Sei sulla pagina 1di 9

Multipor external thermal insulation composite systems (ETICS) 3.

0
Mechanical fastening of ETICS 3.4

Mechanical fastening of ETICS 3.4

Determining wind loads and Mechanical fixings are used to reli- When the wind blows against a
anchor dimensions ably absorb and distribute these building, it backs up and exerts
The Multipor ETICS is a bonded and loads. They work by transferring the pressure on the windward facade.
mechanically fixed system governed wind suction load into the load-bear- This is referred to as ram pressure.
by the structural requirements of ing substrate. But the wind does not remain
DIBt approval Z-­33.43-­596. Multipor ‘suspended‘ on the facade, it is
ETICS mineral insulation boards Wind suction explained deflected upwards over the roof and
applied to the facade are subject to In technical terms, wind suction is around the building. This creates 3
various load types during installation a force exerted on a surface gen- turbulence at the corners of the
and subsequent use. Both the dead erated by wind flow at the surface. building. Airborne gas particles
load of the system and the hygro- This phenomenon is known as the entrained in the wind flowing past
thermal loads are absorbed by the Bernoulli effect. David Bernoulli are carried to the surface, generat-
bond strength of the Multipor light- discovered the relation between ing a negative pressure, or suction,
weight mortar. In most cases wind pressure, velocity and flow cross- perpendicular to the areas around
loads constitute the greatest loading section. The effect can be seen in which the wind flows.
in terms of force. It is easy to imagine the way a river flows around a
that wind blowing onto the facade will bridge pier. By reducing the flow The higher the wind speed and les-
exert compressive forces on it. All cross-section, the flow rate of the ser the turbulence, the greater this
Multipor ETICS system components water increases. negative pressure. The determina-
can easily absorb these forces tion of wind loads acting in corners
and transmit them to the facade. This effect also occurs in buildings and turbulent areas of buildings is
At the same time, wind suction loads when wind circulates around them governed by DIN EN 1991-­1-­4 in
can occur in the corners of buildings (Fig.1). Germany.
which are greater than wind pressure
forces in absolute terms.

Fig. 1: Action of wind suction on the building envelope

Wind suction
Wind pressure

Wind load

Plan view of building

Wind suction

Multipor ETICS 63
3.0 Multipor external thermal insulation composite systems (ETICS)
3.4 Mechanical fastening of ETICS

Fig. 2: Wind zone map (as per DIN 1991-1-4 NA) Wind suction forces are always
greatest at the corners of buildings.
4
4 To simplify the wind load calcula-
Schleswig- tions, these forces are always
Holstein 3
4 regarded as static surface loads.
Mecklenburg-
3 Western Pomerania
Hamburg
Anchor fixings
Bremen
Wind suction forces are absorbed
by the anchors, which invariably
Lower Saxony
2 Berlin require national technical approval
Brandenburg when used in conjunction with an
Saxony-Anhalt external thermal insulation com-
North Rhine-Westphalia
posite system. Wind suction forces
generally constitute the greatest
Saxony
load exerted on anchors and are
Thuringia

Hessen
therefore used as the basis for
determining the design value, even
Rhineland- 1 if other loads are absorbed by the
Palatinate
anchor.

Saarland
Bavaria
The length and type of anchor de-
Baden-
pends on the substrate, e.g. con-
Württemberg
crete, solid block, perforated block
2 or AAC, as well as the thickness
of the insulation.

