Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
P438/EN M/R-b5-A
Technical Manual
General Note on the PDF Version of this Technical Manual
All entries in the Table of Contents and all cross-references to other sections,
figures etc. in green letters are hyperlinks, i.e. by a single mouse click on the
reference one can navigate directly to the referenced part of the manual.
In the Adobe Reader (or the Acrobat Pro), one can return back to the previous
view by using the menu point View / Page Navigation / Previous View (keyboard
shortcut: ALT + Left cursor key). (It might be necessary to do this several times,
if the view at the target location has also been changed (e.g. by scrolling or
changing the zoom setting).
IMPORTANT INFORMATION
NOTICE: Read these instructions carefully, and look at the equipment to become familiar
with the device before trying to install, operate, or maintain it. The following
special messages may appear throughout this documentation or on the equipment
to warn of potential hazards or to call attention to information that clarifies or
simplifies a procedure.
The addition of this symbol to a Danger or Warning safety label indicates that an
electrical hazard exists, which will result in death or serious injury if the
instructions are not followed.
This is the safety alert symbol. It is used to alert you to a potential personal injury
hazard. Obey all safety messages that follow this symbol to avoid possible injury or
death.
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided,
will result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided,
can result in death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided,
can result in minor or moderate injury with or without equipment damage.
NOTICE
NOTICE, used without safety alert symbol, indicates a potentially hazardous
situation which, if not avoided, can result in equipment damage.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ Switch off the auxiliary power supply before any work in the terminal strip
area.
⚫ Switch off all the power supplies in connection to the equipment before
any work in the terminal strip area to isolate the device.
⚫ Do not touch the terminal strip area when equipment is in operation.
⚫ Do not remove or add wires in the terminal strip area when equipment is
in operation.
⚫ Short-circuit the system current transformers before disconnecting wires
to the transformer board (valid only for pin terminals, not required for ring
terminals which have a shortening block).
⚫ A protective conductor (ground/earth) of at least 1.5 mm2 must be
connected to the protective conductor terminal on the power supply board
and on the main relay case.
⚫ Do never remove the protective conductor connection to the device casing
as long as other wires are connected to it.
⚫ Where stranded conductors are used, insulated crimped wire end ferrules
must be employed.
Failure to follow these instructions will result in death or serious
injury.
Note: Regarding the appropriate wiring connections of the equipment refer to the
document Px3x_Grounding_Application_Guide_EN_h.pdf.
WARNING
HAZARD OF UNSAFE OPERATION
⚫ Only qualified personnel, trained, authorized and familiar with the device
and all the safety instructions in the general Safety Guide (SFTY/5LM/L11
or later version) and appropriate Chapter 5, Chapter 10, Chapter 11,
Chapter 12 and Chapter 13 of this manual, shall work on installation,
connection, commissioning, maintenance or servicing of this device.
⚫ Proper and safe operation of this device depends on appropriate shipping
and handling, proper storage, installation and commissioning, and on
careful operation, maintenance and servicing. For this reason only
qualified personnel shall work on or operate this device.
⚫ Any modifications to this device must be in accordance with the manual. If
any other modification is made without the express permission of
Schneider Electric, it will invalidate the warranty, and may render the
product unsafe.
Failure to follow these instructions can result in unintended
equipment operation.
The signals MAI N: Bl ocked/faulty and SFMON: War ning (LED) are
permanently assigned to the LEDs labeled OUT OF SERVICE and ALARM and can
be assigned to output relays to indicate the health of the device.
It is recommended that the signals MA IN: Blocke d/faulty and
SFMON : Wa rning ( LED) are communicated to the substation automation
system for alarm purposes, using hardwiring via output relays or the
communication interface.
Changes after going to press
P438
Table of Contents
3 Operation ............................................................................................................3-1
3.1 Modular Structure ....................................................................................................... 3-1
3.2 Operator-Machine Communication ............................................................................. 3-3
3.3 Cyber Security (Function Group CS) ............................................................................3-4
3.3.1 Users, Roles and Rights for Easergy MiCOM P30 ........................................................................................... 3-4
3.3.2 Cyber Security Implementation ..................................................................................................................... 3-6
3.4 Configuration of the Local Control Panel (Function Group LOC) ..................................3-7
3.4.1 Bay Panel .......................................................................................................................................................3-8
3.4.2 Signal Panel .................................................................................................................................................3-11
3.4.3 Operation Panel ...........................................................................................................................................3-12
3.4.4 Fault Panel ...................................................................................................................................................3-13
3.4.5 Overload Panel ............................................................................................................................................ 3-14
3.4.6 Selection of the Control Point ...................................................................................................................... 3-15
3.4.7 Configurable Clear Key ................................................................................................................................ 3-15
3.5 Communication Interfaces ........................................................................................ 3-16
3.5.1 PC Interface (Function Group PC) ................................................................................................................ 3-17
3.5.2 Communication Interface 1 (Function Group COMM1) ................................................................................ 3-18
3.5.3 Communication Interface 2 (Function Group COMM2) ................................................................................ 3-27
3.5.4 Communication Interface 3 (Function Group COMM3) ................................................................................ 3-30
3.5.5 Communication Interface Ethernet (Function Groups IEC and GOOSE) ....................................................... 3-35
3.6 IRIG-B Clock Synchronization (Function Group IRIGB) ...............................................3-57
3.7 Configurable Function Keys (Function Group F_KEY) ................................................ 3-58
3.8 Configuration and Operating Mode of the Binary Inputs (Function Group INP) ......... 3-60
3.9 Measured Data Input (Function Group MEASI) .......................................................... 3-62
3.9.1 Direct Current Input on the Analog (I/O) Module Y ...................................................................................... 3-63
3.9.2 Connecting a Resistance Thermometer to the “PT 100 Analog Input” on the Analog (I/O) Module Y .......... 3-66
3.10 Configuration, Operating Mode, and Blocking of the Output Relays (Function Group
OUTP) ........................................................................................................................3-68
3.11 Measured Data Output (Function Group MEASO) ......................................................3-71
3.11.1 General Settings ..........................................................................................................................................3-71
3.11.2 BCD Measured Data Output ........................................................................................................................ 3-73
3.11.3 Analog Measured Data Output .................................................................................................................... 3-77
3.11.4 Output of “External” Measured Data ........................................................................................................... 3-83
3.12 Configuration and Operating Mode of the LED Indicators (Function Group LED) ...... 3-84
3.12.1 Configuring the LED Indicators .................................................................................................................... 3-84
3.12.2 Layout of the LED Indicators ........................................................................................................................3-84
3.12.3 Operating Mode of the LED Indicators ......................................................................................................... 3-86
3.13 Main Functions of the P438 (Function Group MAIN) .................................................. 3-88
3.13.1 Conditioning of the Measured Variables ...................................................................................................... 3-88
3.13.2 Operating Data Measurement ..................................................................................................................... 3-95
3.13.3 Configuring and Enabling the Device Functions ........................................................................................ 3-105
3.13.4 Inrush Stabilization .................................................................................................................................... 3-107
3.13.5 Harmonics Blocking ................................................................................................................................... 3-109
3.13.6 Measurement of Frequency ....................................................................................................................... 3-111
3.13.7 Function Blocks ......................................................................................................................................... 3-112
3.38 Circuit Breaker Failure Protection (Function Group CBF) ........................................ 3-303
3.38.1 Disabling and Enabling Circuit Breaker Failure Protection .........................................................................3-303
3.38.2 Readiness of Circuit Breaker Protection .................................................................................................... 3-303
3.38.3 Circuit Breaker Failure Protection ..............................................................................................................3-304
3.39 Circuit Breaker Monitoring (Function Group CBM) .................................................. 3-307
3.39.1 Disabling and Enabling Circuit Breaker Monitoring ....................................................................................3-307
3.39.2 Variants ..................................................................................................................................................... 3-307
3.39.3 CB Wear Characteristic ..............................................................................................................................3-308
3.39.4 Calculating the CB Wear State .................................................................................................................. 3-309
3.39.5 Operating Modes ....................................................................................................................................... 3-310
3.39.6 Cycle for Circuit Breaker Monitoring ..........................................................................................................3-312
3.39.7 Monitoring the Number of CB Operations ..................................................................................................3-313
4 Design .................................................................................................................4-1
4.1 Designs ....................................................................................................................... 4-2
4.2 Dimensional Drawings ................................................................................................ 4-4
4.2.1 Dimensional Drawings for the 40 TE Case .....................................................................................................4-4
4.2.2 Dimensional Drawings for the 84 TE Case .....................................................................................................4-6
4.3 Hardware Modules ...................................................................................................... 4-8
7 Settings ...............................................................................................................7-1
7.1 Parame ters .............................................................................................................. 7-1
7.1.1 D e v i c e I d e n t i f i c a t i o n ............................................................................................................................. 7-4
7.1.2 C o n f i g u r a t i o n P a r a m e t e r s .................................................................................................................. 7-13
A3 Glossary ............................................................................................................A3-1
Modules ...................................................................................................................................... A3-1
Symbols ...................................................................................................................................... A3-1
Examples of Signal Names ......................................................................................................... A3-7
Symbols Used ............................................................................................................................. A3-8
1.1 Overview
The P438 catenary protection device is used for selective short-circuit and
overload protection of catenaries and is designed for various applications in
single- or multi-voltage systems with nominal frequencies of 25, 50 or 60 Hz
(settable).
The multitude of protection functions incorporated into the P438 enable the user
to cover a wide range of applications in the protection of catenaries.
In addition, many supplementary protective functions are incorporated in the
devices. The P438 provides four setting groups for easy adaptation to varying
system operation conditions. Due to the powerful, freely configurable logic of the
device, special applications can be accommodated.
The control functions are designed for the control of up to ten electrically
operated switchgear units equipped with plant status signaling and located in the
bay of a railway substation.
The number of external auxiliary devices required is largely minimized by the
integration of binary signal inputs operating from any auxiliary voltage, and
versatile relay output contacts, by the direct connection option for current and
voltage transformers, and by the comprehensive interlocking capabilities. This
simplifies the handling of switch protection and control technology from planning
to commission.
During operation, the user-friendly interface makes it easy to set the device
parameters and allows safe operation of the substation by preventing
nonpermissible switching operations.
All main functions are individually configurable. The user can adapt the device
flexibly to the scope of protection and control required in each particular
application.
50BU BocPhsPTOCx BUOC Backup definite time overcurrent protection, two stages ✓
50TD DtpPhAPTOCx/ DTOCA/ Definite time overcurrent protection, two stages, for ✓
DtpPhBPTOCx DTOCB "Autotranformer feed" only
Voltages 2
Mmuxxx Measuring ✓
TIMER Timer 4
Plausibility/
21 50/27 50TD/50V/67 50HS 51/50V/67 49 50BF 79 25 27/59 81
Defrost-line DIST SOTF DTOC DTOC IDMT THERM CBF CBM ARC ASC DFRST V<> DELTA
f <>
I Plaus / I Dfrst
Vref
Further Always
30/74 50BU
options available
DELTA MCMON BUOC
IB Φ
I Plaus / I Dfrst
VA
VB Φ
Further Always
30/74 50BU 50TD 51
options available
DELTA MCMON BUOC DTOCB IDMTB
1.5 Design
The P438 is modular in design. The plug-in modules are housed in a robust
aluminum case and electrically interconnected via one analog p/c board and one
digital p/c board.
Configurable function keys are available on the HMI with text display only.
To the right of the text display, there are six freely configurable function keys
available. These may be used for easy control operation access.
See also Chapter 6, (p. 6-1).
2 Technical Data
2.1 Conformity
Notice
Applicable to P438, version ‑311 ‑418/419/420 ‑661.
Declaration of Conformity
The product designated “P438 Rail Catenary Protection Device” has been
designed and manufactured in conformance with the EMC and safety standards
IEC 60255‑26 and IEC 60255‑27 and with the “EMC Directive” and the “Low
Voltage Directive” issued by the Council of the European Community.
Design
● Surface-mounted case suitable for wall installation, or
● Flush-mounted case for 19″ cabinets and for control panels.
Installation Position
● Vertical ± 30°.
Degree of Protection
Per DIN VDE 0470 and IEC 60529.
● IP 52 for the front panel.
● Flush-mounted case:
o IP 50 for the case (excluding the rear connection area)
o IP 20 for the rear connection area, pin-terminal connection
o IP 10 for the rear connection area, ring-terminal connection
● Surface-mounted case:
o IP 50 for the case
o IP 50 for the fully enclosed connection area with the supplied rubber
grommets fitted
Weight
● 40 TE case: Approx. 7 kg
● 84 TE case: Approx. 11 kg
Terminals
PC interface (X6)
● EIA RS232 (DIN 41652) connector, type D-Sub, 9-pin
2.3 Tests
Conducted Emission
Per IEC 60255-26 and CISPR 22 Class A.
● 0.15 - 0.5 MHz, 79 dBμV (quasi peak) 66 dBμV (average).
● 0.5 - 30 MHz, 73 dBμV (quasi peak) 60 dBμV (average).
Radiated Emission
Per IEC 60255-26 and CISPR 11 Class A.
● 30 - 230 MHz, 40 dBμV / m at 10 m measurement distance.
● 230 - 1 GHz, 47 dBμV / m at 10 m measurement distance.
Phase-to-phase
● RMS value 150 V.
● Coupling resistance 100 Ω.
● Coupling capacitor 0.1 μF, for 10 s.
Phase-to-ground
● RMS value 300 V.
● Coupling resistance 220 Ω.
● Coupling capacitor 0.47 μF, for 10 s.
To comply with this standard, it is suggested to set the parameter (010 220)
IN P: F il ter to 6 [steps].
2.3.1.2 Insulation
Insulation Resistance
Per IEC 60255-27.
Insulation resistance > 100 MΩ at 500 Vdc.
Vibration Test
Per IEC 60255‑21-1, test severity class 1.
Seismic Test
Per IEC 60255‑21‑3, test procedure A, class 1.
Frequency range
● Horizontal axes of vibration: 1 Hz to 8 Hz with 3.5 mm peak displacement, 8
to 35 Hz with 10 m / s² peak acceleration. 2 x 1 cycle.
● Vertical axis of vibration: 1 Hz to 8 Hz with 1.5 mm peak displacement, 8 to
35 Hz with 5 m / s² peak acceleration. 1 x 1 cycle.
Temperatures
Per IEC 60255-1 & IEC 60068-2-1
Solar Radiation
Direct solar radiation on the front of the device must be avoided.
Frequency
● Nominal frequency fnom: 25 Hz, 50 Hz and 60 Hz (settable).
● Operating range: 0.95 to 1.05 fnom.
Binary I/O Module X(6I 6O) Binary I/O Modules X(4H) All other modules
for switchgear control. with high-break contacts,
applicable to DC circuits
only.
Continuous 8A 10 A 5A
current:
2.6 Interfaces
2.6.2 PC Interface
● Transmission rate: 300 to 115,200 baud (adjustable)
Wire Leads
● Per RS 485 or RS 422, 2 kV isolation
● Distance to be bridged
o Point-to-point connection: max. 1200 m
o Multipoint connection: max. 100 m
2.9 Deviations
2.9.1.1 Definitions
Reference Conditions
● Quasi-stationary sinusoidal signals at nominal frequency fnom (frequency
protection excepted), total harmonic distortion ≤ 2 %, ambient
temperature 20°C (68°F), and nominal auxiliary voltage VA,nom.
Deviation
● Deviation relative to the setting under reference conditions.
Operate values
● Delta I / Delta Phi deviation: ± 3% of the setting or ± 1% of the nominal
value
● Line reactance measurement X<:
Deviation at ϕ = 0°, 90°: ± 3% of the setting
Deviation at ϕ = 30°, 60°: ± 5% of the setting
● Harmonics dependence: ± 5% of the setting
Operate value Θ
● Deviation: ± 5% of the setting or ± 1% of the nominal value
Operate values
● V<>: ± 1% (in the range 0.6 to 1.4 Vnom)
2.9.2.1 Definitions
Reference conditions
● Sinusoidal signals at nominal frequency fnom, total harmonic distortion
≤ 2 %, ambient temperature 20°C (68°F), and nominal auxiliary voltage
VA,nom.
Deviation
● Deviation relative to the setting under reference conditions.
2.9.3.1 Definitions
Reference conditions
● Sinusoidal signals at nominal frequency fnom, total harmonic distortion ≤
2%, ambient temperature 20°C (68°F), and nominal auxiliary voltage
VA,nom.
Deviation
● Deviation relative to the nominal values under reference conditions.
Load angle
● Deviation: ± 1°
Frequency
● Deviation: ± 10 mHz
Amplitude resolution
● at Inom = 1 A: 2.0 mA rms
● at Inom = 5 A: 10.1 mA rms
2.10.3 Voltage
Dynamic range
● 150 V
Amplitude resolution
● 9.2 mV rms
Overload Memory
Number
● The 8 most recent overload events
Fault Memory
Number
● The 8 most recent faults.
Nominal burden
● … where VA = 220 V DC and with maximum module configuration
o 40 TE case, relays de-energized/energized: approx. 12.6 W / 34.1 W
o 84 TE case, relays de-energized/energized): approx. 14.5 W / 42.3 W
2.13.1 Symbols
The following symbols are used in accordance with IEC 61869 standards:
Xp
K d = K max ≈ 1 + Rp = 1 + ω · Tp
30
A
25
20
15
K emp B
10
C
As per IEC 60255-121 (draft 2011), the following 4 fault conditions have to be
checked to determine the required CT dimensioning.
A B
DIST
2 3 4
Case 1:
● Close-up backward short-circuit (security case)
Acceptance criteria: Stable backward direction decision, no trip
Select required Kemp per curve C
Case 2:
● Close-up forward short-circuit (dependability case)
Acceptance criterion: Instantaneous trip with less than 1 period add. delay
Required Kemp = 1.5
Case 3:
● Short-circuit at 80% of Zone 1 reach limit (dependability case)
Acceptance criterion: Trip with less than 3 periods add. delay
Select required Kemp per curve B
Case 4:
● Short-circuit at 110% of Zone 1 reach limit (security case)
Acceptance criterion: Correct time delayed zone 2 trip
Select required Kemp per curve C
Depending on the fault location, different maximum short-circuit currents and
primary system X/R ratios apply! Therefore the required CT dimensioning has to
be calculated separately for all 4 cases. The biggest sizing from all 4 cases then
has to be used.
It is recommended to use CTs of accuracy class 5P (or equivalent).
3 Operation
Communic. module
TRIP
ALARM
OUT OF SERVICE
HEALTHY
A A A
EDIT MODE
P μP
Processor module
Analog
Digital busbus module
module
T X Y V
Transformer module
Voltages Currents Signals Commands Signals Measured data Signals Commands Auxiliary voltage
Commands Signals Commands Commands Signals
“Parameters” Branch
All settings are contained in this branch. This branch carries all settings,
including the identification data of the P438, the configuration parameters for
adapting the P438 interfaces to the system, and the function parameters for
adapting the device functions to the process. All values in this group are stored
in non-volatile memory, which means that the values will be preserved even if
the power supply fails.
“Operation” Branch
This branch includes all information relevant for operation such as measured
operating data and binary signal states. This information is updated periodically
and consequently is not stored. In addition, various controls are grouped here,
for example those for resetting counters, memories and displays.
“Events” Branch
The third branch is reserved for the recording of events. All information in this
group is therefore stored. In particular, the start/end signals during a fault, the
measured fault data, and the sampled fault waveforms are stored here and can
be read out when required.
Cyber Security is based on the model of Role Based Access Control (RBAC) which
is a method to restrict resource access to authorized users. One role can have
one and more access rights, one user (subject) can have several roles. A user
(subject) is based on a session. This session controls for example the activity of
the user. If the user is inactive for 15 minutes (default setting) the user will be
locked out automatically.
Static separation
of duty
Subject Right
assignment assignment
1 1..n Right
Dynamic
1..n 1 separation of duty
Session
User accounts
When the user tries to access an IED, they need to login using their own
username and their own password. The username/ password combination is then
checked against the records stored on the IED. It is the role that defines their
access to the relevant parts of the system.
The default user accounts for Easergy MiCOM P30 is as below:
DefaultEngineer x x x
DefaultOperator x x
DefaultViewer x
SecurityAdmin x
(for SAT only)
DefaultUser x
(for HMI only)
Tab. 3-1: Default user accounts for Easergy MiCOM P30.
Roles
Different named roles are associated with different access rights. Roles and
Rights are setup in a pre-defined arrangement, according to the IEC 62351
standard, but customized to the Easergy MiCOM P30 equipment.
The default roles for Easergy MiCOM P30 is as below:
Role Description
VIEWER Can View what objects are present within a Logical-Device by presenting the
type ID of those objects.
OPERATOR An Operator can view what objects and values are present within a Logical-
Device by presenting the type ID of those objects as well as perform control
actions.
ENGINEER An Engineer can view what objects and values are present within a Logical-
Device by presenting the type ID of those objects. Moreover, an engineer has
full access to Datasets and Files and can configure the server locally or
remotely.
Rights
In a similar way in which a set of pre-defined Roles have been created, a
predefined set of Rights have been created.
The reason why these are described as Default, is that it is possible to change the
definitions of Roles and Rights, by using the SAT software. Depending on the work
done by the system administrator, it is possible that your own situation may vary
from these initial recommendations.
To create customized bay types, the “Bay Type Configurator” (BTC), version 2.7
or higher, is needed. Older versions of the BTC can create not compatible hex files
and thus can lead to communication failures.
When the text display has been fitted the Bay Panel will display switching state
signals from external devices (closed, open, intermediate position) and the active
control site (local or remote).
In addition the P438 offers Measured Value Panels, which display the measured
values relevant at a given time.
During normal power system operation; the Bay Panel or – if activated – the
Operation Panel is displayed. If the Operation Panel is activated as an event
occurs, the display switches to the appropriate Event Panel – provided that
measured values have been selected for the Event Panels. In the event of
overload or ground fault events, the display will automatically switch to the
Operation Panel at the end of the event. In the event of a fault, the Fault Panel
remains active until the LED indicators or the fault memories are reset.
If the change enabling command has been issued (LOC: Param. change
enabl.) it will be cancelled after the time period, defined by setting L OC: Hold-
time for Panels has elapsed and the Bay Panel will be called up.
LOC:
DEV01: Character set
Designat. ext. dev. [ 221 038 ]
[ 210 000 ]
LOC: LOC:
Displ. ext.dev.desig Fct.asg. num. displ.
[ 221 032 ] [ 221 041 ]
LOC: LOC:
Display L/R Fct. asg. bar displ.
[ 221 070 ] [ 221 042 ]
LOC: LOC:
Displ. interl. stat. Bar display type
[ 221 071 ] [ 221 039 ]
LOC: LOC:
Designation busbar 1 Scal. bar display I
[ 221 033 ] [ 221 044 ]
LOC: LOC:
Designation busbar 2 Scal. bar display V
[ 221 034 ] [ 221 045 ]
LOC: LOC:
Designation busbar 3 Display bar scale
[ 221 043 ] [ 221 046 ]
LOC: LOC:
Designat. bus sect.1 Return time select.
[ 221 035 ] [ 221 030 ]
LOC: LOC:
Designat. bus sect.2 Return time illumin.
[ 221 036 ] [ 003 023 ]
BB1
Q0
LOC:
Return t.select. trg
305 551
19Z5003A
LOC:
DEV01: Display L/R
Designat. ext. dev. [ 221 070 ]
[ 210 000 ]
LOC:
Displ. interl. stat.
[ 221 071 ]
LOC:
Return time select.
[ 221 030 ]
LOC:
Return time illumin.
[ 003 023 ]
Q0
Remote Locked
LOC:
Return t.select. trg
305 551
45Z8003A
LOC:
Fct. Signal Panel
[ 221 072 ]
Signal 1
Signal 2
m out of n
Signal 3 LOC: LOC:
Autom. return time Autom. return time
[ 003 014 ]
Signal n
LOC: LOC:
Selected signals Hold-time for Panels Hold-time for Panels
[ 031 075 ]
LOC:
LOC: Aut.activ.Sign.Panel
Indicat.Sign.Panel [ 221 073 ]
[ 221 075 ]
LOC:
Stat.ind.Sign.Panel
[ 221 074 ]
0: Without signalling 0
Selection
1)
LOC:
Chg.Sig.Panel stat.
[ 221 076 ]
Sig. Panel
LOC:
1) Chg.Sig.Panel flash.
[ 221 077 ]
44Z5209A
LOC:
Fct. Operation Panel
[ 053 007 ]
LOC:
Selected meas. val. Hold-time for Panels LOC:
[ 031 075 ] Hold-time for Panels
FT_RC:
Record. in progress S1 1 ≥1 C
[ 035 000 ]
R1
OL_RC:
Record. in progress
[ 035 003 ] Operation Panel
MAIN:
General reset USER
[ 003 002 ]
1: execute ≥1
MAIN:
General reset EXT
[ 005 255 ]
FT_RC:
Reset record. USER
[ 003 006 ]
1: execute
FT_RC:
Reset record. EXT
[ 005 243 ]
MAIN:
Reset LED
306 020
47Z1301A
LOC:
Fct. Fault Panel
[ 053 003 ]
Measured value 3
Measured value N
LOC:
Hold-time for Panels
[ 031 075 ]
R
MAIN:
General reset USER
[ 003 002 ]
1: execute ≥1 Fault Panel
MAIN:
General reset EXT
[ 005 255 ]
FT_RC:
Reset record. USER
[ 003 006 ]
1: execute
FT_RC:
Reset record. EXT
[ 005 243 ]
MAIN:
Reset LED
306 020
50Z01EJA
LOC:
Fct. Overload Panel
[ 053 005 ]
Measured value 3
Measured value n
MAIN:
General reset EXT
[ 005 255 ]
OL_RC:
Reset record. USER
[ 100 003 ]
1: execute
OL_RC:
Reset record. EXT
[ 005 241 ]
MAIN:
Reset LED
306 020
50Z0140A
LOC:
Fct. assign. L/R key
[ 225 208 ]
1: R <-> L
2: R & L <-> L
1)
& & 1
MAIN:
Inp.asg. L/R key sw.
[ 221 008 ]
Signal 1
Signal 2 m out of n
Signal 3
Signal n
Without function
Selected signal
PC:
Bay address
[ 003 068 ]
PC:
Device address
[ 003 069 ]
PC:
Baud rate
[ 003 081 ]
PC:
Parity bit
[ 003 181 ]
PC:
Spontan. sig. enable
[ 003 187 ]
PC:
Select. spontan.sig.
[ 003 189 ]
PC:
Transm.enab.cycl.dat
[ 003 084 ]
PC:
Cycl. data ILS tel.
[ 003 185 ]
PC:
Delta V
[ 003 055 ]
PC:
Delta I
[ 003 056 ]
PC:
Sig./meas.val.block. PC:
[ 003 086 ] Delta P
[ 003 059 ]
0 PC:
Delta f
1 [ 003 057 ]
0: No PC:
Delta meas.v.ILS tel
1: Yes [ 003 155 ]
PC:
Delta t
MAIN: [ 003 058 ]
Prot. ext. disabled
[ 038 046 ]
PC:
Time-out
PC: [ 003 188 ]
Command blocking
[ 003 182 ]
0: No
1: Yes
PC interface
MAIN:
Test mode
[ 037 071 ]
19Z80ECA
COMM1:
Command block. USER
[ 003 172 ]
0: No COMM1:
Command blocking
[ 003 174 ]
1: Yes
COMM1:
Command block. EXT
[ 003 173 ]
COMM1:
Basic IEC870-5 enabl
[ 003 215 ] COMM1:
Communicat. protocol
[ 003 167 ]
0
1
0: No
1: Yes
COMM1:
Addit. -101 enable
[ 003 216 ]
COMM1:
0 Selected protocol Selected protocol
304 415
1
0: No
1: Yes
COMM1:
Addit. ILS enable
[ 003 217 ]
0: No
1: Yes
COMM1:
MODBUS enable
[ 003 220 ]
0: No
1: Yes
COMM1:
DNP3 enable
[ 003 231 ]
0: No
1: Yes
COMM1:
COURIER enable
[ 103 040 ]
0: No
1: Yes
64Z51FEA
COMM1: COMM1:
-103 prot. variant Select. spontan.sig.
[ 003 178 ] [ 003 179 ]
COMM1: COMM1:
Line idle state Transm.enab.cycl.dat
[ 003 165 ] [ 003 074 ]
COMM1: COMM1:
Baud rate Cycl. data ILS tel.
[ 003 071 ] [ 003 175 ]
COMM1: COMM1:
Parity bit Delta V
[ 003 171 ] [ 003 050 ]
COMM1: COMM1:
Dead time monitoring Delta I
[ 003 176 ] [ 003 051 ]
COMM1: COMM1:
Mon. time polling Delta P
[ 003 202 ] [ 003 054 ]
COMM1: COMM1:
Octet comm. address Delta f
[ 003 072 ] [ 003 052 ]
COMM1: COMM1:
Test monitor on Delta meas.v.ILS tel
[ 003 166 ] [ 003 150 ]
COMM1: COMM1:
Name of manufacturer Delta t
[ 003 161 ] [ 003 053 ]
COMM1: COMM1:
Octet address ASDU Delta t (energy)
[ 003 073 ] [ 003 151 ]
COMM1: COMM1:
Spontan. sig. enable Contin. general scan
[ 003 177 ] [ 003 077 ]
COMM1:
Selected protocol
304 415
COMM1:
IEC 60870-5-103
[ 003 219 ]
COMM1:
General enable USER
[ 003 170 ]
1: Yes
COMM1:
Command blocking
[ 003 174 ]
MAIN: COMM1:
Test mode Communic. interface Communication error
[ 037 071 ] 304 422
COMM1:
Sig./meas.block.USER
[ 003 076 ]
0: No COMM1:
Sig./meas.val.block.
1: Yes
[ 037 075 ]
COMM1:
Sig./meas. block EXT
[ 037 074 ]
MAIN:
Prot. ext. disabled
[ 038 046 ]
12Z62FFA
Fig. 3-12: Communication interface 1, settings for the IEC 60870‑5-103 interface protocol.
COMM1: COMM1:
Line idle state Delta t
[ 003 165 ] [ 003 053 ]
COMM1: COMM1:
Baud rate Delta t (energy)
[ 003 071 ] [ 003 151 ]
COMM1: COMM1:
Parity bit Contin. general scan
[ 003 171 ] [ 003 077 ]
COMM1: COMM1:
Dead time monitoring Comm. address length
[ 003 176 ] [ 003 201 ]
COMM1: COMM1:
Mon. time polling Octet 2 comm. addr.
[ 003 202 ] [ 003 200 ]
COMM1: COMM1:
Octet comm. address Cause transm. length
[ 003 072 ] [ 003 192 ]
COMM1: COMM1:
Test monitor on Address length ASDU
[ 003 166 ] [ 003 193 ]
COMM1: COMM1:
Name of manufacturer Octet 2 addr. ASDU
[ 003 161 ] [ 003 194 ]
COMM1: COMM1:
Octet address ASDU Addr.length inf.obj.
[ 003 073 ] [ 003 196 ]
COMM1: COMM1:
Spontan. sig. enable Oct.3 addr. inf.obj.
[ 003 177 ] [ 003 197 ]
COMM1: COMM1:
Select. spontan.sig. Inf.No.<->funct.type
[ 003 179 ] [ 003 195 ]
COMM1: COMM1:
Transm.enab.cycl.dat Time tag length
[ 003 074 ] [ 003 198 ]
COMM1: COMM1:
Cycl. data ILS tel. ASDU1 / ASDU20 conv.
[ 003 175 ] [ 003 190 ]
COMM1: COMM1:
Delta V ASDU2 conversion
[ 003 050 ] [ 003 191 ]
COMM1: COMM1:
Delta I Initializ. signal
[ 003 051 ] [ 003 199 ]
COMM1: COMM1:
Delta P Balanced operation
[ 003 054 ] [ 003 226 ]
COMM1:
Selected protocol
304 415 COMM1: COMM1:
Delta f Direction bit
COMM1: [ 003 052 ] [ 003 227 ]
IEC 60870-5-101
[ 003 218 ] COMM1: COMM1:
Delta meas.v.ILS tel Time-out interval
[ 003 150 ] [ 003 228 ]
COMM1:
General enable USER
[ 003 170 ]
1: Yes
COMM1:
Command blocking
[ 003 174 ]
MAIN:
Test mode
[ 037 071 ] COMM1:
Sig./meas.block.USER
[ 003 076 ]
0: No
COMM1:
Sig./meas.val.block.
1: Yes [ 037 075 ]
COMM1:
Sig./meas. block EXT
[ 037 074 ]
MAIN:
Prot. ext. disabled
[ 038 046 ] 19Z51FGA
Fig. 3-13: Communication interface 1, settings for the IEC 870-5-101 interface protocol.
COMM1: COMM1:
Line idle state Transm.enab.cycl.dat
[ 003 165 ] [ 003 074 ]
COMM1: COMM1:
Baud rate Cycl. data ILS tel.
[ 003 071 ] [ 003 175 ]
COMM1: COMM1:
Parity bit Delta V
[ 003 171 ] [ 003 050 ]
COMM1: COMM1:
Dead time monitoring Delta I
[ 003 176 ] [ 003 051 ]
COMM1: COMM1:
Mon. time polling Delta P
[ 003 202 ] [ 003 054 ]
COMM1: COMM1:
Octet comm. address Delta f
[ 003 072 ] [ 003 052 ]
COMM1: COMM1:
Test monitor on Delta meas.v.ILS tel
[ 003 166 ] [ 003 150 ]
COMM1: COMM1:
Name of manufacturer Delta t
[ 003 161 ] [ 003 053 ]
COMM1: COMM1:
Octet address ASDU Delta t (energy)
[ 003 073 ] [ 003 151 ]
COMM1: COMM1:
Spontan. sig. enable Contin. general scan
[ 003 177 ] [ 003 077 ]
COMM1:
Select. spontan.sig.
[ 003 179 ]
COMM1:
Selected protocol
304 415
COMM1:
IEC 60870-5, ILS
[ 003 221 ]
COMM1:
General enable USER
[ 003 170 ]
1: Yes
COMM1:
Command blocking
[ 003 174 ] COMM1:
Comm. interface Communication error
304 422
MAIN:
Test mode
[ 037 071 ]
COMM1:
Sig./meas.block.USER
[ 003 076 ]
0: No COMM1:
Sig./meas.val.block.
1: Yes [ 037 075 ]
COMM1:
Sig./meas. block EXT
[ 037 074 ]
MAIN:
Prot. ext. disabled
[ 038 046 ]
19Z51FHA
Fig. 3-14: Communication interface 1, settings for the ILS-C interface protocol.
COMM1: COMM1:
MODBUS prot. variant Test monitor on
[ 003 214 ] [ 003 166 ]
COMM1: COMM1:
Line idle state Reg.asg. selec. cmds
[ 003 165 ] [ 003 210 ]
COMM1: COMM1:
Baud rate Reg.asg. selec. sig.
[ 003 071 ] [ 003 211 ]
COMM1: COMM1:
Parity bit Reg.asg. sel. m.val.
[ 003 171 ] [ 003 212 ]
COMM1: COMM1:
Dead time monitoring Reg.asg. sel. param.
[ 003 176 ] [ 003 213 ]
COMM1: COMM1:
Mon. time polling Delta t (MODBUS)
[ 003 202 ] [ 003 152 ]
COMM1: COMM1:
Octet comm. address Autom.event confirm.
[ 003 072 ] [ 003 249 ]
COMM1:
Selected protocol
304 415
COMM1:
MODBUS
[ 003 223 ]
COMM1:
General enable USER
[ 003 170 ]
1: Yes
COMM1:
Commun. interface Communication error
304 422
COMM1:
Command blocking
[ 003 174 ]
MAIN:
Test mode
[ 037 071 ]
19Z50FJB
COMM1: COMM1:
Line idle state Link Confirm.Timeout
[ 003 165 ] [ 003 244 ]
COMM1: COMM1:
Baud rate Link Max. Retries
[ 003 071 ] [ 003 245 ]
COMM1: COMM1:
Parity bit Appl.Confirm.Timeout
[ 003 171 ] [ 003 246 ]
COMM1: COMM1:
Dead time monitoring Appl. Need Time Del.
[ 003 176 ] [ 003 247 ]
COMM1: COMM1:
Mon. time polling Ind./cl. bin. inputs
[ 003 202 ] [ 003 232 ]
COMM1: COMM1:
Octet comm. address Ind./cl. bin.outputs
[ 003 072 ] [ 003 233 ]
COMM1: COMM1:
Oct.2 comm.addr.DNP3 Ind./cl. bin. count.
[ 003 240 ] [ 003 234 ]
COMM1: COMM1:
Test monitor on Ind./cl. analog inp.
[ 003 166 ] [ 003 235 ]
COMM1: COMM1:
Phys. Charact. Delay Ind./cl. analog outp
[ 003 241 ] [ 003 236 ]
COMM1: COMM1:
COMM1: Phys. Char. Timeout Delta meas.v. (DNP3)
Selected protocol [ 003 242 ] [ 003 250 ]
304 415
COMM1:
General enable USER
[ 003 170 ]
1: Yes
COMM1:
Command blocking
[ 003 174 ]
MAIN: COMM1:
Test mode Commun. interface Communication error
[ 037 071 ] 304 422
19Z50AZA
Fig. 3-16: Communication interface 1, settings for the DNP 3.0 protocol.
COMM1: COMM1:
Line idle state Test monitor on
[ 003 165 ] [ 003 166 ]
COMM1: COMM1:
Baud rate Command selection
[ 003 071 ] [ 103 042 ]
COMM1: COMM1:
COMM1: Parity bit Signal selection
Selected protocol [ 003 171 ] [ 103 043 ]
304 415
COMM1: COMM1:
Mon. time polling Parameter selection
[ 003 202 ] [ 103 045 ]
COMM1:
General enable USER COMM1: COMM1:
[ 003 170 ] Octet comm. address Delta t (COURIER)
[ 003 072 ] [ 103 046 ]
0: No
1: Yes
COMM1:
Command blocking
[ 003 174 ]
MAIN: COMM1:
Test mode Commun. interface Communication error
[ 037 071 ] 304 422
19Z51BAA
COMM1:
Sel.spontan.sig.test
[ 003 180 ]
Signal 1
Signal 2
Signal 3
Signal n
Selected signals
COMM1:
Test spont.sig.start
[ 003 184 ]
COMM1:
Spontan. sig. start
0 [ --- --- ]
0: don't execute
1: execute
COMM1:
Test spont.sig. end
[ 003 186 ]
COMM1:
Spontan. sig. end
0 [ --- --- ]
0: don't execute
1: execute
48Z50FKA
COMM2:
Line idle state
[ 103 165 ]
COMM2:
Baud rate
[ 103 071 ]
COMM2:
Parity bit
[ 103 171 ]
COMM2:
Dead time monitoring
[ 103 176 ]
COMM2:
Mon. time polling
[ 103 202 ]
COMM2:
Octet comm. address
[ 103 072 ]
COMM2:
Name of manufacturer
[ 103 161]
COMM2:
Octet address ASDU
[ 103 073 ]
COMM2:
Spontan. sig. enable
[ 103 177 ]
COMM2: COMM2:
General enable USER Select. spontan.sig.
[ 103 170 ] [ 103 179 ]
COMM2:
Transm.enab.cycl.dat
0
[ 103 074 ]
1
COMM2:
0: No Cycl. data ILS tel.
[ 103 175 ]
1: Yes
COMM2:
Delta V
[ 103 050 ]
COMM2:
Delta I
[ 103 051 ]
COMM2:
Sig./meas.block.USER COMM2:
Delta P
[ 103 076 ]
[ 103 054 ]
0 COMM2:
Delta f
1 [ 103 052 ]
0: No COMM2:
Delta meas.v.ILS tel
1: Yes [ 103 150 ]
COMM2:
MAIN: Delta t
Prot. ext. disabled
[ 103 053 ]
[ 038 046 ]
COMM2:
Command block. USER
[ 103 172 ]
0: No
1: Yes
Commun. interface
MAIN:
Test mode
[ 037 071 ]
40Z5070A
COMM2:
Sel.spontan.sig.test
[ 103 180 ]
Signal 1
Signal 2
Signal 3
Signal n
Selected signals
COMM2:
Test spont.sig.start
[ 103 184 ]
COMM2:
Spontan. sig. start
0 [ --- --- ]
0: don't execute
1: execute
COMM2:
Test spont.sig. end
[ 103 186 ]
COMM2:
Spontan. sig. end
0 [ --- --- ]
0: don't execute
1: execute
48Z50FLA
3.5.4.1 Application
Communication interface 3 is designed to establish a digital communication link
between two devices from Schneider Electric's device family “Easergy MiCOM
30”.
Over this communication link can be transmitted up to 8 binary protection
signals. Whereas communication interfaces 1 and 2 are designed as information
interfaces to connect to data acquisition subsystems and for remote access,
communication interface 3 is designed as a protection signaling interface that
will transmit real time signals (InterMiCOM protection signaling interface). Its
main application is to transmit signals from protective signaling (function group
PSIG). In addition, any other internal or external binary signals may also be
transmitted.
Digital network:
● Asynchronous data interface of primary multiplexing equipment
Preference: Security.
Recommended setting: Select binary signal from groups 1 to 4 or 5 to 8 and set operating
mode Direct intertrip.
Preference: Dependability.
Recommended setting: Select binary signal from group 5 to 8 and set operating mode
Permissive.
Preference: Speed.
Recommended setting: Select binary signal from group 1 to 4 and set operating mode
Blocking.
Speed
Blocking
Permissive
slow
low
Intertrip
Security Dependability
47Z1030A
Fig. 3-21: Comparison of speed, security and dependability offered by the three operating modes.
Message
received
Blocking signals
accepted
Telegram
receive check
Permissive signals
accepted
(Re)start of the
monitoring
timer stages
COMM3:
Time-out comm.fault
[ 120 033 ]
COMM3:
1 Communications fault
[ 120 043 ]
COMM3:
Time-out link fail.
[ 120 035 ]
COMM3:
1 Comm. link failure
[ 120 044 ]
47Z1031B
From the software version -661, the Single IP Ethernet module and Redundant IP
Ethernet module are available for the devices of the Easergy MiCOM 30 Series. To
get information of the former Ethernet module, please refer to the manuals before
-661.
The P438 Rail Catenary Protection Device can be fitted with new communication
module, the Single IP Ethernet module or Redundant IP Ethernet module. (See
Chapter 15, (p. 15-1) for the exact order information and Section 5.7, (p. 5-
34) for the location and connection diagrams.)
The Ethernet modules are developed to support PRP/HSR/RSTP redundancy
protocol, conformance of IEC 61850 edition 1 and 2, Cyber Security (CS) and
Flexible Product Naming (fPN).
Parameter Description
The maximum age of the information transmitted by the Bridge when it is the
Max age
Root Bridge.
Forward delay The delay used by Bridges to transition Root and Designated Ports to Forwarding.
From the software version -661, Easergy MiCOM P30 redundant brick configuration
tool is available to configure and read the RSTP configurations.
Forwarding
The devices from the families Easergy MiCOM 30, 40, the C264 and the MiCOM H
switches support store and forward mode. The MiCOM switch forwards messages
with known addresses to the appropriate port. The messages with unknown
addresses, the broadcast messages and the multicast messages are forwarded
out to all ports except the source port. MiCOM switches do not forward error
packets, 802.3x pause frames or local packets.
Priority Tagging
802.1p priority is enabled on all ports.
information, for instance “reports”. In its function as server the P438 can supply
up to 16 clients, linked into the network, with spontaneous or cyclic information.
It is not possible to read the IEC configuration back from the P438 if the “Dataset”
sizes exceed the GOOSE size limit significantly. Therefore it is recommended to
limit the “Dataset” size(s) to 100% of the GOOSE capacity. Too large a dataset can
spoil IEC 61850 communication. Hence, the dataset size limit of 100% of the
GOOSE capacity should not be exceeded, neither for GOOSE nor for reports.
Data objects provided by the P438 are available for selection with a structure as
specified by IEC 61850. Within the quality descriptor for each piece of
information the invalid bit and the test bit are served according to the P438’s
state; the other attributes are not set. Any number of datasets may be created
with the IED Configurator. Saving datasets at System\LLN0 is compulsory. The
knowledge of dataset content is imperative for decoding and evaluating received
signals. Configuration files possess a listing of all datasets with a description of
all data objects included.
Next to their use with high priority transmission methods (see
Section 3.5.5.2.1.9, (p. 3-45)) datasets are used mainly for reporting. The P438
provides up to 16 unbuffered reports and 8 buffered reports independent of the
number of clients logged-on. Management is arranged into 16 Unbuffered Report
Control Blocks (urcbA to urcbP) and 8 Buffered Report Control Blocks (brcbA to
brcbH). Whereas with unbuffered reporting pieces of information may be lost
during a communications failure, the buffered report control blocks support a
buffered transmission which is required for the uninterrupted writing of events. A
pre-defined dataset may be assigned to each report which will then determine
which data object will be transmitted with the relevant report. Assigning datasets
is not limited; the same dataset may be referenced in various reports or even in
GOOSEs.
The P438 can serve up to 16 clients. Each client can log-on to any number of
available reports. One unbuffered report can be allocated to max. 8 clients, and
one buffered report can be allocated to max. 4 clients. A client is then able to
activate the wanted report for himself and to set the transmission behavior to his
requirements. The system concept with intended clients must be taken into
account when datasets are assigned to the reports.
Reports are not received by the P438.
3.5.5.2.1.4 Transmitting Modeled Signals Not Provided by the IEC 61850 Data Model
In addition to the information included in the IEC 61850 data model an optional
number of up to 16 signals can be selected from all the signals available in the
P438 to be transmitted via reporting. A selection of state signals (shuttling to
communications) is made by setting IEC: SigGGIO1 selection. The data
object indexes defined for SigGGIO1 must follow the sequence given for the ‘m
out of n’ selection for the state signals. The indexes SigGGIO1.ST.ind1 to
SigGGIO1.ST.ind16 may then be included in the datasets just as the other data
objects.
1 remote-control See note [1] The control command is sent by an operator at station level.
(at the end of
this table).
2 automatic-remote See note [1]. The control command is sent by an automatic function at
station level.
3 station-control See note [1]. The control command is sent by an operator at network
level.
4 automatic-station See note [1]. The control command is sent by an automatic function at
network level.
5 bay-control Local HMI The control command is generated at the local HMI of the
Control P438.
6 bay-control Local EXT The control command is sent via binary input (see note [2])
Control by an operator at an external local control panel, using the
setting
● (221 061) MA IN: El ectri cal contr ol = Local
and any of the following input signals:
● DEV xx: Inp.asg.e l .ct rl .open
● DEVxx: In p.asg. el. ctr.cl ose .
7 remote-control Remote EXT The control command is sent via binary input (see note [2])
Control by an operator at an external local control panel, using the
setting
● (221 061) MA IN: El e ctrical con trol = Remote
and any of the following input signals:
● DEV xx: Inp.asg.e l .ctrl .open
● DEV xx: In p.asg. e l. ctr.cl ose .
[1]: The P438 copies the Originator Identification from the command request into
the information report.
The P438 does never send the Originator Category “automatic-bay”. In all
protection devices from the Easergy MiCOM 30 family, Automatic Reclose is
implemented as part of the protection functionality, and therefore it is treated as
process, see table row No. 8 above.
UC 7
UC 1,2
Network
HMI
Trip/close by external
Gateway protection or control
UC 7
UC 3,4 UC 10 , 11
UC 9
Circuit
Station
breaker
HMI UC 6, 7 UC 5 UC 8
F1
F2
t
F3
F4
F5
F6 I
Binary signal
Communication link
Internal interface 12Z7312D
Fig. 3-24: Use cases in the network context. The “UC” numbers refer to Originator Categories in the table above.
From the software version -661, VLAN is available for the devices of the Easergy
MiCOM 30 Series.
A virtual LAN (VLAN) is any broadcast domain that is partitioned and isolated in a
computer network at the data link layer (OSI layer 2). VLANs work through tags
within network packets and tag handling in networking systems - recreating the
appearance and functionality of network traffic that is physically on a single
network but acts as if it is split between separate networks. It is possible to
assign traffic to different VLANs to allow the separation of the traffic while using
a single physical network.
In the table below shows the link between the Hardware modules/ ports and IED
configurator inclusive requested VLAN support capability. Only physical interface
1 is to support VLANs in fixed number (2 VLANs for physical interface 1).
Default configuration
In general the Ethernet communication module is designed that all TCP/IP
services are working on all physical / virtual interfaces. The factory delivers a
communication module without any specific port assignment. In this case –
without port assignment and without VLAN – the communication services are
available without restriction on the physical Ethernet Interfaces. Depending on
the physical module type all services are working on A/B and C for redundant
modules or A and C for the single fiber module or only C for the single copper
module.
There is one exception the Web services for the SAT tool are only available on
one interface at a time. Please find the details in Section 3.5.5.2.4, (p. 3-48).
the second network is dedicated for maintenance services. The user can
configure configuration / administration services (configuration bus) as available
on physical port C and the client application services (station bus) as available on
port A/B.
The port assignment feature is available to together with the VLAN feature since
the firmware version 661. The same scenario as above can be configured with
VLAN together. For example VLAN1 as station bus and VLAN2 as configuration
bus.
TCP/IP service
The following list of TCP/IP services can be assigned to interfaces.
Services Description
IED configuration (TLS) Services via TLS to configure the device from Easergy Studio
1) Minimum configuration: at least ONE "IEC 61850 (MMS)" and at least ONE "Basic administration
(SSH/SFTP)" should be enabled across all interfaces
2) "User management via RBAC (Webservice)" option can be fully disabled or only enabled on ONE of
the available interfaces
Tab. 3-7: TCP/IP service in port assignment.
Configured example
3.5.5.2.5 Secure Communication with the Easergy Studio via the Ethernet Interface
When P438 and Easergy Studio are connected via the Ethernet interface, they
will communicate securely using TLS (Transport Layer Security Protocol). The
benefits of secure communication are:
● Help in the prevention of unwanted eavesdropping between Easergy Studio
and the IED.
● Help in the prevention of modification of data between Easergy Studio and
the IED.
● Ensure integrity of data.
● Help to prevent replay of data at a later data.
Setting up a connection, as a quick guide you need to do the following:
When attempting to connect to the IED via Ethernet, Easergy Studio will first
attempt to communicate with the IED via secure communication.
IEC:
IEC 61850 enable
[ 104 077 ]
IEC:
IEC prot. variant
[ 104 084 ]
IEC:
ETH COMM Mode
[ 104 080 ]
IEC:
Block Port A/B
[ 104 073 ]
IEC:
Block Port C
[ 104 074 ]
IEC:
Switch Config. Bank
[ 104 043 ]
IEC:
SigGGIO1 selection
[ 104 064 ]
IEC:
Diff. local time
[ 104 206]
IEC:
Diff. dayl.sav. time
[ 104 207 ]
IEC:
Switch.dayl.sav.time
[ 104 219 ]
IEC:
Dayl.sav.time start
[ 104 220 ]
IEC:
Dayl.sav.time st. d
[ 104 221 ]
IEC:
Dayl.sav.time st. m
[ 104 222 ]
IEC:
General enable USER IEC:
Dayl.sav.t.st.0:00 +
[ 104 000 ]
[ 104 223 ]
0 IEC:
Dayl.sav.time end
1 [ 104 225 ]
0: No IEC:
Dayl.sav.time end d
1: Yes [ 104 226 ]
IEC:
Dayl.sav.time end m
[ 104 227 ]
IEC:
Dayl.sav.t.end 0:00+
IEC: [ 104 228 ]
Ctrl blocked user
[ 221 125 ]
0: No
1: Yes
Commun. interface IEC:
Comm. link faulty
[ 105 180 ]
MAIN:
Test mode
[ 037 071 ] IEC:
Control blocked
[ 221 126 ]
48Z93A1A
The setting parameters from the IEC function group as well as the related GOOSE
function group are not automatically active in the P438. The P438 features two
memory “banks” one of which includes the active setting parameters. The other
memory bank is used with the configuration procedure for parameters from the
IED Configurator and the operating system. Specific project-related extensions of
the IEC 61850 parameters from the IED Configurator are loaded into the P438 by
downloading a .MCL file (Ed1) or .CID file (Ed2). The inactive communication
parameters are activated by executing the command IEC: Switch Config.
Bank. This command may also be issued from the IED Configurator.
System configurator
PACiS SCE
.iid
.scd
.icd
Operating program
.mcl (Ed1)
.cid (Ed2) .x3v
F1
F2
F3
F4
F5
F6
P438
12Z9002A
IED
Control PC
Processor module
Operating program
Device
parameters
Parameter
switch
Parameter download
Bank 1 Bank 2
IEC:
Sel.spontan.sig.test
[ 104 245 ]
Signal 1
Signal 2
Signal 3
Signal n
Selected signals
IEC:
Test spont.sig.start
[ 104 246 ]
IEC:
Spontan. sig. start
0 [ --- --- ]
0: don't execute
1: execute
IEC:
Test spont.sig. end
[ 104 247 ]
IEC:
Spontan. sig. end
0 [ --- --- ]
0: don't execute
1: execute
49Z9002A
» Device A » Device B
IEC 61850
Mapping
Easerg Studio
IED Configurator
System/LLN0/Dataset x
19Z8203C
It is not possible to read the IEC configuration back from the P438 if the “Dataset”
sizes exceed the GOOSE size limit significantly. Therefore it is recommended to
limit the “Dataset” size(s) to 100% of the GOOSE capacity. Too large a dataset can
spoil IEC 61850 communication. Hence, the dataset size limit of 100% of the
GOOSE capacity should not be exceeded, neither for GOOSE nor for reports.
When defining the datasets for GOOSE it is advised to select the individual data
attributes and not the overlapping data objects. By this the amount of data is
kept within a limit and decoding is guaranteed on the receiving end.
When a state change occurs with a selected state signal or a measured value
changes which is greater than the dead band set for the relevant data point then
the complete GOOSE is sent. There will be multiple send repetitions at ascending
time periods. The first send repetition occurs at the given cycle time set with the
parameter [IC]: Minimum Cycle Time. The cycles for the following send
repetitions result from a conditional equation with the increment set with the
parameter [IC] : Incre me nt. Should no further state changes occur up to the
time when the maximum cycle time has elapsed [ IC]: Maximu m Cy cle Time,
then GOOSE will be sent cyclically at intervals as set for the maximum cycle
time.
In order to have unambiguous identification of a GOOSE sent, characteristics
such as [I C]: Multicas t MAC Addres s, [IC] : A pplication I D (hex ),
[I C]: VL A N Identi fi er (he x), [I C] : V LA N P r iorit y and
[I C]: G OOSE Id en tif ie r must be entered in the IED Configurator settings.
Further characteristics are [IC ] : Datase t Ref e rence and
[IC]: Confi gu rat io n Re vis ion.
Each GOOSE is given the state change index and the number of send repetitions.
» Device A » Device B
Control/LLN0.ST.OrdRun.stVal
IED Configurator
System/LLN0/Dataset
x
19Z7004C
If with a system application it must be ensured that only one control command at
a time is being processed system wide (“uniqueness”) then interlocking of
secondary devices among themselves is setup with GOOSE. The P438 sets the
status information Control/LLN0.ST.OrdRun.stVal. when it has received a control
command. This information – stored in a dataset – is distributed in the system by
GOOSE and is therefore available to all other devices as an interlocking
condition. The state information is reset and accordingly signaled after
termination of the command sequence.
The P438 is capable to monitor the command status of up to 32 further devices.
With the IED Configurator OrdRunGGIO1.ind1.stVal to OrdRunGGIO1.ind32.stVal
are configured in a similar way to the other GOOSE inputs. A shuttling to the
interlocking equations is not necessary as their consideration within command
checking is automatically enabled when the first binary signal input is configured.
During a signaling receipt phase command effecting will be rejected.
Synchronization Readiness
If the IRIG-B interface is enabled and receiving a signal, the P438 checks the
received signal for plausibility. Implausible signals are rejected by the P438. If
the P438 does not receive a correct signal in the long run, synchronization will
not be ready any longer.
IRIGB:
General enable USER
[ 023 200 ]
IRIGB:
Enabled
[ 023 201 ]
IRIGB:
Synchron. ready
[ 023 202 ]
IRIGB:
EBR Synchron. ready
[ 023 203 ]
19Z9001A
Configurable function keys are available on the HMI with text display only.
The P438 provides six freely configurable function keys. A password may be
configured for each function key (e.g. for F1 at F_KEY: Password funct .k ey
1), and if a password has been configured then the respective function key will
only be enabled when the configured password is entered.
As an example the operation of function key F1 is shown in Fig. 3-33, (p. 3-59).
After the password has been entered the function key will remain active for the
time period set at F_KEY: Re tu rn ti me f ct.ke ys. Thereafter, the function key
is disabled until the password is entered again. The same is valid for function
keys F2 to F6. Exception: If a function key is configured as a control key a
password request is only issued when the function “Local/Remote switching” has
been assigned to this function key.
LED indicators including the six positioned directly next to the function keys are
configured independently and in this respect there is no relationship to the
respective function key configuration.
These control functions may only be used sensibly if all four of the above
commands have been configured thus engaging four of the available six function
keys.
Exception: For function keys configured as control keys the operating mode is
irrelevant and it is therefore ignored.
Handling keys
If backlighting for the LC display is switched off it will automatically light up when
a function key or the "READ" key is pressed. The assigned function will only be
triggered when the respective key is pressed a second time. This is also valid for
the other keys.
F_KEY:
Fct. assignm. F1
[ 080 112 ]
Function 1 EXT
Function 2 EXT
Function 3 EXT
Function n EXT
F_KEY:
Operating mode F1
[ 080 132 ]
1 & F_KEY:
State F1
2 [ 080 122 ]
1: Key
2: Switch
& & S1 1
& R1 0
1)
Fig. 3-33: Configuration and operating mode of function keys. The assigned function is either a single function or a
menu jump list.
Filter Function
An additional filter function may be enabled in order to suppress transient
interference peaks at the logic signal inputs (operating modes Active "high", filt.
or Active "low", filt.). With this function enabled a status change at the binary
logic input is only signaled when the input signal remains at a steady signal level
during a set number of sampling steps (sampling step size = period / 20). The
number of sampling steps is set at parameter INP : Filt er.
INP:
Fct. assignm. U xxx
[ XXX XXX ]
Function 1 EXT
Function 2 EXT
Function 3 EXT
Function n EXT
INP:
Oper. mode U xxx
[ YYY XXX ]
0: Active "low"
1: Active "high"
2: Active "low", filt.
3: Active "high", filt.
-Uxxx
&
Input signal
&
INP: &
Filter
[ 010 220 ]
&
INP:
State U xxx
&
[ ZZZ ZZZ ]
&
12Z6213A
Fig. 3-34: Configuration and operating mode of the binary signal inputs.
MEASI:
General enable USER
[ 011 100 ]
0
MEASI:
1 Enabled
[ 035 008 ]
0: No
1: Yes
S8Z52H1A
I DC,lin / I DC,nom
1.2
1.1
I DC,lin20 1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
I DC,lin1 0
0 0.1 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.6 I DC / I DC,nom
I DC1 I DC20
19Z5266A_EN
Fig. 3-36: Example of the conversion of 4 to 10 mA input current to 0 to 20 mA monitored current, IDC,lin.
IDC,lin / IDC,nom
0.8
Interpolation points
IDC,lin20 0.7
0.6
IDC,lin4 0.5
0.4
IDC,lin3 0.3
IDC,lin2 0.2
IDC,lin1 0.1
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2
Fig. 3-37: Example of a characteristic with five interpolation points (characteristic with zero suppression setting of
0.1 IDC,nom is shown as a broken line).
MEASI:
Enabled
[ 035 008 ]
SFMON:
Invalid scaling IDC
[ 093 116 ]
MEASI:
Overload 20mA input
[ 040 191 ]
Input channel 1(I-1) SFMON:
Overload 20 mA input
[ 098 025 ]
MEASI:
Open circ. 20mA inp.
[ 040 192 ]
SFMON:
Open circ. 20mA inp.
[ 098 026 ]
MEASI:
Curr. IDC,lin. p.u.
[ 004 136 ]
MEASI:
Current IDC p.u.
