LEGEND : SPECIFICATIONS :
1.THE WORK UNDER THIS CONTRACT IS TO BE INSTALLED ACCORDING TO THE
LIGHTNING OUTLET
REQUIREMENTS OF THE LATEST PHILIPPINE ELECTRICAL CODE, THE RULES
CONVENIENCE OUTLET AND REGULATIONS OF THE LOCAL AUTHORITIES AND THE REQUIREMENTS OF
LOCAL POWER COMPANY.
3.0000
S 1 POLE SWITCH
3.THE ELECTRICAL CONTRACTOR SHALL, DURING THE PROGRESS OF THE
S2 2 POLE SWITCH WORK, KEEP A CAREFUL RECORD OF ALL CHANGES WHERE THE ACTUAL
INSTALLATION DIFFERS FROM THAT SHOWN ON THE CONTRACTOR DRAWINGS.
S3 3 POLE SWITCH UPON COMPLETION, THE ELECTRICAL CONTRACTOR SHALL, IN A NEAT AND
ACCURATE MANNER, FINALIZE "as-built" DRAWINGS ON TRACING PAPER. THESE
S2 PANEL BOARD DRAWING SHALL BE SUBMITTED TO THE OWNER FOR APPROVAL. AFTER
PB ACU APPROVAL, THEY SHALL BECOME THE PROPERTY OF THE OWNER.
4 M KILOWATT-HOUR METER
1
3. ALL ELECTRICAL MATERIALS SHALL BE NEW AND SHALL MEET
PB CIRCUIT BREAKER REQUIREMENTS AND SHALL BEAR THE INSPECTION LABEL WHENEVER
3 STANDARDS HAVE BEEN ESTABLISHED. AS SOON AS PRACTICABLE, AND
SERVICE ENTRANCE WITHIN TEN (10) DAYS AFTER THE OFFICIAL AWARD OF CONTRACT, AND
PB
S2 1 CIRCUIT HOMERUN BEFORE ANY MATERIALS OR EQUIPMENT ARE ORDERED, THE ELECTRICAL
CONTRACTOR SHALL SUBMIT TO THE ENGINEERS FOR APPROVAL A COMPLETE
LIST OF MATERIALS, APPARATUS AND EQUIPMENT IN TRIPLICATE, GIVING THE
MANUFACTURER'S NAME, ADDRESS, DESCRIPTION DATA, TRADE NAME OF
8.0000 ITEM, RATED CAPACITIES, CERTIFIED ANALYSIS, CATALOG NUMBERS, ETC.
PB WHEN CALLED UPON TO DO SO, THE ELECTRICAL CONTRACTOR SHALL REVISE
S 2
2-8.0mm² THHN IN 25mm∅ uPVC PIPE AND RESUBMIT THE COMPLETE OR PORTION OF THE LIST, AS REQUIRED BY
THE OWNER, FOR EVERY MATERIAL THE ELECTRICAL CONTRACTOR PROPOSES
PB TO USE OR INSTALL.
40AT 15AT 4. PROVIDE GROUNDING WIRE TO ALL OUTLETS AND LIGHTING CIRCUIT, ALL
S 1 LO NON CURRENT CARRYING METAL PARTS SHALL BE GROUNDED AND BONDED
INCLUDING FENCE AND GATES.
20AT 20AT
CO 2 3 CO 5. MOUNTING HEIGHTS FOR ALL WIRING DEVICES AND PANEL BOARDS SHALL
S3 BE:
5.1 LIGHTING SWITCHES--------------1.40 M. ABOVE FLOOR FINISH
S 20AT
5.2 CONVENIENCE OUTLETS----------0.30 M. ABOVE FLOOR FINISH
ACU 4 5 SPARE 5.3 PANEL BOARDS ---------------------1.40 M. ABOVE FLOOR FINISH
2.5000 G
5.5 mm² TW GROUND CONDUCTOR N
S
GROUND ROD
W E
LIGHTNING LAYOUT POWER LAYOUT PANEL BOARD DETAIL
S
L HIGHWAY
CKT. NATIONA
DESCRIPTION VA V A P AF PROTECTION SIZE OF WIRE & CONDUIT SICSICAN
NO.
1 LO-11 1100 230 4.78 60 15AT,CB 2.0mm² THHN IN 20mm∅

ELEMEN
2 CO-6 1080 230 4.69 2 60 20AT,CB 2-3.5mm² THHN IN 20mm∅

TARY SC
RRA
PUROK NA
3 CO-6 1080 230 4.69 2 60 20AT,CB 2-3.5mm² THHN IN 20mm∅ 3.0000

HOOL
THIS SITE
4 ACU-1HP 1840 230 8 2 60 20AT,CB 2-3.5mm² THHN IN 20mm∅
SERVICE ENTRANCE
5 SPARE 1840 230 8 2 60 20AT,CB 2-3.5mm² THHN IN 20mm∅
M PB 60AF
LOAD SCHEDULE
1.5000
TOTAL LOAD CURRENT : 6940 x 0.8/230 + 25%(8) = 26.13 A
MAIN PROTECTION : 40AT/60AF, 2P, 230/60Hz, CIRCUIT BREAKER
FEEDER CONDUCTROR : 2-8.0mm² THHN COPPER WIRE in 25mm∅ uPVC PIPE
GROUNDING CONDUCTOR : 5.5mm² TW GROUNDING CONDUCTOR
COMPUTATION RISER DIAGRAM LOCATION
SCALE 1 : 1 meter
DESIGNER : OWNER : PROJECT TITLE : CHECKED BY : SHEET CONTENTS : SHEET NO. :
C
EC
EELLE TTRR

IC
CLARENCE JAY M. GANIR CESAR MARCELO PROPOSED RESIDENTIAL E

AL
WORKS
WORKS
CG ELECTRICAL WORKS AND DESIGNS
DWELLING AS SHOWN
AND
AND
DESIGNS
DESIGNS ADDRESS : PUERTO PRINCESA CITY REG NO. : 21435 ADDRESS : SICSICAN, PPC, PALAWAN ADDRESS : 1
MOBILE NO. : +63-9152-657-329 PTR NO. : 330416 MOBILE NO. : DATE : SEPTEMBER 02, 2019