Determining wind suction forces

Wind zone 4 Wind zone 3 Wind zone 2 Wind zone 1


The wind load acting on the facade
is determined in accordance with
DIN EN 1991-­1-­4 together with the
relevant national application docu-
Wind suction also occurs on the lee- A tall building on the North Sea ment DIN EN 1991-1-4/NAD.
ward side of the building due to wake coast is exposed to considerably The Federal Republic of Germany as
turbulence. stronger wind loads than a de- a whole is divided into 4 wind zones
tached house in Frankfurt am Main, with different wind velocities vb,0 (vref)
In coastal areas especially, wind for example. and wind velocity pressures qb,0
suction can exert significant forces on (Table 1). As the wind zone map
flat roofs and facades. The ETICS absorbs the stresses (Fig. 2) shows, most of Germany is
generated by the wind loads via the covered by Zones 1 and 2. The rele-
According to DIN EN 1991­1-­4, the lightweight mortar adhesive bond vant wind load for a building can
wind load depends on the building on the wall surface and the anchor either be taken from the wind zone
shape, the wind zone (Fig. 2) and local fixings inserted into the load-bear- map or from an online table pub-
topography. ing substrate. lished by the German Institute for
Building Technology (DIBt).

64 Multipor ETICS
Multipor external thermal insulation composite systems (ETICS) 3.0
Mechanical fastening of ETICS 3.4

Practical method
Table 1: Basic wind velocities vb,0 (vref) and associated velocity pressures qb,0
depending on the wind zone The practical method is even easier
to use. Like the simplified method, it
Wind zone vb,0 (vref) qb,0
applies only to:
1 22.5 m/s 0.32 kN/m2
■■ building heights up to 25 m
2 25.0 m/s 0.39 kN/m2
■■ rectangular buildings
3 27.5 m/s 0.47 kN/m2
■■ height-to-width ratio h/d < 2
4 30.0 m/s 0.56 kN/m2

This method can be used only for


The length, width and height of There are three different ways of cal- wind zones 1 to 3. The classification 3
each face of the building must be culating the critical wind load – and of wind suction into different zones as
geometrically measured. There are thus the number of anchor fixings shown in Figure 3 does not apply with
four different wind suction zones required – the simplified method, the this method.
in total (A, B, C and E). Zone D practical method and the detailed
describes the windward side where method. All you have to do is determine the
wind pressure forces are generated required number of anchor fixings
(see Fig. 3). The length of each Simplified method for the area where the wind suction
wind suction zone is determined by The simplified method assumes forces are greatest (Zone A). Then
the geometrical constraints and that the velocity pressure for build- fit the resulting number of anchor
DIN EN 1991­-1-­4 regulations. ings up to 25 m tall is constant over fixings uniformly to all wall surfaces.
the entire height of the building in
The strongest wind suction forces accordance with the standard. Detailed method
occur in Zone A and decrease signifi- The maximum height is critical. The detailed calculation method
cantly in the direction of the wind is always used with buildings over
(Zone B, C) (see Fig. 1 and 3). Zone E The corresponding critical velocity 25 m tall, although it can be used
is on the leeward side of the building pressures for the different wind for any other building too.
and corresponds in absolute terms suction zones are shown in Table 2.
to Zone C. The windward side of the
building is defined as Zone D. The
compressive stress generated by the
Fig. 3: Wind suction zones
wind has a positive value. Wind suc-
tion in wind zones A, B, C and E has Plan view
a negative value. Since the wind can A B C
blow from any direction, Zone A may Wind

equally occur at any corner of the D E


building. Thus separate calcula-
tions must be performed for all four C
A B
wind directions on a rectangular
Elevation
plan view to determine the effect on
Wind
the building and the results from
each calculation must be superim- A B C
posed on each wall.

Multipor ETICS 65
3.0 Multipor external thermal insulation composite systems (ETICS)
3.4 Mechanical fastening of ETICS

Table 2: Extract from DIN EN 1991-1-4

Wind zone Wind velocity pressure qp in kN/m2


for a building height h within the limits of

h ≤ 10m 10 m < h ≤ 18 m 18 m < h ≤ 25 m


1 Inland 0.50 0.65 0.75
Inland 0.65 0.80 0.90
2
Coast and islands in the Baltic Sea 0.85 1.00 1.10
Inland 0.80 0.95 1.10
3
Coast and islands in the Baltic Sea 1.05 1.20 1.30
Inland 0.95 1.15 1.30
North Sea and Baltic Sea coast and
4 1.25 1.40 1.55
islands in the Baltic Sea
Islands in the North Sea 1.40 – –

Table 3: Aerodynamic coefficient cpe,1 for vertical walls of rectangular buildings

Zone A B C E

h/d cpe,1
≥5 −1.7 −1.1 −0.7 −0.7
1 −1.4 −1.1 −0.5 −0.5
≤ 0.25 −1.4 −1.1 −0.5 −0.5

Intermediate values should be interpolated.


