventilatoren.de

Technical data
AXIS-P 560-2
Voltage Fan model with Fans model with fiberglass Blade setting Weight Lenght L Curve
Size Number [V / aluminum blades impeller reinforced polyamide blades Installed motor RPM [min⁻¹] Number of number
of poles 50 Hz] (AL) impeller (PAG) power Ny [kW] blades angle [°] [kg] [mm] on graph

- Axis-P 560-2D/1.5-6/25/PAG 1.5 2880 6 25 70.8 450 


Axis-P 560-2D/2.2-6/30/AL Axis-P 560-2D/2.2/6/30/PAG 2.2 2880 6 30 72.8 450 
Axis-P 560-2D/3-8/30/AL Axis-P 560-2D/3-8/30/PAG 3 2880 8 30 82.4 450 (550*) 
560 2 3~400
Axis-P 560-2D/4-8/35/AL Axis-P 560-2D/4-8/35/PAG 4 2880 8 35 92.5 550 
Axis-P 560-2D/5.5-8/40/AL Axis-P 560-2D/5.5-8/40/PAG 5.5 2880 8 40 113.9 550 
Axis-P 560-2D/7.5-8/45/AL Axis-P 560-2D/7.5-8/45/PAG 7.5 2880 8 45 117.9 550 (650*) 
* Including a motor with energy efficiency IE3

Aerodynamic characteristics
Air flow [CFM]
4000 6000 8000 10000 12000 14000
800 L
3.2
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 560 Ø12
100 Number of poles: 2 12 holes
99
700 101 2.8
97

660
600 2.4
99
100 102
97
94 Pd
500 2.0
99
92 102

620
100
400 1.6 56
93 96 0

90

AXIS-P 560
97
300 1.2
92 94 99 101 Axis-P 560-2

88
200 0.5
90 96
92 98 100
86 dBA L
100 0.4
88
90 94 99 Ø12
97
83 12 holes
1 2 3 4 5 6
6000 8000 10000 12000 14000 16000 18000 20000 22000 24000 26000
Air flow [m3/h]
660

2 2.4 2.8 3.2 3.6 4 4.4 4.8 5.2 5.6 6 6.4 6.8
Air flow [m3/h]
8.0
Power [kW]

6.0
6
620

5 56
0
4.0
4
3 59
0
2.0 2
1
0
6000 8000 10000 12000 14000 16000 18000 20000 22000 24000 26000
Air flow [m3/h]
Axis-P 560-2 ...-K

AXIS-P | AXIS-FP 13
AXIS-P | AXIS-FP

Technical data
AXIS-P 630-4
Voltage Fan model with Fans model with fiberglass Blade setting Weight Lenght L Curve
Size Number [V / aluminum blades impeller reinforced polyamide blades Installed motor RPM [min⁻¹] Number of number
of poles 50 Hz] (AL) impeller (PAG) power Ny [kW] blades angle [°] [kg] [mm] on graph

- Axis-P 630-4D/0.37-8/25/PAG 0.37 1440 8 25 67.9 350 


Axis-P 630-4D/0.55-8/30/AL Axis-P 630-4D/0.55-8/30/PAG 0.55 1440 8 30 71 350 (450*) 
Axis-P 630-4D/0.75-8/35/AL Axis-P 630-4D/0.75-8/35/PAG 0.75 1440 8 35 71.8 450 
Axis-P 630-4D/1.1-8/40/AL Axis-P 630-4D/1.1-8/40/PAG 1.1 1440 8 40 77 450 
630 4 3~400 Axis-P 630-4D/1.5-6/32.5/AL Axis-P 630-4D/1.5-6/32.5/PAG 1.5 1440 6 32.5 81.1 450 
Axis-P 630-4D/1.5-8/45/AL Axis-P 630-4D/1.5-8/45/PAG 1.5 1440 8 45 80 450 
Axis-P 630-4D/1.5-6/37.5/AL Axis-P 630-4D/1.5-6/37.5/PAG 1.5 1440 6 37.5 81.1 450 
Axis-P 630-4D/2.2-6/40/AL Axis-P 630-4D/2.2-6/40/PAG 2.2 1440 6 40 83.2 450 (550*) 
Axis-P 630-4D/2.2-6/45/AL Axis-P 630-4D/2.2-6/45/PAG 2.2 1440 6 45 83.2 450 (550*) 
* Including a motor with energy efficiency IE3

Aerodynamic characteristics
Air flow [CFM]
3000 4000 5000 6000 7000 8000 9000 10000 11000 12000
L
250 1
Static pressure [Ps (Pa)]

Standard size: 630 Static pressure [Ps (in WG)] Ø12


Number of poles: 4 12 holes
0.9
89
88
Pd
200 0.8
85 89

730
85 90
87
0.7
83
87 89
AXIS-P 630

85
150 0.6
84

690
88 90
0.5 63
80 82 86
0
87 88
83 84
100 0.4

80 Axis-P 630-4
77 87 89
0.3
81 83 85 86 87
dBA L
50 0.2
74 77
Ø12
12 holes
0.1
79 86 86 88
70 75 81 84 85
1 2 3 4 5 6 7 8 9
730

4000 6000 8000 10000 12000 14000 16000 18000 20000


Air flow [m3/h]

1.2 1.6 2.0 2.4 2.8 3.2 3.6 4.0 4.4 4.8 5.2 5.6
Air flow [m3/h]
2.5
Power [kW]

9
690

2.0 63
0
8
1.5
7
5 6 65
0
1.0
4
3
0.5 2
1
0
4000 6000 8000 10000 12000 14000 16000 18000 20000 Axis-P 630-4 ...-K
Air flow [m3/h]

14 blaubergventilatoren.de
blaubergventilatoren.de

Technical data
AXIS-P 630-2
Voltage Fan model with Fans model with fiberglass Blade setting Weight Lenght L Curve
Size Number [V / aluminum blades impeller reinforced polyamide blades Installed motor RPM [min⁻¹] Number of number
of poles 50 Hz] (AL) impeller (PAG) power Ny [kW] blades angle [°] [kg] [mm] on graph

- Axis-P 630-2D/3-8/25/PAG 3 2880 8 25 88 450 (550*) 


Axis-P 630-2D/4-8/30/AL Axis-P 630-2D/4-8/30/PAG 4 2880 8 30 98.1 550 
Axis-P 630-2D/5.5-8/35/AL Axis-P 630-2D/5.5-8/35/PAG 5.5 2880 8 35 119.5 550 
Axis-P 630-2D/7.5-8/40/AL Axis-P 630-2D/7.5-8/40/PAG 7.5 2880 8 40 123.5 550 (650*) 
Axis-P 630-2D/9.2-6/30/AL Axis-P 630-2D/9.2-6/30/PAG 9.2 2880 6 30 130.1 650 
630 2 3~400
Axis-P 630-2D/11-6/32.5/AL Axis-P 630-2D/11-6/32.5/PAG 11 2880 6 32.5 154.1 650 (750*) 
Axis-P 630-2D/11-6/35/AL Axis-P 630-2D/11-6/35/PAG 11 2880 6 35 154.1 650 (750*) 
Axis-P 630-2D/15-6/37.5/AL Axis-P 630-2D/15-6/37.5/PAG 15 2880 6 37.5 166.7 750 
Axis-P 630-2D/15-6/40/AL Axis-P 630-2D/15-6/40/PAG 15 2880 6 40 166.7 750 
Axis-P 630-2D/18.5-6/45/AL Axis-P 630-2D/18.5-6/45/PAG 18.5 2880 6 45 179.8 750 
* Including a motor with energy efficiency IE3

Aerodynamic characteristics
Air flow [CFM]
5000 10000 15000 20000 25000
L
1000 4.0
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


103 Standard size: 630 Ø12

900 Number of poles: 2 3.6


12 holes
103

103 Pd
800 3.2
104

730
99 101 102
102
700 2.8
104
96 102 105

AXIS-P 630
600 2.4
100
102

690
102
98
500 2.0 63
96 104 0

101 103
99
400 95
1.6
101

96 101 Axis-P 630-2


102 104
300 93 1.2
100
102
97 100 104 L
200 93 100
0.8
90
Ø12
98
12 holes
100 103 0.4
100 dBA
87 91 95 98 99 101

1 2 3 4 5 6 7 8 9 10
730

5000 10000 15000 20000 25000 30000 35000 40000 45000


Air flow [m3/h]

2 3 4 5 6 7 8 9 10 11 12
Air flow [m3/h]
18.0 10
Power [kW]

15.0
690

9 63
0
12.0
8
9.0 7 65
6 0
5
6.0 4
3
3.0 1 2
0
5000 10000 15000 20000 25000 30000 35000 40000 45000 Axis-P 630-2 ...-K

Air flow [m /h] 3

AXIS-P | AXIS-FP 15
AXIS-P | AXIS-FP

Technical data
AXIS-P 710-4
Voltage Fan model with Fans model with fiberglass Blade setting Weight Lenght L Curve
Size Number [V / aluminum blades impeller reinforced polyamide blades Installed motor RPM [min⁻¹] Number of number
of poles 50 Hz] (AL) impeller (PAG) power Ny [kW] blades angle [°] [kg] [mm] on graph

Axis-P 710-4D/0.75-6/20/AL Axis-P 710-4D/0.75-6/20/PAG 0.75 1440 6 20 99.1 450 


Axis-P 710-4D/1.1-6/25/AL Axis-P 710-4D/1.1-6/25/PAG 1.1 1440 6 25 104.3 450 
Axis-P 710-4D/1.5-6/30/AL Axis-P 710-4D/1.5-6/30/PAG 1.5 1440 6 30 107.3 450 
Axis-P 710-4D/2.2-6/32.5/AL Axis-P 710-4D/2.2-6/32.5/PAG 2.2 1440 6 32.5 109.4 450 (550*) 
710 4 3~400
Axis-P 710-4D/2.2-6/35/AL Axis-P 710-4D/2.2-6/35/PAG 2.2 1440 6 35 109.4 450 (550*) 
Axis-P 710-4D/2.2-6/37.5/AL Axis-P 710-4D/2.2-6/37.5/PAG 2.2 1440 6 37.5 109.4 450 (550*) 
Axis-P 710-4D/3-6/40/AL Axis-P 710-4D/3-6/40/PAG 3 1440 6 40 118.3 550 
Axis-P 710-4D/4-6/45/AL Axis-P 710-4D/4-6/45/PAG 4 1440 6 45 129.4 550 
* Including a motor with energy efficiency IE3

Aerodynamic characteristics
Air flow [CFM]
4000 6000 8000 10000 12000 14000 16000 L
300 1.2
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 710 Ø12
Number of poles: 4 1.1 16 holes
270 89
87 90 91
92 Pd 1.0
240
85 90

810
91
89 0.9
210
90
87 0.8
91 92
180 88 89 0.7
84
90

770
AXIS-P 710

150 0.6 71
86 89 92 0
91

120
88 0.5
82 87

84 Axis-P 710-4
0.4
90 92
88 89 90
87 0.3
79 86
60 82
dBA 0.2 L
91
30 Ø12
87 88 89 0.1
76 80 84 85 16 holes
1 2 3 4 5 6 7 8
5000 10000 15000 20000 25000 30000
Air flow [m3/h]
810

2 3 4 5 6 7 8
Air flow [m3/h]
4.0
Power [kW]

8
3.0
770

7 71
0
2.0 6
5
4
1.0
3 76
5
1 2

0
5000 10000 15000 20000 25000 30000
Air flow [m3/h]
Axis-P 710-4...-K

16 blaubergventilatoren.de
blaubergventilatoren.de

Technical data
AXIS-P 710-2
Voltage Fan model with Fans model with fiberglass Blade setting Weight Lenght L Curve
Size Number [V / aluminum blades impeller reinforced polyamide blades Installed motor RPM [min⁻¹] Number of number
of poles 50 Hz] (AL) impeller (PAG) power Ny [kW] blades angle [°] [kg] [mm] on graph

Axis-P 710-2D/7.5-6/20/AL Axis-P 710-2D/7.5-6/20/PAG 7.5 2880 6 20 150.8 550 (650*) 


Axis-P 710-2D/9.2-6/25/AL Axis-P 710-2D/9.2-6/25/PAG 9.2 2880 6 25 156.3 650 
Axis-P 710-2D/15-6/30/AL Axis-P 710-2D/15-6/30/PAG 15 2880 6 30 192.9 750 
710 2 3~400 Axis-P 710-2D/15-6/32.5/AL Axis-P 710-2D/15-6/32.5/PAG 15 2880 6 32.5 192.9 750 
Axis-P 710-2D/18.5-6/35/AL Axis-P 710-2D/18.5-6/35/PAG 18.5 2880 6 35 206 750 
Axis-P 710-2D/18.5-6/37.5/AL Axis-P 710-2D/18.5-6/37.5/PAG 18.5 2880 6 37.5 206 750 
Axis-P 710-2D/22-6/40/AL Axis-P 710-2D/22-6/40/PAG 22 2880 6 40 246 850 
* Including a motor with energy efficiency IE3

Aerodynamic characteristics
Air flow [CFM]
9000 12000 15000 18000 21000 24000 27000 30000 L
1200 4.8
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 710 Ø12
1100 Number of poles: 2 4.4 16 holes
103 105
104
102 105 106
1000 4.0

810
900 3.6
Pd
103 104 105
800 3.2
99 101 106

700 105 2.8

770

AXIS-P 710
71
600 100 102 103 104 2.4 0
106
97
500 2.0

Axis-P 710-2
400 105
1.6

98 101
102 103 105
300 1.2
95

200 0.8 L
dBA
103 104 Ø12
100 100
0.4
91 95 99 102 16 holes
1 2 3 4 5 6 7
10000 20000 30000 40000 50000
Air flow [m3/h]
810

3 4 5 6 7 8 9 10 11 12 13 14 15
Air flow [m3/h]
25
Power [kW]

20 7
770

15 6 71
0
5
10 4
3 76
2 5
5 1
0
10000 20000 30000 40000 50000
Air flow [m3/h] Axis-P 710-2...-K

AXIS-P | AXIS-FP 17
AXIS-P | AXIS-FP

Technical data
AXIS-P 800-6
Voltage Fan model with Fans model with fiberglass Blade setting Weight Lenght L Curve
Size Number [V / aluminum blades impeller reinforced polyamide blades Installed motor RPM [min⁻¹] Number of number
of poles 50 Hz] (AL) impeller (PAG) power Ny [kW] blades angle [°] [kg] [mm] on graph

Axis-P 800-6D/0.37-6/20/AL Axis-P 800-6D/0.37-6/20/PAG 0.37 960 6 20 109.6 450 


Axis-P 800-6D/0.55-6/25/AL Axis-P 800-6D/0.55-6/25/PAG 0.55 960 6 25 111.1 450 
Axis-P 800-6D/0.75-6/30/AL Axis-P 800-6D/0.75-6/30/PAG 0.75 960 6 30 116.4 450 
Axis-P 800-6D/0.75-6/32.5/AL Axis-P 800-6D/0.75-6/32.5/PAG 0.75 960 6 32.5 116.4 450 
800 6 3~400
Axis-P 800-6D/1.1-6/35/AL Axis-P 800-6D/1.1-6/35/PAG 1.1 960 6 35 116.5 450 
Axis-P 800-6D/1.1-6/37.5/AL Axis-P 800-6D/1.1-6/37.5/PAG 1.1 960 6 37.5 116.5 450 
Axis-P 800-6D/1.1-6/40/AL Axis-P 800-6D/1.1-6/40/PAG 1.1 960 6 40 116.5 450 
Axis-P 800-6D/1.5-6/45/AL Axis-P 800-6D/1.5-6/45/PAG 1.5 960 6 45 124.6 550 

Aerodynamic characteristics
Air flow [CFM]
4000 6000 8000 10000 12000 14000 L
0.6
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


140 Standard size: 800 Ø12
Number of poles: 6 16 holes

80 84 85
82
86 Pd 0.5
120 83 84

900
84 85
82
100 80 0.4
86

78 81 83
82 85

860
80
AXIS-P 800

84 80
79
0.3 0
86
77

60
80
82 84
Axis-P 800-6
77 83
0.2
75
80
40
86
79

81 84 L
72 75 dBA 0.1
20 82 Ø12
78 16 holes
69 73 77 80 83 85
1 2 3 4 5 6 7 8
6000 9000 12000 15000 18000 21000 24000 27000
900

Air flow [m3/h]

2 3 4 5 6 7
Air flow [m3/h]
1.5
Power [kW]

8
1.2
860

7 80
0
0.9 6
5 84
0.6 4 5
3
0.3 2
1
0
6000 9000 12000 15000 18000 21000 24000 27000
Axis-P 800-6 ...-K
Air flow [m3/h]

18 blaubergventilatoren.de
blaubergventilatoren.de

Technical data
AXIS-P 800-4
Voltage Fan model with Fans model with fiberglass Blade setting Weight Lenght L Curve
Size Number [V / aluminum blades impeller reinforced polyamide blades Installed motor RPM [min⁻¹] Number of number
of poles 50 Hz] (AL) impeller (PAG) power Ny [kW] blades angle [°] [kg] [mm] on graph