[ 004 135 ]
MEASI:
Current IDC
[ 004 134 ]
S8Z52H2A
Beyond the linearization described above, the user has the option of scaling the
linearized values. Thereby negative values, for example, can be displayed as well
and are available for further processing by protection functions.
MEASI:
Scaled val. IDC,lin1
[ 037 192 ]
MEASI:
Scaled val.IDC,lin20
[ 037 193 ]
MEASI: MEASI:
Curr. IDC,lin. p.u. Scaled value IDC,lin
[ 004 136 ] [ 004 180 ]
Q9Z5029A
MEASI:
Enabled
[ 035 008 ]
MEASI:
Open circ. PT100
Measur. input PT100 [ 040 190 ]
SFMON:
PT100 open circuit
[ 098 024 ]
MEASI:
Temperature T
[ 004 133 ]
MEASI:
Temperature p.u. T
[ 004 221 ]
MEASI:
Temperature Tmax
[ 004 233 ]
19Z5262A
Fig. 3-40: Temperature measurement using a PT 100 resistance thermometer connected to the analog (I/O)
module.
OUTP:
Outp.rel.block USER
[ 021 014 ]
0
OUTP:
1 Outp. relays blocked
≥1 [ 021 015 ]
0: No
OUTP: 1: Yes
Block outp.rel. EXT
[ 040 014 ] ≥1
MAIN:
Prot. ext. disabled
[ 038 046 ]
SFMON:
Hardware fault
304 950
OUTP:
Oper. mode K xxx
[ xxx xxx ]
1 ≥1
2
3
-K xxx
4
≥1
5
6
≥1
1: ES updating
2: ES manual reset
≥1
3: ES reset (fault)
OUTP:
Fct.assignment K xxx & S1 1
[ yyy xxx ]
R1
Signal 1
Signal 2
Signal 3 m out of n
Signal n
≥1 & ≥1
Selected signal
&
MAIN:
General starting OUTP:
1 Latching reset
[ 036 000 ] & [ 040 088 ]
FT_RC:
System disturb. runn
[ 035 004 ]
MAIN:
General reset USER
[ 003 002 ]
1: execute
MAIN:
General reset EXT
[ 005 255 ]
OUTP:
Reset latch. USER
[ 021 009 ]
1 1
100 ms
0: don't execute
1: execute
OUTP:
Reset latch. EXT
[ 040 015 ]
45Z8001A
Fig. 3-41: Configuration, setting the operating mode, and blocking the output relays.
OUTP:
Relay assign. f.test
[ 003 042 ]
OUTP:
Fct.assignment K xx1
[ AAA AAA ]
OUTP:
Fct.assignment K xx2
[ BBB BBB ]
OUTP:
Fct.assignment K xx3 -K xxx
[ CCC CCC ]
OUTP:
Fct.assignment K xxx
[ ZZZ ZZZ ]
OUTP:
Relay test
OUTP:
[ 003 043 ] Hold-time for test
[ 003 044 ]
0: don't execute
1: execute
Q6Z0139B
MEASI:
General enable USER
[ 011 100 ]
0
MEASI:
1 Enabled
[ 035 008 ]
0: No
1: Yes
S8Z52H1A
INP:
Fct. assignm. U xxx
[ xxx xxx ]
U x1
U x2
U x3
U xx
S8Z52H5A
MEASO:
Reset output USER
[ 037 116 ]
1
0: don't execute
1: execute
MEASO:
MEASO: Output reset
Reset output EXT
[ 036 087 ] [ 037 117 ]
MAIN:
General reset USER
[ 003 002 ] MEASO:
Reset meas.val.outp.
1: execute 304 601
MAIN:
Reset indicat. USER
[ 021 010 ]
1: execute
MAIN:
General reset EXT
[ 005 255 ]
MAIN:
Reset indicat. EXT
[ 065 001 ]
47Z13H6A
3.11.1.4 Scaling
Scaling is used to map the physical measuring range to the P438 inherent setting
range.
Scaling of analog output is also suited for directional-signed output of some fault
measurands, in particular fault location in percent.
Measurands Range
Scaling is made with reference to the complete range of values for the selected
measurand (variable Mx). The complete range of values is defined by their end
values Mx,RL1 and Mx,RL2. (Mx,RL1 and Mx,RL2 are listed in the operating
program - Easergy Studio - under “minimum” and “maximum”.)
Designation of the set values in the data "Scaled min. val. BCD" ... "Scaled max. val. BCD"
model
Measurands in the range "Measurands to BCD-Out min. value ... BCD-Out max. value
be output" (Valid BCD value)
Measurands Range
053 002 ME ASO : F ct. assi gnm. BC D FT_DA: Fau lt locat. pe rce nt
The following figure displays the values output as a function of the fault location.
The BCD value and the signal MEASO: Vali d BCD value = Yes are only issued
in the value range 0% to 200%.
200
FT_DA:
-320% 0% 200% 320% Fault locat. percent
[004 027]
47Z1040A
Except from radial, single circuit lines the fault location value gives a reasonable
value only for faults up to the line end. For any fault on a subsequent line the fault
location is more or less incorrect due to unknown fault current infeed in the remote
substation.
It is recommended to limit the calculation of a fault location to a practical and
sensible range on the line by setting F T _ D A : O u t p . f l t . l o c a t . P S x = Only aft.tr.
Z1ze/t1.
MEASO:
MEASO: Hold time output BCD
Enabled [ 010 010 ]
[ 037 102 ]
MEASO:
1-digit bit 0 (BCD)
[ 037 051 ]
MEASO:
1-digit bit 1 (BCD)
[ 037 052 ]
Setting blocked
MEASO:
1-digit bit 2 (BCD)
[ 037 053 ]
MEASO: MEASO:
Enable 1-digit bit 3 (BCD)
304 600 [ 037 054 ]
MEASO:
10-digit bit 0 (BCD)
[ 037 055 ]
MEASO:
10-digit bit 1 (BCD)
MEASO: [ 037 056 ]
Reset meas.val.outp.
304 601 MEASO:
10-digit bit 2 (BCD)
[ 037 057 ]
MEASO:
10-digit bit 3 (BCD)
[ 037 058 ]
MEASO:
100-dig. bit 0 (BCD)
[ 037 059 ]
Selected
MEASO:
meas. oper. value 100-dig. bit 1 (BCD)
[ 037 060 ]
Selected
Meas. event value
being updated
MEASO:
Selected meas. val. Valid BCD value
Value not measured [ 037 050 ]
MEASO:
Fct. assignm. BCD Meas. value ≥ 399
[ 053 002 ]
Measured value 1
Measured value 2
Measured value 3
Measured value n c1
c2
Scaling of the
BCD output
Selected meas. val. 1
++ 2
MEASO: 1...2
Output value x
[ * ]
0 . . . 100 %
x: 3 MEASO:
037 122 BCD-Out max. value 037 143
19Z5264A
Fig. 3-47: BCD measured data output. Overflow behavior is displayed in BCD example (see previous figure).
values Mx,RL1 and Mx,RL2. (Mx,RL1 and Mx,RL2 are listed in the operating
program – Easergy Studio – under “minimum” and “maximum”.)
Measurands Range
Scaled measurands with a scaled knee-point to be Mx,scal,min ... Mx,scal,knee ... Mx,scal,max
output with:
Mx,scal,min = (Mx,min - Mx,RL1) / (Mx,RL2 -
Mx,RL1
Mx,scal,knee = (Mx,knee - Mx,RL1) / (Mx,RL2 -
Mx,RL1)
Mx,scal,max = (Mx,max - Mx,RL1) / (Mx,RL2 -
Mx,RL1
Designation of the set values in the data model "Scal. min. value Ax" ...
... "Scal. knee-point Ax"
... "Scaled max. val. Ax"
Measurands Range
In this example the following P438 settings are selected in the menu branch
Parameter/Config. parameters:
053 000 MEASO : F ct. assig nm. A-1 MAIN: Freque ncy f
037 104 MEASO : Scaled m in. val. A-1 0.013 (corresponds with 0.02 Vnom)
037 105 ME ASO : Scaled k ne e val. A -1 0.067 (corresponds with 0.10 Vnom)
037 106 MEASO : Sca le d m ax. val . A-1 0.667 (corresponds with 1.00 Vnom)
By setting MEASO: AnOu t m in. val. A -1, the user can specify the output
current that will be output when values are smaller than or equal to the set
minimum measured value to be transmitted. The setting at MEASO: AnO ut
max . va l. A-1 defines the output current that is output for the maximum
measured value to be transmitted. By defining the knee-point, the user can
obtain two characteristic curve sections with different slopes. When entering this
setting the user must keep in mind that only a rising/rising or falling/falling curve
sense is permitted (peaky or vee shapes not allowed). If the setting was not
properly entered, the signal SFMON: I nvalid scaling A -1 will be issued.
A check of the set characteristic and its acceptance by the P438, if the setting was
properly entered, will only occur after the P438 is switched on-line again (with the
setting M A I N : P r o t e c t i o n e n a b l e d).
Ia / mA
20
Max. 18
output value
Knee point 16
output value
14
12
10
Min. 4
output value
2
0
0 0.02 0.1 1 1.2 1.3 1.4 1.5 Vnom
0.013 0.067 0.667 1.0 Mx,scal
19Z5265A
Fig. 3-48: Example of a characteristic curve for analog measured data output . In this example the range starting
value is = 0; also possible is directional-signed output (see corresponding example in section BCD Measured Data
Output).
MEASO:
Value A-1 output
[ 037 118 ]
MEASO:
MEASO: Hold time output A-1
Enabled [ 010 114 ]
[ 037 102 ]
Setting(s) blocked c
MEASO:
Enable
304 600
An. outp. ch.1 (A-1)
[ --- --- ]
MEASO: R
Reset meas.val.outp.
304 601
Selected
meas. oper. value
OUTP: Selected
Fct.assignment K xxx Meas. event value
[ xxx xxx ] being updated
c
K x1
K x2 MEASO:
Scaled min. val. A-1
K x3 [ 037 104 ]
K xx MEASO:
Scaled knee val. A-1
[ 037 105 ]
c
MEASO:
Value A-1 output MEASO:
[ 037 118 ] Scaled max. val. A-1
[ 037 106 ]
MEASO:
AnOut min. val. A-1
[ 037 107 ]
MEASO:
Fct. assignm. A-1
MEASO:
[ 053 000 ] AnOut knee point A-1
[ 037 108 ]
Measured value 1
MEASO:
AnOut max. val. A-1
Measured value 2 [ 037 109 ]
Measured value 3
Measured value n
SFMON:
Selected meas. val. Invalid scaling A-1
[ 093 114 ]
c1
0 . . . 100 % Value < AnOut range c2
c3
S8Z52H8B
H 4 (red) TRIP With the P438 this LED indicator is customarily configured with
function MA IN: Ge n. tri p si gnal, but the configuration may
be modified.
H 17 (red) EDIT MODE Not configurable. H 17 indicates the input (edit) mode. Only
when the P438 is in this mode, can parameter settings be
changed by pressing the “Up” and “Down” keys. (See
Section 6.2, (p. 6-2))
H 5 to H 16 ― For each of these LED indicators both colors (red & green) may
H 18 to H 23 be configured freely and independently.
TRIP
H18
ALARM
OUT OF SERVICE
HEALTHY
H19
EDIT MODE
H20
H21
H22
H23
Fig. 3-50: Layout of the LED indicators (local control panel with text display)
The following figure illustrates the layout of LED indicators situated on the local
control panel with graphic display.
H4 TRIP
H3 ALARM
H2 OUT OF SERVICE
H1 HEALTHY
H17 EDIT MODE
H5
H6
H7
H8
H9
H10
H11
H12
H13
H14
H15
H16
Fig. 3-51: Layout of the LED indicators (local control panel with graphic display)
This results in 12 operating modes that are available for every freely configurable
LED indicator.
LED:
Oper. mode H xx
[ xxx xxx ]
10
11
12
13 ≥1
1: ES updating
2: ES manual reset
3: ES reset (fault)
4: ES reset (syst.dist) !G!
5: NE updating
6: NE manual reset
7: ES updating bl
8: ES manual reset bl -Hxx (red)
9: ES reset (fault) bl
10: ES rst (syst.dst) bl
11: NE updating bl
12: NE manual reset bl
13: ES Alarmunit
& LED:
State Hxx red
[ zzz zzz ]
LED: &
Fct.assig. Hxx red
[ yyy yyy ]
&
Signal 1 &
Signal 2 &
Signal 3 m out of n
Signal n
& S1 1
& R1
Selected signals
&
&
MAIN:
General starting
[ 036 000 ]
&
FT_RC:
System disturb. runn
[ 035 004 ]
MAIN:
General reset EXT
[ 005 255 ]
MAIN:
General reset USER
[ 003 002 ]
1: execute
MAIN:
Reset LED
306 020 19Z8100A
Supply Catenary
MAIN:
I> Feeder mode
[ 010 135 ]
MAIN:
Vnom V.T. sec.
[ 010 009 ]
V̲A
V̲
MAIN: MAIN:
Conn. meas. circ. I Inom device
[ 010 004 ] [ 010 003 ]
I̲A
X.Y I̲
1: Standard
2: Opposite
Catenary
Rail 48Z9301A
Fig. 3-53: Connecting the P438 measuring circuits in the 'Classic single feed' operating mode.
Supply Catenary
Supply Feeder
MAIN:
Feeder mode
[ 010 135 ]
2
I>
3
V̲B/V̲ref
V̲B/V̲ref
+ V̲
-
MAIN: MAIN:
Conn. meas. circ. I Inom device
[ 010 004 ] [ 010 003 ]
I̲A
X.Y I̲A
I̲B
X.Y I̲B
1: Standard
2: Opposite
+ I̲
-
Feeder
Catenary
Rail 48Z9302A
Fig. 3-54: Connecting the P438 measuring circuits in the 'Autotransformer feed' operating mode.
Supply Catenary
I>
MAIN:
Feeder mode
[ 010 135 ]
V̲
MAIN: MAIN:
Conn. meas. circ. I Inom device
[ 010 004 ] [ 010 003 ]
I̲A
X.Y I̲A
I̲B
X.Y I̲B
1: Standard
2: Opposite
+ I̲
-
Catenary
Rail
Catenary
Rail 48Z9304A
Fig. 3-55: Connecting the P438 measuring circuits in the 'single feed with summated current' operating mode.
In addition to the protection of the catenary in normal train operation, the P438
also provides defrost protection. An additional current transformer must be
connected when the device is in the 'Defrost operation' operating mode.
Fig. 3-56, (p. 3-92) shows the connection with 'Defrost operation'. In this
operating mode, circuit breakers Q1, Q3 and Q4 are closed whereas circuit
breaker Q2 is open. It is important to ensure - from the installation side - that
circuit breaker Q2 is opened before circuit breakers Q3 and Q4 are closed.
Supply Catenary
Q1 Q2
MAIN: MAIN:
Conn. meas. circ. I Inom device
[ 010 004 ] [ 010 003 ]
I̲A
I̲
1: Standard
2: Opposite
MAIN: MAIN:
MsCirc.Iplaus/Idfrst Iplaus/Idfrst,CTnom
[ 010 036 ] [ 010 017 ]
I̲plaus/I̲dfrst
X.Y I̲plaus/I̲dfrst
1: Standard
2: Opposite
Catenary 1
Q3
Catenary 2
Q4
Rail
48Z9303A
Fig. 3-56: Connecting the P438 measuring circuits for 'Defrost operation'.
Supply Catenary
I>
MAIN:
Vnom V.T. sec.
[ 010 009 ]
V̲A
V̲
MAIN: MAIN:
Conn. meas. circ. I Inom device
[ 010 004 ] [ 010 003 ]
I̲A
X.Y I̲
1: Standard
2: Opposite
MAIN: MAIN:
MsCirc.Iplaus/Idfrst Iplaus/Idfrst,CTnom
[ 010 036 ] [ 010 017 ]
I̲plaus/I̲dfrst
X.Y I̲plaus/I̲dfrst
1: Standard
2: Opposite
Catenary
Rail 48Z9300A
Fig. 3-57: Connecting the P438 measuring circuits for 'Plausibility check'.
Fig. 3-58, (p. 3-94) shows the connection with optional function Automatic
Synchronism Check. The ASC is available in classical single feeding mode or
Single feed w. sum I mode, 1st voltage for the phase voltage, and 2nd voltage for
the reference voltage of the network.
Supply Catenary
MAIN:
Feeder mode
[ 010 135 ]
I> 1
V̲
I>
V̲B/V̲ref
V̲B/V̲ref
Catenary
Rail
48Z9305A
Fig. 3-58: Connecting the P438 measuring circuits in the 'Classic single feed' operating mode, optional with
reference voltage for ASC.
MAIN:
Meas. value rel. I
MAIN: [ 011 030 ]
General start. int.
306 539
MAIN: c
Hardware fault
306 540
I̲ c1
I̲A c2
I̲B c3
I̲plaus/I̲dfrst c4
1 MAIN:
Current I p.u.
[ 004 111 ]
2 MAIN:
Current IA p.u.
[ 005 041 ]
3 MAIN:
Current IB p.u.
[ 006 041 ]
4 MAIN:
Iplaus/Idfrst. p.u.
[ 004 201 ]
MAIN:
Inom C.T. prim.
[ 010 001 ]
MAIN:
Current I prim.
[ 004 110 ]
MAIN:
Current IA prim.
[ 005 040 ]
MAIN:
Current IB prim.
[ 006 040 ]
MAIN:
Iplaus/Idfrst,CTprim
[ 010 016 ]
MAIN:
Iplaus/Idfrst. prim.
[ 004 200 ]
48Z9306A
MAIN:
Meas. value rel. I
MAIN: [ 011 030 ]
General start. int.
306 539
MAIN: c
Hardware fault
306 540
I̲ c1
fnom MAIN:
Current I(fn) p.u.
[ 008 110 ]
2 * fnom
MAIN:
Current I(2fn) p.u.
[ 008 096 ]
3 * fnom MAIN:
Current I(3fn) p.u.
[ 008 098 ]
5 * fnom MAIN:
Current I(5fn) p.u.
[ 008 100 ]
7 * fnom
MAIN:
Current I(7fn) p.u.
[ 021 058 ]
MAIN:
Inom C.T. prim.
[ 010 001 ]
MAIN:
Current I(fn) prim
[ 008 109 ]
MAIN:
Current I(2fn) prim
[ 008 095 ]
MAIN:
Current I(3fn) prim
[ 008 097 ]
MAIN:
Current I(5fn) prim
[ 008 099]
MAIN:
Current I(7fn) prim
[ 021 051 ]
48Z9307A
MAIN:
MCMON: Meas. value rel. I
Meas. circ. V faulty [ 011 030 ]
[ 038 023 ]
MAIN: c
Hardware fault
306 540
V̲ c1
V̲A c2
V̲B/V̲ref c3
1 MAIN:
Voltage V p.u.
[ 004 113 ]
2 MAIN:
Voltage VA p.u.
[ 005 043 ]
3 MAIN:
Voltage VB/Vref p.u.
[ 006 043 ]
MAIN:
Vnom V.T. prim.
[ 010 002 ]
MAIN:
Voltage V prim.
[ 004 112 ]
MAIN:
Voltage VA prim.
[ 005 042 ]
MAIN:
Voltage VB/Vref prim
[ 006 042 ]
48Z9308A
The measured voltage values are displayed both as per-unit quantities referred
to the nominal quantities of the P438 and as primary quantities. To allow a
display in primary values, the primary nominal voltage of the system transformer
needs to be set in the P438.
3.13.2.3 Measured Values for Power, Active Power Factor, and Load Flow
If there is a fault in the hardware or in the voltage-measuring circuit, the
measured values are not determined.
The fundamental components of current and voltage are used for determining
the measured values.
Calculation of these derived operating quantities is subject to the following
conditions:
● Angles and load flow direction are determined only if the current exceeds
the minimum threshold of 0.1 In and if the voltage exceeds the threshold of
1 V.
● Values for active and reactive power will always be calculated and
displayed as these quantities are required for the subsequent energy
measurement. Greater deviations in measurements may occur with low
phase currents or a critical power factor value.
● The active power factor will be calculated only if the apparent power value
exceeds 5% of the nominal apparent power Snom.
MCMON:
Meas. circ. V faulty
[ 038 023 ] & &
MAIN:
Hardware fault
306 540
I̲
>0.1 Inom
V̲
<1V
MAIN:
Nominal frequ. fnom c
[ 010 030 ]
fnom
MAIN:
fnom Load angle phi
[ 004 167 ]
/100° MAIN:
Load angle phi p.u.
[ 004 078 ]
-45°> N <135° 1
-45°< N >135° 2
MAIN:
1 ... 2 Load flow direction
[ 004 166 ]
1 MAIN:
Load flow forward
[ 039 076 ]
2 MAIN:
Load flow backwards
[ 039 077 ]
48Z9309A
Fig. 3-62: Measured operating data – Angle and load flow direction.
MCMON:
Meas. circ. V faulty
[ 038 023 ] &
MAIN:
Hardware fault
306 540
MAIN:
Nominal frequ. fnom c
[ 010 030 ]
I̲ fnom
MAIN:
Active power P p.u.
[ 004 051 ]
V̲ fnom
MAIN:
Reac. power Q p.u.
[ 004 053 ]
MAIN:
Active power factor
[ 004 054 ]
MAIN:
Inom C.T. prim.
[ 010 001 ]
MAIN:
Vnom V.T. prim.
[ 010 002 ]
MAIN:
Active power P prim.
[ 004 050 ]
MAIN:
Reac. power Q prim.
[ 004 052 ]
48Z9310A
Fig. 3-63: Measured operating data – Power and active power factor.
MCMON:
Meas. circ. V faulty
[ 038 023 ] & &
MAIN:
Hardware fault
306 540
I̲
>0.1 Inom
V̲
<1V
MAIN:
Nominal frequ. fnom c
[ 010 030 ]
fnom
MAIN:
Load impedance Z p.u
[ 005 004 ]
fnom
c
MAIN:
Inom device
[ 010 003 ]
MAIN:
Vnom V.T. sec.
[ 010 009 ]
MAIN:
Load impedance Z sec
[ 005 000 ]
MAIN:
Load reactance X sec
[ 005 195 ]
MAIN:
Load resist. R sec
[ 005 197 ]
MAIN:
Inom C.T. prim.
[ 010 001 ]
MAIN:
Vnom V.T. prim.
[ 010 002 ]
MAIN:
Load imped. Z prim.
[ 005 005 ]
MAIN:
Load react. X prim.
[ 005 196 ]
MAIN:
Load resist. R prim.
[ 005 198 ]
48Z9311A
Fig. 3-64: Measured operating data – Operating impedance, reactance and resistance.
3.13.2.5 Frequency
< 10 V
MCMON:
Meas. circ. V faulty c
[ 038 023 ] &
MAIN:
Hardware fault
306 540
V̲ c
f MAIN:
Frequency f
[ 004 040 ]
MAIN:
Nominal frequ. fnom
[ 010 030 ]
MAIN:
Frequency f p.u.
[ 004 070 ]
48Z9312A
The P438 determines the frequency from the voltage. The frequency is
determined only if the voltage exceeds a minimum threshold of 10 V and if there
is no fault in the voltagemeasuring circuit.
MAIN:
Active power P prim.
[ 004 050 ] ∫P(t) dt MAIN:
Act.energy outp.prim
R [ 005 061 ]
-∫P(t) dt MAIN:
Act.energy inp. prim
R [ 005 062 ]
MAIN:
Reac. power Q prim.
[ 004 052 ] ∫Q(t) dt MAIN:
MAIN: React.en. outp. prim
Reset meas.v.en.USER R [ 005 063 ]
[ 003 032 ]
0 -∫Q(t) dt MAIN:
React. en. inp. prim
R [ 005 064 ]
1
0: don't execute
Overflow MAIN:
No.overfl.act.en.inp
Transfer [ 009 091 ]
Overflow MAIN:
No.ov/fl.reac.en.out
Transfer [ 009 092 ]
MAIN:
Overflow No.ov/fl.reac.en.inp
[ 009 093 ]
Transfer
48Z9356A
Fig. 3-66: Determining the active and reactive energy output and input.
The P438 determines the active and reactive energy output and input based on
the primary active or reactive power.
Measured energy values are presented as text parameters with a value range of
about 0 … 6.5 TWh and a resolution of 10 kWh. In addition, 16 bit values and
overflow counters are provided, which are needed for transmission via serial
protocols (e.g. Modbus, DNP3, Courier).
Energy values as 32 bit / text Energy values as 16 bit values Overflow counters for the 16 bit
values Value range: 0 … 655,35 MWh energy values
Value range: 0 … Value range: 0 … 10000
6553500.00 MWh
(008 065) MAIN: Act .energy (005 061) MAI N: A ct. en ergy (009 090)
ou tp. prim outp.pri m MA IN: No.overfl .act.en.out
(008 066) MAIN: Act .energy (005 062) MAI N: A ct.en ergy (009 091)
in p. p rim inp. prim MA IN: No.overfl. act.e n.inp
(008 067) M AIN: React .en. (005 063) MA IN: React.e n. (009 092) MAI N: No.ov/
outp. prim out p. prim fl .re ac.en.ou t
(008 068) MAIN: R eact . en. (005 064) MA IN: React. en . (009 093) MA IN: No.ov/
inp. prim inp. prim f l.reac.en .in p
5%
2%
45° 70°
Phase Angle
S8Z0401B
Fig. 3-67: Error of measurement in the determination of energy output resulting from the phase angle error of the
P438.
Error of measurement:
● Approx. ±2% of the measured value for |cos φ| ≥ 0.7
● Approx. ±5% of the measured value for |cos φ| ≥ 0.3
● where the whole measuring range is −180° ≤ φ ≤ 180°.
For phase angles φ with |cos φ| < 0.3, or when the error of measurement
resulting from the maximum phase-angle error is not acceptable, external
counters should be used to determine the energy output.
MAIN:
Protection enabled
[ 003 030 ]
0 0: No (= off)
1 MAIN:
Protection active
306 001
0: No (= off)
1: Yes (= on)
INP:
Fct. assignm. U xxx
[ 152 xxx ]
U x1
U x2
U x3
U xx
MAIN:
Enable protect. EXT
[ 003 027 ]
MAIN:
Prot. ext. disabled
MAIN: [ 038 046 ]
Disable protect. EXT
[ 003 026 ]
D5Z5004A
If the protection is disabled via a binary signal input that is configured for
M A I N : D i s a b l e p r o t e c t . E X T, the signal M A I N : B l o c k e d / f a u l t y is not issued.
MAIN: MAIN:
Protection active &
Rush restraint ready
306 001
[ 041 024 ]
MAIN:
Block.rush restr.EXT
[ 039 169 ]
MAIN:
Rush I(2fn)/I(fn)PSx
[*]
blocked
MAIN: MAIN:
I> lift rush rstrPSx t lift rush rstr.PSx
C
[ * ] [ * ]
I̲ MAIN:
Rush restr.triggered
& 1 t &
[ 041 025 ]
MAIN:
I> enable rush r.PSx
[ * ]
48Z9313A
MAIN:
Funct.Rush restr.PSx
[ * ]
m out of n
MAIN:
Inrush stabil. trigg
306 014
BUOC: BUOC:
MAIN: Starting I> Bl.Start. I>
Rush restr.triggered 036 013
[ 041 025 ] BUOC: BUOC:
Starting I>> Bl.Start. I>>
036 115
DELTA: DELTA:
Delta I starting Bl.Start Delta I
038 060
DIST: DIST:
WPC starting Bl.Start. WPC
039 158
DIST: DIST:
Z1 (Z1,ze) starting Bl.Start. Z1(Z1, ze)
039 003
DIST: DIST:
Z1'(Z1',ze) starting Bl.Start. Z1'(Z1', ze)
039 004
DIST: DIST:
Z2 starting Bl.Start. Z2
039 005
DIST: DIST:
Z2' starting Bl.Start. Z2'
039 006
DIST: DIST:
Z3 starting Bl.Start. Z3
039 140
DIST: DIST:
Z3' starting Bl.Start. Z3'
039 141
DIST: DIST:
Z4 starting Bl.Start. Z4
039 042
DIST: DIST:
Z4' starting Bl.Start. Z4'
039 043
DTOC: DTOC:
Starting I> Bl.Start. I>
035 020
DTOC: DTOC:
Starting I>> Bl.Start. I>>
035 021
DTOCA: DTOCA:
Starting I> Bl.Start. I>
130 069
DTOCA: DTOCA:
Starting I>> Bl.Start. I>>
130 070
DTOCB: DTOCB:
Starting I> Bl.Start. I>
130 089
DTOCB: DTOCB:
Starting I>> Bl.Start. I>>
130 090
MAIN:
Parameter Funct.Rush restr.PSx IDMT: IDMT:
Starting Iref> Bl.Start. Iref>
040 080
set 1 017 093
48Z9314A
IDMTA: IDMTA:
set 2 017 064 Starting Iref> Bl.Start. Iref>
130 110
set 3 017 082
IDMTB: IDMTB:
set 4 017 083 Starting Iref> Bl.Start. Iref>
130 130
Fig. 3-70: Selection of the stabilization criteria for the inrush stabilization.
The inrush stabilization is designed with respect to function groups DIST, DELTA,
BUOC, DTOC, DTOCA, DTOCB, IDMT, IDMTA and IDMTB. Depending on the
parameter MAIN : Funct.R ush re str .P Sx the starting of these function groups
is blocked selectively.
MAIN: MAIN:
Protection active &
Harm.blocking ready
306 001
[ 021 016 ]
MAIN:
Block. harm.blk. EXT
[ 021 073 ]
MAIN:
I(3fn)/I(fn) PSx &
[*]
blocked
MAIN:
I(5fn)/I(fn) PSx
[*]
blocked MAIN:
I>Lift harm.blk. PSx
MAIN: C
I(7fn)/I(fn) PSx [ * ]
[*]
blocked
t MAIN:
I̲ & 0 HARM. blk. triggered
[ 021 011 ]
MAIN:
I>Enable harm.b. PSx
[ * ]
MAIN:
I(3fn)/I(fn) PSx
[ * ]
MAIN:
& I(3fn) starting
3*fnom
[ 023 253 ]
MAIN:
I(5fn)/I(fn) PSx
[ * ]
fnom
MAIN:
& I(5fn) starting
5*fnom
[ 023 254 ]
MAIN:
I(7fn)/I(fn) PSx
[ * ]
fnom
MAIN:
I(7fn) starting
&
7*fnom [ 023 255 ]
set 1 020 248 020 244 020 229 020 233 020 238
set 2 020 249 020 245 020 230 020 235 020 239
set 3 020 250 020 246 020 231 020 236 020 242
set 4 020 251 020 247 020 232 020 237 020 243
48Z9315A
Harmonics blocking is blocked if all of MAI N: I( 3fn )/I(fn ) PSx, MAI N: I(5fn)/
I (fn) PSx and MA IN: I(7f n) /I(f n) PSx are set to 'Blocked' or if an external
blocking signal has been triggered.
The harmonics blocking function detects the ratio of the third, fifth and seventh
harmonic currents to the fundamental and can selectively prevent starting of
selected protection functions. If this ratio exceeds the threshold, then the
harmonics blocking operates.
The current trigger MA IN: I >En able harm.b. PSx and a threshold
MAI N: I>Lift harm.blk. PSx define the range in which the harmonics blocking
operates. If the current is outside of this range then the harmonics blocking is
blocked.
The harmonics blocking function gets activated only, if the harmonics were
detected for minimal 2 periods of the base frequency. This avoids an early
blocking of the distance protection in the transient phase of a real network fault
appearance.
MAIN:
Funct.Harm.block.PSx
[ * ]
m out of n
MAIN:
Harm. blk. trigg
460 649
BUOC: BUOC:
MAIN: Starting I> Bl.Start. I>
HARM. blk. triggered 036 013
DIST: DIST:
WPC starting Bl.Start. WPC
039 158
DIST: DIST:
Z1 (Z1,ze) starting Bl.Start. Z1(Z1, ze)
039 003
DIST: DIST:
Z1'(Z1',ze) starting Bl.Start. Z1'(Z1', ze)
039 004
DIST: DIST:
Z2 starting Bl.Start. Z2
039 005
DIST: DIST:
Z2' starting Bl.Start. Z2'
039 006
DIST: DIST:
Z3 starting Bl.Start. Z3
039 140
DIST: DIST:
Z3' starting Bl.Start. Z3'
039 141
DIST: DIST:
Z4 starting Bl.Start. Z4
039 042
DIST: DIST:
Z4' starting Bl.Start. Z4'
039 043
DTOC: DTOC:
Starting I> Bl.Start. I>
035 020
DTOC: DTOC:
Starting I>> Bl.Start. I>>
035 021
DTOCA: DTOCA:
Starting I> Bl.Start. I>
130 069
DTOCA: DTOCA:
Starting I>> Bl.Start. I>>
130 070
DTOCB: DTOCB:
Starting I> Bl.Start. I>
130 089
DTOCB: DTOCB:
Starting I>> Bl.Start. I>>
130 090
IDMT: IDMT:
MAIN: Starting Iref>
Parameter Funct.Harm.block.PSx Bl.Start. Iref>
040 080
Fig. 3-72: Selection of the stabilization criteria for the Harmonics blocking.
The harmonics blocking is designed with respect to function groups DIST, BUOC,
DTOC, DTOCA, DTOCB, IDMT, IDMTA and IDMTB. Depending on the parameter
MAIN : Funct.Harm .bl ock.P Sx the starting of these function groups is blocked
selectively.
MAIN: &
Protection active
f<>:
Ready
[ 042 101 ]
& f<>:
V̲Meas
fnom
V̲
MAIN:
Undervolt. block. V<
[ 018 200 ]
f<>:
Blocked by V<
[ 042 102 ]
MAIN:
Evaluation time
[ 018 201 ]
f Φ
f<>:
No. periods reached
f<>:
fMeas
48Z9317A
The over-/underfrequency protection f<> uses some general settings for the
frequency measurement:
● the evaluation time
● the undervoltage blocking
The over-/underfrequency protection requires a measuring voltage of sufficient
magnitude. Therefore it is blocked instantaneously if the measuring voltage falls
below the set threshold of the undervoltage stage.
In order to avoid frequency stage starting caused by brief frequency fluctuations
or interference, the evaluation time can be set by the user. The operate
conditions must be satisfied for at least the duration of the set evaluation time in
order for a signal to be issued.
MAIN:
Inp.asg. fct.block.1
[ 221 014 ]
Signal 1
Signal 2 MAIN:
Op. delay fct. block
Signal 3 [ 221 029 ]
Signal n
t 0 MAIN:
Selected signal Fct. block. 1 active
[ 221 015 ]
t 0 MAIN:
MAIN: Fct. block. 2 active
Inp.asg. fct.block.2 [ 221 023 ]
[ 221 022 ]
Selected signal
F0Z5016B
MAIN:
Fct.assign. block. 1
[ 021 021 ]
Function 1
m out of n
Function 2
Function n
MAIN:
Blocking 1 EXT
[ 040 060 ]
MAIN:
Fct.assign. block. 2
[ 021 022 ]
Function 1
m out of n
Function 2
Function n
MAIN:
Blocking 2 EXT
[ 040 061 ]
D5Z50CLA
3.13.9 Blocked/Faulty
MAIN:
Protection enabled
[ 003 030 ]
0: No (= off) MAIN:
Protect. not ready
[ 004 060 ]
MAIN:
SFMON: Blocked/faulty
Blocking [ 004 065 ]
304 951
MAIN:
Trip cmd. blocked
[ 021 013 ]
MAIN:
Fct. assign. fault
[ 021 031 ]
Signal 1
m out of n
Signal 2
Signal 3
Signal n
Selected signals
D5Z50EHA
functions can be selected that will issue the MAIN: Blocked/faulty signal by
setting a “m out of n” parameter.
3.13.10 Coupling between Control and Protection for the CB Closed Signal
Bay type selection defines the external device (DEV01 or DEV02 or ...) that
represents the circuit breaker. Coupling between control and protection for the
“Closed” position signal is made by the setting MAIN: Sig.assign. CB close.
As a result, the CB status signal needs to be assigned to one binary signal input
only if this coupling is implemented.
MAIN:
Sig.assign. CB close
[ 021 020 ]
DEV01:
Closed signal EXT
[ 210 031 ]
DEV02:
Closed signal EXT
[ 210 081 ]
DEV10:
Closed signal EXT
[ 211 231 ] Selected signal
[ xxx xxx ]
U x1
U x2
U x3
U xx
19Z9301A
Fig. 3-77: Coupling between control and protection for the CB closed signal.
MAIN:
M-trip signal 1
[ 039 101 ]
MAIN:
R-trip signal 1
[ 039 103 ]
MAIN:
CB closed A EXT
[ 036 051 ]
MAIN:
CB closed B EXT
[ 031 030 ]
MAIN:
ClCmd inhib.by CB cl
[ 015 042 ]
0: No
1: Yes
MAIN: MAIN:
En.man.clos.cmd.USER Rel.t. enab. man.cmd
[ 003 105 ] [ 003 088 ]
0
1 t MAIN:
1 Man. cl. cmd.enabl.
[ 039 113 ]
0: No
1: Yes
MAIN:
Man. close cmd. USER
[ 018 033 ]
MAIN:
tCB, Close
0 [ 000 032 ]
MAIN: MAIN:
Man.cl.cmd.enabl.EXT Man. close cmd. EXT
[ 041 023 ] [ 041 022 ]
MAIN:
Man. close cmd. EXT
[ 041 022 ]
MAIN:
C Close cmd.pulse time
ARC: &
(Re)close request [ 015 067 ]
[ 037 077 ]
MAIN:
ASC: Close command
Close enable
[ 037 083 ] 1 t [ 037 009 ]
ASC:
Enabled
&
[ 018 024 ]
&
ASC:
Manual close request
305 000 &
MAIN:
Reset c. cl/tr.cUSER
[ 003 007 ]
0 + MAIN:
No. close commands
1 [ 009 055 ]
MAIN:
General reset EXT
[ 005 255 ]
MAIN:
Reset c. cl/tr.c EXT
[ 005 210 ]
48Z9318A
The circuit breaker can be closed by the auto-reclosing control function (ARC), by
the automatic synchronism check (ASC), by parameters or via an appropriately
configured binary signal input. The close command by parameters or a binary
signal input is only executed if there is no trip command 1 present and no trip
has been issued by a protection device operating in parallel. Moreover, with the
setting of MAI N: C lCm d i nh ib.by CB cl to Yes, the close command is not
executed if there is a “CB closed” position signal present. The duration of the
close command can be set.
If the ARC function issues a close request while the ASC function is enabled, then
the close command requires a close enable by the ASC function.
MAIN:
Inp.asg. mult.sig. 1
[ 221 051 ]
Signal 1
Signal 2
Signal 3
Signal n
MAIN:
Mult. sig. 1 stored
MAIN: S 11
[ 221 054 ]
Inp.asg. mult.sig. 2
[ 221 052 ] R1
COMM1:
Reset mult. sig. 1 MAIN:
[ --- --- ] Mult. sig. 2 stored
S 11 [ 221 055 ]
COMM1:
Reset mult. sig. 2 R1
[ --- --- ]
MAIN:
General reset USER
[ 003 002 ]
1: execute
MAIN:
General reset EXT
[ 005 255 ]
OUTP:
Reset latching
402 102
MAIN:
Reset LED
306 020
12Z62FMA
The multiple signals 1 and 2 are formed by the programmable logic function
using OR operators. The programmable logic output to be interpreted as multiple
signaling is defined by the configuration of the binary signal input assignment
with the corresponding multiple signaling. Both an updated and a stored signal
are generated. The stored signal is reset by the following actions:
● General reset
● Latching reset
● LED indicators reset
● A command received through the communication interface
If the multiple signaling is still present at the time of a reset, the stored signal
will follow the updated signal.
MAIN:
General reset USER MAIN:
[ 003 002 ] >+ No. general start.
↗ 1: execute ≥1 >R [ 004 000 ]
MAIN:
General reset EXT
[ 005 255 ]
DIST: ≥1
Starting MAIN:
General starting
[ 036 135 ]
[ 036 000 ]
DELTA:
Delta I starting
[ 038 060 ]
BUOC:
Starting I>
[ 036 013 ]
BUOC:
Starting I>>
[ 036 115 ]
DTOC:
Starting I>
[ 035 020 ]
DTOC:
Starting I>>
[ 035 021 ]
DTOCA:
Starting I>
[ 130 069 ]
DTOCA:
Starting I>>
[ 130 070 ]
DTOCB:
Starting I>
[ 130 089 ]
DTOCB:
Starting I>>
[ 130 090 ]
IDMT:
Starting Iref>
[ 040 080 ]
IDMTA:
Starting Iref>
[ 130 110 ]
IDMTB:
Starting Iref>
[ 130 130 ]
48Z9319A
MAIN:
MAIN: ≥1 500 ms Start. PIR M-trip
M-trip command 1
[ 039 014 ]
[ 039 011 ]
MAIN:
M-trip command 2
[ 039 058 ]
MAIN: ≥1 MAIN:
500 ms Start. PIR R-trip
R-trip command 1
[ 039 012 ] [ 039 015 ]
MAIN:
R-trip command 2
[ 039 059 ] 48Z9320A
In the event of the end of the main-trip and re-trip command a timer stage of 500
ms is started. While this timer stage is running, the 'PIR Starting' signals are set.
(PIR: Automatic testing device for Catenary, with a pre-insertion/pre-closing
resistor as a line check)
MAIN:
Trip cmd. blocked
[ 021 013 ]
MAIN:
Block. M-trip USER
[ 022 090 ]
MAIN:
0 M-trip blocked
[ 039 050 ]
1
0: No
1: Yes
MAIN:
Block. M-trip EXT
[ 038 050 ]
MAIN: MAIN:
Man. M-trip signal 1 M-trip signal 1
[ 039 081 ] [ 039 101 ]
MAIN:
Min.dur. M-trip cmd1
MAIN:
Fct.asg. M-trip cmd1 [ 021 034 ]
[ 021 007 ]
Signal 1 1 t MAIN:
M-trip command 1
Signal 2 [ 039 011 ]
m out of n
Signal 3
…
Signal n
Selected signals
MAIN:
Latching M-trip cmd1
[ 021 040 ]
>S1 1
0
>R1
1
0: No
1: Yes
MAIN: MAIN:
Man. M-trip signal 2 M-trip signal 2
[ 039 084 ] [ 039 102 ]
MAIN:
Min.dur. M-trip cmd2
MAIN:
Fct.asg. M-trip cmd2 [ 021 035 ]
[ 021 008 ]
Signal 1 1 t MAIN:
M-trip command 2
Signal 2 [ 039 058 ]
m out of n
Signal 3
…
Signal n
Selected signals
MAIN:
Latching M-trip cmd2
[ 021 041 ]
>S1 1
0
>R1
1
0: No
1: Yes
MAIN:
Latch. trip c. reset
[ 040 139 ] 48Z9321A
MAIN:
Trip cmd. blocked
[ 021 013 ]
MAIN:
Block. R-trip USER
[ 022 091 ]
MAIN:
0 R-trip blocked
[ 039 051 ]
1
0: No
1: Yes
MAIN:
Block. R-trip EXT
[ 038 051 ]
MAIN: MAIN:
Man. R-trip signal 1 R-trip signal 1
[ 039 082 ] [ 039 103 ]
MAIN:
Min.dur. R-trip cmd1
MAIN:
Fct.asg. R-trip cmd1 [ 021 036 ]
[ 021 025 ]
Signal 1 1 t MAIN:
R-trip command 1
Signal 2 [ 039 012 ]
m out of n
Signal 3
…
Signal n
Selected signals
MAIN:
Latching R-trip cmd1
[ 021 042 ]
>S1 1
0
>R1
1
0: No
1: Yes
MAIN: MAIN:
Man. R-trip signal 2 R-trip signal 2
[ 039 085 ] [ 039 104 ]
MAIN:
Min.dur. R-trip cmd2
MAIN:
Fct.asg. R-trip cmd2 [ 021 037 ]
[ 021 026 ]
Signal 1 1 t MAIN:
R-trip command 2
Signal 2 [ 039 059 ]
m out of n
Signal 3
…
Signal n
Selected signals
MAIN:
Latching R-trip cmd2
[ 021 043 ]
>S1 1
0
>R1
1
0: No
1: Yes
MAIN:
Latch. trip c. reset
[ 040 139 ] 48Z9322A
MAIN:
Trip cmd. blocked
[ 021 013 ]
MAIN:
Block. M-trip USER
[ 022 092 ]
MAIN:
0 B-trip blocked
[ 039 052 ]
1
0: No
1: Yes
MAIN:
Block. B-trip EXT
[ 038 052 ]
MAIN: MAIN:
Man. B-trip signal 1 B-trip signal 1
[ 039 083 ] [ 039 105 ]
MAIN:
Min.dur. B-trip cmd1
MAIN:
Fct.asg. B-trip cmd1 [ 021 038 ]
[ 021 027 ]
Signal 1 1 t MAIN:
B-trip command 1
Signal 2 [ 039 013 ]
m out of n
Signal 3
…
Signal n
Selected signals
MAIN:
Latching B-trip cmd1
[ 021 0404 ]
>S1 1
0
>R1
1
0: No
1: Yes
MAIN: MAIN:
Man. B-trip signal 2 B-trip signal 2
[ 039 098 ] [ 039 106 ]
MAIN:
Min.dur. B-trip cmd2
MAIN:
Fct.asg. B-trip cmd2 [ 021 039 ]
[ 021 028 ]
Signal 1 1 t MAIN:
B-trip command 2
Signal 2 [ 039 060 ]
m out of n
Signal 3
…
Signal n
Selected signals
MAIN:
Latching B-trip cmd2
[ 021 045 ]
>S1 1
0
>R1
1
0: No
1: Yes
MAIN:
Latch. trip c. reset
[ 040 139 ] 48Z9323A
The trip command, set to latch mode, will remain active until reset by parameter
(MAIN : R set.l atch .tri p USE R) or reset through an appropriately configured
binary signal input (MAI N: R es et latch.trip E XT).
MAIN:
Trip cmd.block. USER
[ 021 012 ]
1 MAIN:
Trip cmd. blocked
0: No [ 021 013 ]
1: Yes
MAIN:
Block. trip cmd. EXT
[ 036 045 ]
47Z01AWA
MAIN: ≥1
M-trip signal 1 MAIN:
Gen. trip signal
[ 039 101 ]
[ 036 251 ]
MAIN:
R-trip signal 1
[ 039 103 ]
MAIN:
B-trip signal 1
[ 039 105 ]
MAIN:
M-trip signal 2
[ 039 102 ]
MAIN:
R-trip signal 2
[ 039 104 ]
MAIN:
B-trip signal 2
[ 039 106 ] 48Z9326A
Trip signals from the Main-Trip command, the Re-Trip command and the Back-
Trip command are collectively issued as the "Gen Trip Signal" (general trip).
DIST: MAIN:
Trip signal >+ No. final trip cmds.
≥1 & ≥1 &
[ 036 009 ] >R [ 004 005 ]
BUOC: MAIN:
Trip signal I> Final trip
1 100ms
[ 036 014 ] [ 038 103 ]
DELTA:
Trip signal
[ 038 056 ]
DTOC:
Trip signal tI>
[ 041 020 ]
DTOC:
Trip signal tI>>
[ 040 011 ]
DTOC:
Trip signal tI>H
[ 040 076 ]
DTOCA:
Trip signal tI>
[ 130 071 ]
DTOCA:
Trip signal tI>>
[ 130 072 ]
DTOCB:
Trip signal tI>
[ 130 091 ]
DTOCB:
Trip signal tI>>
[ 130 092 ]
IDMT:
Trip signal tIref>
[ 040 084 ]
IDMTA:
Trip signal tIref>
[ 130 113 ]
IDMTB:
Trip signal tIref>
[ 130 133 ]
ARC: ≥1
Cycle running
[ 037 000 ] >S
11 &
1
>R
MAIN:
Close command
[ 037 009 ]
ARC:
Close command
MAIN:
Trip cmd. blocked
[ 021 013 ]
MAIN: >+ MAIN:
M-trip command 1 No. M-trip cmds. 1
[ 039 011 ] >R
[ 009 005 ]
MAIN: >+ MAIN:
R-trip command 1 No. R-trip cmds. 1
>R
[ 039 012 ] [ 009 006 ]
>+ MAIN:
MAIN: No. B-trip cmds. 1
B-trip command 1 >R
[ 009 007 ]
[ 039 013 ]
>+ MAIN:
MAIN: No. M-trip cmds. 2
M-trip command 2 >R
[ 009 027 ]
[ 039 058 ] >+ MAIN:
No. R-trip cmds. 2
MAIN: >R
R-trip command 2 [ 009 028 ]
[ 039 059 ] >+ MAIN:
No. B-trip cmds. 2
MAIN: >R
B-trip command 2 [ 009 029 ]
[ 039 006 ] MAIN:
Reset c. cl/tr.cUSER
[ 003 007 ]
1 ≥1
The number of trip commands is counted (individually for each of the trip
commands).
The counters can be reset either individually or as a group.
MAIN:
En.man.trip cmd. EXT
[ 039 053 ]
MAIN:
En.man.trip cmd.USER MAIN:
[ 003 064 ] Rel.t. enab. man.cmd
[ 003 088 ]
MAIN:
0 Man. trip cmd enabl.
[ 039 080 ]
1 1 t
0: No
1: Yes
MAIN:
Man.M-trip cmd USER
[ 003 065 ]
MAIN:
0 1 100ms Man. M-trip signal 1
[ 039 081 ]
1
0: don't execute
1: execute
MAIN:
Man. M-trip cmd1 EXT
[ 039 054 ]
MAIN:
Man.M-trip cmd2 USER
[ 003 082 ]
MAIN:
0 1 100ms Man. M-trip signal 2
[ 039 084 ]
1
0: don't execute
1: execute
MAIN:
Man. M-trip cmd2 EXT
[ 039 056 ]
MAIN:
Man.R-trip cmd USER
[ 003 066 ]
MAIN:
0 1 100ms Man. R-trip signal 1
[ 039 082 ]
1
0: don't execute
1: execute
MAIN:
Man. R-trip cmd1 EXT
[ 039 055 ]
MAIN:
Man.R-trip cmd2 USER
[ 003 083 ]
MAIN:
0 1 100ms Man. R-trip signal 2
[ 039 085 ]
1
0: don't execute
1: execute
MAIN:
Man. R-trip cmd2 EXT
[ 039 057 ]
MAIN:
Man.B-trip cmd USER
[ 003 067 ]
MAIN:
0 1 100ms Man. B-trip signal 1
[ 039 083 ]
1
0: don't execute
1: execute
MAIN:
Man. B-trip cmd1 EXT
[ 039 107 ]
MAIN:
Man.B-trip cmd2 USER
[ 003 087 ]
MAIN:
0 1 100ms Man. B-trip signal 2
[ 039 098 ]
1
0: don't execute
1: execute
MAIN:
Man. B-trip cmd2 EXT
[ 039 108 ] 48Z9324A
The manual trip command may be issued using setting parameters or via an
appropriately configured binary signal input. It will be issued only if the manual
trip command was enabled. The manual trip command issued using a setting
parameter is enabled only for a set time period. The manual trip command
issued from an appropriately configured binary signal input is enabled only for as
long as the associated enabling input is set.
MAIN:
Inp.assign. tripping
[ 221 010 ]
Signal 1
Signal 2
Signal 3
Signal n
Selected signal
MAIN:
M-trip command 1
[ 039 011 ]
MAIN: MAIN:
R-trip command 1 Prot.trip>CB tripped
[ 039 012 ] [ 221 012 ]
MAIN:
B-trip command 1 0
[ 039 013 ]
1
MAIN:
M-trip command 2 2
[ 039 058 ]
3
MAIN:
R-trip command 2
[ 039 059 ] 0 3
MAIN:
B-trip command 2 0: Without function
[ 039 060 ] 1: Gen. trip command 1
2: Gen. trip command 2
3: Gen.trip command 1/2
MAIN:
Oper. mode CB Trip
[ 221 080 ]
1 2
1: With command
2: W/o command
MAIN:
Inp. asg. CB trip
[ 221 013 ]
DEV01:
Switch. device open
[ 210 036 ]
DEV10:
Switch. device open
[ 211 236 ] MAIN:
CB trip internal
Selected signal [ 221 006 ]
MAIN:
Inp.asg.CB tr.en.ext
[ 221 050 ]
MAIN:
CB tripped
[ 221 016 ]
Selected signal
MAIN:
Inp.asg. CB trip ext
[ 221 024 ]
Selected signal
ARC:
Sig.interr. CB trip
[ 036 040 ]
48Z9327A
The signal “CB Trip” depends on the mode of operation and is based on different
events:
Mode of operation: “With command” (MA IN: Ope r. mode C B Tr ip, 221 080):
In this mode of operation, in addition the MA IN: C B trip int ernal (221 006)
signal is formed.
The signal MA IN : C B tr ip i ntern al is issued if the following conditions are met
simultaneously:
● The binary signal input configured for “tripping” is set to a logic value of
“1” or the selected trip command from the P438 is present.
● At the binary signal input configured as “CB trip” a logic value of “1” is
present.
Mode of operation: “W/o command” (MAI N: Oper. mode CB Trip, 221 080):
The MAI N: C B tri pped signal will only be issued, if the circuit breaker is
tripping without any command issued by the P438. Commands via
communication interfaces, local control panel or binary inputs are treated in the
same manner. This mode of operation disables the MAI N: CB trip int e rnal
signal.
The CB trip signal of an external device can also be signaled. For this task, one
input needs to be configured for “MA IN: In p.as g.C B t r.en .e xt“, a further
input for “MAI N: I np.asg. CB trip e xt“.
COMM1: MAIN:
Communication error ≥1 Communication error
[ 221 019 ]
304 422
DVICE:
Module A not fitted
307 140
19Z5070A
MAIN:
Date
[ 003 090 ]
MAIN:
Time of day
[ 003 091 ]
MAIN:
Time switching
[ 003 095 ]
MAIN:
Min-pulse clock EXT
[ 060 060 ]
MAIN:
Time tag
306 021
MAIN:
Time switching
Q6Z0152B
Fig. 3-91: Date/time setting and clock synchronization with minute pulses presented at a binary signal input.
Switching from standard to daylight saving time or back requires correct time
setting frames from the time synchronization master (according the applied
communication protocol).
The data stored in the operating data memory, the monitoring signal memory
and the event memories are date- and time-tagged. For correct tagging, the date
and time need to be set in the P438.
The time of different devices may be synchronized by a pulse given to an
appropriately configured binary signal input. The P438 evaluates the rising edge.
This will set the clock to the nearest full minute, rounding either up or down. If
several start/end signals occur (bouncing of a relay contact), only the last edge is
evaluated.
MAIN:
General reset USER
[ 003 002 ]
1 1: execute
0: don't execute
1: execute
MAIN:
Reset indicat. USER
[ 021 010 ]
0: don't execute
1: execute MAIN:
≥1 Reset LED
306 020
MAIN:
Reset indicat. EXT
[ 065 001 ]
12Z6115A
Fig. 3-92: General reset, LED reset and measured event data reset from the local control panel.
LOC: OP_RC:
Reset key active & ≥1 Reset record. EXT
310 024 [ 005 213 ]
LOC:
Fct. reset key
[ 005 251 ]
m out of n
OP_RC:
Reset record. EXT
[005 213]
MAIN: MAIN:
Group reset 1 USER Group reset 2 USER
[ * ] [ * ]
0 0
1 ≥1 & 1 ≥1 &
0: don't execute 0: don't execute
m out of n m out of n
OP_RC: OP_RC:
Reset record. EXT Reset record. EXT
[005 213] [005 213]
12Z61RMB
Fig. 3-93: “CLEAR” key on the local control panel and, as an example, group resetting of the operating data
recording (e.g. as an example for the reset signal O P _ R C : R e s e t r e c o r d . E X T.
A complete list of all resetting parameters that can be used in the way shown in
Fig. 3-93, (p. 3-131) can be obtained from the separately available
DataModelExplorer: Look up the setting parameter MA IN: Fct. ass ign. reset 1
in the file P438‑661_en_Addresses.pdf, and there follow the link to the referenced
config. table.
MAIN:
Chann.assign.COMM1/2
[ 003 169 ]
1: COMM1->chann.1,(2-2)
2: COMM1->chann.2,(2-1)
"Logical"
Communic. interface
COMM1
Comm. interface
Channel 1
"Logical"
Communic. interface
COMM2
Comm. interface
Channel 2
45Z5171A
MAIN:
Test mode USER
[ 003 012 ]
0
MAIN:
1 ≥1 Test mode
[ 037 071 ]
0: No
1: Yes
MAIN:
Test mode EXT
[ 037 070 ]
D5Z50EBB
If tests are run on the P438, the user is advised to activate the test mode so that
all incoming signals via the serial interfaces will be identified accordingly.
PSS:
Control via USER
[ 003 100 ]
0: No
1: Yes PSS:
Control via user
PSS: [ 036 102 ]
Control via user EXT
[ 036 101 ] PSS:
Param.subs.sel. USER
INP: [ 003 060 ]
Fct. assignm. U xxx
[ 152 xxx ]
1
2
U x1
3
U x2
4
U x3
1: Parameter subset 1
U xx
2: Parameter subset 2
Address 065 002
PSS:
1 4 Actual param. subset
[ 003 062 ]
PSS:
PS 1 active
[ 036 090 ]
PSS:
Activate PS 1 EXT PSS:
[ 065 002 ] PS 2 active
[ 036 091 ]
PSS: PSS:
Activate PS 2 EXT PS 3 active
[ 065 003 ] [ 036 092 ]
PSS: PSS:
Activate PS 3 EXT PS 4 active
[ 065 004 ] [ 036 093 ]
PSS:
Activate PS 4 EXT
[ 065 005 ]
1 4
PSS:
Keep time
[ 003 063 ]
1
PSS:
0 4 Ext.sel.param.subset
[ 003 061 ]
PSS:
PS 1 activated ext.
[ 036 094 ]
PSS:
PS 2 activated ext.
[ 036 095 ]
PSS:
PS 3 activated ext.
[ 036 096 ]
PSS:
PS 4 activated ext.
[ 036 097 ]
D5Z5002A
3.15.3 Signals
SFMON:
Fct. assign. warning
[ 021 030 ]
Signal 1
m out of n
Signal 2
Signal 3
Signal n
SFMON:
Selected monit. sig. ≥1 Warning (LED)
[ 036 070 ]
SFMON:
SFMON: Warning (relay)
Hardware fault [ 036 100 ]
304 950
Q6Z0154B
The monitoring signals are also signaled via the output relay configured
SFMON : Warnin g ( rel ay). The output relay operates as long as an internal
fault is detected.
OP_RC:
Operat. data record.
[ 003 024 ]
Operating memory
MAIN:
Oper.-relev. signal
306 024
MAIN: OP_RC:
General reset USER No. oper. data sig.
[ 003 002 ] +
[ 100 002 ]
1: execute R
MAIN:
General reset EXT
[ 005 255 ]
OP_RC:
Reset record. EXT
[ 005 213 ]
OP_RC:
Reset record. USER
[ 100 001 ]
0: don't execute
1: execute
12Z61CMA
Fig. 3-98: Operating data recording and counter for signals relevant to system operation.
MT_RC:
Mon. signal record.
[ 003 001 ]
MAIN:
Time tag
306 021
SFMON:
Hardware fault
304 950
MT_RC:
Reset record. USER
[ 003 008 ]
CT30 SFMON:
≥1 Overflow MT_RC
[ 090 012 ]
0
MT_RC:
1 ≥1 No. monit. signals
[ 004 019 ]
0: don't execute
1: execute
MT_RC:
Reset record. EXT
[ 005 240 ]
12Z6155A
Fig. 3-99: Monitoring signal recording and the monitoring signal counter.