Clarification of h/d: h is the building height, d the length or width of the building, whichever is the lesser.

A detailed wind load calculation must be carried out in accordance with DIN EN 1991­-1-­4 and subject to the national
application document (NAD) for all building for which the simplified or practical method does not apply (the maximum
height is critical).

The velocity pressures and aerodynamic coefficients must be calculated for all areas of the building facade, differ-
entiated by height and subject to the shape of the building. It is customary and indeed advisable to use software to
calculate wind suction, because it enables specific wind suction loads for a given building to be determined.
This calculation method can also be used with buildings which permit the simplified wind load calculation method.
Compared with the simplified method, this detailed calculation method can reduce the number of anchor fixings
required – especially for building heights of just over 10 or 18 m – and thus reduce costs.

Critical wind loads


To calculate critical wind loads, you need to know the wind zone, the associated basic velocity pressure qb,0, the
height-related peak velocity pressure qp(z) and the aerodynamic coefficients cpe (Table 1). These are also known
as external pressure coefficients. External pressure coefficients have a negative value and are shown in Table 3.
A negative external pressure coefficient indicates that wind suction occurs at the area under investigation.

The critical (peak) velocity pressure qp(z) depends on the height of the building and is calculated in accordance
with DIN 1991-1-4, NA.B3.3.

66 Multipor ETICS
Multipor external thermal insulation composite systems (ETICS) 3.0
Mechanical fastening of ETICS 3.4

For building heights ≤ 7 m the following applies: qp(z) = 1.5 · qb

The critical wind loads we (we = qp(z) · cpe) for the respective suction zones are derived from the product of the peak
velocity pressure qp(z) and the external pressure coefficients.

Comparison of wind suction loads calculated by means of the detailed and the simplified method (Table 4)
Calculating the effective wind suction load using the detailed calculation method:
Small building, h = 7 m, h/d = 2, wind zone 1

Peak velocity wind pressure qb(z), as a function of height, as per DIN EN 1991-­1­-4, NA.B.1:
qp(z) = 1.5 · qb,0 = 1.5 · 0.32 kN/m² = 0.48 kN/m² 3
Note: The value is smaller than the value given in Table 2 (0.50 kN/m²). This is because the values in Table 2
are designed for the simplified calculation method and include a safety margin.

Table 4: Comparison of detailed and simplified calculation methods

Zone Design wind suction Simplified calculation method

A we,A = qp(z) · cpe,1A = 0.48 kN/m² · −1.4751) = −0.71 kN/m² 0.50 · −1.475 = −0.74 kN/m²

B we,B = qp(z) · cpe,1B = 0.48 kN/m² · −1.1 = −0.53 kN/m² 0.50 · −1.1 = −0.55 kN/m²

C (and E) we,C = qp(z) · cpe,1C = 0.48 kN/m² · −0.55 1)


= −0.26 kN/m² 0.50 · −0.55 = −0.28 kN/m²

1)
numerical values interpolated

The values obtained can be used to determine the number of anchor fixings required. The comparative values shown
in the right-hand column are derived from the simplified calculation method. These values can be read straight from
Table 2 without having to calculate the height-related peak velocity pressure and are then simply multiplied by the
aerodynamic (external pressure) coefficients.

Once the wind suction loads have been calculated, the quantity of anchor fixings required can be determined from
Table 7.

The following examples illustrate the differences between the two methods.