Axis-P 800-4D/1.1-6/20/AL Axis-P 800-4D/1.1-6/20/PAG 1.1 1440 6 20 115.6 450 


Axis-P 800-4D/1.5-6/25/AL Axis-P 800-4D/1.5-6/25/PAG 1.5 1440 6 25 118.6 450 
Axis-P 800-4D/2.2-6/30/AL Axis-P 800-4D/2.2-6/30/PAG 2.2 1440 6 30 120.7 450/(550*) 
Axis-P 800-4D/3-6/32.5/AL Axis-P 800-4D/3-6/32.5/PAG 3 1440 6 32.5 129.6 550 
800 4 3~400
Axis-P 800-4D/3-6/35/AL Axis-P 800-4D/3-6/35/PAG 3 1440 6 35 129.6 550 
Axis-P 800-4D/4-6/37.5/AL Axis-P 800-4D/4-6/37.5/PAG 4 1440 6 37.5 140.7 550 
Axis-P 800-4D/4-6/40/AL Axis-P 800-4D/4-6/40/PAG 4 1440 6 40 140.7 550 
Axis-P 800-4D/5.5-6/45/AL Axis-P 800-4D/5.5-6/45/PAG 5.5 1440 6 45 157.6 550 
* Including a motor with energy efficiency IE3

Aerodynamic characteristics
Air flow [CFM]
4000 6000 8000 10000 12000 14000 16000 18000 20000 22000 24000 L
1.3
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 800 Ø12
300 Number of poles: 4 1.2 16 holes
92
87 91 93 93
89 94 1.1
90
250

900
1.0
92 Pd
95
0.9
86 93
88 91
200 0.8
90 92

0.7

860
85 91 95

AXIS-P 800
87 80
0
150 0.6
89 93

88
0.5
83 91 94
Axis-P 800-4
100 0.4
85
91 92
0.3
87 88 90 94
80 L
83
50 0.2
dBA Ø12
0.1 16 holes
77 81 85 87 89 90 91 93
1 2 3 4 5 6 7 8
5000 10000 15000 20000 25000 30000 35000 40000
900

Air flow [m3/h]

2 3 4 5 6 7 8 9 10 11
Air flow [m3/h]
6.0
Power [kW]

5.0
8
860

4.0 80
0
7
3.0
6
5 84
5
2.0
3 4
1.0 2
1
0
5000 10000 15000 20000 25000 30000 35000 40000
Air flow [m3/h] Axis-P 800-4...-K

AXIS-P | AXIS-FP 19
AXIS-P | AXIS-FP

Technical data
AXIS-P 900-6
Voltage Fan model with Fans model with fiberglass Blade setting Weight Lenght L Curve
Size Number [V / aluminum blades impeller reinforced polyamide blades Installed motor RPM [min⁻¹] Number of number
of poles 50 Hz] (AL) impeller (PAG) power Ny [kW] blades angle [°] [kg] [mm] on graph

Axis-P 900-6D/0.75-8/20/AL Axis-P 900-6D/0.75-8/20/PAG 0.75 960 8 20 121.6 450 


Axis-P 900-6D/1.1-8/25/AL Axis-P 900-6D/1.1-8/25/PAG 1.1 960 8 25 121.7 450 
Axis-P 900-6D/1.5-8/30/AL Axis-P 900-6D/1.5-8/30/PAG 1.5 960 8 30 129.8 550 
Axis-P 900-6D/1.5-8/32.5/AL Axis-P 900-6D/1.5-8/32.5/PAG 1.5 960 8 32.5 129.8 550 
900 6 3~400
Axis-P 900-6D/2.2-8/35/AL Axis-P 900-6D/2.2-8/35/PAG 2.2 960 8 35 135.3 550 
Axis-P 900-6D/2.2-8/37.5/AL Axis-P 900-6D/2.2-8/37.5/PAG 2.2 960 8 37.5 135.3 550 
Axis-P 900-6D/2.2-8/40/AL Axis-P 900-6D/2.2-8/40/PAG 2.2 960 8 40 135.3 550 
Axis-P 900-6D/3-8/45/AL Axis-P 900-6D/3-8/45/PAG 3 960 8 45 155.8 650 

Aerodynamic characteristics
Air flow [CFM]
4000 6000 8000 10000 12000 14000 16000 18000 20000 L
250 1
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 900 Ø15
Number of poles: 6 16 holes
0.9

87 89
200 0.8

1015
85 88
84
90
86 0.7
89
84
150 88 0.6
87
86 89
82 86

970
Pd
AXIS-P 900

0.5 90
88
0
83
100 86 0.4
85 88
79
84 Axis-P 900-6
87
82 85
0.3
84
82 87
50 0.2 L
76 79 81 dBA
85

Ø15
86 0.1 16 holes
72 75 79 81 82 83
84
1 2 3 4 5 6 7 8
5000 10000 15000 20000 25000 30000 35000
1015

Air flow [m3/h]

2 3 4 5 6 7 8 9
Air flow [m3/h]
3.0
Power [kW]

2.5
8
970

2.0 7 90
0
1.5 6
5
4 98
1.0 3 5
2
0.5 1
0
5000 10000 15000 20000 25000 30000 35000
Air flow [m3/h] Axis-P 900-6...-K

20 blaubergventilatoren.de
blaubergventilatoren.de

Technical data
AXIS-P 900-4
Voltage Fan model with Fans model with fiberglass Blade setting Weight Lenght L Curve
Size Number [V / aluminum blades impeller reinforced polyamide blades Installed motor RPM [min⁻¹] Number of number
of poles 50 Hz] (AL) impeller (PAG) power Ny [kW] blades angle [°] [kg] [mm] on graph

Axis-P 900-4D/3-8/20/AL Axis-P 900-4D/3-8/20/PAG 3 1440 8 20 134.8 550 


Axis-P 900-4D/4-8/25/AL Axis-P 900-4D/4-8/25/PAG 4 1440 8 25 145.9 550 
Axis-P 900-4D/5.5-8/30/AL Axis-P 900-4D/5.5-8/30/PAG 5.5 1440 8 30 162.8 550 
Axis-P 900-4D/5.5-8/32.5/AL Axis-P 900-4D/5.5-8/32.5/PAG 5.5 1440 8 32.5 162.8 550 
900 4 3~400
Axis-P 900-4D/7.5-8/35/AL Axis-P 900-4D/7.5-8/35/PAG 7.5 1440 8 35 165.3 650 
Axis-P 900-4D/7.5-8/37.5/AL Axis-P 900-4D/7.5-8/37.5/PAG 7.5 1440 8 37.5 165.3 650 
Axis-P 900-4D/7.5-8/40/AL Axis-P 900-4D/7.5-8/40/PAG 7.5 1440 8 40 165.3 650 
Axis-P 900-4D/11-8/45/AL Axis-P 900-4D/11-8/45/PAG 11 1440 8 45 199.6 750 

Aerodynamic characteristics
Air flow [CFM]
6000 9000 12000 15000 18000 21000 24000 27000 30000 L
2.2
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 900 Ø15
500 Number of poles: 4 2.0 16 holes

97
95 96 96
1.8

1015
94 98
400 1.6
92

97
95
1.4
94 95 96
93 98 Pd
300 1.2

970
91
90
0

AXIS-P 900
96
95 1
94
91 92 97
200 89 0.8
93 Axis-P 900-4
95

94
0.6

88 92 97
86 90 L
100 0.4
94

dBA Ø15
0.2 16 holes
89
81 84 87 91 92 93 95
1 2 3 4 5 6 7 8
10000 20000 30000 40000 50000
1015

Air flow [m3/h]

3 4 5 6 7 8 9 10 11 12 13 14 15
Air flow [m3/h]
12
Power [kW]

10 8
970

90
8.0 0
7
6.0 6
5 98
4.0 4 5
3
2
2.0 1
0
10000 20000 30000 40000 50000
Axis-P 900-4...-K
Air flow [m3/h]

AXIS-P | AXIS-FP 21
AXIS-P | AXIS-FP

Technical data
AXIS-P 1000-6
Voltage Fan model with Fans model with fiberglass Blade setting Weight Lenght L Curve
Size Number [V / aluminum blades impeller reinforced polyamide blades Installed motor RPM [min⁻¹] Number of number
of poles 50 Hz] (AL) impeller (PAG) power Ny [kW] blades angle [°] [kg] [mm] on graph

Axis-P 1000-6D/1.5-8/25/AL Axis-P 1000-6D/1.5-8/25/PAG 1.5 960 8 25 167.5 550 


Axis-P 1000-6D/2.2-8/30/AL Axis-P 1000-6D/2.2-8/30/PAG 2.2 960 8 30 173 550 
Axis-P 1000-6D/2.2-8/32.5/AL Axis-P 1000-6D/2.2-8/32.5/PAG 2.2 960 8 32.5 173 550 
Axis-P 1000-6D/3-8/35/AL Axis-P 1000-6D/3-8/35/PAG 3 960 8 35 193.5 650 
1000 6 3~400
Axis-P 1000-6D/3-8/37.5/AL Axis-P 1000-6D/3-8/37.5/PAG 3 960 8 37.5 193.5 650 
Axis-P 1000-6D/4-8/40/AL Axis-P 1000-6D/4-8/40/PAG 4 960 8 40 203.5 650 
Axis-P 1000-6D/5.5-8/45/AL Axis-P 1000-6D/5.5-8/45/PAG 5.5 960 8 45 207.5 650 
Axis-P 1000-6D/5.5-8/50/AL Axis-P 1000-6D/5.5-8/50/PAG 5.5 960 8 50 207.5 650 

Aerodynamic characteristics
Air flow [CFM]
6000 9000 12000 15000 18000 21000 24000 27000 30000
L
250 1.0
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 1000 Ø15
Number of poles: 6 16 holes
0.9

89 91 Pd
200 90 0.8
88 88 92

1115
93

86
0.7
87 91 92 93
89
150 0.6
88 90
93

1070
85 90 92 10
0.5 00
AXIS-P 1000

86
88

87
100 0.4
90 93
85 89
91 Axis-P 1000-6
83 87
0.3

93
85 89 90
50 0.2 L
83 86 87
80
dBA
Ø15
87 0.1 16 holes
85 89 92
76 81 83 84
1 2 3 4 5 6 7 8
10000 20000 30000 40000 50000
1115

Air flow [m3/h]

3 4 5 6 7 8 9 10 11 12 13 14 15
Air flow [m3/h]
6.0
Power [kW]

8
5.0
1070

10
4.0 7 00

3.0 6 10
5 80
2.0
3 4
1.0
2
1
0
10000 20000 30000 40000 50000
Axis-P 1000-6...-K
Air flow [m3/h]

22 blaubergventilatoren.de
blaubergventilatoren.de

Technical data
AXIS-P 1000-4
Voltage Fan model with Fans model with fiberglass Blade setting Weight Lenght L Curve
Size Number [V / aluminum blades impeller reinforced polyamide blades Installed motor RPM [min⁻¹] Number of number
of poles 50 Hz] (AL) impeller (PAG) power Ny [kW] blades angle [°] [kg] [mm] on graph

Axis-P 1000-4D/5.5-8/25/AL Axis-P 1000-4D/5.5-8/25/PAG 5.5 1440 8 25 200.5 550 


Axis-P 1000-4D/7.5-8/30/AL Axis-P 1000-4D/7.5-8/30/PAG 7.5 1440 8 30 203 650 
Axis-P 1000-4D/7.5-8/32.5/AL Axis-P 1000-4D/7.5-8/32.5/PAG 7.5 1440 8 32.5 203 650 
Axis-P 1000-4D/9.2-8/35/AL Axis-P 1000-4D/9.2-8/35/PAG 9.2 1440 8 35 233.5 650 
1000 4 3~400
Axis-P 1000-4D/11-8/37.5/AL Axis-P 1000-4D/11-8/37.5/PAG 11 1440 8 37.5 237.3 800 
Axis-P 1000-4D/11-8/40/AL Axis-P 1000-4D/11-8/40/PAG 11 1440 8 40 237.3 800 
Axis-P 1000-4D/15-8/45/AL Axis-P 1000-4D/15-8/45/PAG 15 1440 8 45 256.4 800 
Axis-P 1000-4D/18.5-8/50/AL Axis-P 1000-4D/18.5-8/50/PAG 18.5 1440 8 50 301.9 900 

Aerodynamic characteristics
Air flow [CFM]
12000 16000 20000 24000 28000 32000 36000 40000 44000
L
2.2
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 1000 Ø15
500 Number of poles: 4 2.0 16 holes

99
98
101 1.8
98 101

1115
Pd
97
400 1.6
96
94 102
100
98
99 100 1.4

102
300 1.2

1070
96 10
00

AXIS-P 1000
94 99
93 96 98 1.0
100

102
200 0.8
Axis-P 1000-4

98
94
97 0.6
90 92 95
99 101
L
100 0.4
dBA
Ø15
96
0.2 16 holes
86 90 92 94 95 98 100

1 2 3 4 5 6 7 8
20000 30000 40000 50000 60000 70000 80000
1115

Air flow [m3/h]

6 8 10 12 14 16 18 20 22
Air flow [m3/h]
20
Power [kW]

8
1070

15 10
7 00

10 6
5 10
80
3 4
5 2
1
0
20000 30000 40000 50000 60000 70000 80000
Axis-P 1000-4...-K
Air flow [m3/h]

AXIS-P | AXIS-FP 23
AXIS-P | AXIS-FP

Technical data
AXIS-P 1120-6
Voltage Fan model with Fans model with fiberglass Blade setting Weight Lenght L Curve
Size Number [V / aluminum blades impeller reinforced polyamide blades Installed motor RPM [min⁻¹] Number of number
of poles 50 Hz] (AL) impeller (PAG) power Ny [kW] blades angle [°] [kg] [mm] on graph

Axis-P 1120-6D/2.2-8/25/AL Axis-P 1120-6D/2.2-8/25/PAG 2.2 960 8 25 192 550 


Axis-P 1120-6D/3-8/30/AL Axis-P 1120-6D/3-8/30/PAG 3 960 8 30 212.5 650 
Axis-P 1120-6D/4-8/32.5/AL Axis-P 1120-6D/4-8/32.5/PAG 4 960 8 32.5 222.5 650 
Axis-P 1120-6D/4-8/35/AL Axis-P 1120-6D/4-8/35/PAG 4 960 8 35 222.5 650 
1120 6 3~400
Axis-P 1120-6D/5.5-8/37.5/AL Axis-P 1120-6D/5.5-8/37.5/PAG 5.5 960 8 37.5 226.5 650 
Axis-P 1120-6D/5.5-8/40/AL Axis-P 1120-6D/5.5-8/40/PAG 5.5 960 8 40 226.5 650 
Axis-P 1120-6D/7.5-8/45/AL Axis-P 1120-6D/7.5-8/45/PAG 7.5 960 8 45 254.8 800 
Axis-P 1120-6D/9.2-8/50/AL Axis-P 1120-6D/9.2-8/50/PAG 9.2 960 8 50 272.5 800 

Aerodynamic characteristics
Air flow [CFM]
12000 16000 20000 24000 28000 32000 36000 40000 44000
L
1.2
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 1120 Ø15
Number of poles: 6 1.1 20 holes
92
94
250 93 1.0
95 96

1270
90

91 92 0.9
94 96 Pd
200 0.8
93
95
90 92
91 0.7
88 96
93

1190
150 0.6 11
20
AXIS-P 1120

92
94
86 91
88 89
0.5
96
93 Axis-P 1120-6
100 91 0.4
94
90
83
0.3
88 96
86
89 90 92 93 L
50 0.2
81 dBA Ø15
95 20 holes
86 88 89 92 0.1
80 84 90
1 2 3 4 5 6 7 8
20000 30000 40000 50000 60000 70000 80000
1270

Air flow [m3/h]

6 8 10 12 14 16 18 20 22
Air flow [m3/h]
10
Power [kW]

8
8
1190

11
6 7 20

6 12
4 5 10
3 4
2 2
1
0
20000 30000 40000 50000 60000 70000 80000
Air flow [m3/h] Axis-P 1120-6...-K

24 blaubergventilatoren.de
blaubergventilatoren.de

Technical data
AXIS-P 1120-4
Voltage Fan model with Fans model with fiberglass Blade setting Weight Lenght L Curve
Size Number [V / aluminum blades impeller reinforced polyamide blades Installed motor RPM [min⁻¹] Number of number
of poles 50 Hz] (AL) impeller (PAG) power Ny [kW] blades angle [°] [kg] [mm] on graph

Axis-P 1120-4D/7.5-8/25/AL Axis-P 1120-4D/7.5-8/25/PAG 7.5 1440 8 25 222 650 


Axis-P 1120-4D/11-8/30/AL Axis-P 1120-4D/11-8/30/PAG 11 1440 8 30 256.3 800 
Axis-P 1120-4D/11-8/32.5/AL Axis-P 1120-4D/11-8/32.5/PAG 11 1440 8 32.5 256.3 800 
1120 4 3~400 Axis-P 1120-4D/15-8/35/AL Axis-P 1120-4D/15-8/35/PAG 15 1440 8 35 275.4 800 
Axis-P 1120-4D/18.5-8/37.5/AL Axis-P 1120-4D/18.5-8/37.5/PAG 18.5 1440 8 37.5 320.9 900 
Axis-P 1120-4D/18.5-8/40/AL Axis-P 1120-4D/18.5-8/40/PAG 18.5 1440 8 40 320.9 900 
Axis-P 1120-4D/22-8/45/AL Axis-P 1120-4D/22-8/45/PAG 22 1440 8 45 334.2 900 

Aerodynamic characteristics
Air flow [CFM]
15000 20000 25000 30000 35000 40000 45000 50000 55000 L
700 2.8
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 1120 Ø15
Number of poles: 4 20 holes

600 2.4
102
101 102
99 104

1270
500 2.0
97 102 103
101
100 104 Pd
99
400 1.6
101 102 102

1190
96 99 103 11
20

AXIS-P 1120
98
300 102 1.2
100 101
98 103
Axis-P 1120-4
94 96
200 99 0.8
101
97
99 102 L
91 95 98
100 0.4
Ø15
dBA
99 20 holes
95 97
88 93 96 101
1 2 3 4 5 6 7
20000 30000 40000 50000 60000 70000 80000 90000 100000
1270