OL_RC: OL_DA:
Record. in progress + Overload duration
[ 035 003 ] [ 004 102 ]
R
MAIN: ≥1
General reset USER
[ 003 002 ]
1: execute
MAIN:
General reset EXT
[ 005 255 ]
OL_RC:
Reset record. EXT
[ 005 241 ]
OL_RC:
Reset record. USER
[ 100 003 ]
1: execute
50Z0137A
OL_RC:
Record. in progress C
[ 035 003 ]
THERM: OL_DA:
Status therm.replica Status THERM replica
[ 004 016 ] [ 004 147 ]
R
THERM: OL_DA:
I Load current THERM
305 202 [ 004 058 ]
R
THERM: OL_DA:
Object temperature Object temp. THERM
[ 004 137 ] [ 004 035 ]
R
THERM: OL_DA:
Coolant temperature Coolant temp. THERM
[ 004 149 ] [ 004 036 ]
R
THERM: OL_DA:
Pre-trip time left Pre-trip t.leftTHERM
[ 004 139 ] [ 004 148 ]
R
THERM: OL_DA:
Temp. offset replica Offset THERM replica
[ 004 109 ] [ 004 154 ]
R
MAIN:
General reset USER
[ 003 002 ]
1: execute ≥1
MAIN:
General reset EXT
[ 005 255 ]
OL_RC:
Reset record. EXT
[ 005 241 ]
OL_RC:
Reset record. USER
[ 100 003 ]
1: execute
12Z6238A
Fig. 3-101: Measured overload values from the thermal overload protection.
OL_RC:
Record. in progress
[ 035 003 ]
THERM:
Starting k*Iref>
[ 041 108 ] +
R OL_RC:
No. overload
[ 004 101 ]
MAIN:
General reset USER
[ 003 002 ]
1: execute
MAIN:
General reset EXT
[ 005 255 ]
OL_RC:
Reset record. EXT
[ 005 241 ]
OL_RC:
Reset record. USER
[ 100 003 ]
1: execute
52Z01C3A
OL_RC: C
Record. in progress
[ 035 003 ]
Signal 3 1
Signal n 1 OL_RC:
Overload recording 1
[ * ]
OL_RC:
n Overload recording 1
Measured value 1
1 033 020
Measured value 2
2 033 021
Measured value 3
3 033 022
Measured value N
4 033 023
MAIN:
Time tag
306 021 5 033 024
MAIN:
1 ≥1
General reset USER 0: don't execute
[ 003 002 ]
1: execute
1: execute
MAIN:
General reset EXT
[ 005 255 ]
OL_RC:
Reset record. EXT
[ 005 241 ]
12Z6117A
Running time:
(004 021) FT_DA: Ru nni ng time
Fault duration:
(008 010) FT_ DA: Faul t duration
The fault data with suffix A and B are available only when the Autotransformer feed
mode or Single feed with sum I mode is selected.
! G ! FT_DA:
MAIN: Running time
General starting +
[ 004 021 ]
[ 036 000 ]
R
≥1
MAIN: ≥1
General reset USER
[ 003 002 ]
1: execute ≥1
MAIN:
General reset EXT
[ 005 255 ]
MAIN:
Reset LED
306 020
49Z64DMA
The time difference between the begining of the fault and the fault data
acquisition time is also displayed.
FT_RC:
Record. in progress
[ 035 000 ]
DTOC:
Starting I>H
[ 035 022 ]
DIST:
Starting
[ 036 135 ]
BUOC:
Starting I>
[ 036 013 ]
BUOC:
Starting I>>
[ 036 115 ]
DTOC:
Starting I>
[ 035 020 ]
DTOC:
Starting I>>
[ 035 021 ]
DTOCA:
Starting I>
[ 130 069 ]
DTOCA:
Starting I>>
[ 130 070 ]
DTOCB:
Starting I>
[ 130 089 ]
DTOCB:
Starting I>>
[ 130 090 ]
IDMT:
Starting Iref>
[ 040 080 ]
IDMTA:
Starting Iref>
[ 130 110 ]
IDMTB:
Starting Iref>
[ 130 130 ]
DFRST:
Starting
[ 041 204 ]
V<>:
Starting V>
[ 041 030 ]
V<>:
Starting V>>
[ 041 096 ]
V<>:
Starting V< FT_DA:
Fault determ.
[ 041 037 ]
[ 004 198 ]
V<>:
Starting V<<
[ 041 099 ] C1
THERM:
Trip signal C2
[ 039 020 ]
C3
C4
C5
FT_RC:
I> triggered C6
[ 035 013 ] C7
C8
C9
FT_RC:
Trigger
[ 037 076 ]
|I̲max|
I̲ 1 4 6 9
,
|I̲d,max| 5
I̲plaus/I̲dfrst
1 9 FT_DA:
Save measured values
305 052
FT_DA:
MAIN: Run time to meas.
General reset USER [ 004 199 ]
[ 003 002 ]
↗ 1: execute
MAIN:
General reset EXT
[ 005 255 ]
MAIN:
Reset LED 48Z9329A
The setting at FT_DA : Outp. flt .l ocat. P Sx determines the conditions under
which calculation and output of the fault location occur. The following settings
are possible:
● Always: Calculation and output of the fault location always occurs if the
other measured fault data are also being determined.
● Only aft. trip Z1/t1: Calculation and output of the fault location occurs if the
P438 decides in favor of a trip in impedance zone 1 with standard reach
(non-extended zone).
● Only aft.tr. Z1ze/t1: Calculation and output of the fault location occurs if the
P438 decides in favor of a trip in impedance zone 1 with standard and
extended reach.
FT_DA:
Save measured values
305 052
FT_DA:
Outp. flt.locat. PSx
[ * ]
1: Always
DIST:
Trip signal Z1/t1
[ 039 016 ]
DIST:
Trip signal Z1,ze
[ 035 074 ] Parameter FT_DA:
Outp. flt.locat. PSx
set 1 010 032
set 2 010 033
set 3 010 034
set 4 010 035
48Z9328A
FT_RC:
Record. in progress
[ 035 000 ]
FT_DA:
Save measured values
C
035 052
BUOC:
Starting I> C1
[ 036 013 ]
BUOC:
Starting I>>
[ 036 115 ]
MAIN:
Inom C.T. prim.
[ 010 001 ] C
MAIN:
Vnom V.T. prim.
[ 010 002 ]
I̲ FT_DA:
Fault current p.u.
[ 004 025 ]
R
V̲
FT_DA:
Fault voltage p.u.
[ 004 026 ]
R
FT_DA:
Fault loop angle
[ 004 024 ]
R
FT_DA:
Fault reactance,sec.
[ 004 028 ]
R
FT_DA:
Fault impedance,sec.
[ 004 023 ]
R
FT_DA:
Fault reactance,prim
[ 004 029 ]
R
FT_DA:
Fault impedance,prim
[ 004 176 ]
R
MAIN:
General reset USER
[ 003 002 ]
↗1: execute
MAIN:
General reset EXT
[ 005 255 ]
MAIN:
Reset LED 48Z9330A
Fig. 3-107: Acquisition of the fault currents and voltage, fault angles, fault reactance and impedance. (The fault
data with suffix A and B are available only when the Autotransformer feed mode or Single feed with sum I mode is
selected. )
FT_RC:
Record. in progress
[ 035 000 ]
FT_DA:
Save measured values C C
305 052
FT_DA:
I̲plaus/I̲dfrst Iplaus/Idfrst. p.u.
[ 004 177 ]
R
MAIN:
General reset USER
[ 003 002 ]
↗ 1: execute
MAIN:
General reset EXT
[ 005 255 ]
MAIN:
Reset LED
48Z9331A
FT_DA:
Forw.length A-1 PSx
[ * ]
FT_DA:
XLforw.,sec A-1 PSx
[ * ]
FT_DA:
Forw.length B-1 PSx
[ * ]
FT_DA:
XLforw.,sec B-1 PSx
[ * ]
FT_DA:
Backw.length A-1 PSx
[ * ]
FT_DA:
XLbackw.,secA-1 PSx
[ * ]
FT_DA:
Backw.length B-1 PSx
[ * ]
FT_DA:
XLbackw.,secB-1 PSx
[ * ]
FT_DA:
Outp. fault location C
305 051
FT_DA: FT_DA:
Fault reactance,sec. Fault location
[ 004 028 ]
R [ 004 022 ]
FT_DA:
Fault react.,sec A FT_DA:
[ 235 205 ] Fault location A
R [ 235 201 ]
FT_DA:
Fault react.,sec B FT_DA:
[ 236 205 ] Fault location B
R [ 236 201 ]
FT_DA:
Fault locat. percent
[ 004 027 ]
R
FT_DA:
Fault loc. percent A
[ 235 204 ]
R
MAIN: FT_DA:
General reset USER Fault loc. percent B
[ 003 002 ] [ 236 204 ]
1: execute R
MAIN:
General reset EXT
[ 005 255 ] Parameter FT_DA: FT_DA: FT_DA: FT_DA:
Forw.length A-1 PSx XLforw.,sec A-1 PSx Forw.length B-1 PSx XLforw.,sec B-1 PSx
MAIN:
Reset LED set 1 010 005 010 012 011 145 011 185
306 020
set 2 010 006 010 013 011 146 011 186
set 3 010 007 010 014 011 147 011 187
set 4 010 008 010 015 011 148 011 188
Fig. 3-109: Acquisition of fault location. (The diagram displays data points with only one line section used. The P438
can consider a maximum of 10 line sections in its acquisition of the fault location.)
The settings with suffix B are available only when the Autotransformer feed or
Single feed with sum I mode is selected.
FT_RC:
Fct. assig. trigger
[ 003 085 ]
Signal 1
Signal 2
m out of n
Signal 3
Signal n
Selected signals
FT_RC: FT_RC:
Trigger
Trigger EXT ≥1
[ 036 089 ] [ 037 076 ]
FT_RC:
Trigger USER
[ 003 041 ]
0 0 1 min FT_RC:
≥1 Record. in progress
1 [ 035 000 ]
0: don't execute
1: execute
MAIN:
General starting
[ 036 000 ]
MAIN:
Gen. trip signal
[ 036 251 ]
FT_RC:
MAIN: + No. of faults
General reset USER [ 004 020 ]
[ 003 002 ]
≥1 R
1: execute
MAIN:
General reset EXT FT_RC:
[ 005 255 ] + No. system disturb.
[ 004 010 ]
FT_RC:
Reset record. USER R
[ 003 006 ]
1: execute
FT_RC:
Reset record. EXT
[ 005 243 ]
FT_RC:
& System disturb. runn
≥1 [ 035 004 ]
ARC:
Cycle running
[ 037 000 ]
& S1 1
R1
48Z9333A
FT_RC: C
Record. in progress
[ 035 000 ]
FT_RC:
Signal 1 + CT200 Fault mem. overflow
1 ≥1 [ 035 001 ]
Signal 2 1 R
Signal 3 1
Signal n 1 FT_RC:
Fault recording n
[ * ]
1
FT_RC:
Pre-fault time
[ 003 078 ]
FT_RC:
Post-fault time
[ 003 079 ]
FT_RC:
n Fault recording n
Fault memory n
1 003 000
2 033 001
3 033 002
MAIN:
General reset USER &
[ 003 002 ]
1: execute R
≥1
MAIN:
General reset EXT
[ 005 255 ]
FT_RC:
Reset record. EXT
[ 005 243 ]
FT_RC:
Reset record. USER
[ 003 006 ]
1 1: execute
0: don't execute
1: execute
12Z6161B
Protection signals, including the signals during the settable pre-fault and post-
fault times, are logged in chronological order with reference to the specific fault.
A total of eight faults, each involving a maximum of 200 start or end signals, can
be stored in the non-volatile fault memories. After eight faults have been
recorded, the oldest fault recording will be overwritten, unless memories have
been cleared in the interim. If more than 199 start or end signals have occurred
during a single fault, then FT_RC : F aul t me m . overflow will be entered as the
last signal. If the time and date are changed during the pre-fault time, the signal
F T_RC : F aulty t ime tag is generated.
In addition to the fault signals, the measured fault data will also be entered in the
fault memory.
The fault recordings can be read from the local control panel or through the PC or
communication interfaces.
FT_RC:
Record. in progress C
[ 035 000 ]
FT_RC:
Max. recording time
[ 003 075 ]
FT_RC:
Pre-fault time
[ 003 078 ]
FT_RC:
Post-fault time
[ 003 079 ]
MAIN:
General reset EXT
[ 005 255 ]
FT_RC:
Reset record. EXT
[ 005 243 ] 48Z9334A
DIST:
General enable USER
[ 031 073 ]
& DIST:
1 Enabled
[ 036 104 ]
0: No
1: Yes
DIST:
Enable PSx
[ * ]
DIST:
Parameter Enable PSx
Fig. 3-113: Enable/disable the distance protection and fault detection blocking.
DIST: DIST:
Enabled Blocking
[ 036 104 ] 303 667
MAIN:
M.c.b. trip V EXT
[ 004 061 ]
MCMON:
Meas. circ. V faulty
[ 038 023 ]
DIST:
Wrong setting DIST
[ 041 085 ]
48Z5028A
DIST: DIST:
Z1 enabled Zone 1 not ready
[ 039 066 ] [ 038 034 ]
DIST:
Blocking
303 667
DIST:
Z1, forward PSx
[ * ]
blocked
DIST:
Z1, backward PSx
[ * ]
blocked
DIST:
t1 PSx
[ * ]
blocked
DIST:
Blocking t1 EXT
[ 039 163 ]
DIST:
Z1' enabled
[ 039 067 ]
DIST:
Z1', forward PSx
[ * ]
blocked
DIST:
Z1', backward PSx
[ * ]
blocked
DIST: DIST:
Z2 enabled Zone 2 not ready
[ 039 068 ] [ 038 035 ]
DIST:
Z2' enabled
[ 039 069 ]
DIST:
Blocking
303 667
DIST:
Z2, forward PSx
[ * ]
blocked
DIST:
Z2, backward PSx
[ * ]
blocked
DIST:
Z2', forward PSx
[ * ]
blocked
DIST:
Z2', backward PSx
[ * ]
blocked
DIST:
t2S PSx
[ * ]
blocked
DIST:
Blocking t2S EXT
[ 039 164 ]
DIST:
t2L PSx
[ * ]
blocked
DIST:
Blocking t2L EXT
[ 039 165 ]
DIST:
Op.mode dx/dt, Z2PSx
[ * ]
0: Without
DIST:
Delta I(di/dt),Z2PSx
[ * ]
blocked
DIST:
Delta V(dv/dt),Z2PSx
[ * ]
blocked
DIST:
D.phi(dphi/dt),Z2PSx
[ * ]
blocked
Parameter DIST: DIST: DIST: DIST: DIST:
Z2, forward PSx Z2, backward PSx Z2', forward PSx Z2', backward PSx t2S PSx
set 1 076 094 076 101 076 097 076 104 012 029
set 2 077 094 077 101 077 097 077 104 012 079
set 3 078 094 078 101 078 097 078 104 013 029
set 4 079 094 079 101 079 097 079 104 013 079
set 1 012 190 072 107 072 198 072 139 072 206
set 2 012 191 073 107 073 198 073 139 073 206
set 3 012 192 074 107 074 198 074 139 074 206
set 4 012 193 075 107 075 198 075 139 075 206 48Z5410C
DIST: DIST:
Zone 1 not ready Not ready
[ 038 034 ] [ 041 086 ]
DIST:
Zone 2 not ready
[ 038 035 ]
DIST:
Zone 3 not ready
[ 038 036 ]
DIST:
Zone 4 not ready
[ 038 064 ]
DIST:
WPC not ready
[ 039 156 ]
48Z6332A
The distance protection function issues the DIST: Not ready signal if all
impedance zones and the wrong phase coupling protection are blocked.
DIST:
I> PSx
[ * ]
DIST:
Enabled
[ 036 104 ]
I̲ DIST:
I> starting
[ 039 001 ]
Parameter DIST:
I> PSx
Fig. 3-118: Base point release for impedance and direction determination.
● VF > 0.1 Vn
The direction decision is issued on the basis of the fault current and the
measured fault voltage.
● VF < 0.1 Vn
Voltage memory enabled: The direction decision is issued on the basis of
the fault current and the voltage stored in the voltage memory.
Voltage memory not enabled: The direction decision is issued on the basis
of the fault current and the measured fault voltage down to a minimum
value of 1 V. If the fault voltage drops to a value of less than approximately
1 V, an accurate direction determination is no longer possible. In this case,
a forward decision is issued - independent of the actual fault direction.
DIST:
Voltage mem. enabled
303 549
DIST:
I> starting
[ 039 001 ]
<1V DIST:
Forw. w/o measurem.
[ 038 044 ]
DIST:
Direct. using Vmeas
[ 038 045 ]
DIST:
Direct. using memory
[ 038 047 ]
1
2
V̲ φF 1
DIST:
I̲ Direction forward
φS 2 -45° < φN < 135°
V̲(memory) C 303 669
MAIN:
DIST: Fault forward
Starting
[ 036 018 ]
[ 036 135 ]
MAIN:
Fault backward
[ 036 019 ]
48Z6335A
DIST:
Characteristic PSx
[ * ]
1 1: Circle
2 2: Polygon
1: Circle
2: Polygon
Parameter DIST:
Characteristic PSx
set 1 012 040
set 2 073 097
set 3 074 097
set 4 075 097
D5Z5019A
DIST:
Control via USER
[ 022 008 ]
0
1 DIST:
Control via user
0: No [ 038 172 ]
1: Yes
DIST:
Control via user EXT
[ 038 171 ]
DIST:
Select Z1/Z1' USER
[ 022 011 ] DIST:
& Z1 enabled
1 [ 039 066 ]
2 &
1: Z1
2: Z1'
& DIST:
DIST: Z1' enabled
Z1' enabled EXT [ 039 067 ]
&
[ 038 067 ]
DIST:
Z1' ext. enabled
[ 038 078 ]
DIST:
Select Z2/Z2' USER
[ 022 021 ] DIST:
& Z2 enabled
1 [ 039 068 ]
2 &
1: Z2
2: Z2'
& DIST:
DIST: Z2' enabled
Z2' enabled EXT [ 039 069 ]
&
[ 038 069 ]
DIST:
Z2' ext. enabled
[ 038 079 ]
DIST:
Select Z3/Z3' USER
[ 022 038 ] DIST:
& Z3 enabled
1 [ 036 124 ]
2 &
1: Z3
2: Z3'
&
DIST:
DIST: Z3' enabled
Z3' enabled EXT
[ 036 123 ] & [ 036 125 ]
DIST:
Z3' ext. enabled
[ 038 147 ]
DIST:
Select Z4/Z4' USER
[ 022 194 ]
& DIST:
Z4 enabled
1 [ 036 154 ]
2 &
1: Z4
2: Z4'
&
DIST:
DIST: Z4' enabled
Z4' enabled EXT
& [ 036 156 ]
[ 036 129 ]
DIST:
Z4' ext. enabled
[ 038 090 ]
48Z6334A
Forward direction
Zn,fwd
Backward direction αLn
ßn
αn
Rgn,rev
R
Rgn,fwd
γn
Zn,rev
48Z5453A
Fig. 3-122: P438 impedance and direction characteristic for the 'Circle' setting
For zone 1, the impedance reach can be extended by the zone extension factor
kze. Valid impedance and reactance values are extended for each of the set
directions.
Z1,kze=kze·Z1 or Z1,kze'=kze·Z1'
Rg1,kze=kze·Rg1 or Rg1,kze'=kze·Rg1'
Impedance reach is extended using the following parameters:
● Zone extension factor for high-speed reclosure (DIST: kze, HSR PSx)
Impedance reach is extended by the set factor if the internal auto-reclose
function permits a zone extension during high-speed reclosures
(AR C : Z one ex t. f. H SR P Sx). Depending on the setting, zone extension
may remain active until the reclosure command (ARC: Zone ext.dur . RC
PS x) is terminated.
● Zone extension factor for time-delay reclosure (DIST: k ze , TDR PSx)
Impedance reach is extended by the set factor if the internal auto-reclose
function permits a zone extension during time-delayed reclosures
(AR C: Z one ex t. f. TDR PSx). Depending on the setting, zone extension
may remain active until the reclosure command (ARC: Zone ext.d ur. RC
PS x) is terminated.
● Zone extension factor for external extension or tripping by the switch on to
a fault protection (DI ST: kze Ext/SOTF/PSIG PSx)
Impedance reach is extended by the set factor if switch on to fault
protection (SOTF: Z1 e xte nded) has been activated or an external signal
(D IST: Zon e e xte n si on EXT) is set.
& DIST:
Zone extension TDR
[ 038 022 ]
DIST:
& Zone extension SOTF
[ 036 134 ]
DIST:
& Z1 extended extern.
[ 036 140 ]
48Z9352A
Fig. 3-123: Setting impedance zone 1 and distance measurement, operating mode set to 'Circle'.
DIST:
Enabled
[ 036 104 ] c
& Parameter DIST: DIST: DIST:
DIST: Characteristic PSx Z2, forward PSx Rg2, forward PSx
I> starting
DIST:
set 1 012 040 076 094 076 139
[ 039 001 ] c Z2, forward PSx
MCMON: [ * ] set 2 073 097 077 094 077 139
Meas. circ. V faulty set 3 074 097 078 094 078 139
DIST:
[ 038 023 ] set 4 075 097 079 094 079 139
c Rg2, forward PSx
DIST: [ * ]
Characteristic PSx Parameter DIST: DIST: DIST:
[ * ] Z2', forward PSx Rg2', forward PSx Z2, backward PSx
1: Circle DIST:
c Z2', forward PSx set 1 076 097 076 142 076 101
[ * ] set 2 077 097 077 142 077 101
DIST: set 3 078 097 078 142 078 101
c Rg2', forward PSx set 4 079 097 079 142 079 101
DIST: & [ * ]
Direction forward Parameter DIST: DIST: DIST:
303 669 DIST: Rg2, backward PSx Z2', backward PSx Rg2', backward PSx
DIST: c Z2, backward PSx
Z2 enabled & [ * ] set 1 076 145 076 104 076 148
[ 039 068 ] set 2 077 145 077 104 077 148
DIST:
DIST: set 3 078 145
c Rg2, backward PSx 078 104 078 148
Z2' enabled set 4 079 145 079 104 079 148
& [ * ]
[ 039 069 ]
DIST: DIST: Parameter DIST: DIST: DIST:
Direction backward c Z2', backward PSx Alpha 2 PSx Beta 2 PSx Gamma 2 PSx
303 670
& [ * ] set 1 076 091 072 209 076 248
DIST: set 2 077 091 073 209 077 248
c Rg2', backward PSx set 3 078 091 074 209 078 248
[ * ] set 4 079 091 075 209 079 248
DIST:
Z parameter avail. DIST:
[ 023 051 ] c Alpha 2 PSx
[ * ]
&
0 DIST:
c Beta 2 PSx
1 [ * ]
DIST:
0: No DIST: Starting
c Gamma 2 PSx
1: Yes [ 036 135 ]
[ * ]
& DIST:
Z2 starting
[ 039 005 ]
DIST:
& Z2' starting
[ 039 006 ]
MAIN: SFMON:
ΣI(xfn)/I(fn) Wrong set. DIST Rg2
310 053
[ 098 048 ]
I̲ SFMON:
Wrong set. DIST Rg2'
[ 098 049 ]
V̲
MAIN:
Inrush stabil. trigg
306 014 DIST:
MAIN: Wrong setting DIST
Harm. blk. trigg [ 041 085 ]
460 649
SFMON:
Wrong set. DIST X/R
[ 097 023 ]
48Z9353A
Fig. 3-124: Setting impedance zones 2 to 4 (showing the example of zone 2) and distance measurement, operating
mode set to 'Circle'.
Forward direction
(Xn,fwd) Zn,fwd
ßn
αLn
αn
Rgn,rev
Rn,fwd
R
Rn,rev
Rgn,fwd
γn
Zn,rev (Xn,rev)
48Z9351A
Fig. 3-125: P438 impedance and direction characteristic for the 'Polygon’ setting.
For zone 1, the impedance reach can be extended by the zone extension factor
kze. Valid impedance and reactance values are extended for each of the set
directions.
Z1,kze=kze·Z1 or Z1,kze'=kze·Z1'
(X1,kze=kze·X1 or X1,kze'=kze·X1')
R1,kze=kze·R1 or R1,kze'=kze·R1'
Rg1,kze=kze·Rg1 or Rg1,kze'=kze·Rg1'
Impedance reach is extended using the following parameters:
DIST: &
Enabled Parameter DIST: DIST: DIST:
[ 036 104 ] Characteristic PSx Z1, forward PSx X1, forward PSx
c
DIST: set 1 012 040 076 093 021 239
I> starting 073 097 021 245
DIST: set 2 077 093
[ 039 001 ]
MCMON: c Z1, forward PSx set 3 074 097 078 093 021 246
[ * ] set 4 075 097 079 093 021 247
Meas. circ. V faulty
[ 038 023 ] DIST: Parameter DIST: DIST: DIST:
DIST: c X1, forward PSx R1, forw. (poly) PSx Rg1, forward PSx Z1', forward PSx
Characteristic PSx [ * ]
[ * ] set 1 076 115 076 138 076 096
2: Polygon DIST: set 2 077 115 077 138 077 096
& & c R1, forw. (poly) PSx set 3 078 115 078 138 078 096
[ * ] set 4 079 115 079 138 079 096
DIST:
Z1 enabled DIST:
c Rg1, forward PSx Parameter DIST: DIST: DIST:
[ 039 066 ] & X1', forward PSx R1', forw.(poly) PSx Rg1', forward PSx
[ * ]
set 1 021 243 076 118 076 141
DIST: set 2 077 141
021 251 077 118
DIST: & & c Z1', forward PSx
[ * ] set 3 021 252 078 118 078 141
Direction forward set 4 021 253 079 118 079 141
303 669 DIST:
DIST: & c X1', forward PSx Parameter DIST: DIST: DIST:
Z1' enabled [ * ] Z1, backward PSx X1, backward PSx R1, backw.(poly) PSx
[ 039 067 ] DIST: set 1 076 100 021 242 076 121
R1', forw.(poly) PSx
c set 2 077 100 021 248 077 121
[ * ]
set 3 078 100 021 249 078 121
DIST: set 4 079 100 021 250 079 121
c Rg1', forward PSx
[ * ] Parameter DIST: DIST: DIST:
Rg1, backward PSx Z1', backward PSx X1', backward PSx
DIST:
c Z1, backward PSx set 1 076 144 076 103 021 244
& &
[ * ] set 2 077 144 077 103 021 254
DIST:
Direction backward DIST: set 3 078 144 078 103 021 255
303 670 c X1, backward PSx set 4 079 144 079 103 022 198
& [ * ]
DIST: Parameter DIST: DIST: DIST:
X parameter avail. DIST: R1', backw.(poly)PSx Rg1', backward PSx Alpha_L 1 (poly) PSx
c R1, backw.(poly) PSx
set 1 076 124 076 147 012 013
[ 023 051 ] & & [ * ]
set 2 077 124 077 147 012 063
DIST: set 3 078 124 078 147 013 034
0 c Rg1, backward PSx
& set 4 079 124 079 147 013 063
1 [ * ]
DIST: Parameter DIST: DIST: DIST:
0: No Alpha 1 PSx Beta 1 PSx Gamma 1 PSx
c Z1', backward PSx
1: Yes [ * ] set 1 076 090 072 208 076 247
set 2 077 090 073 208 077 247
DIST:
DIST: c X1', backward PSx set 3 078 090 074 208 078 247
X parameter avail. [ * ] set 4 079 090 075 208 079 247
Fig. 3-126: Setting impedance zone 1 and distance measurement, operating mode set to ‘Polygon’.
DIST: &
Enabled
[ 036 104 ] c
DIST:
I> starting Parameter DIST: DIST: DIST:
DIST: Characteristic PSx Z2, forward PSx X2, forward PSx
[ 039 001 ] c Z2, forward PSx
MCMON: [ * ]
set 1 012 040 076 094 022 199
Meas. circ. V faulty set 2 073 097 077 094 023 004
[ 038 023 ] DIST: set 3 074 097 078 094 023 005
DIST: c X2, forward PSx set 4 075 097 079 094 023 006
Characteristic PSx [ * ]
[ * ]
2: Polygon DIST: Parameter DIST: DIST: DIST:
c R2, forw. (poly) PSx R2, forw. (poly) PSx Rg2, forward PSx Z2', forward PSx
& &
[ * ] set 1 076 116 076 139 076 097
DIST: set 2 077 116 077 139 077 097
Z2 enabled DIST:
c Rg2, forward PSx set 3 078 116 078 139 078 097
[ 039 068 ] & set 4 079 116 079 139 079 097
[ * ]
DIST: Parameter DIST: DIST: DIST:
DIST: & & c Z2', forward PSx X2', forward PSx R2', forw.(poly) PSx Rg2', forward PSx
Direction forward [ * ]
set 1 023 002 076 119 076 142
303 669 DIST: set 2 023 044 077 119 077 142
DIST: & c X2', forward PSx
set 3 023 045 078 119 078 142
Z2' enabled [ * ] set 4 023 046 079 119 079 142
[ 039 069 ] DIST:
Rg2', forward PSx Parameter
c DIST: DIST: DIST:
[ * ] Z2, backward PSx X2, backward PSx R2, backw.(poly) PSx
1: Yes [ * ]
Parameter DIST: DIST: DIST:
DIST: Alpha 2 PSx Beta 2 PSx Gamma 2 PSx
DIST: c X2', backward PSx
set 1 076 091 072 209 076 248
X parameter avail. [ * ]
set 2 077 091 073 209 077 248
[ 023 050 ] DIST: set 3 078 091 074 209 078 248
cR2', backw.(poly)PSx set 4 079 091 075 209 079 248
0 [ * ]
DIST:
1 & c Rg2', backward PSx
[ * ]
0: No
DIST:
1: Yes c Alpha_L 2 (poly) PSx
[ * ]
DIST: DIST:
X parameter used
c Alpha 2 PSx
[ 023 052 ] [ * ]
& DIST:
0 c Beta 2 PSx
& [ * ]
1
DIST: DIST:
0: No c Gamma 2 PSx Starting
[ * ] [ 036 135 ]
1: Yes
& DIST:
Z2 starting
[ 039 005 ]
DIST:
& Z2' starting
[ 039 006 ]
SFMON:
Wrong set. DIST Rg2
[ 098 048 ]
SFMON:
MAIN: Wrong set. DIST Rg2'
ΣI(xfn)/I(fn) [ 098 049 ]
310 053
DIST:
I̲ Wrong setting DIST
V̲ [ 041 085 ]
SFMON:
MAIN: Wrong set. DIST X/R
Inrush stabil. trigg
306 014
[ 097 023 ]
MAIN:
Harm. blk. trigg
460 649
48Z9355A
Fig. 3-127: Setting impedance zones 2 to 4 (showing the example of zone 2) and distance measurement, operating
mode set to ‘Polygon’.
DIST:
DIST: t1 PSx
Blocking t1 EXT
[ * ]
[ 039 163 ]
DIST: t 0 DIST:
Z1 (Z1,ze) starting t1 elapsed
[ 039 003 ] [ 036 026 ]
DIST: Z1 Decision DIST:
Z1'(Z1',ze) starting Trip signal Z1/t1
[ 039 004 ] [ 039 016 ]
DIST:
& t1,zeExt/SOF/PSG PSx
DIST: [ * ]
Z1 extended extern.
[ 036 140 ] t 0
DIST: DIST:
Zone extension SOTF t1,ze elapsed
[ 036 134 ] [ 035 079 ]
Parameter DIST: DIST: Z1 Decision DIST:
t1 PSx t1,zeExt/SOF/PSG PSx Trip signal Z1,ze
set 1 012 028 012 198 [ 035 074 ]
set 2 012 078 012 199
set 3 013 028 012 200
set 4 013 078 012 201 48Z6336B
Fig. 3-128: Setting the time-delay period for distance protection, zone 1.
DIST:
DIST: t2S PSx
Blocking t2S EXT
[ * ]
[ 039 164 ]
t 0 DIST:
DIST: & t2S elapsed
t2S enable
[ 039 009 ]
303 671
Z2 Decision DIST:
DIST: Trip signal Z2/t2S
DIST: t2L PSx [ 039 017 ]
Blocking t2L EXT
[ * ]
[ 039 165 ]
t 0 DIST:
& t2L elapsed
DIST:
Z2 starting [ 039 010 ]
[ 039 005 ] Z2 Decision DIST:
Trip signal Z2/t2L
DIST:
Z2' starting [ 039 018 ]
[ 039 006 ]
DIST:
DIST: t3S PSx
Blocking t3S EXT
[ * ]
[ 039 166 ]
t 0 DIST:
DIST: & t3S elapsed
t3S enable
[ 039 143 ]
303 672
Z3 Decision DIST:
DIST: Trip signal Z3/t3S
DIST: t3L PSx [ 039 145 ]
Blocking t3L EXT
[ * ]
[ 039 167 ]
t 0 DIST:
& t3L elapsed
DIST:
Z3 starting [ 039 144 ]
[ 039 140 ] Z3 Decision DIST:
Trip signal Z3/t3L
DIST:
Z3' starting [ 039 146 ]
[ 039 141 ]
DIST:
DIST: t4S PSx
Blocking t4S EXT
[ * ]
[ 039 002 ]
t 0 DIST:
DIST: & t4S elapsed
t4S Enable
[ 039 047 ]
310 056
Z4 Decision DIST:
DIST: Trip signal Z4/t4S
DIST: t4L PSx [ 039 040 ]
Blocking t4L EXT
[ * ]
[ 039 019 ]
t 0 DIST:
& t4L elapsed
DIST:
Z4 starting [ 039 048 ]
[ 039 042 ] Z4 Decision DIST:
Trip signal Z4/t4L
DIST:
Z4' starting [ 039 041 ]
[ 039 043 ]
Parameter DIST: DIST: DIST: DIST: DIST: DIST:
t2S PSx t2L PSx t3S PSx t3L PSx t4S PSx t4L PSx
set 1 012 029 012 190 012 030 012 194 080 011 080 012
set 2 012 079 012 191 012 080 012 195 081 011 081 012
set 3 013 029 012 192 013 030 012 196 082 011 082 012
set 4 013 079 012 193 013 080 012 197 083 011 083 012 48Z6337B
Fig. 3-129: Setting the time-delay period for distance protection, zones 2, 3 and 4.
Using zone 2 as an example, the following figure shows conditions to be met for
the train start-up detection stages to be ready. This applys accordingly to zones
3 and 4.
DIST:
Delta I(di/dt),Z2PSx
[ * ]
DIST:
blocked > 1 du/dt not ready, Z2
[ 039 031 ]
DIST:
Delta V(dv/dt),Z2PSx
[ * ]
blocked > 1 DIST:
dphi/dt not ready,Z2
[ 039 032 ]
DIST:
D.phi(dphi/dt),Z2PSx
[ * ]
blocked
Fig. 3-130: Readiness of the train start-up detection stages, zones 2 to 4 (showing the example of zone 2).
DIST:
Op.mode dx/dt, Z2PSx
[ * ] DIST:
t2S enable
0 303 671
1 &
2
&
0: Without
1: OR
2: AND
DIST:
di/dt not ready, Z2 &
[ 039 030 ]
DIST:
du/dt not ready, Z2
[ 039 031 ]
DIST:
dphi/dt not ready,Z2
[ 039 032 ]
DIST:
C Delta I(di/dt),Z2PSx
[ * ]
I̲ COMP S 1 DIST:
di/dt starting, Z2
R [ 039 007 ]
1 t &
DIST:
C Delta V(dv/dt),Z2PSx
[ * ]
COMP S 1 DIST:
V̲ dv/dt starting, Z2
[ 039 008 ]
R
1 t &
DIST:
C D.phi(dphi/dt),Z2PSx
[ * ]
COMP S 1 DIST:
dphi/dt starting, Z2
R [ 039 142 ]
1 t &
DIST:
Starting
[ 036 135 ] Parameter DIST: DIST: DIST: DIST:
Op.mode dx/dt, Z2PSx Delta I(di/dt),Z2PSx Delta V(dv/dt),Z2PSx D.phi(dphi/dt),Z2PSx
set 1 072 107 072 198 072 139 072 206
set 2 073 107 073 198 073 139 073 206
set 3 074 107 074 198 074 139 074 206
set 4 075 107 075 198 075 139 075 206 48Z6338A
Fig. 3-131: Train start-up detection stages, zones 2 to 4 (showing the example of zone 2).
three-phase system (see figure below). Each catenary section has its own supply.
In order to achieve an optimum load balance in the three-phase system, the
catenary sections are usually supplied from different phases of the three-phase
system.
The catenary sections can be connected to allow compensation for the failure of
one of the section supplies. This coupling is permissible only when the supply of
a section has actually failed. If two out-of-phase supplies are inadvertently
connected via the catenary, a short circuit results. The fault (short-circuit)
impedance is located on the line perpendicular to the resultant impedance of
catenary and transformers.
A
B
C
Transformer a Transformer b
Catenary
Rail
Section a Section b
X
X transf. a
Angle between
feed Z̲res
voltages
Z̲ Section a + b
Z̲
X transf. b
48Z5445A
The settings for the characteristics of the wrong phase coupling protection
function have to be selected such that the fault (short-circuit) impedance is
located safely within the tripping area.
Tripping zone
WPC Zmax
WPC Zmin
WPC ß
WPC γ
R
48Z5448A
DIST:
WPC zone available
[ 022 002 ]
1
0: No
1: Yes
DIST:
WPC enabled PSx
[ * ]
& DIST:
1 WPC enabled
0: No [ 039 155 ]
1: Yes
DIST:
Enabled
& DIST:
[ 036 104 ] WPC not ready
[ 039 156 ]
> 1
DIST:
Blocking
303 667
DIST:
WPC t PSx Parameter DIST: DIST:
[ * ] WPC enabled PSx WPC t PSx
blocked
set 1 076 130 076 137
DIST: set 2 077 130 077 137
Blocking tWPC EXT
set 3 078 130 078 137
[ 039 168 ]
set 4 079 130 079 137 48Z5447A
Fig. 3-134: Disabling, enabling and readiness of the wrong phase coupling protection.
MAIN:
Protection active
306 001
DIST: DIST:
WPC enabled WPC Zmin PSx
[ 039 155 ] [ * ]
DIST: DIST:
WPC not ready WPC Zmax PSx
[ 039 156 ] [ * ]
DIST:
I> starting DIST:
WPC beta PSx
[ 039 001 ]
DIST: [ * ]
WPC V< PSx
DIST:
[ * ] WPC alpha PSx
[ * ]
V̲
I̲
& DIST:
WPC starting
MAIN: [ 039 158 ]
Inrush stabil. trigg
306 014
DIST:
MAIN: WPC t PSx
Harm. blk. trigg
460 649
[ * ]
DIST:
Trip signal WPC
[ 039 159 ]
DIST: DIST:
Z1 (Z1,ze) starting Starting
[ 039 003 ] [ 036 135 ]
DIST:
Z2 starting
[ 039 005 ]
DIST:
Z3 starting
[ 039 140 ]
DIST:
Z4 starting
[ 039 042 ]
DIST:
Z1'(Z1',ze) starting
[ 039 004 ]
DIST:
Z2' starting
[ 039 006 ]
DIST:
Z3' starting
[ 039 141 ]
DIST:
Z4' starting
[ 039 043 ]
DIST:
WPC starting
[ 039 158 ] 48Z6339A
DIST: DIST:
Trip signal Z1/t1 Trip signal
[ 039 016 ] [ 036 009 ]
THERM:
3 PL active
[ 039 074 ]
DIST:
Trip signal Z2/t2S
[ 039 017 ]
DIST:
Trip signal Z2/t2L
[ 039 018 ]
DIST:
Trip signal Z3/t3S
[ 039 145 ]
DIST:
Trip signal Z3/t3L
[ 039 146 ]
DIST:
Trip signal Z4/t4S
[ 039 040 ]
DIST:
Trip signal Z4/t4L
[ 039 041 ]
DIST:
Trip signal WPC
[ 039 159 ] 48Z6340A
DELTA:
General enable USER
[ 022 179 ]
0
DELTA:
1 Enabled
[ 038 054 ]
0: No
1: Yes
DELTA:
Enable PSx
[ * ]
Parameter DELTA:
Enable PSx
0
set 1 062 030
1 set 2 063 030
set 3 064 030
0: No set 4 065 030
1: Yes
48Z6351A
High impedance protection is not ready when one of the following conditions are
met:
● High impedance protection has not been enabled.
● High impedance protection is blocked by an appropriately configured binary
input function.
● High impedance protection is blocked by a Close command, issued to the
circuit breaker, dependent on the duration of the blocking time period
tBlock.
● Time-delay tDelta is set to Blocked.
● Measuring-circuit monitoring has detected a fault in the voltage-measuring
circuit AND the function is to be blocked according to the setting.
DELTA:
Enabled DELTA:
Not ready
[ 038 054 ]
[ 038 055 ]
DELTA:
Block. tDelta EXT
[ 038 053 ]
DELTA:
tDelta PSx
[ * ]
blocked
DELTA:
Blocking by CB-close DELTA:
tBlock PSx
[ 022 191 ]
[ * ]
0
1 & 1 t
0: No
1: Yes
MAIN:
Close command
[ 037 009 ]
MAIN:
Manual close EXT
[ 036 047 ]
DELTA:
Mode w/o Voltg. PSx
[ * ]
1
2 &
1: Delta I only
2: blocked
MCMON:
Meas. circ. V faulty
[ 038 023 ]
MAIN:
M.c.b. trip V EXT
[ 004 061 ]
DELTA:
Vmin triggered
310 051
DELTA:
Delta Phi available
[ 022 189 ]
1: Yes
DELTA:
X superv. available
[ 022 188 ]
Parameter DELTA: DELTA: DELTA:
1: Yes tDelta PSx tBlock PSx Mode w/o Voltg. PSx
set 1 062 039 062 045 062 036
set 2 063 039 063 045 063 036
set 3 064 039 064 045 064 036
set 4 065 039 065 045 065 036 48Z6352C
DELTA: c
Enabled
[ 038 054 ] DELTA:
Imin PSx
[ * ]
I̲ DELTA:
Imin starting
[ 038 059 ]
Triggering of high impedance protection will be fairly unlikely when the minimum
value is set in only one direction. In such a case high impedance protection will
operate only in the direction "opposite" to the set reactance limit.
DELTA: c
Enabled
[ 038 054 ] DELTA:
X superv. available
[ 022 188 ]
0: No
1: Yes
&
DELTA:
Imin starting
[ 038 059 ]
MCMON: c
Meas. circ. V faulty
[ 038 023 ] DELTA:
MAIN: X, forward PSx
M.c.b. trip V EXT [ * ]
[ 004 061 ] DELTA:
DELTA: X, backward PSx
Vmin triggered [ * ]
310 051
V̲ DELTA:
X-release
I̲ [ 038 065 ]
Parameter DELTA: DELTA:
X, forward PSx X, backward PSx
3.23.4 Checking for Changes of the Phase Angle (Sudden Angle Change
Detection)
The P438 will check for sudden angle changes to distinguish between load
variations and high impedance faults. A the phase angle change may be used as
a criterion for a fault.
The P438 checks whether the current value exceeds the minimum current value
set at DEL TA: I mi n P Sx and that no fault is apparent in the voltage-measuring
circuit. If this is the case, the P438 will monitor the phase angle. Should the
phase angle value change by more than the set DELTA: Delta Phi PSx value
during a set sampling interval then the DELTA: De lta Phi starting signal is
issued.
DELTA: c
Enabled
[ 038 054 ] DELTA:
Delta Phi available
[ 022 189 ]
0: No
1: Yes
&
DELTA:
Imin starting
[ 038 059 ]
MCMON:
Meas. circ. V faulty
[ 038 023 ]
MAIN: c
M.c.b. trip V EXT
[ 004 061 ] DELTA:
DELTA: Delta Phi PSx
Vmin triggered [ * ]
310 051
V̲ DELTA:
Delta Phi starting
I̲ [ 038 063 ]
Parameter DELTA:
Delta Phi PSx
DELTA: C
Enabled &
[ 038 054 ] DELTA:
I(3fn)/I(fn) PSx
DELTA:
Imin starting [ * ]
[ 038 059 ]
MAIN: DELTA:
I(3fn)/I(fn) I(3fn) starting
310 054 [ 038 076 ]
c
DELTA:
Superv. I(5fn)avail.
[ 022 193 ]
&
0
1 C
0: No DELTA:
1: Yes I(5fn)/I(fn) PSx
[ * ]
MAIN: DELTA:
I(5fn)/I(fn) I(5fn) starting
310 055
[ 038 077 ]
DELTA:
& Delta I blocked
[ 038 068 ]
DELTA:
kSt,I(xfn)/I(fn) PSx DELTA:
[ * ]
Parameter DELTA: DELTA: DELTA: Delta I extended
blocked I(3fn)/I(fn) PSx I(5fn)/I(fn) PSx kSt,I(xfn)/I(fn) PSx
[ 038 066 ]
set 1 062 040 062 042 062 041
set 2 063 040 063 042 063 041
set 3 064 040 064 042 064 041
set 4 065 040 065 042 065 041 48Z6355C
When tDelta is set to Blocked then resetting of the recorded start is carried out
after the 100 ms pulse duration.
DELTA:
Enabled
&
[ 038 054 ]
DELTA:
Not ready
[ 038 055 ]
DELTA:
Imin starting
[ 038 059 ]
DELTA:
Delta I blocked
[ 038 068 ]
MAIN:
Inrush stabil. trigg
306 014
DELTA:
Mode w/o Voltg. PSx
[ * ]
1
2 &
1: Delta I only
2: blocked
MCMON:
Meas. circ. V faulty
[ 038 023 ]
MAIN:
M.c.b. trip V EXT
[ 004 061 ]
DELTA:
Vmin triggered
310 051
DELTA:
X-release
[ 038 065 ]
C
DELTA:
X superv. available
[ 022 188 ] DELTA:
Delta I PSx
1: Yes
[ * ]
DELTA:
Delta Phi starting DELTA:
[ 038 063 ] kSt,I(xfn)/I(fn) PSx
DELTA: [ * ]
Delta Phi available
[ 022 189 ] fnom
1: Yes
S 1 DELTA:
I̲ & Delta I starting
R [ 038 060 ]
DELTA:
Delta I extended
[ 038 066 ]
t 0
DELTA: C
Block. tDelta EXT
[ 038 053 ] DELTA:
tDelta PSx
[ * ]
t 0 DELTA:
Trip signal
[ 038 056 ]
MCMON:
General enable USER
[ 014 001 ]
0
MCMON:
1 Enabled
[ 040 094 ]
0: No
1: Yes
MCMON:
Enable PSx
[ * ]
Parameter MCMON:
Enable PSx
0
set 1 014 200
1 set 2 014 201
set 3 014 202
0: No set 4 014 203
1: Yes
48Z5053A
Operating zone
Blocking zone
48Z5066A
The P438 signals a fault in the current-measuring circuit if the differential current
is in the operate region shown.
MCMON:
I-monit. enabled PSx
[ * ]
1 c
0: No MAIN:
Inom C.T. prim.
1: Yes [ 010 001 ]
MAIN:
Iplaus/Idfrst,CTprim
[ 010 016 ]
SFMON:
Match.fct.I MCMONinv
COMP [ 098 059 ]
MCMON:
Mismatch scal.Iplaus
[ 040 129 ]
MCMON:
Scaling fact. Iplaus
[ 004 255 ]
MCMON:
Enabled
[ 040 094 ]
DIST:
Starting
[ 036 135 ]
& c
MCMON:
Id>, I-monit. PSx
[ * ]
MCMON:
I̲ <Inom C.T.prim. m1, I-monit. PSx
[ * ]
I̲plaus/I̲dfrst <Iplaus,nom C.T.prim.
MCMON:
Meas. circ. I faulty
[ 040 087 ]
● Undervoltage monitoring
● Fuse failure monitoring
If triggered both sub-functions automatically block all functions using the
measured voltage.
If undervoltage monitoring is enabled and it is not blocked by a binary signal
input and there is no general starting, the P438 monitors the voltage for it to fall
below the threshold set at MCMON: V <, V -moni t. PSx. In this case the
current must exceed the threshold set at MC MON: I> enable V <,F F PSx.
Once the set time delay has elapsed, the MCMON: Undervoltage signal is
issued.
MAIN:
General starting
[ 036 000 ]
MCMON:
Enabled
[ 040 094 ]
MCMON:
Blocking V< EXT
[ 038 033 ]
MCMON:
V-monit. enabled PSx
[ * ]
0
& c
1
MCMON: MCMON:
0: No V<, V-monit. PSx tV<, V-monit. PSx
1: Yes [ * ] [ * ]
& S1 1 MCMON:
Undervoltage
t 0 R1 [ 038 038 ]
V̲
MCMON:
V< triggered
MCMON:
I> enable V<,FF PSx 304 652
[ * ]
I̲
● A voltage drop has to exceed the set threshold MCMON: D elta V , FF PSx
within 2 power frequency cycles.
● As the voltage drops, the change in current must not exceed the set
threshold MC MON: De l ta I, FF P Sx.
● After the voltage drop, the voltage must be lower than the set threshold
MC MO N : V <, FF P Sx.
● After the voltage drop, the current is higher than the set threshold
MC MO N : I> e nabl e V <,F F PSx.
The MC MON: FF, V tri gge r ed signal will be reset if the following conditions
are satisfied:
● The voltage is higher than the set threshold: MC MO N: V >, FF PSx
● A minimum hold-time period of 125 ms has elapsed.
MAIN:
General starting
[ 036 000 ]
MCMON:
Enabled
[ 040 094 ]
MCMON:
Blocking FF EXT
[ 038 037 ]
MCMON:
FF enabled PSx
[ * ]
MCMON:
0: No Delta V, FF PSx
1: Yes [ * ]
MCMON:
FF, V triggered
V̲ - ΔV/Δt [ 035 081 ]
MCMON:
Delta I, FF PSx
[ * ]
I̲ + ΔI/Δt
MCMON:
V<, FF PSx
[ * ]
MCMON:
I> enable V<,FF PSx
[ * ]
MCMON:
V>, FF PSx
[ * ]
MCMON:
FF,Vref enabled USER
MCMON:
[ 014 013 ] Oper. delay FF, Vref
[ 014 012 ]
0
t 0
1 & MCMON:
FF, Vref triggered
0: No [ 038 100 ]
1: Yes
MCMON:
Blocking FF,Vref EXT
[ 018 099 ]
V̲B/V̲ref
|V̲ref|-|V̲Meas|≥
ASC: 0.1 Vnom
Vmeas
MAIN:
CB closed B EXT
[ 031 030 ] 48Z9336A
The P438 includes “Fuse Failure” monitoring of the reference voltage function,
which is required by the “Automatic Synchronism Check” (ASC).
Fuse Failure monitoring of the reference voltage is only possible if the ASC
function has been configured. This is specifically applied when no auxiliary
contact is available on the voltage transformer m.c.b. If fuse failure monitoring is
not desired it can be disabled by setting parameters.
Fuse Failure monitoring must be able to discriminate between a short circuit in
the network being monitored and a reference voltage missing because of a short
circuit or an open circuit in the secondary circuits of the reference voltage.
A short circuit or an open circuit in the secondary circuits of the reference
voltage is present when the following conditions are met:
● The circuit breaker is closed.
● The voltage difference between the line side and the busbar must exceed
0.1⋅Vnom.
MCMON:
V< triggered
304 652
MCMON:
FF, V triggered
[ 035 081 ] 48Z5060A
MAIN: MCMON:
M.c.b. trip V EXT Meas. circ. V faulty
[ 004 061 ] [ 038 023 ]
MCMON:
Undervoltage
[ 038 038 ]
MCMON:
FF, V triggered
[ 035 081 ] 48Z5470A
BUOC:
General enable USER
[ 014 011 ]
0
BUOC:
1 Enabled
[ 040 093 ]
0: No
1: Yes
BUOC:
Enable PSx
[ * ]
Parameter BUOC:
Enable PSx
0
set 1 072 118
1 set 2 073 118
set 3 074 118
0: No set 4 075 118
1: Yes
48Z5055A
BUOC protection is ready when it is activated, enabled and at least one stage is
unblocked. If this is the case then BUOC protection will become effective
automatically as soon as the distance protection function is not ready. The latter
can occur, for example, if there is a malfunction in the voltage-measuring circuit
or if the distance protection function is not enabled in the active setting group.
Provided that the backup time-delayed overcurrent protection has started, it
remains active at least until the end of this starting, even when the condition for
its activation disappear (for example M.c.b. trip).
BUOC: BUOC:
Enabled Not ready
[ 040 093 ] [ 040 030 ]
BUOC:
Blocking tI> EXT
[ 038 127 ]
BUOC:
Blocking tI>> EXT
BUOC:
[ 038 128 ] Active
DIST: [ 037 021 ]
Not ready
[ 041 086 ]
48Z5056A
BUOC:
Active
[ 037 021 ]
BUOC:
Blocking tI> EXT
[ 038 127 ]
BUOC: BUOC:
I> PSx tI> PSx
MAIN: [ * ] [ * ]
Protection active
306 001
BUOC:
Trip signal I>
I̲ [ 036 014 ]
BUOC:
Starting I>
[ 036 013 ]
BUOC: BUOC:
Blocking tI>> EXT Gen. trip signal
[ 038 128 ] [ 036 122 ]
BUOC: BUOC:
I>> PSx tI>> PSx
[ * ] [ * ]
BUOC:
Trip signal I>>
[ 036 116 ]
BUOC:
Starting I>>
[ 036 115 ]
MAIN:
Inrush stabil. trigg
306 014
MAIN:
Harm. blk. trigg
460 649
SOTF:
General enable USER
[ 011 068 ]
0
SOTF:
1 Enabled
[ 040 069 ]
0: No
1: Yes
SOTF:
Enable PSx
[ * ]
Parameter SOTF:
Enable PSx
0
set 1 011 120
1 set 2 011 121
set 3 011 122
0: No set 4 011 123
1: Yes
48Z5065A
Fig. 3-156: Disabling and enabling switch on to fault (short circuit) protection.
SOTF:
Enabled &
[ 040 069 ]
SOTF: & SOTF:
Par. ARC running EXT Z1 extended
[ 039 063 ] [ 035 076 ]
SOTF:
Blocking EXT
[ 036 098 ] SOTF:
MAIN: Man. close timer PSx
Protection active
306 001 [ * ]
SOTF:
Operating mode PSx
[ * ]
Parameter SOTF:
4
Operating mode PSx
5
set 1 011 061
set 2 011 114 4: Trip with starting
set 3 011 115
set 4 011 116
5: Trip with overreach
48Z5321A
PSIG1:
General enable USER
[ 015 004 ]
1
0: No
1: Yes
PSIG1:
Enable PSx
[ * ]
PSIG1:
0 Enabled
[ 015 008 ]
1
0: No
1: Yes
INP:
Fct. assignm. U xxx
[ xxx xxx ]
U x1
U x2
U x3
U xx
PSIG1:
Ext./user enabled
[ 037 023 ]
PSIG1:
Enable EXT
[ 037 025 ]
PSIG1:
Enable USER
[ 003 132 ]
0: don't execute
1: execute
PSIG1:
Disable EXT
[ 037 026 ]
PSIG1:
Disable USER
[ 003 131 ]
0: don't execute
PSIG1:
Ready
1: execute
[ 037 027 ]
MAIN:
Protection active
306 001
PSIG1:
Blocking EXT
[ 036 049 ]
Parameter PSIG1:
Enable PSx
48Z9375A
PSIG1:
PSIG1: Release t. send PSx
Reset send timer
[ * ]
[ 019 148 ]
PSIG1:
Fct. Send Signal PSx 0 t
PSIG1:
[ * ] Send
[ 012 243 ]
Signal 1
m out of n
Signal 2
Signal n
Selected signals
& PSIG1:
Send signal
[ 036 035 ]
PSIG1:
Send Echo
[ 019 228 ]
To secure that an active receive signal get processed only when it was send by
the sender, a plausibility check with the PSIG1: Telecom. fault y is required
(see Fig. 3-161, (p. 3-208)).
The received signal PSIG1: Re ce ive s ignal can be used for the following
different functionalities:
PSIG1:
Fct. Trip Signal PSx
[ * ]
Signal 1
PSIG1:
Start signal
Signal 2
m out of n [ 019 183 ]
Signal n PSIG1:
Trip delay time PSx
[ * ]
Selected signals
& t 0 PSIG1:
& Trip signal
[ 038 007 ]
PSIG1:
Transient blocking
[ 037 255 ]
[ xxx xxx ]
U x1
U x2
U x3
U xx
PSIG1:
Address 036 048 & & Receive signal
[ 006 036 ]
X Blocking signal 1
Blocking signal n
[ XXX XXX ]
Selected signals
1
& PSIG1:
Z1 Extended
2
[ 019 233 ]
X
PSIG1:
Address 036 048 & Operating mode PSx
PSIG1: [ * ]
Receive EXT
[ 036 048 ]
0
PSIG1:
Telecom. faulty 4
[ 036 060 ]
5
0: Without
4: Release scheme
5: Blocking scheme
3: Zone extension
PSIG1:
Fct.Telecom.chnl.PSx
[ * ]
PSIG1:
Telec.faulty EXT PSIG1:
Telecom.flt.enl. PSx
[ 004 064 ]
[ * ]
COMM3:
Communications fault
1 out of n 0 t PSIG1:
[ 120 043 ] Telecom. faulty
[ 036 060 ]
COMM3:
Comm. link failure
[ 120 044 ]
GOOSE:
Input 01 faulty
[ 111 100 ]
.
.
.
GOOSE:
Input 128 faulty
[ 111 227 ]
Selected signal
* PSIG1: PSIG1:
Parameter
Fct.Telecom.chnl.PSx Telecom.flt.enl. PSx
set 1 019 149 019 175
set 2 019 160 019 176
set 3 019 161 019 177
set 4 019 162 019 178
48Z9378A
PSIG1:
Operating mode PSx
[ * ]
0 0: Without
4 4: Release scheme
5 5: Blocking scheme
3 3: Zone extension
0: Without
4: Release scheme Parameter PSIG1:
Operating mode PSx
5: Blocking scheme
3: Zone extension set 1 015 000
set 2 024 000
set 3 024 070
set 4 025 020
48Z9377A
All operating modes transmit binary signals. These are exchanged either via the
integrated InterMiCOM interface, via IEC 61850 GOOSE over Ethernet, or via
binary inputs / output relays (directly using pilot wires in case of short distances,
otherwise using external signal transmission devices).
IED1 IED2
> <
Z2 Z1
105% t
48Z9388A
PSIG1: &
Telecom. faulty
[ 036 060 ]
DIST:
t1 PSx
[ * ]
t 0
DIST: DIST:
Z1 (Z1,ze) starting Trip signal Z1/t1
[ 039 003 ] [ 039 016 ]
Parameter DIST:
t1 PSx
set 1 012 028
set 2 012 078
set 3 013 028
set 4 013 078
48Z9385A
Fig. 3-164: Release procedure example 1. (Note: The dotted line block is an example of send logic configured by
P S I G 1 : F c t . T r i p S i g n a l P S x.)
IED1 IED2
> <
Release Procedure 2
t
85%
Z1 Z2
Z2 Z1
85%
t
48Z9389A
PSIG1:
Telecom. faulty
[ 036 060 ]
DIST:
t2S PSx
[ * ]
t 0
DIST: OR / &
di/dt starting, Z2 DIST:
AND Trip signal Z2/t2S
[ 039 007 ]
[ 039 017 ]
DIST:
dv/dt starting, Z2
[ 039 008 ]
DIST:
dphi/dt starting, Z2
[ 039 142 ]
Fig. 3-166: Release procedure example 2. (Note: The dotted line block is an example of send logic configured by
P S I G 1 : F c t . T r i p S i g n a l P S x.)
105%
IED1 IED2
> <
Blocking Procedure
t 105%
Z1 Z2
Z2 Z1
105% t
48Z9390A
PSIG1:
Block signal
[ 019 226 ]
& PSIG1:
Trip signal
[ 038 007 ]
PSIG1: &
Telecom. faulty
[ 036 060 ]
DIST:
t1 PSx
[ * ]
t 0
DIST: DIST:
Z1 (Z1,ze) starting Trip signal Z1/t1
[ 039 003 ] [ 039 016 ]
DIST:
t2S PSx
[ * ]
t 0
DIST: DIST:
Z2 starting Trip signal Z2/t2S
[ 039 005 ] [ 039 017 ]
Fig. 3-168: IED2 receive logic - blocking procedure example. (Note: The dotted line block is an example of send
logic configured by P S I G 1 : F c t . T r i p S i g n a l P S x.)