Examples of simplified and detailed calculation method

1. Sample wind suction load calculation

Initial conditions:
Small, rectangular house, simplified method
Wind load zone 1
Dimensions: w = 10 m, l = 14 m, h = 10 m

Calculated action of the wind loads:


Figures 4 and 5 show the forces exerted by wind that have to be considered in accordance with the standard. It is clear from
Figure 4 that wind suction and wind pressure respectively are assumed to be constant across the height of the building.

Multipor ETICS 67
3.0 Multipor external thermal insulation composite systems (ETICS)
3.4 Mechanical fastening of ETICS

The wind suction load is greatest Fig. 4: Wind zones for gable and side elevation
at the corners (edge zone) within
the first fifth of the longer windward Roof
side of the building or the height Wind Wind

10
A B A B C
(the smaller value applies).

Gable elevation Side elevation


Since the wind can come from any
direction, these wind suction loads Fig. 5: Wind zones for longitudinal and transverse plan view
can occur vertically at any corner
area. A corresponding wind suction
load is also applied to the other
sections of walls which run parallel
to the wind direction.

14
10
Wind Wind

This example shows that to factor


in the two wind directions that are
relevant to Zone A on the gable end,
40% of the surface of the gable wall Plan view Plan view
must be regarded as the corner
area.
Table 5: Number of anchor fixings based on the simplified method

Zone we nanchor
When dealing with low wind loads
and low buildings and to avoid A 0.74 kN/m² 4.4

design faults, it is therefore advis- B 0.55 kN/m² 3.3*

able to design the anchors for these C 0.28 kN/m² 1.6*


corner margins and use the same
* Minimum number of fixings 1 anchor/plate; 4.3/m²
spacing and number across the
entire surface of the building (practical method).

Determining the number of anchor fixings


Using the wind suction forces derived from the simplified calculation method, it is now possible to work out
the number of anchor fixings required per square meter from Table 7.

Zone A is critical. The number of anchor fixings used must not fall below the minimum number specified
in the national technical approval (one anchor per mineral insulation board).

2. Sample wind suction load calculation


Initial conditions:
Tall rectangle building, flat roof, detailed and simplified calculation method
Wind load zone 1
Dimensions: w = 15 m, l = 34 m, h = 24 m
(Fig. 6 and 7)

68 Multipor ETICS
Multipor external thermal insulation composite systems (ETICS) 3.0
Mechanical fastening of ETICS 3.4

Fig. 6: Wind zones and wind forces with the required number of anchor fixings calculated for all wind directions using
the simplified method.

Gable elevation Longitudinal side

Zone A B A Zone A B C B A

we = [kN/m2] 1.11 0.83 1.11 we = [kN/m2] 1.11 0.83 0.41 0.83 1.11
24

nanchor = [unit/m2] 8 6 8 nanchor = [unit/m2] 8 6 4 6 8

3
6.8 1.4 6.8 3 12 4 12 3

Wind distribution across the plan view is equivalent to the previous example in qualitative terms. Figures 6 and 7
show the critical zones (taking account of all wind directions), the loads and the number of anchor fixings required
based on the simplified and the detailed calculation method.

Fig. 7: Wind zones and wind forces with the required number of anchor fixings calculated for all wind directions using
the detailed method.

Gable end Longitudinal side

Zone A2 B2 C2 B2 A2
Zone A B A we = [kN/m ]2
1.05 0.83 0.38 0.83 1.05
9

nanchor = [unit/m2] 8 6 4 6 8
we = [kN/m2] 1.08 0.83 1.08
24

Zone A1 B1 C1 B1 A1
we = [kN/m2] 0.88 0.69 0.32 0.69 0.88
15

nanchor = [unit/m2] 8 6 8
nanchor = [unit/m2] 6 4 4 4 6

6.8 1.4 6.8 3 12 4 12 3

Table 6: Comparison of wind suction force we in kN/m², simplified and detailed method

Wind zone A B C
Simplified calculation method 1.11 0.83 0.41
Detailed calculation method
Long side
Calculated > 15 m 1.05 0.83 0.38
Calculated < 15 m 0.88 0.69 0.32
Short side
Total height 1.08 0.83 –

Multipor ETICS 69
3.0 Multipor external thermal insulation composite systems (ETICS)
3.4 Mechanical fastening of ETICS

With the detailed method, the wind forces are no longer constant over the height of the building (Fig. 7).
The critical reference heights and height ranges are determined in accordance with DIN EN 1991­-1-­4 specifications.