Air flow [m3/h]

6 8 10 12 14 16 18 20 22 24 26
Air flow [m3/h]
25
Power [kW]

7
20
1190

11
15
6 20
5
4
10 3 12
10
2
5 1

0
20000 30000 40000 50000 60000 70000 80000 90000 100000
Air flow [m3/h] Axis-P 1120-4...-K

AXIS-P | AXIS-FP 25
AXIS-P | AXIS-FP

Technical data
AXIS-P 1250-6
Voltage Fan model with Fans model with fiberglass Blade setting Weight Lenght L Curve
Size Number [V / aluminum blades impeller reinforced polyamide blades Installed motor RPM [min⁻¹] Number of number
of poles 50 Hz] (AL) impeller (PAG) power Ny [kW] blades angle [°] [kg] [mm] on graph

Axis-P 1250-6D/2.2-8/25/AL Axis-P 1250-6D/2.2-8/25/PAG 2.2 960 8 25 211 550 


Axis-P 1250-6D/3-8/30/AL Axis-P 1250-6D/3-8/30/PAG 3 960 8 30 231.5 650 
Axis-P 1250-6D/4-8/32.5/AL Axis-P 1250-6D/4-8/32.5/PAG 4 960 8 32.5 241.5 650 
Axis-P 1250-6D/5.5-8/35/AL Axis-P 1250-6D/5.5-8/35/PAG 5.5 960 8 35 245.5 650 
1250 6 3~400
Axis-P 1250-6D/5.5-8/37.5/AL Axis-P 1250-6D/5.5-8/37.5/PAG 5.5 960 8 37.5 245.5 650 
Axis-P 1250-6D/7.5-8/40/AL Axis-P 1250-6D/7.5-8/40/PAG 7.5 960 8 40 273.8 800 
Axis-P 1250-6D/9.2-8/45/AL Axis-P 1250-6D/9.2-8/45/PAG 9.2 960 8 45 291.5 800 
Axis-P 1250-6D/11-8/50/AL Axis-P 1250-6D/11-8/50/PAG 11 960 8 50 299.3 800 

Aerodynamic characteristics
Air flow [CFM]
10000 15000 20000 25000 30000 35000 40000 45000 50000 L
300 1.2
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 1250 Ø15
Number of poles: 6 1.1 20 holes

92 92 93 94
250 95 1.0
Pd

1400
90 95
92 0.9
89 92 96
93
200 95 0.8
86
90 96

92
0.7
91 93

1320
89 94
12
150 0.6 50
AXIS-P 1250

86 96
89
92
91 0.5
89
87 94
Axis-P 1250-6
100 96 0.4
83 92
87
0.3
85 90
91
88 93 L
81 95
50 0.2
dBA Ø15
83
84 20 holes
77 88 90 95
0.1
86 92
1 2 3 4 5 6 7 8
1400

10000 20000 30000 40000 50000 60000 70000 80000 90000


Air flow [m3/h]

4 6 8 10 12 14 16 18 20 22 24
Air flow [m3/h]
12
Power [kW]

10 8
1320

12
8 50
7
6
6 13
30
4 4 5
2 3
2 1
0
10000 20000 30000 40000 50000 60000 70000 80000 90000 Axis-P 1250-6...-K
Air flow [m3/h]

26 blaubergventilatoren.de
blaubergventilatoren.de

Technical data
AXIS-P 1250-4
Voltage Fan model with Fans model with fiberglass Blade setting Weight Lenght L Curve
Size Number [V / aluminum blades impeller reinforced polyamide blades Installed motor RPM [min⁻¹] Number of number
of poles 50 Hz] (AL) impeller (PAG) power Ny [kW] blades angle [°] [kg] [mm] on graph

Axis-P 1250-4D/7.5-8/25/AL Axis-P 1250-4D/7.5-8/25/PAG 7.5 1440 8 25 241 650 


Axis-P 1250-4D/11-8/30/AL Axis-P 1250-4D/11-8/30/PAG 11 1440 8 30 275.3 800 
Axis-P 1250-4D/15-8/32.5/AL Axis-P 1250-4D/15-8/32.5/PAG 15 1440 8 32.5 294.4 800 
1250 4 3~400 Axis-P 1250-4D/15-8/35/AL Axis-P 1250-4D/15-8/35/PAG 15 1440 8 35 294.4 800 
Axis-P 1250-4D/18.5-8/37.5/AL Axis-P 1250-4D/18.5-8/37.5/PAG 18.5 1440 8 37.5 339.9 900 
Axis-P 1250-4D/22-8/40/AL Axis-P 1250-4D/22-8/40/PAG 22 1440 8 40 353.2 900 
Axis-P 1250-4D/30-8/45/AL Axis-P 1250-4D/30-8/45/PAG 30 1440 8 45 416.2 900 

Aerodynamic characteristics
Air flow [CFM]
20000 30000 40000 50000 60000 70000 L
700 2.8
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 1250 Ø15
Number of poles: 4 20 holes

600 2.4
101 102
100 103

1400
99
500 98 102 2.0
101
100 103

95 98
Pd
400 1.6
102

1320
97 101
100 103 12
50

AXIS-P 1250
98
300 101 1.2
94 96
100
99
103 Axis-P 1250-4
97
100
200 0.8
93 94
98

96 102 L
90 94 99
100 92 0.4 Ø15
dBA 20 holes
86 90 93 95 96 98 101
1 2 3 4 5 6 7
1400

20000 40000 60000 80000 100000 120000


Air flow [m3/h]

6 8 10 12 14 16 18 20 22 24 26 28 30 32
Air flow [m3/h]
30
Power [kW]

25 7
1320

12
20 50
6
15 5
13
3 4 30
10 2
5 1
0
20000 40000 60000 80000 100000 120000 Axis-P 1250-4...-K
Air flow [m3/h]

AXIS-P | AXIS-FP 27
AXIS-P | AXIS-FP

Axis-FP
Axial smoke extraction fan

Use
The fans are used for extraction of smoke in case Air flow:
of fire and removal of hot air outside. The fans are up to 108 000 m³/h
also used for general ventilation systems.
The fans are rated for permanent operation at
ambient air temperatures from -60 °C up to +50 °C Fire
(depends on climatic category, see the Designation resistance rating:
key). The fans are able to operate 2 hours at the 200 °C/2 hours
temperatures +200 °C, +300 °C and +400 °C. 300 °C/2 hours
400 °C/2 hours

Design Impeller
The fan consists of the casing, impeller and motor. The metal casing with Depending on the size and the required air capacity the fans are
rolled flanges helps achieve outstanding rigidity and minimum clearan- equipped with impellers with 6 or 8 blades angled from 20° to 50° with
ces between the casing and the blades. There is an inspection hatch in the from 2.5 up to 5° stepping to ensure precise matching of fans with the
casing for easy maintenance. operating point.
All the casing components are powder coated for improved protection The specially designed impeller blades ensure high efficiency of the fan
against the environmental effects. while keeping noise well under control.
The weight of the fans may differ from the one stated in the catalogue and The impellers are dynamically balanced. Low weight and low moment of
depends on the components used (motor, terminal box, etc.). the impeller inertia help reduce the fan start-up time.
The fan blades are made of cast aluminium.
Motor
AXIS-FP

The fans are equipped with three-phase (400 V/50 Hz) motors.
Mounting
Depending on the model, the fans have single- or double-speed The fans can be mounted on any flat surface or directly into
modifications. a ventilation duct. The units are suitable for both horizontal and vertical
The single-speed models are equipped with 2-, 4- or 6-pole motors. configurations.
The double-speed models are equipped with 2/4- or 4/8-pole motors. Installation in the air duct requires flanges to attach the fan to the
ductwork.
To attach the fan to the floor, a wall or the ceiling use the O-AF carriers
(not included as standard, should be purchased separately).
The fans are suitable for installation on rooftops.

Accessories
Carrier Flange Flexible joint Hood Roof adapter Mounting curb Inlet cone

O-AF F-AF EVAF-AF...400/2 Z-AF PK-AF SM-AF VK-AF

28 blaubergventilatoren.de
blaubergventilatoren.de

Designation key
Casing Motor Impeller Modification

AXIS-FP 630 K - 2 D/ 5.5 - 8 /35/AL - U 1 - 300/2


Axis-FP: Axial smoke extraction fan

Standard size (dict diameter) [mm]

Modification:
_: standard casing;
K: shortened casing

Number of the motor poles

Motor phase:
E: single-phase;
D: three-phase

Motor power [kW]

Number of the impeller blades [items]

Blade setting angle [ °]

Blade material: AL: Aluminium

Climatic category:
U: moderate climate (-40 ... +40 °C)
HL: cold climate (-60 ... +40 °C)
UHL: moderate and cold climate (-60 ... +40 °C)
T: tropical climate (-10 ... +50 °C)
M: maritime moderately cold climate (-40 ... +40 °C)
O: general climatic modification (except maritime climate) (-60 ... +50 °C)
OM: general maritime climatic modification (-40 ... +40 °C)
V: universal climatic modification (-60 ... +50 °C)

Placement category:
1: outdoors
2: under a shed or indoors with the same conditions as outdoors except solar radiation and precipitation

AXIS-FP
3: in closed rooms without artificial climate control
4: in closed rooms with artificial climate control (ventilation, heating)
5: in rooms with high levels of humidity, without artificial climate control

Fire resistance rating:


200/2: 200 °C, 2 hours
300/2: 300 °C, 2 hours
400/2: 400 °C, 2 hours

Accessories
Backdraft damper Silencer Protective mesh Anti-vibration mount

VRV-AF...400/2 SD SDV SZ-AF SIF-AF

AXIS-P | AXIS-FP 29
AXIS-P | AXIS-FP

Technical data
AXIS-FP 400-4
Voltage Number of Blade setting Weight
Size Number
[V / Model
Installed motor RPM [min⁻¹] Lenght L [mm] Curve number
of poles power Ny [kW] blades angle [°] [kg] on graph
50 Hz]

Axis-FP 400-4D/0.55-6/30/AL 0.55 1440 6 30 26.5 400 


Axis-FP 400-4D/0.55-6/35/AL 0.55 1440 6 35 26.5 400 
400 4 3~400 Axis-FP 400-4D/0.55-6/40/AL 0.55 1440 6 40 26.5 400 
Axis-FP 400-4D/0.55-6/45/AL 0.55 1440 6 45 26.5 400 
Axis-FP 400-4D/0.55-8/45/AL 0.55 1440 8 45 27 400 

Aerodynamic characteristics
Air flow [CFM]
1000 1500 2000 2500 3000 3500
120
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 400 L
110 Number of poles: 4
Ø8
100 0.4 12 holes
77 80

75 77 78
90
Pd

490
76 80
80
0.3
75 77 79
70
76 78
60
74 76

450
79 40
50 0.2 0
75 77
AXIS-FP 400

40 52
72 76 5
74 78
30
77
75 0.1
70 73
20
Axis-FP 400-4

10 dBA
69 72 74 76 77
1 2 3 4 5
1000 2000 3000 4000 5000 6000
Air flow [m3/h]

0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 1.3 1.4 1.5 1.6
Air flow [m3/h]
0.4
Power [kW]

0.3
5
0.2 4
3
0.1 2
1
0
1000 2000 3000 4000 5000 6000
Air flow [m3/h]

30 blaubergventilatoren.de
blaubergventilatoren.de

Technical data
AXIS-FP 400-2
Voltage Number of Blade setting Weight
Size Number
[V / Model
Installed motor RPM [min⁻¹] Lenght L [mm] Curve number
of poles power Ny [kW] blades angle [°] [kg] on graph
50 Hz]

Axis-FP 400-2D/0.75-6/30/AL 0.75 2880 6 30 26.5 400 


Axis-FP 400-2D/1.1-6/35/AL 1.1 2880 6 35 27.5 400 
400 2 3~400 Axis-FP 400-2D/1.5-6/40/AL 1.5 2880 6 40 32.5 400 
Axis-FP 400-2D/2.2-6/45/AL 2.2 2880 6 45 34.5 400 
Axis-FP 400-2D/2.2-8/45/AL 2.2 2880 8 45 35 400 
Axis-FP 400-2/4D/0.8/0.2-6/30/AL 0.8/0.2 2880/1440 6 30 26.5 400 *
Axis-FP 400-2/4D/1.1/0.25-6/35/AL 1.1/0.25 2880/1440 6 35 27.5 400 *
400 2/4 3~400 Axis-FP 400-2/4D/1.5/0.37-6/40/AL 1.5/0.37 2880/1440 6 40 32.5 400 *
Axis-FP 400-2/4D/2.2/0.5-6/45/AL 2.2/0.5 2880/1440 6 45 34.5 400 *
Axis-FP 400-2/4D/2.2/0.5-8/45/AL 2.2/0.5 2880/1440 8 45 35 400 *
* maximum speed graph

Aerodynamic characteristics
Air flow [CFM]
2000 3000 4000 5000 6000 7000
500 2.0
Static pressure [Ps (Pa)]

Standard size: 400 Static pressure [Ps (in WG)]


L
450 Number of poles: 2
1.8
Ø8
96 12 holes
400 90 1.6
92
89 91
95 Pd 490
350 1.4
92

AXIS-FP 400
90
91
300 1.2
88 95
89 92
250 90 1

450
94 40
87 0
200 91 0.8
89
52
90 5
150 0.6
86 88
93
89 91
100 0.4
87
84 Axis-FP 400-2

50 dBA 0.2
86 87 90 93
82
1 2 3 4 5
2000 4000 6000 8000 10000 12000
Air flow [m3/h]

0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2
Air flow [m3/h]
2.5
Power [kW]

2.0 5
4
1.5

1.0 3
2
1
0.5

0
2000 4000 6000 8000 10000 12000
Air flow [m3/h]

AXIS-P | AXIS-FP 31
AXIS-P | AXIS-FP

Technical data
AXIS-FP 450-4
Voltage Number of Blade setting Weight
Size Number
[V / Model
Installed motor RPM [min⁻¹] Lenght L [mm] Curve number
of poles power Ny [kW] blades angle [°] [kg] on graph
50 Hz]

Axis-FP 450-4D/0.55-6/30/AL 0.55 1440 6 30 36.1 400 


Axis-FP 450-4D/0.55-6/35/AL 0.55 1440 6 35 36.1 400 
450 4 3~400 Axis-FP 450-4D/0.55-6/40/AL 0.55 1440 6 40 36.1 400 
Axis-FP 450-4D/0.55-6/45/AL 0.55 1440 6 45 36.1 400 
Axis-FP 450-4D/0.55-8/45/AL 0.55 1440 8 45 36.6 400 

Aerodynamic characteristics
Air flow [CFM]
1500 2000 2500 3000 3500 4000 4500
0.6
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


140 Standard size: 450 L
Number of poles: 4
Ø8
12 holes
0.5
120
82
78
79 80

540
77 Pd
100 0.4
82
78
76 80
80
79
0.3

500
81 45
75 77 0
60
80
AXIS-FP 450

58
0.2 0
74 78
40
76 80
79
72 77
0.1 Axis-FP 400-4
75
20
79
70 74 76
78 dBA
1 2 3 4 5
2000 3000 4000 5000 6000 7000 8000
Air flow [m3/h]

0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2


Air flow [m3/h]
0.5
Power [kW]

0.4
5
0.3 4

0.2 3
2
0.1 1

0
2000 3000 4000 5000 6000 7000 8000
Air flow [m3/h]

32 blaubergventilatoren.de
blaubergventilatoren.de

Technical data
AXIS-FP 450-2
Voltage Number of Blade setting Weight
Size Number
[V / Model
Installed motor RPM [min⁻¹] Lenght L [mm] Curve number
of poles power Ny [kW] blades angle [°] [kg] on graph
50 Hz]

Axis-FP 450-2D/1.1-6/30/AL 1.1 2880 6 30 37.1 400 


Axis-FP 450-2D/1.5-6/35/AL 1.5 2880 6 35 42.1 400 
450 2 3~400 Axis-FP 450-2D/2.2-6/40/AL 2.2 2880 6 40 44.1 400 
Axis-FP 450-2D/3-8/40/AL 3 2880 8 40 53.6 500 
Axis-FP 450-2D/4-8/45/AL 4 2880 8 45 64.6 500 
Axis-FP 450-2/4D/1.1/0.25-6/30/AL 1.1/0.25 2880/1440 6 30 37.1 400 *
Axis-FP 450-2/4D/1.5/0.37-6/35/AL 1.5/0.37 2880/1440 6 35 42.1 400 *
450 2/4 3~400 Axis-FP 450-2/4D/2.2/0.5-6/40/AL 2.2/0.5 2880/1440 6 40 44.1 400 *
Axis-FP 450-2/4D/3.1/0.8-8/40/AL 3.1/0.8 2880/1440 8 40 55.6 500 *
Axis-FP 450-2/4D/4.4/1.1-8/45/AL 4.4/1.1 2880/1440 8 45 65.6 500 *
* maximum speed graph

Aerodynamic characteristics
Air flow [CFM]
3000 4000 5000 6000 7000 8000 9000
600 2.4
Static pressure [Ps (Pa)]

Standard size: 450 Static pressure [Ps (in WG)] L


Number of poles: 2 2.2
Ø8
500 12 holes
2.0
97 98
93 1.8
92
90 Pd 540
400 1.6
97

AXIS-FP 450
93 1.4
90 98
92
97
300 1.2

500
92 97 45
89 0
1
91 96
58
200 92 0.8 0
88 96
90
0.6
95

86 91
100 0.4 Axis-FP 450-2
89

96 dBA
0.2
84 88 90 94
1 2 3 4 5
4000 6000 8000 10000 12000 14000 16000
Air flow [m3/h]

