Sei sulla pagina 1di 4

Page |1

TEST REPORT OF METERING PT AKSHAR ELECINFRA PVT. LTD.


Client ADANI GREEN ENERGY (MP) LTD., DAYAPAR Tested On 23/11/2019
Plant 725MW WIND POWER PLANT, DAYAPAR, GUJARAT Tested By SOUMYA KANTI
Location 33KV METERING BAY-3
Feeder FEEDER NO-3 (SWITCHGEAR SIDE)

1.0 P.T. SPECIFICATION AND NAME PLATE DETAILS :


VA OF CORE ACC. CLASS OF CORE
PHASE P.T. RATIO P.T. SR. NO.
CORE-1 CORE-2 CORE-1 CORE-2
33000/√3V/110/√3-
R OP-8946/6/13/19 15 VA 15 VA 0.2 0.2
110/√3V
33000/√3V/110/√3-
Y OP-8946/6/14/19 15 VA 15 VA 0.2 0.2
110/√3V
33000/√3V/110/√3-
B OP-8946/6/15/19 15 VA 15 VA 0.2 0.2
110/√3V

1.1 INSULATION RESISTANCE OF PT @ 60 Sec: ALL VALUE IN G Ω


REFERENCE VOLTAGE R PHASE Y PHASE B PHASE
PRI – EARTH 5 kV 25.1 GΩ 21.6 GΩ 17.5 GΩ
PRI- CORE 1 5 kV 20.2 GΩ 43.9 GΩ 52.0 GΩ
PRI- CORE 2 5 kV 18.4 GΩ 20.9 GΩ 31.5 GΩ
CORE 1 – CORE 2 500 V 19.2 GΩ 17.3 GΩ 51.2 GΩ
CORE 1 – EARTH 500 V 12.3 GΩ 17.3 GΩ 51.7 GΩ
CORE 2 – EARTH 500 V 14.5 GΩ 37.1 GΩ 17.3 GΩ

1.2 WINDING RESISTANCE OF PT: ALL VALUES IN Ω


REFERENCE R PHASE (Ω) Y PHASE (Ω) B PHASE (Ω)
PRI-N 5.96 KΩ 5.96 KΩ 5.94 KΩ
CORE-1 0.29 Ω 0.28 Ω 0.32 Ω
CORE-2 0.29 Ω 0.30 Ω 0.33 Ω

1.3 RATIO TEST:

Tested by Akshar Witness by Adani


Name SOUMYA KANTI BHOWMICK

Sign
Date
AKSHAR ELECINFRA PVT. LTD.
Page |2

INJECTED MEASURED SECONDARY


CALCULATED RATIO ± % ERROR
PHASE PRIMARY VOLTAGE (V)
VOLTAGE (V) 1a-1n 2a-2n 1a-1n 2a-2n 1a-1n 2a-2n
R-N 241.0 0.804 0.807 0.803 0.803 0.12 0.50
Y-N 244.4 0.809 0.809 0.815 0.815 -0.74 -0.74
B-N 242.4 0.807 0.807 0.808 0.808 -0.12 -0.12

POLARITY CHECK : OK
GENERAL CHECK-UP : OK
MAKE OF PT : MEHRU ELECTRICAL & MECHANICAL ENGINEERS PVT. LTD.
CONTINUITY CHECK : OK
REMARKS : TESTED OK.

TEST REPORT OF METERING PT AKSHAR ELECINFRA PVT. LTD.

Tested by Akshar Witness by Adani


Name SOUMYA KANTI BHOWMICK

Sign
Date
AKSHAR ELECINFRA PVT. LTD.
Page |3

Client ADANI GREEN ENERGY (MP) LTD., DAYAPAR Tested On 23/11/2019


Plant 725MW WIND POWER PLANT, DAYAPAR, GUJARAT Tested By SOUMYA KANTI
Location 33KV METERING BAY-3
Feeder FEEDER-3 (INCOMER FROM WIND POOLING STATION)

1.0 P.T. SPECIFICATION AND NAME PLATE DETAILS :


VA OF CORE ACC. CLASS OF CORE
PHASE P.T. RATIO P.T. SR. NO.
CORE-1 CORE-2 CORE-1 CORE-2
33000/√3V/110/√3-
R OP-8946/6/16/19 15 VA 15 VA 0.2 0.2
110/√3V
33000/√3V/110/√3-
Y OP-8946/6/17/19 15 VA 15 VA 0.2 0.2
110/√3V
33000/√3V/110/√3-
B OP-8946/6/18/19 15 VA 15 VA 0.2 0.2
110/√3V

1.1 INSULATION RESISTANCE OF PT @ 60 Sec: ALL VALUE IN G Ω


REFERENCE VOLTAGE R PHASE Y PHASE B PHASE
PRI – EARTH 5 kV 23.8 GΩ 24.3 GΩ 23.6 GΩ
PRI- CORE 1 5 kV 63.3 GΩ 58.0 GΩ 39.3 GΩ
PRI- CORE 2 5 kV 66.5 GΩ 70.7 GΩ 64.3 GΩ
CORE 1 – CORE 2 500 V 61.2 GΩ 63.9 GΩ 49.2 GΩ
CORE 1 – EARTH 500 V 32.9 GΩ 34.1 GΩ 32.9 GΩ
CORE 2 – EARTH 500 V 21.6 GΩ 39.6 GΩ 29.4 GΩ

1.2 WINDING RESISTANCE OF PT: ALL VALUES IN Ω


REFERENCE R PHASE (Ω) Y PHASE (Ω) B PHASE (Ω)
PRI-N 5.97 KΩ 5.92 KΩ 5.95 KΩ
CORE-1 0.30 Ω 0.41 Ω 0.45 Ω
CORE-2 0.48 Ω 0.41 Ω 0.46 Ω

1.3 RATIO TEST:


MEASURED SECONDARY
PHASE CALCULATED RATIO ± % ERROR
VOLTAGE (V)
Tested by Akshar Witness by Adani
Name SOUMYA KANTI BHOWMICK

Sign
Date
AKSHAR ELECINFRA PVT. LTD.
Page |4

INJECTED
PRIMARY 1a-1n 2a-2n 1a-1n 2a-2n 1a-1n 2a-2n
VOLTAGE (V)
R-N 241.5 0.806 0.806 0.805 0.805 0.12 0.12
Y-N 244.0 0.810 0.810 0.813 0.813 -0.37 -0.37
B-N 242.5 0.808 0.808 0.808 0.808 0.00 0.00

POLARITY CHECK : OK
GENERAL CHECK-UP : OK
MAKE OF PT : MEHRU ELECTRICAL & MECHANICAL ENGINEERS PVT. LTD.
CONTINUITY CHECK : OK
REMARKS : TESTED OK.

Tested by Akshar Witness by Adani


Name SOUMYA KANTI BHOWMICK

Sign
Date
AKSHAR ELECINFRA PVT. LTD.

Potrebbero piacerti anche