Nfw
A B
Nfw
49Z8953A
Fig. 3-169: Reaches with zone extension. Dashed line: measuring range extended by zone extension factor.
DIST: PSIG1:
Backwards fault Reset send timer
& ≥1
[ 036 139 ] [ 019 148 ]
PSIG1:
Operating mode PSx
[*]
5 &
0: Without
3: Zone extension
4: Release scheme
DIST: 5: Blocking scheme
Forward fault
[ 036 138 ]
PSIG1:
t Trans.block. PSx
[ * ]
t+1s PSIG1:
S1 1 Transient blocking
DIST: [ 037 255 ]
Starting R1
[ 036 135 ]
* PSIG1: PSIG1:
Parameter
Operating mode PSx t Trans.block. PSx
PSIG1:
V< triggered
[ 019 230 ]
&
PSIG1: PSIG1:
PSIG1: Trip signal V< PSx
Weak inf. ready V< weak infeed PSx
[ 019 231 ] [ * ] [ * ]
PSIG1:
tV< PSx
[ * ]
0
V̲
1
t 0 PSIG1:
WI Trip Signal
0: Without
[ 019 232 ]
1: With
PSIG1:
Receive signal
[ 006 036 ] &
& PSIG1:
Weak infeed start.
INP:Fct. assign. UXX [ 043 064 ]
≥1
[ xxx xxx ]
U x1
U x2
U x3
U xx
Without function
PSIG1:
Weak inf. trigg. EXT
[ 043 062 ]
48Z9381A
PSIG1:
Block. weak inf. EXT
[ 036 255 ]
V < 0.35Vnom
5s 0
V̲
MAIN:
CB open A EXT
[ 044 131 ]
DIST:
Starting
[ 036 135 ]
MAIN:
General starting S1 1
[ 036 000 ]
& R1
PSIG1: 0 50ms
Receive signal
[ 006 036 ]
48Z9382A
PSIG1:
Echo on receive PSx PSIG1:
[ * ] Echo starting
[ 019 227 ]
PSIG1: t 0 t PSIG1:
Receive signal ≥1 Send Echo
[ 006 036 ] [ 019 228 ]
t+1s
DIST:
Starting ≥1
[ 036 135 ]
PSIG1:
Echo started
[ 019 229 ]
&
MAIN:
CB open A EXT
[ 044 131 ]
48Z9379A
The conditions for activation of the echo pulse should persist for a period in
excess of the set operate time delay PSIG1: Op. delay echo PSx, and
distance protection starting is absent for the echo pulse to be activated. But if
the local CB is open, the operate delay time P SIG1: Op. de lay ech o PSx will
be bypassed to active the echo pulse without time delay. The echo pulse is then
transmitted to the remote station for the set pulse duration PSIG1: Pulse dur.
echo PS x. Thereafter, the transmission of the receive signal is blocked for the
set pulse duration + 1 s. This prevents a permanent signal from being
transmitted.
The echo function can be disabled.
PSIG1:
Release t. send PSx
[ * ] PSIG1:
Send
[ 012 243 ]
0 t PSIG1:
Send signal
[ 036 035 ]
PSIG1: 1 PSIG1:
Test telecom. EXT ≥1 Test telecom. chann.
500ms
[ 036 038 ] [ 034 016 ]
PSIG1:
Test telecom. USER
[ 015 009 ]
0 PSIG1:
Parameter Release t. send PSx
1
set 1 015 002
0: don't execute set 2 024 001
1: execute set 3 024 061
set 4 025 021
49Z8964A
The communications link can be tested. For this purpose a 500 ms send signal is
issued through a binary signal input or by a setting parameter. It is extended by
the reset time-delay of the send signal. The remote station receives this signal if
the transmission link is in order.
ARC:
General enable USER
[ 015 060 ]
0: No
1: Yes
ARC:
Enable PSx
[ * ]
0 ARC:
Enabled
1 [ 015 064 ]
0: No
1: Yes
INP:
Fct. assignm. U xxx
[ xxx xxx ]
U x1
U x2
U x3
U xx
ARC:
Ext./user enabled
[ 037 013 ]
ARC:
Enable EXT
[ 037 010 ]
ARC:
Enable USER
[ 003 134 ]
0
1
0: don't execute
1: execute
ARC:
Disable EXT
[ 037 011 ]
ARC:
Disable USER
[ 003 133 ]
0: don't execute
1: execute
Parameter ARC:
Enable PSx
set 1 015 046
set 2 015 047
set 3 015 048
set 4 015 049
45Z5039A
ARC:
CB clos.pos.sig. PSx
[ * ]
0: Without ARC:
CB closed
1: With 303 004
MAIN:
CB closed A EXT
[ 036 051 ] ARC:
Ready
MAIN: [ 004 068 ]
Protection active
306 001
ARC:
CB drive ready EXT
[ 004 066 ]
ARC: ARC:
Blocked Not ready
[ 004 069 ] [ 037 008 ]
ASC:
Cycle running
[ 038 019 ]
Parameter ARC:
ARC: CB clos.pos.sig. PSx
Cycle running set 1 015 050
[ 037 000 ] set 2 024 024
set 3 024 084
set 4 025 044
D5Z5066A
ARC: 1
Enabled
[ 015 064 ]
SOTF: 1 ARC:
ARC blocked Blocked
305 650 [ 004 069 ]
ARC:
With R-trip
[ 015 018 ]
ARC:
Block. time int. PSx
[ * ]
0 &
1
1 t ARC:
1 Block. time running
0: No
1: Yes [ 037 004 ]
MAIN:
R-trip signal 1
1
[ 039 103 ]
MAIN:
R-trip signal 2
[ 039 104 ]
MAIN:
B-trip signal 1
[ 039 105 ]
MAIN:
B-trip signal 2
[ 039 106 ]
MAIN:
Man. M-trip signal 1
[ 039 081 ]
MAIN:
Man. M-trip signal 2
[ 039 084 ]
MAIN:
Man. R-trip signal 1
[ 039 082 ] ARC:
Blocked by I>
MAIN: [ 037 126 ]
Man. R-trip signal 2
[ 039 085 ]
MAIN:
Man. B-trip signal 1
[ 039 083 ]
MAIN:
Man. B-trip signal 2
[ 039 098 ]
ARC:
Block. ARC f. I> PSx
[ * ]
I̲ ARC:
Block. time ext. PSx
[ * ]
ARC: 1 t
Blocking EXT
[ 036 050 ]
The beginning of the following starts or input signals trigger the trip times,
provided that the starting conditions are met and the respective trip times are
not "blocked":
● D IS T: Z 1 (Z1,ze ) s tarti ng
● DI ST: Z2 st ar ting together with train start-up detection dx/dt Z2
● D IS T: Z 3 startin g together with train start-up detection dx/dt Z3
● D IST: Z4 startin g together with train start-up detection dx/dt Z4
● D ELTA : De lt a I startin g
● D TOC : St arting I>H
● DT OC : Start in g I>
● D TOC: Start in g I>>
● DTOCA : St ar ting I>
● DTOCA : St ar ting I>>
● D TOCB: St arti ng I >
● D TOC B: St art in g I >>
● ID MT: Start ing Ire f>
● IDMTA: S tartin g I ref>
● I DMTB: Start in g I ref>
● BUOC: S tart in g I >
● BUOC: S tart ing I >>
● Start by programmable logic
MAIN:
Fct.asg. M-trip cmd1
[ 021 007 ]
Signal 1
Signal 2 m out of n
Signal n
Selected signal
MAIN:
Fct.asg. R-trip cmd1
[ 021 025 ]
Signal 1
Signal 2 m out of n
Signal n
Selected signal
ARC:
With R-trip
[ 015 018 ] ARC:
Trip time HSR elaps.
303 152
ARC:
Ready
[ 004 068 ]
ARC:
Cycle running
[ 037 000 ]
ARC:
Oper. time 1 running
[ 037 005 ] ARC:
HSR-tr.DIST t1 PSx
ARC:
Oper. time 2 running [ * ]
[ 037 065 ]
DIST: DIST:
Z1 (Z1,ze) starting t1 elapsed
[ 039 003 ] [ 036 026 ]
DIST: DIST:
Z1'(Z1',ze) starting Trip signal Z1/t1
[ 039 004 ] ARC: [ 039 016 ]
HSR-tr.DIST t2S PSx
[ * ]
DIST: DIST:
t2S enable t2S elapsed
303 671
[ 039 009 ]
DIST:
Z2 starting DIST:
[ 039 005 ] Trip signal Z2/t2S
DIST: ARC: [ 039 017 ]
Z2' starting HSR-tr.DIST t2L PSx
[ 039 006 ] [ * ]
DIST:
t2L elapsed
[ 039 010 ]
DIST:
Trip signal Z2/t2L
ARC: [ 039 018 ]
HSR-tr.DIST t3S PSx
[ * ]
DIST: DIST:
t3S enable t3S elapsed
303 672
DIST: [ 039 143 ]
Z3 starting DIST:
[ 039 140 ] Trip signal Z3/t3S
ARC: [ 039 145 ]
DIST: HSR-tr.DIST t3L PSx
Z3' starting
[ 039 141 ] [ * ]
DIST:
t3L elapsed
[ 039 144 ]
DIST:
Trip signal Z3/t3L
ARC: [ 039 146 ]
HSR-tr.DIST t4S PSx
[ * ]
DIST: DIST:
t4S enable t4S elapsed
460 662 [ 039 047 ]
DIST:
Z4 starting DIST:
[ 039 042 ] Trip signal Z4/t4S
ARC: [ 039 040 ]
DIST: HSR-tr.DIST t4L PSx
Z4' starting
[ 039 043 ] [ * ]
DIST:
t4L elapsed
[ 039 048 ]
DIST:
Trip signal Z4/t4L
[ 039 041 ]
MAIN:
Fct.asg. M-trip cmd1
[ 021 007 ]
Signal 1
Signal 2 m out of n
Signal n
Selected signal
MAIN:
Fct.asg. R-trip cmd1
[ 021 025 ]
Signal 1
Signal 2 m out of n
Signal n
Selected signal
ARC:
With R-trip
[ 015 018 ] ARC:
Trip time TDR elaps.
ARC: 303 153
Ready
[ 004 068 ]
ARC:
Cycle running
[ 037 000 ]
ARC:
Oper. time 1 running
[ 037 005 ] ARC:
TDR-tr.DIST t1 PSx
ARC:
Oper. time 2 running [ * ]
[ 037 065 ]
DIST: DIST:
Z1 (Z1,ze) starting t1 elapsed
[ 039 003 ] [ 036 026 ]
DIST: DIST:
Z1'(Z1',ze) starting Trip signal Z1/t1
[ 039 004 ] ARC: [ 039 016 ]
TDR-tr.DIST t2S PSx
[ * ]
DIST: DIST:
t2S enable t2S elapsed
303 671
[ 039 009 ]
DIST:
Z2 starting DIST:
[ 039 005 ] Trip signal Z2/t2S
DIST: ARC: [ 039 017 ]
Z2' starting TDR-tr.DIST t2L PSx
[ 039 006 ] [ * ]
DIST:
t2L elapsed
[ 039 010 ]
DIST:
Trip signal Z2/t2L
ARC: [ 039 018 ]
TDR-tr.DIST t3S PSx
[ * ]
DIST: DIST:
t3S enable t3S elapsed
303 672
DIST: [ 039 143 ]
Z3 starting DIST:
[ 039 140 ] Trip signal Z3/t3S
ARC: [ 039 145 ]
DIST: TDR-tr.DIST t3L PSx
Z3' starting
[ 039 141 ] [ * ]
DIST:
t3L elapsed
[ 039 144 ]
DIST:
Trip signal Z3/t3L
ARC: [ 039 146 ]
TDR-tr.DIST t4S PSx
[ * ]
DIST: DIST:
t4S enable t4S elapsed
460 662 [ 039 047 ]
DIST:
Z4 starting DIST:
[ 039 042 ] Trip signal Z4/t4S
ARC: [ 039 040 ]
DIST: TDR-tr.DIST t4L PSx
Z4' starting
[ 039 043 ] [ * ]
DIST:
t4L elapsed
[ 039 048 ]
DIST:
Trip signal Z4/t4L
[ 039 041 ]
TDR-tr.DIST t1 PSx TDR-tr.DIST t2S PSx TDR-tr.DIST t2L PSx TDR-tr.DIST t3S PSx TDR-tr.DIST t3L PSx TDR-tr.DIST t4S PSx TDR-tr.DIST t4L PSx
set 1 015 073 015 148 015 156 015 164 015 172 015 184 015 192
set 2 024 041 015 149 015 157 015 165 015 173 015 185 015 193
set 3 025 001 015 150 015 158 015 166 015 174 015 186 015 194
set 4 025 061 015 151 015 159 015 167 015 175 015 187 015 195
MAIN:
Fct.asg. M-trip cmd1
[ 021 007 ]
Signal 1
Signal 2 m out of n
Signal n
Selected signal
MAIN:
Fct.asg. R-trip cmd1
[ 021 025 ]
Signal 1
Signal 2 m out of n
Signal n
Selected signal
&
ARC:
With R-trip
[ 015 018 ]
ARC:
Ready &
[ 004 068 ]
ARC:
Cycle running
[ 037 000 ]
ARC:
Oper. time 1 running
[ 037 005 ] ARC:
C HSR-tr.DELTA tD. PSx
ARC: [ * ]
Oper. time 2 running
[ 037 065 ]
t 0
DELTA: ARC:
Delta I starting Trip time HSR elaps.
303 152
[ 038 060 ]
DELTA:
Trip signal
[ 038 056 ]
ARC:
C TDR-tr.DELTA tD. PSx
[ * ]
t 0
ARC:
Trip time TDR elaps.
303 153
Fig. 3-180: HSR and TDR auto-reclose trip times for high impedance protection.
MAIN:
Fct.asg. M-trip cmd1
[ 021 007 ]
Signal 1
Signal 2 m out of n
Signal n
Selected signal
MAIN:
Fct.asg. R-trip cmd1
[ 021 025 ]
Signal 1
Signal 2 m out of n
Signal n ARC:
Trip time HSR elaps.
Selected signal 303 152
ARC:
With R-trip
[ 015 018 ]
ARC:
Ready
[ 004 068 ]
ARC:
Cycle running
[ 037 000 ]
ARC:
Oper. time 1 running ARC:
HSR-tr.DTOC tI>H PSx
[ 037 005 ]
[ * ]
ARC:
Oper. time 2 running
[ 037 065 ]
DTOC: DTOC:
Starting I>H Trip signal tI>H
[ 035 022 ] [ 040 076 ]
ARC:
HSR-tr.DTOC tI> PSx
[ * ]
DTOC: DTOC:
Starting I> tI> elapsed
[ 035 020 ] [ 040 010 ]
ARC:
HSR-tr.DTOCA tI> PSx DTOC:
Trip signal tI>
[ * ] [ 041 020 ]
DTOCA: DTOCA:
Starting I> tI> elapsed
[ 130 069 ] [ 130 077 ]
ARC:
HSR-tr.DTOCA tI>>PSx DTOCA:
Trip signal tI>
[ * ]
[ 130 071 ]
DTOCA: DTOCA:
Starting I>> tI>> elapsed
[ 130 070 ] [ 130 078 ]
ARC:
HSR-tr.DTOCB tI> PSx DTOCA:
Trip signal tI>>
[ * ] [ 130 072 ]
DTOCB: DTOCB:
Starting I> tI> elapsed
[ 130 089 ] [ 130 097 ]
ARC:
HSR-tr.DTOCB tI>>PSx DTOCB:
Trip signal tI>
[ * ]
[ 130 091 ]
DTOCB: DTOCB:
Starting I>> tI>> elapsed
[ 130 090 ] [ 130 098 ]
ARC: DTOCB:
HSR-tr.DTOC tI>> PSx Trip signal tI>>
[ * ] [ 130 092 ]
DTOC: DTOC:
Starting I>> tI>> elapsed
[ 035 021 ] [ 040 106 ]
ARC:
HSR-tr.IDMT kIrefPSx DTOC:
Trip signal tI>>
[ * ]
[ 040 011 ]
IDMT: IDMT:
Starting Iref> Trip signal tIref>
[ 040 080 ] [ 040 084 ]
ARC:
HSR-tr.IDMTAkIrefPSx
[ * ]
IDMTA: IDMTA:
Starting Iref> tIref> elapsed
[ 130 110 ] [ 130 112 ]
ARC:
HSR-tr.IDMTBkIrefPSx IDMTA:
Trip signal tIref>
[ * ] [ 130 113 ]
IDMTB:
48Z9367A
Parameter ARC: ARC: ARC: ARC: ARC: ARC: ARC: ARC: ARC: ARC:
HSR-tr.DTOC tI>H PSx
HSR-tr.DTOC tI> PSx
HSR-tr.DTOC tI>> PSx
HSR-tr.IDMT kIrefPSxHSR-tr.DTOCA tI> PSx
HSR-tr.DTOCA tI>>PSx HSR-tr.DTOCB tI>>PSx
HSR-tr.DTOCB tI> PSx HSR-tr.IDMTAkIrefPSx
HSR-tr.IDMTBkIrefPSx
set 1 015 069 015 105 015 074 015 094 015 196 015 197 015 213 015 214 015 217 015 219
set 2 024 052 020 105 020 107 020 113 020 196 020 197 020 213 020 214 020 217 020 219
set 3 024 053 021 105 021 107 021 113 021 196 021 197 021 213 021 214 021 217 021 219
set 4 024 054 022 105 022 107 022 113 023 196 023 197 023 213 023 214 023 217 023 219
Fig. 3-181: Auto-reclose trip times for DTOC and IDMT protection HSR.
MAIN:
Fct.asg. M-trip cmd1
[ 021 007 ]
Signal 1
Signal 2 m out of n
Signal n
Selected signal
MAIN:
Fct.asg. R-trip cmd1
[ 021 025 ]
Signal 1
Signal 2 m out of n
Signal n ARC:
Trip time TDR elaps.
Selected signal 303 153
ARC:
With R-trip
[ 015 018 ]
ARC:
Ready
[ 004 068 ]
ARC:
Cycle running
[ 037 000 ]
ARC:
Oper. time 1 running ARC:
TDR-tr.DTOC tI>H PSx
[ 037 005 ]
[ * ]
ARC:
Oper. time 2 running
[ 037 065 ]
DTOC: DTOC:
Starting I>H Trip signal tI>H
[ 035 022 ] [ 040 076 ]
ARC:
TDR-tr.DTOC tI> PSx
[ * ]
DTOC: DTOC:
Starting I> tI> elapsed
[ 035 020 ] [ 040 010 ]
ARC:
TDR-tr.DTOCA tI> PSx DTOC:
Trip signal tI>
[ * ] [ 041 020 ]
DTOCA: DTOCA:
Starting I> tI> elapsed
[ 130 069 ] [ 130 077 ]
ARC:
TDR-tr.DTOCA tI>>PSx DTOCA:
Trip signal tI>
[ * ]
[ 130 071 ]
DTOCA: DTOCA:
Starting I>> tI>> elapsed
[ 130 070 ] [ 130 078 ]
ARC:
TDR-tr.DTOCB tI> PSx DTOCA:
Trip signal tI>>
[ * ] [ 130 072 ]
DTOCB: DTOCB:
Starting I> tI> elapsed
[ 130 089 ] [ 130 097 ]
ARC:
TDR-tr.DTOCB tI>>PSx DTOCB:
Trip signal tI>
[ * ]
[ 130 091 ]
DTOCB: DTOCB:
Starting I>> tI>> elapsed
[ 130 090 ] [ 130 098 ]
ARC: DTOCB:
TDR-tr.DTOC tI>> PSx Trip signal tI>>
[ * ] [ 130 092 ]
DTOC: DTOC:
Starting I>> tI>> elapsed
[ 035 021 ] [ 040 106 ]
ARC:
TDR-tr.IDMT kIrefPSx DTOC:
Trip signal tI>>
[ * ]
[ 040 011 ]
IDMT: IDMT:
Starting Iref> Trip signal tIref>
[ 040 080 ] [ 040 084 ]
ARC:
TDR-tr.IDMTAkIrefPSx
[ * ]
IDMTA: IDMTA:
Starting Iref> tIref> elapsed
[ 130 110 ] [ 130 112 ]
ARC:
TDR-tr.IDMTBkIrefPSx IDMTA:
Trip signal tIref>
[ * ] [ 130 113 ]
48Z9368A
IDMTB:
IDMTB: tIref> elapsed
Starting Iref>
[ 130 130 ] [ 130 132 ]
IDMTB:
Trip signal tIref>
[ 130 133 ]
Parameter ARC: ARC: ARC: ARC: ARC: ARC: ARC: ARC: ARC: ARC:
TDR-tr.DTOC tI>H PSx
TDR-tr.DTOC tI> PSx
TDR-tr.DTOC tI>> PSx
TDR-tr.IDMT kIrefPSx
TDR-tr.DTOCA tI> PSx
TDR-tr.DTOCA tI>>PSx TDR-tr.DTOCB tI>>PSx
TDR-tr.DTOCB tI> PSx TDR-tr.IDMTAkIrefPSx
TDR-tr.IDMTBkIrefPSx
set 1 015 070 015 106 015 075 015 095 015 198 015 199 015 215 015 216 015 218 015 220
set 2 024 055 020 106 020 108 020 114 020 198 020 199 020 215 020 216 020 218 020 220
set 3 024 056 021 106 021 108 021 114 021 198 021 199 021 215 021 216 021 218 021 220
set 4 024 057 022 106 022 108 022 114 023 198 023 199 023 215 023 216 023 218 023 220
Fig. 3-182: Auto-reclose trip times for DTOC and IDMT protection TDR.
MAIN:
Fct.asg. M-trip cmd1
[ 021 007 ]
Signal 1
Signal 2 m out of n
Signal n
Selected signal
MAIN:
Fct.asg. R-trip cmd1
[ 021 025 ]
Signal 1
Signal 2 m out of n
Signal n
Selected signal
ARC:
With R-trip
[ 015 018 ]
ARC:
Ready
[ 004 068 ]
ARC:
Cycle running
[ 037 000 ]
ARC:
Oper. time 1 running
[ 037 005 ] ARC:
HSR-tr.BUOC tI> PSx
ARC: [ * ]
Oper. time 2 running
[ 037 065 ]
BUOC: ARC:
Starting I> Trip time HSR elaps.
[ 036 013 ] 303 152
ARC:
HSR-tr.BUOC tI>> PSx
[ * ]
BUOC: BUOC:
Starting I>> Trip signal I>
[ 036 115 ] [ 036 014 ]
ARC:
TDR-tr.BUOC tI> PSx
[ * ]
ARC:
Trip time TDR elaps.
303 153
ARC:
TDR-tr.BUOC tI>> PSx
[ * ]
BUOC:
Trip signal I>>
[ 036 116 ]
Fig. 3-183: Auto-reclose trip times for BUOC protection HSR and TDR.
AR C: Not re ady
AND NOT
(037 008)
In this example, the following list settings need to be set (see Section 6.13.5.1,
(p. 6-44)).
LOGIC:
Fct.assignm. outp. 1
[ 030 000 ]
LOGIC:
Op. mode t output 1
[ 030 001 ]
ARC:
Signal 1 Fct.assignm. tLOGIC
[ 015 033 ]
Signal 2 m out of n
Signal n
Output 1 1 out of n
t 0
LOGIC:
Output 01 (t) ARC:
Start by LOGIC
[ 037 078 ]
LOGIC:
Fct.assignm. outp. 2
[ 030 004 ]
LOGIC:
Op. mode t output 2
[ 030 005 ]
m out of n
ARC:
Not ready
[ 037 008 ]
Output 2
LOGIC: LOGIC:
Output 02 (t) Output 02 (t)
[ 042 035 ]
48Z5366A
MAIN:
Fct.asg. M-trip cmd1
[ 021 007 ]
Signal 1
Signal 2 m out of n
Signal n
Selected signal
MAIN:
Fct.asg. R-trip cmd1
[ 021 025 ]
Signal 1
Signal 2 m out of n
Signal n
Selected signal
ARC:
With R-trip
[ 015 018 ]
ARC:
Ready
[ 004 068 ]
ARC:
Cycle running
[ 037 000 ]
ARC:
Oper. time 1 running
[ 037 005 ] ARC:
HSR-tr. LOGIC PSx
ARC: ARC:
Oper. time 2 running [ * ] Trip time HSR elaps.
[ 037 065 ] 303 152
t 0
ARC: ARC:
Start by LOGIC Trip signal
[ 037 078 ] [ 039 099 ]
ARC:
TDR-tr. LOGIC PSx
[ * ]
Parameter ARC: ARC:
HSR-tr. LOGIC PSx TDR-tr. LOGIC PSx
t 0
set 1 015 098 015 099 ARC:
Trip time TDR elaps.
set 2 024 110 024 122 303 153
set 3 024 160 024 172
set 4 025 110 025 122
48Z5358A
Fig. 3-185: HSR and TDR auto-reclose trip times for programmable logic.
Voltage-independent reclosure
When the start signal is reset, operative time 1 is terminated and the HSR dead
time begins. If there is no starting during the HSR dead time, a reclose command
is issued once the HSR dead time has elapsed. Simultaneously reclaim time 1 is
triggered. If there is no starting during reclaim time 1, the ARC : Reclosure
successful signal will be issued when reclaim time 1 has elapsed. The auto-
reclose cycle is complete.
Voltage-dependent reclosure
Should starting conditions for an auto-reclose cycle drop out after operative time
1 has elapsed but not before operative time 2 has elapsed, the maximum dead
time (ARC : Dead time max PSx) will be triggered. With the triggering of the
maximum dead time a reclosure of the line from the far end will be expected. A
reclose command is issued and the maximum dead time is reset when the
voltage criterion (AR C: tV> PSx) is met and the associated time delay
(A RC : V> PS x) has elapsed. Simultaneously reclaim time 1 is triggered. If no
start occurs during reclaim time 1, the ARC: R eclosur e successful signal will
be issued when reclaim time 1 has elapsed. The auto-reclose cycle is complete.
HSR rejection
Reclaim time 1 is triggered should the circuit breaker fail to clear the fault during
the operative times. All protection timer stages are enabled again
simultaneously, provided that their trip time was not set to 'Blocked'.
If operative times elapse without the protection having reached a decision to trip,
the ARC function is ready again immediately after the relevant starting condition
has dropped out.
ARC:
Ready
[ 004 068 ]
ARC:
Cycle running
[ 037 000 ]
DIST:
Z1 (Z1,ze) starting
[ 039 003 ]
ARC:
HSR-tr.DIST t1
460 670 1 1
ARC:
t1 running
460 672 6
DIST:
Trip signal Z1/t1
[ 039 016 ]
MAIN:
M-trip command 1
[ 039 011 ]
ARC:
Oper. time 1 running
[ 037 005 ] 2 2
ARC:
Dead time HSR runn.
[ 037 067 ] 3 3
MAIN:
Close command
[ 037 009 ] 7 7
ARC:
Recl. time 1 running
[ 036 042 ] 4 4
ARC:
Reclosure successful
[ 036 062 ]
ARC:
Recl. time 2 running
[ 036 221 ] 5
MAIN:
Final trip
[ 038 103 ]
ARC:
Sig.interr. CB trip
[ 036 040 ]
1 2 3 4 5 6 7
Parameter ARC: ARC: ARC: ARC: ARC: DIST: MAIN:
HSR-tr.DIST t1 PSx Operative time 1 PSx HSR dead time PSx Reclaim time 1 PSx Reclaim time 2 PSx t1 PSx Close cmd.pulse time
[ 015 067 ]
set 1 015 072 015 066 015 056 015 054 015 124 012 028
ARC:
set 2 024 040 024 035 024 030 024 028 015 125 012 078 No. permit. TDR PSx
set 3 025 000 024 095 024 090 024 088 015 126 013 028 [ 015 068 ]
set 4 025 060 025 055 025 050 025 048 015 127 013 078 Setting: 0
48Z5359B
Fig. 3-186: Signal sequence for a HSR with a trip during operative time 1, triggered by a trip in distance protection
zone 1.
ARC:
Ready
[ 004 068 ]
ARC:
Cycle running
[ 037 000 ]
DIST:
Z1 (Z1,ze) starting
[ 039 003 ]
ARC:
HSR-tr.DIST t1
460 670 1 1
ARC:
t1 running
460 672
DIST:
Trip signal Z1/t1
[ 039 016 ]
MAIN:
M-trip command 1
[ 039 011 ]
ARC:
Oper. time 2 running
[ 037 065 ]
2 2
ARC:
Max. dead time runn.
[ 037 069 ] 3 3
ARC:
V> starting 4
ARC:
tV> running 5
MAIN:
Close command
[ 037 009 ] 7
ARC:
Recl. time 1 running
[ 036 042 ] 6 6
ARC:
Reclosure successful
[ 036 062 ]
ARC:
Sig.interr. CB trip
[ 036 040 ]
1 2 3 4 5 6 7
Parameter ARC: ARC: ARC: ARC: ARC: ARC: MAIN:
HSR-tr.DIST t1 PSx Operative time 2 PSx Dead time max PSx V> PSx tV> PSx Reclaim time 1 PSx Close cmd.pulse time
[ 015 067 ]
set 1 015 072 015 083 015 084 015 128 015 140 015 054
ARC:
set 2 024 040 024 042 024 043 015 129 015 141 024 028 No. permit. TDR PSx
set 3 025 000 025 002 025 003 015 138 015 142 024 088 [ 015 068 ]
set 4 025 060 025 062 025 063 015 139 015 143 025 048 Setting: 0
48Z5360C
Fig. 3-187: Signal sequence for a HSR with a trip during operative time 2, triggered by a trip in distance protection
zone 1.
time has elapsed, further triggering during the reclaim time does not result in a
further HSR.
A test HSR can be triggered either from the front panel user interface (HMI) or
using a binary signal input and it will add an increment to the ARC: No. o f HSR
Recloses counter.
For each ‘Test HSR’ request that does not result in a HSR test, the ARC: Re ject
test HSR signal i s generated.
ARC:
Test HSR USER
[ 011 066 ]
ARC:
Test HSR
0: don't execute [ 034 023 ]
1: execute
ARC: ARC:
Test HSR EXT Reject test HSR
[ 037 017 ] [ 036 055 ]
ARC:
Ready
[ 004 068 ]
48Z5361A
Voltage-independent reclosure
When the start signal is reset, operative time 1 is terminated and the TDR dead
time begins. If there is no starting during the TDR dead time, a reclose command
is issued once the TDR dead time has elapsed. Simultaneously reclaim time 1 is
triggered. If there is no starting during reclaim time 1, the ARC: Reclosure
successful signal will be issued when reclaim time 1 has elapsed. The auto-
reclose cycle is complete.
Voltage-dependent reclosure
Should starting conditions for an auto-reclose cycle drop out after operative time
1 has elapsed but not before operative time 2 has elapsed, the maximum dead
time (A RC : D ead tim e max P Sx) will be triggered. With the triggering of the
maximum dead time a reclosure of the line from the far end will be expected. A
reclose command is issued and the maximum dead time is reset when the
voltage criterion (ARC : t V> PSx) is met and the associated time delay
(ARC : V> PSx) has elapsed. Simultaneously reclaim time 1 is triggered. If no
start occurs during reclaim time 1, the A RC : Re cl osure succe ssful signal will
be issued when reclaim time 1 has elapsed. The auto-reclose cycle is complete.
TDR rejection
Reclaim time 1 is triggered should the circuit breaker fail to clear the fault during
the operative times. All protection timer stages are enabled again
simultaneously, provided that their trip time was not set to 'Blocked'.
If operative times elapse without the protection having reached a trip decision,
reclaim time 1 is triggered. The auto-reclose cycle is complete when reclaim time
1 has elapsed.
ARC:
Ready
[ 004 068 ]
ARC:
Cycle running
[ 037 000 ]
DIST:
Z1 (Z1,ze) starting
[ 039 003 ]
ARC:
HSR-tr.DIST t1
460 670
1
ARC:
TDR-tr.DIST t1
460 671
2 2
DIST:
Trip signal Z1/t1
[ 039 016 ]
MAIN:
M-trip command 1
[ 039 011 ]
ARC:
Oper. time 1 running
[ 037 005 ] 3 3 3
ARC:
Dead time HSR runn.
[ 037 067 ] 4
ARC:
Dead time TDR runn.
[ 037 003 ] 5 5
MAIN:
Close command
[ 037 009 ] 7 7 7
ARC:
Recl. time 1 running
[ 036 042 ] 6 6 6
ARC:
Reclosure successful
[ 036 062 ]
ARC:
Sig.interr. CB trip
[ 036 040 ]
1 2 3 4 5 6 7
Parameter ARC: ARC: ARC: ARC: ARC: ARC: MAIN:
HSR-tr.DIST t1 PSx TDR-tr.DIST t1 PSx Operative time 1 PSx HSR dead time PSx TDR dead time PSx Reclaim time 1 PSx Close cmd.pulse time
[ 015 067 ]
set 1 015 072 015 073 015 066 015 056 015 057 015 054
ARC:
set 2 024 040 024 041 024 035 024 030 024 031 024 028 No. permit. TDR PSx
set 3 025 000 025 001 024 095 024 090 024 091 024 088 [ 015 068 ]
set 4 025 060 025 061 025 055 025 050 025 051 025 048 Setting: 2
48Z5362B
Fig. 3-189: Signal sequence of a failed HSR followed by a failed TDR and then by a final successful TDR with a trip
during operative time 1, triggered by a trip in distance protection zone 1.
BUOC:
Trip signal I>
[ 036 014 ]
DIST:
Trip signal ARC:
[ 036 009 ] Zone ext. f. HSR PSx
[ * ]
ARC: 1 ARC:
Recl. time 1 running Zone extension HSR
[ 036 042 ] 0: No 303 001
ARC: 1: Yes
Ready
[ 004 068 ]
ARC:
Oper. time 1 running
ARC:
[ 037 005 ] Zone ext.dur. RC PSx
[ * ]
ARC:
(Re)close signal HSR 0
[ 037 007 ] ARC:
1 Zone extension RC
MAIN: 2
303 002
Close command
[ 037 009 ] 0: No
1: Following HSR
2: Following TDR
ARC:
Zone ext. f. TDR PSx
[ * ]
0
ARC:
1 Zone extension TDR
303 000
0: No
ARC:
TDR permitted 1: Yes
303 019
ARC:
Dead time TDR runn.
[ 037 003 ]
Trigger with ARC: General Starting EXT Trigger with ARC: General Starting EXT
ARC:
Ready
[ 004 068 ]
ARC:
Cycle running
[ 037 000 ]
ARC:
General starting EXT
[ 037 096 ]
MAIN:
Parallel trip EXT
[ 037 019 ]
MAIN:
M-trip command 1
[ 039 011 ]
Terminated Terminated
ARC:
Oper. time 1 running
[ 037 005 ] 2 2
ARC:
Dead time HSR runn.
[ 037 067 ] 3 3
MAIN:
Close command
[ 037 009 ] 7 7
ARC:
Recl. time 1 running
[ 036 042 ]
4 4
ARC:
Reclosure successful
[ 036 062 ]
ARC:
Sig.interr. CB trip
[ 036 040 ]
1 2 3 4 5 6 7
Parameter ARC: ARC: ARC: ARC: ARC: DIST: MAIN:
HSR-tr.DIST t1 PSx Operative time 1 PSx HSR dead time PSx Reclaim time 1 PSx Reclaim time 2 PSx t1 PSx Close cmd.pulse time
[ 015 067 ]
set 1 015 072 015 066 015 056 015 054 015 124 012 028
ARC:
set 2 024 040 024 035 024 030 024 028 015 125 012 078 No. permit. TDR PSx
set 3 025 000 024 095 024 090 024 088 015 126 013 028 [ 015 068 ]
set 4 025 060 025 055 025 050 025 048 015 127 013 078 Setting: 0
48Z5363A
Fig. 3-191: Signal sequence for a HSR with a trip during operative time 1, triggered by a trip from a protection
device, operating in parallel.
ARC:
DELTA: Operative time 1 PSx
Delta I starting [ * ]
[ 038 060 ]
ARC: ARC:
Enabled Operative time 2 PSx
[ 015 064 ]
[ * ]
ARC:
Blocked
[ 004 069 ] ARC:
HSR dead time PSx
DIST: [ * ]
Z1 (Z1,ze) starting
[ 039 003 ]
DIST: ARC:
Z1'(Z1',ze) starting Dead time max PSx
[ 039 004 ] [ * ]
DIST:
Z2 starting ARC:
[ 039 005 ] No. permit. TDR PSx
DIST: [ * ]
Z2' starting
[ 039 006 ]
ARC:
DIST: TDR dead time PSx
Z3 starting [ * ]
[ 039 140 ]
DIST:
Z3' starting ARC:
[ 039 141 ] Reclaim time 1 PSx
[ * ]
DIST:
Z4 starting
[ 039 042 ] ARC:
DIST: Reclaim time 2 PSx
Z4' starting [ * ]
[ 039 043 ]
DTOC: ARC:
Starting I>H Parallel trip PSx
[ 035 022 ] [ * ]
DTOC:
Starting I>
[ 035 020 ] ARC:
RC f. THERM trip PSx
DTOC: [ * ]
Starting I>>
[ 035 021 ]
DTOCA:
Starting I>
[ 130 069 ]
DTOCA:
Starting I>> ARC:
[ 130 070 ] Trip signal
[ 039 099 ]
DTOCB:
Starting I> ARC:
[ 130 089 ] Cycle running
DTOCB: [ 037 000 ]
Starting I>>
[ 130 090 ] ARC:
Oper. time 1 running
IDMT: [ 037 005 ]
Starting Iref>
[ 040 080 ] ARC:
Oper. time 2 running
BUOC: [ 037 065 ]
Starting I>
[ 036 013 ] ARC:
Dead time HSR runn.
BUOC: [ 037 067 ]
Starting I>>
[ 036 115 ] ARC:
ARC: Max. dead time runn.
Start by LOGIC [ 037 069 ]
[ 037 078 ] ARC:
ARC: Dead time TDR runn.
Trip time HSR elaps. [ 037 003 ]
303 152
ARC:
ARC: Dead time running
Trip time TDR elaps. [ 037 002 ]
303 153
ARC:
THERM: Recl. time 1 running
Trip signal [ 036 042 ]
[ 039 020 ]
ARC:
MAIN: Recl. time 2 running
M-trip signal 1
[ 039 101 ] [ 036 221 ]
ARC: ARC:
With R-trip Def. recl.time runn.
[ 015 018 ] [ 036 228 ]
MAIN: ARC:
R-trip signal 1 Lock f. Gen.starting
[ 039 103 ] [ 036 229 ]
ARC: ARC:
General starting EXT (Re)close signal HSR
[ 037 096 ] [ 037 007 ]
MAIN: ARC:
Parallel trip EXT (Re)close signal TDR
[ 037 019 ] [ 037 006 ]
ARC:
Test HSR ARC:
[ 034 023 ] Sig.interr. CB trip
[ 036 040 ]
IDMTA:
Starting Iref> ARC:
[ 130 110 ] Reclosure successful
[ 036 062 ]
IDMTB:
Starting Iref>
[ 130 130 ]
Parameter ARC: ARC: ARC: ARC: ARC:
Operative time 1 PSx Operative time 2 PSx HSR dead time PSx Dead time max PSx No. permit. TDR PSx
set 1 015 066 015 083 015 056 015 084 015 068
set 2 024 035 024 042 024 030 024 043 024 037
set 3 024 095 025 002 024 090 025 003 024 097
set 4 025 055 025 062 025 050 025 063 025 057
ARC: + ARC:
(Re)close signal HSR No. of HSR
[ 037 007 ] R [ 004 004 ]
ARC: + ARC:
(Re)close signal TDR No. of TDR
[ 037 006 ] R [ 004 008 ]
MAIN:
General reset USER
[ 003 002 ]
1: execute
MAIN:
General reset EXT
[ 005 255 ]
ARC:
Reset counters EXT
[ 005 244 ]
ARC:
Reset counters USER
[ 003 005 ]
1
0: don't execute
1: execute
48Z6365A
LOGIC:
Fct.assignm. outp. 1
[ 030 000 ]
LOGIC:
Op. mode t output 1
[ 030 001 ]
IDMT: ARC:
Trip signal tIref> Fct.assignm. tLOGIC
[ 040 084 ] [ 015 033 ]
LOGIC: 1 out of n
Output 01
t 0
ARC:
Start by LOGIC
LOGIC: [ 037 078 ]
Output 01 (t)
MAIN:
Fct.asg. M-trip cmd1
[ 021 007 ]
m out of n
48Z93A4A
Fig. 3-194: Example: Start of the ARC operative time using output 01 of the programmable logic.
By using the assignment (015 033) A RC: Fct.ass ignm. tL OGIC, additional
user-specific conditions for starting an ARC cycle can easily be defined within the
programmable logic.
All internal signals (for example an IDMT trip signal or a ground fault direction
determination decision) and all external conditions fed in by means of binary
input signals are available for that purpose (unless for the latter the equivalent
signal (037 096) AR C: Gen er al s tarti ng EXT is to be used). With the logical
operators and time stages of the programmable logic, even complex
dependencies can be realized.
Under the precondition that the auto-reclosing control function (ARC) is ready,
the ARC operative time is started as soon as the assigned logical output enters
the active state.
Note that this signal assignment does not automatically lead to a trip. A trip has
to be defined separately in the programmable logic. In the simplest case, this can
be achieved by linking the logical signal (with or without an appropriate delay) to
the general trip command 1. Solely the successful execution of this trip
command (more precisely, the raise and termination of the general trip signal 1
prior to the operative time 1 or 2 have elapsed) lead to the start of the dead
time.
The example in Fig. 3-194, (p. 3-243) illustrates a possible configuration.
In general, any equation within the programmable logic function can be used to
start the ARC tripping time.
ASC:
General enable USER
[ 018 000 ]
0: No
1: Yes
ASC:
Enable PSx
[ * ]
0 ASC:
Enabled
1 [ 018 024 ]
0: No
1: Yes
INP:
Fct. assignm. U xxx
[ xxx xxx ]
U x1
U x2
U x3
U xx
ASC:
Ext./user enabled
[ 037 092 ]
ASC:
Enable EXT
[ 037 049 ]
ASC:
Enable USER
[ 003 136 ]
1
0: don't execute
1: execute
ASC:
Disable EXT
[ 037 061 ]
ASC:
Disable USER
[ 003 135 ]
0: don't execute
1: execute
Parameter ASC:
Enable PSx
set 1 018 020
set 2 018 021
set 3 018 022
set 4 018 023
19Z5232A
signal input, then the ASC will be enabled by a positive edge of the input signal
and disabled by a negative edge. If only the A SC: Dis able E XT function has
been assigned to a binary signal input, then a signal at this input will have no
effect.
If the ASC function is disabled an activation enable will always be issued.
MAIN:
M.c.b. trip V EXT
[ 004 061 ]
MAIN:
M.c.b. trip Vref EXT
[ 036 086 ]
ASC: ASC:
Blocking EXT Blocked
[ 037 048 ] [ 038 018 ]
ASC: ASC:
Enabled Ready
[ 018 024 ] [ 037 079 ]
ASC:
MAIN: Not ready
Protection active [ 037 082 ]
306 001
ASC:
Clos.rej.w.block PSx
[ * ]
ASC:
Close enable w.block
305 001
0 ASC:
Close reject.w.block
1 305 002
0: No
1: Yes
ASC:
Active for HSR PSx
[ * ]
ASC:
0 Active
305 003
1
0: No
1: Yes
ARC:
HSR
303 156
ASC:
Active for TDR PSx
[ * ]
0: No
1: Yes
ARC:
TDR
303 006
ASC:
Manual close request
305 000
19Z51BCA
ARC:
(Re)close request ASC:
[ 037 077 ] Gen. close request
306 012
ARC:
Cycle running
[ 037 000 ]
DEV01: ASC:
Close request Manual close request
307 001
305 000
ASC:
AC effect. for DEV01
305 040
ASC:
AR close requ. USER
[ 008 238 ]
1 500ms 1
0: don't execute
1: execute
ASC:
AR Close request
[ 008 239 ]
ASC: 50ms 0
AR close request EXT 1
[ 008 236 ] 500ms
ASC: 50ms 0
Enabl.close requ.EXT
[ 037 063 ]
INP:
Fct. assignm. U xxx
[ 152 xxx ]
U x1
U x2
U x3
U x4
U xx
ASC:
Test AR close r.USER
[ 008 237 ]
ASC:
Test
305 004
0
1 100ms 1 1
500ms
0: don't execute
1: execute
ASC: ASC:
Test AR close r. EXT Test AR close requ.
[ 000 106 ] [ 008 240 ]
19Z8073A
The ASC function can be triggered by ARC, via setting parameters, from an
appropriately configured binary signal input (A SC: Enabl.close requ.EXT), or
via a close request from the control function. Close requests via a setting
parameter, the binary signal input or the control function are accepted only if no
ARC cycle is running.
ARC:
(Re)close request ASC:
[ 037 077 ] Gen. close request
306 012
ARC:
Cycle running
[ 037 000 ]
DEV01: ASC:
Close request Manual close request
307 001
305 000
ASC:
AC effect. for DEV01
305 040
ASC:
MC close requ. USER
[ 018 004 ]
1 500ms 1
0: don't execute
1: execute
ASC:
MC Close request
[ 034 018 ]
ASC: 50ms 0
MC Close request EXT 1
[ 037 062 ] 500ms
ASC: 50ms 0
Enabl.close requ.EXT
[ 037 063 ]
INP:
Fct. assignm. U xxx
[ 152 xxx ]
U x1
U x2
U x3
U x4
U xx
ASC:
Test MC close r.USER
[ 018 005 ]
ASC:
Test
305 004
0
1 100ms 1 1
500ms
0: don't execute
1: execute
ASC: ASC:
Test MC close r. EXT Test MC close requ.
[ 037 064 ] [ 034 019 ]
19Z8072A
The ASC operative time is started with the close request. If the close enable is
issued before the ASC operative time has elapsing, the close command is issued.
Otherwise an A SC : C lose r e j ecti on signal is generated for 100 ms.
ASC: ASC:
Cycle running Cycle running
[ 038 019 ] [ 038 019 ]
ASC: ASC:
Gen. close request Gen. close request
ASC: ASC:
Operat.time running Operat.time running
[ 037 093 ] [ 037 093 ]
① ①
ASC: ASC:
Close enable Close rejection
[ 037 083 ] [ 037 086 ]
100ms
100ms
MAIN: MAIN:
Close command Close command
[ 037 009 ] [ 037 009 ]
②
① ②
ASC: MAIN:
Parameter Operative time PSx Close cmd.pulse time
[ 015 067 ]
set 1 018 010
set 2 077 034
set 3 078 034
set 4 079 034 D5Z5073C
Fig. 3-199: Signal flow for a close enable and a close rejection.
ASC:
Operative time PSx
[ * ]
ASC:
Φ ASC:
Gen. close request Cycle running
[ 038 019 ]
ASC: ASC:
Test Close rejection
[ 037 086 ]
ASC: ASC:
Close reject.w.block Operat.time running
[ 037 093 ]
ASC:
Parameter Operative time PSx
Close enable conditions for Auto- Close enable conditions for Manual
reclose control close command
The automatic reclosure setting parameters become active when a close request
is issued by the integrated ARC (for an RRC, HSR or TDR) or by a close request
from an external ARC device sent to the binary signal input function A SC: AR
close reque st E XT.
yes yes
no no
47Z1085C_EN
Fig. 3-201: Functional sequence and close conditions for the Synchronism check.
In slightly asynchronous power systems, setting ASC: AR with tCB PSx to Yes
makes it possible to consider the circuit breaker closing time when issuing a
close command.
The condition for “slightly asynchronous power systems” is given if the difference
in frequencies lies within the range of 10 mHz < Δf < Δfmax. If this condition and
the voltage condition (ΔV < ΔVmax) are met then the next point in time is
continuously calculated at which the phasors for Vref and the corresponding
voltage of the three-phase system are in phase (e.g. difference in voltage phase
angles approaches 0°). The close command, allowing for the set CB close time
M AIN: tC B, C lose is then issued sooner.
ASC:
Enabled
[ 018 024 ]
ASC:
Active
305 003
ASC:
AR op. mode PSx
[ * ]
1: Voltage-checked
ASC:
AR V> volt.check PSx
3: Volt./sync.-checked [ * ]
V̲A
Vref
ASC:
AR V< volt.check PSx
[ * ]
ASC:
AR tmin v-check PSx
[ * ]
ASC:
AR Op.mode v-chk.PSx
[ * ]
ASC : AR V> v olt .ch eck PSx ASC: MC V> vol t.ch eck P Sx
ASC : AR V< v olt .che ck P Sx A SC: MC V < volt.che ck PSx
Depending on the operating mode selected for the voltage check, all three
phase-to-ground voltages (or – alternatively, see above – the voltage measured
at T90) need to exceed or fall below the set value in order to meet the condition
for voltage-checked closing. If the conditions corresponding to the set operating
mode for the voltage synchronism check are met, then the close enable is issued
after the set minimum time has elapsed.
The following operating modes for voltage checking can be selected separately
for each parameter subset:
● Vref but not V
● V but not Vref
● Not V and not Vref
● Not V or not Vref
● N V&Vref or V&n Vref
ASC:
Enabled
[ 018 024 ]
ASC:
Active
305 003
ASC:
MC op. mode PSx
[ * ]
1: Voltage-checked
ASC:
MC V> volt.check PSx
3: Volt./sync.-checked [ * ]
V̲A
Vref
ASC:
MC V< volt.check PSx
[ * ]
ASC:
MC tmin v-check PSx
[ * ]
ASC:
MC op.mode v-chk.PSx
[ * ]
ASC: &
Active
ASC:
AR op. mode PSx
[ * ] ASC:
c AR V> sync.check PSx
↗ 2: Sync.-checked ≥1 [ * ]
↗ 3: Volt./sync.-checked
V̲A
ASC:
Vref AR tmin sync.chk PSx
[ * ]
& t 0 1 ASC:
100ms Close enable,sync.ch
[ 037 084 ]
t1 t2
ASC: >
Test
ASC:
>R Volt. magnit. diff.
ASC:
c AR Delta Vmax PSx [ 004 091 ]
[ * ] ASC:
>R Frequ. difference
[ 004 090 ]
ΔVmax ASC:
>R Angle difference
[ 004 089 ]
ASC:
◄
◄ c AR Delta f max PSx
[ * ]
c
Δfmax
ASC:
Parameter AR op. mode PSx
φ
set 1 018 025
◄
◄ set 2 018 026
set 3 018 027
ASC: ASC: set 4 018 028
Phi offset PSx AR Delta phi max PSx
[ * ] [ * ] ASC:
Parameter AR V> sync.check PSx
set 1 018 015 018 012 018 014 018 034 018 013
set 2 077 039 077 036 077 038 077 042 077 037
set 3 078 039 078 036 078 038 078 042 078 037
set 4 079 039 079 036 079 038 079 042 079 037
48Z9347A
Before a close enable signal is issued, the ASC checks the voltages for
synchronism. Synchronism is recognized if the following conditions are met
simultaneously:
● The measuring voltage and the reference voltage must exceed the set
threshold value.
If these conditions are met for at least the set time A SC : A R tmin s ync.chk
PS x or AS C: MC t min sync.ch k P Sx, respectively, then a close enable signal
is issued. The ASC operating time for the determination of differences in voltage,
angle, and frequency is approximately 100 ms.
The voltage magnitude difference, angle difference, and frequency difference are
stored as measured synchronism data at the time the close request is issued. In
the event of another close request, they are automatically overwritten by the
new data.
ASC: &
Active
ASC:
MC op. mode PSx
[ * ] ASC:
cMC V> sync.check PSx
↗ 2: Sync.-checked ≥1 [ * ]
↗ 3: Volt./sync.-checked
V̲A
ASC:
Vref MC tmin sync.chk PSx
[ * ]
& t 0 1 ASC:
100ms Close enable,sync.ch
[ 037 084 ]
t1 t2
ASC: >
Test
ASC:
>R Volt. magnit. diff.
ASC:
c MC Delta Vmax PSx [ 004 091 ]
[ * ] ASC:
>R Frequ. difference
[ 004 090 ]
ΔVmax ASC:
>R Angle difference
[ 004 089 ]
ASC:
◄
◄ c MC Delta f max PSx
[ * ]
c
Δfmax
ASC:
Parameter MC op. mode PSx
φ
set 1 000 056
◄
◄ set 2 000 057
set 3 000 058
ASC: ASC: set 4 000 059
Phi offset PSx MC Delta phi max PSx
[ * ] [ * ] ASC:
Parameter MC V> sync.check PSx
set 1 000 098 000 080 000 084 018 034 000 089
set 2 000 099 000 081 000 086 077 042 000 091
set 3 000 100 000 082 000 087 078 042 000 092
set 4 000 101 000 083 000 088 079 042 000 093
48Z9348A
ASC: ASC:
Cycle running Cycle running
[ 038 019 ] [ 038 019 ]
ASC: ASC:
Gen. close request Gen. close request
ASC: ASC:
Operat.time running Operat.time running
[ 037 093 ] [ 037 093 ]
① ①
ASC: ASC:
Close enable Close enable
[ 037 083 ] [ 037 083 ]
② ② ②
ASC: ASC:
Close rejection Close rejection
[ 037 086 ] [ 037 086 ]
100ms
① ②
ASC:
Parameter Operative time PSx ≥ 100 ms
set 1 018 010
set 2 077 034
set 3 078 034
set 4 079 034 19Z5230B
For test purposes a close request can be issued via a setting parameters or an
appropriately configured binary signal input (see Fig. 3-206, (p. 3-259)). In this
case no close command is issued and it is not counted.
Separate triggering parameters are available for testing the function with
parameters for manual (MC) and automatic (AR) reclosure.
The ASC cycle and the operating time are started by the test close request.
The network synchronism is checked during the whole operating time and
ASC: C lose en abl e is set accordingly. If at the end of the operate time no
network synchronism is registered, a 100 ms signal ASC : C lose r ejection is
issued.
3.29.8 Integrating the ASC Function into the Control and Monitoring of
Switchgear Units
ASC:
Enabled
[ 018 024 ]
ASC:
CB assignment PSx
[ * ]
No assignment
DEV01
DEV02
DEV03
DEVxx ASC:
AC effect. for DEV01
305 040
Sel. DEV01
ASC:
Close enable DEV01
305 041
ASC:
Close enable
[ 037 083 ]
ASC:
System integrat. PSx
[ * ]
2
1: Autom.synchron.check
2: Autom.synchr.control
12Z51BGB
Fig. 3-207: Integrating the ASC function into the control and monitoring of switchgear units.
ASC triggering by a close request from the control functions is also possible.
This requires that the circuit breaker is assigned to an external device and that
the ASC system integration is set to Autom.synchr.control. If the control function
issues a close request then the close command for the circuit breaker requires
the ASC : Cl ose enable (see Section 3.43.6.6, (p. 3-345)).
However if AS C: Syst e m inte grat. PSx is set to Autom.synchron.check ASC
will not interfere with any switching commands. Data generated and
continuously updated by the ASC function is transmitted – when configurations
have been set accordingly – to the central control station, where operators may
make decisions as to which external device is to be given a switching command.
ASC:
Transm.cycle,meas.v.
[ 101 212 ]
ASC:
Cycle running c
[ 038 019 ]
ASC:
Voltage Vref
[ 004 087 ]
ASC:
Volt. magnit. diff.
[ 004 091 ]
ASC:
Angle difference
[ 004 089 ]
ASC:
Frequ. difference
[ 004 090 ]
48Z9349A
The following measured values are obtained and calculated during an ASC cycle
and are transmitted during a set cycle time:
● Voltage from the reference voltage channel
● Difference in phase voltage magnitudes
● Difference in phase angles
● Frequency difference
Outside of the ASC cycle the measured values have the status of Not measured.
ASC: >S
Manual close request 11 & >+
1 ASC:
>R No. RC aft. man.clos
>R
MAIN: [ 004 009 ]
Close command
[ 037 009 ]
ASC: >+
Gen. close request ASC:
>R No. close requests
[ 009 033 ]
ASC: >+
Close rejection ASC:
No. close rejections
[ 037 086 ] >R
[ 009 034 ]
MAIN:
General reset USER
[ 003 002 ]
↗ 1: execute ≥1
MAIN:
General reset EXT
[ 005 255 ]
ASC:
Reset counters EXT
[ 006 074 ]
ASC:
Reset counters USER
[ 003 089 ]
0: don't execute
1: execute 47Z1377B
DTOC:
General enable USER
[ 031 068 ]
0
DTOC:
1 Enabled
[ 040 120 ]
0: No
1: Yes
DTOC:
Enable PSx
[ * ]
Parameter DTOC:
Enable PSx
0
set 1 072 098
1 set 2 073 098
set 3 074 098
0: No set 4 075 098
1: Yes
45Z8089A
DTOC:
Enabled
[ 040 120 ]
DTOC:
Blocking tI> EXT
[ 041 060 ]
MAIN:
Protection active DTOC: DTOC:
306 001 I> PSx tI> PSx DTOC:
Trip signal tI>
[ * ] [ * ]
[ 041 020 ]
DTOC:
tI> elapsed
I̲
[ 040 010 ]
DTOC:
Starting I>
[ 035 020 ]
DTOC:
Blocking tI>> EXT
[ 041 061 ] DTOC: DTOC:
I>> PSx tI>> PSx DTOC:
[ * ] Trip signal tI>>
[ * ]
[ 040 011 ]
DTOC:
tI>> elapsed
[ 040 106 ]
DTOC:
Starting I>>
[ 035 021 ]
DTOC:
Blocking tI>H EXT
[ 041 062 ]
DTOC: DTOC:
I>H PSx tI>H PSx
[ * ] [ * ]
DTOC:
Trip signal tI>H
[ 040 076 ]
DTOC:
Starting I>H
MAIN:
Inrush stabil. trigg [ 035 022 ]
306 014
MAIN:
Harm. blk. trigg
460 649
48Z9361A
threshold V<. Setting the undervoltage threshold V< to Blocked will disable this
voltage scan and tripping will be permanently enabled.
For very low fault voltages, the voltage from the voltage memory is used in place
of the measured voltage in order to avoid erroneous direction decisions. The
direction decision is dependent on the following conditions:
● VF > 0.1 Vn
The direction decision is issued on the basis of the fault current and the
measured fault voltage Vf.
● VF < 0.1 Vn
Voltage memory enabled:
The direction decision is issued on the basis of the fault current and the
voltage values stored in the voltage memory.
Voltage memory not enabled:
The direction decision is issued on the basis of the fault current and the
measured fault voltage down to a minimum value of 1 V. If the fault voltage
drops to a value of less than approximately 1 V, an accurate direction
determination is no longer possible. In this case, a Fault forward decision is
issued - independently of the actual fault direction.
Another setting is used to determine whether a failure of the voltage-measuring
circuit will either lead to the DTOC protection operating non-directionally or to it
becoming blocked.
The starting direction may be freely set.
Forward direction
Backward direction V̲
I̲
68Z50ABB
The load flow direction is displayed for as long as there is no fault (short-circuit)
condition apparent, which would be characterized by the starting of the current
stages and the enabling of the undervoltage stage.
DTOC:
Timer Start tI> PSx
[ * ]
1
2
1: With starting
DTOC: 2: With direction
Blocking tI> EXT DTOC:
C tI> PSx
[ 041 060 ]
DTOC: [ * ]
Enabled DTOC:
[ 040 120 ] C I> PSx
DTOC:
MAIN: [ * ] tI> elapsed
Protection active [ 040 010 ]
306 001
I̲ DTOC:
Starting I>
[ 035 020 ]
DTOC:
Direction I> forw.
402 412
DTOC:
Direction I> backw.
402 413 DTOC:
DTOC: I> triggered
Trip I> Non-direct. 310 049
402 414 DTOC:
DTOC: Trip signal tI>
Direction measurem. [ 041 020 ]
[ 031 131 ]
0: Without
DTOC:
Timer Start tI>> PSx
[ * ]
1
2
1: With starting
2: With direction
DTOC: DTOC:
Blocking tI>> EXT C tI>> PSx
[ 041 061 ] [ * ]
DTOC:
C I>> PSx
DTOC:
[ * ] tI>> elapsed
[ 040 106 ]
DTOC:
Starting I>>
[ 035 021 ]
DTOC:
Direction I>> forw.