1.2 1.6 2 2.4 2.8 3.2 3.6 4 4.4


Air flow [m3/h]
4.0
Power [kW]

3.0 5
4
2.0
3
2
1.0 1

0
4000 6000 8000 10000 12000 14000 16000
Air flow [m3/h]

AXIS-P | AXIS-FP 33
AXIS-P | AXIS-FP

Technical data
AXIS-FP 500-4
Voltage Number of Blade setting Weight
Size Number
[V / Model
Installed motor RPM [min⁻¹] Lenght L [mm] Curve number
of poles power Ny [kW] blades angle [°] [kg] on graph
50 Hz]

Axis-FP 500-4D/0.55-6/30/AL 0.55 1440 6 30 47.7 400 


Axis-FP 500-4D/0.55-6/35/AL 0.55 1440 6 35 47.7 400 
500 4 3~400 Axis-FP 500-4D/0.55-6/40/AL 0.55 1440 6 40 47.7 400 
Axis-FP 500-4D/0.55-6/45/AL 0.55 1440 6 45 47.7 400 
Axis-FP 500-4D/0.75-8/45/AL 0.75 1440 8 45 49.3 400 

Aerodynamic characteristics
Air flow [CFM]
1500 2000 2500 3000 3500 4000 4500 5000 5500
0.6
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


140 Standard size: 500 L
Number of poles: 4
84
Ø12
82 12 holes
80 81 Pd 0.5
120
78
84

600
82
100 0.4
81
80
83
77
80
82
0.3
80

560
79
50
83 0
60
75
AXIS-FP 500

57
81 0.2 5
79
40 77
82
73 81
dBA 0.1 Axis-FP 500-4
20
78
75
71
80 81
1 2 3 4 5
2000 3000 4000 5000 6000 7000 8000 9000 10000
Air flow [m3/h]

0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6


Air flow [m3/h]
0.8
Power [kW]

0.6
5
0.4
4
3
2
0.2
1

0
2000 3000 4000 5000 6000 7000 8000 9000 10000
Air flow [m3/h]

34 blaubergventilatoren.de
blaubergventilatoren.de

Technical data
AXIS-FP 500-2
Voltage Number of Blade setting Weight
Size Number [V / Model Installed motor RPM [min⁻¹] blades Lenght L [mm] Curve number
on graph
of poles 50 Hz] power Ny [kW] angle [°] [kg]

Axis-FP 500-2D/1.5-6/30/AL 1.5 2880 6 30 53.7 400 


Axis-FP 500-2D/2.2-6/35/AL 2.2 2880 6 35 55.7 400 
500 2 3~400 Axis-FP 500-2D/3-8/35/AL 3 2880 8 35 65.3 400 
Axis-FP 500-2D/4-8/40/AL 4 2880 8 40 76.3 500 
Axis-FP 500-2D/5.5-8/45/AL 5.5 2880 8 45 95.3 500 
Axis-FP 500-2/4D/1.5/0.37-6/30/AL 1.5/0.37 2880/1440 6 30 53.7 400 *
Axis-FP 500-2/4D/2.2/0.5-6/35/AL 2.2/0.5 2880/1440 6 35 55.7 400 *
500 2/4 3~400 Axis-FP 500-2/4D/3.1/0.8-8/35/AL 3.1/0.8 2880/1440 6 40 67.3 500 *
Axis-FP 500-2/4D/4.4/1.1-8/40/AL 4.4/1.1 2880/1440 8 40 77.3 500 *
Axis-FP 500-2/4D/6.0/1.5-8/45/AL 6/1.5 2880/1440 8 45 92.3 550 *
* maximum speed graph

Aerodynamic characteristics
Air flow [CFM]
3000 4000 5000 6000 7000 8000 9000 10000 11000
700 2.8
Static pressure [Ps (Pa)]

Standard size: 500 Static pressure [Ps (in WG)] L


Number of poles: 2
98 99 Ø12
600 2.4 12 holes

100
99
500 2.0
94 Pd 600
92 98

AXIS-FP 500
400 1.6
94 98 100
91
97

560
300 1.2 50
93 99 0

97 62
90 0
200 95 0.8
99
92
96
88 dBA
100 0.4 Axis-FP 500-2
98
93 95
90
86
1 2 3 4 5
4000 6000 8000 10000 12000 14000 16000 18000 20000
Air flow [m3/h]

1.2 1.6 2 2.4 2.8 3.2 3.8 4 4.4 4.8 5.2


Air flow [m3/h]
6.0
Power [kW]

5.0
5
4.0

3.0 4
3
2.0 2
1
1.0

0
4000 6000 8000 10000 12000 14000 16000 18000 20000
Air flow [m3/h]

AXIS-P | AXIS-FP 35
AXIS-P | AXIS-FP

Technical data
AXIS-FP 560-4
Voltage Number of Blade setting Weight
Size Number
[V / Model
Installed motor RPM [min⁻¹] Lenght L [mm] Curve number
of poles power Ny [kW] blades angle [°] [kg] on graph
50 Hz]

Axis-FP 560-4D/0.55-6/30/AL 0.55 1440 6 30 64.8 400 


Axis-FP 560-4D/0.55-6/35/AL 0.55 1440 6 35 64.8 400 
560 4 3~400 Axis-FP 560-4D/0.55-6/40/AL 0.55 1440 6 40 64.8 400 
Axis-FP 560-4D/0.75-6/45/AL 0.75 1440 6 45 65.8 400 
Axis-FP 560-4D/1.1-8/45/AL 1.1 1440 8 45 72.4 400 

Aerodynamic characteristics
Air flow [CFM]
2000 3000 4000 5000 6000 7000
200 0.8
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 560 L
180 Number of poles: 4
0.7 Ø12
12 holes
160
85
84 0.6
82

660
140
80
81 Pd
0.5
120 82 85

81 84
100 0.4
79

620
82 56
85 0
80
80 84 0.3
AXIS-FP 560

68
0
77
60
81
0.2
79 84
83
40
80 Axis-FP 560-4
75
77
dBA 0.1
20
73 79 82 83
1 2 3 4 5
3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000
Air flow [m3/h]

1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4
Air flow [m3/h]
1.0
Power [kW]

0.75
5
4
0.5
3
2
0.25 1

0
3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000
Air flow [m3/h]

36 blaubergventilatoren.de
blaubergventilatoren.de

Technical data
AXIS-FP 560-2
Voltage Number of Blade setting Weight
Size Number [V / Model Installed motor RPM [min⁻¹] blades Lenght L [mm] Curve number
on graph
of poles 50 Hz] power Ny [kW] angle [°] [kg]

Axis-FP 560-2D/2.2-6/30/AL 2.2 2880 6 30 72.8 400 


Axis-FP 560-2D/3-8/30/AL 3 2880 8 30 82.4 400 
560 2 3~400 Axis-FP 560-2D/4-8/35/AL 4 2880 8 35 93.4 500 
Axis-FP 560-2D/5.5-8/40/AL 5.5 2880 8 40 112.4 500 
Axis-FP 560-2D/7.5-8/45/AL 7.5 2880 8 45 118.4 500 
Axis-FP 560-2/4D/2.2/0.5-6/30/AL 2.2/0.5 2880/1440 6 30 72.8 400 *
Axis-FP 560-2/4D/3.1/0.8-8/30/AL 3.1/0.8 2880/1440 8 30 84.4 500 *
560 2/4 3~400 Axis-FP 560-2/4D/4.4/1.1-8/35/AL 4.4/1.1 2880/1440 8 35 94.4 500 *
Axis-FP 560-2/4D/6/1.5-8/40/AL 6/1.5 2880/1440 8 40 109.4 550 *
Axis-FP 560-2/4D/8/2-8/45/AL 8/2 2880/1440 8 45 118.4 550 *
* maximum speed graph

Aerodynamic characteristics
Air flow [CFM]
4000 6000 8000 10000 12000 14000
800 3.2
Static pressure [Ps (Pa)]

Standard size: 560 Static pressure [Ps (in WG)] L


Number of poles: 2
700 100 2.8 Ø12
99 12 holes
97
101
600 2.4
99
660
100 102
97 Pd

AXIS-FP 560
500 94 2.0

99
102
400 1.6
100
96

620
93
56
0
97
300 1.2
99
94 68
92 101 0

200 0.8
90 92 96 98
100
Axis-FP 560-2
100 dBA 0.4
88 90
94 97 99

1 2 3 4 5
6000 8000 10000 12000 14000 16000 18000 20000 22000 24000 26000
Air flow [m3/h]

2 2.4 2.8 3.2 3.6 4 4.4 4.8 5.2 5.6 6 6.4 6.8
Air flow [m3/h]
8.0
Power [kW]

6.0 5

4.0 4
3
2
2.0 1

0
6000 8000 10000 12000 14000 16000 18000 20000 22000 24000 26000
Air flow [m3/h]

AXIS-P | AXIS-FP 37
AXIS-P | AXIS-FP

Technical data
AXIS-FP 630-4
Voltage Number of Blade setting Weight
Size Number
[V / Model
Installed motor RPM [min⁻¹] Lenght L [mm] Curve number
of poles power Ny [kW] blades angle [°] [kg] on graph
50 Hz]

Axis-FP 630-4D/0.55-8/30/AL 0.55 1440 8 30 71 400 


Axis-FP 630-4D/0.75-8/35/AL 0.75 1440 8 35 72 400 
Axis-FP 630-4D/1.1-8/40/AL 1.1 1440 8 40 78 400 
Axis-FP 630-4D/1.5-6/32.5/AL 1.5 1440 6 32.5 82.1 400 
630 4 3~400
Axis-FP 630-4D/1.5-8/45/AL 1.5 1440 8 45 81 400 
Axis-FP 630-4D/1.5-6/37.5/AL 1.5 1440 6 37.5 82.1 400 
Axis-FP 630-4D/2.2-6/40/AL 2.2 1440 6 40 88.1 400 
Axis-FP 630-4D/2.2-6/45/AL 2.2 1440 6 45 88.1 400 

Aerodynamic characteristics
Air flow [CFM]
3000 4000 5000 6000 7000 8000 9000 10000 11000 12000
250 1
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 630 L
Number of poles: 4
0.9
Ø12
88 12 holes
200
Pd
0.8
85 89 90
85
87

730
0.7

89
83 87
150 85 0.6
84
AXIS-FP 630

90 0.5

690
82 88
86 87
63
84 0
100 0.4
83
75
80 0
89 0.3
87 87
81 83 85 86

50 0.2
77
Axis-FP 630-4
dBA
0.1
75 79 81 84 85 86 86 88

1 2 3 4 5 6 7 8
4000 6000 8000 10000 12000 14000 16000 18000 20000
Air flow [m3/h]

1.2 1.6 2 2.4 2.8 3.2 3.6 4 4.4 4.8 5.2 5.6
Air flow [m3/h]
2.5
Power [kW]

2.0 8

1.5 7
6
1.0 5
4
3
0.5 2
1
0
4000 6000 8000 10000 12000 14000 16000 18000 20000
Air flow [m3/h]

38 blaubergventilatoren.de
blaubergventilatoren.de

Technical data
AXIS-FP 630-2
Voltage Number of Blade setting Weight
Size Number
[V / Model
Installed motor RPM [min⁻¹] Lenght L [mm] Curve number
of poles power Ny [kW] blades angle [°] [kg] on graph
50 Hz]

Axis-FP 630-2D/4-8/30/AL 4 2880 8 30 99 500 


Axis-FP 630-2D/5.5-8/35/AL 5.5 2880 8 35 118 500 
Axis-FP 630-2D/7.5-8/40/AL 7.5 2880 8 40 124 500 
Axis-FP 630-2D/9.2-6/30/AL 9.2 2880 6 30 143.1 600 
630 2 3~400 Axis-FP 630-2D/11-6/32.5/AL 11 2880 6 32.5 162.1 600 
Axis-FP 630-2D/11-6/35/AL 11 2880 6 35 162.1 600 
Axis-FP 630-2D/15-6/37.5/AL 15 2880 6 37.5 169.1 700 
Axis-FP 630-2D/15-6/40/AL 15 2880 6 40 169.1 700 
Axis-FP 630-2D/18.5-6/45/AL 18.5 2880 6 45 184.1 700 

Aerodynamic characteristics
Air flow [CFM]
5000 10000 15000 20000 25000
1000 4
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 630 L
900 Number of poles: 2
103 3.6
103 Ø12
12 holes
103
800 3.2
Pd
104
700

730
102 2.8
101
99 102
102
600 2.4
105
102

AXIS-FP 630
100 102
98
500 2.0
101

690
63
104 0
400 101 1.6
99 103
96 75
0
300 101 102
1.2
100 104
100
200 97 102 0.8
93
100 Axis-FP 630-2
98
100 103 0.4
98
91 95 99 100 101 dBA
4
1 2 3 5 6 7 8 9
5000 10000 15000 20000 25000 30000 35000 40000 45000
Air flow [m3/h]

2 3 4 5 6 7 8 9 10 11 12
Air flow [m3/h]
18.0
Power [kW]

9
15.0

12.0 8
7
9.0 6
4 5
6.0 3
2
3.0 1
0
5000 10000 15000 20000 25000 30000 35000 40000 45000
Air flow [m3/h]

AXIS-P | AXIS-FP 39
AXIS-P | AXIS-FP

Technical data
AXIS-FP 630-4
Voltage Number of Blade setting Weight
Size Number
[V / Model
Installed motor RPM [min⁻¹] Lenght L [mm] Curve number
of poles power Ny [kW] blades angle [°] [kg] on graph
50 Hz]

Axis-FP 630-4/8D/0.6/0.15-8/30/AL 0.6/0.15 1440/720 8 30 72 400 *


Axis-FP 630-4/8D/0.8/0.2-8/35/AL 0.8/0.2 1440/720 8 35 72 400 *
Axis-FP 630-4/8D/1.2/0.3-8/40/AL 1.2/0.3 1440/720 8 40 77 400 *
Axis-FP 630-4/8D/1.2/0.3-6/32.5/AL 1.2/0.3 1440/720 6 32.5 78.1 400 *
630 4/8 3~400
Axis-FP 630-4/8D/1.6/0.4-8/45/AL 1.6/0.4 1440/720 8 45 80 400 *
Axis-FP 630-4/8D/1.6/0.4-6/37.5/AL 1.6/0.4 1440/720 6 37.5 81.1 400 *
Axis-FP 630-4/8D/2.2/0.55-6/40/AL 2.2/0.55 1440/720 6 40 88.1 500 *
Axis-FP 630-4/8D/2.2/0.55-6/45/AL 2.2/0.55 1440/720 6 45 88.1 500 *
* maximum speed graph

Aerodynamic characteristics
Air flow [CFM]
3000 4000 5000 6000 7000 8000 9000 10000 11000 12000
250 1
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 630 L
Number of poles: 4/8
0.9
Ø12
88 12 holes
200
Pd
0.8
85 89 90
85
87
0.7

89 730
83 87
150 0.6
AXIS-FP 630

84 85

90 0.5

690
82 88
86 87 63
84 0
100 0.4
83
75
80 0
89 0.3
87 87
81 83 85 86

50 0.2
77
Axis-FP 630-4
dBA
0.1
75 79 81 84 85 86 86 88

1 2 3 4 5 6 7 8
4000 6000 8000 10000 12000 14000 16000 18000 20000
Air flow [m3/h]

1.2 1.6 2 2.4 2.8 3.2 3.6 4 4.4 4.8 5.2 5.6
Air flow [m3/h]
2.5
Power [kW]

2.0 8

1.5 7
6
1.0 5
4
3
0.5 2
1
0
4000 6000 8000 10000 12000 14000 16000 18000 20000
Air flow [m3/h]

40 blaubergventilatoren.de
blaubergventilatoren.de

Technical data
AXIS-FP 630-2
Voltage Number of Blade setting Weight
Size Number
[V / Model
Installed motor RPM [min⁻¹] Lenght L [mm] Curve number
of poles power Ny [kW] blades angle [°] [kg] on graph
50 Hz]

Axis-FP 630-2/4D/4.4/1.1-8/30/AL 4.4/1.1 2880/1440 8 30 100 500 *


Axis-FP 630-2/4D/6/1.5-8/35/AL 6/1.5 2880/1440 8 35 115 600 *
Axis-FP 630-2/4D/8/2-8/40/AL 8/2 2880/1440 8 40 124 600 *
Axis-FP 630-2/4D/12/3-6/30/AL 12/3 2880/1440 6 30 176.1 700 *
630 2/4 3~400 Axis-FP 630-2/4D/12/3-6/32.5/AL 12/3 2880/1440 6 32.5 176.1 700 *
Axis-FP 630-2/4D/12/3-6/35/AL 12/3 2880/1440 6 35 176.1 700 *
Axis-FP 630-2/4D/12/3-6/37.5/AL 12/3 2880/1440 6 37.5 176.1 700 *
Axis-FP 630-2/4D/16/4-6/40/AL 16/4 2880/1440 6 40 193.1 700 *
Axis-FP 630-2/4D/20/5.5-6/45/AL 20/5.5 2880/1440 6 45 218.1 700 *
* maximum speed graph

Aerodynamic characteristics
Air flow [CFM]
5000 10000 15000 20000 25000
1000 4
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 630 L
900 Number of poles: 2/4
103 3.6
103 Ø12
12 holes
103
800 3.2
Pd
104

730
700 102 2.8
101
99 102
102
600 2.4

AXIS-FP 630
105
102
100 102
98
500 2.0
101

690
63
104
0
400 101 1.6
99 103
75
96 0
300 101 102
1.2
100 104
100
200 97 102 0.8
93
100 Axis-FP 630-2
98
100 103 0.4
98
91 95 4 99 100 101 dBA
1 2 3 5 6 7 8 9
5000 10000 15000 20000 25000 30000 35000 40000 45000
Air flow [m3/h]