Fig. 7 shows that it is advisable on economic grounds to determine the wind loads for the different zones and to
calculate the number of anchors required using Table 7.

The geometric constraints of this example, whereby the smaller width is smaller than the height, means that no
height differentiation is carried out on the gable end.

General determination of the number of anchors


With the aid of these wind suction forces it is now easy to work out the number of anchor fixings required –
based on one square meter and allowing for the anchor load class.

Table 7: Design number of anchor fixings required per m2 as a function of height and wind zone, based on the simplified method

Building height
< 10 m < 18 m < 25 m
Wind zone (h/d ≤ 2) A B C/E A B C/E A B C/E
we [kN/m2] 0.7383) 0.553) 0.2753) 0.9593) 0.7153) 0.3583) 1.1063) 0.8253) 0.4133)
Wind zone 1
Anchor load class wRD [kN] 0.11) 7.4 5.5 2.83) 9.6 7.2 3.63) 11.1 8.3 4.13)
– Inland
Anchor load class wRD [kN] 0.1672) 4.4 3.33) 1.63) 5.7 4.3 2.13) 6.6 4.9 2.53)
we [kN/m2] 0.9593) 0.7153) 0.3583) 1.183) 0.883) 0.443) 1.3283) 0.993) 0.4953)
Wind zone 2
Anchor load class wRD [kN] 0.11) 9.6 7.2 3.63) 11.8 8.8 4.4 13.3 9.9 5.0
– Inland
Anchor load class wRD [kN] 0.1672) 5.7 4.3 2.13) 7.1 5.3 2.63) 8.0 5.9 3.03)
we [kN/m ] 2
1.254 3)
0.935 3)
0.468 3)
1.475 3)
1.1 3)
0.55 3)
1.623 3)
1.21 3)
0.6053)
Wind zone 2
– Coast and islands Anchor load class wRD [kN] 0.11) 12.5 9.4 4.7 14.8 11.0 5.5 16.2 12.1 6.1
in the Baltic Sea
Anchor load class wRD [kN] 0.167 2)
7.5 5.6 2.83)
8.8 6.6 3.33)
9.7 7.2 3.63)
we [kN/m2] 1.183) 0.883) 0.443) 1.4013) 1.0453) 0.5233) 1.6233) 1.213) 0.6053)
Windzone 3
Anchor load class wRD [kN] 0.11) 11.8 8.8 4.4 14.0 10.5 5.2 16.2 12.1 6.1
– Inland
Anchor load class wRD [kN] 0.167 2)
7.1 5.3 2.63)
8.4 6.3 3.13)
9.7 7.2 3.63)
we [kN/m2] 1.5493) 1.1553) 0.5783) 1.773) 1.323) 0.663) 1.9183) 1.433) 0.7153)
Wind zone 3
– Coast and islands Anchor load class wRD [kN] 0.11) 15.5 11.6 5.8 17.7 13.2 6.6 19.2 14.3 7.2
in the Baltic Sea
Anchor load class wRD [kN] 0.1672) 9.3 6.9 3.53) 10.6 7.9 4.03) 11.5 8.6 4.3
we [kN/m2] 1.4013) 1.0453) 0.5233) 1.6963) 1.2653) 0.6333) 1.9183) 1.433) 0.7153)
Wind zone 4
Anchor load class wRD [kN] 0.1 1)
14.0 10.5 5.2 17.0 12.7 6.3 19.2 14.3 7.2
– Inland
Anchor load class wRD [kN] 0.167 2)
8.4 6.3 3.13)
10.2 7.6 3.83)
11.5 8.6 4.3
Wind zone 4 we [kN/m ]2
1.844 3)
1.375 3)
0.688 3)
2.065 3)
1.54 3)
0.77 3)
2.286 3)
1.705 3)
0.8533)
– North Sea and
Baltic Sea coast Anchor load class wRD [kN] 0.11) 18.4 13.8 6.9 20.7 15.4 7.7 22.9 17.1 8.5
and islands in the
Baltic Sea Anchor load class wRD [kN] 0.167 2)
11.0 8.2 4.13)
12.4 9.2 4.6 13.7 10.2 5.1
we [kN/m ]2
2.065 3)
1.54 3)
0.77 3)
Wind zone 4
– Islands in the Anchor load class wRD [kN] 0.1 1)
20.7 15.4 7.7
North Sea
Anchor load class wRD [kN] 0.1672) 12.4 9.2 4.6
1)
Insulation thickness 60/80 mm  2)
Insulation thickness 100 bis 300 mm  3)
Minimum number of anchors 1 anchor/board; 4.3/m2