402 415 DTOC:
DTOC: I>> triggered
Direction I>> backw. 310 050
402 416 DTOC:
DTOC: Trip signal tI>>
Trip I>> Non-direct.
402 417 [ 040 011 ]
MAIN:
Inrush stabil. trigg
306 014
MAIN:
Harm. blk. trigg
460 649
48Z9362A
MCMON: <1V
Meas. circ. V faulty DTOC:
Direct. using Vmeas
[ 038 023 ] [ 036 137 ]
V̲
DTOC:
Direct. using memory
DTOC: [ 036 136 ]
Beta (I>) PSx
[ * ]
>0.05 Inom DTOC:
Gamma (I>) PSx
[ * ]
C1
I̲
C2
φF DTOC:
Φ 1
Fault I> forward
[ 035 137 ]
φS
Φ 2 DTOC:
V̲(memory) Fault I> backward
[ 035 140 ]
DTOC: 30 ms 0
Direction I> forw. DTOC:
Power flow I>forw.
MAIN: [ 035 223 ]
Vmemory enable DTOC:
Direction I> backw. 30 ms 0 DTOC:
310 057 Power flow I>backw.
DTOC: [ 035 224 ]
I> triggered
310 049
DTOC:
DTOC: I> Forw. w/o meas.
V < V< (I>) DTOC: [ 041 198 ]
403 410 Beta (I>>) PSx
[ * ]
DTOC:
V ≥ Vmin (I>) DTOC:
Gamma (I>>) PSx
402 418 [ * ]
C1
C2
DTOC:
Φ 1 Fault I>> forward
[ 035 147 ]
Φ 2 DTOC:
Fault I>> backward
[ 035 148 ]
DTOC: 30 ms 0 DTOC:
Direction I>> forw. Power flow I>>forw.
[ 035 227 ]
DTOC:
Direction I>> backw. 30 ms 0 DTOC:
Power flow I>>backw.
DTOC: [ 035 228 ]
I>> triggered
310 050
DTOC:
DTOC: I>> Forw. w/o meas.
V < V< (I>>)
403 411 [ 041 199 ]
DTOC:
V ≥ Vmin (I>>)
402 419
DTOC:
Vmin (I>) PSx
[ * ]
V̲ DTOC:
V ≥ Vmin (I>)
402 418
DTOC:
Mode V<Vmin (I>) PSx
[ * ]
1: Non-directional
2: Blocked
MAIN:
M.c.b. trip V EXT
[ 004 061 ]
MCMON:
Meas. circ. V faulty
[ 038 023 ]
DTOC:
Mode w/o V (I>) PSx
DTOC:
[ * ] Meas. I> non-direct.
[ 035 077 ]
1 DTOC:
Dir.meas. I> blocked
[ 035 080 ]
2
1: Non-directional
2: Blocked
DTOC: DTOC:
V< (I>) PSx Direction (I>) PSx
[ * ] [ * ]
1
V̲
2
3
Setting blocked
1: Forward directional
2: Backward directional
3: Non-directional
DTOC:
Direction I> forw.
402 412
DTOC:
Fault I> forward
[ 035 137 ]
DTOC:
Direction I> backw.
DTOC: 402 413
Fault I> backward
[ 035 140 ]
DTOC:
Trip I> Non-direct.
402 414
DTOC:
V < V< (I>)
403 410
48Z93A7
Fig. 3-215: Determining the starting direction for stage I> (also valid for stage I>>).
DTOCA:
General enable USER
[ 130 065 ]
0
DTOCA:
1 Enabled
[ 130 073 ]
0: No
1: Yes
DTOCA:
Enable PSx
[ * ]
0: No
1: Yes DTOCA:
Not ready
DTOCA: [ 130 076 ]
Blocking EXT
[ 130 079 ] MAIN:
Feeder mode
[ 010 135 ]
2
Parameter DTOCA:
3 Enable PSx
set 1 130 060
1: Classic single feed
set 2 131 060
2: Autotransformer feed set 3 132 060
3: Single feed w. sum I set 4 133 060 48Z9341
Fig. 3-216: Disabling, enabling and readiness in DTOCA protection. (Only DTOCA is shown; the logic, however, also
applies to DTOCB with different numerical addresses.)
DTOCA:
Blocking tI> EXT
[ 130 066 ]
DTOCA:
Not ready
[ 130 076 ]
DTOCA: DTOCA:
Enabled DTOCA:
I> PSx tI> PSx DTOCA:
[ 130 073 ] tI> elapsed
[ * ] [ * ]
MAIN: [ 130 077 ]
Protection active
306 001
DTOCA:
Trip signal tI>
I̲A [ 130 071 ]
DTOCA:
Starting I>
[ 130 069 ]
DTOCA:
Blocking tI>> EXT
[ 130 068 ]
DTOCA: DTOCA:
I>> PSx tI>> PSx DTOCA:
tI>> elapsed
[ * ] [ * ]
[ 130 078 ]
DTOCA:
Trip signal tI>>
[ 130 072 ]
DTOCA:
Starting I>>
[ 130 070 ]
MAIN:
Inrush stabil. trigg
306 014
MAIN:
Harm. blk. trigg
460 649
IDMT:
General enable USER
[ 017 096 ]
1 IDMT:
Enabled
0: No [ 040 100 ]
1: Yes
IDMT:
Enable PSx
[ * ]
0: No
1: Yes
Parameter IDMT:
Enable PSx
set 1 072 000
set 2 073 000
set 3 074 000
set 4 075 000
48Z6377A
0 Definite Time t =k
a
Per IEC 255–3 t =k · I b
(I ) -1
ref
1 Standard Inverse 0.14 0.02
2 Very Inverse 13.50 1.00
3 Extremely Inverse 80.00 2.00
4 Long Time Inverse 120.00 1.00
a k ·R
Per IEEE C37.112 t = k ·( I + c) tr = I 2
(I )b - 1 -
1 (I )
ref ref
5 Moderately Inverse 0.0515 0.0200 0.1140 4.85
6 Very Inverse 19.6100 2.0000 0.4910 21.60
7 Extremely Inverse 28.2000 2.0000 0.1217 29.10
a k ·R
Per ANSI t = k ·( I + c) tr = I 2
b
(I ) -1 1- ( I )
ref ref
8 Normally Inverse 8.9341 2.0938 0.17966 9.00
9 Short Time Inverse 0.2663 1.2969 0.03393 0.50
10 Long Time Inverse 5.6143 1.0000 2.18592 15.75
1
11 RI-Type Inverse t =k · 0.236
0.339 - I
(I )
ref
I
12 RXIDG-Type Inverse t = k · (5.8 - 1.35 · ln I )
ref
Once a ratio I/Iref greater than 20 is reached, the tripping time is bounded on the
lower end.
Characteristic 1: IEC 255–3, Standard Inverse Characteristic 2: IEC 255–3, Very Inverse
1000 1000
100 100
k=10
10 10
k=10
t/s k=1
t/s
1 1
k=1
k=0.1
0.1 k=0.05 0.1
k=0.1
k=0.05
0.01 0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
I/Iref I/Iref
Characteristic 3: IEC 255–3, Extremely Inverse Characteristic 4: IEC 255–3, Long Time Inverse
1000 1000
100 100
k=10
10 10
k=1
t/s t/s
k=10
1 1
k=0.1
k=0.05
k=1
0.1 0.1
k=0.1
0.01 k=0.05 0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
I/Iref I/Iref
Characteristic 5: IEEE C37.112, Moderately Inverse Characteristic 6: IEEE C37.112, Very Inverse
1000 1000
100 100
10 k=10 10
k=10
t/s t/s
1 k=1 1
k=1
I/Iref I/Iref
1000
100
10
t/s
k=10
1
k=1
0.1
k=0.1
0.01 k=0.05
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
I/Iref
1000 1000
100 100
10 10
t/s t/s
k=10
1 1
k=10
k=1
0.1 0.1
k=1
k=0.1
0.01 k=0.05 0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 k=0.1
k=0.05
I/Iref I/Iref
1000
100
k=10
10
t/s k=1
1
k=0.1
0.1 k=0.05
0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
I/Iref
100 100
k=10
k=10
10 10
k=0.1
k=0.05 k=0.1
0.1 0.1 k=0.05
0.01 0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
I/Iref I/Iref
MAIN:
Protection active
306 001
IDMT:
Enabled
[ 040 100 ]
IDMT:
Iref PSx
[ * ]
1.05 Iref
I̲ IDMT:
Starting Iref>
[ 040 080 ]
IDMT:
Characteristic PSx
IDMT: [ * ]
Block. tIref> EXT
[ 040 101 ] IDMT:
MAIN: Char. factor kt PSx
Inrush stabil. trigg [ * ]
306 014
MAIN: IDMT:
Harm. blk. trigg Min. trip time PSx
460 649 [ * ]
IDMT:
Hold time PSx
[ * ]
IDMT:
Reset PSx
[ * ]
IDMT:
Memory clear
[ 040 110 ]
IDMT:
Hold time running
I/Iref [ 040 053 ]
IDMT:
tIref> elapsed
[ 040 082 ]
IDMT:
Trip signal tIref>
[ 040 084 ]
Setting
IDMT:
Characteristic PSx
0: Definite Time
1: IEC Standard Inverse
2: IEC Very Inverse
3: IEC Extr. Inverse
4: IEC Long Time Inv.
5: IEEE Moderately Inv.
6: IEEE Very Inverse
7: IEEE Extremely Inv. Setting
8: ANSI Normally Inv. IDMT:
9: ANSI Short Time Inv. Reset PSx
10: ANSI Long Time Inv.
11: RI-Type Inverse 1: Without delay
12: RXIDG-Type Inverse 2: Delayed as per char.
48Z9364A
Forward direction
Backward direction V̲
I̲
68Z50ABB
IDMT: IDMT:
C Iref PSx Timer Sta. tIref>PSx
[ * ] [ * ]
1
1.05 Iref
2
1: With starting
2: With direction
IDMT:
Enabled C
[ 040 100 ]
IDMT:
MAIN: Starting Iref>
Protection active
[ 040 080 ]
306 001
I̲
MAIN:
Inrush stabil. trigg
306 014
IDMT:
Forwards trip
307 104
IDMT:
Backwards trip IDMT:
307 105 Iref> triggered
310 038
IDMT:
Non-directional trip
307 106
IDMT:
Direction measurem. IDMT:
[ 017 109 ] Characteristic PSx
[ * ]
0: Without
IDMT:
Char. factor kt PSx
[ * ]
IDMT:
IDMT: Min. trip time PSx
Block. tIref> EXT [ * ]
[ 040 101 ]
IDMT:
Setting Hold time PSx
IDMT: [ * ]
Characteristic PSx C
IDMT:
Reset PSx
0: Definite Time [ * ]
1: IEC Standard Inverse
2: IEC Very Inverse C
3: IEC Extr. Inverse
4: IEC Long Time Inv. IDMT:
5: IEEE Moderately Inv. Memory clear
6: IEEE Very Inverse I/Iref [ 040 110 ]
7: IEEE Extremely Inv.
8: ANSI Normally Inv. IDMT:
Hold time running
9: ANSI Short Time Inv. [ 040 053 ]
10: ANSI Long Time Inv.
11: RI-Type Inverse IDMT:
12: RXIDG-Type Inverse tIref> elapsed
[ 040 082 ]
IDMT:
Setting Trip signal tIref>
IDMT: [ 040 084 ]
Reset PSx
1: Without delay
2: Delayed as per char.
48Z6375A
V̲
< 0. 1 Vnom
IDMT:
Direct. using memory
[ 041 014 ]
IDMT:
Beta PSx
[ * ]
> 0. 05 Inom IDMT:
Gamma PSx
[ * ]
C1
I̲
C2
IDMT:
K Φ1 Fault forward
[ 041 008 ]
IDMT:
S Φ2 Fault backward
V̲(memory) [ 041 009 ]
IDMT:
Forward direction 30 ms 0 Power flow forward
[ 041 017 ]
IDMT:
Iref> triggered
310 038 IDMT:
Forw. w/o measurem.
IDMT: [ 041 189 ]
V < V<
307 108
*
Parameter IDMT: IDMT:
Beta PSx Gamma PSx
set 1 072 046 072 047
set 2 073 046 073 047
set 3 074 046 074 047
set 4 075 046 075 047
48Z6376A
MCMON:
Meas. circ. V faulty
[ 038 023 ]
IDMT:
Mode w/o voltage PSx
[ * ]
IDMT:
Meas.non-directional
1 [ 041 007 ]
2 IDMT:
Dir. meas. blocked
1: Non-directional
[ 041 006 ]
2: Blocked
IDMT: IDMT:
V< PSx Direction (I>) PSx
[ * ] [ * ]
1
V̲
2
3
Setting blocked
1: Forward directional
2: Backward directional
3: Non-directional
IDMT:
Forwards trip
IDMT: 307 104
Fault forward
[ 041 008 ]
IDMT:
Backwards trip
IDMT: 307 105
Fault backward
[ 041 009 ]
IDMT:
Non-directional trip
307 106
IDMT:
V < V<
307 108
*
Parameter IDMT: IDMT: IDMT:
Mode w/o voltage PSx V< PSx Direction (I>) PSx
set 1 072 119 072 081 072 048
set 2 073 119 073 081 073 048
set 3 074 119 074 081 074 048
set 4 075 119 075 081 075 048
48Z63AJA
Case A
IDMT:
Starting Iref>
[ 040 080 ]
IDMT:
Hold time running
[ 040 053 ]
Per characteristic
Non-delayed
IDMT:
tIref> elapsed
[ 040 082 ]
Case B
IDMT:
Starting Iref>
[ 040 080 ]
IDMT:
Hold time running
[ 040 053 ]
Non-delayed
Per characteristic
IDMT:
tIref> elapsed
[ 040 082 ]
Parameter IDMT:
Hold time PSx
set 1 072 071
set 2 073 071
set 3 074 071
set 4 075 071 19Z5025B
Fig. 3-228: Effect of hold time shown with a phase current stage as an example. Example A: Hold time determined
is not reached. Example B: Hold time determined is reached.
Depending on the current flow the P438 will determine the tripping time and a
timer stage is started. The setting of the hold time defines the time period during
which the IDMT protection starting time is stored after the starting has dropped
out. Should starting recur during the hold time period then the time of the
renewed starting will be added to the time period stored. When the starting
times sum reach the tripping time value determined by the P438 then the
corresponding signal will be issued. Should starting not recur during the hold
time period then, depending on the setting, the memory storing the accumulated
starting times value will either be cleared without delay or according to the
characteristic set. In Fig. 3-228, (p. 3-282), the effect of hold time is shown by
the example of a phase current stage.
IDMTA:
General enable USER
[ 130 107 ]
0
IDMTA:
1 Enabled
[ 130 109 ]
0: No
1: Yes
IDMTA:
Enable PSx
[ * ]
0: No
1: Yes IDMTA:
Not ready
IDMTA: [ 130 117 ]
Blocking EXT
[ 130 116 ] MAIN:
Feeder mode
[ 010 135 ]
2
Parameter IDMTA:
3 Enable PSx
set 1 130 100
1: Classic single feed
set 2 131 100
2: Autotransformer feed set 3 132 100
3: Single feed w. sum I set 4 133 100 48Z9343
Fig. 3-229: Disabling, enabling and readiness in IDMTA protection. (Only IDMTA is shown; the logic, however, also
applies to IDMTB with different numerical addresses.)
IDMTA (IDMTB) function can be cancelled when the inrush stabilization function
has detected an inrush current or harmonic blocking.
IDMTA: &
Enabled
[ 130 109 ]
IDMTA:
Not ready
[ 130 117 ]
MAIN:
Protection active
306 001
IDMTA:
c Iref PSx
[ * ]
c
1.05 Iref
IDMTA:
I̲A Starting Iref>
&
[ 130 110 ]
IDMTA:
Block. tIref> EXT
[ 130 108 ]
MAIN:
Inrush stabil. trigg
306 014
IDMTA: Setting
Characteristic PSx
MAIN: IDMTA:
Harm. blk. trigg [ * ] Characteristic PSx
460 649
c
c
Φ IDMTA:
Memory clear
[ 130 115 ]
I/Iref IDMTA:
Hold time running
[ 130 114 ]
IDMTA:
IDMTA: IDMTA: IDMTA: tIref> elapsed
Parameter Iref PSx Characteristic PSx Char. factor kt PSx [ 130 112 ]
IDMTA:
set 1 130 101 130 102 130 103 Trip signal tIref>
set 2 131 101 131 102 131 103 [ 130 113 ]
set 3 132 101 132 102 132 103
set 4 133 101 133 102 133 103
DFRST:
General enable USER
[ 019 096 ]
0: No
1: Yes
DFRST:
Enable PSx
[*]
DFRST:
Enabled
0 [ 041 203 ]
1
Parameter DFRST:
0: No Enable PSx
1: Yes set 1 019 130
set 2 019 131
set 3 019 132
set 4 019 133
48Z5058A
Operating zone
Blocking zone
48Z5066A
DFRST:
General enable USER
[ 019 096 ]
1 DFRST:
Enabled
[ 041 203 ]
0: No
1: Yes
c
MAIN:
Inom C.T. prim.
[ 010 001 ]
MAIN:
Iplaus/Idfrst,CTprim
[ 010 016 ]
SFMON:
Match.fact.DFRSTinv.
COMP [ 098 033 ]
DFRST:
Mismatch
[ 041 207 ]
DFRST:
Scaling factor
[ 004 203 ]
DFRST:
Blocking t EXT
[ 041 206 ]
c
DFRST:
Id> PSx
[*]
DFRST:
DFRST: c t PSx
m1 PSx [*]
[*]
I̲
DFRST:
Trip signal
I̲plaus/I̲dfrst [ 041 205 ]
DFRST:
Starting
[ 041 204 ]
THERM:
General enable USER
[ 022 050 ]
0
THERM:
1 & Enabled
[ 040 068 ]
0: No
1: Yes
THERM:
Enable PSx
[ * ]
0: No
1: Yes y PSU: Parameter THERM:
PS y active Enable PSx
19Z6112B
THERM:
Control v. user EXT
[ 038 169 ] THERM:
Control via USER
[ 022 009 ]
>1
0
1
0: No
1: Yes
THERM:
Number PL USER
[ 022 062 ]
THERM:
& >1 1 PL active
1 [ 039 070 ]
& >1
2 THERM:
& >1 2 PL active
3
[ 039 072 ]
1: 1 par. line
THERM:
2: 2 par. lines 3 PL active
& [ 039 074 ]
3: 3 par. lines
THERM: THERM:
Select 2 PL EXT 2 PL select. extern.
[ 038 072 ] [ 038 073 ]
THERM: THERM:
Select 3 PL EXT 3 PL select. extern.
[ 038 074 ] [ 038 075 ]
c1
c2
c3
THERM:
Iref PSx
[ * ]
THERM:
Factor 2 PL PSx
[ * ]
THERM:
Factor 3 PL PSx
[ * ]
Iref 1
c2PL · Iref 2
c3PL · Iref 3
Parameter THERM: THERM: THERM:
Iref PSx Factor 2 PL PSx Factor 3 PL PSx
THERM:
set 1 072 179 072 173 072 174 cPL · Iref
set 2 073 179 073 173 073 174 305 203
THERM:
Select CTA PSx
[ * ]
2
& THERM:
With CTA
0: Default temp. value 305 201
1: From PT100
2: From 20 mA input
MEASI: &
Open circ. PT100
[ 040 190 ]
&
MEASI:
Overload 20mA input
[ 040 191 ]
MEASI: THERM:
Open circ. 20mA inp. CTA error
[ 040 192 ] [ 039 111 ]
THERM:
CTA error EXT
[ 038 062 ]
SFMON:
THERM: CTA error
Funct.f.CTA fail.PSx
[ 098 034 ]
[ * ]
2
& THERM:
Block. by CTA error
3 305 200
THERM: THERM:
Parameter Select CTA PSx Funct.f.CTA fail.PSx
The maximum permitted coolant temperature Θc,max is derived from the difference
between the T H E R M : M a x . p e r m . o b j . t m p . P S x and T H E R M : O / T f . I r e f p e r s .
P S x settings.
Θ/%
10000
1000
τ / min
100
200
10 110 1000
50
t / min
1
200
110
30
50
0.1
200
110
0.01
50 1
0.001
0 1 2 3 4 5 6 7 8 9 10 11
I / I ref
D5Z50BEB_EN
Fig. 3-237: Tripping characteristics of thermal overload protection (tripping characteristics apply to ΔϑP = 0 % and
identical settings for the maximum permissible coolant temperature and coolant temperature).
The Δϑtrip tripping threshold is set to a fixed value of 100% if the operating mode
is Absolute replica.
3.35.11 Trip
THERM:
I
305 202
MAIN:
Protection active & c
306 001
THERM:
Enabled
[ 040 068 ]
THERM:
Starting k*Iref>
THERM: [ 041 108 ]
Block Replica EXT
[ 041 074 ]
THERM:
Block. by CTA error &
305 200
THERM:
Iref PSx c
[ * ] <0.1 Iref
THERM:
THERM: Tim.const.1,>Ibl PSx
Start.fact.OL_RC PSx c [ * ]
[ * ]
THERM:
c Tim.const.2,<Ibl PSx
k·Iref [ * ]
THERM:
c Max.perm.obj.tmp.PSx
THERM: [ * ]
Absolute replica
[ 022 065 ] THERM:
c Max.perm.cool.tmpPSx
[ * ]
0 THERM: THERM:
c Rel. O/T warning PSx Within pre-trip time
[ * ]
1 [ 041 109 ]
THERM:
0: No Rel. O/T trip PSx SFMON:
c [ * ] Setting error THERM
1: Yes [ 098 035 ]
THERM:
c Default CTA PSx THERM:
[ * ] Setting error,block.
THERM: THERM: [ 039 110 ]
Relative replica Hysteresis trip PSx THERM:
[ 022 064 ] [ * ] Warning
THERM: [ 039 025 ]
0 Warning pre-trip PSx THERM:
[ * ] Trip signal
1 [ 039 020 ]
THERM:
0: No Buffer empty
1: Yes [ 039 112 ]
THERM:
THERM: Status therm.replica
With CTA c [ 004 016 ]
305 201
R THERM:
Coolant temperature I/Iref Object temperature
[ 004 137 ]
THERM: THERM:
Reset replica Coolant temperature
[ 039 061 ] [ 004 149 ]
c THERM:
Pre-trip time left
[ 004 139 ]
THERM:
Temp. offset replica
[ 004 109 ]
THERM:
Coolant temp. p.u.
Parameter THERM: THERM: THERM:
Iref PSx Start.fact.OL_RC PSx Tim.const.1,>Ibl PSx [ 004 178 ]
THERM:
set 1 072 179 072 180 072 187 Object temp. p.u.
set 2 073 179 073 180 073 187 [ 004 179 ]
set 3 074 179 074 180 074 187 THERM:
set 4 075 179 075 180 075 187 Therm. replica p.u.
[ 004 017 ]
Parameter THERM: THERM: THERM:
Tim.const.2,<Ibl PSx Max.perm.obj.tmp.PSx Current I,therm prim
set 1 072 188 072 182 [ 007 220 ]
set 2 073 188 073 182 THERM:
Current I,therm p.u
set 3 074 188 074 182
[ 007 221 ]
set 4 075 188 075 182
set 1 072 185 072 184 072 181 072 186 072 183 072 191
set 2 073 185 073 184 073 181 073 186 073 183 073 191
set 3 074 185 074 184 074 181 074 186 074 183 074 191
set 4 075 185 075 184 075 181 075 186 075 183 075 191 48Z9340A
The trip threshold is set according to the selected operating mode with the
following parameters:
● Relative replica: TH ERM: R el. O/T tr ip P Sx
● Absolute replica: TH ERM: Max. pe rm.obj. tmp.PSx
If a trip command is issued, the trip signal is maintained until the status of the
thermal replica has decreased by the value set at THERM: Hystere sis t rip
PSx, at least for a fixed time of 5 s.
3.35.12 Cooling
If the current falls below the default threshold of 0.1 Iref, the thermal replica is
applied with the time constant set at TH ER M: Tim .const.2,<Ibl PSx. This
element in the thermal model takes account of the cooling characteristics of
stopped motors.
3.35.13 Resetting
The thermal replica may be reset either via a setting parameter or via an
appropriately configured binary signal input. Resetting is possible even when
thermal overload protection is disabled. Thermal overload protection can be
blocked via an appropriately configured binary signal input.
THERM:
Reset replica USER
[ 022 061 ]
0
THERM:
1 Reset replica
[ 039 061 ]
0: don't execute
1: execute
THERM:
Enabled
[ 040 068 ]
THERM:
Reset replica EXT
[ 038 061 ]
Q9Z5020A
V<>:
General enable USER
[ 023 030 ]
0
1
0: No
1: Yes
V<>:
Enable PSx
[ * ] V<>:
&
Enabled
0 [ 040 066 ]
1
0: No
1: Yes & V<>:
Ready
MCMON: [ 042 003 ]
Meas. circ. V faulty
[ 038 023 ]
MAIN: V<>:
M.c.b. trip V EXT Not ready
[ 004 061 ] [ 042 004 ]
Parameter V<>:
Enable PSx
V<>:
Blocking tV> EXT
[ 041 068 ]
V<>:
Ready
[ 042 003 ] V<>:
MAIN: Hyst. V<> meas. PSx
Protection active [ * ]
306 001
V<>: V<>:
V> PSx tV> PSx
[ * ] [ * ]
V<>:
V̲ tV> elapsed
[ 041 034 ]
V<>:
Starting V>
[ 041 030 ]
V<>: V<>:
Blocking tV>> EXT V> PSx
[ 041 069 ] [ * ]
V<>: V<>:
V>> PSx tV>> PSx
[ * ] [ * ]
V<>:
tV>> elapsed
[ 041 035 ]
V<>:
Starting V>>
Parameter V<>: V<>: V<>: V<>: V<>: [ 041 096 ]
V> PSx tV> PSx V>> PSx tV>> PSx Hyst. V<> meas. PSx
set 1 076 003 076 005 076 004 076 006 076 048
set 2 077 003 077 005 077 004 077 006 077 048
set 3 078 003 078 005 078 004 078 006 078 048
set 4 079 003 079 005 079 004 079 006 079 048 48Z9338A
V<>:
Blocking tV< EXT
[ 041 070 ]
V<>:
Ready
[ 042 003 ]
MAIN:
Protection active
306 001
V<>: V<>:
V< PSx tV< PSx
V<>:
V> PSx [ * ] [ * ]
[ * ]
V<>:
tV< elapsed
V̲
[ 041 041 ]
V<>:
tV< elapsed & Vmin
[ 041 026 ]
V<>:
V<< PSx
IDMT:
[ * ] Dir. meas. blocked
[ 041 006 ]
V<>:
tV<< elapsed
[ 041 042 ]
Setting(s) blocked
IDMT:
Fault backward
[ 041 009 ]
V<>: 1 V<>:
Vmin PSx Fault V<<
[ * ] [ 041 112 ]
V<>:
tTransient PSx
[ * ]
V<>:
tV< elaps. transient
1 [ 042 023 ]
V<>:
tV<< elapsed trans.
1 [ 042 025]
1 V<>:
tV</<< elaps. trans.
[ 042 007]
Parameter V<>: V<>: V<>:
V< PSx tV< PSx Vmin PSx
set 1 076 007 076 009 076 046
set 2 077 007 077 009 077 046
set 3 078 007 078 009 078 046
set 4 079 007 079 009 079 046
f<>:
General enable USER
[ 023 031 ]
1 f<>:
& Enabled
[ 042 100 ]
0: No
1: Yes
f<>:
Enable PSx
[ * ]
f<>:
1 Not ready
0
[ 042 140 ]
1
f<>:
0: No & Ready
1: Yes [ 042 101 ]
f<>:
Blocked by V<
[ 042 102 ]
f<>:
Parameter Enable PSx
f<
Δf
Δt Δt
t
Start Δt Start Δt
Function blocked
Trip Δf/Δt
F5Z0128C
sense to take the mean value of the frequency gradient into account for load-
shedding systems.
In this operating mode of over-/underfrequency protection, frequency monitoring
must be set for “underfrequency monitoring”.
Monitoring the mean value of the frequency gradient is started with the starting
of frequency monitoring. If the frequency decreases by the set value Δf within
the set time Δt, then the Δf/Δt monitoring function operates instantaneously and
generates a trip signal. If a frequency change does not lead to an operate
decision of the monitoring function, then the Δf/Δt monitoring function will be
blocked until the underfrequency monitoring function drops out. The trip signal
can be blocked by way of an appropriately configured binary signal input.
f<>:
Blocking f1 EXT
[ 042 103 ]
f<>:
Oper. mode f1 PSx
[ * ]
1: f
2: f with df/dt
f<>:
f1 PSx
3: f w. Delta f/Delta t [ * ]
MAIN:
Nominal frequ. fnom
[ 010 030 ]
f<>:
f<>: tf1 PSx
Ready [ * ]
[ 042 101 ]
MAIN:
Protection active
306 001
f<>:
f<>: Trip signal f1
Blocked by V< [ 042 111 ]
[ 042 102 ]
MAIN:
M.c.b. trip V EXT
[ 004 061 ]
f<>:
Starting f1
[ 042 107 ]
f<>:
df1/dt PSx
[ * ]
f<>:
No. periods reached
305 701
f<>:
fMeas df/dt
305 726
f<>:
Start. cond. met Starting f1/df1
[ 042 108 ]
SFMON:
f> Setting error f<>
f<>: [ 098 028 ]
Delta f1 PSx
[ * ]
f<>:
Delta t1 PSx
[ * ]
df/dt
f<>:
Delta f1 triggered
[ 042 109 ]
Start. cond. met
f<>:
Delta t1 elapsed
[ 042 110 ]
47Z0152A
CBF:
General enable USER
[ 022 100 ]
0
CBF:
1 Enabled
[ 040 055 ]
0: No
1: Yes
CBF:
Enable PSx
[ * ]
Parameter CBF:
Enable PSx
0
set 1 072 110
1 set 2 073 110
set 3 074 110
0: No set 4 075 110
1: Yes
48Z5061A
MAIN: CBF:
Protection active Not ready
306 001 [ 040 025 ]
CBF:
Enabled
[ 040 055 ]
CBF:
Blocking EXT
[ 038 058 ]
48Z5062A
CBF:
Imin< PSx
[ * ]
f0
I̲
CBF: c
Not ready
[ 040 025 ]
CBF: CBF:
Mon. time M-trip PSx R-trip signal
[ 039 022 ]
[ * ]
& CBF:
Failure M-trip
MAIN: >1 t 0 [ 039 021 ]
M-trip command 1
[ 039 011 ] CBF:
&
MAIN: Mon. t. M-trip runn.
M-trip command 2 [ 036 066 ]
[ 039 058 ]
>1 CBF:
MAIN: CB failure
Parallel trip EXT [ 036 017 ]
[ 037 019 ]
c CBF:
CB1 failure
[ 036 075 ]
CBF: CBF:
Mon. time R-trip PSx B-trip signal
[ * ] [ 039 023 ]
& CBF:
Failure R-trip
t 0 [ 036 056 ]
& CBF:
Mon. t. R-trip runn.
[ 036 110 ]
CBF:
tImin< PSx
[ * ]
&
CBF:
CB Superv. Signal
[ 039 000 ]
MAIN: t 0
CB closed A EXT
[ 036 051 ]
CBF:
Operative time PSx
[ * ]
Fig. 3-248: CB failure protection and CB monitoring, operating mode is set to classic single feed.
stage. If the monitored current exceeds CBF: Imi n< PSx, then a CBF : C B
Supe rv. Signal alarm results.
The auxiliary contact supervision is only active for the set operative time. This
ensures that a C BF: CB Supe rv. Signal signal (which might lead to switching
off the entire installation) will not be issued during protection injection testing.
Following figure shows the function with one circuit breaker. The measured
current I is evaluated internally by the functions when the parameter
MAIN : Feeder mode has been set to the operating mode classic single feed.
CBF:
Imin< PSx
[ * ]
f0
I̲A >1
f0
I̲B
CBF: c
Not ready
[ 040 025 ]
CBF: CBF:
Mon. time M-trip PSx R-trip signal
[ 039 022 ]
[ * ]
& CBF:
Failure M-trip
MAIN: >1 t 0 [ 039 021 ]
M-trip command 1
[ 039 011 ] & CBF:
MAIN: Mon. t. M-trip runn.
M-trip command 2 [ 036 066 ]
[ 039 058 ]
MAIN: >1
Parallel trip EXT
[ 037 019 ]
c
CBF: CBF:
Mon. time R-trip PSx B-trip signal
[ 039 023 ]
[ * ]
& CBF:
Failure R-trip
t 0 [ 036 056 ]
& CBF:
Mon. t. R-trip runn.
[ 036 110 ]
CBF:
Operative time PSx
[ * ]
>1 CBF:
CB Superv. Signal
[ 039 000 ]
Fig. 3-249: CB failure protection and CB monitoring, operating mode is set to either autotransformer feed or classic
single feed with residual current measurement.
Above figure shows the function with two circuit breakers. The measured
currents IA (catenary 1) and IB (catenary 2 or feeder) are evaluated internally by
the functions when the parameter MA IN: Fe eder mode has been set to the
following operating modes:
● Autotransformer feed
● Classic single feed with residual current measurement (Single feed w. sum
I)
CBM:
General enable USER
[ 022 010 ]
0
CBM:
1 Enabled
[ 044 130 ]
0: No
1: Yes
48Z5404A
3.39.2 Variants
The wear condition of a circuit breaker may be determined using a variety of
methods:
● Monitoring the mechanical switching operations
● Accumulating ruptured current values
● Accumulating the squared ruptured current values
● Calculating the current-time integral of ruptured and accumulated current
values
● Calculating the remaining switching operations with reference to the CB
wear characteristic.
100000
Number of permissible CB operations
10000
1000
100
10
0.1 1 10 100
Disconnection current in kA 19Z6123A_EN
The knee points in Fig. 3-251, (p. 3-308) are necessary to set the wear
characteristic for the circuit breaker:
● The circuit breaker's nominal current (CBM: Inom,CB) and the permitted
number of CB operations at nominal current (CBM: Perm. CB op.
Inom,C B)
● The circuit breaker's mean ruptured current (CBM: Med. curr. Itrip ,CB)
and the permitted number of CB operations at mean ruptured current
(CBM: Pe rm. C B op. Im e d,C B)
● The circuit breaker's maximum ruptured current (CBM: Max. curr.
I trip,C B) and the permitted number of CB operations at maximum
ruptured current (CBM: Pe rm. CB op. Imax,CB)
The mean ruptured current is not available for all types of circuit breakers.
In such a case the parameters for this knee point are to be set to Blocked. A knee
point is not considered in the characteristic when at least one of the parameters
for the knee point is set to Blocked.
For proper performance of circuit breaker monitoring it should be observed that
the knee points must be applied in a logically correct sequence (continuously
descending). When set currents and numbers of CB operations are not plausible
according to the characteristic the P438 will issue an error message and block
circuit breaker monitoring.
Where:
● Inom,CB: Nominal current for the CB
● n(Inom,CB): Max permitted number of CB operations at Inom,CB
● Id,CB: Ruptured current
● n(Id,CB): Permitted number of CB operations at Id,CB according to wear
characteristics
● nrem,0(Inom,CB): Remaining permitted number of CB operations at Inom,CB
before disconnection
● nrem,(Inom,CB): Remaining permitted number of CB operations at Inom,CB after
disconnection
MAIN: & c
Protection active
306 001
CBM:
Enabled CBM:
[ 044 130 ] Operating mode
[ 022 007 ]
CBM: c
Blocked
[ 044 199 ]
CBM:
& >1 c Inom,CB
[ 022 012 ]
MAIN: >1
M-trip signal 1 CBM:
[ 039 101 ]
& c Perm. CB op. Inom,CB
MAIN: [ 022 013 ]
M-trip signal 2
[ 039 102 ] CBM:
c Med. curr. Itrip,CB
MAIN: [ 022 014 ]
R-trip signal 1 &
[ 039 103 ] CBM:
MAIN: c Perm. CB op. Imed,CB
R-trip signal 2 [ 022 015 ]
[ 039 104 ] >1
CBM:
MAIN: c Max. curr. Itrip,CB
CB open A EXT [ 022 016 ]
[ 044 131 ] CBM:
c Perm. CB op. Imax,CB
[ 022 017 ]
CBM:
c Corr. Acqu.t.CB sig.
[ 022 018 ]
fnom CBM:
No. of CB oper. A
I̲ [ 008 011 ]
CBM:
Remain. No. CB op. A
[ 008 014 ]
48Z9372A
Fig. 3-252: Triggering and calculation of CB condition monitoring, operating mode is set to classic single feed.
MAIN: & c
Protection active
306 001
CBM:
Enabled CBM:
[ 044 130 ] Operating mode
[ 022 007 ]
CBM: c
Blocked
[ 044 199 ]
CBM:
& >1 c Inom,CB
[ 022 012 ]
MAIN: >1
M-trip signal 1 CBM:
[ 039 101 ]
& c Perm. CB op. Inom,CB
MAIN: [ 022 013 ]
M-trip signal 2
[ 039 102 ] CBM:
c Med. curr. Itrip,CB
MAIN: [ 022 014 ]
R-trip signal 1 &
[ 039 103 ] CBM:
MAIN: c Perm. CB op. Imed,CB
R-trip signal 2 [ 022 015 ]
[ 039 104 ] >1
CBM:
MAIN: c Max. curr. Itrip,CB
CB open A EXT [ 022 016 ]
[ 044 131 ] CBM:
c Perm. CB op. Imax,CB
[ 022 017 ]
CBM:
c Corr. Acqu.t.CB sig.
[ 022 018 ]
fnom CBM:
No. of CB oper. A
I̲A [ 008 011 ]
CBM:
Remain. No. CB op. A
[ 008 014 ]
fnom CBM:
No. of CB oper. B
I̲B [ 008 012 ]
CBM:
Remain. No. CB op. B
[ 008 015 ]
48Z9373A
Fig. 3-253: Triggering and calculation of CB condition monitoring, operating mode is set to either autotransformer
feed or classic single feed with residual current measurement.
Setting the parameter CB M: Operati ng m ode will select the condition under
which the function will be triggered:
● With trip cmd. only: Function triggered only by the general trip command
● With CB sig.EXT only: Function triggered by the CB open signal generated
by an auxiliary contact
● CB sig. EXT or trip: Function triggered by the general trip command or CB
open signal generated by an auxiliary contact
Measured values and counters are re-determined with each triggering and
compared with set threshold values.
A correction value for the CB open time can be set in order to determine the
exact trip time C BM: Corr. A cqu. t.C B si g.. This permits proper evaluation of
leading or lagging auxiliary contacts.
The triggering and calculation of CB condition monitoring are shown in the above
figures when parameter MA IN: Feeder mode has been set to one of these
operating modes:
● Classic single feed: please refer to Fig. 3-252, (p. 3-310)
● Autotransformer feed or classic single feed with residual current
measurement (Single feed w. sum I): please refer to Fig. 3-253, (p. 3-311)
CBM:
c No. CB operations >
[ 022 019 ]
CBM:
No. of CB oper. B
[ 008 012 ]
46Z5036A
At the same time each switching operation will increment the P438's counter for
the number of CB operations. The number of CB operations performed is
displayed. A threshold value can be set with the parameter CBM: No. C B
ope rat ions >. An alarm is issued should the number of CB operations
performed exceed this threshold.
CBM:
c Remain No. CB op. <
[ 022 020 ]
CBM:
Remain. No. CB op. B
[ 008 015 ]
46Z5037A
CBM: CBM:
General enable USER Blocked
[ 044 199 ]
[ 022 010 ]
&
CBM:
Blocking EXT
[ 044 128 ]
CBM:
Blocking USER
[ 022 150 ]
0: No
1: Yes
48Z5346B
Only such measured values and counter values in the P438 may be set to new
values that do not have their default values set to Blocked.
The stored value will remain unchanged if the default value is set to Blocked.
Executing the set command results in initializing all default values in the P438 to
Blocked.
LIMIT:
General enable USER
[ 014 010 ]
0: No
1: Yes
LIMIT:
Enable PSx
[*]
LIMIT:
Enabled
[ 040 074 ]
0: No
1: Yes
Parameter LIMIT:
Enable PSx
set 1 072 240
set 2 073 240
set 3 074 240
set 4 075 240
48Z5405A
LIMIT:
Enabled LIMIT: LIMIT:
[ 040 074 ] I> PSx tI> PSx
[*] [*]
MAIN:
Protection active
306 001
I̲ LIMIT:
tI> elapsed
[ 004 062 ]
LIMIT: LIMIT:
I>> PSx tI>> PSx
[*] [*]
LIMIT:
tI>> elapsed
[ 040 157 ]
LIMIT:
Enabled LIMIT: LIMIT:
[ 040 074 ] IA> PSx tIA> PSx
[*] [*]
MAIN:
Protection active
306 001
I̲A LIMIT:
tIA> elapsed
[ 040 232 ]
LIMIT: LIMIT:
IA>> PSx tIA>> PSx
[*] [*]
LIMIT:
tIA>> elapsed
[ 040 233 ]
LIMIT: LIMIT:
IB> PSx tIB> PSx
[*] [*]
I̲B LIMIT:
tIB> elapsed
[ 040 234 ]
LIMIT: LIMIT:
IB>> PSx tIB>> PSx
[*] [*]
LIMIT:
tIB>> elapsed
[ 040 235 ]
The catenary and feeder currents are monitored by two stages to determine
whether they exceed set thresholds. If any of the thresholds are exceeded a
signal is issued after a set time-delay has elapsed.
LIMIT:
Enabled LIMIT: LIMIT:
[ 040 074 ] Iplaus/Idfrst> PSx tIplaus/Idfrst> PSx
[*] [*]
MAIN:
Protection active
306 001
I̲plaus/I̲dfrst LIMIT:
tIplaus/Idfrst> elps
[ 040 236 ]
LIMIT: LIMIT:
Iplaus/Idfrst>> PSx tIplaus/Idfrst> PSx
[*] [*]
LIMIT:
tIplaus/Idfrst>>elps
[ 040 237 ]
MAIN:
Protection active
306 001
V̲ LIMIT:
tV> elapsed
[ 040 140 ]
LIMIT:
tV> & tV< elapsed
LIMIT: LIMIT: [ 040 144 ]
V>> PSx tV>> PSx
[*] [*]
LIMIT:
tV>> elapsed
[ 040 141 ]
LIMIT: LIMIT:
V< PSx tV< PSx
[*] [*]
LIMIT:
tV< elapsed
[ 040 142 ]
LIMIT:
tV>>&tV<< elapsed
LIMIT: LIMIT: [ 040 145 ]
V<< PSx tV<< PSx
[*] [*]
LIMIT:
tV<< elapsed
[ 040 143 ]
48Z5407A
V̲A LIMIT:
tVA> elapsed
[ 040 240 ]
LIMIT: LIMIT:
VB> PSx tVB> PSx
[*] [*]
V̲B/V̲ref LIMIT:
tVB> elapsed
[ 040 246 ]
48Z5408A
The catenary and feeder voltages are monitored by two stages to determine
whether they exceed set thresholds. If any of the thresholds are exceeded a
signal is issued after a set time-delay has elapsed.
MAIN:
Protection active
306 001
f LIMIT:
tf> elapsed
[ 040 196 ]
LIMIT: LIMIT:
f>> PSx tf>> PSx
[*] [*]
LIMIT:
tf>> elapsed
[ 040 197 ]
LIMIT: LIMIT:
f< PSx tf< PSx
[*] [*]
LIMIT:
tf< elapsed
[ 040 198 ]
LIMIT: LIMIT:
f<< PSx tf<< PSx
[*] [*]
LIMIT:
tf<< elapsed
[ 040 199 ]
48Z5418A
LIMIT:
Starting IDC,lin>
[ 040 180 ]
LIMIT:
Enabled LIMIT: LIMIT:
[ 040 074 ] IDC,lin> tIDC,lin>
[ 014 110 ] [ 014 112 ]
MAIN:
Protection active
306 001
MEASI: LIMIT:
Curr. IDC,lin. p.u. tIDC,lin> elapsed
[ 004 136 ] [ 040 182 ]
LIMIT:
Starting IDC,lin>>
[ 040 181 ]
LIMIT: LIMIT:
IDC,lin>> tIDC,lin>>
[ 014 111 ] [ 014 113 ]
LIMIT:
tIDC,lin>> elapsed
[ 040 183 ]
LIMIT:
Starting IDC,lin<
[ 040 184 ]
LIMIT: LIMIT:
IDC,lin< tIDC,lin<
[ 014 114 ] [ 014 116 ]
LIMIT:
tIDC,lin< elapsed
[ 040 186 ]
LIMIT:
Starting IDC,lin<<
[ 040 185 ]
LIMIT: LIMIT:
IDC,lin<< tIDC,lin<<
[ 014 115 ] [ 014 117 ]
LIMIT:
tIDC,lin<< elapsed
[ 040 187 ]
S8Z52G6A
The direct current, linearized by the analog measured data input, is monitored by
two stages to determine if it exceeds or falls below set thresholds. If any of the
measured values exceed or fall below the corresponding upper or lower limit
values then a signal is issued after the associated time period has elapsed.
LIMIT:
Starting T>
[ 040 170 ]
LIMIT:
Enabled
[ 040 074 ] LIMIT: LIMIT:
T> tT>
[ 014 100 ] [ 014 103 ]
MAIN:
Protection active
306 001
MEASI: LIMIT:
Temperature T tT> elapsed
[ 004 133 ] [ 040 172 ]
LIMIT:
Starting T>>
[ 040 171 ]
LIMIT: LIMIT:
T>> tT>>
[ 014 101 ] [ 014 104 ]
LIMIT:
tT>> elapsed
[ 040 173 ]
LIMIT:
Starting T<
[ 040 174 ]
LIMIT: LIMIT:
T< tT<
[ 014 105 ] [ 014 107 ]
LIMIT:
tT< elapsed
[ 040 176 ]
LIMIT:
Starting T<<
[ 040 175 ]
LIMIT: LIMIT:
T<< tT<<
[ 014 106 ] [ 014 108 ]
LIMIT:
tT<< elapsed
[ 040 177 ]
19Z5212A
Binary signals in the P438 may be linked by logical “OR” or “AND” operations
with the option of additional NOT operations by setting L OGIC: Fct.assignm.
outp. 1 (or LOGIC : F ct.as s ignm . outp. 2 to L OGIC : Fct.assignm.outp.
128, or LOG_2 : F ct .as si gnm. ou tp. 1 to L OG_2: Fct.assignm. out p. 4).
The Boolean equations need to be defined without the use of brackets. The
following rule applies to the operators: “NOT” before “AND” before “OR”.
A maximum of 32 elements can be processed in one Boolean equation. In
addition to the signals generated by the P438, initial conditions for governing the
equations can be set using setting parameters, through binary signal inputs, or
through the serial interfaces.
Logical operations of the function group LOGIC can be controlled through the
binary signal inputs in different ways.
The binary input signals LOGI C: Inpu t 01 EXT (or LOGIC: Input 0 2 EXT, …,
LOGIC : I np ut 4 0 EXT) have an updating function, whereas the input signals
LOGIC : Set 1 EXT (or LOGI C: Set 2 E XT, …, LOGIC: Set 8 EXT) are
latched. The logic can only be controlled from the binary signal inputs configured
for LOGIC : Se t 1 E XT if the corresponding reset input LOGIC: Reset 1 EX T)
has been configured for a binary signal input. If only one or neither of the two
functions is configured, then this is interpreted as “Logic externally set”. If the
input signals of the two binary signal inputs are implausible (such as when they
both have a logic value of “1”), then the last plausible state remains stored in
memory. (For LOG_2, there are no such parameters for assigning binary input
signals.)
WARNING
HAZARD OF UNINTENDED EQUIPMENT OPERATION
⚫ When using the programmable logic, it is necessary to carry out a
functional type test to conform with the requirements of the relevant
protection/control application. In particular, it is necessary to verify that
the requirements for the implementation of logic linking (by setting) as
well as the time performance during startup of the P438, during operation
and when there is a fault (blocking of the P438) are fulfilled.
Failure to follow these instructions can result in unintended
equipment operation.
LOGIC:
Set 1 USER
[ 034 030 ]
0
LOGIC:
1 1 has been set
[ 034 067 ]
0: No
1: Yes
INP:
Fct. assignm. U xxx
[ xxx xxx ]
U x1
U x2
U x3
U xx
LOGIC:
Address 034 051 1 set externally
[ 034 075 ]
Address 034 059
LOGIC:
Set 1 EXT
[ 034 051 ]
LOGIC:
Reset 1 EXT
[ 034 059 ]
49Z9107A
Fig. 3-266: Control of logic operations via setting parameters or stored input signals. (The logic does not apply to
LOG_2.)
LOGIC:
General enable USER
LOGIC:
[ 031 099 ] Enabled
[ 034 046 ]
0: No
1: Yes
MAIN: LOGIC:
Protection active Fct.assignm. outp. 1
306 001
[ 030 000 ]
Signal 1
Signal 2
Signal 3
Signal n
LOGIC: LOGIC:
Input 01 EXT Op. mode t output 1
[ 034 000 ] [ 030 001 ]
0
LOGIC:
Input 16 EXT
[ 034 015 ] 1
2
3
LOGIC:
1 has been set 4
[ 034 067 ]
5
0 5
LOGIC:
8 has been set
[ 034 074 ] 0: Without timer stage
LOGIC:
Time t1 output 1
1: Oper./releas.delay
[ 030 002 ]
2: Oper.del./puls.dur.
LOGIC: LOGIC:
1 set externally Time t2 output 1
[ 034 075 ] 3: Op./rel.delay,retrig
[ 030 003 ]
4: Op.del./puls.dur.,rt
5: Minimum time
LOGIC:
8 set externally LOGIC:
[ 034 082 ] Output 01 (t)
[ 042 033 ]
LOGIC:
Set 1 USER
[ 034 030 ]
LOGIC:
Set 8 USER
[ 034 037 ]
LOGIC:
Trigger 1
[ 034 038 ]
0
LOGIC:
1 Output 01
[ 042 032 ]
0: don't execute
1: execute
LOGIC:
Trigger 8
[ 034 045 ]
1
0: don't execute
1: execute
D5Z52CDA
Fig. 3-267: Setting options for programmable logic, function group LOGIC (shown here for output 1).
LOG_2:
General enable USER
LOG_2:
[ 011 137 ] Enabled
[ 011 138 ]
0: No
1: Yes LOG_2:
Op. mode t output 1
[ 050 001 ]
MAIN: LOG_2:
Protection active Fct.assignm. outp. 1
306 001 [ 050 000 ] 0
1
Signal 1 2
3
Signal 2
4
Signal 3 5
0 5
Signal n
0: Without timer stage
LOG_2:
1: Oper./releas.delay Time t1 output 1
2: Oper.del./puls.dur. [ 050 002 ]
3: Op./rel.delay,retrig
LOG_2:
4: Op.del./puls.dur.,rt Time t2 output 1
5: Minimum time [ 050 003 ]
LOG_2:
Output 1 (t)
[ 052 033 ]
LOG_2:
Output 1
[ 052 032 ]
19Z80CDA
Fig. 3-268: Setting options for programmable logic, function group LOG_2 (shown here for output 1).
The output signal of an equation can be fed into a further, higher order, equation
as an input signal thus creating a sequence of interlinked Boolean equations. The
equations are processed in the sequence defined by the order of each equation.
It should be noted that in the case of overlapping equations, the result is
provided by the equation with the highest order.
The output signal of each equation is fed to a separate timer stage with two
timer elements and a choice of operating modes. This offers the possibility of
assigning a freely configurable time characteristic to the output signal of each
Boolean equation. In the Minimum time operating mode, the setting of timer
stage t2 has no effect. The following diagrams (Fig. 3-269, (p. 3-328) to
Fig. 3-273, (p. 3-330)) show the time characteristics for the various timer stage
operating modes.
If the P438 is switched to offline the equations are not processed and all outputs
are set to the “0” logic level.
t2 = 0s
LOGIC:
Output n
LOGIC:
Output n (t)
t1 t1
t1 = 0s
LOGIC:
Output n
LOGIC:
Output n (t) t2 t2
t1, t2 > 0s
LOGIC:
Output n
LOGIC:
Output n (t)
t1 t2 t1 t2
D5Z50BYA
Fig. 3-269: Operating mode 1: Pickup/reset delay (Oper./releas.delay). (This diagram is also valid for LOG_2, if the
signal parameters are replaced by the corresponding ones from LOG_2 .)
t2 = 0s
LOGIC:
Output n
LOGIC:
Output n (t)
t1 t1
t1 = 0s
LOGIC:
Output n
LOGIC:
Output n (t) t2 t2
t1, t2 > 0s
LOGIC:
Output n
LOGIC:
Output n (t)
t1 t2 t1 t2
D5Z50BZA
Fig. 3-270: Operating mode 2: Pulse, delayed pickup (Oper.del./puls.dur.). (This diagram is also valid for LOG_2, if
the signal parameters are replaced by the corresponding ones from LOG_2 .)
t2 = 0s
LOGIC:
Output n
LOGIC:
Output n (t)
t1 t1
Retrigger pulse
t1 = 0s
LOGIC:
Output n
LOGIC:
Output n (t)
t2 t2
t2
Retrigger pulse
t1, t2 > 0s
LOGIC:
Output n
LOGIC:
Output n (t)
t1 t2 t1 t2
t2
t2
D5Z50CAA
Fig. 3-271: Operating mode 3: Pickup/reset delay, retriggerable (Op./rel.delay,retrig). (This diagram is also valid for
LOG_2, if the signal parameters are replaced by the corresponding ones from LOG_2 .)
t2 = 0s
LOGIC:
Output n
LOGIC:
Output n (t)
t1 t1
t1 = 0s
LOGIC:
Output n
LOGIC:
Output n (t)
t2 t2
Retrigger pulse
t1, t2 > 0s
LOGIC:
Output n
LOGIC:
Output n (t)
t1 t2 t1 t2
t1 t1
D5Z50CBA
Fig. 3-272: Operating mode 4: Pulse, delayed pickup, retriggerable (Op.del./puls.dur.,rt). (This diagram is also valid
for LOG_2, if the signal parameters are replaced by the corresponding ones from LOG_2 .)
LOGIC:
Output n
LOGIC:
Output n (t)
t1 t1
D5Z50CCA
Fig. 3-273: Operating mode 5: Minimum time (Minimum time). (This diagram is also valid for LOG_2, if the signal
parameters are replaced by the corresponding ones from LOG_2 .)
LOGIC:
Sig.assig. outp. 1
[ 044 000 ]
Signal 1 EXT
[ AAA AAA ]
Signal 2 EXT
[ BBB BBB ]
Signal 3 EXT
[ CCC CCC ]
Signal n EXT
[ NNN NNN ]
Signal 1 EXT
Address AAA AAA
LOGIC: [ AAA AAA ]
Output 01
[ 042 032 ]
INP:
Fct. assignm. U xxx
[ xxx xxx ]
-Uxxx
LOGIC:
Sig.assig.outp. 1(t)
[ 044 001 ]
Signal 2 EXT
Address BBB BBB
[ BBB BBB ]
LOGIC:
Output 01 (t)
[ 042 033 ]
INP:
Fct. assignm. U xxx
[ xxx xxx ]
-Uxxx
D5Z52FBA
Fig. 3-274: Signal assignment to outputs of Boolean equations. (This diagram is also valid for LOG_2, if the
parameters from LOGIC are replaced by the corresponding ones from LOG_2 .)
TIMER:
Calendar 1
TIMER: c
General enable USER [ 014 178 ]
[ 014 199 ]
TIMER: m out of n
Monday
[ 014 139 ]
.
.
.
TIMER:
Sunday
[ 014 169 ]
Φ
Hardware clock
TIMER:
Start hour 1
[ 014 089 ]
TIMER:
Start minute 1
[ 014 102 ]
TIMER:
End hour 1
[ 014 109 ]
TIMER:
End minute 1
[ 014 118 ]
Φ
TIMER:
Timer stage 1
[ 015 006 ]
19Z8854A
Fig. 3-275: TIMER logic (Calendar 1 shown as an example for 4 calendar timers).
To create customized bay types, the “Bay Type Configurator” (BTC), version 2.7
or higher, is needed. Older versions of the BTC can create not compatible hex files
and thus can lead to communication failures.
The parameter – MAI N: Type of bay – can then be used to select (i. e. activate)
this user-defined bay type. Note that there is no restriction to only one user-
defined bay type: In fact, multiple customized bay types can be created with
different IDs and be loaded into the P438. When using the BTC to create a bay
type, it is recommended to always use an ID number in the range of 5000 …
9999 for any customized bay type, because the pre-defined standard bay types
use IDs in the reserved range of 0001 … 4999. If the user tries to select a non-
existing ID via (220 000) MAI N: Type of bay (i. e. an ID for which neither a
standard nor a customized bay type is defined), then the selection will be
rejected and an error message “Signal from device: Bay type not assigned
(0x8073)” will be reported in the “kommprot.txt” log file.
Once the user has selected a bay type, the P438 can automatically configure the
binary inputs and output relays with function assignments for the control of
switchgear units. This automatic assignment is defined via the parameter
MAIN : Auto-assi gn me nt I/O.
Should the required bay type be missing from the standard selection then the
user can contact the manufacturer of the P438 to request the definition of a
customized bay type to load into the P438.
MAIN:
Inp.asg. ctrl.enabl.
[ 221 057 ]
Signal 1
Signal 2
Signal 3
...
Signal n
MAIN:
Inp.asg.interl.deact
[ 221 007 ]
Selected signal
MAIN:
SI active USER
[ 221 002 ]
≥1 MAIN:
Subst. interl. act.
0 [ 221 000 ]
0: No
1: Yes
MAIN:
BI active USER
[ 221 003 ]
≥1 MAIN:
Bay interlock. act.
0 [ 221 001 ]
0: No
1: Yes
49Z88ABC
Fig. 3-276: General enable for switch commands issued by the control functions; activating or canceling the
interlocks.
Before a switching unit within the bay is closed or opened by the control
functions of the P438, the P438 first checks whether the switch command may be
executed. A switch command will be executed if the optional control enable has
been issued and the interlock conditions are met. The interlock conditions are
defined in the interlocking logic for each switching unit within the bay that is
subject to control actions and for each control direction (Open/Close). Different
conditions are defined for the bay interlock equations to operate with or without
station interlock. The check of bay or station interlock equations can be cancelled
for all electrically controllable switchgear units within a bay. If the station
interlock is active, it may be cancelled selectively for each switching unit and
each control direction.
The bay and station interlocks may be cancelled through an appropriately
configured binary signal input. This cancellation is effective for all of the
operating modes “Local”, “Remote” and “Remote & Local” (setting L OC : F ct .
assign. L /R k ey = R & L <-> L). In other words, the functionality of the binary
input for cancelling the bay and station interlocks is independent of the operating
mode of the control point for switching between local and remote control.
ILOCK:
Rset ILOCK violation
[ 221 123 ]
0 t
DEV01: ≥1 ≥1 MAIN:
Open cmd. rejection Interlock equ. viol.
⋮ [ 221 018 ]
DEVxx:
Open cmd. rejection
DEV01: ≥1
Close cmd. rejection
⋮
DEVxx:
Close cmd. rejection
19Z83ADA
Cmd start:
Internal no
Command
parameter rejected.
check OK?
yes
no
Interlocking Command
check OK? rejected.
yes
DEV01:
Inp.asg. sw.tr. plug
[ 210 014 ]
Signal 1
Signal 2
⋮
Signal n
Without function ≥1
Selected signal
DEV01:
≥1 Switch. device open
DEV01:
Gr. assign. debounc. [ 210 036 ]
[ 210 011 ] & DEV01:
Switch.device closed
≥1 [ 210 037 ]
DEV01:
=1 1 Dev. interm./flt.pos
>S [ 210 038 ]
11 &
1
>R
Selected group >S &
11
◄ >R
1
c
◄
DEV01:
Open signal EXT Φ & >S
11
[ 210 030 ] Debouncing 1
>R
&
DEV01:
Closed signal EXT Chatter suppression DEV01:
[ 210 031 ] Op.time switch. dev.
[ 210 004 ]
t 0
&
DEV01:
Stat.ind.interm.pos.
[ 210 027 ]
& ≥1
0 5s 0 &
&
1
0: No ◄
1: Yes
0
0⋯3 DEV01:
Control state
0: Intermediate pos. [ 210 018 ]
1: Open
2: Closed
3: Faulty position 19Z50AJB
Fig. 3-279: Processing Status Signals from Manually Operated Switchgear Units.
monitoring or until the contacts on the switchgear unit are back to a defined
position – either “Open” or “Closed” – the signal “Intermediate position” is
issued.
If DEV01: Int erm. pos . suppr. is set to Yes, the previous switchgear unit
status will continue to be signaled to the communication interfaces while the
switchgear unit is operating. Once the contacts on the switchgear unit have
reached their new position, the updated status is signaled accordingly to the
communication interfaces. This parameter has no impact to internal signals, such
as DEV01: Swit ch. device ope n, D EV 01: Switch.device closed or
D EV01: D ev. inte rm./f lt. pos.
The signal “Faulty position” is issued if the contacts on the switchgear unit have
not reached either their “Open” or “Closed” position after the set time period for
running time monitoring and the delay time set in MAIN: Delay
Man.Op .Supe rv. have elapsed. If DEV 01: Stat.ind.interm.pos. is set to
Yes, a delay time of 5 s is started. Once this time period has elapsed and there is
no status signal for the position, the state actually present at the binary inputs
will be signaled.
LOC:
Loc.acc.block.active
[ 221 005 ]
LOC:
Return t. illum. trg
305 550
LOC:
Return t.select. trg
305 551
MAIN:
Interlock equ. viol.
[ 221 018 ]
DEV01
DEV01:
Open request
307 000
DEV01:
Close request
307 001
MAIN:
Electrical control
[ 221 061 ]
2: Local
1: Remote
LOC:
Rem.acc.block.active
[ 221 004 ]
DEV01:
Inp.asg.el.ctrl.open
[ 210 019 ]
Signal 1
Signal 2
Signal 3
Signal n
Selected signal
DEV01:
Inp.asg.el.ctr.close
[ 210 020 ]
Selected signal
COMM1:
Open command DEV01
[ --- --- ]
COMM1:
Close command DEV01
[ --- --- ]
DEV01:
Latching time
[ 210 005 ]
DEV01:
End open command
307 002
DEV01:
End close command
307 003
MAIN:
Direct motor control
306 029
DEV01:
Latching time elaps.
MAIN:
307 012
End command
306 028
DEV01:
Latching time runn.
COMM1:
Motor rel. mon. trg. 307 011
[ --- --- ]
1) Keys, local control
19Z50AAA
DEV01:
Open request
DEV01:
Close request
DEV01:
Fct.asg.BI w/o SI op
[ 210 041 ]
ILOCK:
Output 01
[ 250 032 ]
⋮
ILOCK:
Output 32
[ 250 063 ] & DEV01:
ILOCK: Enable BI open
Output 01 & ≥1
MAIN:
Bay interlock. act. &
DEV01:
[ 221 001 ] Fct.asg.BI w/o SI cl
[ 210 042 ] & ≥1 DEV01:
Open cmd. rejection
MAIN:
Subst. interl. act. ≥1
[ 221 000 ]
MAIN:
Communication error
[ 221 019 ] & DEV01:
ILOCK: Enable BI close
Output 02 & ≥1
DEV01:
Open w/o stat.interl ≥1
[ 210 025 ]
&
↗ 1: Yes & ≥1 DEV01:
Close cmd. rejection
DEV01:
Close w/o stat. int. ≥1
[ 210 026 ]
&
↗ 1: Yes DEV01:
Fct.assig.BIwSI open
[ 210 039 ]
ILOCK:
Output 03 &
DEV01:
Fct.assig.BIwSI clos
[ 210 040 ]
ILOCK:
Output 04 &
&
&
DEV01:
Enable SI Open
DEV01:
Enable SI Close 19Z50AEB
Fig. 3-281: Assignment of the equations of the interlocking logic to the switching commands; enabling of switching
commands by the bay interlock function.
3.43.6.4 Bay Interlock for Operation with the Station Interlock Function
MAIN:
Communication error
[ 221 019 ]
DEV01:
Close request
307 001
DEV01:
Open request
307 000
MAIN:
Bay interlock. act.
[ 221 001 ]
DEV01:
Enable BI open
307 004
DEV01:
Enable BI close
307 005 COMM1:
Open request DEV01
MAIN:
[ --- --- ]
Subst. interl. act.
[ 221 000 ]
DEV01:
Open w/o stat.interl
[ 210 025 ] DEV01:
Enable SI Open
307 019
0
0: No
1: Yes
COMM1: COMM1:
Enable SI open DEV01 Close request DEV01
[ --- --- ] [ --- --- ]
DEV01:
Close w/o stat. int.
[ 210 026 ]
DEV01:
Enable SI Close
307 020
0: No
1: Yes
COMM1:
Enabl.SI close DEV01
[ --- --- ]
19Z50AFA
DEV01:
With gen. trip cmd.1
[ 210 021 ]
MAIN:
DEVxx is a C.B.
306 044
0
DEV01:
1 Protection trip cmd.
307 013
0: No
1: Yes
MAIN:
M-trip command 1
[ 039 011 ]
DEV01:
With gen. trip cmd.2
[ 210 022 ]
0: No
1: Yes
MAIN:
M-trip command 2
[ 039 058 ]
DEV01:
With close cmd./prot
[ 210 023 ]
1 DEV01:
Protect. close cmd.
307 014
0: No
1: Yes
MAIN:
Close command
[ 037 009 ]
48Z9357A
DEV01:
Protection trip cmd.
DEV01:
Protect. close cmd.
↗ MAIN:
Cmd. dur.long cmd.
[ 221 230 ]
↗ MAIN:
Cmd. dur. short cmd.
[ 221 231 ]
DEV01:
Oper. mode cmd.
[ 210 024 ]
1 & 1
t
2
& 1
t
3
1: Long command
2: Short command
3: Time control
& 1
t
& 1
t DEV01:
MAIN: ≥1 Open command
Protection enabled [ 210 028 ]
&
[ 003 030 ]
DEV01:
↗ 0: No (= off) & ≥1 Close command
& [ 210 029 ]
MAIN:
Mon. mot. drives tr.
[ 221 056 ]
MAIN:
Enable control
[ 221 058 ]
MAIN:
Bay interlock. act. ≥1
[ 221 001 ]
&
DEV01:
Enable BI open
DEV01:
Enable SI Open
DEV01:
Open cmd blocked
DEV01:
Open request
&
≥1
&
DEV01:
Enable BI close
DEV01:
Enable SI Close
DEV01:
Close cmd blocked
DEV01: & ≥1
Close request
ASC:
AC effect. for DEV01
&
ASC:
Close enable DEV01 19Z81AGB
Dependent on the operating mode (set at D EV 0 1: Ope r. mode cmd.) set for
commands, switching commands are issued for the set timer durations or
according to time control.
When the automatic synchronism check (ASC) is active and the parameter
AS C: Syst em int egrat . P Sx is set to Autom.synchr.control a “Close” request
will automatically issue a “Close” command for the circuit breaker after a close
enable was issued by the ASC.
DEV01: c
Function group DEV01
[ 210 047 ]
DEV01:
Block cmd open
[ 218 120 ]
Signal 1
Signal 2
DEV01:
Open cmd blocked
Signal n 460 513
Selected signal
DEV01:
Block cmd close
[ 218 160 ]
Signal 1
Signal 2
DEV01:
Close cmd blocked
Signal n 460 514
Selected signal
19Z8103A
DEV01:
Inp.asg. sw.tr. plug
[ 210 014 ]
Signal 1
Signal 2
⋮
Signal n
Without function ≥1
Selected signal
DEV01:
≥1 Switch. device open
DEV01:
Gr. assign. debounc. [ 210 036 ]
[ 210 011 ] & DEV01:
Switch.device closed
≥1 [ 210 037 ]
DEV01:
=1 1 Dev. interm./flt.pos
>S [ 210 038 ]
11 &
1
>R
Selected group >S &
11
◄ >R
1
≥1 DEV01:
End open command
c
≥1 DEV01:
◄ End close command
DEV01:
Open signal EXT Φ & >S
11
[ 210 030 ] Debouncing 1
>R
&
DEV01:
Closed signal EXT Chatter suppression DEV01:
[ 210 031 ] Op.time switch. dev.
[ 210 004 ]
◄ ◄
MAIN: t 0
Direct motor control & ≥1 ≥1
DEV01: &
Open command &
DEV01:
[ 210 028 ] Switch. device runn.
DEV01: &
Close command DEV01:
Stat.ind.interm.pos.
[ 210 029 ]
& [ 210 027 ]
DEV01:
Start runn.time mon.
& & ≥1
0 5s 0 &
&
1
0: No ◄
1: Yes
0
0⋯3 DEV01:
DEV01: Control state
StartCmdTime superv. [ 210 018 ]
0: Intermediate pos.
[ 210 007 ]
1: Open
2: Closed
19Z80AKB
After sending an Open / Close command, running time monitoring for the
switchgear unit is started.
The P438 expects that the switchgear unit has reached its intermediate position
within a period of time that can be configured via DEV0 1: StartC mdTime
superv . (for DEV01, respective setting parameters exist for the other DEVxx). If
the switchgear unit has not reached its intermediate position after this time has
elapsed then the command is deactivated and an exceeded timer is flagged by
the signal MA IN : Startcmdti me e xcee d.. In case of a switchgear unit for
which it is (almost) impossible to detect the intermediate position (for example a
Circuit Breaker) it is recommended to switch off this monitoring by setting the
parameter to Blocked.
Moreover, the P438 expects a status signal – “Open” or “Closed” to be issued by
the switchgear unit within the duration of running time monitoring. The status
signal for the position of the contacts on the switchgear unit is present at
appropriately configured binary inputs on the P438, which can be set to
debouncing and chatter suppression mode (see Section 3.46.1.1, (p. 3-364)). For
the duration of running time monitoring or until the contacts on the switchgear
unit are back to a defined position – either “Open” or “Closed” – the signal
“Intermediate position” is issued.
If DEV01: Int erm. pos. s u ppr. is set to Yes, the previous switchgear unit
status will continue to be signaled to the communication interfaces while the
switchgear unit is operating. Once the contacts on the switchgear unit have
reached their new position, the updated status is signaled accordingly to the
communication interfaces. This parameter has no impact to internal signals, such
as DEV01: Swi tch. de vice ope n, DEV 01: Swit ch. device closed or
D EV01: Dev. int erm./flt.pos.
If the contacts on the switchgear unit have not reached either their “Open” or
“Closed” position after the set time period for running time monitoring has
elapsed the signal Faulty position is issued. If DE V0 1: Stat .in d.in ter m. pos. is
set to Yes, a delay time of 5 s is started. Once this time period has elapsed and
there is no status signal for the position, the state actually present at the binary
inputs will be signaled.
If the operating mode without external termination contacts was selected
(MAIN : W. e xt. cmd. termi n.. is set to No) the switching command is
terminated after the set latching time has elapsed, when either the ‘Open’ or
‘Closed’ position status signal is received or the set time period for running time
monitoring has elapsed (see Fig. 3-280, (p. 3-341)).
If the operating mode with external termination contacts was selected
(MAIN : W. e xt. cmd. termi n.. is set to Yes) the switching command is
terminated, after the set latching time has elapsed, when a termination
command is issued while the set time period for running time monitoring is
active.
DEV01:
Close command
[ 210 029 ]
3
1
DEV01:
Switch. device open
[ 210 036 ]
DEV01:
Switch.device closed
[ 210 037 ]
1 3 4
10 ms DEV01: DEV01:
Latching time Op.time switch. dev.
[ 210 005 ] [ 210 004 ]
19Z5201B
Fig. 3-287: Sequence for time control of switching commands without external termination control, example for
switching operation “close”.
DEV01:
Close command
[ 210 029 ]
DEV01:
3
Switch. device open
[ 210 036 ]
DEV01:
Switch.device closed
[ 210 037 ]
DEV01:
Inp. asg. end Close
[ 210 016 ]
1 3
10 ms DEV01:
Latching time
[ 210 005 ]
19Z5202B
Fig. 3-288: Sequence for time control of switching commands with external termination control, example for
switching operation “close”.
DEV01: + MAIN:
Start runn.time mon. No. motor drive op.
307 008
R [ 221 025 ]
MAIN:
Perm.No.mot.drive op
MAIN: [ 221 027 ]
General reset USER
[ 003 002 ]
1: execute COMP
MAIN: n
General reset EXT
[ 005 255 ]
MAIN:
Reset LED MAIN:
306 020 n>No. permiss. oper. Mon. mot. drives tr.
[ 221 056 ]
n=1
MAIN:
Mon.time mot.drives
[ 221 026 ]
MAIN:
Cool.time mot.drives t
[ 221 028 ]
19Z6417A
Fig. 3-289: Monitoring the Motor Drives in Case of Direct Motor Control.
For bays with direct motor drive control of load disconnecting switches, isolating
links or grounding switches, a monitoring function is provided to protect motors
from overheating.
The number of switching operations within a set monitoring period is counted. If
the number of switching operations within the monitoring period exceeds the set
limit, the signal MAI N: Mon. mot. drive s tr . is issued. For the duration of the
set cooling time, no control commands to motor-driven switchgear units will be
executed. Once the set cooling time has elapsed, the control commands are
enabled again.
DEV01:
Operation counter
[ 210 043 ]
DEV01:
m CT=m Operation counter
[ 210 043 ]
DEV01:
Open command
[ 210 028 ] ≥1 +
DEV01:
Oper.count.limit
R
DEV01: [ 218 211 ]
Close command
[ 210 029 ]
COMP
[ 003 002 ] 1 ≥1 DEV01:
1: execute Warning op.count.
[ 219 081 ]
MAIN:
General reset EXT
[ 005 255 ]
19Z8104A
The diagram above shows the example of function group DEV01. The logic,
however, is valid for all DEVxx with the appropriate parameters.
All Open and Close commands to the switchgear unit are counted. One counter
per DEVxx function group is available for this purpose.
Moreover, a limit value can optionally be set for the counter value. If the counter
value reaches the set limit a warning signal is issued. Due to safety reasons the
switchgear control will not be blocked when the set limit has been reached.
For further processing each of these fault signals may be configured to selection
parameters from the function groups LED (assignment to LED indicators), OUTP
(assignment to output relays), LOGIC (processing by the programmable logic
function), COMMx / IEC / GOOSE (signaling via the control system) or they may be
mapped to the signal panel as an alarm signal. Acknowledging from the local
control panel HMI is done by pressing the CLEAR (C) key.
If the status signal from the motor relay is issued during the monitoring time
period, the running time monitoring of the motor relay is started simultaneously
with this status signal. Monitoring of the switching command is then the same as
with electromechanically operated switchgear units.
If the operating mode without external termination contacts was selected the
“Close” command to the motor relay is terminated after the set latching time has
elapsed, when either the “Open” or “Closed” position status signal is received or
the set time period for running time monitoring has elapsed (see Fig. 3-280,
(p. 3-341)). The monitoring time period is again started with the termination of
the “Close” command to the motor relay and after it has elapsed the control
commands “Open” or “Close” are also terminated. The same is valid for the
shunt windings.
MAIN:
Protection enabled
[ 003 030 ]
0: No (= off)
MAIN:
W. ext. cmd. termin.
[ 221 063 ]
0: No
1: Yes
DEV01:
Switch. device runn.
307 010
DEV01:
Latching time runn.
307 011
DEV01:
Inp. asg. end Open
[ 210 015 ]
Signal 1
Signal 2
Signal 3
&
Signal n
Selected signal
DEV01:
Inp. asg. end Close
[ 210 016 ]
Selected signal
MAIN:
Direct motor control
306 029
DEV01:
Close command
[ 210 029 ]
& & CMD_1:
Command C011
[ 200 051 ]
DEV01:
Latching time elaps.
307 012
MAIN:
Mon.time Dir.Contr.
[ 221 060 ]
COMM1:
& Motor rel. mon. trg.
SIG_1: Debouncing [ --- --- ]
Signal S012 EXT
[ 226 092 ] &
MAIN:
Chatter suppression & End command
306 028
DEV01:
& Start runn.time mon.
307 008
SIG_1:
Logic signal S012
[ 226 093 ]
48Z9358A
CMD_1:
Command C011
[ 200 051 ]
DEV01:
Close command
[ 210 029 ]
CMD_1:
Command C012
[ 200 056 ]
DEV01:
Switch. device open
[ 210 036 ]
DEV01:
Switch.device closed
[ 210 037 ]
Fig. 3-292: Sequence of time monitoring for direct motor control without external termination.
DEV01:
Close command
[ 210 029 ]
CMD_1:
Command C012
[ 200 056 ]
DEV01:
Switch. device open
[ 210 036 ]
DEV01:
Switch.device closed
[ 210 037 ]
DEV01:
Inp. asg. end Close
[ 210 016 ]
10 ms MAIN: DEV01:
Mon.time Dir.Contr. Latching time
[ 221 060 ] [ 210 005 ]
19Z5204C
Fig. 3-293: Sequence of time monitoring for direct motor control with external termination.
ILOCK:
Fct.assignm. outp. 1
[ 250 000 ]
MAIN:
Fct. block. 1 active
[ 221 015 ]
MAIN:
Fct. block. 2 active
[ 221 023 ]
MAIN:
DEV op.time exceeded
[ 221 110 ]
LOGIC:
Output 01
[ 042 032 ]
LOGIC:
Output 01 (t)
[ 042 033 ]
DEV01:
Switch. device open
[ 210 036 ]
DEV01:
Switch.device closed
[ 210 037 ]
DEV01:
Dev. interm./flt.pos
[ 210 038 ]
SIG_1:
Logic signal S001
[ 226 005 ]
GOOSE:
Ext.Dev01 closed
[ 109 002 ]
GOOSE:
Ext.Dev01 interm.pos
[ 109 003 ]
ILOCK:
Output 01
[ 250 032 ]
& ≥1
ILOCK:
Output 01
[ 250 032 ]
48Z9359A
MAIN:
Cmd. dur.long cmd. OUTP:
[ 221 230 ] Fct.assignment K xxx
[ xxx xxx ]
MAIN:
Cmd. dur. short cmd.
[ 221 231 ]
K x1
CMD_1: CMD_1:
Command C001 config. Oper. mode cmd. C001 K x2 -K xxx
[ 200 004 ] [ 200 002 ]
K x3
K xx
0 1
0: No 3
1: Yes
1: Long command
2: Short command
3: Persistent command
CMD_1:
& 1 ≥1 Command C001
& t [ 200 001 ]
COMM1:
Command C001
[ - - - - - - ]
LOC:
Rem.acc.block.active
[ 221 004 ]
& 1
t
&
19Z50ALB
Fig. 3-295: Functional sequence for single-pole commands, as illustrated for Command C001.
SIG_1: SIG_1:
Signal S001 config. Gr.asg. debounc.S001
[ 226 007 ] [ 226 003 ]
0: No Selected group
1: Yes
Debouncing SIG_1:
Logic signal S001
SIG_1: [ 226 005 ]
Signal S001 EXT
[ 226 004 ]
Chatter suppression
SIG_1:
Min. sig. dur. S001
[ 226 002 ]
COMM1:
Signal S001,log
[ --- ---]
SIG_1:
Oper. mode sig. S001
[ 226 001 ]
0: Without function
1: Start/end signal
2: Transient signal
19Z50AMA
Fig. 3-296: Functional sequence for single-pole signals with the example for logic signal S001.
SIG_1:
Gr.asg. debounc.S001
[ 226 003 ]
1: Group 1
2: Group 2
3: Group 3
4: Group 4
5: Group 5
6: Group 6
7: Group 7
8: Group 8
SIG_1:
Signal S001 EXT
[ 226 004 ]
DEV01:
Gr. assign. debounc.
[ 210 011 ]
8 MAIN:
Debounce time gr. 1
1: Group 1 [ 221 200 ]
2: Group 2 MAIN:
Chatt.mon. time gr.1
3: Group 3
[ 221 201 ]
4: Group 4
MAIN:
5: Group 5 Change of state gr.1
6: Group 6 [ 221 202 ]
7: Group 7
8: Group 8
Debouncing
&
COMM1:
DEV01: Chatter suppression Debounced signal
Closed signal EXT 304 400
[ 210 031 ] Group 1
DEV01:
Open signal EXT
[ 210 030 ]
19Z5067B
Fig. 3-297: Group assignment and setting of debouncing and chatter suppression, illustrated for group 1.
In the acquisition of signals for control purposes, the functions real time
acquisition (time tagging), debouncing and chatter suppression are included as
standard. Each of these signals can be assigned to one of eight groups and for
each of these groups the debouncing time and chatter suppression can be set.
Matching of these two parameters achieves the suppression of multiple spurious
pickups.
3.46.1.1.1 Debouncing
Telegram with
time tag 1s 2e
Signal sequence
time tag
F0Z5011B
Fig. 3-298: Signal flow with debouncing when time tagging occurs with the 1st pulse edge (e.g. parameter
M A I N : T i m e t a g set to the value 1stEdge,OpMem unsort or 1stEdge,OpMem sorted.) Example: Set debouncing
time: 50 ms, s: start, e: end.
The first pulse edge of a signal starts a timer stage running for the duration of
the set debouncing time. Each pulse edge during the debouncing time re-triggers
the timer stage.
If the signal is stable until the set debouncing time elapses, a telegram
containing the time tag of the first pulse edge is generated. As an alternative the
time tag may be generated after debouncing by setting parameter MAIN: Tim e
t ag to the value After debounce time.
After the set debouncing time has elapsed, the state of the signal is checked. If it
is the same as prior to the occurrence of the first pulse edge, no telegram is
generated.
Time-tagged entries of the first pulse edge are only generated after debounce
time has elapsed. If these entries are saved without delay (setting of
MAIN : Time tag to the value 1stEdge,OpMem unsort) they are not necessarily
saved in chronological order in the operating data memory. If above parameter
has been set to the value 1stEdge,OpMem sorted then all entries are always
saved in chronological order in the operating data memory.
Time Tag
The following overview illustrates how the (221 098) MAIN: Time tag setting is
operating.
}
(no time tag, internal signal to start debouncing)2)
1stEdge,OpMem sorted:
(226 005) SIG_1: Logic signal S001
● on COMM1/IEC T L
1stEdge,OpMem unsort:
(226 005) SIG_1: Logic signal S001
● on COMM1/IEC T L
T = Time tag
L = Log of state
Telegram with
time tag 1s 2e 3s 4e
Signal sequence
20ms 200ms
20ms 200ms
20ms 200ms
200ms
time tag
Debouncing
F0Z5012A
Fig. 3-299: Signal flow for debouncing and chatter suppression. Set debouncing time: 20 ms, set chatter monitoring
time: 200 ms, number of admissible signal changes: 4, s: start, e: end.
Sending of the first telegram starts a timer stage running for the duration of the
set monitoring time. While the timer stage is elapsing, telegrams are generated
for the admissible signal changes. The number of admissible signal changes can
be set. After the first “inadmissible” signal change, no further telegrams are
generated and the timer stage is re-triggered. While the timer stage is elapsing,
it is re-triggered by each new signal change. Once the timer stage has elapsed,
each signal change triggers a telegram.
3.47.2 Debouncing
Count
Signal sequence
50ms
19Z50APA
The first positive pulse edge of the binary input signal to be counted will trigger a
timer stage which will continue to run for the set debouncing time period. Each
positive pulse edge during the debouncing time re-triggers the timer stage. The
binary input signal will be counted if it is stable during the set debouncing time
period.
The debouncing time can be set separately for each of the four counters.
After the set debouncing time has elapsed, the state of the signal is checked. If it
is the same as prior to the occurrence of the first pulse edge, it will not be
counted.
60/(set cycle time) comes to an integer. In all other cases the counter values are
transmitted at time intervals determined by a free running internal clock.
COUNT:
General enable USER
[ 217 000 ]
0
COUNT:
1 Enabled
0: No [ 217 001 ]
MAIN: 1: Yes
Protection enabled COUNT:
[ 003 030 ] Count 1
1: Yes (= on) [ 217 100 ]
COUNT: COUNT:
Debounce t. count. 1 m CT=m Count 1
[ 217 160 ] [ 217 100 ]
+
COUNT: Debouncing
Set counter 1 EXT
R
[ 217 130 ]
COUNT:
Transmit counts USER
[ 217 008 ]
0
COUNT:
1 Transmit counts
[ 217 010 ]
0: don't execute
1: execute
C
COUNT:
Transmit counts EXT
[ 217 009 ]
COUNT:
Cycle t.count transm
C
[ 217 007 ] COMM1:
Count 1
[ --- --- ]
G
COUNT:
Reset USER
[ 217 003 ]
= 0 min
0
COUNT:
1 Reset
[ 217 005 ]
0: don't execute
1: execute
COUNT:
Reset EXT
[ 217 004 ]
MAIN:
General reset USER
[ 003 002 ] 1
1: execute
MAIN:
General reset EXT
[ 005 255 ]
19Z82ANA
Fig. 3-301: Binary Count. (This diagram shows counter 1 as an example. The displayed logic is also valid for
counters 2 to 4, where C O U N T : S e t c o u n t e r 1 E X T and C O U N T : C o u n t 1 have to be replaced by the
respective parameters.
4 Design
The P438 is available in different types of cases and with different combinations
of modules.
The P438 is equipped with a fixed local control panel. The local control panel is
covered with a tough film so that the specified degree of IP protection will be
maintained. In addition to the essential control and display elements, a parallel
display consisting of multi-colored LED indicators is also incorporated (see
Section 6.2, (p. 6-2)). The meaning of the various LED indications is shown in
plain text on a label strip.
The PC interface (9-pin D-Sub female connector) is located under the hinged
cover at the bottom of the local control panel.
4.1 Designs
The P438 is available in a surface-mounted and a flush-mounted case. Depending
on the connection type – pin-terminal or ring-terminal connection – the case sizes
differ. The location diagrams (Section 5.7, (p. 5-34)) show the available
combinations of case widths and connection types.
Electrical connections are made via plug-in threaded terminal blocks. The
threaded terminal blocks in the surface-mounted case are accessible from the
front of the device after unscrewing the torx head steal screws on the sides (see
Fig. 4-1, (p. 4-3), ➀) and removing the local control panel. The local control
panel can then be secured by inserting the tabs in the slots in the left side wall
(see Fig. 4-1, (p. 4-3), ➁). The flush-mounted case is connected at the back of
the case.
WARNING
HAZARD OF EQUIPMENT DAMAGE
⚫ The local control panel (or front element) is connected to processor
module P by a plug-in connecting cable. Make sure the connector position
is correct. Do not bend the connecting cable!
Failure to follow these instructions can result in equipment damage
or unintended equipment operation.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ Do not open the secondary circuit of live system current transformers! If
the secondary circuit of a live CT is opened, there is the danger that the
resulting voltages will endanger personnel and damage the insulation.
⚫ For pin-terminal connection devices, the terminal block for system current
transformer connection is not a shorting block! Therefore always short-
circuit the system current transformers before loosening the threaded
terminals.
Failure to follow these instructions will result in death or serious
injury.
Fig. 4-1: Surface-mounted case, removal of local control panel . The illustration shows the 84TE case with fixed
local control panel.
147.5
177.5
184.5
213.4 257.1
242.6
260.2
177.5
227.9
213.4 253.6
203.0
155.4
159.0
168.0
5.0
5.0
181.3
Fig. 4-3: Flush-mounted case 40 TE with panel opening, flush-mount method 1 (without angle brackets).
(Dimensions in mm.)
101.6
177.5
213.4 227.9
242.6 253.6
260.2
6.4
186.5
101.6
224.5
242.6
Fig. 4-4: Flush-mounted case 40 TE with panel opening, flush-mount method 2 (with angle brackets and frame).
(Dimensions in mm.)
147.5
177.5
184.5
434.8 257.1
464.0
481.6
227.9
434.8 253.6
284.9
259.0
25.9
159.0
168.0
5.0
5.0
410.0
Fig. 4-6: Flush-mounted case 84 TE with panel opening, flush-mount method 1 (without angle brackets).
(Dimensions in mm.)
101.6
177.5
434.8 227.9
253.6
464.0
481.6
6.4
186.5
101.6
445.9
464.0
Fig. 4-7: Flush-mounted case 84 TE with panel opening, flush-mount method 2 (with angle brackets and frame).
(Dimensions in mm.)
Key:
● ●: standard equipment,
● ○: optional,
● ☐: depending on order,
● *: Module is not depicted in the terminal connection diagrams (Section 5.7,
(p. 5-34)).
● →xx: Module has to be fitted into slot number xx.
● 1st→xx, 2nd→yy [etc.]: If several modules of the same type may be ordered,
these must be fitted into the appropriate slots in a particular order: If only
one has been ordered it must be fitted into slot xx (i. e. slot yy is not
permitted). If two modules have been ordered these must be fitted into
slots xx and yy, etc.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ When electrical equipment is in operation, dangerous voltage will be
present in certain parts of the equipment.
⚫ Proper and safe operation of this device depends on appropriate shipping
and handling, proper storage, installation and commissioning, and on
careful operation, maintenance and servicing. For this reason only
qualified personnel shall work on or operate this device.
Failure to follow these instructions will result in death or serious
injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ Switch off the auxiliary power supply before any work in the terminal strip
area.
⚫ Switch off all the power supplies in connection to the equipment before
any work in the terminal strip area to isolate the device.
⚫ Do not touch the terminal strip area when equipment is in operation.
⚫ Do not remove or add wires in the terminal strip area when equipment is
in operation.
⚫ Short-circuit the system current transformers before disconnecting wires
to the transformer board (valid only for pin terminals, not required for ring
terminals which have a shortening block).
⚫ A protective conductor (ground/earth) of at least 1.5 mm2 must be
connected to the protective conductor terminal on the power supply board
and on the main relay case.
⚫ Do never remove the protective conductor connection to the device casing
as long as other wires are connected to it.
⚫ Where stranded conductors are used, insulated crimped wire end ferrules
must be employed.
Failure to follow these instructions will result in death or serious
injury.
Note: Regarding the appropriate wiring connections of the equipment refer to the
document Px3x_Grounding_Application_Guide_EN_h.pdf.
WARNING
HAZARD OF UNSAFE OPERATION
⚫ The user should be familiar with the warnings in the Safety Guide
(SFTY/5LM/L11 or later version) before working on the equipment.
⚫ The user should be familiar with the safety messages in Chapter 5,
Chapter 10, Chapter 11 and Chapter 12 and with the content of Chapter 13
of this technical manual, before working on the equipment.
⚫ Proper and safe operation of this device depends on appropriate shipping
and handling, proper storage, installation and commissioning, and on
careful operation, maintenance and servicing. For this reason only
qualified personnel shall work on or operate this device.
⚫ Any modifications to this device must be in accordance with the manual. If
any other modification is made without the express permission of
Schneider Electric, it will invalidate the warranty, and may render the
product unsafe.
Failure to follow these instructions can result in unintended
equipment operation.
The signals MAI N: Bl ocked/faulty and SFMON: War ning (LED) are
permanently assigned to the LEDs labeled OUT OF SERVICE and ALARM and can
be assigned to output relays to indicate the health of the device.
It is recommended that the signals MA IN: Blocke d/faulty and
SFMON : Wa rning ( LED) are communicated to the substation automation
system for alarm purposes, using hardwiring via output relays or the
communication interface.
WARNING
HAZARD OF EQUIPMENT DAMAGE OR LIFETIME REDUCTION
⚫ The instructions given in the Section 5.5, (p. 5-14) (“Protective and
Operational Grounding”) should be noted. In particular, check that the
protective ground connection is secured with a tooth lock washer, as per
the diagram “Installing the protective grounding conductor terminal” (Fig.
5-8. (p. 5-15)).
⚫ If a cable screen is added to this connection or removed from it, then the
protective grounding should be checked again.
Failure to follow these instructions can result in death, serious injury
or equipment damage.
WARNING
HAZARD OF EQUIPMENT DAMAGE OR LIFETIME REDUCTION
⚫ Do not sustain exposure to high humidity during storage, the value shall
not exceed 75 % relative humidity.
⚫ Once the device has been unpacked, it is recommended to energize it
within the three following months.
⚫ The device has to be energized at least once in 4 years, if it is not in
permanent operation.
⚫ Where electrical equipment is being installed, sufficient time should be
allowed for acclimatization to the ambient temperature of the environment
before energization.
Failure to follow these instructions can result in equipment damage,
unintended equipment operation or reduction of equipment lifetime.
Px3x-xxxxxxxx-3xx-4xx-6xx-7xx- 48 - 250 V
9xx-8xx Vx-
100 - 230 V
SER No. 3xxxxxxx /xx/xx
In 1/5A 50 / 60Hz
E.Serial No. 3.xxxxxx.x
E.Reg No. STxxxxxxxxx Vn 50 - 130V
Fig. 5-1: Example of the type identification label of a device from the Easergy MiCOM 30 family.
The P438 design version can be determined from the order number. A
breakdown of the order number is given in Chapter “Order Information”
(Chapter 15, (p. 15-1)).
5.4 Installation
The dimensions and mounting dimensions for surface-mounted cases are given
in Section 4.2, (p. 4-4). When the P438 is surface-mounted on a panel, the wiring
to the P438 is normally run along the front side of the mounting plane. If the
wiring is to be at the back, an opening can be provided above or below the
surface-mounted case. Fig. 5-2, (p. 5-7) shows such an opening.
D5Z50MBA
Fig. 5-2: Opening (cutout) for running the connecting leads to an 40 TE surface-mounted case.
The opening width for the 40 TE surface-mounted case: 213 mm (shown in this
figure), for the 84 TE surface-mounted case: 435 mm. The other dimensions are
the same for all cases.
Flush-mounted cases are designed for control panels. The dimensions and
mounting dimensions are given in Chapter “Design”. When the P438 is mounted
on a cabinet door, special sealing measures are necessary to provide the degree
of protection required for the cabinet (IP 51).
Connection of protective grounding conductor: See “Protective and Operational
Grounding” (Section 5.5, (p. 5-14))
For flush-mount method 1 (without angle brackets and frame), the procedure is
as follows:
Before the P438 can be installed into a control panel, the local control panel must
be taken down. The local control panel is removed as described below:
1. Remove both top and bottom hinged flaps from the device. (Lift/lower
both hinged flaps 180° up/down. Hold them in the middle and bend them
slightly. The side mountings of both hinged flaps can then be disengaged.)
2. Remove the M3.5 screws (see Fig. 5-3, (p. 5-9)).
3. Then remove the local control panel.
WARNING
HAZARD OF EQUIPMENT DAMAGE
⚫ The local control panel (or front element) is connected to processor
module P by a plug-in connecting cable. Make sure the connector position
is correct. Do not bend the connecting cable!
Failure to follow these instructions can result in equipment damage
or unintended equipment operation.
Then remove the lower M4 screws and only loosen the upper M4 screws (see
Fig. 5-3, (p. 5-9)). Now insert the P438 into the panel opening from the rear so
that the upper M4 screws fit into the corresponding holes. Then tighten all the
M4 screws. After this, replace the local control panel.
NOTICE
HAZARD OF EQUIPMENT DAMAGE
⚫ When replacing the local control panel, take care not to tighten the screws
with too much strength! (Fastening torque 1.5 to 1.8 Newton meters).
⚫ If the control panel thickness is ≥ 2 mm, the longer screws as enclosed
within the device packing must be used.
Failure to follow these instructions can result in equipment damage.
< 3 mm
M4
M3.5
12Y6181B
Fig. 5-3: Installation of a case into a control panel. Flush-mount method 1 (without the angle brackets and frame ).
Example for a device with a 40 TE case.
NOTICE
HAZARD OF EQUIPMENT DAMAGE
⚫ The equipment provides increased mechanical robustness if either the
surface-mounted case or for the flush-mounted case flush-mount method 2
(with angle brackets and frame, see Fig. 5-5, (p. 5-10)) is used.
Failure to follow these instructions can result in equipment damage.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ Secure connection of protective grounding conductor: See Section 5.5, (p.
5-14).
Failure to follow these instructions will result in death or serious
injury.
For flush-mount method 2 (using the angle brackets and frame), the procedure is
as follows:
1. Remove the screws as shown in Fig. 5-4, (p. 5-10), ➀ and mount the
enclosed angle brackets using these same screws.
2. Then push the device into the control panel cutout from the front.
3. Secure the device to the control panel by using the enclosed M6 screws
(see Fig. 5-5, (p. 5-10)).
4. Assemble the cover frame and snap-fasten onto the fixing screws.
45Z5058A
Angle brackets
M6
B6
6.4
M6 x 15
Height: 204mm
for
Frame 280mm
Width:
E case
the 40T
12Y6183B
Fig. 5-5: Installation of a case into a control panel, flush-mount method 2 (with angle brackets and frame). Example
for a device in a 40 TE case.
The cover frame width of the 40 TE surface-mounted case is: 280 mm, of the
84 TE case is: 486 mm. The cover frame height is for all cases: 204 mm.
NOTICE
HAZARD OF EQUIPMENT DAMAGE
⚫ The equipment provides increased mechanical robustness if either the
surface-mounted case or for the flush-mounted case flush-mount method 2
(with angle brackets and frame, see Fig. 5-5, (p. 5-10)) is used.
Failure to follow these instructions can result in equipment damage.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ Secure connection of protective grounding conductor: See Section 5.5, (p.
5-14).
Failure to follow these instructions will result in death or serious
injury.
Connection flange
Tapped bush
Bolt
61Y5077A
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ Secure connection of protective grounding conductor: See Section 5.5, (p.
5-14).
Failure to follow these instructions will result in death or serious
injury.
Covering flange
Rack frame
61Y5078A
Fig. 5-7: Installing the P438 in a cabinet with a 19″ mounting rack.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ Secure connection of protective grounding conductor: See Section 5.5, (p.
5-14).
Failure to follow these instructions will result in death or serious
injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ The device must be reliably grounded to meet protective equipment
grounding requirements.
⚫ The surface-mounted case is grounded using the bolt and nut,
appropriately marked, as the ground connection. The flush-mounted case
must be grounded in the area of the rear sidepieces at the location
provided. The bracket is marked with the protective ground symbol: .
The cross-section of the ground conductor must conform to applicable
national standards. A minimum cross section of 2.5 mm² (≤ AWG12) is
required.
⚫ In addition, a protective ground connection at the terminal contact on the
power supply module (identified by the letters “PE” on the terminal
connection diagram) is also required for proper operation of the device.
The cross-section of this ground conductor must also conform to applicable
national standards. A minimum cross section of 1.5 mm² (US: AWG14 or
thicker) is required.
⚫ All grounding connections must be low-inductance, i.e. it must be kept as
short as possible.
⚫ The protective conductor (earth) must always be connected to the
protective grounding conductor terminal in order to guarantee the safety
given by this setup.
Failure to follow these instructions will result in death or serious
injury.
1
2 1
3
2
4
4
PE terminal PE terminal
surface-mount. case flush-mount. case
1 Nut M4 1 Nut M4
4 Bolt M4 4 Bolt M4
19Y5220B
5.6 Connection
The P438 Rail Catenary Protection Device must be connected in accordance with
the terminal connection diagram as indicated on the type identification label. The
relevant terminal connection diagrams that apply to the P438 are to be found
either in the supporting documents supplied with the device, or in Section 5.7,
(p. 5-34).
In general copper conductors with a cross section of 2.5 mm² (US: AWG12) are
sufficient to connect a system current transformer to a current input on the P438.
To reduce CT knee-point voltage requirements, it may be necessary to install
shorter copper conductors with a greater cross section between the system
current transformers and the current inputs on the P438. Copper conductors
having a cross section of 1.5 mm² (US: AWG14) are adequate to connect binary
signal inputs, the output relays and the power supply input.
All connections run into the system must always have a defined potential.
Connections that are pre-wired but not used should preferably be grounded when
binary inputs and output relays are isolated. When binary inputs and output
relays are connected to common potential, the pre-wired but unused connections
should be connected to the common potential of the grouped connections.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ When increased-safety machinery is located in a hazardous area the
device must always be installed outside of this hazardous area to protect
this equipment.
Failure to follow these instructions will result in death or serious
injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ The power supply must be turned off for at least 5 s before power supply
module V is removed. Otherwise there is the danger of an electric shock.
Failure to follow these instructions will result in death or serious
injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ Do not open the secondary circuit of live system current transformers! If
the secondary circuit of a live CT is opened, there is the danger that the
resulting voltages will endanger personnel and damage the insulation.
⚫ For pin-terminal connection devices, the terminal block for system current
transformer connection is not a shorting block! Therefore always short-
circuit the system current transformers before loosening the threaded
terminals.
Failure to follow these instructions will result in death or serious
injury.
Supply Catenary
MAIN:
I> Feeder mode
[ 010 135 ]
MAIN:
Vnom V.T. sec.
[ 010 009 ]
V̲A
V̲
MAIN: MAIN:
Conn. meas. circ. I Inom device
[ 010 004 ] [ 010 003 ]
I̲A
X.Y I̲
1: Standard
2: Opposite
Catenary
Rail 48Z9301A
Fig. 5-9: Connecting the measuring circuits in the 'Classic single feed' operating mode.
Supply Catenary
Supply Feeder
MAIN:
Feeder mode
[ 010 135 ]
2
I>
3
V̲B/V̲ref
V̲B/V̲ref
+ V̲
-
MAIN: MAIN:
Conn. meas. circ. I Inom device
[ 010 004 ] [ 010 003 ]
I̲A
X.Y I̲A
I̲B
X.Y I̲B
1: Standard
2: Opposite
+ I̲
-
Feeder
Catenary
Rail 48Z9302A
Fig. 5-10: Connecting the measuring circuits in the 'Autotransformer feed' operating mode.
Supply Catenary
I>
MAIN:
Feeder mode
[ 010 135 ]
V̲
MAIN: MAIN:
Conn. meas. circ. I Inom device
[ 010 004 ] [ 010 003 ]
I̲A
X.Y I̲A
I̲B
X.Y I̲B
1: Standard
2: Opposite
+ I̲
-
Catenary
Rail
Catenary
Rail 48Z9304A
Fig. 5-11: Connecting the measuring circuits in the 'single feed with summated current' operating mode.
Supply Catenary
Q1 Q2
MAIN: MAIN:
Conn. meas. circ. I Inom device
[ 010 004 ] [ 010 003 ]
I̲A
I̲
1: Standard
2: Opposite
MAIN: MAIN:
MsCirc.Iplaus/Idfrst Iplaus/Idfrst,CTnom
[ 010 036 ] [ 010 017 ]
I̲plaus/I̲dfrst
X.Y I̲plaus/I̲dfrst
1: Standard
2: Opposite
Catenary 1
Q3
Catenary 2
Q4
Rail
48Z9303A
Supply Catenary
I>
MAIN:
Vnom V.T. sec.
[ 010 009 ]
V̲A
V̲
MAIN: MAIN:
Conn. meas. circ. I Inom device
[ 010 004 ] [ 010 003 ]
I̲A
X.Y I̲
1: Standard
2: Opposite
MAIN: MAIN:
MsCirc.Iplaus/Idfrst Iplaus/Idfrst,CTnom
[ 010 036 ] [ 010 017 ]
I̲plaus/I̲dfrst
X.Y I̲plaus/I̲dfrst
1: Standard
2: Opposite
Catenary
Rail 48Z9300A
Supply Catenary
MAIN:
Feeder mode
[ 010 135 ]
I> 1
V̲
I>
V̲B/V̲ref
V̲B/V̲ref
Catenary
Rail
48Z9305A
Protection device a L+ L-
PSIG1:
Send signal
[ 036 035 ]
-K1
L+
PSIG1:
Receive EXT
L-
[ 036 048 ]
P438
Protection device b L- L+
PSIG1:
Receive EXT -K2
[ 036 048 ]
L+
L-
PSIG1:
Send signal
[ 036 035 ]
P438
48Z93A2A
L+ L-
Protection device a
PSIG1:
Send signal
[ 036 035 ]
L+
PSIG1:
Receive EXT
L-
[ 036 048 ]
P438
L-
Protection device b L+
PSIG1:
Send signal
[ 036 035 ]
PSIG1: L+
Receive EXT
[ 036 048 ] L-
P438
48Z93A3A
PT 100
P438
S8Z52H9A
Kxx CB
49Z9005A
In order to ascertain that the inductive coil current is switched off from the CB
auxiliary contacts, the setting of minimum pulse duration for trip commands
(MA IN : Mi n.dur. M-tri p cmd1 etc.) and close command need to consider the
operating times of the circuit breaker and its auxiliary contacts. Sufficient margin
has to be applied for pulse duration. A common setting is to double operating
time of the circuit breaker, e.g. for a CB trip operation time top of 100 ms, the
minimum trip pulse time should be 0.2 s (see the following figure).
CB Closed (52a)
top
tmop= 2*top
MAIN:
Min.dur. M-trip cmd1
48Z93A6A
This of course also applies to device open/close command outputs operated with
fix (short or long) command duration (e.g. DEVxx Oper. mode cmd. = Short
command).
If the Px30 output contact triggers an auxiliary relay which opens or closes the
CB consecutively, then it should be verified, that the make/continuous/break coil
currents of this auxiliary relay are within the limit values given in Section 2.5.7,
(p. 2-12).
Note: Upon testing such command outputs, the CB (or equivalent auxiliary
components) must not be mechanically locked, so that the auxiliary 52a/b
contact could operate and break the DC current. If the CB has to stay locked,
tripping or closing circuit has to be opened by terminal disconnection or test
switch.
CIRCUIT BREAKER DRIVE Q1 DRIVE Q2 DRIVE Q8 TRIGGER. Shunt wd. MOTOR RELAY
‑K200.1
P438
‑X061 3 5 9 ‑X062 2 6 8 ‑X071 3 5 ‑X072 6 8
P438
‑X061 2 8 ‑X062 5 ‑X071 2
E1 E3 E1 E3 E1 E3 ‑X073 8
M1 M2 M3 X//Y
‑U706
P438
E4 E4 E4 ‑X073 9
‑K200.3
‑X072 7 9
‑K705.2 ‑K706.2
P438
‑X072 5
S8Z01G3A
Fig. 5-20: Connection example, motor with shunt winding for a direct motor control, bay type No. 89
(A23.105.M04), feeder bay with circuit breaker, double busbar.
5.6.3.1 PC Interface
The PC interface is provided so that personnel can operate the device from a
personal computer (PC).
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ The PC interface is not designed as a permanent connection.
Consequently, the female connector does not have the extra insulation
from circuits connected to the system that is required per IEC/EN
60255-27. Therefore DO NOT leave any permanent cable connection on
the PC interface connector at the HMI front panel.
Failure to follow these instructions will result in death or serious
injury.
WARNING
UNEXPECTED EQUIPMENT OPERATION
⚫ Do not use a PC with active termination on any connection pin of the
RS232 interface. Wrong termination can drive the device to delay
operating actions from the HMI as long as this wrong termination is active
on the PC interface.
Failure to follow these instructions can result in unintended
equipment operation.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ Do not connect or disconnect the RS 485 or fiber-optic interface when the
supply voltage for the device is under power and in operation.
Failure to follow these instructions will result in death or serious
injury.
An RS 485 data transmission link between a master and several slave devices
can be established by using the optional communication interface. The
communication master could be, for instance, a central control station. Devices
linked to the communication master, e.g. P438, are set-up as slave devices.
The RS 485 interface available on the P438 was designed so that data transfer in
a full duplex transmission mode is possible using a 4-wire data link between
devices. Data transfer between devices using the RS 485 interface is set up only
for a half duplex transmission mode. To connect the RS 485 communication
interface the following must be observed:
● Only twisted pair shielded cables must be used, that are common in
telecommunication installations.
● At least one symmetrical twisted pair of wires is necessary.
● Conductor insulation and shielding must only be removed from the core in
the immediate vicinity of the terminal strips and connected according to
national standards.
● All shielding must be connected to an effective protective ground surface at
both ends.
● Unused conductors must all be grounded at one end.
A 4‑wire data link as an alternative to a 2-wire communications link is also
possible. A cable with two symmetrical twisted pair wires is required for a 4-wire
data link. A 2-wire data link is shown in Fig. 5-21, (p. 5-31), and a 4-wire data
link is shown in Fig. 5-22, (p. 5-32) as an example for channel 2 on the
communication module. The same is valid if channel 1 on the communication
module is available as a RS 485 interface.
2-wire data link:
The transmitter must be bridged with the receiver on all devices equipped
electrically with a full duplex communication interface, e.g. the P438. The two
devices situated at either far end must have a 200 to 220 Ω resistor installed to
terminate the data transmission conductor. In devices from the Easergy MiCOM
30 family, and also in the P438, a 220 Ω resistor is integrated into the RS 485
interface hardware and can be connected with a wire jumper. An external
resistor is therefore not necessary.
4-wire data link:
Transmitter and receiver must be bridged in the device situated on one far end
of the data transmission conductor. The receivers of slave devices, that have an
electrically full-duplex communication interface as part of their electrical system,
e.g. the P438, are connected to the transmitter of the communication master
device, and the transmitters of slave devices are connected to the receiver of the
master device. Devices equipped electrically with only a half duplex RS 485
communication interface are connected to the transmitter of the communication
master device. The last device in line (master or slave device) on the data
transmission conductor must have the transmitter and receiver terminated with
a 200 to 220 Ω resistor each. In devices from the Easergy MiCOM 30 family, and
also in the P438, a 220 Ω resistor is integrated into the RS 485 interface
-X9/-X10
− 1 −
D1[T] + 2 + D2[R]
− 4 −
D2[R] + 5 + D1[T]
XXXX P438
-X9/-X10 1 2 3 4 5
− + − + − + − +
P438 XXXX
Fig. 5-21: 2-wire data link. (Note: the setting M A I N : C h a n n . a s s i g n . C O M M 1 / 2 decides about whether -X9
(=channel 1) or -X10 (=channel 2) is used.)
-X9/-X10
D1[T] D2[R]
D2[R] D1[T]
XXXX P438
-X9/-X10
P438 XXXX
Fig. 5-22: 4-wire data link. (Note: the setting M A I N : C h a n n . a s s i g n . C O M M 1 / 2 decides about whether -X9
(=channel 1) or -X10 (=channel 2) is used.)
For CH1/CH2 connection diagram, please refer to Section 5.7, (p. 5-34)
B A ETH
ACT
LNK
A ETH
ACT
LNK
ETH A
ETH A
ETH B
ETH A
ETH B
ETH C
ETH C
ETH C
ETH C
IRIG B
IRIG B
IRIG B
IRIG B
Fig. 5-23: SEB Fiber. Fig. 5-24: SEB Fig. 5-25: REB Fiber. Fig. 5-26: REB
Copper. Copper.
Connector Connections
ETH A Fiber/Copper
ETH B Fiber/Copper
ETH C Copper
IRIG-B Demodulated (DC IRIG-B)/ Modulated (AC IRIG-B)
Tab. 5-1: Connector functionality.
01 02 03 04 05 06 07 08 09 10
P A A T X X Y V X
CH1 CH3 3J 6I 6I 4I 4I 6O
CH2 2V 8O 8O 8O
alt.
alt. alt. alt. alt. alt.
A
SEB Y X X X X
LC/ 4I 6I 6I 24I 6I
RJ45 6O 6O 3O
alt. alt.
A
REB X
LC/ 4H
RJ45
01 02 03 04 05 06 07 08 09 10
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
P A A T Y X X X X X V
CH1 CH3 3J 4I 6I 6I 6I 6I 6O 4I
CH2 2V 8O 8O 8O 8O 8O
alt.
alt. alt. alt. alt.
A
SEB X X X X
LC/ 6I 6I 24I 6I
RJ45 6O 6O 3O
alt.
A alt.
REB
LC/ X
RJ45 4H
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
P A A T Y X X X X X V
CH1 CH3 3J 4I 6I 6I 6I 6I 6O 4I
CH2 2V 8O 8O 8O 8O 8O
alt. alt. alt. alt. alt.
A X X X X
SEB 6I 6I 24I 6I
LC/ 6O 6O 3O
RJ45
alt. alt.
A X
REB 4H
LC/
RJ45
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
X__2 X__2
X__2
10 1 10 1 Vin
11 7 10 1 U_09
11 2 K_04 11 2 K_04 11 2
12 8 12 3 K_05 12 3 U_10
12 3
13 4 K_06 13 4 U_11
13 4
14 5 K_07 14 5 U_12
Current measuring 14 5
inputs 15 6 15 6 K_05 U_13
15 6
X042 16 7 K_08 16 7 U_14
16 7
1 1 IA 17 8 17 8 K_06 U_15
► T1
Signal inputs 18 9
17
18
8
9
U_16
2 2 18 9
Vin Signal inputs
3 3 IB U_01 X__3
► T2
X__3
19 1 Vin
U_01
X__3
4 4
19 1 Vin
20 2 19 1 U_17
5 5 I̲plaus/I̲dfrst Vin
► T3 20 2
Vin
U_02
21 3 U_02 20 2
U_18
6 6 21 3 22 4 21 3
Vin U_19
22 4 U_03 22 4
7 7 Vin
U_03 23 5 U_20
23 5
8 8 Vin U_21
23 5 24 6 U_04 24 6
Vin U_22
24 6 U_04 25 7 25 7
Vin U_23
U_05 26 8
Power supply U_24
25 7 26 8 27 9
+ V Vin
26 8
aux
U100 27 9 U_06
−
27 9
X__2 X__2
X__2
10 1 10 1
10 1
11 2 11 2 K_04 11 2 11 2
12 3 12 3 K_05 K_02
12 3 12 3 +
13 4 13 4 K_06 13 4
14 5 K_03 14 5 K_07 14 5 K_03
15 6 15 6
15 6
16 7 16 7 K_08
16 7
17 8 Signal 17 8 X__3
inputs 17 8
18 9 18 9
Signal 18 9
inputs
Vin
U_01 X__3
Vin
19 1 U_01 19 1
X__3 X__3
Vin K_03
19 1 U_02 20 2 19 1 20 2 +
Vin
20 2 21 3 U_02 20 2 K_04
Vin
21 3 U_03 21 3
Vin
22 4 22 4 U_03 22 4
Vin
23 5 U_04 23 5 23 5 K_05 26 8
Vin
24 6 24 6 U_04 24 6 K_04
Vin 27 9 +
25 7 U_05 25 7 25 7
Vin
26 8 U_05 26 8 K_06
Vin
27 9 U_06 26 8 27 9
Vin
27 9 U_06
Ring Pin
Port B
Port B X14
X14 1
and Ethernet RX > X//Y U30
service interface IRIG-B
Port C
time synchronization
X//Y U28 RJ45
X15 TX
1 X11
> X//Y U31 1
(DC IRIG-B)
Demodulated
RJ45
2 Isolated GND U21
3 and Ethernet and Ethernet
service interface service interface
Modulated Port C Port C
(AC IRIG-B)
X15 X15
1 1
IRIG-B
> X//Y U31 > X//Y U31
time synchronization RJ45 RJ45
X11
(DC IRIG-B)
1 Demodulated
IRIG-B IRIG-B
2 Isolated GND U21
time synchronization time synchronization
3
X11 X11
Modulated (DC IRIG-B) (DC IRIG-B)
(AC IRIG-B) 1 Demodulated 1 Demodulated
TRIP
H18
ALARM
OUT OF SERVICE
HEALTHY
H19
EDIT MODE
H20
H21
H22
H23
Fig. 6-1: View of the local control panel and layout of the LED indicators for the text display
H4 TRIP
H3 ALARM
H2 OUT OF SERVICE
H1 HEALTHY
H17 EDIT MODE
H5
H6
H7
H8
H9
H10
H11
H12
H13
H14
H15
H16
Fig. 6-2: View of the local control panel and layout of the LED indicators for the graphic display.
Panel Level: The “up”/“down” keys switch between the pages of the Measured
Value Panel.
Menu Tree Level: Press the “up” and “down” keys to navigate up and down
through the menu tree in a vertical direction. If the unit is in input mode, the
“up” and “down” keys have a different function.
Input mode: Settings can only be changed in the input mode, which is signaled
by the LED indicator labeled EDIT MODE. Press the “up” and “down” keys in this
mode to change the setting value.
● “Up” key: the next higher value is selected.
● “Down” key: the next lower value is selected.
With list settings, press the “up” and “down” key to change the logic operator of
the value element.
Menu Tree Level: Press the “left” and “right” keys to navigate through the
menu tree in a horizontal direction. If the unit is in input mode, the “left” and
“right” keys have a different function.
Input mode: Settings can only be changed in the input mode, which is signaled
by the LED indicator labeled EDIT MODE. When the “left” and “right” keys are
pressed, the cursor positioned below one of the digits in the change-enabled
value moves one digit to the right or left.
● “Left” key: the cursor moves to the next digit on the left.
● “Right” key: the cursor moves to the next digit on the right.
In the case of a list setting, press the “left” and “right” keys to navigate through
the list of items available for selection.
Panel Level: Press the ENTER key at the Panel level to go to the menu tree.
Menu Tree Level: Press the ENTER key to enter the input mode. Press the
ENTER key a second time to accept the changes as entered and exit the input
mode. The LED indicator labeled EDIT MODE signals that the input mode is
active.
Press the CLEAR key to reset the LED indicators and clear all measured event
data. The records in the recording memories are not affected by this action.
Input mode: When the CLEAR key is pressed all changes entered are rejected
and the input mode is exited.
Press the READ key to access a selected event recording from either the Panel
level or from any other point in the menu tree.
The local/remote key is effective in the Bay Panel except where a binary signal
input has been configured for this function.
The local/remote key is the transfer switch between remote and local control
(setting R <-> L), or between remote&local and local control (setting R & L <->
L). If the “Local/Remote” key is set to switch from Remote control to Local
control, then this can only occur if the password has first been entered first.
Switching from Local to Remote control will occur without checking the password.
Panel Level: Pressing the page key shows the next panel.
Menu Tree Level: When the page key is pressed the Menu Tree Level is exited
and the Bay Panel is accessed.
Bay Panel: The Selection key is effective only in the Bay Panel and only if local
control is activated.
If local control has been selected, pressing the selection key selects the
switchgear unit to be controlled. The selected external device will be marked by
an asterisk (*) – as long as no external device names are displayed. Otherwise
the external device name will flash and will be displayed in the status line.
Signal Panel: The Selection key is used to select a flashing signal (not yet
acknowledged) and will also automatically switch to pages that might be
available. When the last flashing signal has been reached pressing the Selection
key again will start with the first flashing signal.
Pressing the OPEN key controls the selected switchgear unit – taking into account
the interlock equation – to assume the “open” status.
To access a selected event recording from either the panel level or from any
other point in the menu tree, press the “READ” key .
From the control and display panels (e.g. measured value panels or the bay
panel) the user can access the menu tree level by pressing the “ENTER” key.
To return to the previously selected control and display panel from the menu tree
level the user must simultaneously press the keys “Cursor up” and “RESET”. (If
previously no panel was selected, i.e. after a system restart, then the bay panel,
if available, is accessed.)
After the set LOC : Au tom. re turn time has elapsed the protection unit will
also return automatically from the menu tree level to the control and display
panel last selected.
The user can move from a bay panel to a measured value panel by pressing the
key “Cursor left” and back again by pressing the key “Cursor right”.
Measured Value
Bay Panel Panel(s) Record View
(state-dependent)
X0 :running Voltage VAB prim. Oper/Rec/OP_RC
>Q0 :running 20.7 kV Operat. data record
Q8 :running Voltage VBC prim.
Local Remote 20.6 kV
+
Device type
Bay Panel Signal Panel Measured Value Panel(s) Event Panel Record View
(state-dependent)
Device type
This section applies only to devices fitted with an HMI with text display (ordering
option).
“Down”
“Right”
“Up”
The display will change as shown in the right hand side
column. *
Now press the ENTER key. If the correct password has Voltage A-B prim.
20.7 kV
been entered, the active display will re-appear. Voltage B-C prim.
Function key [F1] is now effective for the set return 20.6 kV
time.
By default, no password is required and therefore
function key [F1] is always effective.
Each function key can be assigned its own password,
and the return time is running after correct password
entry for each individual function key!)