2 3 4 5 6 7 8 9 10 11 12
Air flow [m3/h]
18.0
Power [kW]

9
15.0

12.0 8
7
9.0 6
4 5
6.0 3
2
3.0 1
0
5000 10000 15000 20000 25000 30000 35000 40000 45000
Air flow [m3/h]

AXIS-P | AXIS-FP 41
AXIS-P | AXIS-FP

Technical data
AXIS-FP 710-4
Voltage Number of Blade setting Weight
Size Number
[V / Model
Installed motor RPM [min⁻¹] Lenght L [mm] Curve number
of poles power Ny [kW] blades angle [°] [kg] on graph
50 Hz]

Axis-FP 710-4D/0.75-6/20/AL 0.75 1440 6 20 99.3 450 


Axis-FP 710-4D/1.1-6/25/AL 1.1 1440 6 25 105.3 450 
Axis-FP 710-4D/1.5-6/30/AL 1.5 1440 6 30 108.3 450 
Axis-FP 710-4D/2.2-6/32.5/AL 2.2 1440 6 32.5 114.3 450 
710 4 3~400
Axis-FP 710-4D/2.2-6/35/AL 2.2 1440 6 35 114.3 450 
Axis-FP 710-4D/2.2-6/37.5/AL 2.2 1440 6 37.5 114.3 450 
Axis-FP 710-4D/3-6/40/AL 3 1440 6 40 117.3 560 
Axis-FP 710-4D/4-6/45/AL 4 1440 6 45 131.3 560 

Aerodynamic characteristics
Air flow [CFM]
4000 6000 8000 10000 12000 14000 16000
300 1.2
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 710 L
270 Number of poles: 4 1.1
89 Ø12
87
16 holes
91 Pd 1.0
240
91
90
85 90 0.9
89

810
210
87 92 0.8
91
180
84 90 0.7
89
88
AXIS-FP 710

150 0.6
86 91 92

770
90
89 71
0.5 0
120
82 88
87
84
84 92 0.4 5
90 90
89
88
87 0.3
79 86
60
82
0.2 Axis-FP 710-4
91 dBA
30
80 84 85 87 88 89 0.1
76
1 2 3 4 5 6 7 8
5000 10000 15000 20000 25000 30000
Air flow [m3/h]

2 3 4 5 6 7 8
Air flow [m3/h]
4.0
Power [kW]

3.0 8
7
2.0 6
5
4
1.0 3
1 2
0
5000 10000 15000 20000 25000 30000
Air flow [m3/h]

42 blaubergventilatoren.de
blaubergventilatoren.de

Technical data
AXIS-FP 710-2

Voltage Number of Blade setting Weight


Size Number [V / Model Installed motor RPM [min⁻¹] Lenght L [mm] Curve number
of poles power Ny [kW] blades angle [°] [kg] on graph
50 Hz]

Axis-FP 710-2D/7.5-6/20/AL 7.5 2880 6 20 151.3 560 


Axis-FP 710-2D/9.2-6/25/AL 9.2 2880 6 25 169.3 560 
Axis-FP 710-2D/15-6/30/AL 15 2880 6 30 195.3 750 
710 2 3~400 Axis-FP 710-2D/15-6/32.5/AL 15 2880 6 32.5 195.3 750 
Axis-FP 710-2D/18.5-6/35/AL 18.5 2880 6 35 210.3 750 
Axis-FP 710-2D/18.5-6/37.5/AL 18.5 2880 6 37.5 210.3 750 
Axis-FP 710-2D/22-6/40/AL 22 2880 6 40 256.3 750 

Aerodynamic characteristics
Air flow [CFM]
9000 12000 15000 18000 21000 24000 27000 30000
1200 4.8
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 710 L
1100 Number of poles: 2 4.4
105 105 Ø12
103 104
102 16 holes
1000 4.0

900 3.6
106

810
103 104 105 Pd
800 3.2
101
99

700 2.8
106
105
104
600 2.4

AXIS-FP 710
103
102

770
100
97 71
500 2.0 0
106

400 1.6 84
5

103 105 105


98 101 102
300 1.2
95

200 0.8 Axis-FP 710-2

102
103 104 dBA
100 100 0.4
91 95 99
1 2 3 4 5 6 7
10000 20000 30000 40000 50000
Air flow [m3/h]

3 4 5 6 7 8 9 10 11 12 13 14 15
Air flow [m3/h]
25
Power [kW]

20
7
15 6
5
10 4
3
2
5 1
0
10000 20000 30000 40000 50000
Air flow [m3/h]

AXIS-P | AXIS-FP 43
AXIS-P | AXIS-FP

Technical data
AXIS-FP 710-4
Voltage Number of Blade setting Weight
Size Number
[V / Model
Installed motor RPM [min⁻¹] Lenght L [mm] Curve number
of poles power Ny [kW] blades angle [°] [kg] on graph
50 Hz]

Axis-FP 710-4/8D/0.8/0.2-6/20/AL 0.8/0.2 1440/720 6 20 99.3 450 *


Axis-FP 710-4/8D/1.2/0.3-6/25/AL 1.2/0.3 1440/720 6 25 104.3 450 *
Axis-FP 710-4/8D/1.6/0.4-6/30/AL 1.6/0.4 1440/720 6 30 107.3 450 *
Axis-FP 710-4/8D/2.2/0.55-6/32.5/AL 2.2/0.55 1440/720 6 32.5 114.3 560 *
710 4/8 3~400
Axis-FP 710-4/8D/2.2/0.55-6/35/AL 2.2/0.55 1440/720 6 35 114.3 560 *
Axis-FP 710-4/8D/2.2/0.55-6/37.5/AL 2.2/0.55 1440/720 6 37.5 114.3 560 *
Axis-FP 710-4/8D/2.8/0.7-6/40/AL 2.8/0.7 1440/720 6 40 117.3 560 *
Axis-FP 710-4/8D/3.8/1-6/45/AL 3.8/1 1440/720 6 45 127.3 560 *
* maximum speed graph

Aerodynamic characteristics
Air flow [CFM]
4000 6000 8000 10000 12000 14000 16000
300 1.2
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 710 L
270 Number of poles: 4/8 1.1
89 Ø12
87
16 holes
91 Pd 1
240
91
90
85 90 0.9
89

810
210
87 92 0.8
91
180
84 90 0.7
89
88
AXIS-FP 710

150 0.6
86 91 92

770
90
89 71
0.5 0
120
88
87
82 84
84 92 0.4 5
90 90
89
88
87 0.3
79 86
60
82
0.2 Axis-FP 710-4
91 dBA
30
80 84 85 87 88 89 0.1
76
1 2 3 4 5 6 7 8
5000 10000 15000 20000 25000 30000
Air flow [m3/h]

2 3 4 5 6 7 8
Air flow [m3/h]
4.0
Power [kW]

3.0 8
7
2.0 6
5
4
1.0
3
1 2

0
5000 10000 15000 20000 25000 30000
Air flow [m3/h]

44 blaubergventilatoren.de
blaubergventilatoren.de

Technical data
AXIS-FP 710-2
Voltage Number of Blade setting Weight
Size Number
[V / Model
Installed motor RPM [min⁻¹] Lenght L [mm] Curve number
of poles power Ny [kW] blades angle [°] [kg] on graph
50 Hz]

Axis-FP 710-2/4D/6/1.5-6/20/AL 6/1.5 2880/1440 6 20 142.3 560 *


Axis-FP 710-2/4D/12/3-6/25/AL 12/3 2880/1440 6 25 202.3 750 *
Axis-FP 710-2/4D/12/3-6/30/AL 12/3 2880/1440 6 30 202.3 750 *
710 2/4 3~400 Axis-FP 710-2/4D/16/4-6/32.5/AL 16/4 2880/1440 6 32.5 219.3 750 *
Axis-FP 710-2/4D/16/4-6/35/AL 16/4 2880/1440 6 35 219.3 750 *
Axis-FP 710-2/4D/20/5.5-6/37.5/AL 20/5.5 2880/1440 6 37.5 244.3 750 *
Axis-FP 710-2/4D/20/5.5-6/40/AL 20/5.5 2880/1440 6 40 244.3 750 *
* maximum speed graph

Aerodynamic characteristics
Air flow [CFM]
9000 12000 15000 18000 21000 24000 27000 30000
1200 4.8
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 710 L
1100 Number of poles: 2/4 4.4
105 105 Ø12
103 104
102 16 holes
1000 4.0

900 3.6
106

810
103 104 105 Pd
800 3.2
101
99

700 2.8
106
105

AXIS-FP 710
104
600 2.4
103
102

770
100
97 71
500 2.0 0
106

400 1.6 84
5
103 105 105
98 101 102
300 1.2
95

200 0.8
Axis-FP 710-2

102
103 104 dBA
100 100 0.4
91 95 99
1 2 3 4 5 6 7
10000 20000 30000 40000 50000
Air flow [m3/h]

3 4 5 6 7 8 9 10 11 12 13 14 15
Air flow [m3/h]
25
Power [kW]

20
7
15 6
5
10 4
3
2
5 1
0
10000 20000 30000 40000 50000
Air flow [m3/h]

AXIS-P | AXIS-FP 45
AXIS-P | AXIS-FP

Technical data
AXIS-FP 800-6D
Voltage Number of Blade setting Weight
Size Number
[V / Model
Installed motor RPM [min⁻¹] Lenght L [mm] Curve number
of poles power Ny [kW] blades angle [°] [kg] on graph
50 Hz]

Axis-FP 800-6D/0.37-6/20/AL 0.37 960 6 20 109.6 400 


Axis-FP 800-6D/0.55-6/25/AL 0.55 960 6 25 110.6 400 
Axis-FP 800-6D/0.75-6/30/AL 0.75 960 6 30 115.6 400 
Axis-FP 800-6D/0.75-6/32.5/AL 0.75 960 6 32.5 115.6 400 
800 6 3~400
Axis-FP 800-6D/1.1-6/35/AL 1.1 960 6 35 119.6 400 
Axis-FP 800-6D/1.1-6/37.5/AL 1.1 960 6 37.5 119.6 400 
Axis-FP 800-6D/1.1-6/40/AL 1.1 960 6 40 119.6 400 
Axis-FP 800-6D/1.5-6/45/AL 1.5 960 6 45 122.6 500 

Aerodynamic characteristics
Air flow [CFM]
4000 6000 8000 10000 12000 14000
0.6
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


140 Standard size: 800 L
Number of poles: 6
Ø12
85
16 holes
120 Pd 0.5
84
80 82 83

86

900
85
84
100 82
80 0.4
86
84
78 83
80
AXIS-FP 800

82
81 85
79

860
86
0.3 80
77 81 0
60
84
80 83
92
82 5
75 77 80
40 0.2
86
79 84
81
72 75 Axis-FP 800-6
20 78
85
dBA 0.1
69 73 77 78 80 82 83
1 2 3 4 5 6 7 8
6000 9000 12000 15000 18000 21000 24000 27000
Air flow [m3/h]

2 3 4 5 6 7
Air flow [m3/h]
1.5
Power [kW]

8
1.2
7
0.6
6
5
0.6 4
3
0.3 2
1
0
6000 9000 12000 15000 18000 21000 24000 27000
Air flow [m3/h]

46 blaubergventilatoren.de
blaubergventilatoren.de

Technical data
AXIS-FP 800-4
Voltage Number of Blade setting Weight
Size Number
[V / Model
Installed motor RPM [min⁻¹] Lenght L [mm] Curve number
of poles power Ny [kW] blades angle [°] [kg] on graph
50 Hz]

Axis-FP 800-4D/1.1-6/20/AL 1.1 1440 6 20 116.6 400 


Axis-FP 800-4D/1.5-6/25/AL 1.5 1440 6 25 119.6 400 
Axis-FP 800-4D/2.2-6/30/AL 2.2 1440 6 30 125.6 400 
Axis-FP 800-4D/3-6/32.5/AL 3 1440 6 32.5 128.6 500 
800 4 3~400
Axis-FP 800-4D/3-6/35/AL 3 1440 6 35 128.6 500 
Axis-FP 800-4D/4-6/37.5/AL 4 1440 6 37.5 142.6 500 
Axis-FP 800-4D/4-6/40/AL 4 1440 6 40 142.6 500 
Axis-FP 800-4D/5.5-6/45/AL 5.5 1440 6 45 156.6 500 
Axis-FP 800-4/8D/1.2/0.3-6/20/AL 1.2/0.3 1440/720 6 20 115.6 400 *
Axis-FP 800-4/8D/1.6/0.4-6/25/AL 1.6/0.4 1440/720 6 25 118.6 400 *
Axis-FP 800-4/8D/2.2/0.55-6/30/AL 2.2/0.55 1440/720 6 30 125.6 500 *
Axis-FP 800-4/8D/2.8/0.7-6/32.5/AL 2.8/0.7 1440/720 6 32.5 128.6 500 *
800 4/8 3~400
Axis-FP 800-4/8D/2.8/0.7-6/35/AL 2.8/0.7 1440/720 6 35 128.6 500 *
Axis-FP 800-4/8D/3.8/1-6/37.5/AL 3.8/1 1440/720 6 37.5 138.6 500 *
Axis-FP 800-4/8D/3.8/1-6/40/AL 3.8/1 1440/720 6 40 138.6 500 *
Axis-FP 800-4/8D/5/1.3-6/45/AL 5/1.3 1440/720 6 45 163.6 600 *
* maximum speed graph

Aerodynamic characteristics
Air flow [CFM]
4000 6000 8000 10000 12000 14000 16000 18000 20000 22000 24000
1.3
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]

Standard size: 800 L


300 Number of poles: 4 1.2

AXIS-FP 800
Ø12
92
89 93 93 1.1 16 holes
87 91
90 94 Pd
250 1.0
900

0.9
88 95
86 92
93
91
200 0.8
90 92
85
0.7
87
91 95
860

150 0.6
80
89 93
0
0.5
83 88 94
91 92
5
100 92 0.4
85
91
0.3
87 90
80 88
94
83 Axis-FP 800-4
50 0.2
dBA
85 89 90 91
0.1
77 81 87 93
1 2 3 4 5 6 7 8
5000 10000 15000 20000 25000 30000 35000 40000
Air flow [m3/h]

2 3 4 5 6 7 8 9 10 11
Air flow [m3/h]
6.0
Power [kW]

5.0
8
4.0
7
3.0 6
5
2.0 4
3
1.0 2
1
0
5000 10000 15000 20000 25000 30000 35000 40000
Air flow [m3/h]

AXIS-P | AXIS-FP 47
AXIS-P | AXIS-FP

Technical data
AXIS-FP 900-6
Voltage Number of Blade setting Weight
Size Number
[V / Model
Installed motor RPM [min⁻¹] Lenght L [mm] Curve number
of poles power Ny [kW] blades angle [°] [kg] on graph
50 Hz]

Axis-FP 900-6D/0.75-8/20/AL 0.75 960 8 20 120.8 400 


Axis-FP 900-6D/1.1-8/25/AL 1.1 960 8 25 124.8 400 
Axis-FP 900-6D/1.5-8/30/AL 1.5 960 8 30 127.8 500 
Axis-FP 900-6D/1.5-8/32.5/AL 1.5 960 8 32.5 127.8 500 
900 6 3~400
Axis-FP 900-6D/2.2-8/35/AL 2.2 960 8 35 138.8 500 
Axis-FP 900-6D/2.2-8/37.5/AL 2.2 960 8 37.5 138.8 500 
Axis-FP 900-6D/2.2-8/40/AL 2.2 960 8 40 138.8 500 
Axis-FP 900-6D/3-8/45/AL 3 960 8 45 152.8 500 

Aerodynamic characteristics
Air flow [CFM]
4000 6000 8000 10000 12000 14000 16000 18000 20000
250 1.0
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 900 L
Number of poles: 6
0.9
Ø15
16 holes
200 0.8
87 89
85
84 88

1015
90 0.7
86

150 0.6
84 89
88
87 Pd
82 86
86 89
0.5
AXIS-FP 900

970
88 90
83 0
100 0.4
85 86
79 84 88 10
25
82 0.3
87
85
84
82 87
50 0.2
76 79 81 85
83 Axis-FP 900-6
dBA
0.1
75 79 81 82 83 84 86
72
1 2 3 4 5 6 7 8
5000 10000 15000 20000 25000 30000 35000
Air flow [m3/h]

2 3 4 5 6 7 8 9
Air flow [m3/h]
3.0
Power [kW]

8
2.5

2.0
7
6
1.5 5
3 4
1.0
2
0.5 1
0
5000 10000 15000 20000 25000 30000 35000
Air flow [m3/h]

48 blaubergventilatoren.de
blaubergventilatoren.de

Technical data
AXIS-FP 900-4
Voltage Number of Blade setting Weight
Size Number
[V / Model
Installed motor RPM [min⁻¹] Lenght L [mm] Curve number
of poles power Ny [kW] blades angle [°] [kg] on graph
50 Hz]

