Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Number of Earthing
Electrodes (Strips, Plates
and Pipes) – part 1
By jiguparmar | April, 5th 2013 | 40 comments | Save to PDF
Share!
Home / Technical Articles / How to Determine Correct Number of Earthing Electrodes (Strips, Plates
Introduction
Number of Earthing Electrode and Earthing Resistance depends on
the resistivity of soil and time for fault current to pass through (1 sec
or 3 sec). If we divide the area for earthing required by the area of one
earth plate gives the number of earth pits required.
How to Determine Correct Number of Earthing Electrodes (Strips,
Plates and Pipes) – part 1
There is no general rule to calculate the exact number of earth pits and
size of earthing strip, but discharging of leakage current is certainly
dependent on the cross section area of the material so for any
equipment the earth strip size is calculated on the current to be
carried by that strip.
However a strip with lesser size which can carry a current of 35A can
be used for body earthing. The reason for using 2 earth pits for each
body and neutral and then shorting them is to serve as back up. If one
strip gets corroded and cuts the continuity is broken and the other
leakage current flows through the other run thery by completing the
circuit.
Similarly for panels the no of pits should be 2 nos. The size can be
decided on the main incomer circuit breaker.
For example if main incomer to breaker is 400A, then body earthing for
panel can have a strip size of 25×6 mm which can easily carry 100A.
Number of earth pits is decided by considering the total fault current to
be dissipated to the ground in case of fault and the current that can be
dissipated by each earth pit. Normally the density of current for GI strip
can be roughly 200 amps per square cam. Based on the length and dia
of the pipe used the number of earthing pits can be finalized.
R=100xρ/2×3.14xL (loge(4xL/d))
Where:
ρ = Resistivity of soil (Ω meter),
L = Length of electrode (cm),
D = Diameter of electrode (cm)
Example:
Calculate number of CI earthing pipe of 100mm diameter, 3 meter
length. System has fault current 50KA for 1 sec and soil resistivity is
72.44 Ω-Meters.
Current Density At The Surface of Earth Electrode (As per IS
3043):
Max. allowable current density I = 7.57×1000/(√ρxt) A/m2
Max. allowable current density = 7.57×1000/(√72.44X1) =
889.419 A/m2
Surface area of one 100mm dia. 3 meter Pipe = 2 x 3.14 x r x L =
2 x 3.14 x 0.05 x3 = 0.942 m2
Max. current dissipated by one Earthing Pipe = Current
Density x Surface area of electrode
Max. current dissipated by one earthing pipe = 889.419x 0.942 =
837.83 A say 838 Amps
Number of earthing pipe required = Fault Current / Max.current
dissipated by one earthing pipe.
Number of earthing pipe required = 50000/838 = 59.66 Say 60
No’s.
Total number of earthing pipe required = 60 No’s.
Resistance of earthing pipe (isolated) R =
100xρ/2×3.14xLx(loge (4XL/d))
Resistance of earthing pipe (isolated) R = 100×72.44
/2×3.14x300x(loge (4X300/10)) = 7.99 Ω/Pipe
Overall resistance of 60 no of earthing pipe = 7.99/60 = 0.133 Ω.
Example:
Calculate GI strip having width of 12mm , length of 2200 meter buried
in ground at depth of 200mm, soil resistivity is 72.44 Ω-meter.
Resistance of earth strip(Re) = 72.44/2×3.14x2200x(loge
(2x2200x2200/.2x.012)) = 0.050 Ω
From above calculation overall resistance of 60 no of earthing
pipes (Rp) = 0.133 Ω.
And it connected to bury earthing strip. Here net earthing
resistance = (RpxRe)/(Rp+Re)
Net eatrthing resistance = (0.133×0.05)/(0.133+0.05) = 0.036 Ω
9 3.61
10 3.8
For electrodes equally spaced around a hollow square, e.g. around the
perimeter of a building, the equations given above are used with
a value of λ taken from following table.
Example:
Calculate Total Earthing Rod Resistance of 200 Number arranges in
Parallel having 4 Meter Space of each and if it connects in Hollow
Square arrangement. The Earthing Rod is 4 Meter Long and having
12.2mm Diameter, Soil Resistivity 500 Ω.
a = 500/(2×3.14x136x4) =0.146
Ra (Parallel in Line) =136.23x (1+10×0.146/200) = 1.67 Ω.
If earthing rod is connected in Hollow square than rod in each side of
square is 200 = (4n-1) so n = 49 No.
Lighting Arrestor
2 25 X 3 mm (Copper)
PLC Panel
3 25 X 3 mm (Copper)
Transformer Body
5 50X6 mm (GI)
Distribution Board
8 25 X 6 mm (GI)
Motor up to 5.5 kw
9 4 mm2 (GI)
Motor 5.5 kw to 55 kw
10 25 X 6 mm (GI)
Motor 22 kw to 55 kw
11 40 X 6 mm (GI)
Motor Above 55 kw
12 55 X 6 mm (GI)
LA, High current less than Normal Soil/ up to 50 ohm-meter Single Electrode
Equipment./ 50kA 1 ohm
Sandy Soil/ between 50 to 2000 ohm- meter Multiple
Electrodes
Rocky Soil/ More than 2000 ohm- meter Multiple
Electrodes
PRS, UTS, RTUs, less than Normal Soil/ up to 50 ohm-meter Single Electrode
Data processing 0.5 ohm
centre etc./5KA Sandy Soil/ between 50 to 2000 ohm- meter Multiple
Electrodes
40 x 6 2 Kg Per meter
GI Earthing Plate:
Plate Weight
GI Earthing Pipe:
Pipe Weight
GI Earthing Wire:
Plate Weight
6 Swg 5 meter in 1 Kg
8 Swg 9 meter in 1 Kg