If an invalid password has been entered, the display
shown above in Step 1 will appear.
Step 2b This control step can be canceled at any time by Voltage A-B prim.
20.7 kV
pressing the CLEAR key before the ENTER key is Voltage B-C prim.
pressed. 20.6 kV
Step 3 Press [F1] again. The function configured to this Voltage A-B prim.
20.7 kV
function key is carried out. Voltage B-C prim.
20.6 kV
Step 4 When function keys are pressed during their associated Oper/CtrlTest/LOC
Param. change enabl.
return time, then the set function is carried out directly, Yes
i.e. without checking for the password again.
(By default, i.e. no password required, this step does
not exist and the function key is permanently effective.)
Step 0 From the Menu Tree Level, the user can jump to the Par/Func/Glob/MAIN
Device on-line
Panel Level from any position within the menu tree. No (=off)
Step 1 First press the “up” key and hold it down while pressing Voltage A-B prim.
20.7 kV
the CLEAR key. Voltage B-C prim.
Note: It is important to press the “up” key first and 20.6 kV
+
release it last in order to avoid unintentional resetting of
stored data.
Step 1 Press the Enter key to go from the Panel Level to the P438
Menu Tree Level.
After the set return time has elapsed (setting in menu tree: “Par/Conf/LOC”), the
display will automatically switch to the Panel level if a Measured Value Panel has
been configured.
After start-up of the device, the display is at the Panel Level. The Bay Panel is
displayed.
Locked Q8
1: Remote
1088A ↑
Curr. IP,max prim. ↓
Step 1 Press the Enter key to go from the Panel Level to the P438
Parameters
Menu Tree Level.
Step 0 From the Menu Tree Level, the user can jump to the Par/Func/Glob/MAIN
Device on-line
Panel Level from any position within the menu tree. No (=off)
stored data. Q9
+ Locked Q8
1: Remote
1088A ↑
Curr. IP,max prim. ↓
After the set return time has elapsed (setting in menu tree: “Par/Conf/LOC”), the
display will switch automatically to the Bay Panel.
6.11.1 Usage
Step 6 If decided not to login (by pressing the 'CLEAR' key), User not selected
Aborted with C key
the message is displayed for 2 seconds.
Step 1 If more than two measured values have been selected, Voltage V prim.
20.8 kV
they can be viewed one page at a time by pressing the Current I prim.
“up” or “down” keys. 415 A
or
The device will also show the next page of the
Measured Value Panel after the set Hold-Time for
Panels (LOC : Hold -tim e for Pan els, located at “Par/
Conf” in the menu tree) has elapsed.
Step 1 Press the “local/remote” key (L/R) to switch the device to P438 10:33:22
local operation. The Bay Panel is no longer displayed.
The device type appears in the first line and eight ********
asterisks (*) appear in the fourth line as a prompt to
enter the password.
“Left”
*
Step 2b This control step can be canceled at any time by pressing X0 :Closed
Q0 :Closed
the Clear key before the enter key is pressed. Q8 :Closed
Remote Locked
Step 3a Press the Selection key to select a switchgear unit. Only X0 :Closed
>Q0 :Closed
switchgear units that are electrically controllable can be Q8 :Closed
selected. The external device designation for the Local Locked
selected switchgear unit –“Q0”, for example – is marked
by a flashing “>” character.
2: Closed
3: Faulty position
0: Intermediate pos.
2: Closed
3: Faulty position
0: Intermediate pos.
Disconnector 1: Open
2: Closed
3: Faulty position
0: Intermediate pos.
2: Closed
3: Faulty position
0: Intermediate pos.
2: Closed
Q1 Q2
A configuration step determines whether the measured
value will also be displayed in bar chart form. The Q0
position of the bar chart can also be set for horizontal or Q9
vertical display (the setting applies to all measured
values). The arrows under the bar chart indicate that Locked
1: Remote
Q8
or Q1 Q2
Q0
Q9
Locked Q8
1: Remote
1000A ↑
Current A prim. ↓
Q1 Q2
Q0
Q9
Locked Q8
1: Remote
1088A ↑
Curr. IP,max prim. ↓
Step 1 Press the “local/remote” key (L/R) to switch the device to P438 10:33:22
local operation. The Bay Panel is no longer displayed.
The device type appears in the first line and eight ********
asterisks (*) appear in the fourth line as a prompt to
enter the password.
“Left”
*
Locked Q8
2: Local
1088A ↑
Curr. IP,max prim. ↓
BB2
Q1 Q2
Q0
Q9
Locked Q8
1: Remote
1088A ↑
Curr. IP,max prim. ↓
Q1 Q2
Q0
Q9
Locked Q8
2: Local
1088A ↑
Curr. IP,max prim. ↓
operating.
Q0
Q9
Locked Q8
2: Local
1088A ↑
Curr. IP,max prim. ↓
BB2
Q1 Q2
Q0
Q9
Locked Q8
2: Local
1088A ↑
Curr. IP,max prim. ↓
Q1 Q2
If the LED indicators have been configured accordingly,
the LED indicator for MAI N: Inter lock equ. viol. will Q0
be illuminated. Q9
Locked Q8
2: Local
1088A ↑
Curr. IP,max prim. ↓
BB2
Q1 Q2
Q0
Q9
Locked Q8
1: Remote
1088A ↑
Curr. IP,max prim. ↓
The Signal Panel is applicable to the local control panel with graphic display only.
The Signal Panel is used to display the up to 28 different physical and logical
binary states that the device has available. The top line in the display shows the
panel designation “Signals” and the current time of day. The following empty line
separates the heading from actual signals. This gives display capacity of up to
seven signals to one Signal Panel. Additional pages are created when more than
seven signals have been configured. As with all other panels, switching between
pages is carried out automatically, after the parameter panel hold-time
(LOC : Hold -ti me for P ane ls) has elapsed, or manually by pressing the “Up”/
“Down” keys.
Each signal consists of two lines. The first line shows a status marker (square).
Moreover, the first line shows the associated function group. The second line
shows the full text for this signal.
this point it may occur that the display will automatically jump to the next page.
When the last flashing signal has been reached pressing the Selection key again
will start with the first flashing signal.
Depending on LOC : Sign. caus. Si gn. Pan elthe cause of a flashing signal may
be set. Either each status change of the binary information or only “incoming”
edges for transient signals will lead to a flashing signal. The status change is
generally shown as ’storing” i.e. the flashing signal will remain until it has been
acknowledged.
Description Display
■INP:
State U 1604
□MAIN:
M.c.b. trip Vref EXT
■FT_RC:
Fault mem. overflow
■LOC:
Rem.acc.block.active
■OUTP:
Outp. relays blocked
□PSS:
Activate PS 3 EXT
■LOGIC:
Reset 3 EXT
■ INP:
State U 1604
□ MAIN:
M.c.b. trip Vref EXT
■ FT_RC:
Fault mem. overflow
■ LOC:
Rem.acc.block.active
■ OUTP:
Outp. relays blocked
□ PSS:
Activate PS 3 EXT
■ LOGIC:
Reset 3 EXT
Step 0 The uppermost line of the display shows the type of Meas.values 16:57:33
measured values being displayed. In this example, the Voltage A-B prim.
display shows measured operating values (abbreviated 20.7 kV
as “Meas. values”). The time of day is shown at the Voltage B-C prim.
upper right of the display. 20.6 kV
Voltage C-A prim.
Up to six selected measured values can be displayed
20.8 kV
on the Panel simultaneously. Current A prim.
415 A
Current B prim.
416 A
Current C prim.
417 A
↓↑
Step 1 If more than six measured values have been selected, Meas.values 16:57:35
they can be viewed one page at a time by pressing the Voltage A-B norm.
“up” or ”down” keys. The device will also show the 0.7 kV
next page of the Measured Value Panel after the set or Voltage B-C norm.
Hold-time for Panels (setting in menu tree: “Par/Conf/ 0.6 kV
LOC”) has elapsed. Voltage C-A norm.
0.8 kV
Current A norm.
1.5 A
Current B norm.
1.6 A
Current C norm.
1.7 A
↓↑
Step 0 The uppermost line of the display shows the panel Events 16:57:33
designation and the current time of day. Below this 20.04.13
line, the signals are shown in chronological order. The 05:21:32.331 MAIN
arrows at the bottom of the display area indicate that Trip command
additional signals can also be displayed. Start
05:21:35.501 MAIN
Trip command
End
21.04.13
00:03:57.677 MAIN
Blocked/faulty
Start
↓↑
Step 1 Pressing the “up” or “down” keys will display the Events 16:57:35
signals one at a time.
05:21:35.501 MAIN
or Trip command
End
21.04.13
00:03:57.677 MAIN
Blocked/faulty
Start
08:10:59.688 GRUND
Blocked/faulty
End
↓↑
PX yyy
Unit
type
Oper/
Folder Cyclic measurements
plane 2
Oper/Cycl/
Folder Meas. operating data
plane 3
Oper/Cycl/Data/
Function MAIN
groups
Oper/Cycl/Data/MAIN
Data Date
01.01.16 dd.mm.yy
points
Step 0 In this example, the user switches from plain text mode Par/Func/Glob/MAIN
Device online
to address mode. No (=off)
Step 1 To switch from address mode to plain text mode or vice Par/Func/Glob/MAIN
003.030
versa, press the CLEAR key and either the “left” key or 0
the “right” key simultaneously. This can be done at any
point in the menu tree. +
or
Press the ENTER key. Eight asterisks (*) appear in the User Password?
********
display.
Step 2 The LED indicator labeled EDIT MODE will light up. This Oper/CtrlTest/LOC
Param. change enabl.
indicates that the setting can now be changed by No
pressing the “up” or “down” keys.
Step 4 Press the enter key again. The LED indicator will go out. Oper/CtrlTest/LOC
Param. change enabl.
The unit is enabled for further setting changes. Yes
The same procedure applies to any setting change unless the global change-
enabling function has been activated. This method is recommended for a single
setting change only. If several settings are to be changed, then the global
change-enabling function is preferable. In the following examples, the global
change-enabling function has been activated.
It is important to press the “up” key first and release it last in order to avoid
unintentional deletion of stored data.
Even when the change-enabling function is activated, not all settings can be
changed. For some settings it is also necessary to disable the protective function
(MAIN : Prote ction e na bl ed, menu tree: Par/Func/Glob/MAIN). Such settings
include the configuration settings, by means of which the device interfaces can
be adapted to the system. The following entries in the “Change” column of the
“Telegram Documentation” (part of the separately available
“DataModelExplorer”) indicate whether values can be changed or not:
● “on”: The value can be changed even when the protective function is
enabled.
● “off”: The value can only be changed when the protective function is
disabled.
● “–”: The value can be read out but cannot be changed.
The device is factory-set so that the protective function is disabled.
Press the ENTER key. Eight asterisks (*) appear in the User Password?
********
display.
Step 3 he LED indicator labeled EDIT MODE will light up. The Par/Conf/LOC
Autom. return time
last digit of the value is highlighted by a cursor 50000̲ s
(underlined).
Step 4 Press the “left” or “right” keys to move the cursor to Par/Conf/LOC
Autom. return time
the left or right. 5000̲0 s
Step 6 Press the ENTER key. The LED indicator labeled EDIT Par/Conf/LOC
Autom. return time
MODE will go out and the device will now operate with 50010 s
the new value. Press the keys to select another setting
for a value change.
Step 7 If you wish to reject the new setting while you are still Par/Conf/LOC
Autom. return time
entering it (LED indicator labeled EDIT MODE is on), 50000 s
press the CLEAR key. The LED indicator will go out and
the device will continue to operate with the old value.
A further setting can be selected for a value change by
pressing the keys.
Step 0 Select a list setting (in this example, the parameter Par/Conf/LOC
Fct.asg. num. displ.
LOC : Fct .a sg. num. di spl. at “Par/Conf/LOC” in the
menu tree). The down arrow (↓) indicates that a list ↓
setting has been selected.
Step 1 Press the “down” key. The first function and the first Par/Conf/LOC
Fct.asg. num. displ.
selected signal will appear in the third and fourth lines, #01 MEASO
respectively. The symbol “#01” in the display indicates Current A-1
the first item of the selection. If MAIN: W i th out
funct ion appears for the first item, then this means
that no function assignment has yet been made.
Once the end of the list is reached, the display shown Par/Conf/LOC
Fct.asg. num. displ.
on the right will appear. #05 MAIN
?????
Step 3 Press the ENTER key at any position in the list. The LED Par/Conf/LOC
Fct.asg. num. displ.
indicator labeled EDIT MODE will light up. #02 MAIN
Frequency f,1
Step 5 Select the operator or the class using the “up” and Par/Conf/LOC
Fct.asg. num. displ.
“down“ keys. In this particular case, only the “OR” OR #02 MAIN
operator can be selected. There is no limitation on the Angle phi N,1
selection of classes.
Step 6 Press the ENTER key. The LED indicator will go out. The Par/Conf/LOC
Fct.asg. num. displ.
assignment has been made. The unit will now operate OR #02 MAIN
with the new settings. Angle phi N,1
If no operator has been selected, the “OR” operator is
always assigned automatically when the ENTER key is
pressed. There is no automatic assignment of classes.
Step 7 Press the “up” key to exit the list at any point in the Par/Conf/LOC
Fct.asg. num. displ.
list.
↓
Step 8 If you wish to reject the new setting while you are still Par/Conf/LOC
Fct.asg. num. displ.
entering it (LED indicator labeled EDIT MODE is on), OR #02 MAIN
press the CLEAR key. The LED indicator labeled EDIT Frequency f,1
MODE will be extinguished.
Step 0 Select the entry point for the operating data memory. Oper/Rec/OP_RC
Operat. data record.
Step 1 Press the “down” key to enter the operating data Oper/Rec/OP_RC
01.01.13 11:33 ARC
memory. The latest entry is displayed. Enabled USER
No
Step 2 Press the “left” key repeatedly to display the entries Oper/Rec/OP_RC
01.01.13 11:33 PSIG
one after the other in chronological order. Once the Enabled USER
end of the operating data memory has been reached, Yes
pressing the “left” key again will have no effect.
Step 3 Press the “right” key to display the previous entry. Oper/Rec/OP_RC
01.01.13 11:33 ARC
Enabled USER
No
Step 4 Press the “up” key at any point within the operating Oper/Rec/OP_RC
Operat. data record.
data memory to return to the entry point.
↓
Step 0 Select the entry point for the monitoring signal Oper/Rec/MT_RC
Mon. signal record.
memory.
↓
Step 1 Press the “down” key to enter the monitoring signal Mon. signal record.
01.01.13 13:33 SFMON
memory. The oldest entry is displayed. Checksum error param
Step 2 Press the “right” key repeatedly to display the entries Mon. signal record.
01.01.13 10:01 SFMON
one after the other in chronological order. If more than Exception oper. syst.
30 monitoring signals have been entered since the last
reset, the “overflow” signal is displayed as the last
entry.
Step 3 Press the “left” key to display the previous entry. Mon. signal record.
01.01.13 13:33 SFMON
Checksum error param
Step 4 If the “down” key is held down while a monitoring Mon. signal record.
01.01.13 13:33 SFMON
signal is being displayed, the following additional Checksum error param
information will be displayed:
Step 5 Press the “up” key at any point within the monitoring Oper/Rec/MT_RC
Mon. signal record.
signal memory to return to the entry point.
↓
Step 0 Select the entry point for the first fault memory, for Events/Rec/FT_RC
Fault recording 1
example. If the memory contains entries, the third line 01.01.13 10:00:33
of the display will show the date and time the fault ↓
began. If the third line is blank, then there are no entries
in the fault memory.
Step 1 Press the “down” key to enter the fault memory. First, Fault recording 1
FT_RC
the fault number is shown. In this example it is the 22nd Event
fault since the last reset. 22
Step 2 Press the “right” key repeatedly to see first the Fault recording 1
200 ms FT_DA
measured fault data and then the binary signals in Running time
chronological order. The time shown in the second line is 0.17 s
the time, measured from the onset of the fault, at which
the value was measured or the binary signal started or Fault recording 1
ended. 0 ms FT_RC
Record. in progress
Once the end of the fault has been reached (after the
Start
“right” key has been pressed repeatedly), pressing the
“right” key again will have no effect.
Fault recording 1
241 ms FT_RC
Record. in progress
End
Step 3 Press the “left” key to see the previous measured value Fault recording 1
0 ms FT_RC
or the previous signal. Record. in progress
Start
Step 4 Press the “up” key at any point within the fault memory Events/Rec/FT_RC
Fault recording 1
to return to the entry point. 01.01.13 10:00:33
↓
6.13.7 Resetting
All information memories – including the event memories and the monitoring
signal memory – as well as the LED indicators can be reset manually. In addition,
the LED indicators are automatically cleared and initialized at the onset of a new
fault – provided that the appropriate operating mode has been selected – so that
they always indicate the latest fault.
The LED indicators can also be reset manually by pressing the CLEAR key, which
is always possible in the standard control mode. This action also triggers an LED
indicator test and an LCD display test. The event memories are not affected by
this action, so that inadvertent deletion of the records associated with the reset
signal pattern is reliably prevented.
Because of the ring structure of the event memories, the data for eight
consecutive events are updated automatically so that manual resetting should
not be necessary, in principle.
Deleting the event memories completely (e.g. after a function test), can be
accomplished by various resetting actions including the configuration of a group
resetting for several memories. An overview of all resetting actions can be found
in section “Resetting Actions” in Chapter “Operation”.
Resetting a single memory from the local control panel is described in the
following with the example of a fault memory. In this example the global change-
enabling function has already been activated.
Step 0 Select the reset setting. Line 3 of the display shows the Oper/CtrlTest/FT_RC
Reset recording
number of faults since the last reset, 10 in this 10
example.
Press the ENTER key. Eight asterisks (*) appear in the User Password?
********
display.
Step 2 The LED indicator labeled EDIT MODE will light up. Oper/CtrlTest/FT_RC
Reset recording
10
Don't execute
Step 3 Press the “Up” or “Down” keys to change the setting to Oper/CtrlTest/FT_RC
Reset recording
Execute. 10
Execute
Step 4 Press the ENTER key. The LED indicator labeled EDIT Oper/CtrlTest/FT_RC
Reset recording
MODE will be extinguished. The value in line 3 is reset 0
to 0.
Press the ENTER key. Eight asterisks (*) appear in the User Password?
********
display.
Step 2 The LED indicator labeled EDIT MODE will light up. This Oper/CtrlTest/MAIN
Man.M-trip cmd USER
indicates that the setting can now be changed by Don't execute
pressing the “up” or “down” keys.
Step 4 Press the enter key again. The LED indicator labeled Oper/CtrlTest/MAIN
Man.M-trip cmd USER
EDIT MODE will go out. The unit will execute the Don't execute
command.
Step 5 As long as the LED indicator labeled EDIT MODE is on, Oper/CtrlTest/MAIN
Man.M-trip cmd USER
the control action can be terminated by pressing the Don't execute
CLEAR key. The LED indicator labeled EDIT MODE will
be extinguished.
1 2
Press the ENTER key. Eight asterisks (*) appear in the User Password?
********
display.
Step 2 The LED indicator labeled EDIT MODE will light up. The Par/Conf/LOC
Password
third line shows an underscore character ( _ ) as the _
prompt for entering a new password.
Step 3 Enter the new password, which in this example is done Par/Conf/LOC
Password
by pressing the “up” key followed by the “down” key. *
Par/Conf/LOC
Password
**
Step 4 Press the enter key again. Asterisks appear in the third Par/Conf/LOC
Password
line, and a cursor (underscore) in the fourth line **
prompts the user to enter the new password again. _
Par/Conf/LOC
Password
**
**
Step 6a Press the ENTER key again. If the password has been Par/Conf/LOC
Password
re-entered correctly, the LED indicator labeled EDIT ********
MODE goes out and the display appears as shown on
the right. The new Password is now valid.
Press the ENTER key. Eight asterisks (*) appear in the User Password?
********
display.
Step 2 The red LED indicator labeled EDIT MODE will be Par/Conf/LOC
Password L/R
illuminated. The current Password L/R will appear in the 1423
third line.
Step 3 Enter the new password, which in this example is done Par/Conf/LOC
Password L/R
by pressing the “up” key followed by the “down” key. *
Par/Conf/LOC
Password L/R
**
Step 4 Press the enter key again. Asterisks appear in the third Par/Conf/LOC
Password L/R
line, and a cursor (underscore) in the fourth line **
prompts the user to enter the new Password L/R again. _
Par/Conf/LOC
Password L/R
**
**
Step 6a Press the ENTER key again. If the new Password L/R has Par/Conf/LOC
Password L/R
been re-entered correctly, the red LED indicator labeled ********
EDIT MODE will be extinguished and the display
appears as shown on the right. The new Password L/R is
now valid.
Step 7 The change of the Password L/R can be canceled at any Par/Conf/LOC
Password L/R
time before Step 7 by pressing the CLEAR key. If this is ********
done, the original Password L/R continues to be valid.
7 Settings
7.1 Parameters
The P438 must be adjusted to the system and to the protected equipment by
appropriate settings. This chapter gives instructions for determining the settings,
which are located in the folder titled “Parameters” in the menu tree. The
sequence in which the settings are listed and described in this chapter
corresponds to their sequence in the menu tree.
The P438 devices are supplied with a factory-set standard configuration of
settings that, in most cases, correspond to the default settings or become
apparent after a “cold restart”. The P438 is blocked in that case. All settings
must be re-entered after a cold restart.
Note
Detailed information about all parameters, including complete selection tables and
IEC 60870‑5‑103 protocol properties, are separately available as a set of interlinked
PDF files for user-friendly navigation, packed in one ZIP archive named
DataModelExplorer_P438_en_P01.zip.
In contrast to P438 versions before P438‑630, the implementation of the IEC 61850
protocol now features parameters that cannot be modified from the local control
panel (HMI) or with the operating program. Instead, these parameters are set with
a special IEC 61850 operating software, named “IED Configurator”.
Therefore these settings are not listed in this chapter or the following chapter.
These parameters are described in Chapter “IEC 61850 Settings via IED
Configurator”.
as a separate ZIP archive file) gives information about the configuration options
for all binary inputs.
The P438 identifies the installed modules during startup. If a given binary I/O
module is not installed or has fewer binary signal inputs than the maximum
number possible at this slot, then the configuration addresses for the missing
binary signal inputs are automatically hidden in the menu tree.
When configuring binary inputs, one should keep in mind that the same function
can be assigned to several signal inputs. Thus one function can be activated from
several control points having different signal voltages.
The configuration in slots A and B and the configuration for the binary inputs
U C01 to U C08 will be changed with the selection of a new bay type. (Whether
automatic configuration occurs, is defined in the setting MA IN: Auto-
assignme nt I /O.) Depending on the connection type chosen for the P438 – pin-
type or ring-type cable socket terminals – the symbolic slots A, B and C refer to
the following slots:
Symbolic slot Pin-type cable socket terminals Ring-type cable socket terminals
A 06 12
B 07 14
C 08 16
The configuration of binary inputs for each bay type – in the case of auto-
assignment – is given in the List of Bay Types in the Appendix.
In the case of auto-assignment, the following notes apply:
Before selecting a new bay type, make sure that the binary inputs at slots A and B
as well as the binary inputs U C01 to U C08 are configured for functions from the
DEVxx function groups only. Otherwise there will be an error message, and the new
bay type will not be activated.
Before selecting a new bay type, make sure that all binary inputs specified in the
List of Bay types for the selected bay type are actually available in the device.
Otherwise there will be an error message, and the new bay type will not be
activated.
In order to ensure that the device will recognize the input signals, the triggering
signals must persist for at least 30 ms. The operating mode for each binary
signal input can be defined.
The user can specify whether the presence (active ‘high’ mode) or absence
(active ‘low’ mode) of a voltage shall be interpreted as the logic “1” signal.
The contact data for the all-or-nothing relays permits them to be used either as
command relays or as signal relays. It is important to note that the contact rating
of the binary I/O modules (X) varies (see Chapter “Technical Data”). One signal
can also be assigned simultaneously to several output relays for the purpose of
contact multiplication.
Selecting a new bay type can change the configuration for slots A and B.
(Whether automatic configuration occurs, is defined in the setting MA IN : Auto-
assignme nt I/O.) Depending on the connection type chosen for the P438 – pin-
type or ring-type cable socket terminals – the symbolic slots A and B correspond
to the following slots:
Symbolic slot Pin-type cable socket terminals Ring-type cable socket terminals
A 06 12
B 07 14
The configuration of output relays for each bay type – in the case of auto-
assignment – is given in the List of Bay Types in the Appendix.
In the case of auto-assignment, the following notes apply:
Before selecting a new bay type, make sure that the output relays at slots A and B
are configured for functions from the DEVxx function groups only. Otherwise there
will be an error message, and the new bay type will not be activated.
Before selecting a new bay type, make sure that all output relays specified in the
List of Bay types for the selected bay type are actually available in the device.
Otherwise there will be an error message, and the new bay type will not be
activated.
An operating mode can be defined for each output relay. Depending on the
selected operating mode, the output relay will operate in either an energize-on-
signal (ES) mode or a normally-energized (NE) mode and in either a latching or
non-latching mode. For output relays operating in latching mode, the operating
mode setting also determines when latching will be cancelled.
mixture of red and green, i.e. when both functions assigned to the LED indicator
are simultaneously present.
Parameter Address
438 0 1000
[spacer]
The device type is displayed. This display cannot be altered.
[spacer] DVICE: S oft ware ve rsi on 1X X 024 219
[spacer]
The setting defines the software version of the device. This display cannot be
altered.
[spacer] DVICE: S W date 002 122
[spacer]
Date the software was created. This display cannot be altered.
Note: The centuries are not displayed. The supported dates range from January
1st, 1997, until November 7th, 2098.
[spacer] DVICE: S W ve rsion communic. 002 103
[spacer]
Software version for the device's communication software. This display cannot
be altered.
[spacer] DVICE: DM I EC 618 50 ve rsion 002 059
[spacer]
Software version of the communication software based on the device's protocol
per IEC 61850. This display cannot be altered.
[spacer] DVICE: Text vers .dat a mode l 002 121
0 0 255
[spacer]
Using the ‘text replacement tool' provided by the operating program, the user
can change the parameter descriptors (plain text designations) and load them
into the device. These customized data models contain an identifier defined by
the user while preparing the data model. This identifier is displayed at this point
in the menu tree. Standard data models have the identifier ‘0' (factory-set
default).
[spacer] DVICE: Lang uage v ersion 002 123
[spacer]
Identification of the change level of the texts of the data model. This display
cannot be altered.
[spacer] DVICE: F numb er 002 124
0 0 9999
[spacer]
The F number is the serial number of the device. The display cannot be altered.
[spacer] DVICE: AFS Orde r No. 001 000
0:
Parameter Address
0:
[spacer]
Order numbers for the device. The user cannot alter this number.
[spacer] DVICE: Order ext . No. 1 000 003
0 0 999
0 0 999
0 0 999
0 0 999
0 0 999
0 0 999
0 0 999
0 0 999
0 0 999
0 0 999
0 0 999
0 0 999
0 0 999
0 0 999
0 0 999
0 0 999
0 0 999
Parameter Address
0 0 999
0 0 999
0 0 999
0 0 999
0 0 999
0 0 999
0 0 999
0 0 999
0 0 999
0 0 999
[spacer]
Order extension numbers for the device.
[spacer] DVICE: M odule v ar. slot 1 086 050
Parameter Address
[spacer]
Item number of the module inserted in the respective slot 1 to 21.
The display always shows the actual component configuration at any given time.
[spacer] DVICE: M odule vers . slot 1 086 193
Parameter Address
[spacer]
Index letter specifying the version of the module fitted in the respective slot.
[spacer] DVICE: Variant of module A 086 047
[spacer]
Item number of module A in this design version.
Parameter Address
[spacer]
Index letter specifying the version of module A.
[spacer] DVICE: M AC add ress module A 104 061
2:
[spacer]
MAC address for the network hardware of the Ethernet module. This address is
introduced during manufacture and can only be read.
[spacer] DVICE: Variant of module L 086 048
[spacer]
Item number of module L in this design version.
[spacer] DVICE: Vers ion of module L 086 191
[spacer]
Index letter specifying the version of module L.
[spacer] DVICE: Variant of module B 086 049
[spacer]
Item number of module B in this design version.
[spacer] DVICE: Vers ion of module B 086 192
[spacer]
Index letter specifying the version of the digital bus module B.
[spacer] DVICE: Variant module B (a) 086 046
[spacer]
Item number of the analog bus module B in this design version.
[spacer] DVICE: Vers ion m odul e B (a) 086 189
[spacer]
Index letter specifying the version of the digital bus module B.
[spacer] DVICE: IP addres s 111 000
2:
2:
2:
[spacer]
Display of the IP address (or subnet mask, MAC address, respectively) of the
Ethernet interface of the processor module. This can be useful for network
analysis, especially if these settings have been retrieved via DHCP.
[spacer] DVICE: Cust omer ID data 1 000 040
Parameter Address
[spacer]
Set your numerically coded user data here for your records.
[spacer] DVICE: Location 001 201
0:
[spacer]
Reference input for the device's location as selected by user.
[spacer] DVICE: De vice ID 000 035
0 0 9999
[spacer]
ID code for use by the PC programs for operating and setting. Further
instructions on this setting are given in the description of the respective
operating program.
[spacer] DVICE: S ubst ation ID 000 036
0 0 9999
[spacer]
ID code for use by the PC programs for operating and setting. Further
instructions on this setting are given in the description of the respective
operating program.
[spacer] DVICE: Fee de r ID 000 037
0 0 9999
[spacer]
ID code for use by the PC programs for operating and setting. Further
instructions on this setting are given in the description of the respective
operating program.
[spacer] DVICE: De vice password 1 000 048
0 0 9999
Parameter Address
0 0 9999
[spacer]
ID code used by the operating program for identification purposes. See
description of the respective operating program for more detailed setting
instructions.
[spacer] DVICE: S W ve rsion DHMI 002 131
[spacer]
Internal software version numbers.
Parameter Address
1: Yes
[spacer]
When set to Yes it is apparent that the device is fitted with the local control
panel (HMI).
Parameter Address
2 0 65535
[spacer]
Version of Cyber Security implementation within the device. Easergy MiCOM 30
is starting with value 2 to be compatible with other Schneider Electric devices.
[spacer] CS: Num ber of us e rs 180 002
0 0 9999
[spacer]
Actual number of users in RBAC configuration.
[spacer] CS: Comms log out 180 032
0: don't execute
[spacer]
If executed, the current logged in user at PC port or via Tunneling interface is
logged out (can be only executed by Comms).
[spacer] CS: HM I logout 180 033
0: don't execute
[spacer]
If executed, the current logged in user at HMI interface is logged out (can be
only executed by HMI).
[spacer] CS: Comms us ername 180 043
0:
[spacer]
Display of the name of the user which is logged in either at PC-port or via
Tunneling.
[spacer] CS: HM I us ername 180 034
0:
[spacer]
Display of the name of the user which is logged in at HMI.
[spacer] CS: Us e r acces s role 180 013
0:
[spacer]
Role(s) of user which is actually logged in. It will be set by the device after
successful login and will be cleared when user is logged off. Of the first 5 roles of
a user, the first 3 chars of the roles names will be displayed separated with one
blank between each.
[spacer] CS: Max log in at te mpts 180 011
0 0 9999
[spacer]
Number of possible login attempts or blocked (blocked means no limitation of
attempts).
[spacer] CS: Log in at te mpt s l eft 180 010
0 0 9999
[spacer]
Remaining login attempts.
Parameter Address
0 0 1800 s
[spacer]
Time how long login shall be blocked after erroneous login attempts or blocked
(blocked means it will not getting active).
[spacer] CS: Block time left 180 012
0 0 1800 s
[spacer]
Remaining blocking login time after erroneous login attempts.
[spacer] CS: Res ult E PW s ett ing 180 041
0 -5 0
[spacer]
Display of a value to informe on the result of the password setting. (EPW =
Encrypted Password)
[spacer] CS: Change p inco de 180 003
0 0 0
[spacer]
Change the PIN code using the navigation keys of the HMI. It is not necessary at
communication interface.
[spacer] CS: Config dis abled 180 044
1: Yes
[spacer]
Configure disabled or not.
[spacer] CS: Recovery Pass wor d 180 014
0:
[spacer]
Display of the Token and allow entry for reset to factory password.
[spacer] CS: Res et RBAC 180 045
12 1 12
[spacer]
Only on HMI. Starting reset timer and display code.
Parameter Address
tion keys
061 000: MAIN: Without function
[spacer]
Assignment of functions to the function keys. Either a single function or a menu
jump list may be selected. There are two menu jump lists, which are assembled
at LOC: Fct. menu jmp lis t 1 or LO C: F ct . me nu jmp list 2,
respectively.
[spacer] F_KEY: Oper ating mode F 1 080 132
1: Key
1: Key
1: Key
1: Key
1: Key
1: Key
[spacer]
Choice between operation of the function key as a key or switch.
[spacer] F_KEY: Re tur n time fct .k e ys 003 037
60 60 60000 s
[spacer]
Once the password has been entered, the function keys remain active for no
longer than this time. Thereafter, the function keys are disabled until the
password is entered again.
[spacer] F_KEY: Pas s wor d funct. key 1 003 036
0 0 4444
Parameter Address
0 0 4444
0 0 4444
0 0 4444
0 0 4444
0 0 4444
[spacer]
Definition of the password for enabling the function keys.
Parameter Address
2: English
[spacer]
Language in which texts will be displayed on the user interface (HMI).
[spacer] LOC: De cim al de limit er 003 021
1: Dot
[spacer]
Character to be used as decimal delimiter on the local control panel.
[spacer] LOC: Dis pl. ex t.de v.de sig 221 032
[spacer]
This setting defines whether the external device designations shall be displayed
on the Bay Panel.
[spacer] LOC: Dis play L/ R 221 070
[spacer]
This setting defines whether the control site – “Local” or “Remote” – shall be
displayed on the bay panel.
[spacer] LOC: Dis pl. inte rl. stat . 221 071
[spacer]
This setting defines whether the “Locked” or “Unlocked” status shall be
displayed on the bay panel.
[spacer] LOC: Pas s word 003 035
1234 0 4444
[spacer]
The password to be used for changing settings from the local control panel can
be defined here.
[spacer] LOC: Pas s word L / R 221 040
1423 0 4444
[spacer]
The password used to change the setting from “Remote” to “Local” control can
be defined here. (Switching from “Local” to “Remote” control occurs without
checking the password.)
[spacer] LOC: Bus bar1 Name by Use r 218 191
0:
0:
Parameter Address
0:
[spacer]
Setting for the busbar designations to be displayed on the Bay Panel. At
LOC: Bus bar1 Name by Use r any text (max. 3 characters) may be
entered which will then be used as the designation, if the associated parameter
LOC: De signat ion busbar 1 has been set to BB-User Name. When
instead one of the pre-defined designations is selected at L OC: Designat ion
busbar 1 it will be used and L OC : Busbar 1 Name by User will be
ignored. A designation with more than 3 characters is internally truncated. (The
same is true of BB2,...)
[spacer] LOC: BB S ect.1-Name Use r 218 195
0:
0:
[spacer]
Setting for the busbar section designations to be displayed on the Bay Panel. At
LOC: BB S ect.1-Name Use r any text (max 3 characters) may be entered
which will then be used as the designation, if the associated parameter
LOC: De signat. bus se ct .1 has been set to BB-Sect.User Name. When
one of the pre-defined designations is selected at LOC: De signat. bus
sect.1 it will be used and LOC : BB S ect .1 -Na meUse r will be ignored. A
designation with more than 3 characters is internally truncated. (The same is
true of busbar section 2.)
[spacer] LOC: Character se t 221 038
[spacer]
The user can choose between several character sets to represent switchgear
and their switching states on the Bay Panel.
Note: Character set 3 is identical to character set 1 in the factory default
setting, but can be replaced by an user-defined character set, by applying an
accessory tool to the operating program.
[spacer] LOC: Fct. re set ke y 005 251
[spacer]
Selection of counters and memories that are reset by pressing the RESET key on
the local control panel. (Resetting LED indicators and measured event values is
permanently assigned internally, so that they are always reset when the RESET
key is pressed.)
Parameter Address
[spacer]
Selection of up to 16 functions to be triggered when pressing the read key.
Event counters and event recordings are offered for selection. If several
functions have been selected then they will be sequentially triggered by
repeated pressing of the read key.
[spacer] LOC: Oper ation mode 011 240
0: LOC Direct
[spacer]
This setting defines which of the three implemented operating modes the P438
shall use for the local control of switchgear units via LOC.
[spacer] LOC: SI reque st 221 118
1: Yes
[spacer]
This setting defines whether or not the check of the interlock equations, that is
carried out with the local control of switchgear units, also includes a check of
station interlocking.
[spacer] LOC: Fct. ass ign. L/R k e y 225 208
[spacer]
This setting defines whether the (electric) key-operated switch switches
between remote / local control (L↔R) or between remote+local control / local
control (R&L↔L).
[spacer] LOC: Fct. m enu jmp li st 1 030 238
[spacer]
Selection of specified functions which will be sequentially displayed by repeated
reading of the menu jump list 1 (or 2).
[spacer] LOC: Fct. Operat ion P anel 053 007
[spacer]
Definition of the values to be displayed on the Measured Value Panel also
referred to as the Operation Panel.
[spacer] LOC: Fct. Ove r lo ad Pane l 053 005
[spacer]
Definition of the values to be displayed on the Overload Panel.
[spacer] LOC: Fct. Sig nal P anel 221 072
[spacer]
Definition of the values to be displayed on the Signal Panel.
Parameter Address
[spacer]
Activation of the automatic switching to the Signal Panel at every change of
state of a configured signal.
[spacer] LOC: St at.ind.S ign.P anel 221 074
[spacer]
Definition of display type of active / inactive signals on the Signal Panel.
[spacer] LOC: Indicat.S ign .P anel 221 075
[spacer]
Definition of signal type at change of state and response to an acknowledge
command.
[spacer] LOC: Sig n.caus .S ign.P anel 221 078
[spacer]
Definition of cause for signaling (every change of state / incoming signals only).
[spacer] LOC: Fct. Fault Panel 053 003
[spacer]
Definition of the values to be displayed on the Fault Panel.
[spacer] LOC: Fct.as g. num. dis pl. 221 041
[spacer]
Definition of the measured values to be displayed on the Bay Panel in numerical
form.
[spacer] LOC: Fct. asg . b ar displ. 221 042
[spacer]
Definition of the measured values to be displayed on the Bay Panel in bar form.
Note: Measured values to be displayed in bar chart form must also be selected
for display as numerical measured values. However, not all measured values
that can be displayed in numerical form can also be displayed in bar chart form!
In such cases, a dummy or placeholder must be included in the selection list for
the bar chart display at the same point at which a measured value that cannot
be displayed in bar chart form appears in the selection list for numerical
measured values.
Example: Current IB is to be displayed. In this case, either the primary current
IB or the per-unit current IB shall be selected for the numerical display. The per-
unit current IB shall be entered at the same position in the selection list for the
bar chart display.
[spacer] LOC: Bar disp lay ty pe 221 039
[spacer]
Disabling the bar chart display or definition of the orientation of the bar chart to
display measured values on the Bay Panel.
Parameter Address
[spacer]
Scaling of measured current values to be displayed in bar chart form.
[spacer] LOC: Scal. bar dis play V 221 045
[spacer]
Scaling of measured voltage values to be displayed in bar chart form.
[spacer] LOC: Dis play b ar scale 221 046
[spacer]
Setting this window can disable the scalable bar chart.
[spacer] LOC: Hold- tim e for P anels 031 075
[spacer]
Setting for the time period during which a panel is displayed, before switching to
the next panel. This setting is only relevant if more values are selected than can
be shown on the LC-Display.
[spacer] LOC: Hold- t. meas.v. dis pl 031 072
Blocked 1 60 s
[spacer]
Always when the time period set here has elapsed the next value will be shown
on the Bay Panel display. With a setting to Blocked this automatic switching
forward to the next measured value will be deactivated. Independent of this the
next or the previous configured measured value may be selected by pressing
the keys “cursor down” or “cursor up”.
[spacer] LOC: Autom . re t ur n t ime 003 014
[spacer]
If the user does not press a key on the local control panel during this set time
period, the change-enabling function is deactivated.
[spacer] LOC: Re t ur n time selec t. 221 030
[spacer]
If the user does not press a key on the local control panel during this set time
period, then the selection of a switchgear unit is cancelled.
[spacer] LOC: Re t ur n time illumi n. 003 023
[spacer]
If the user does not press a key on the local control panel during this set time
period, then the backlighting of the LCD display is switched off.
Parameter Address
[spacer]
Bay and device addresses are used to address the device in communication via
the PC interface. An identical setting must be selected for both addresses.
[spacer] PC: Baud rate 003 081
[spacer]
Baud rate of the PC interface.
[spacer] PC: Parit y bit 003 181
[spacer]
Set the same parity that is set at the interface of the PC connected to the P438.
[spacer] PC: Spontan. sig. e nable 003 187
[spacer]
Enable for the transmission of spontaneous signals via the PC interface.
[spacer] PC: Select. s pontan. si g. 003 189
[spacer]
Selection of spontaneous signals for transmission via the PC interface.
[spacer] PC: Trans m.enab.cyc l. dat 003 084
[spacer]
Enable for the cyclic transmission of measured values via the PC interface.
[spacer] PC: Cycl. d ata ILS t e l. 003 185
[spacer]
Selection of the measured values that are transmitted in a user-defined
telegram via the PC interface.
[spacer] PC: De lta V 003 055
[spacer]
A measured voltage value is transmitted via the PC interface if it differs by the
set delta quantity from the last measured value transmitted.
[spacer] PC: De lta I 003 056
[spacer]
A measured current value is transmitted via the PC interface if it differs by the
set delta quantity from the last measured value transmitted.
Parameter Address
[spacer]
The active power value is transmitted via the PC interface if it differs by the set
delta quantity from the last measured value transmitted.
[spacer] PC: De lta f 003 057
[spacer]
The measured frequency value is transmitted via the PC interface if it differs by
the set delta from the last measured value transmitted.
[spacer] PC: De lta T 003 156
[spacer]
The measured temperature value is transmitted via the PC interface if it differs
by more than the set delta from the last measured value transmitted.
[spacer] PC: De lta Z 003 157
[spacer]
The measured operating impedance value is transmitted via the PC interface if it
differs by more than the set delta from the last measured value transmitted.
[spacer] PC: De lta phi 003 158
[spacer]
The measured load angle value is transmitted via the PC interface if it differs by
more than the set delta from the last measured value transmitted.
[spacer] PC: De lta meas.v.ILS te l 003 155
[spacer]
The telegram is transmitted if a measured value differs by the set delta quantity
from the last measured value transmitted.
[spacer] PC: De lta t 003 058
[spacer]
All measured values are transmitted again via the PC interface after this time
period has elapsed – provided that transmission has not been triggered by the
other delta conditions.
[spacer] PC: Time-out 003 188
[spacer]
Setting for the time to elapse after the last telegram exchange via the PC
interface before activating the second communication channel of
communication module A.
Parameter Address
communication
interface 1
0: Without
[spacer]
Cancelling function group COMM1 or including it in the configuration. If the
function group is cancelled from the configuration, then all associated settings
and signals are hidden, with the exception of this setting.
[spacer] COMM 1: General enabl e USE R 003 170
0: No
[spacer]
Disabling or enabling communication interface 1.
[spacer] COMM 1: Basic IEC87 0-5 e nabl 003 215
[spacer]
Common settings for enabling all protocols based on IEC 870-5-xxx.
[spacer] COMM 1: Addit . - 10 1 e nable 003 216
[spacer]
Enabling additional settings that are relevant for the protocol based on
IEC 870-5-101.
[spacer] COMM 1: Addit . I LS e nable 003 217
[spacer]
Enabling additional settings that are relevant for the ILS protocol.
[spacer] COMM 1: MODB US e nable 003 220
[spacer]
Enabling settings relevant for the MODBUS protocol.
[spacer] COMM 1: DNP3 enable 003 231
[spacer]
Enabling settings relevant for the DNP 3.0 protocol.
[spacer] COMM 1: COUR IER e nable 103 040
[spacer]
Enabling settings relevant for the COURIER protocol.
[spacer] COMM 1: Com m unicat. prot ocol 003 167
[spacer]
Select the communication protocol that shall be used for the communication
interface.
Parameter Address
[spacer]
The user may select between two variants of the 103 protocol.
Note: This setting is hidden unless the IEC 870-5-xxx protocol is enabled.
[spacer] COMM 1: MODB US prot . variant 003 214
[spacer]
The user may select between two variants of the MODBUS protocol.
Note: This setting is hidden unless the MODBUS protocol is enabled.
[spacer] COMM 1: Line idle stat e 003 165
[spacer]
Setting for the line idle state indication.
[spacer] COMM 1: Baud rat e 003 071
[spacer]
Baud rate of the communication interface.
[spacer] COMM 1: Parity bit 003 171
[spacer]
Set the same parity that is set at the interface of the control system connected
to the P438.
Parameter Address
[spacer]
The P438 monitors telegram transmission to make sure that no excessive pause
occurs within a telegram. This monitoring function can be disabled if it is not
required.
Note: This setting is only necessary for modem transmission.
[spacer] COMM 1: Mon. tim e pol ling 003 202
[spacer]
The time between two polling calls from the communication master must be less
than the time set here.
[spacer] COMM 1: Octet comm. addre ss 003 072
[spacer]
The communication address and the ASDU address are used to identify the
device in communication via the interface. An identical setting must be selected
for both addresses.
“ASDU”: Application Service Data Unit
[spacer] COMM 1: Oct.2 comm.addr.DNP 3 003 240
[spacer]
In the DNP 3.0 protocol, a 16-bit address is used to identify devices.
The address that can be set here is the higher-order octet, whereas the address
set at COM M1: Octet comm. addr ess is the lower-order octet of the
DNP address.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
Parameter Address
1: Single character E5
[spacer]
The following transmission frame formats are available (according to the
standard):
● Short message FT 1.2: short message with a fixed block length of 5
characters
● Single character E5: single control character
[spacer] COMM 1: Address mode 003 168
1: Physical
[spacer]
Setting for the address mode.
[spacer] COMM 1: Tes t monit or on 003 166
[spacer]
Setting specifying whether data shall be recorded for service activities.
[spacer] COMM 1: Name of manufac ture r 003 161
[spacer]
Setting for the name of the manufacturer.
Note:
● This setting can be changed to ensure compatibility.
● This setting is hidden unless an IEC 870-5 protocol is enabled.
[spacer] COMM 1: Octet address ASD U 003 073
[spacer]
The communication address and the ASDU address are used to identify the
device in communication via the interface. An identical setting must be selected
for both addresses.
Note: This setting is hidden unless an IEC 870-5 protocol is enabled.
“ASDU”: Application Service Data Unit
Parameter Address
[spacer]
Enable for the transmission of spontaneous signals via the communication
interface.
Note: This setting is hidden unless an IEC 870-5 protocol is enabled.
[spacer] COMM 1: Se le ct. s pont an.sig. 003 179
[spacer]
Selection of spontaneous signals for transmission via “logical” communication
interface 1.
[spacer] COMM 1: Transm .enab.c ycl.dat 003 074
[spacer]
Enabling of cyclic transmission of measured values via the communication
interface.
Note: This setting is hidden unless an IEC 870-5 protocol is enabled.
[spacer] COMM 1: Cycl. dat a ILS t e l. 003 175
[spacer]
Selection of the measured values that are transmitted in a user-defined
telegram via the communication interface.
Note: This setting is hidden unless an IEC 870-5 protocol is enabled.
[spacer] COMM 1: Delta V 003 050
[spacer]
A measured voltage value is transmitted via the communication interface if it
differs by the set delta quantity from the last measured value transmitted.
Note: This setting is hidden unless an IEC 870-5 protocol is enabled.
[spacer] COMM 1: Delta I 003 051
[spacer]
A measured current value is transmitted via the communication interface if it
differs by the set delta quantity from the last measured value transmitted.
Note: This setting is hidden unless an IEC 870-5 protocol is enabled.
Parameter Address
[spacer]
The active power value is transmitted via the communication interface if it
differs by the set delta quantity from the last measured value transmitted.
Note: This setting is hidden unless an IEC 870-5 protocol is enabled.
[spacer] COMM 1: Delta f 003 052
[spacer]
The measured frequency value is transmitted via the communication interface if
it differs by the set delta quantity from the last measured value transmitted.
Note: This setting is hidden unless an IEC 870-5 protocol is enabled.
[spacer] COMM 1: Delta T 003 251
[spacer]
The measured temperature is transmitted via the communication interface if it
differs by more than the set delta quantity from the last measured value
transmitted.
Note: This setting is hidden unless an IEC 870-5 protocol is enabled.
[spacer] COMM 1: Delta Z 003 252
[spacer]
The measured operating impedance is transmitted via the communication
interface if it differs by more than the set delta quantity from the last measured
value transmitted.
Note: This setting is hidden unless an IEC 870-5 protocol is enabled.
[spacer] COMM 1: Delta phi 003 253
[spacer]
The measured load angle is transmitted via the communication interface if it
differs by more than the set delta quantity from the last measured value
transmitted.
Note: This setting is hidden unless an IEC 870-5 protocol is enabled.
[spacer] COMM 1: Delta me as. v.ILS t el 003 150
[spacer]
The telegram is transmitted if a measured value differs by the set delta quantity
from the last measured value transmitted.
Note: This setting is hidden unless an IEC 870-5 protocol is enabled.
Parameter Address
[spacer]
All measured values are transmitted again via the communication interface after
this time period has elapsed – provided that transmission has not been triggered
by the other delta conditions.
Note: This setting is hidden unless an IEC 870-5 protocol is enabled.
[spacer] COMM 1: Delta t (e ne r gy) 003 151
[spacer]
The measured values for active energy and reactive energy are transmitted via
the communication interface after this time has elapsed.
Note: This setting is hidden unless an IEC 870-5 protocol is enabled.
[spacer] COMM 1: Cont in. ge ner al scan 003 077
[spacer]
A continuous or background general scan means that the P438 transmits all
settings, signals, and monitoring signals through the communication interface
during slow periods when there is not much activity. This ensures that there will
be data consistency with a connected control system. The time to be set defines
the minimum time difference between two telegrams.
Note: This setting is hidden unless an IEC 870-5 protocol is enabled.
[spacer] COMM 1: Com m . addr ess le ngth 003 201
[spacer]
Setting for the communication address length.
Note: This setting is hidden unless the IEC 870-5-101 protocol is set.
[spacer] COMM 1: Octet 2 comm. addr. 003 200
[spacer]
Setting for the length of the higher-order communication address.
Note: This setting is hidden unless the IEC 870-5-101 protocol is set.
[spacer] COMM 1: Caus e transm. le ngth 003 192
[spacer]
Setting for the length of the cause of transmission.
Note: This setting is hidden unless the IEC 870-5-101 protocol is set.
Parameter Address
[spacer]
Setting for the length of the common address for identification of telegram
structures.
Note: This setting is hidden unless the IEC 870-5-101 protocol is set.
“ASDU”: Application Service Data Unit
[spacer] COMM 1: Octet 2 addr. ASD U 003 194
[spacer]
Setting for the length of the common higher-order address for identification of
telegram structures.
Note: This setting is hidden unless the IEC 870-5-101 protocol is set.
“ASDU”: Application Service Data Unit
[spacer] COMM 1: Addr.le ngth inf. obj. 003 196
[spacer]
Setting for the length of the address for information objects.
Note: This setting is hidden unless the IEC 870-5-101 protocol is set.
[spacer] COMM 1: Oct.3 addr. inf.obj. 003 197
[spacer]
Setting for the length of the higher-order address for information objects.
Note: This setting is hidden unless the IEC 870-5-101 protocol is set.
[spacer] COMM 1: Inf .No.<- >funct.t ype 003 195
[spacer]
Setting specifying whether information numbers and function type shall be
reversed in the object address.
Note: This setting is hidden unless the IEC 870-5-101 protocol is set.
[spacer] COMM 1: Tim e tag length 003 198
[spacer]
Setting for the time tag length.
Note: This setting is hidden unless the IEC 870-5-101 protocol is set.
[spacer] COMM 1: AS DU1 / ASDU20 conv . 003 190
[spacer]
Setting specifying whether telegram structure 1 or 20 shall be converted as a
single signal or double signal.
Note: This setting is hidden unless the IEC 870-5-101 protocol is set.
“ASDU”: Application Service Data Unit
Parameter Address
[spacer]
Setting specifying whether telegram structure 2 shall be converted as a single
signal or double signal.
Note: This setting is hidden unless the IEC 870-5-101 protocol is set.
“ASDU”: Application Service Data Unit
[spacer] COMM 1: Init ializ. signal 003 199
[spacer]
Setting specifying whether an initialization signal shall be issued.
Note: This setting is hidden unless the IEC 870-5-101 protocol is set.
[spacer] COMM 1: Balance d ope ration 003 226
[spacer]
Setting that determines whether communication takes place on a balanced basis
(full duplex operation).
Note: This setting is hidden unless the IEC 870-5-101 protocol is set.
[spacer] COMM 1: Direction bit 003 227
[spacer]
Setting for the transmission direction. Normally this value will be set to '1' at
the control center and to '0' at the substation.
Note: This setting is hidden unless the IEC 870-5-101 protocol is enabled.
[spacer] COMM 1: Tim e- out int erv al 003 228
[spacer]
Setting for the maximum time that will elapse until the status signal for the
acknowledgment command is issued.
Note: This setting is hidden unless the IEC 870-5-101 protocol is set.
[spacer] COMM 1: Reg.asg. sel ec. cmds 003 210
[spacer]
MODBUS registers in the range 00301 to 00400 are assigned to the selected
commands. Assignment is made in the order of selection. This means that the
first command is given the register no. 00301, the second the register no.
00302, etc.
Note: This setting is hidden unless the MODBUS protocol is enabled.
[spacer] COMM 1: Reg.asg. sel ec. si g. 003 211
[spacer]
MODBUS registers in the range 10301 to 10400 are assigned to the selected
signals. Assignment is made in the order of selection. This means that the first
signal is given the register no. 10301, the second the register no. 10302, etc.
Note: This setting is hidden unless the MODBUS protocol is enabled.
Parameter Address
[spacer]
MODBUS registers in the range 30301 to 30400 are assigned to the selected
measured values. Assignment is made in the order of selection. This means that
the first measured value is given the register no. 30301, the second the register
no. 30302, etc.
Note: This setting is hidden unless the MODBUS protocol is enabled.
[spacer] COMM 1: Reg.asg. sel . par am. 003 213
[spacer]
MODBUS registers in the range 40301 to 40400 are assigned to the selected
parameters. Assignment is made in the order of selection. This means that the
first parameter is given the register no. 40301, the second the register no.
40302, etc.
Note: This setting is hidden unless the MODBUS protocol is enabled.
[spacer] COMM 1: Delta t ( MO DBUS) 003 152
[spacer]
All MODBUS registers are transmitted again through the communication
interface after this time has elapsed.
Note: This setting is hidden unless the MODBUS protocol is enabled.
[spacer] COMM 1: Autom .eve nt c onfirm. 003 249
[spacer]
Setting specifying whether an event must be confirmed by the master in order
for an event to be deleted from the 'event queue'.
Note: This setting is hidden unless the MODBUS protocol is enabled.
[spacer] COMM 1: Phys . Char act . De lay 003 241
[spacer]
Number of bits that must pass between the receipt of the 'request' and the start
of sending the 'response'.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
[spacer] COMM 1: Phys . Char . Time out 003 242
[spacer]
Number of bits that may be missing from the telegram before receipt is
terminated.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
[spacer] COMM 1: Link Confirm. M ode 003 243
[spacer]
Setting for the acknowledgment mode of the link layer.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
Parameter Address
[spacer]
Setting for the time period within which the master must acknowledge at the
link layer.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
[spacer] COMM 1: Link Max. Re tr ie s 003 245
[spacer]
Number of repetitions that are carried out on the link layer if errors have
occurred during transmission (such as failure to acknowledge).
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
[spacer] COMM 1: Appl.Con firm.T ime out 003 246
[spacer]
Setting for the time period within which the master must acknowledge at the
application layer.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
[spacer] COMM 1: Appl. Ne ed Time De l. 003 247
[spacer]
Time interval within which the slave requests time synchronization cyclically
from the master.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
[spacer] COMM 1: Ind ./cl. bin. input s 003 232
[spacer]
Selection of data points and data classes for object 1 – binary inputs.
Assignment of indices is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
[spacer] COMM 1: Ind ./cl. bin.output s 003 233
[spacer]
Selection of data points and data classes for object 10 – binary outputs.
Assignment of indices is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
[spacer] COMM 1: Ind ./cl. bin. count . 003 234
[spacer]
Selection of data points and data classes for object 20 – binary counters.
Assignment of indexes is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
Parameter Address
[spacer]
Selection of data points and data classes for object 30 – analog inputs.
Assignment of indices is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
[spacer] COMM 1: Ind ./cl. analog outp 003 236
[spacer]
Selection of data points and data classes for object 40 – analog outputs.
Assignment of indices is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
[spacer] COMM 1: Delta me as. v. ( DNP 3 ) 003 250
[spacer]
Initialization value of threshold values for transmission of measured values in
object 30. The threshold values can be changed separately by the master for
each measured value by writing to object 34, 'analog input reporting deadband'.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
[spacer] COMM 1: Delta t ( DNP 3) 003 248
[spacer]
Cycle time for updating DNP object 30 (analog inputs).
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
[spacer] COMM 1: Com m and sel ect ion 103 042
[spacer]
Selection of commands to be issued via the COURIER protocol.
Note: This setting is hidden unless the COURIER protocol is enabled.
[spacer] COMM 1: Signal se lec tion 103 043
[spacer]
Selection of signals to be transmitted via the COURIER protocol.
Note: This setting is hidden unless the COURIER protocol is enabled.
[spacer] COMM 1: Meas . v al. sel ect ion 103 044
[spacer]
Selection of measured values to be transmitted via the Courier protocol.
Note: This setting is hidden unless the Courier protocol is enabled.
[spacer] COMM 1: Param et er s ele ct ion 103 045
[spacer]
Selection of settings to be altered via the Courier protocol.
Note: This setting is hidden unless the Courier protocol is enabled.
Parameter Address
[spacer]
Cycle time at the conclusion of which the selected measured values are again
transmitted.
Note: This setting is hidden unless the COURIER protocol is enabled.
Parameter Address
communication
interface 2
0: Without
[spacer]
Cancelling function group COMM2 or including it in the configuration. If the
function group is cancelled from the configuration, then all associated settings
and signals are hidden, with the exception of this setting.
[spacer] COMM 2: General enabl e USE R 103 170
[spacer]
Disabling or enabling communication interface 2.
[spacer] COMM 2: Line idle stat e 103 165
[spacer]
Setting for the line idle state indication.
[spacer] COMM 2: Baud rat e 103 071
[spacer]
Baud rate of the communication interface.
[spacer] COMM 2: Parity bit 103 171
[spacer]
Set the same parity that is set at the interface of the control system connected
to the P438.
[spacer] COMM 2: Dead t ime moni toring 103 176
[spacer]
The P438 monitors telegram transmission to make sure that no excessive pause
occurs within a telegram. This monitoring function can be disabled if it is not
required.
Note: This setting is only necessary for modem transmission.
[spacer] COMM 2: Mon. time pol ling 103 202
[spacer]
The time between two polling calls from the communication master must be less
than the time set here.
[spacer] COMM 2: Posit ive ackn. faul t 103 203
0: No
[spacer]
It is possible to set whether or not faults can be acknowledged positively after
transmission (and consequently deleted from the fault overview at the
COMM2/PC interface).
Parameter Address
[spacer]
The communication address and the ASDU address are used to identify the
device in communication via the interface. An identical setting must be selected
for both addresses.
“ASDU”: Application Service Data Unit
[spacer] COMM 2: Name of manufac ture r 103 161
[spacer]
Setting for the name of the manufacturer.
Note: This setting can be changed to ensure compatibility.
[spacer] COMM 2: Octet address ASD U 103 073
[spacer]
The communication address and the ASDU address are used to identify the
device in communication via the interface. An identical setting must be selected
for both addresses.
