TAKENAKA VIETNAM METHOD FOR GROUNDING RESISTANCE TEST

Flow Descriptive Procedures


Process Constraint Corrective Measures
Point 1: At Start, all participants for Grounding Resistance TestEarth Resistance
are present.

(1) Start. Point 2: Test instrument, reference drawings and Test Forms
should be available.

Point 3: Verify
the wires probesthat
arethe earth spike
separately P & C are properly driven and
connected.
(2) Tester, Dwg. and Forms.

Inspect the distance of Electrodes E, P & C and ensure that they


are 5~10 meters apart.

(3) Verification and


Inspection. Point 4: Check battery and select X 100 Ω range. This is the initial
setting of Earth Tester since the actual reading is unpredictable.

Point 5: Connect the test probe ( Green, Yellow, Red) to Earth


Resistance Tester.
Measure the Ground Resistance: Adjust the setting gradually
(4) Check Tester then set the
range to maximum setting . according to the displayed result in order to get the accurate
reading.

Point 6: Check the reading (follow TCVN).


(B) Drive additional
(5) Measure Ground. Res. then rod if necessary then
adjust setting gradually. network.
Point 7: Record the test result to Test Form (E-TC-02) and
keep as final after signed by respective attending parties.

Result Good
Follow TCVN Standard
Point A: Trace the caused of high ground resistance.

(6) Test (A) Trace to caused of


result. failure. Point B: Drive additional rod if necessary then connect to
the object electrode being tested as a network to reduce the
resistance reading then check again the ground.

(7) Read and Record


the Test Result to Test
Form.
WI/OPR - E002
GROUNDING RESISTANCE TEST Rev. 0
Date / /

Supplementary Information
Earth Resistance Tester

Grounding Resistance Test

Form (FM/OPR - E002)


TAKENAKA VIETNAM TEST REPORT FOR GROUNDING RES

Project HVC BINH DUONG NEW PROJECT Name Make


Location My Phuoc-Binh Duong Instrument Used
Climate ✘ Sunny Rainy Cloudy Digital Earth Tester Kyorit

Grounding Materials Used


Grounding Application And Name Of Classification Grounding Conductor
No Equipment To Be Grounded (EA, EB or EC ) ( Size and Type )

Copper Plate Copper Rod

1 Main system (1/A-B Axis) EA ✘


Cu 70mm2
2 Low Voltage system (Guard house) Ec ✘
Cu 35mm2
3 Lightning system (E1 Axis) ELA ✘
Cu 70mm2
4 Lightning system (E11 Axis) ELA ✘
Cu 70mm2

Remarks :
Ref. : IEEE Std 142-1991(4.1.2 Recomme
Remarks :

Mentioned: Resistances follow TCVN standard (ohms) range are


suitable for industrial plant substation, building, and large
installations.

Prepared By: KINDEN VIETNAM Check By: KINDEN VIETNAM

Sign over printed name Sign over printed name

Date: Date:
E-002
OR GROUNDING RESISTANCE Rev. 0
Date / /

Maker Type/Model Serial No. Calibration date

24 - March - 2019
Kyoritsu 4105A

Ground Resistance in Ω (ohms)


Grounding Conductor
( Size and Type ) Multiple Rods Network/Combined Network/Combined
Single ( Individual test ) Test Test Yes No
Copperplate
Rod 1 Rod 2 Rod 3 Rod 1, Rod 2 and Rod 3 Copperplate &Rod

Cu 70mm2 2.5 Ω ✘

Cu 35mm2 1.7 Ω ✘

Cu 70mm2 5.2 Ω ✘

Cu 70mm2 2.2 Ω ✘

Legend:
Ref. : IEEE Std 142-1991(4.1.2 Recommended Acceptable Value)

X - Not applicable
X - Not applicable
d: Resistances follow TCVN standard (ohms) range are generally found
ble for industrial plant substation, building, and large commercial Ground Resistance follow
installations. TCVN √ - Result/Check box
standard

Approved By: TAKENAKA VIETNAM

Sign over printed name

Date: