Installation of this equipment should only be performed by skilled personnel such as The following information is a list of basic steps required to install an XW Inverter/Charger.
Actual installation procedures will vary depending upon the configuration of the intended
qualified electricians and Certified Renewable Energy (RE) System Installers. system.

120/240 Vac or
240 Vac only

Grid (AC1) Grid (AC1)

Inverting Inverting
Flashing = sell Flashing = sell
Gen (AC2) Gen (AC2)

Fault / Fault /
Charging Charging
Warning Warning

Equalize Equalize
Battery Battery

24 Vdc or 48 Vdc

All configurations must comply with local and national


electrical code jurisdiction. Consult your local certified
installer or local electrical authority to ensure compliance.

975-0238-01-01 Rev A.vsd 4/24/2007


© 2007 Xantrex Technology Inc.
1 2 3

Or….

Or….

4 5

975-0238-01-01 Rev A.vsd 4/24/2007


© 2007 Xantrex Technology Inc.
Adjustment to these configuration settings should
be done by a qualified installer. Misadjustment of
these settings could create a safety hazard or
damage the attached equipment.

1 2

3 4

Or…. Or….

975-0238-01-01 Rev A.vsd 4/24/2007


© 2007 Xantrex Technology Inc.
1 4a

Or….

2 4b

3
5

975-0238-01-01 Rev A.vsd 4/24/2007


© 2007 Xantrex Technology Inc.
1 4a

2 4b Or….

Or….

3 5

975-0238-01-01 Rev A.vsd 4/24/2007


© 2007 Xantrex Technology Inc.
xantrex

Grid
(AC1)
Inverting
Gen Flashing =
(AC2) sell

Fault /
Charging
Warning

Equalize
Battery

Hybrid
Hybrid Inverter/Charger

Inverter/Charger

All configurations must comply with local and national


electrical code jurisdiction. Consult your local certified
24 Vdc or 48 Vdc Vented Battery Enclosure
installer or local electrical authority to ensure compliance.
975-0238-01-01 Rev A.vsd/SI(6)/April 24, 2007
© 2007 Xantrex Technology Inc.
All configurations must comply with local and national
electrical code jurisdiction. Consult your local certified
installer or local electrical authority to ensure compliance.

xantrex
AC LEGEND
Grid (AC1)

Neutral Gen (AC2)


Inverting
Flashing = sell

Fault /
Charging
Warning

Equalize
Battery

HOT L1
NEUTRAL

L1 L2
HOT L2

Ground

AC OUT AC IN AC IN

Inv Grid GEN


OUT

GROUND L1 N L2 L1 N L2 L1 N L2

Hybrid Inverter/Charger

(+) (–)

(+)
ON
(–)
L1 L2

OFF

G N

Fuse Block
BATTERY
LEGEND
FUSE
FUSE
CLASS TT
CLASS

(optional) 300 AMP


300 AMP

Negative (–)

Negative (–)
Positive (+)

Positive (+)

24 Vdc or 48 Vdc
xantrex
Ground
975-0238-01-01 Rev A.vsd/SI Wiring(7)/April 24, 2007
© 2007 Xantrex Technology Inc.
xantrex

Grid
(AC1) Invertin
g
Gen Flashin
(AC2) g = sell
Fault /
Chargin
Warnin
g
g
Equaliz
e Battery

xantrex

XWBAT
BA Solar Charge
PV PV Controller
T+ – – +

Hybrid Inverter/Charger XW Power Distribution Panel

XW Conduit Box

Battery Bank

Vented Battery

All configurations must comply with local and national


Enclosure

975-0238-01-01 Rev A.vsd/SI RE Solar(8)/April 24, 2007


© 2007 Xantrex Technology Inc.
electrical code jurisdiction. Consult your local certified
installer or local electrical authority to ensure compliance.
N
xantrex

AC LEGEND Grid
(AC1)

Gen
Inverting
Flashing
(AC2) = sell

Fault / Chargin
Warning g

AC Breakers
AC Breakers (See Note 1)
Neutral Equalize
Battery

INV 1 INV 1 GEN


Bypass
IN OUT

HOT L1 xantrex
xantrex

HOT L2

Ground
BAT BAT PV PV
+ – – +

PV + BAT + PV – BAT –
(–)

AC OUT AC IN AC IN

Inv Grid GEN


OUT

L1 N L2 L1 N L2 L1 N L2
Mppt PV

DC Disconnects

Hybrid Inverter/Charger
L1 L2

(+) (–) G N

DC LEGEND

Negative (–)

120/240 Vac or
240 Vac only
Positive (+)

Ground

BTS Communication
Cable

If no Grid is available,
BATTERY
the generator can be
LEGEND
connected to the AC breakers
All configurations must comply with local and national in the XW Power Distribution
electrical code jurisdiction. Consult your local certified Panel, instead of to a separate
Negative (–) AC breaker.
installer or local electrical authority to ensure compliance.

Battery Temperature Sensor Positive (+)


(BTS)
xantrex
975-0238-01-01 Rev A.vsd/SI RE Wiring (Solar)(9)/April 24, 2007
© 2007 Xantrex Technology Inc. Ground
Charge/Diversion
Load Controller

C-Series

xantrex

Grid
(AC1) Invertin
g
Gen Flashing
(AC2) = sell
Fault / Chargin
Warning g

Equaliz
e Battery

Hybrid Inverter/Charger XW Power Distribution Panel

DC In
XW Conduit Box

Vented Battery
All configurations must comply with local and national
975-0238-01-01 Rev A.vsd/SI RE DL(10)/April 24, 2007
Enclosure
electrical code jurisdiction. Consult your local certified
© 2007 Xantrex Technology Inc.
installer or local electrical authority to ensure compliance.
L1 L2

G N

XW Inverter/Charger
Communication Ports
CM/CMR BTS

BAT PV/Load COM COM


POS POS NEG NEG

(on Bottom of Inverter)


N

xantrex

AC Breakers (See Note 1)

INV 1 GEN
Bypass INV 1 OUT
IN

AC LEGEND

Neutral

HOT L1 (–)

HOT L2
AC OUT AC IN AC IN

Inv
Ground OUT
Grid GEN DC Disconnect

L1 N L2 L1 N L2 L1 N L2
Mppt PV

Hybrid Inverter/Charger

All configurations must comply with local and national If no Grid is available, the generator
electrical code jurisdiction. Consult your local certified can be connected to the AC breakers in the
installer or local electrical authority to ensure compliance. XW Power Distribution Panel, instead of to a
separate AC breaker.