Axis-FP 900-4D/3-8/20/AL 3 1440 8 20 133.8 400 


Axis-FP 900-4D/4-8/25/AL 4 1440 8 25 147.8 500 
Axis-FP 900-4D/5.5-8/30/AL 5.5 1440 8 30 161.8 500 
Axis-FP 900-4D/5.5-8/32.5/AL 5.5 1440 8 32.5 161.8 500 
900 4 3~400
Axis-FP 900-4D/7.5-8/35/AL 7.5 1440 8 35 169.8 600 
Axis-FP 900-4D/7.5-8/37.5/AL 7.5 1440 8 37.5 169.8 600 
Axis-FP 900-4D/7.5-8/40/AL 7.5 1440 8 40 169.8 600 
Axis-FP 900-4D/11-8/45/AL 11.0 1440 8 45 206.8 600 
Axis-FP 900-4/8D/2.8/0.7-8/20/AL 2.8/0.7 1440/720 8 20 133.8 500 *
Axis-FP 900-4/8D/3.8/1-8/25/AL 3.8/1 1440/720 8 25 143.8 500 *
Axis-FP 900-4/8D/5/1.3-8/30/AL 5/1.3 1440/720 8 30 168.8 600 *
Axis-FP 900-4/8D/7.2/1.8-8/32.5/AL 7.2/1.8 1440/720 8 32.5 180.8 600 *
900 4/8 3~400
Axis-FP 900-4/8D/7.2/1.8-8/35/AL 7.2/1.8 1440/720 8 35 180.8 600 *
Axis-FP 900-4/8D/7.2/1.8-8/37.5/AL 7.2/1.8 1440/720 8 37.5 180.8 600 *
Axis-FP 900-4/8D/11/3-8/40/AL 11/3 1440/720 8 40 219.8 700 *
Axis-FP 900-4/8D/11/3-8/45/AL 11/3 1440/720 8 45 219.8 700 *
* maximum speed graph

Aerodynamic characteristics
Air flow [CFM]
6000 9000 12000 15000 18000 21000 24000 27000 30000
2.2
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]

Standard size: 900 L


Number of poles: 4

AXIS-FP 900
500 2.0
Ø15
16 holes
97
1.8
95 96
94
400 1.6
1015

98
92
97
1.4
95
94 95 96

300 93 Pd
1.2
91 98
970

1.0 90
95 96 0
93 94
91 92
200 97 0.8
89 10
25
95
94
0.6
92 97
88 91
86 90
100 0.4
93 94 Axis-FP 900-4
90
88 dBA
0.2
87 89 91 92 93 95
81 84
1 2 3 4 5 6 7 8
10000 20000 30000 40000 50000
Air flow [m3/h]

3 4 5 6 7 8 9 10 11 12 13 14 15
Air flow [m3/h]
12
Power [kW]

10
8
8
7
6 6
5
4 3 4
2
2 1
0
10000 20000 30000 40000 50000
Air flow [m3/h]

AXIS-P | AXIS-FP 49
AXIS-P | AXIS-FP

Technical data
AXIS-FP 1000-6
Voltage Number of Blade setting Weight
Size Number
[V / Model
Installed motor RPM [min⁻¹] Lenght L [mm] Curve number
of poles power Ny [kW] blades angle [°] [kg] on graph
50 Hz]

Axis-FP 1000-6D/1.5-8/25/AL 1.5 960 8 25 165.5 550 


Axis-FP 1000-6D/2.2-8/30/AL 2.2 960 8 30 176.5 550 
Axis-FP 1000-6D/2.2-8/32.5/AL 2.2 960 8 32.5 176.5 550 
Axis-FP 1000-6D/3-8/35/AL 3 960 8 35 190.5 650 
1000 6 3~400
Axis-FP 1000-6D/3-8/37.5/AL 3 960 8 37.5 190.5 650 
Axis-FP 1000-6D/4-8/40/AL 4 960 8 40 204.5 650 
Axis-FP 1000-6D/5.5-8/45/AL 5.5 960 8 45 211.5 650 
Axis-FP 1000-6D/5.5-8/50/AL 5.5 960 8 50 211.5 650 

Aerodynamic characteristics
Air flow [CFM]
6000 9000 12000 15000 18000 21000 24000 27000 30000
250 1.0
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 1000 L
Number of poles: 6
0.9
Ø15
16 holes
Pd
200 89 91 0.8
88 88 90 92

1115
86
0.7
93
87 91
89 92
150 0.6
88 90
93
85 90
AXIS-FP 1000

86 92
0.5

1070
88 10
00
100 0.4
87 93
89 90
85 11
83 91 40
87
0.3

85 86 89 93
50 0.2
83 87 90
80 Axis-FP 1000-6
dBA
0.1
85 87 89 92
76 81 83 84
1 2 3 4 5 6 7 8
10000 20000 30000 40000 50000
Air flow [m3/h]

3 4 5 6 7 8 9 10 11 12 13 14 15
Air flow [m3/h]
6
Power [kW]

5 8
4
7
3
6
5
2 4
3
1 2
1
0
10000 20000 30000 40000 50000
Air flow [m3/h]

50 blaubergventilatoren.de
blaubergventilatoren.de

Technical data
AXIS-FP 1000-4
Voltage Number of Blade setting Weight
Size Number
[V / Model
Installed motor RPM [min⁻¹] Lenght L [mm] Curve number
of poles power Ny [kW] blades angle [°] [kg] on graph
50 Hz]

Axis-FP 1000-4D/5.5-8/25/AL 5.5 1440 8 25 199.5 550 


Axis-FP 1000-4D/7.5-8/30/AL 7.5 1440 8 30 207.5 650 
Axis-FP 1000-4D/7.5-8/32.5/AL 7.5 1440 8 32.5 207.5 650 
Axis-FP 1000-4D/9.2-8/35/AL 9.2 1440 8 35 226.5 650 
1000 4 3~400
Axis-FP 1000-4D/11-8/37.5/AL 11 1440 8 37.5 244.5 750 
Axis-FP 1000-4D/11-8/40/AL 11 1440 8 40 244.5 750 
Axis-FP 1000-4D/15-8/45/AL 15 1440 8 45 259.5 750 
Axis-FP 1000-4D/18.5-8/50/AL 18.5 1440 8 50 312.5 850 
Axis-FP 1000-4/8D/5/1.3-8/25/AL 5/1.3 1440/720 8 25 206.5 550 *
Axis-FP 1000-4/8D/7.2/1.8-8/30/AL 7.2/1.8 1440/720 8 30 218.5 650 *
Axis-FP 1000-4/8D/7.2/1.8-8/32.5/AL 7.2/1.8 1440/720 8 32.5 218.5 650 *
Axis-FP 1000-4/8D/11/3-8/35/AL 11/3 1440/720 8 35 257.5 650 *
1000 4/8 3~400
Axis-FP 1000-4/8D/11/3-8/37.5/AL 11/3 1440/720 8 37.5 257.5 750 *
Axis-FP 1000-4/8D/11/3-8/40/AL 11/3 1440/720 8 40 257.5 750 *
Axis-FP 1000-4/8D/14/3.5-8/45/AL 14/3.5 1440/720 8 45 273.5 750 *
Axis-FP 1000-4/8D/17/4.3-8/50/AL 17/4.3 1440/720 8 50 273.5 850 *
* maximum speed graph

Aerodynamic characteristics
Air flow [CFM]
12000 16000 20000 24000 28000 32000 36000 40000 44000
2.2
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]

Standard size: 1000 L

AXIS-FP 1000
500 Number of poles: 4 2.0
Ø15
Pd 16 holes
98 1.8
98 101
101
400 1.6
97
1115

96
100
98
1.4
94 102
99 100
300 1.2

96
94 99
1.0
1070

93 96 102 10
98 00
100
200 0.8
11
40
98
97 0.6
92 95 101
94 99
90
100 0.4

dBA Axis-FP 1000-4


0.2
86 90 92 94 95 96 98 100

1 2 3 4 5 6 7 8
20000 30000 40000 50000 60000 70000 80000
Air flow [m3/h]

6 8 10 12 14 16 18 20 22
Air flow [m3/h]
20
Power [kW]

8
15
7
10
6
5
4
5 3
2
1
0
20000 30000 40000 50000 60000 70000 80000
Air flow [m3/h]

AXIS-P | AXIS-FP 51
AXIS-P | AXIS-FP

Technical data
AXIS-FP 1120-6
Voltage Number of Blade setting Weight
Size Number
[V / Model
Installed motor RPM [min⁻¹] Lenght L [mm] Curve number
of poles power Ny [kW] blades angle [°] [kg] on graph
50 Hz]

Axis-FP 1120-6D/2.2-8/25/AL 2.2 960 8 25 195.5 550 


Axis-FP 1120-6D/3-8/30/AL 3 960 8 30 209.5 650 
Axis-FP 1120-6D/4-8/32.5/AL 4 960 8 32.5 223.5 650 
Axis-FP 1120-6D/4-8/35/AL 4 960 8 35 223.5 650 
1120 6 3~400
Axis-FP 1120-6D/5.5-8/37.5/AL 5.5 960 8 37.5 230.5 650 
Axis-FP 1120-6D/5.5-8/40/AL 5.5 960 8 40 230.5 650 
Axis-FP 1120-6D/7.5-8/45/AL 7.5 960 8 45 262.5 750 
Axis-FP 1120-6D/9.2-8/50/AL 9.2 960 8 50 274.5 750 

Aerodynamic characteristics
Air flow [CFM]
12000 16000 20000 24000 28000 32000 36000 40000 44000
1.2
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 1120 L
Number of poles: 6 1.1
Ø15
250 20 holes
92 Pd 1.0
93
90 0.9

1270
91 92 95 96
200 94 0.8
93

90 92 0.7
96
91 93
AXIS-FP 1120

150 0.6
92

1190
91 11
94 0.5 20
88 89 90
85 96
100 12
93
0.4 80
91
94

92
0.3
83 89
88 96
86
90 93
50 0.2 Axis-FP 1120-6
81 dBA
0.1
86 88 89 90 92 95
80 84
1 2 3 4 5 6 7 8
20000 30000 40000 50000 60000 70000 80000
Air flow [m3/h]

6 8 10 12 14 16 18 20 22
Air flow [m3/h]
10
Power [kW]

8 8

6 7
4 6
5
4
2 2 3
1
0
20000 30000 40000 50000 60000 70000 80000
Air flow [m3/h]

52 blaubergventilatoren.de
blaubergventilatoren.de

Technical data
AXIS-FP 1120-4
Voltage Number of Blade setting Weight
Size Number
[V / Model
Installed motor RPM [min⁻¹] Lenght L [mm] Curve number
of poles power Ny [kW] blades angle [°] [kg] on graph
50 Hz]

Axis-FP 1120-4D/7.5-8/25/AL 7.5 1440 8 25 226.5 650 


Axis-FP 1120-4D/11-8/30/AL 11 1440 8 30 263.5 750 
Axis-FP 1120-4D/11-8/32.5/AL 11 1440 8 32.5 263.5 750 
1120 4 3~400 Axis-FP 1120-4D/15-8/35/AL 15 1440 8 35 278.5 750 
Axis-FP 1120-4D/18.5-8/37.5/AL 18.5 1440 8 37.5 331.5 850 
Axis-FP 1120-4D/18.5-8/40/AL 18.5 1440 8 40 331.5 850 
Axis-FP 1120-4D/22-8/45/AL 22 1440 8 45 342.5 850 
Axis-FP 1120-4/8D/7.2/1.8-8/25/AL 7.2/1.8 1440/720 8 25 237.5 650 *
Axis-FP 1120-4/8D/11/3-8/30/AL 11/3 1440/720 8 30 276.5 750 *
Axis-FP 1120-4/8D/11/3-8/32.5/AL 11/3 1440/720 8 32.5 276.5 750 *
1120 4/8 3~400 Axis-FP 1120-4/8D/14/3.5-8/35/AL 14/3.5 1440/720 8 35 292.5 750 *
Axis-FP 1120-4/8D/17/4.3-8/37.5/AL 17/4.3 1440/720 8 37.5 319.5 850 *
Axis-FP 1120-4/8D/20/5-8/40/AL 20/5 1440/720 8 40 334.5 850 *
Axis-FP 1120-4/8D/28/6.5-8/45/AL 28/6.5 1440/720 8 45 392.5 850 *
* maximum speed graph

Aerodynamic characteristics
Air flow [CFM]
15000 20000 25000 30000 35000 40000 45000 50000 55000
700 2.8
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]

Standard size: 1120 L


Number of poles: 4
Ø15
600 2.4 20 holes

AXIS-FP 1120
99

500
1270

104
2.0
97
102 103
100 101
99
104
Pd
400 1.6
102 102
99 101
96 98
103
1190

300 1.2 11
102
20
100 101
98
12
94 96 103 80
200 0.8
101
99
99
97
95 102
100 91 0.4 Axis-FP 1120-4
99
96 97 dBA
88 93 95 101
1 2 3 4 5 6 7
20000 30000 40000 50000 60000 70000 80000 90000 100000
Air flow [m3/h]

6 8 10 12 14 16 18 20 22 24 26
Air flow [m3/h]
25
Power [kW]

20 7
15 6
5
10 4
3
2
5 1

0
20000 30000 40000 50000 60000 70000 80000 90000 100000
Air flow [m3/h]

AXIS-P | AXIS-FP 53
AXIS-P | AXIS-FP

Technical data
AXIS-FP 1250-6
Voltage Number of Blade setting Weight
Size Number
[V / Model
Installed motor RPM [min⁻¹] Lenght L [mm] Curve number
of poles power Ny [kW] blades angle [°] [kg] on graph
50 Hz]

Axis-FP 1250-6D/2.2-8/25/AL 2.2 960 8 25 214.5 550 


Axis-FP 1250-6D/3-8/30/AL 3 960 8 30 228.5 650 
Axis-FP 1250-6D/4-8/32.5/AL 4 960 8 32.5 242.5 650 
Axis-FP 1250-6D/5.5-8/35/AL 5.5 960 8 35 249.5 650 
1250 6 3~400
Axis-FP 1250-6D/5.5-8/37.5/AL 5.5 960 8 37.5 249.5 650 
Axis-FP 1250-6D/7.5-8/40/AL 7.5 960 8 40 281.5 750 
Axis-FP 1250-6D/9.2-8/45/AL 9.2 960 8 45 293.5 750 
Axis-FP 1250-6D/11-8/50/AL 11 960 8 50 306.5 750 

Aerodynamic characteristics
Air flow [CFM]
10000 15000 20000 25000 30000 35000 40000 45000 50000
300 1.2
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]


Standard size: 1250 L
Number of poles: 6 1.1
Ø15
92 93 20 holes
250 92 94 1.0
90
0.9
89 95

1400
92 96
92 93
200 86 0.8
90
95 96
0.7
91 93
92
89
150 0.6
AXIS-FP 1250

86
89 94

1320
92 12
0.5 50
89 91 96
87
94 14
100 96 0.4 50
83
92
85 87
0.3
90
88 91
81 93 95
50 0.2 Axis-FP 1250-6
83 84 dBA
86 88 90 92 95
0.1
77
1 2 3 4 5 6 7 8
10000 20000 30000 40000 50000 60000 70000 80000 90000
Air flow [m3/h]

4 6 8 10 12 14 16 18 20 22 24
Air flow [m3/h]
12
Power [kW]

10
8
8
7
6
6
4 5
4
2 3
2 1
0
10000 20000 30000 40000 50000 60000 70000 80000 90000
Air flow [m3/h]

54 blaubergventilatoren.de
blaubergventilatoren.de

Technical data
AXIS-FP 1250-4
Voltage Number of Blade setting Weight
Size Number
[V / Model
Installed motor RPM [min⁻¹] Lenght L [mm] Curve number
of poles power Ny [kW] blades angle [°] [kg] on graph
50 Hz]

Axis-FP 1250-4D/7.5-8/25/AL 7.5 1440 8 25 245.5 650 


Axis-FP 1250-4D/11-8/30/AL 11 1440 8 30 282.5 750 
Axis-FP 1250-4D/15-8/32.5/AL 15 1440 8 32.5 297.5 750 
1250 4 3~400 Axis-FP 1250-4D/15-8/35/AL 15 1440 8 35 297.5 750 
Axis-FP 1250-4D/18.5-8/37.5/AL 18.5 1440 8 37.5 350.5 850 
Axis-FP 1250-4D/22-8/40/AL 22 1440 8 40 361.5 850 
Axis-FP 1250-4D/30-8/45/AL 30 1440 8 45 424.5 850 
Axis-FP 1250-4/8D/7.2/1.8-8/25/AL 7.2/1.8 1440/720 8 25 256.5 650 *
Axis-FP 1250-4/8D/11/3-8/30/AL 11/3 1440/720 8 30 295.5 750 *
Axis-FP 1250-4/8D/14/3.5-8/32.5/AL 14/3.5 1440/720 8 32.5 311.5 750 *
1250 4/8 3~400 Axis-FP 1250-4/8D/14/3.5-8/35/AL 14/3.5 1440/720 8 35 311.5 750 *
Axis-FP 1250-4/8D/17/4.3-8/37.5/AL 17/4.3 1440/720 8 37.5 338.5 850 *
Axis-FP 1250-4/8D/20/5-8/40/AL 20/5 1440/720 8 40 353.5 850 *
Axis-FP 1250-4/8D/28/6.5-8/45/AL 28/6.5 1440/720 8 45 411.5 850 *
* maximum speed graph

Aerodynamic characteristics
Air flow [CFM]
20000 30000 40000 50000 60000 70000
700 2.8
Static pressure [Ps (Pa)]

Static pressure [Ps (in WG)]

Standard size: 1250 L


Number of poles: 4
Ø15
600 2.4 20 holes
100 101

AXIS-FP 1250
102 103
99
500
1400

2.0
97
100 101 102 103

95 98
400 1.6
96 102 Pd
101
100
103
1320

98 12
300 1.2 50
94 95 101
100
99
97 14
103 50
200 92
0.8
100
93
98
96 102
89 94
99 Axis-FP 1250-4
100 92
0.4
dBA
86 90 93 95 96 98 101
1 2 3 4 5 6 7
20000 40000 60000 80000 100000 120000
Air flow [m3/h]

