1 MODEL PLUS 9000

2 RATING 160KVA 200KVA


3 PHASE 3 Phase in 3 Phase out
ELECTRICAL DATA
1 Input topology Digital controlled IGBT active power factor controller
2 Input wiring R/Y/B/N/G
3 Rectifier type PWM based
4 Nominal input voltage 380/400/415
5 Nominal input current 223A 278A
6 Input voltage range 320-480V
7 Input frequency range 45-55Hz @ 50Hz system
8 Input power factor >.97 @rated load
9 Inrush limitation 10*1
RMS_Norm
10 Current protection Mains input protected by input
ciruit breaker
11 Input current THD <5% @ rated load(with input
voltage THD<1%)
OUTPUT PARAMETERS

1 Power factor 0.7 lag to unity

2 Load power factor range 0.5-1

3 Output votage rates 230V


Output +1%
4 voltage Regulation

5 Rated output current 178A 222A


pf 1
Rated output current 223A 278A
6 pf 0.8

7 Voltage distortion (THDv) <5% for non-linear load/ <2%for linear load

8 Load crust ratio 3:1

9 Output frequency range 47-53Hz@50Hz system


@line mode

10 Output frequency range 47-53Hz@50Hz system Accuracy:+0.1 Hz


@battery mode
Overload capability 110% for 1 hour/125% for 10 Min/150% for 30 sec
11 online mode Overload endurance has linear relationship with overload degree
After overload time up, transfer to bypass
13 Overload capability 110% for 1 hr/125% for 10 Min/150% for 30
Battery Mode
14 Auto Re-transfer The UPS transfer from bypass mode to normal mode.
Auto re-transfer function can be disable via dedicated software
15 Maximum voltage + 10% 0%->100%->0%R Load/+6% 20%->100%->20%
deviation responding R Load
to resistive load step
16 Output short ckt Yes 1. In INV mode, the inverter will limit the output current by
Protection Software, and make the protection action according to setting of
short-circuit clearance function.
2.In Bypass mode, output current until the input breaker trip
17 Short ckt Clearance Yes and Default: Enable This function can be set via software.
Function
18 Efficiency >90% >90%
19 Transfer Time Line to battery 0ms Main input interrupt
Battery to line 0ms Main input recover
INV to bypass 0ms Turn off/common fault occur
Bypass to INV 0ms Turn on / System recover
20 Parallel Operation Up to 1+1
Capability
21 Power Unbalance Ratio Less than 5%
22 Circulation Current Less than 2%
Under No Load
23 Parallel System Output Full capacity and in sharing mode
Power
BYPASS PARAMETER
1 Bypass type SCR
2 Bypass output voltage 312V ̴ 457V
range 294V ̴ 478V Maximum range can be set by user via dedicated
software
3 Bypass output + 3Hz 47 ̴ 53 Hz
frequency range
4 Bypass over load <130% continuous working
capability >150% 5 min
5 Bypass short circuit Yes (Breaker)
protection
6 Maintenance Bypass Yes (optional)
switch

BATTERY PARAMETERS
1 Battery Voltage 504V
2 Battery Nos 42
3 Battery Low warning 11.1 V
voltage
4 Battery Shutdown 10.5 V/Battery
voltage
5 Battery Type VRLA/Tubular
cCHARGER DETAILS
1 Input Voltage Range 350-480V Full output power range
2 Rated Charger Voltage 13.5V/pc Constant current and constant voltage in the prophase
stage
3 Charging Current 20A 20A
4 Charging Voltage + 1%
Accuracy
5 Battery Under/Over Yes.
Voltage protection
6 Battery Current Yes as per the UPS rating (fuse)
Protection
MISCELLANEOUS FUNCTION
1 EPO Function Yes
2 Colour RAL Black
3 Ventilation Forced Fan Cooling
4 Protection Grade IP20
5 Conformal Coating All PCB should Be conformal Coated
6 OVCD Yes Over-Voltage Cut off-device inbuilt
7 Switches Input/output/Bypass Switches inbuilt. Maintenance bypass(optional)
COMMUNICATION INTERFACE
1 Display Panel Smart LCD+LED Panel
2 RS232/USB Standard configuration
3 Intelligent slot SNMP card (optional)
RS485 card (optional)
ENVIROMENTAL PARAMETER
1 Operating Temperature 0 ̊C ̴ 50 ̊C
Range
2 Storage Temperature 0 ̊C ̴ 65 ̊C
3 Relative Humidity 0-95%
4 Altitude <1000m for Nominal power Over 1000m the power the rating is 1%
every 100m
5 Acoustic Noise <75dB