ODOUR CONTROL
FOR BACK OF HOUSE AREAS IN HOTELS
JONATHAN BUNGE (M.ENG CHEMICAL), SHANNON ROGER (B.ED)
AND DR ALLAN HECKENBERG (PhD) I AIREPURE AUSTRALIA 2016

Back of house areas may be a common source of offensive odours and odour complaints for your
hotel. These areas may include garbage/refuge rooms, loading docks, commercial kitchens, designated
outdoor smoking areas or sewer vents.

T
his article seeks to discuss possible The EPA usually investigates odour • Remove the source of the odour.
odour control considerations for complaints for industrial and large • Dilute and ventilate the air (clean
these back of house areas. commercial premises, whilst local while ventilating if ventilating to sensitive
councils investigate odour complaints location) and replace with clean fresh air.
THE SCIENCE OF ODOURS for domestic and smaller commercial
• Treat by providing an air cleaner which
Generally, an odour is perceived when premises (such as restaurants).
circulates air through itself to remove
chemicals in gaseous form stimulate the chemicals inside a closed space.
receptors in your nose. These odours can COMMON BACK OF HOUSE
be organic or inorganic based. Examples of AREA ODOURS GARBAGE/REFUGE ROOMS
different, hazardous or unpleasant odours
Hotel back of house areas such as garbage/ Several approaches exist to reduce odour
include diesel exhaust, decaying plant
refuge rooms, loading docks, commercial in garbage rooms (using the above-
matter, sewer gases and mould or yeast
kitchens, designated outdoor smoking mentioned principals):
spoors due to dampness. Given that the
areas or sewer vents, bio-treatment units
human nose has hundreds of receptors • Make sure bins containing odour can
and septic systems may be a common
that are uniquely coded by DNA to remain closed as much as possible.
source of odour complaints.
each individual, reactions to odours can
• Install a self-contained recirculating
be quite subjective and dependent on
individual sensitivities. An odour that may
ODOUR CONTROL ioniser, whereby electrostatically
charged ions are released into the
be pleasant to one – may be unpleasant METHODS FOR GASEOUS area where it reacts with and destroy
to another. Similarly the strength of odour CONTAMINANTS odour molecules and airborne infection
perceived from one person to another
Basically to clean air from gaseous present in ambient air.
varies widely, making it difficult at times
to achieve an objective assessment. contaminants there are three (3) • Install a self-contained recirculating
main mechanisms: ozone generator, which typically injects
According to the EPA (the statutory Table 1: Common emission types and odorous gases
authority responsible for administering Area Emission Type Odorous Gases
the Environmental Protection Act), “an Garbage/refuge room Organic waste, landfill rubbish Decomposing organics, sulphides, VOC’s
offensive odour is one that affects the
Loading docks Diesel exhaust Nitrogen oxides, sulphur oxides,
general life, health and wellbeing of an hydrocarbons, aldehydes, organic acids
individual as a result of the intensity, Kitchen Cooking exhaust, grease trap waste VOC’s, amines
character, frequency and duration
Designated outdoor Cigarette smoke Nitrosamines, amines, benzene,
of the odour.” Odorous gases most smoking areas aldehydes, hydrocarbons
commonly become an issue because of
Sewer vents, bio- Anaerobic microbial processes VOC’s, Volatile sulphur compounds
their nuisance value and – generating treatment units, septic (VSC’s), Hydrogen sulphide,
complaints by surrounding neighbours. systems Nitrogenous compounds, aldehydes

38
ozone into controlled space where it LOADING DOCKS • Design to code to assure kitchen
reacts with and oxidises odour particles exhaust is of the right volumes
The main way to reduce odour coming
in a chemical reaction which results and temperature.
inside from loading docks:
in the production of carbon dioxide, • Allow adequate and suitable make up
water vapour and oxygen. Note: ozone • Change the location/system design air into the kitchen to avoid stalling
generators must be controlled so there with air intakes located away from the the kitchen exhaust system or creating
is sufficient residence time, and that no loading docks. If this is not possible, “fugitive” odours from the kitchen.
excessive ozone is present in occupied the air will need to be treated using a • Locate air exhaust points away from
rooms for safety reasons. variety of odour and chemical based sensitive areas and fresh air intakes
• Install a self-contained recirculating adsorption media. If carbon monoxide and with good expectation of dilution
gas-phase chemical media unit (such as or dioxide levels are excessive, this will by prevailing winds.
a side access unit or corrosive air unit). need to be dealt with via ventilation
• Treat odours, smoke and particulates
Gas phase chemical media is used to rather than treatment. Note: No CO2/CO
with a staged and standards compliant
target and adsorb contaminant gases. treatment method that assures safety will
approach. This may include UL rated
• Increase room “Air Changes” by be cost effective.
high efficiency hood filters, adequate
exhausting certain calculated volumes • Clean the supply air, so that fumes are duct cleaning processes, treatment
of air.The contaminated air should be treated at this supply stage and not methods such as filters, odour absorbing
cleaned, or diluted during extraction so transferred inside.This can be done with activated carbon media or filters,
the odour is not transferred to other gas-phase chemical media filtration or with ESPs and roof-top dilution fan
areas.This can be achieved with gas-phase ozone generators. Note: ozone generators exhaust systems.
chemical media or with ozone generators. must be controlled so there is sufficient
residence time, and that no excessive ozone Roof-top dilution fan exhaust system
Self-contained recirculating ioniser
is exhausted for safety reasons.
• Increase local air-changes and use
positive pressurisation or air curtains
at building entry points to ensure fumes
are not transferred inside.
Chemical adsorption filtration media