6 8 10 12 14 16 18 20 22 24 26 28 30 32
Air flow [m3/h]
30
Power [kW]

25 7
20
6
15 5
4
10 3
2
5 1
0
20000 40000 60000 80000 100000 120000
Air flow [m3/h]

AXIS-P | AXIS-FP 55
AXIS-P | AXIS-FP

Fan accessories selection table

Fan Ø 400 Ø 450 Ø 500 Ø 560 Ø 630

Carrier O-AF-400 O-AF-450 O-AF-500 O-AF-560 O-AF-630

Flange F-AF-400 F-AF-450 F-AF-500 F-AF-560 F-AF-630

Flexible joint EVAF-AF-400 EVAF-AF-450 EVAF-AF-500 EVAF-AF-560 EVAF-AF-630

Fire-resistant flexible joint EVAF-AF-400- EVAF-AF-450- EVAF-AF-500- EVAF-AF-560- EVAF-AF-630-


up to 400°C 400/2 400/2 400/2 400/2 400/2

Hood Z-AF-400 Z-AF-450 Z-AF-500 Z-AF-560 Z-AF-630

Roof adapter PK-AF-400 PK-AF-450 PK-AF-500 PK-AF-560 PK-AF-630

Mounting curb SM-AF 400-450 SM-AF 400-450 SM-AF 500 SM-AF 560-630 SM-AF 560-630
ACCESSORIES

Inlet cone VK-AF-400 VK-AF-450 VK-AF-500 VK-AF-560 VK-AF-630

Backdraft damper VRV-AF-400 VRV-AF-450 VRV-AF-500 VRV-AF-560 VRV-AF-630

Fire-resistant backdraft VRV-AF-400- VRV-AF-450- VRV-AF-500- VRV-AF-560- VRV-AF-630-


damper up to 400 °C 400/2 400/2 400/2 400/2 400/2

Backdraft damper VRV1-AF-400 VRV1-AF-450 VRV1-AF-500 VRV1-AF-560 VRV1-AF-630

SD-400-1D SD-450-1D SD-500-1D SD-560-1D SD-630-1D


Silencer SD SD-400-1.5D SD-450-1.5D SD-500-1.5D SD-560-1.5D SD-630-1.5D

SD-400-2D SD-450-2D SD-500-2D SD-560-2D SD-630-2D

SDV-400-1D SDV-450-1D SDV-500-1D SDV-560-1D SDV-630-1D


Silencer SDV SDV-400-1.5D SDV-450-1.5D SDV-500-1.5D SDV-560-1.5D SDV-630-1.5D

SDV-400-2D SDV-450-2D SDV-500-2D SDV-560-2D SDV-630-2D

Protective mesh SZ-AF-400 SZ-AF-450 SZ-AF-500 SZ-AF-560 SZ-AF-630

Spring-loaded antivibration
mount
SIF-AF* SIF-AF* SIF-AF* SIF-AF* SIF-AF*

Rubber antivibration mount SIG-AF* SIG-AF* SIG-AF* SIG-AF* SIG-AF*

* selection according to the fan weight

56 blaubergventilatoren.de
blaubergventilatoren.de

Fan Ø 710 Ø 800 Ø 900 Ø 1000 Ø 1120 Ø 1250

Carrier O-AF-710 O-AF-800 O-AF-900 O-AF-1000 O-AF-1120 O-AF-1250

Flange F-AF-710 F-AF-800 F-AF-900 F-AF-1000 F-AF-1120 F-AF-1250

Flexible joint EVAF-AF-710 EVAF-AF-800 EVAF-AF-900 EVAF-AF-1000 EVAF-AF-1120 EVAF-AF-1250

Fire-resistant flexible joint EVAF-AF-710- EVAF-AF-800- EVAF-AF-900- EVAF-AF-1000- EVAF-AF-1120- EVAF-AF-1250-


up to 400°C 400/2 400/2 400/2 400/2 400/2 400/2

Hood Z-AF-710 Z-AF-800 Z-AF-900 Z-AF-1000 Z-AF-1120 Z-AF-1250

Roof adapter PK-AF-710 PK-AF-800 PK-AF-900 PK-AF-1000 PK-AF-1120 PK-AF-1250

Mounting curb SM-AF 710-800 SM-AF 710-800 SM-AF 900 SM-AF 1000-1120 SM-AF 1000-1120 SM-AF 1250

ACCESSORIES
Inlet cone VK-AF-710 VK-AF-800 VK-AF-900 VK-AF-1000 VK-AF-1120 VK-AF-1250

Backdraft damper VRV-AF-710 VRV-AF-800 VRV-AF-900 VRV-AF-1000 VRV-AF-1120 VRV-AF-1250

Fire-resistant backdraft VRV-AF-710- VRV-AF-800- VRV-AF-900- VRV-AF-1000- VRV-AF-1120- VRV-AF-1250-


damper up to 400 °C 400/2 400/2 400/2 400/2 400/2 400/2

Backdraft damper VRV1-AF-710 VRV1-AF-800 VRV1-AF-900 VRV1-AF-1000 VRV1-AF-1120 VRV1-AF-1250

SD-710-1D SD-800-1D SD-900-1D SD-1000-1D SD-1120-1D SD-1250-1D


Silencer SD SD-710-1.5D SD-800-1.5D SD-900-1.5D SD-1000-1.5D SD-1120-1.5D SD-1250-1.5D

SD-710-2D SD-800-2D SD-900-2D SD-1000-2D SD-1120-2D SD-1120-2D

SDV-710-1D SDV-800-1D SDV-900-1D SDV-1000-1D SDV-1120-1D SDV-1250-1D


Silencer SDV SDV-710-1.5D SDV-800-1.5D SDV-900-1.5D SDV-1000-1.5D SDV-1120-1.5D SDV-1250-1.5D

SDV-710-2D SDV-800-2D SDV-900-2D SDV-1000-2D SDV-1120-2D SDV-1120-2D

Protective mesh SZ-AF-710 SZ-AF-800 SZ-AF-900 SZ-AF-1000 SZ-AF-1120 SZ-AF-1250

Spring-loaded antivibration
mount
SIF-AF* SIF-AF* SIF-AF* SIF-AF* SIF-AF* SIF-AF*

Rubber antivibration mount SIG-AF* SIG-AF* SIG-AF* SIG-AF* SIG-AF* SIG-AF*

* selection according to the fan weight

AXIS-P | AXIS-FP 57
AXIS-P | AXIS-FP

CARRIER O-AF
Used for mounting the fans to the floor, walls or ceiling.
The carrier consists of two brackets. The unit is made of steel with a polymer coating.

Dimensions [mm]
Model
A B H M a R Ød n Weight [kg]

O-AF-400 510 395 115 45 160 225 8 4 1.15


O-AF-450 560 435 125 45 180 250 8 4 1.3 B
O-AF-500 610 480 130 45 200 280 12 4 1.4
O-AF-560 670 525 140 45 230 310 12 4 1.6 Ød

R
n
O-AF-630 740 575 150 45 255 345 12 4 1.8
O-AF-710 820 630 160 45 280 385 12 5 2.0
O-AF-800 910 705 180 45 315 430 12 5 2.35 a

H
O-AF-900 1020 795 215 52 360 485 15 5 6.3 a
A
O-AF-1000 1120 875 235 52 400 535 15 5 7.2
M
O-AF-1120 1240 1002 270 52 460 595 15 6 9.1
O-AF-1250 1370 1087 285 52 510 660 15 6 10.25

FLANGE F-AF
Enables attaching round ducts of appropriate size to the fan.
The unit is made of steel with a polymer coating.
100
Dimensions [mm]
Model
ØD Ø D1 Ø D2 Ød n Weight [kg]

F-AF-400 400 450 490 8 12 2.26

Ø D2
Ø D1
F-AF-450 450 500 540 8 12 2.53

ØD
F-AF-500 500 560 600 12 12 2.9
F-AF-560 560 620 660 12 12 3.24
ACCESSORIES

F-AF-630 630 690 730 12 12 3.63


F-AF-710 710 770 810 12 16 4.08 Ød
F-AF-800 800 860 900 12 16 4.58 n

F-AF-900 900 970 1015 15 16 5.41


F-AF-1000 1000 1070 1115 15 16 6.0
F-AF-1120 1120 1190 1270 15 20 7.51
F-AF-1250 1250 1320 1400 15 20 8.36

FLEXIBLE JOINT EVAF-AF


FIRE-RESISTANT FLEXIBLE JOINT EVAF-AF...400/2
Flexible joints cancel out any potential vibrations transmitted by the fans or air handling units to the air
ducting as well as partially compensate for the air duct assembly deformations caused by temperature
variation.
The flexible joints are formed by two flanges joined with vibration-cancelling material and are made
of polymer-coated steel and PVC tape reinforced with polyamide fabric. The joints are not intended
to withstand any significant mechanical loads and, therefore, may not be used as load-bearing
structures.
The EVAF-AF...400/2 joints are designed for operation at a temperature of 400 °C for 2 hours.
Ød
n
Dimensions [mm]
Model
ØD Ø D1 Ø D2 Ød n Weight [kg]

EVAF-AF-400 EVAF-AF-400-400/2 400 450 490 8 12 4.76


EVAF-AF-450 EVAF-AF-450-400/2 450 500 540 8 12 5.34
EVAF-AF-500 EVAF-AF-500-400/2 500 560 600 12 12 6.12
EVAF-AF-560 EVAF-AF-560-400/2 560 620 660 12 12 6.83 ØD
ØD
EVAF-AF-630 EVAF-AF-630-400/2 630 690 730 12 12 7.66 Ø 1
D2
EVAF-AF-710 EVAF-AF-710-400/2 710 770 810 12 16 8.6
0
26
EVAF-AF-800 EVAF-AF-800-400/2 800 860 900 12 16 9.67
EVAF-AF-900 EVAF-AF-900-400/2 900 970 1015 15 16 11.4
EVAF-AF-1000 EVAF-AF-1000-400/2 1000 1070 1115 15 16 12.64
EVAF-AF-1120 EVAF-AF-1120-400/2 1120 1190 1270 15 20 15.73
EVAF-AF-1250 EVAF-AF-1250-400/2 1250 1320 1400 15 20 17.52

58 blaubergventilatoren.de
blaubergventilatoren.de

HOOD Z-AF
Ensures trouble-free operation of fans on rooftops.
The unit is made of steel with a polymer coating.
B
Dimensions [mm]
Model
ØD Ø D1 Ø D2 Ød n H H1 A B Weight [kg]

A
H1
Z-AF-400 400 450 490 8 12 265 301 672 774 10.15

H
Z-AF-450 450 500 540 8 12 280 326 742 855 12.23 Ød
n
Z-AF-500 500 560 600 12 12 320 367 790 910 13.88
560 620 660 335 382 860 991 15.95 ØD
Z-AF-560 12 12
ØD1
Z-AF-630 630 690 730 12 12 360 406 988 1139 27.25
ØD2
Z-AF-710 710 770 810 12 16 420 466 1072 1236 36.54
Z-AF-800 800 860 900 12 16 478 536 1190 1371 47.42
Z-AF-900 900 970 1015 15 16 527 582 1346 1551 69.09
Z-AF-1000 1000 1070 1115 15 16 655 710 1552 1789 99.81
Z-AF-1120 1120 1190 1270 15 20 670 725 1707 1968 118
Z-AF-1250 1250 1320 1400 15 20 700 755 1845 2128 136

ROOF ADAPTER PK-AF


The unit is used for mounting Axis-P on rooftops.
The unit is made of steel with a polymer coating.
Ø
Dimensions [mm] Ød ØD D2
Model n ØD 1
ØD Ø D1 Ø D2 Ød n ØF Ø F1 Ø F2 Ø d1 n1 A B H Weight [kg]
H
PK-AF-400 400 450 490 8 12 450 500 540 8 12 580 701 115 7.2 Ød1
n1
PK-AF-450 450 500 540 8 12 500 560 600 12 12 580 701 130 7.5
PK-AF-500 500 560 600 12 12 560 620 660 12 12 640 770 140 10.3 A

ACCESSORIES
Ø B
PK-AF-560 560 620 660 12 12 630 690 730 12 12 750 920 155 14.2 Ø F
ØF F1
2
PK-AF-630 630 690 730 12 12 710 770 810 12 16 750 920 170 15.1
PK-AF-710 710 770 810 12 16 800 860 900 12 16 980 1150 210 27.7
PK-AF-800 800 860 900 12 16 900 970 1015 15 16 980 1150 230 28.7
PK-AF-900 900 970 1015 15 16 1000 1070 1115 15 16 1050 1220 250 41.7
PK-AF-1000 1000 1070 1115 15 16 1120 1190 1270 15 20 1340 1510 280 72.5
PK-AF-1120 1120 1190 1270 15 20 1250 1320 1400 15 20 1340 1510 295 75.1
PK-AF-1250 1250 1320 1400 15 20 1400 1470 1550 15 20 1500 1700 325 91

MOUNTING CURB SM-AF


The mounting curb is designed to enable fan installation on rooftops.
The unit is made of steel with a polymer coating. The outer frames are supported for installation on
the roof. The mounting curb is equipped with a side inspection door.

Dimensions [mm] B
A
Model
H A B C Weight [kg]

SM-AF-400-450 600 580 692 979 50.1


SM-AF-500 600 640 760 1047 53.7
H

SM-AF-560-630 600 750 910 1197 61.8


SM-AF-710-800 600 980 1140 1427 74.2 C
SM-AF-900 650 1050 1208 1495 81.3
SM-AF-1000-1120 750 1340 1498 1784 129.4
SM-AF-1250 750 1500 1688 1974 143.1

AXIS-P | AXIS-FP 59
AXIS-P | AXIS-FP

INLET CONE VK-AF


The inlet cone is recommended to be installed upstream of the fan to improve the air flow parameters.
However, it must be installed in the absence of ducting attached to the fan inlet. The inlet cone helps
reduce the fan dynamic pressure and increase the static component of the total fan pressure. The unit
can be used in combination with the SZ-AF protective mesh which must be one size larger than the
unit.
The unit has two flanges and is made of steel with a polymer coating.
H
Dimensions [mm]
Model
ØD Ø D1 Ø D2 Ød n ØF Ø F1 Ø F2 H Ø d1 n Weight [kg]

VK-AF-400 400 450 490 8 12 450 500 540 95 8 12 2.7 Ød


n
VK-AF-450 450 500 540 8 12 500 560 600 110 12 12 3.3

Ø F2
Ø F1
Ø D2
Ø D1

ØF
ØD
VK-AF-500 500 560 600 12 12 560 620 660 120 12 12 4.0
VK-AF-560 560 620 660 12 12 630 690 730 135 12 12 4.65
Ø d1
VK-AF-630 630 690 730 12 12 710 770 810 150 12 16 6.8 n1

VK-AF-710 710 770 810 12 16 800 860 900 170 12 16 12


VK-AF-800 800 860 900 12 16 900 970 1015 190 15 16 15
VK-AF-900 900 970 1015 15 16 1000 1070 1115 210 15 16 21
VK-AF-1000 1000 1070 1115 15 16 1120 1190 1270 240 15 20 36.7
VK-AF-1120 1120 1190 1270 15 20 1250 1320 1400 255 15 20 45
VK-AF-1250 1250 1320 1400 15 20 1400 1470 1550 285 15 20 53.5

BACKDRAFT DAMPER VRV-AF


FIRE-RESISTANT BACKDRAFT DAMPER VRV-AF...400/2
The backdraft damper with spring-loaded blades is used for shutoff of air flow in the air ducts
and prevention of air backdraft during standstill of ventilation equipment. The damper blades are
opened with the air pressure and closed with the spring.
The damper placement in a ventilation system should account for the air flow direction.  In case of a
horizontal installation of the damper, the pivot axis of the blades must be true horizontal. A vertically
installed damper is only suitable for air extraction duty. To aasemble the Axis-FP fans, use the
VRV-AF...400/2 dampers, which are designed to operate at a temperature of 400 °C for 2 hours.
ACCESSORIES

The unit casing and the two spring-loaded blades are made of polymer-coated steel.

Dimensions [mm]
Model L
ØD Ø D1 Ø D2 Ød n L Weight [kg]

VRV-AF-400 VRV-AF-400-400/2 400 450 490 8 12 250 5.4


VRV-AF-450 VRV-AF-450-400/2 450 500 540 8 12 250 6.2
VRV-AF-500 VRV-AF-500-400/2 500 560 590 12 12 250 7.1
Ød
VRV-AF-560 VRV-AF-560-400/2 560 620 650 12 12 320 9.6 n
VRV-AF-630 VRV-AF-630-400/2 630 690 720 12 12 370 14.2
VRV-AF-710 VRV-AF-710-400/2 710 770 810 12 16 390 21.4 ØD
VRV-AF-800 VRV-AF-800-400/2 800 860 900 12 16 390 25.4 Ø D1
Ø D2
VRV-AF-900 VRV-AF-900-400/2 900 970 1010 15 16 450 32.6
VRV-AF-1000 VRV-AF-1000-400/2 1000 1070 1110 15 16 450 36.9
VRV-AF-1120 VRV-AF-1120-400/2 1120 1190 1260 15 20 540 59.5
VRV-AF-1250 VRV-AF-1250-400/2 1250 1320 1390 15 20 540 67.4

60 blaubergventilatoren.de
blaubergventilatoren.de

BACKDRAFT DAMPER VRV1-AF


The backdraft damper with a gravity plate is used for supply pressurisation systems and designed for
shutoff of air flow during standstill of ventilation equipment. The damper plate opens with the pressure
created by the air flow and closes under its own weight, blocking the duct.
The VRV1-AF damper is only suitable for air supply duty and must be installed in the vertical position.
The damper is made from polymer coated steel and has a single blade which closes under its own weight.