975-0238-01-01 Rev A.vsd/SI RE DL Wiring(11)/April 24, 2007 Vented Battery


© 2007 Xantrex Technology Inc. Enclosure
xantrex
xantrex xantrex

Grid Grid
(AC1) Invertin (AC1) Invertin
g g
Gen Flashin Gen Flashin
(AC2) g = sell (AC2) g = sell
Fault / Fault /
Chargin Chargin
Warnin Warnin
g g
g g
Equaliz Equaliz
e Battery e Battery

xantrex

+
XW Solar
BAT BAT

PV PVCharge Controller
– +

Hybrid Inverter/Charger Hybrid Inverter/Charger XW Power Distribution Panel

xantrex

XW Solar
BAT BATPV PVCharge Controller
+ – – +

XW Conduit Box XW Conduit Box

975-0238-01-01 Rev A.vsd/DI RE Solar(12)/April 24, 2007 All configurations must comply with local and national
© 2007 Xantrex Technology Inc. Vented Battery
Enclosure
electrical code jurisdiction. Consult your local certified
installer or local electrical authority to ensure compliance.
L1 L2

All configurations must comply with local and national G N

electrical code jurisdiction. Consult your local certified


installer or local electrical authority to ensure compliance.

AC LEGEND N
xantrex xantrex XW Solar
Charge
Neutral Controller

HOT L1 AC Breakers (See Note 1)

INV 1 IN INV 2 IN Grid Grid INV 1 OUT INV 2 OUT INV 1 IN INV 2 IN
(Grid) (Grid) Bypass Bypass (AC Loads) (AC Loads) (Gen) (Gen)

HOT L2 Inverter AC
xantrex Distribution
Ground Panel
NEUTRAL

L1 L2

BAT BAT PV PV
+ – – +

(–)

AC OUT AC IN AC IN AC OUT AC IN AC IN

Inv Inv Grid


Grid GEN GEN
OUT OUT

DC
L1 N L2 L1 N L2 L1 N L2 L1 N L2 L1 N L2 L1 N L2
Mppt PV
Disconnects
CC CC PV
+
PV GROUND
+ + +

Hybrid Inverter/Charger Hybrid Inverter/Charger

xantrex

BAT BAT PV PV
+ – – +

DC LEGEND

BATTERY
LEGEND Negative (–)

If no Grid is available, the generator can be


connected to the AC breakers in the XW Power Negative (–) Positive (+)
Distribution Panel, instead of to a separate AC breaker.
Positive (+) Ground
975-0238-01-01 Rev A.vsd/DI RE Solar Wiring(13)/April 24, 2007
© 2007 Xantrex Technology Inc.
xantrex
24 Vdc or 48 Vdc Ground
Charge/Diversion Load Charge/Diversion Load
Controller Controller

C-Series C-Series

xantrex xantrex

Grid (AC1) Grid (AC1)

Inverting Inverting
Flashing = sell Flas hing = sell

Gen (AC2) Gen (AC2)

Fault / Fault /
Charging Charging
Warning Warning

Equalize Equalize
Battery Battery

Hybrid Inverter/Charger Hybrid Inverter/Charger XW Power Distribution Panel


Communication

DC In
XW Conduit Box XW Conduit Box

975-0238-01-01 Rev A.vsd/DI RE DL(14)/April 24, 2007 All configurations must comply with local and national
© 2007 Xantrex Technology Inc.
electrical code jurisdiction. Consult your local certified
installer or local electrical authority to ensure compliance.
L1 L2

G N

All configurations must comply with local and national


electrical code jurisdiction. Consult your local certified
installer or local electrical authority to ensure compliance.
CM/CMR BTS

BAT PV/Load COM COM


POS POS NEG NEG

N
xantrex xantrex

Grid (AC1)

Inverting
Flashing = sell

Gen (AC2)

Fault /
Charging
Warning

Equalize
AC Breakers (See Note 1)
Battery

INV 1 IN INV 2 IN Grid Grid INV 1 OUT INV 2 OUT INV 1 IN INV 2 IN
(Grid) (Grid) Bypass Bypass (AC Loads) (AC Loads) (Gen) (Gen)

(–)

AC OUT AC IN AC IN AC OUT AC IN AC IN

Inv Inv Grid


Grid GEN GEN
OUT OUT

L1 N L2 L1 N L2 L1 N L2 L1 N L2 L1 N L2 L1 N L2
Mppt PV

DC Disconnects

Hybrid Inverter/Charger Hybrid Inverter/Charger

BTS Communication
Cable

If no Grid is available, the generator can be connected


to the AC breakers in the XW Power Distribution Panel, instead
of to a separate AC breaker.
xantrex

Vented Battery
Enclosure
975-0238-01-01 Rev A.vsd/DI RE DL Wiring(15)/April 24, 2007 Battery Temperature
Sensor (BTS)
© 2007 Xantrex Technology Inc.

Potrebbero piacerti anche