Self-contained recirculating ozone generator

Self-contained recirculating media unit with gas-phase


chemical media
OUTDOOR SMOKING AREAS
Exterior and less frequently, interior
smoking rooms form a significant legal
KITCHENS
and OH&S challenge, however, the
Kitchens are initially a source of generally technical solution for the odour issues
pleasant odours, however, when is well understood and established.
exhausted into communal or residential This includes:
areas, they may be found offensive due
to odour, smoke, heat or other reasons. • Enhanced room or area air changes and
In general the approaches to this are: ventilation to remove smoke and odour.

39
Typical drum scrubber
• Targeted extraction from “high-risk” areas, such as gaming and materials.
tables in casinos. The build up of odours in
• Treatment and recycle systems involving electronic air cleaning these systems is inevitable,
systems like ESPs, air ionisation systems or particle filters and and only hazardous
odour absorbing media. in unusual, enclosed
circumstances (e.g. Carbon
• In general, these systems will require custom design and large
Monoxide or Hydrogen
scale air volume movements, involving significant room for plant
Sulphide). In locations where
and equipment, so retro-fits are generally problematic.
hazardous levels have been
• It should be noted that any of these system will not avoid the identified, adequate sensing
inevitable health effects of primary smoke inhalation, and only and alarm systems, such as
reduce, but not eliminate, secondary inhalation effects. carbon monoxide detectors,
Large scale self-washing ESP system configuration need to be allowed for in the
design of systems.

In general, the ways that


most of the “non-hazardous”
odours are dealt with is by
capture, treatment and then
exhaust of the air:

• Controlled and targeted exhaust systems or hoods are used


to collect fumes from the source, with adequate supplies of
fresh air to replace, and the contaminated air removed.
SEWER VENTS, BIO-TREATMENT UNITS
• Treatment systems such as drum scrubbers, containing
AND SEPTIC SYSTEMS carbon, odour treatment media or bio filtration systems are
Many “green-buildings” are taking opportunities to enhance all routinely used solutions with a variety of cost effectiveness
their status with various local recycling systems for waste water profiles depending on the volume, nature and concentration
of the odours.
• Exhaust of the odours to areas that will allow effective
Dometic drawer miniBar DM50C dispersion of the remaining odours from the treatment systems.
Guidance is given to the location and nature of these exhaust

NEW
points in various AS/NZS standards including 1668.2.

FINAL THOUGHTS
Odours are seldom hazardous, but should be taken seriously
STANDARDS as they can often be an indicator of more significant problems
located within the Hotel. This may include black mould from
IN CONVENIENCE leaks or excessive carbon monoxide or VOC’s from diesel
operation in inadequately ventilated areas.

Airepure Australia offers a range of products, services and consulting expertise


that can assist you with odour control and your compliance to AS/NZS 1668.1
and 1668.2. Airepure is a leading national air filtration company providing unique,
powerful and integrated air filtration solutions, ranging from basic HVAC filtration
and odour control right through to high end HEPA/ULPA filtration and airborne
containment technologies. Airepure recommends ELTA and Fantech Fans.
For more information, visit www.airepure.com.au or call 1300 886 353.
A unique modern design concept pull-out
compressor drawer miniBar for convenient
access from above with all contents in view.
REFERENCES
EPA Victoria: http://www.epa.vic.gov.au/your-environment/odour
In the 50 litre class, the DM50C
is another award winning and patented AS/NZS 1668.1:The use of ventilation and air conditioning in buildings.
solution introduced by Dometic. Part 1: Fire and smoke control in buildings: SAI Global 2015

P: 07 5507 6073 AS/NZS 1668.2:The use of ventilation and air conditioning in buildings.
E: lodging@dometic.com.au Part 2: Mechanical ventilation in buildings: SAI Global 2012

Hvitved-Jacobsen T.,Vollertsen J.,Yongsiri C., Nielsen A.H., Abdul-Talib S: Sewer


www.dometic.com.au microbial processes, emissions and impacts, Aalborg University – Department
of Environmental Engineering DENMARK, April 2002

40
DM50C-quarterpage-ad.indd 1 21/06/2016 2:20 pm
QUALITY
ODOUR CONTROL
FOR YOUR
FACILITY Plasmaclean Air Purifiers
• air ionisers & ozone generators
• neutralise & destroy odours

NEEDS
• air purification & disinfection

Purafil Self-Contained Systems


• self-contained air scrubbing systems
• gas-phase chemical media
• effective odour control

PowerClean Self-Washing ESP Activated Carbon Filters


• large scale auto-wash ESP systems • effective odour & ozone removal
• electronic air cleaning • combined particle & gas filtration
• reliable, cost effective operation • high performance & efficiency

Purafil Chemical Media


• target & neutralise odourous gases
• high efficiency & working capacity
ph:1300 886 353
• powerful air cleaning media
www.airepure.com.au

Strobic Air Tri-Stack Systems


• roof-top dilution fan exhaust
• prevents odour re-entrainment
• low energy consumption

aire
australia
pure ®

41