Dimensions [mm]
Model

L
ØD Ø D1 Ø D2 Ød n L Weight [kg]

Ød
VRV1-AF-400 400 450 490 8 12 500 8.1 n
VRV1-AF-450 450 500 540 8 12 550 9.8
VRV1-AF-500 500 560 600 12 12 600 14.4
VRV1-AF-560 560 620 660 12 12 660 17.5
VRV1-AF-630 630 690 730 12 12 730 21.4 ØD
VRV1-AF-710 710 770 810 12 16 810 26.8 Ø D1
Ø D2
VRV1-AF-800 800 860 900 12 16 900 33.2
VRV1-AF-900 900 970 1015 15 16 1000 53.7
VRV1-AF-1000 1000 1070 1115 15 16 1100 65
VRV1-AF-1120 1120 1190 1270 15 20 1220 82.1
VRV1-AF-1250 1250 1320 1400 15 20 1350 100.3

SILENCER SD
The silencer is used for attenuation of the operation noise generated by ventilation equipment and
spreaded in the the air ducts. Designed for connection to round air ducts.
SD silencer has a polymer-coated steel casing filled with noncombustible material that has a protective
coating to prevent fiber deformation.

Dimensions [mm]
L
Model L L L Weight [kg]
ØD Ø D1 Ø D2 Md n
(1D) (1.5D) (2D) (1D) (1.5D) (2D) Md

ACCESSORIES
n
SD-400-1D SD-400-1.5D SD-400-2D 400 450 515 402 602 802 M6 12 9.5 13.1 16.7
SD-450-1D SD-450-1.5D SD-450-2D 450 500 565 452 677 902 M6 12 11.6 16.2 20.8
SD-500-1D SD-500-1.5D SD-500-2D 500 560 615 502 752 1002 M10 12 13.9 19.5 25.4
SD-560-1D SD-560-1.5D SD-560-2D 560 620 675 562 842 1122 M10 12 17.2 24.5 31.5
SD-630-1.5D SD-630-2D ØD
SD-630-1D 630 690 745 632 947 1262 M10 12 20.5 29.3 38.1 ØD
1
2
SD-710-1D SD-710-1.5D SD-710-2D 710 770 825 712 1067 1422 M10 16 25.6 36.2 47.6 ØD

SD-800-1D SD-800-1.5D SD-800-2D 800 860 903 801 1202 1601 M10 16 32.3 46.3 65.2
SD-900-1D SD-900-1.5D SD-900-2D 900 970 1003 901 1382 1801 M10 16 40.2 57.8 80.4
SD-1000-1D SD-1000-1.5D SD-1000-2D 1000 1070 1120 1002 1502 2002 M10 16 54.4 79.0 109.0
SD-1120-1D SD-1120-1.5D SD-1120-2D 1120 1190 1273 1122 1682 2242 M12 20 70.2 101.0 141.4
SD-1250-1D SD-1250-1.5D SD-1250-2D 1250 1320 1410 1252 1877 2502 M12 20 86.3 124.8 172.6

SILENCER SDV
The silencer is used for attenuation of the operation noise generated by ventilation equipment and spreaded in
the the air ducts. Designed for connection to round air ducts.
SDV silencer has a polymer-coated steel casing filled with noncombustible material that has a protective
coating to prevent fiber deformation. The silencer has an internal sound-absorbing element to increase
sound attenuation efficiency.

Dimensions [mm]
L
Model L L L Weight [kg]
ØD Ø D1 Ø D2 Md n
(1D) (1.5D) (2D) (1D) (1.5D) (2D)
Md
SDV-400-1D SDV-400-1.5D SDV-400-2D 400 450 515 402 602 802 M6 12 14.0 19.0 24.0
SDV-450-1D SDV-450-1.5D SDV-450-2D 450 500 565 452 677 902 M6 12 17.0 22.0 27.0
SDV-500-1D SDV-500-1.5D SDV-500-2D 500 560 615 502 752 1002 M10 12 23.0 31.0 38.0
SDV-560-1D SDV-560-1.5D SDV-560-2D 560 620 675 562 842 1122 M10 12 27.0 35.0 46.0
SDV-630-1D SDV-630-1.5D SDV-630-2D 630 690 745 632 947 1262 M10 12 33.0 46.0 59.0 ØD
1
ØD
SDV-710-1.5D SDV-710-2D 2
SDV-710-1D 710 770 825 712 1067 1422 M10 16 39.0 55.0 71.0 ØD
SDV-800-1D SDV-800-1.5D SDV-800-2D 800 860 903 801 1202 1601 M10 16 53.0 74.0 100.6
SDV-900-1D SDV-900-1.5D SDV-900-2D 900 970 1003 901 1382 1801 M10 16 63.0 84.0 126.0
SDV-1000-1D SDV-1000-1.5D SDV-1000-2D 1000 1070 1120 1002 1502 2002 M10 16 85.0 120.0 170.0
SDV-1120-1D SDV-1120-1.5D SDV-1120-2D 1120 1190 1273 1122 1682 2242 M12 20 105.0 148.0 210.0
SDV-1250-1D SDV-1250-1.5D SDV-1250-2D 1250 1320 1410 1252 1877 2502 M12 20 134.0 190.0 260.0

AXIS-P | AXIS-FP 61
AXIS-P | AXIS-FP

PROTECTIVE MESH SZ-AF


Protects the fans against ingress of foreign objects.
Protective mesh with 25x25 mm cells.
Ø D2
Dimensions [mm] ØD
Model
ØD Ø D1 Ø D2 Ød n Weight [kg]

SZ-AF-400 400 450 490 8 12 1.28


SZ-AF-450 450 500 540 8 12 1.45
SZ-AF-500 500 560 600 12 12 1.77 Ød
n
SZ-AF-560 560 620 660 12 12 2.0
SZ-AF-630 630 690 730 12 12 2.28 6

SZ-AF-710 710 770 810 12 16 2.59


Ø D1
SZ-AF-800 800 860 900 12 16 2.97
SZ-AF-900 900 970 1015 15 16 3.83
SZ-AF-1000 1000 1070 1115 15 16 4.32
SZ-AF-900 900 970 1015 15 16 3.83
SZ-AF-1000 1000 1070 1115 15 16 4.32
SZ-AF-1120 1120 1190 1270 15 20 6.2
SZ-AF-1250 1250 1320 1400 15 20 7.03

SPRING-LOADED ANTI-VIBRATION MOUNT SIF-AF


The anti-vibration mounts SIF-AF are used for attenuation of noise and vibration generated by
ventilation equipment. The anti-vibration mounts reduce dynamic loads, increase reliability and
durability of ventilation equipment. Four anti-vibration mounts are required to complete one fan.

Dimensions and mounting holes [mm]


Model Load [kg]
L H C Ød Width

SIF-AF-1 7 105 70 82 10.5 58


ACCESSORIES

SIF-AF-2 15 105 70 82 10.5 58 Ød


2

H
SIF-AF-3 24 105 80 82 10.5 58
SIF-AF-4 29 105 90 82 10.5 58
SIF-AF-5 35 105 113 82 10.5 58
C
SIF-AF-6 50 105 113 82 10.5 58 L
SIF-AF-7 80 105 113 82 10.5 58
SIF-AF-8 120 105 113 82 10.5 58

RUBBER ANTI-VIBRATION MOUNT SIG-AF


The rubber anti-vibration mounts SIG-AF are used for attenuation of noise and vibration generated E
by ventilation equipment. B
The anti-vibration mounts reduce dynamic loads, increase reliability and durability of ventilation
equipment. Four anti-vibration mounts are required to complete one fan.

Dimensions and mounting holes [mm]


Model Load [kg]
A B C Ød E L H Ød
H

2
SIG-AF-1 5-35 5 M8 60 9 Ø30 80 40 C
L
35-80 10 M10 76 11 Ø40 105 52
A

SIG-AF-2
SIG-AF-3 50-120 10 M10 76 11 Ø45 105 52

62 blaubergventilatoren.de
blaubergventilatoren.de

OPERATION OF FANS WITH FREQUENCY CONVERTERS


M

Ventilation systems produce a heavy load on the electrical systems of


a building. Therefore, reducing the power consumption is among the top
priorities for construction project designers.

DIRECT ON-LINE STARTING (DOL) Mn

As a rule, smoke extraction systems utilize large high-performance fans.


During starting the high inertia of the shaft causes a substantial increase in
the start-up time - i.e. the time from the application of power to reaching
the rated speed. As a result the motor is subjected to high starting current
for a prolonged period of time.
Torque diagram with FC starting

SOFT STARTER
I Unlike an FC, a soft starter does not change the frequency of speed.
Instead it gradually increases the voltage supplied to the motor – from
the initial level to the nominal level.
The very low voltage initially supplied to the motor during starting helps
avoid sudden jolts.
Both voltage and torque increase gradually.

Current diagram with direct on-line starting

Standard switchgear (automatic circuit breakers, contactors and motor


starters) is not designed to withstand prolonged overloads causing the fan
to shut down automatically during starting.
Using switchgear with a higher maximum current rating renders the electric
motor protection system less sensitive.
As a result the switchgear will not be able to detect motor overload in time
due to a higher current sensing threshold.
Such challenges can only be addressed by utilizing a soft starter or
a  frequency converter to start the fan without causing a prolonged overload. Current diagram with soft starter

ACCESSORIES
M

Torque diagram with soft starter


Torque diagram with direct on-line starting

FREQUENCY CONVERTER APPLICATIONS IN VENTILATION SYSTEMS


A frequency converter (FC) consists of two main component blocks. One Using an FC or a soft starter allows to reduce the starting current thereby
converts alternating current (50 or 60 Hz) into direct current. avoiding a loss of voltage in the electrical mains.
The other converts direct current into alternating current of variable In addition to that the starting torque and mechanical strain on equipment are
frequency ranging from 0 to 250 Hz. also reduced which translates into extended maintenance and repair intervals.
By controlling the frequency output the FC offers a broad range of motor General exhaust ventilation (GV) systems and emergency smoke extraction (SE)
speed regulation. systems of car parks, warehouses, utility and industrial spaces can be integrated
into a single system at the design level.
I
As the air flow rate a GV system is considerably lower than that in an SE system
a high-capacity fan rated for smoke extraction duty runs in partial load mode.
Frequency converters can be programmed for several fixed-speed settings to
enable operation in GV and SE modes.
The fan operating modes can be switched upon receiving an external signal from
the control system.
Such integration of ventilation systems allows overall cost savings.
In
FC-51 AND FC-101: WHEN TO USE?
This catalogue features two series of frequency converters: FC-51 and
FC-101.
The FC-51 series is only suitable for general ventilation systems.
Current diagram with FC starting If intended for a smoke extraction system, the fans should be fitted with
the  FC-101 series units as they feature an integrated fire mode.
During the starting the FC raises the frequency from 0 Hz to the electrical When activated the integrated protection equipment of the frequency
mains frequency (50 or 60 Hz). converter is overridden enabling the unit to continue operation despite
As the frequency is increased gradually, the motor can be assumed to the possibility of sustaining irreparable damage due to overheating or
operate at its nominal speed for a given frequency value. overloading.
Furthermore, on the assumption that the motor runs at its nominal speed In case of a fire, the FC-101 series frequency converters are capable of
the nominal torque should be immediately available whereas the current maintaining a higher air pressure level at landings compared to other areas
will be approximately equal to the nominal value. of the building in order to keep the landings smoke-free.

AXIS-P | AXIS-FP 63
AXIS-P | AXIS-FP

Micro Drive FC-51


Frequency converters

Use
This general-purpose variable frequency drive is
designed for regulating the rotation speed of an
AC electric motor with a maximum power output
of 22 kW.
This unit is only suitable for general ventilation
systems.

Design Installation
The drive construction prevents forced air flow passage through its Back-to-back installation for space savings. Thanks to a compact design
internal electronic components. The internal circuit boards of are well- the drives can be mounted immediately next to one another without any
protected. performance penalties.

Filter Frequency converter type and order code


The unit features an integrated HF filter which blocks RF interference
Three-phase, 380-480 V
from the motor and enables the use of a shielded cable up to 15 m long
or unshielded cable up to 50 m long as per the applicable EU regulations. Power [kW] Rated current [A] Order code Block type

0.37 1.2 132F0017 M1


Inputs and outputs 0.75 2.2 132F0018 M1
 5 programmable digital inputs 1.5 3.7 132F0020 M2
PNP/NPN logic 2.2 5.3 132F0022 M2
20-5000 Hz pulse input 3.0 7.2 132F0024 M3
One 0-10 V or 0-20 mA analogue input 4.0 9.0 132F0026 M3
ACCESSORIES

One 0-20 mA analogue input 5.5 12.0 132F0028 M3


Thermistor input (analogue or digital) 7.5 15.5 132F0030 M3
1 analogue output 11.0 23.0 132F0058 M4
1 relay, 240 V, 2 A 15.0 31.0 132F0059 M4
RS 485 18.0 37.0 132F0060 M5
MODBUS RTU
22.0 43.0 132F0061 M5

Control panels
Outside dimensions (including mounting ledge)
Designation Code mm M1 M2 M3 M4 M5

VLT control panel LCP 11 Height 150 176 239 292 335
132B0100
(without potentiometer) Width 70 75 90 125 165
VLT Control Panel LCP 12
Depth 148 168 194 241 248
132B0101
(with potentiometer) + 6 mm with potentiometer

Designation Code

Remote panel mounting kit 132B0102

64 blaubergventilatoren.de
blaubergventilatoren.de

Basic Drive FC-101


Frequency converters

Use
This general-purpose variable frequency drive is
designed for regulating the rotation speed of an
AC electric motor with a maximum power output
of 90  kW. This drive is suitable for both general
ventilation and smoke extraction ventilation
systems.

Certified fire mode Inputs and outputs


The fire mode prevents the drive from a self-protecting shut-down. While  Four PNP or NPN programmable digital inputs, 0-24 V DC
in this mode the drive continues to perform speed regulation duty for 2 analogue inputs (0-10 V or 0/4-20 mA)
mission-critical fans irrespective of control signals, warnings and alarms 2 analogue outputs (0/4-20 mA)
which may otherwise force it shut down. 2 relay outputs
MODBUS RTU (RS 485)
BACnet MSTP
Filter FC Protocol
A built-in throttle on the DC link ensures a low harmonic load on the power N2 Metasys
mains as per the EN 61000-3-12 standard requirements. FLN Apogee

Installation
Thanks to an ultra-compact design the drive can be easily fitted into a
larger unit or panel of an air ventilation system. The casings are rated
IP20/Type 1/IP21 (optional) and IP54.

ACCESSORIES
Frequency converter type and SKU code
Power Current VLT® FC 101 HVAC Basic Drive 0.37-90 kW (3 x 380 – 480 V~, without a braking transistor)

0.37 1.2 – 131L9861 – –


0.75 2.2 – 131L9862 131NO177 131NO178
1.5 3.7 – 131L9863 131NO179 131NO180
2.2 5.3 – 131L9864 131NO181 131NO182
3 7.2 – 131L9865 131NO183 131NO184
4 9.1 – 131L9866 131NO185 131NO186
5.5 12 – 131L9867 131NO187 131NO188
7.5 15.5 – 131L9868 131NO189 131NO190
11 23 – 131L9869 131NO191 131NO192
15 31 – 131L9870 131NO193 131NO194
18 37 – 131L9871 131NO195 131NO196
22 42.5 – 131L9872 131NO197 131NO198
30 61 131L9873 131L9875 131NO201 131NO202
37 73 131L9881 131L9883 131NO205 131NO206
45 90 131L9889 131L9891 131NO209 131NO210
55 106 131L9897 131L9899 131NO213 131NO214
75 147 131L9905 131L9907 131NO217 131NO218
90 177 131L9913 131L9915 131NO221 131NO222
Casing (E20) IP20/Chassis (E20) IP20/Chasis IP54 IP54
EMC filter
(H2) RFI class A2 (H3/H4) RFI class A1/B (H2) RFI class A2 (H3) RFI class A1/B
(for industrial areas) (for residential areas) (for industrial areas) (for residential areas)
Control panel (X) without panel (X) without panel Integral Integral
VLT® HVAC Basic frequency converters rated up to 22 kW are fitted with circuit boards with a special class 3C3 protective coating. For frequency converters rated higher than 22 kW this
protective coating is optional while, the 3C2 coating is standard.

VLT® FC 101 HVAC Basic Drive frequency converter options


Order code Description Order code Description

132B0200 Operator's digital panel 132B0243 Decoupling plate for H7 standard size (extra large)
132B0201
Kit for remote mounting of the operator panel to an IP55 cabinet, 132B0209 Decoupling plate for H8 standard size
including 3 m cable
132B0244 External EMC filter class A1/B1 for power output from 0.37 to 2.2 kW
132B0202 Decoupling plate for H1 and H2 standard sizes
132B0245 External EMC filter class A1/B1 for power output from 3 to 7.5 kW
132B0204 Decoupling plate for H3 standard size
132B0246 External EMC filter class A1/B1 for power output from 11 to 15 kW
132B0205 Decoupling plate for H4 and H5 standard sizes
132B0247 External EMC filter class A1/B1 for power output from 18.5 to 22 kW
132B0207 Decoupling plate for H6 standard size
132B0242 Decoupling plate for H6 standard size (extra large)
132B0208 Decoupling plate for H7 standard size

AXIS-P | AXIS-FP 65
Blauberg Ventilatoren GmbH
Aidenbachstr. 52
D-81379 Munich

info@blaubergventilatoren.de
www.blaubergventilatoren.de

Technical changes reserved.


Illustrations and texts are non-binding.

06/2019