70 Multipor ETICS
Multipor external thermal insulation composite systems (ETICS) 3.0
Mechanical fastening of ETICS 3.4

Sample calculation of the number of anchors as per Table 7


■■ Incident wind force we: 0.96 kN/m²
■■ Force wRD absorbed per anchor: 0.167 kN/anchor
■■ Number of anchors required: nanchor = we/wRD = 0.96 kN/m²/0.167 kN/anchor = 5.7 anchor/m²
■■ Selected: 6 anchor/m² or 1.5 anchor per board (390 · 600 mm)

The comparison between the simplified and detailed method in Examples 1 and 2 indicates that there is relevant scope
for savings, especially with building heights up to 15 m, although a detailed calculation of the number of anchors
required for a residential home (maximum height 10 m) yields no appreciable savings.

It is clear from Example 2 that the number of anchors required can be reduced when calculating wind loads using the 3
detailed method compared with the simplified method (see Figures 6 and 7). A wind load calculation of this type should
be undertaken by an engineering office.

In the calculated example, 2 anchors/m² can be saved over a height of 15 m and a width of 30 m on the two longitudinal
sides (excluding Zone C, where no savings can be made).

Number of anchors saved: 2 longitudinal sides · 2 anchors/m² · 15 m (height) · 30 m (length) = 1,800 anchors

The cost of anchor fixings includes material and labor costs. It is clear that the detailed method is a more cost-effective
option for the building in this example. At the same time, the building contractor is responsible for ensuring that the
calculated number of anchors is actually installed in accordance with the static wind load calculation.

The steps for calculating the wind load and number of anchors required are summarized below.
■■ Determine the wind zone according to the location of the building
■■ Consider the prevailing wind directions, determine the wind suction zones (A, B, C) and how they are overlaid
■■ Calculate the aerodynamic coefficients (cpe)
■■ Calculate the height, graduations in height and height-related velocity pressures [qp(z)]
■■ Calculate the peak suction forces by multiplying the velocity pressures by the aerodynamic coefficients for all
surface areas.

The wind loads obtained in this way can then be used to calculate the number of anchors required. The rules of
DIN EN­1991­-1­-4 and the associated national annex must be complied with.

The procedure for the simplified method is similar, except there is no need to calculate the height-related velocity
pressures, since the wind pressure is assumed to be constant across the entire height of the building.

With the practical method, all you need to do is multiply the wind pressure from Table 2 by the aerodynamic
coefficient for Zone A (edge zone), then apply the number of anchors obtained to the entire building.

The relevant anchor load class depends on the thickness of the insulation.
Our Multipor technical advisers are happy to help you determine the precise anchor dimensions. You can find your
technical adviser on the contact page of our website at www.multipor.com.

Multipor ETICS 71

Potrebbero piacerti anche