Sei sulla pagina 1di 6

SUI NORTHERN GAS PIPELINE LIMITED

CORROSION CONTROL - DEPARTMENT


PIPE/ SOIL POTENTIAL SURVEY REPORT

Section: Sakhakot-Swat Line Line: Dia: 8" Length: 42.44 miles

Survey Date: May-2019 Surveyed By: Habib-ur-Rehman Sr. Associate Engineer (Corr)

PIPE TO SOIL POTENTIAL


(-Volts)
S.No LOCATION Previous Present REMARKS
Nov-18 May-19
MP-0 V/A Sakhakot Zero I/F Short I/F Short
1 Point Pre-Fab Pre-Fab

i PSP (Open) 1.10/1.15 1.09/1.18

ii PSP (Bond) - -

iii Current to line - -

0.52/Miss 0.47/Miss
2 MP-0.10 cc rail x-ing
1.18 1.18

3 MP-1.61 1.18 1.09

4 MP-2.52 0.97 0.88

5 MP-3.64 0.85 0.80

6 MP-4.75 1.15 1.17

7 MP-6.24 1.19 1.23

8 MP-7.24 1.14 1.22


I/F OK I/F OK
MP-7.30 2" dia I/F SMS
9 Pre-Fab Pre-Fab
Khar kai

i PSP (Open) 1.13/0.24 1.19/0.27

ii PSP (Bond) - -

iii Current to line - -

10 MP-8.18 1.21 1.22

11 MP-8.88 0.97 0.98

12 MP-10 1.18 1.24

13 MP-11 1.01 1.05


PIPE TO SOIL POTENTIAL
(-Volts)
S.No LOCATION Previous Present REMARKS
Nov-18 May-19

14 MP-12.18 1.11 1.22


PIPE TO SOIL POTENTIAL
(-Volts)
S.No LOCATION Previous Present REMARKS
Nov-18 May-19
I/F OK I/F OK
15 MP-12.30 8" dia I/F Plai Pre-Fab Pre-Fab

i PSP (Open) - -

ii PSP (Bond) 1.08/1.08 1.17/1.17

iii Current to line - -


I/F Short I/F Short
MP-12.30 2" dia I/F SMS
16 Pre-Fab Pre-Fab
Plai

i PSP (Open) 1.05/1.03 1.14/1.13

ii PSP (Bond) - -

iii Current to line - -

17 MP-13.07 1.14 1.28

18 MP-13.97 1.26 1.25

19 MP-14.50 1.26 1.27

20 MP-16 1.14 1.19

21 MP-17.07 Miss 1.02

22 MP-17.95 Miss 1.05

23 MP-18.78 1.10 1.08

24 MP-20.16 Miss 1.14

25 MP-21.04 1.16 1.14


I/F OK I/F OK
MP-21.83 4"dia I/F
26 Pre-Fab Pre-Fab
SMS But Khel

i PSP (Open) 1.15/0.49 1.11/0.44

ii PSP (Bond) - -

iii Current to line - -

27 MP-22.76 Miss 1.34

MP-24 CP Station
28 1.30/1.30 1.30/1.30
Thana

i Voltage 10 8
PIPE TO SOIL POTENTIAL
(-Volts)
S.No LOCATION Previous Present REMARKS
Nov-18 May-19

ii Current 0.5A 0.6A

iii G.Bed Res Through Resistance Through Resistance

iv Tapping TEG-Unit TEG-Unit

v Current to line 0.5A 550mA

T-Unit Pressure- T-Unit Pressure-


vi EMR
5.0 PSI 5.0 PSI

vii PSP (Open) - -

viii PSP (Bond) 1.30/1.30 1.30/1.30

29 MP-24.91 Miss 1.41

30 MP-25.73 1.32 1.41

31 MP-26.45 1.30 1.39

32 MP-27.30 1.29 1..37

33 MP-28.29 Miss 1.49

34 MP-29.29 1.23 Miss

35 MP-29.96 1.21 1.44

36 MP-31.07 1.26 1.46

37 MP-32.03 1.26 1.44


I/F OK I/F OK
MP-33.20 4"dia I/F
38 Pre-Fab Pre-Fab
SMS Bari Kot

i PSP (Open) 1.21/0.93 1.47/0.82

ii PSP (Bond) - -

iii Current to line - -

39 MP-34.20 1.29 1.37

40 MP-35.20 1.31 1.38

41 MP-35.90 Miss 1.28

42 MP-37.13 Miss Miss


PIPE TO SOIL POTENTIAL
(-Volts)
S.No LOCATION Previous Present REMARKS
Nov-18 May-19

43 MP-37.98 1.20 1.30

44 MP-39.09 1.19 1.24

45 MP-39.90 Miss Miss

46 MP-40.87 1.15 1.20


I/F Short I/F Short
MP-42 End Point V/A
47 RTJ RTJ
8"dia I/F Mangora

i PSP (Open) 1.23/1.21 1.19/1.18

ii PSP (Bond) - -

iii Current to line - -

REMARKS

HABIB UR REHMAN
SURVEYED BY SR. ASSOCT ENGINEER (CORR)
AYISHA SALEEM
VERIFIED BY ENGINEER (CORR),GR III
M.JAVED FAISAL
REVIEWED BY EXEC.TECH.OFFICER (CORR)
SUI NORTHERN GAS PIPELINES LIMITED
CORROSION CONTROL – DEPARTMENT
SUMMARY OF PIPE TO SOIL POTENTIAL
SURVEY

LINE DATA: SURVEY DATE: May-2019

SECTION: Wah (Transmission)

LINE TITLE: 8" dia Sakhakot-Swat Line

LENGTH: 42.44 miles


NO OF C.P. STATION 01 No.

NO. OF C.P. TEST POINTS: 47 Nos.

STATUS:
DESCRIPTION PREVIOUS STATUS (Nov-18) PRESENT STATUS (May-19)
Cathodic Protection Level Protected Protected
PSP Spread “ON” Potential (-V) MAX 1.32 MIN 0.85 MAX 1.49 MIN 0.80
Current Drained 0.50 Amps. 0.55 Amps.
Current Density 0.0010 mA/Sq.Ft. 0.0011 mA/Sq.Ft.
Coating Condition Excellent Excellent
Coating Type 3 Layer Polyethylene Coated
Construction Year 2002

Integrity of C.P. Flanges


Location Type of Flange Status Remarks
VA Sakakot Zero Point Pre-Fab Short Needs Rectification
2”dia SMS Khar Kai Pre-Fab Ok
8”dia I/F Plai MP-12 Pre-Fab Ok
2”dia SMS Plai Pre-Fab Short Needs Rectification
SMS But khela 4"dia I/F Pre-Fab Ok
V/A Thana 8"dia I/F Pre-Fab Ok
SMS Bari Kot 4"dia I/F Pre-Fab Ok
End Point V/A Mangora 8"dia RTJ Short Needs Rectification
SMS Mangora 6"dia I/F Pre-Fab Short Needs Rectification

COMMENTS:

Coating Assessment Criteria (mA/Sqft)


Excellent Good Average Poor Very Poor Bare
Upto 0.005 0.0051-0.0100 0.0101-0.0200 0.0201-0.1000 0.1010-1.0000 1.0001-3.0000

REMARKS:

HABIB UR REHMAN
SURVEYED BY SR. ASSOCT ENGINEER (CORR)
AYISHA SALEEM
VERIFIED BY ENGINEER (CORR),GR III
M.JAVED FAISAL
REVIEWED BY EXEC.TECH.OFFICER (CORR)

Potrebbero piacerti anche