“ASDU”: Application Service Data Unit
[spacer] COMM 2: Spontan. s ig. enabl e 103 177
[spacer]
Enable for the transmission of spontaneous signals via the communication
interface.
[spacer] COMM 2: Se le ct. s pont an.sig. 103 179
[spacer]
Selection of spontaneous signals for transmission via communication interface 2.
[spacer] COMM 2: Transm .enab.c ycl.dat 103 074
[spacer]
Enable for the cyclic transmission of measured values via the communication
interface.
[spacer] COMM 2: Cycl. dat a ILS t e l. 103 175
[spacer]
Selection of the measured values transmitted in a user-defined telegram via the
communication interface.
[spacer] COMM 2: Delta V 103 050
[spacer]
A measured voltage value is transmitted via the communication interface if it
differs by the set delta quantity from the last measured value transmitted.
Parameter Address
[spacer]
A measured current value is transmitted via the communication interface if it
differs by the set delta quantity from the last measured value transmitted.
[spacer] COMM 2: Delta P 103 054
[spacer]
The active power value is transmitted via the communication interface if it
differs by the set delta quantity from the last measured value transmitted.
[spacer] COMM 2: Delta f 103 052
[spacer]
The measured frequency value is transmitted via the communication interface if
it differs by the set delta quantity from the last measured value transmitted.
[spacer] COMM 2: Delta T 103 251
[spacer]
The measured temperature is transmitted via the communication interface if it
differs by more than the set delta quantity from the last measured value
transmitted.
[spacer] COMM 2: Delta Z 103 252
[spacer]
The measured operating impedance is transmitted via the communication
interface if it differs by more than the set delta quantity from the last measured
value transmitted.
[spacer] COMM 2: Delta phi 103 253
[spacer]
The measured load angle is transmitted via the communication interface if it
differs by more than the set delta quantity from the last measured value
transmitted.
[spacer] COMM 2: Delta me as. v.ILS t el 103 150
[spacer]
The telegram is transmitted if a measured value differs by the set delta quantity
from the last measured value transmitted.
[spacer] COMM 2: Delta t 103 053
[spacer]
All measured values are transmitted again via the communication interface after
this time period has elapsed – provided that transmission has not been triggered
by the other delta conditions.
Parameter Address
interface
0: Without
[spacer]
Cancelling function group COMM3 or including it in the configuration.
This setting parameter is only visible if the relevant optional communication
module is fitted.
If the function group is cancelled from the configuration, then all associated
settings and signals are hidden, with the exception of this setting.
[spacer] COMM 3: General enabl e USE R 120 030
0: No
[spacer]
Disabling or enabling communication interface 3.
[spacer] COMM 3: Baud rate 120 038
[spacer]
Adjustment of the baud rate for telegram transmission via the guidance
interface (InterMiCOM interface) so as to meet the requirements of the
transmission carrier.
[spacer] COMM 3: Source addr es s 120 031
1: 1
[spacer]
Address for send signals.
[spacer] COMM 3: Receiving addr es s 120 032
2: 2
[spacer]
Address for receive signals.
[spacer] COMM 3: Fct. ass ignm. se nd 1 121 001
Parameter Address
[spacer]
Assignment of functions for the 8 send signals.
[spacer] COMM 3: Fct. ass ignm. re c. 1 120 001
[spacer]
Configuration (assignment of functions) for the 8 receive signals
[spacer] COMM 3: Ope r. mode rec eiv e 1 120 002
1: Direct intertrip
1: Direct intertrip
1: Direct intertrip
1: Direct intertrip
[spacer]
Selection of Blocking or Direct intertrip for the operating mode of receive signals
1 to 4 (single-pole transmission).
[spacer] COMM 3: Ope r. mode rec eiv e 5 120 014
1: Direct intertrip
1: Direct intertrip
1: Direct intertrip
Parameter Address
1: Direct intertrip
[spacer]
Selection of Permissive or Direct intertrip for the operating mode of receive
signals 5 to 8 (two-pole transmission).
[spacer] COMM 3: Default value rec . 1 120 060
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
[spacer]
Definition of the default value for the 8 receive signals.
[spacer] COMM 3: Tim e- out comm.faul t 120 033
50 10 60000 ms
[spacer]
This timer triggers the alarm signals COMM3: C ommunications faul t
and S F MON: Com munic .fault CO M M3 the received signals to their user-
defined default values. Time-out occurs when the set time has elapsed since the
most recent 100% valid telegram was received.
[spacer] COMM 3: Tim e- out link fail. 120 035
5 0 600 s
[spacer]
Time indicating a persistent failure of the transmission channel. After this timer
stage has elapsed, alarm signals C OMM 3: C omm. link failure and
SFMO N: Comm .link fail.C OMM3 are raised. These can be mapped to
give the operator a warning LED or contact to indicate that maintenance
attention is required.
Parameter Address
Blocked 1 100 %
[spacer]
Percentage of corrupted messages compared to total messages transmitted
before an alarm is raised (CO M M3 : Lim.e x ce e d.,tel.e rr. and
SFMO N: Lim .e x ce ed.,t e l.e r r.). When this threshold is exceeded, the
receive signals are set to their user-defined default values.
Parameter Address
Communication
0: Without
[spacer]
Cancelling function group IEC or including it in the configuration. If the function
group is cancelled from the configuration, then all associated settings and
signals are hidden.
[spacer] IEC: Ge neral enable US ER 104 000
[spacer]
Enabling and disabling function group IEC.
[spacer] IEC: IEC 61850 e nabl e 104 077
[spacer]
Disabling or enabling IEC 61850.
[spacer] IEC: ET H COM M Mode 104 080
[spacer]
Selection of the redundant Ethernet protocol between PRP, HSR and RSTP.
[spacer] IEC: IEC prot. vari ant 104 084
[spacer]
Selection of the enabled Ethernet protocol.
[spacer] IEC: Block Port A/ B 104 073
[spacer]
When Port A/B blocked is activated, Port A for SEB or Port A&B for REB will be
disabled.
[spacer] IEC: Block Port C 104 074
[spacer]
When Port C blocked is activated, Port C will be disabled.
[spacer] IEC: Switch Config. Bank 104 043
[spacer]
This parameter can only be sent individually. Accepting the previously set
communication parameters as the active communication settings.
[spacer] IEC: Active Conf ig. Name 104 045
2:
[spacer]
Name of the configuration bank currently valid.
Setting is carried out with the IED Configurator.
Parameter Address
2:
[spacer]
Version number of the configuration bank currently valid.
Setting is carried out with the IED Configurator.
[spacer] IEC: Inact . C onfig. Name 104 047
2:
[spacer]
Name of the inactive configuration bank.
Setting is carried out with the IED Configurator.
[spacer] IEC: Inact . C onfig. Ve r s . 104 048
2:
[spacer]
Version number of the inactive configuration bank.
Setting is carried out with the IED Configurator.
[spacer] IEC: IED nam e 104 057
2:
[spacer]
Explicitly assigned unit name for the function in the system (IED); is part of the
Logical Device Name.
Important note: According to the IEC standard the name must consist of only
letters (A..Z, a..z), digits (0..9) and underscore characters (_), and the name
must start with a letter. Note that a non-standard name causes problems with
the IEC 61850 communication.
[spacer] IEC: IP address 104 001
2:
[spacer]
Assigned IP address of the device for the server function in the system.
Note: This is an information parameter ('read only') and its value is set from the
"IED Configurator" with Communications: IP Address.
[spacer] IEC: Subnet m ask 104 005
2:
[spacer]
The subnet mask defines which part of the IP address is addressed by the sub-
network and which part by the device that is logged-on to the network.
Note: This is an information parameter ('read only') and its value is set from the
"IED Configurator" with Communications: SubNet Mask.
[spacer] IEC: Gat eway addre s s 104 011
2:
[spacer]
This parameter shows the IPv4 address of the network gateway for
communication links to clients outside of the local network.
Note: This is an information parameter ('read only') and its value is set from the
"IED Configurator" with Communications: Gateway Address.
Parameter Address
2:
[spacer]
Assigned IP address 2 of the device for the server function in the system.
Note: This is an information parameter ('read only') and its value is set from the
"IED Configurator" with Communications: IP Address Interface 2 (If fitted).
[spacer] IEC: Subnet m ask 2 104 071
2:
[spacer]
The subnet mask 2 defines which part of the IP address 2 is addressed by the
sub-network and which part by the device that is logged-on to the network.
Note: This is an information parameter ('read only') and its value is set from the
"IED Configurator" with Communications: SubNet Mask Interface 2 (If fitted).
[spacer] IEC: Gat eway add re s s 2 104 072
2:
[spacer]
This parameter shows the IPv4 address of the network gateway 2 for
communication links to clients outside of the local network.
Note: This is an information parameter ('read only') and its value is set from the
"IED Configurator" with Communications: Gateway Address Interface 2 (If fitted).
[spacer] IEC: IP address VLAN 1 104 091
2:
2:
[spacer]
Assigned IP address of VLAN in the system.
Note: This is an information parameter ('read only') and its value is set from the
"IED Configurator" with Communications: IP Address.
[spacer] IEC: Identifier VLAN 1 104 092
0 0 65535
0 0 65535
[spacer]
Assigned VLAN ID in the system.
Note: This is an information parameter ('read only') and its value is set from the
"IED Configurator" with Communications: Vlan ID.
[spacer] IEC: Subnet m ask VL AN 1 104 093
2:
2:
[spacer]
The subnet mask of VLAN defines which part of the IP address is addressed by
the sub-network and which part by the device that is logged-on to the network.
Note: This is an information parameter ('read only') and its value is set from the
"IED Configurator" with Communications: VLAN Subnet Mask.
Parameter Address
2:
2:
[spacer]
This parameter shows the network gateway of the VLAN for communication links
to clients outside of the local network.
Note: This is an information parameter ('read only') and its value is set from the
"IED Configurator" with Communications: Gateway Address.
[spacer] IEC: SNTP s erve r 1 IP 104 202
2:
[spacer]
IP address of the preferred server used for clock synchronization.
Note: This is an information parameter ('read only') and its value is set from the
"IED Configurator".
[spacer] IEC: SNTP s erve r 2 IP 104 210
2:
[spacer]
IP address of the backup server used for clock synchronization.
Note: This is an information parameter ('read only') and its value is set from the
"IED Configurator".
[spacer] IEC: SGCB Re svT ms 104 199
30 0 600
[spacer]
The configuration attribute ResvTms defines the time interval in seconds for
which the reservation of a SGCB is granted by a client. A reservation of a SGCB
starts after a successful selection of a Setting Group using the service
SelectEditSG. The client is granted to edit one or multiple parameters of this
SGCB if this time has not elapsed.
[spacer] IEC: SigGGI O1 sel ect ion 104 064
[spacer]
Optional signal assignment for a transmission per communication protocol
IEC 61850 based on the selection table of the binary inputs (opto coupler
inputs).
[spacer] IEC: Diff . local t ime 104 206
[spacer]
Time difference between UTC and local time at the devices' substation (IED).
[spacer] IEC: Diff . d ayl.sav. t ime 104 207
[spacer]
Time difference of the daylight saving time to standard time.
Parameter Address
[spacer]
This setting defines whether an automatic switching to daylight saving time is
wanted. If it is wanted, the time switching is executed upon receiving a related
SNTP frame.
[spacer] IEC: Dayl.sav.tim e s tar t 104 220
[spacer]
These three parameters define the date (e.g. at what day of the year) for
switching from standard time over to daylight saving time. Available for
IEC: Dayl.sav.tim e s tar t are the values First, Second, Third, Fourth, and
Last. For IEC: Dayl.sav.ti me st . d the seven weekdays are available so
that for example a setting like “on the last Sunday in March” may be used.
[spacer] IEC: Dayl.sav.t.st .0:00 + 104 223
[spacer]
Time period in minutes after midnight when daylight saving time is switched to
standard time. If for example the clock is advanced one hour from 2:00 AM to
3:00 AM the parameter IE C: D ayl.sav .t .st .0:00 + is set to 120 (minutes).
[spacer] IEC: Dayl.sav.tim e e nd 104 225
[spacer]
This parameter defines the date and time of day for the clock changeover from
daylight saving time to standard time. The setting is similar to that for the clock
changeover to daylight saving time.
Parameter Address
Orientated
Substation Events
0: Without
[spacer]
Cancelling function group GOOSE or including it in the configuration.
If the function group is cancelled from the configuration, then all associated
settings and signals are hidden.
Parameters included in this function group are only effective when function
group IEC is configured and enabled and when the parameters in this function
group have been activated by setting the parameter IEC: Switch Conf ig.
Bank.
[spacer] GOOSE: Gene ral e nable US ER 106 001
0: No
[spacer]
Enabling and disabling function group GOOSE.
[spacer] GOOSE: Input 1 fct.assig. 107 006
Parameter Address
Parameter Address
Parameter Address
Parameter Address
Parameter Address
Parameter Address
Parameter Address
[spacer]
Function assignment of the virtual binary GOOSE input to a binary logical state
signal on the device (IED) so that it can be processed further by the protection,
control or logic functions. The signal configured at this point will receive the
state of the data attribute, as configured above, and which was received with
the Dataset of GOOSE.
Parameter Address
0: Without
[spacer]
Cancelling function group VINP or including it in the configuration. If the function
group is cancelled from the configuration, then all associated settings and
signals are hidden.
[spacer] VINP: General e nable USE R 115 000
0: No
[spacer]
Disabling or enabling VINP function.
[spacer] VINP: I nput 1 fct .ass ig. 115 150
Parameter Address
Parameter Address
Parameter Address
[spacer]
Function assignment of the virtual binary inputs VINP to a binary logical state
signal on the device so that they can be processed further by the protection,
control or logic functions.
Parameter Address
0: Without
[spacer]
Cancelling function group IRIGB or including it in the configuration. If the
function group is cancelled from the configuration, then all associated settings
and signals are hidden.
[spacer] IRIGB: Gener al e nable US ER 023 200
[spacer]
Disabling or enabling the IRIG-B interface.
Parameter Address
[spacer]
Input filter which is activated when either the mode Active "high", filt. or Active
"low", filt. has been selected for INP: Ope r. mode U xxx. In order to
suppress transient interference peaks at the logic signal inputs it is suggested to
set this parameter to 6 [steps].
[spacer] INP: Fct. as signm. U 301 152 217
Parameter Address
Parameter Address
Parameter Address
Parameter Address
Parameter Address
Parameter Address
[spacer]
Assignment of functions to binary signal inputs.
[spacer] INP: Oper. m ode U 301 152 218
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
Parameter Address
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
Parameter Address
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
Parameter Address
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
Parameter Address
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
Parameter Address
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
Parameter Address
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
1: Active "high"
[spacer]
Selection of operating mode for binary signal inputs.
Parameter Address
0: Without
[spacer]
Cancelling function group MEASI or including it in the configuration.
If the function group is cancelled from the configuration, then all associated
settings and signals are hidden.
[spacer] MEASI: Ge ne ral enabl e US E R 011 100
[spacer]
Disabling or enabling analog measured data input.
[spacer] MEASI: E nable IDC p. u. 037 190
[spacer]
Setting for the minimum current that must flow in order for the P438 to display a
measured value > 0 (zero suppression).
[spacer] MEASI: I DC < ope n circuit 037 191
[spacer]
If the input current falls below the set threshold, the P438 will issue an “open
circuit” signal.
[spacer] MEASI: I DC 1 037 150
Parameter Address
[spacer]
Setting for the input current that will correspond to a linearized value that has
been set accordingly.
[spacer] MEASI: I DC ,lin 1 037 151
Parameter Address
[spacer]
Setting for the linearized current that will correspond to an input current that
has been set accordingly.
[spacer] MEASI: S caled val. IDC ,lin1 037 192
[spacer]
Setting for the scaled value of IDC,lin1.
[spacer] MEASI: S caled val.IDC ,l in2 0 037 193
[spacer]
Setting for the scaled value of IDC,lin20.
[spacer] MEASI: T ype of T empSe ns or s 004 254
0: PT 100
[spacer]
Selection of the temperature sensor type (PT 100, NI 100 or NI 120).
Parameter Address
output
060 000: MAIN: Without function
Parameter Address
Parameter Address
Parameter Address
Parameter Address
[spacer]
Assignment of functions to output relays.
[spacer] OUTP: Oper. mode K 3 01 151 046
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
Parameter Address
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
Parameter Address
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
Parameter Address
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
Parameter Address
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
[spacer]
Selection of operating mode for output relays.
Parameter Address
output
0: Without
[spacer]
Cancelling function group MEASI or including it in the configuration.
If the function group is cancelled from the configuration, then all associated
settings and signals are hidden. If the function group is cancelled from the
configuration, then all associated settings and signals are hidden.
[spacer] MEASO: Ge ne ral e nable US ER 031 074
0: No
[spacer]
Disabling or enabling the measured data output function.
[spacer] MEASO: Fct . as s ignm. BC D 053 002
[spacer]
Selection of the measured value to be transmitted in BCD form.
[spacer] MEASO: Hold t ime output BC D 010 010
[spacer]
Setting for the transmission time of the selected measured value in BCD form.
[spacer] MEASO: Scale B CD 016 082
[spacer]
Scaling factor setting for the measured value to be transmitted in BCD form.
The scaling factor is calculated according to the following formula:
M x,max
Scaling factor =
M x,scal
where:
Mx,scal: scaled measured value
Mx,max: maximum transmitted value for the selected measured value
0 0 399
Parameter Address
399 0 399
[spacer]
The variable Mx is to be issued in BCD form.
For measured values in the range “measured values to be issued” the output
value should change linearly with the measured value.
● Range of measured values for the variable Mx: Mx,RL1 ... Mx,RL2
● Range of associated scaled measured values: 0 ... 1
● Range of measured values to be issued: Mx,min ... Mx,max
● Range of scaled measured values to be issued: Mx,scal,min ... Mx,scal,max
● Designation of the set values in the data model: “Scaled min. val. BCD” ...
“Scaled max. val. BCD”
with:
Mx,scal,min = (Mx,min - Mx,RL1)/(Mx,RL2 - Mx,RL1)
Mx,scal,max = (Mx,max - Mx,RL1)/(Mx,RL2 - Mx,RL1)
BCD display values for measured values in the range “measured values to be
issued”; range: “BCD-Out min. value” ... “BCD-Out max. value”
BBCD display values for measured values ≤ Mx,min; range: “BCD-Out min.
value”
BCD display values for measured values ≥ Mx,max; range: “BCD-Out max.
value”
[spacer] MEASO: Fct . as s ignm. A- 1 053 000
[spacer]
Selection of the measured value to be transmitted in analog form.
[spacer] MEASO: Hold t ime output A- 1 010 114
[spacer]
Setting for the time delay for output of the selected measured value.
[spacer] MEASO: Scale d min. val. A-1 037 104
Parameter Address
[spacer]
After conversion via a characteristic the selected measured value Ax (x = 1, 2) is
to be issued as an output current. For this purpose a range “measured values to
be issued” is defined. In this range the characteristic has two linear sections,
which are separated by a knee point.
● Range of measured values for the variable Mx: Mx,RL1 ... Mx,RL2
● Range of associated scaled measured values: 0 ... 1
● Range of measured values to be issued: Mx,min ... Mx,max
● Range of scaled measured values to be output: Mx,scal,min ... Mx,scal,max
● Designation of the set values in the data model: „Scaled min. val. Ax“ ...
„Scaled max. val. Ax“
with:
Mx,scal,min = (Mx,min - Mx,RL1)/(Mx,RL2 - Mx,RL1)
Mx,scal,max = (Mx,max - Mx,RL1)/(Mx,RL2 - Mx,RL1)
● Designation of value for knee point: Mx,knee
● Designation of scaled knee point value: Mx,scaled,knee
● Designation of this set value in the data model: „Scaled knee val. Ax“
with:
Mx,scaled,knee = (Mx,knee - Mx,RL1)/(Mx,RL2 - Mx,RL1)
[spacer] MEASO: AnOut min. v al. A- 1 037 107
Parameter Address
[spacer]
Output current range for measured values in the range “measured values to be
issued”; designation in the data model: “An-Out min. val. Ax” ... “An-Out max.
val. Ax”
Output current to be set for measured values ≤ Mx,min; designation in the data
model: “An-Out min. val. Ax”
Output current to be set for measured values ≥ Mx,max; designation in the data
model: “An-Out max. val. Ax”
Output current to be set for measured values = Mx,knee; designation in the data
model: “AnOut knee point Ax”
with:
Mx,min ... Mx,max: measured values to be issued
[spacer] MEASO: Output value 1 037 120
[spacer]
Measured values of external devices, which must be scaled to 0 to 100%, can be
issued.
Parameter Address
[spacer]
Display of the operational readiness of the protection device.
The function MAIN: He althy is permanently assigned.
[spacer] LED: F ct.ass ig. H 2 y ell. 085 001
[spacer]
Display of the function assigned to LED indicator H 2.
The function MAIN: Blocke d/ fault y is permanently assigned.
[spacer] LED: F ct.ass ig. H 3 y ell. 085 004
[spacer]
Display of the function assigned to LED indicator H 3.
The function SFM ON: Warning (LED ) is permanently assigned.
[spacer] LED: F ct.ass ig. H 4 red 085 007
Parameter Address
Parameter Address
[spacer]
Assignment of functions to LED indicators.
[spacer] LED: F ct.ass ig. H17 red 085 185
[spacer]
Display of the function assigned to LED indicator H 17.
The function LOC: Edit mode is permanently assigned.
[spacer] LED: O pe rating mode H 1 085 182
1: ES updating
[spacer]
The operating mode ES updating is permanently assigned.
[spacer] LED: O pe rating mode H 2 085 002
1: ES updating
[spacer]
The operating mode ES updating is permanently assigned.
[spacer] LED: O pe rating mode H 3 085 005
1: ES updating
[spacer]
The ES updating operating mode is permanently assigned.
[spacer] LED: O pe rating mode H 4 085 008
3: ES reset (fault)
1: ES updating
1: ES updating
1: ES updating
Parameter Address
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
1: ES updating
[spacer]
Selection of operating mode for LED indicators.
[spacer] LED: O pe rating mode H 17 085 183
1: ES updating
[spacer]
The operating mode ES updating is permanently assigned.
Parameter Address
[spacer]
Assignment of communication interfaces to physical communication channels.
[spacer] MAIN: Cmd blocking USE R 103 213
[spacer]
Blocking of the command from the user interface (HMI) or PC interface.
[spacer] MAIN: Auto- assig nme nt I/ O 221 065
1: Yes
[spacer]
Disabling or enabling of automatic assignment of binary inputs and outputs to
the set bay type.
[spacer] MAIN: Type of bay 220 000
1 1 9999
[spacer]
Configuration of a bay type.
[spacer] MAIN: Prim .S ource TimeS ync 103 210
0: COMM1/IEC
[spacer]
Selection of the primary source for date and time synchronization. Available are
COMM1/IEC, COMM2/PC, IRIG-B or a binary input for minute signal pulses.
[spacer] MAIN: Backup SourceT ime Sy nc 103 211
1: COMM2/PC
[spacer]
Selection of the backup source for date and time synchronization. Available are
COMM1/IEC, COMM2/PC, IRIG-B or a binary input for minute signal pulses. The
backup source is used when there is no synchronization generated by the
primary source after MAIN: Time s ync. time-out has elapsed.
[spacer] MAIN: Tim e s ync. t ime -out 103 212
Blocked 1 60 min
[spacer]
Time-out setting for the time synchronization generated by the primary source.
Parameter Address
1: Current IA
2: Current IB
5: Voltage VA
6: Voltage VB/Vref
[spacer]
The user specifies the channel on which each physical variable is recorded.
Parameter Address
0: Without
[spacer]
Canceling function group DIST or including it in the configuration. If the function
group is cancelled from the configuration, then all associated settings and
signals are hidden.
Parameter Address
tection
0: Without
[spacer]
Cancelling function group DELTA or including it in the configuration.
If the function group is cancelled from the configuration, then all associated
settings and signals are hidden, with the exception of this setting.
Parameter Address
monitoring
0: Without
[spacer]
Cancelling function group MCMON or including it in the configuration.
If the function group is cancelled from the configuration, then all associated
settings and signals are hidden.
Parameter Address
time protection
0: Without
[spacer]
Cancelling function group BUOC or including it in the configuration. If the
function group is cancelled from the configuration, then all associated settings
and signals are hidden.
Parameter Address
protection
0: Without
[spacer]
Cancelling function group SOTF or including it in the configuration. If the
function group is cancelled from the configuration, then all associated settings
and signals are hidden.
Parameter Address
0: Without
0: Without
[spacer]
Cancelling function group PSIG or including it in the configuration. If the
function group is cancelled from the configuration, then all associated settings
and signals are hidden.
Parameter Address
control
0: Without
[spacer]
Cancelling function group ARC or including it in the configuration. If the function
group is cancelled from the configuration, then all associated settings and
signals are hidden.
Parameter Address
synchronism check
0: Without
[spacer]
Cancelling function group ASC or including it in the configuration. If any function
group is cancelled from the configuration, then all associated settings and
signals are hidden.
Parameter Address
current protection
0: Without
[spacer]
Cancelling function group DTOC or including it in the configuration. If the
function group is cancelled from the configuration, then all associated settings
and signals are hidden.
Parameter Address
current protection
0: Without
[spacer]
Cancelling function group DTOCA or including it in the configuration. If the
function group is cancelled from the configuration, then all associated settings
and signals are hidden.
Note: The function group DTOCA is active only with the setting
MAIN: Fe e de r mode = Autotransformer feed.
Parameter Address
current protection
0: Without
[spacer]
Cancelling function group DTOCB or including it in the configuration. If the
function group is cancelled from the configuration, then all associated settings
and signals are hidden.
Note: The function group DTOCB is active only with the setting
MAIN: Fe e de r mode = Autotransformer feed.
Parameter Address
rent protection
0: Without
[spacer]
Canceling function group IDMT or including it in the configuration. If the function
group is cancelled from the configuration, then all associated settings and
signals are hidden.
Parameter Address
rent protection
0: Without
[spacer]
Cancelling function group IDMTA or including it in the configuration. If the
function group is cancelled from the configuration, then all associated settings
and signals are hidden.
Note: The function group IDMTA is active only with the setting MAIN: Feed er
mode = Autotransformer feed.
Parameter Address
rent protection
0: Without
[spacer]
Cancelling function group IDMTB or including it in the configuration. If the
function group is cancelled from the configuration, then all associated settings
and signals are hidden.
Note: The function group IDMTB is active only with the setting M AIN: Feed er
mode = Autotransformer feed.
Parameter Address
0: Without
[spacer]
Cancelling function group DFRST or including it in the configuration.
If the function group is cancelled from the configuration, then all associated
settings and signals are hidden, with the exception of this setting.
Parameter Address
protection
0: Without
[spacer]
Cancelling function group THERM or including it in the configuration. If the
function group is cancelled from the configuration, then all associated settings
and signals are hidden, with the exception of this setting.
Parameter Address
tion
0: Without
[spacer]
Cancelling function group V<> or including it in the configuration. If the
function group is cancelled from the configuration, then all associated settings
and signals are hidden, with the exception of this setting.
Parameter Address
underfrequency pro‐
tection
0: Without
[spacer]
Canceling function group f<> or including it in the configuration. If the function
group is cancelled from the configuration, then all associated settings and
signals are hidden, with the exception of this setting.
Parameter Address
failure protection
0: Without
[spacer]
Cancelling function group CBF or including it in the configuration. If the function
group is cancelled from the configuration, then all associated settings and
signals are hidden, with the exception of this setting.
Parameter Address
condition monitoring
0: Without
[spacer]
Cancelling function group CBM or including it in the configuration. If the function
group is cancelled from the configuration, then all associated settings and
signals are hidden.
Parameter Address
monitoring
0: Without
[spacer]
Cancelling function group LIMIT or including it in the configuration. If the
function group is cancelled from the configuration, then all associated settings
and signals are hidden, with the exception of this setting.
Parameter Address
0: Without
[spacer]
Cancelling function group LOGIC or including it in the configuration.
If the function group is cancelled from the configuration, then all associated
settings and signals are hidden.
Parameter Address
0: Without
[spacer]
Cancelling function group LOG_2 (“Logic 2”) or including it in the configuration.
If the function group is cancelled from the configuration, then all associated
settings and signals are hidden.
Parameter Address
0: Without
[spacer]
Cancelling function group TIMER or including it in the configuration. If the
function group is cancelled from the configuration, then all associated settings
and signals are hidden.
Parameter Address
0: Without
0: Without
0: Without
0: Without
0: Without
0: Without
0: Without
0: Without
0: Without
0: Without
[spacer]
Cancelling function groups DEV01 to DEV03 or including them in the
configuration. If any function group is cancelled from the configuration, then all
associated settings and signals are hidden.
[spacer] DEV01: Funct . type, s ignal 210 034
242 1 254
242 1 254
242 1 254
242 1 254
242 1 254
242 1 254
242 1 254
Parameter Address
242 1 254
242 1 254
242 1 254
[spacer]
Setting the function type of the signal.
Note: If the IEC 870-5-101 communication protocol has been set, then the 'low
address' of the information object will be defined by this setting. If the ILS-C
protocol has been set, then this setting will correspond to DN2.
[spacer] DEV01: Inform. No., signal 210 035
1 0 254
3 0 254
5 0 254
7 0 254
9 0 254
11 0 254
13 0 255
15 0 254
17 0 254
19 0 254
[spacer]
Setting the information number of the signal.
Note: If the IEC 870-5-101 communication protocol has been set, then the 'high
address' of the information object will be defined by this setting. If the ILS-C
protocol has been set, then this setting will correspond to DN3.
[spacer] DEV01: Funct . type, c ommand 210 032
242 1 254
242 1 254
Parameter Address
242 1 254
242 1 254
242 1 254
242 1 254
242 1 254
242 1 254
242 1 254
242 1 254
[spacer]
Setting for the function type of the command.
Note: If the IEC 870-5-101 communication protocol has been set, then the “low
address” of the information object will be defined by this setting. If the ILS-
C protocol has been set, then this setting will correspond to DN2.
[spacer] DEV01: Inform. No., command 210 033
65 0 254
67 0 254
69 0 254
71 0 254
73 0 254
75 0 254
77 0 254
79 0 254
81 0 254
Parameter Address
83 0 254
[spacer]
Setting the information number of the command.
Note: If the IEC 870-5-101 communication protocol has been set, then the 'high
address' of the information object will be defined by this setting. If the ILS-C
protocol has been set, then this setting will correspond to DN3.
Parameter Address
1: With
[spacer]
Cancelling function group ILOCK or including it in the configuration. If the
function group is cancelled from the configuration, then all associated settings
and signals are hidden, with the exception of this setting.
Parameter Address
commands
1: With
[spacer]
Cancelling function group CMD_1 or including it in the configuration.
If the function group is cancelled from the configuration, then all associated
settings and signals are hidden, with the exception of this setting.
[spacer] CMD_1: Com mand C 0 01 config. 200 004
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
[spacer]
Cancelling the command or including it in the configuration. If the command is
cancelled, then all associated settings and signals are hidden, with the
exception of this setting.
Parameter Address
1: With
[spacer]
Cancelling function group SIG_1 or including it in the configuration.
If the function group is cancelled from the configuration, then all associated
settings and signals are hidden, with the exception of this setting.
[spacer] SIG_1: S ignal S 00 1 config. 226 007
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
[spacer]
Cancelling the signal or including it in the configuration. If a signal is cancelled,
then all associated settings and signals are hidden.
Parameter Address
0: Without
[spacer]
Cancelling function group COUNT or including it in the configuration. If the
function group is cancelled from the configuration, then all associated settings
and signals are hidden, with the exception of this setting.
7.1.3.1 Global
Parameter Address
[spacer]
When command blocking is activated, commands are rejected at the PC
interface.
[spacer] PC: Sig./m eas .val.bl ock . 003 086
[spacer]
When signal and measured value blocking is activated, no signals or measured
data are transmitted through the PC interface.
Parameter Address
communication
interface 1
1: Yes Fig. 3-11, (p. 3-19)
[spacer]
When command blocking is activated, commands are rejected at communication
interface 1.
[spacer] COMM 1: Sig./ meas.block .US E R 003 076
[spacer]
When signal and measured value blocking user is activated, no signals or
measured data are transmitted through communication interface COMM1.
Parameter Address
communication
interface 2
0: No Fig. 3-19, (p. 3-28)
[spacer]
When command blocking is activated, commands are rejected at communication
interface 2.
[spacer] COMM 2: Sig./ meas.block .US E R 103 076
[spacer]
When signal and measured value blocking user is activated, no signals or
measured data are transmitted through communication interface COMM2.
Parameter Address
Communication
1: Yes
[spacer]
When command blocking is activated, commands are rejected at IEC
communication interface.
[spacer] IEC: Ctrl b lock e d use r 221 125
[spacer]
When control blocking is activated, controls are rejected at IEC communication,
i.e no output data (digital by relays) will be issued to the process.
[spacer] IEC: Sig./me as.block.US E R 104 088
0: No
[spacer]
When signal and measured value blocking user is activated, no signals or
measured data are transmitted through IEC communication interface.
Parameter Address
output
0: No Fig. 3-41, (p. 3-69)
[spacer]
When this blocking is activated, all output relays are blocked.
Parameter Address
[spacer]
Switching the device off-line or on-line. Some parameters can only be changed
when protection is disabled.
[spacer] MAIN: Tes t m ode USER 003 012
[spacer]
When the test mode user is activated, signals or measured data for PC and
communication interfaces are labeled 'test mode'.
[spacer] MAIN: Nominal fr equ. fnom 010 030
50: 50 Hz Hz
[spacer]
Setting for the nominal frequency of the protected system.
[spacer] MAIN: Tim e tag 221 098
1: 1stEdge,OpMem sorted
[spacer]
For bay control function signals detected via binary signal inputs and
conditioned with debouncing it is now possible to select whether the time tag for
the signal is to be issued after debouncing or when the first pulse edge is
detected. Furthermore it is defined whether entries in the operating data
memory are made in chronological order or not.
[spacer] MAIN: Inom C.T. prim. 010 001
[spacer]
Setting for the primary nominal current of the main current transformers for
measurement of phase currents.
[spacer] MAIN: Iplaus / Id frst ,C Tpri m 010 016
[spacer]
Setting for the primary nominal current of the main current transformer for
measurement of CT Plausibility check current or defrost current.
[spacer] MAIN: Vnom V.T. prim. 010 002
[spacer]
Setting for the primary nominal voltage of the system transformer for
measurement of phase-to-ground and phase-to-phase voltages.
Parameter Address
[spacer]
Setting for the secondary nominal current of the system transformer for
measurement of phase currents. This also corresponds to the nominal device
current.
[spacer] MAIN: Iplaus / Id frst ,C Tnom 010 017
[spacer]
Setting for the secondary nominal current of the CT for measurement of CT
Plausibility check current or defrost current.
[spacer] MAIN: Vnom V.T. sec. 010 009
[spacer]
Setting for the secondary nominal voltage of the system transformer for
measurement of phase-to-ground and phase-to-phase voltages.
Parameter Address
[spacer]
Short-circuit direction determination depends on the connection of the
measuring circuits. If the connection is as shown in Chapter “Installation and
Connection”, then this parameter must be set to Standard, if the P438's
'forward' decision is to be in the direction of the catenary. If the connection
direction is reversed or – given a connection scheme according to Chapter
“Installation and Connection” – if the 'forward' decision is to be in the feeder
direction, it must be set to Opposite.
[spacer] MAIN: Ms Circ.Ip laus/ Idfr st 010 036
[spacer]
If the connection is as shown in Chapter “Installation and Connection”, then the
setting must be Standard. If the connection direction is reversed then the
setting must be Opposite.
[spacer] MAIN: Fe e de r m ode 010 135
[spacer]
For use with single-voltage systems select the Classic single feed setting, for use
with dual-voltage systems select the Autotransformer feed setting.
Parameter Address
[spacer]
Setting for the minimum current that must be exceeded so that measured
operating values of the phase currents and, if applicable, derived currents are
displayed.
[spacer] MAIN: Me as. value re l. V 011 032
[spacer]
Setting for the minimum voltage that must be exceeded so that measured
operating values of the phase-to-ground voltages, phase-to-phase voltages, and,
if applicable, derived voltages are displayed.
[spacer] MAIN: Fct.as sign. res et 1 005 248
[spacer]
Assigning specific memories and counters which are to be reset jointly if
MAIN: Group res e t 1 USER is enabled.
[spacer] MAIN: Fct.as sign. res et 2 005 249
[spacer]
Assigning specific memories and counters which are to be reset jointly if
MAIN: Group res e t 2 USER is enabled.
[spacer] MAIN: Fct.as sign. bloc k. 1 021 021
[spacer]
Assignment of functions that will be blocked simultaneously when blocking
input 1 (MAIN: B lock ing 1 EX T) is activated.
[spacer] MAIN: Fct.as sign. bloc k. 2 021 022
[spacer]
Assignment of functions that will be blocked simultaneously when blocking
input 2 (MAIN: B lock ing 2 EX T) is activated.
[spacer] MAIN: Trip cm d.block . USER 021 012
[spacer]
Blocking the trip commands from the local control panel.
[spacer] MAIN: Block. M -t ri p USE R 022 090
[spacer]
Blocking of the main-trip commands from the user interface (HMI).
[spacer] MAIN: Block. R -t ri p USE R 022 091
[spacer]
Blocking of the re-trip commands from the user interface (HMI).
Parameter Address
0: No
[spacer]
Blocking of the back-trip commands from the user interface (HMI).
[spacer] MAIN: Fct.as g. M-t rip cmd1 021 007
[spacer]
Assignment of the signals leading to a main-trip command.
[spacer] MAIN: Fct.as g. M-t rip cmd2 021 008
[spacer]
Assignment of the signals leading to a main-trip command 2.
[spacer] MAIN: Fct.as g. R-t rip cmd1 021 025
[spacer]
Assignment of the signals leading to a re-trip command.
[spacer] MAIN: Fct.as g. R-t rip cmd2 021 026
[spacer]
Specification as to whether trip command 4 should latch.
[spacer] MAIN: Fct.as g. B-t ri p cmd1 021 027
[spacer]
Assignment of the signals leading to a back-trip command.
[spacer] MAIN: Fct.as g. B-t ri p cmd2 021 028
[spacer]
Assignment of the signals leading to a Trip command 2.
Parameter Address
[spacer]
Setting for the minimum duration of the main-trip command.
[spacer] MAIN: Min.dur . M- trip cmd2 021 035
[spacer]
Setting for the minimum duration of the Main-Trip command 2.
[spacer] MAIN: Min.dur . R- trip cmd1 021 036
[spacer]
Setting for the minimum duration of the re-trip command.
[spacer] MAIN: Min.dur . R- trip cmd2 021 037
[spacer]
Setting for the minimum duration of the Re-Trip command 2.
[spacer] MAIN: Min.dur . B-t rip c md1 021 038
[spacer]
Setting for the minimum duration of the back-trip command.
[spacer] MAIN: Min.dur . B-t rip c md2 021 039
[spacer]
Setting for the minimum duration of the Trip command 2.
[spacer] MAIN: Latching M - trip cmd1 021 040
[spacer]
Specification as to whether the main-trip command should latch.
[spacer] MAIN: Latching M - trip cmd2 021 041
[spacer]
Specification as to whether the main-trip command 2 should latch.
[spacer] MAIN: Latching R- trip cmd1 021 042
[spacer]
Specification as to whether the re-trip command should latch.
[spacer] MAIN: Latching R- trip cmd2 021 043
[spacer]
Specification as to whether the re-trip command 2 should latch.
[spacer] MAIN: Latching B -t rip cmd1 021 044
[spacer]
Specification as to whether the back-trip command should latch.
Parameter Address
[spacer]
Specification as to whether the trip command 2 should latch.
[spacer] MAIN: Sig . as g. CB open 021 017
[spacer]
Definition of the binary signal used by the P438 to evaluate the “CB open”
position signal.
[spacer] MAIN: Sig .as sign. CB clos e 021 020
[spacer]
Definition of the binary signal used by the P438 to evaluate the “CB closed”
position signal.
[spacer] MAIN: Deb ounce time gr . 1 221 200
[spacer]
Setting for the debouncing time.
[spacer] MAIN: Chatt.m on. time gr.1 221 201
Parameter Address
[spacer]
Setting for the chatter monitoring time.
[spacer] MAIN: Change of s tate gr.1 221 202
0 0 254
0 0 254
0 0 254
0 0 254
0 0 254
0 0 254
0 0 254
[spacer]
Setting the number of signal changes allowed during the chatter monitoring
time before chatter suppression operates.
[spacer] MAIN: Cmd . d ur.long cmd. 221 230
20 1 254 s
[spacer]
Setting for the command duration for a long command.
[spacer] MAIN: Cmd . d ur. short cmd. 221 231
1 1 254 s
[spacer]
Setting for the command duration for a short command.
[spacer] MAIN: Tim eT agAft erDe bounce 221 083
0: No
[spacer]
When this setting is activated, the time tag for the signal is issued after
debouncing.
Parameter Address
[spacer]
Definition of the operating mode of the CB trip.
[spacer] MAIN: Inp.asg. ctr l.enabl. 221 057
[spacer]
Definition of the binary signal used to issue a general command output enable.
[spacer] MAIN: Inp.asg.int er l.deact 221 007
[spacer]
Definition of the binary signal used to disable interlocking of control commands
for switchgear.
[spacer] MAIN: Inp.asg. L/R key s w. 221 008
[spacer]
Definition of the binary signal used to switch from remote control to local
control.
[spacer] MAIN: Electrical c ontrol 221 061
1: Remote
[spacer]
This setting determines whether the binary inputs, that are configured to control
switchgear, will be active with remote control or local control.
[spacer] MAIN: Delay Man.Op.S upe r v. 221 079
3 0 255 s
[spacer]
After the delay time period, to be set in this window, has elapsed (with the
signal “Sw. dev. interm. pos.” already present and the status signal continuously
absent), the actual switchgear status signal, as obtained from the respective
binary inputs, will be issued. (See also “Processing status signals from manually
operated switchgear”.)
[spacer] MAIN: Inp.assig n. t ripping 221 010
[spacer]
Definition of the binary signal used to signal the tripping of an external
protection device. This signal is used to form the CB trip signal.
[spacer] MAIN: Prot.t rip>CB tr ipped 221 012
[spacer]
Selection of the protection function trip command that will be used to form the
CB trip signal.
[spacer] MAIN: Inp. as g. CB t ri p 221 013
[spacer]
Definition of the binary signal used by the P438 to signal the “CB open” position
signal.
Parameter Address
[spacer]
Definition of the binary signal used to enable the CB trip signal of an external
device.
[spacer] MAIN: Inp.asg. C B t rip ex t 221 024
[spacer]
Definition of the binary signal used to carry the CB trip signal of an external
device.
[spacer] MAIN: Inp.asg. mult.sig. 1 221 051
[spacer]
Definition of the function that will be interpreted as a multiple signal (group
signal).
[spacer] MAIN: Inp.asg. cnt.tr f.tr . 221 011
[spacer]
Definition of the binary signals used to trigger counters.
[spacer] MAIN: Inp.asg. re set count 221 009
[spacer]
Definition of the binary signals used to reset counters.
[spacer] MAIN: Cycle t.count t r ans f 221 021
3 1 10000 min
[spacer]
Cycle period for transmission of counter values.
[spacer] MAIN: Clos e cmd.puls e ti me 015 067
[spacer]
Setting for the duration of the close command.
[spacer] MAIN: tCB, Close 000 032
[spacer]
This setting determines the CB close time. In slightly asynchronous power
systems, the CB close time is taken into account by the automatic synchronism
check (ASC) to issue of a close command. This is only possible if
setting ASC: AR with t CB P Sx = Yes or ASC : M C with tCB PS x = Yes.
[spacer] MAIN: ClCmd inhi b.by CB cl 015 042
[spacer]
This setting determines whether the reclose command will be inhibited as soon
as the “Circuit breaker closed” signal starts.
Parameter Address
[spacer]
Setting for the release time of the enable for the manual trip or close command,
respectively.
[spacer] MAIN: Fct. as s ign. fault 021 031
[spacer]
Selection of the signals to be signaled as Blocked/Faulty in addition to the
messages that always result in the message Blocked/Faulty.
Parameter Address
selection
0: No Fig. 3-96, (p. 3-135)
[spacer]
If parameter subset selection is to be handled from the integrated local control
panel rather than via binary signal inputs, choose the setting Yes.
[spacer] PSS: Param.sub s.se l. USE R 003 060
[spacer]
Selection of the parameter subset from the local control panel.
[spacer] PSS: Ke ep tim e 003 063
[spacer]
The setting of this timer stage is relevant only if parameter subset selection is
carried out via the binary signal inputs. Any voltage-free pause that may occur
during selection is bridged. If, after this time period has elapsed, no binary
signal input has yet been set, then the parameter subset selected from the local
control panel shall apply.
Parameter Address
[spacer]
Selection of the signals whose appearance shall result in the signals “Warning
(LED)” and “Warning (relay)” and in the activation of the LED indicator labeled
“ALARM”. Signals caused by faulty hardware and leading to blocking of the
device are not configurable. They always result in the above signals and
indication.
[spacer] SFMO N: M on. s ig. r et e ntion 021 018
Blocked 0 240 h
[spacer]
This setting defines the duration (in hours) for which a device-internal fault is
stored, so that a decision may be taken between an automatic warm restart and
an automatic device blocking. (Setting to Blocked may be considered the same
as unlimited storage.)
Parameter Address
[spacer]
This setting defines the signals that will trigger fault recording.
[spacer] FT_RC: I> 016 013
[spacer]
This setting defines the threshold value of the phase current that will trigger
disturbance recording.
[spacer] FT_RC: Pre- fault time 003 078
[spacer]
Setting for the time during which data will be recorded before the onset of a
fault (pre-fault recording time).
[spacer] FT_RC: Post -f ault ti me 003 079
[spacer]
Setting for the time during which data will be recorded after the end of a fault
(post-fault recording time).
[spacer] FT_RC: Max. re cording t ime 003 075
[spacer]
Setting for the maximum recording time per fault. This includes pre-fault and
post-fault recording times.
Parameter Address
[spacer]
Setting for the evaluation time. The operate conditions must be met for the
duration of the set evaluation time in order for a signal to be issued.
[spacer] MAIN: Undervolt . blo ck. V< 018 200
[spacer]
Setting for the threshold of undervoltage blocking. If the voltage falls below this
threshold, the over-/underfrequency protection function will be blocked.
Parameter Address
[spacer]
Enable/disable the distance protection function.
[spacer] DIST: X parame t er av ail . 023 050
[spacer]
Making the reactance parameter "visible", i.e. available.
[spacer] DIST: Z par am e ter av ail . 023 051
[spacer]
Making the impedance parameter "visible", i.e. available.
[spacer] DIST: X parame t er us ed 023 052
[spacer]
This parameter enables the usage of X values as setting parameter for the
polygon characteristic instead of Z values.
It shall be set to "yes" only, if the parameter DIST: X parameter avai l . is
set to "yes" and DIST : Z par ame ter av ail . is set to "No".
[spacer] DIST: WPC zone availabl e 022 002
[spacer]
Making the setting parameters for wrong phase coupling “visible”, i.e. available.
[spacer] DIST: Block. if tr ip I>H 022 151
1: Yes
[spacer]
Setting of temporary blocking (80 ms) of distance protection decisions if high-set
stage I>H has issued a trip signal.
Enable for switching the zone reaches of the distance protection via the local
control panel.
Parameter Address
[spacer]
Enabling switching of distance protection zone reaches via the user interface
(HMI) or the IEC 61850 communication protocol.
When set to No the switching of zone reaches can be done:
● via binary input, or
● via appropriately configured function keys.
When set to Yes the switching of zones can be done:
● via IEC communication protocol (PDIS.Mod), or
● via the local control panel (HMI) or operating program (setting parameters
(022 011) DIST : S el ect Z1/ Z1' US E R, (022 021) DIST: S elect
Z2/Z2' USER, (022 038) D IS T: Se le ct Z3/ Z3' USER).
[spacer] DIST: Select Z1/Z1' USE R 022 011
[spacer]
Switching the zone reaches of the distance zones.
Parameter Address
tection
0: No Fig. 3-138, (p. 3-184)
[spacer]
Enabling/disabling DELTA protection.
[spacer] DELT A: X superv. available 022 188
[spacer]
Making reactance release globally visible, i.e. available.
[spacer] DELT A: D elta Phi avai lable 022 189
[spacer]
Making sudden angle change monitoring globally visible, i.e. available.
[spacer] DELT A: S upe rv. I(5 fn)av ail. 022 193
[spacer]
Making the harmonics stabilization feature globally visible, i.e. available.
[spacer] DELT A: B locking by CB- clos e 022 191
[spacer]
High impedance protection is blocked by a Close command, issued to the circuit
breaker, which depends on the duration of the tBlock time delay.
Parameter Address
monitoring
0: No Fig. 3-145, (p. 3-192)
Fig. 3-146, (p. 3-193)
Fig. 3-232, (p. 3-286)
[spacer]
Enabling or disabling the measuring-circuit monitoring function.
[spacer] MCM ON: FF,Vre f enable d US ER 014 013
[spacer]
Enabling or disabling the “Fuse Failure” monitoring function of the reference
voltage Vref.
[spacer] MCM ON: S caling fact . Iplaus 004 255
[spacer]
Display of the calculated matching factor of the plausibility current.
[spacer] MCM ON: Op er. de lay F F , Vre f 014 012
[spacer]
Setting for the time delay for “Fuse Failure” monitoring of the reference voltage
Vref.
Parameter Address
time protection
0: No Fig. 3-153, (p. 3-199)
[spacer]
Enabling or disabling BUOC protection
Parameter Address
protection
0: No Fig. 3-156, (p. 3-201)
[spacer]
Enabling or disabling the switch on to fault (short circuit) protection.
Parameter Address
0: No
[spacer]
Disabling or enabling protective signaling.
Parameter Address
control
0: No Fig. 3-175, (p. 3-220)
[spacer]
Disabling or enabling auto-reclosing control.
[spacer] ARC: W ith R-trip 015 018
[spacer]
Specify whether the re-trip command is included in the auto-recloser.
[spacer] ARC: Fct.as signm. tL OG IC 015 033
[spacer]
Function assignment to tLOGIC.
Parameter Address
synchronism check
0: No Fig. 3-195, (p. 3-246)
[spacer]
Enabling or disabling the automatic synchronism check.
[spacer] ASC: Transm .cycle ,me as .v. 101 212
[spacer]
Cycle period for transmission of ASC measured values.
Parameter Address
current protection
0: No Fig. 3-210, (p. 3-263)
[spacer]
Enable/disable the definite-time overcurrent protection function.
[spacer] DTOC: Direction meas ure m. 031 131
0: Without
[spacer]
The user may select a definite-time overcurrent protection with or without
direction measurement.
Parameter Address
current protection
0: No Fig. 3-216, (p. 3-269)
[spacer]
Enable/disable the definite-time overcurrent protection function for CT A.
Note: The function group DTOCA is active only with the setting
MAIN: Fe e de r m ode = Autotransformer feed.
Parameter Address
current protection
0: No
[spacer]
Enable/disable the definite-time overcurrent protection function for CT B.
Note: The function group DTOCB is active only with the setting
MAIN: Fe e de r m ode = Autotransformer feed.
Parameter Address
rent protection
0: No Fig. 3-218, (p. 3-271)
[spacer]
Enabling or disabling the inverse-time overcurrent protection function.
[spacer] IDMT: D ire ct ion me as ur em. 017 109
0: Without
[spacer]
The user may select a definite-time overcurrent protection with or without
direction measurement.
Parameter Address
rent protection
0: No Fig. 3-229, (p. 3-283)
[spacer]
Enabling or disabling the inverse-time overcurrent protection function for CT A.
Note: The function group IDMTA is active only with the setting MAIN: Feed er
mode = Autotransformer feed.
Parameter Address
rent protection
0: No
[spacer]
Enabling or disabling the inverse-time overcurrent protection function for CT B.
Note: The function group IDMTB is active only with the setting M AIN: Feed er
mode = Autotransformer feed.
Parameter Address
[spacer]
Enabling/disabling defrost protection.
[spacer] DFR ST : Scaling factor 004 203
[spacer]
Display of the calculated matching factor for defrost protection.
Parameter Address
protection
0: No Fig. 3-234, (p. 3-287)
[spacer]
Disabling or enabling thermal overload protection.
[spacer] THER M : R e lat ive re pl ic a 022 064
[spacer]
Disabling or enabling the Relative replica mode of operation.
Note that it is not permitted to enable both Absolute replica and Relative replica
modes.
[spacer] THER M : Absolut e r eplica 022 065
[spacer]
Enabling or disabling the Absolute replica mode of operation.
Note that it is not permitted to enable both Absolute replica and Relative replica
modes.
[spacer] THER M : Control v ia USER 022 009
[spacer]
Enabling parallel line switching via the user interface (HMI).
[spacer] THER M : Num ber PL USE R 022 062
[spacer]
Setting for the number of parallel lines via the user interface (HMI).
[spacer] THER M : No. of pa r. line s 022 069
1 1 3
[spacer]
Display of the number of active parallel lines.
[spacer] THER M : No. of p.lines e xt . 022 074
1 1 3
[spacer]
Display of the number of parallel lines pre-selected via binary inputs.
[spacer] THER M : O/ T f . I ref per si st 004 138
[spacer]
Display of over-temperature as a result of persisting Iref.
Note: This display is only visible in the Relative replica mode of operation.
Parameter Address
tion
0: No Fig. 3-240, (p. 3-295)
[spacer]
Disabling or enabling time-voltage protection.
Parameter Address
underfrequency pro‐
tection
0: No Fig. 3-243, (p. 3-298)
[spacer]
Disabling or enabling over-/underfrequency protection.
Parameter Address
failure protection
0: No Fig. 3-246, (p. 3-303)
[spacer]
Enabling or disabling circuit breaker failure protection.
Parameter Address
condition monitoring
0: No Fig. 3-250, (p. 3-307)
[spacer]
Enabling or disabling circuit breaker monitoring.
[spacer] CBM: Blocking USER 022 150
[spacer]
Setting for temporary blocking of circuit breaker monitoring during protection
injection testing.
[spacer] CBM: Op er ating mode 022 007
[spacer]
This setting defines starting criteria for circuit breaker monitoring. To evaluate
all trip commands issued by the protection device With trip cmd. only must be
selected. For further evaluation of operational trip commands the additional CB
auxiliary contact CB sig. EXT or trip is used.
[spacer] CBM: I nom,CB 022 012
[spacer]
Setting for the CB nominal current.
[spacer] CBM: M e d. curr. I t ri p,CB 022 014
[spacer]
Setting for the average CB disconnection current.
Note: In general valid only for pneumatically operated CBs.
[spacer] CBM: M ax . curr. It r ip,CB 022 016
[spacer]
Setting for the maximum CB disconnection (ruptured) current.
[spacer] CBM: Per m . CB op. Inom,CB 022 013
[spacer]
Setting for the maximum number of CB operations at nominal current.
[spacer] CBM: Per m . CB op. Imed, CB 022 015
[spacer]
Setting for the maximum number of CB operations at average disconnection
(ruptured) current.
Note: In general valid only for pneumatically operated CBs.
Parameter Address
[spacer]
Setting for the maximum number of CB operations permitted at maximum CB
disconnection (ruptured) current.
[spacer] CBM: No. CB ope rations > 022 019
[spacer]
Setting for the maximum number of mechanical CB switching operations.
[spacer] CBM: R e main No. CB op. < 022 020
[spacer]
Setting for the warning stage with the number of remaining CB operations at CB
nominal current.
[spacer] CBM: ΣItr ip > 022 022
[spacer]
Setting for the warning stage with the accumulated CB disconnection (ruptured)
current values.
[spacer] CBM: ΣItr ip **2> 022 081
[spacer]
Setting for the warning stage with the accumulated CB disconnection (ruptured)
current values to the second power.
[spacer] CBM: ΣI* t> 022 096
[spacer]
Setting for the warning stage with the sum of the current-time integrals of the
CB disconnection (ruptured) current values
[spacer] CBM: C orr. Acqu.t. trip 022 153
[spacer]
Correction of the delay period between the forming of the device internal trip
command and the actual opening of the CB contacts.
[spacer] CBM: C orr. Acqu.t.C B sig. 022 018
[spacer]
Correction of the time tolerances permissible for leading or lagging CB auxiliary
contacts.
Parameter Address
monitoring
0: No Fig. 3-257, (p. 3-315)
[spacer]
Disabling or enabling limit value monitoring.
[spacer] LIMIT : IDC,lin> 014 110
[spacer]
Setting for the operate value IDC,lin> for monitoring the linearized direct
current.
[spacer] LIMIT : IDC,lin>> 014 111
[spacer]
Setting for the operate value IDC,lin>> for monitoring the linearized direct
current.
[spacer] LIMIT : tIDC,lin> 014 112
[spacer]
Setting for the operate delay of overcurrent stage IDC,lin>.
[spacer] LIMIT : tIDC,lin>> 014 113
[spacer]
Setting for the operate delay of overcurrent stage IDC,lin>>.
[spacer] LIMIT : IDC,lin< 014 114
[spacer]
Setting for the operate value IDC,lin< for monitoring the linearized direct
current.
[spacer] LIMIT : IDC,lin<< 014 115
[spacer]
Setting for the operate value IDC,lin<< for monitoring the linearized direct
current.
[spacer] LIMIT : tIDC,lin< 014 116
[spacer]
Setting for the operate delay of undercurrent stage IDC,lin<.
[spacer] LIMIT : tIDC,lin<< 014 117
[spacer]
Setting for the operate delay of undercurrent stage IDC,lin<<.
[spacer] LIMIT : T> 014 100
[spacer]
Setting for the operate value of temperature monitoring T>.
Parameter Address
[spacer]
Setting for the operate value of temperature monitoring T>>.
[spacer] LIMIT : tT > 014 103
[spacer]
Setting for the operate delay of temperature monitoring T>.
[spacer] LIMIT : tT >> 014 104
[spacer]
Setting for the operate delay of temperature monitoring T>>.
[spacer] LIMIT : T< 014 105
[spacer]
Setting for the operate value of temperature monitoring T<.
[spacer] LIMIT : T<< 014 106
[spacer]
Setting for the operate value of temperature monitoring T<<.
[spacer] LIMIT : tT < 014 107
[spacer]
Setting for the operate delay of temperature monitoring T<.
[spacer] LIMIT : tT << 014 108
[spacer]
Setting for the operate delay of temperature monitoring T<<.
Parameter Address
[spacer]
Enable/disable the logic function.
[spacer] LOGIC: Se t 1 US ER 034 030
0: No
0: No
0: No
0: No
0: No
0: No
0: No
[spacer]
These settings define the static input conditions for the logic function.
[spacer] LOGIC: Fct.as s ignm. outp. 1 030 000
Parameter Address
Parameter Address
Parameter Address
Parameter Address
Parameter Address
Parameter Address
Parameter Address
[spacer]
These settings assign functions to the outputs.
[spacer] LOGIC: Op. m ode t output 1 030 001
Parameter Address
Parameter Address
Parameter Address
Parameter Address
Parameter Address
Parameter Address
Parameter Address
[spacer]
These settings define the operating modes for the output timer stages.
[spacer] LOGIC: Tim e t1 output 1 030 002
Parameter Address
Parameter Address
Parameter Address
Parameter Address
Parameter Address
Parameter Address
Parameter Address
[spacer]
Settings of timer stage t1 for the respective outputs.
[spacer] LOGIC: Tim e t2 output 1 030 003
Parameter Address
Parameter Address
Parameter Address
Parameter Address
Parameter Address
Parameter Address
[spacer]
Settings for timer stage t2 for the respective outputs.
Note: This setting has no effect in the “minimum time” operating mode.
[spacer] LOGIC: Sig .as sig. out p. 1 044 000
Parameter Address
Parameter Address
Parameter Address
Parameter Address
Parameter Address
Parameter Address
Parameter Address
[spacer]
These settings assign the function of a binary input signal to the output of the
logic equation.
[spacer] LOGIC: Sig .as sig.out p. 1 (t ) 044 001
Parameter Address
Parameter Address
Parameter Address
Parameter Address
Parameter Address
Parameter Address
Parameter Address
[spacer]
These settings assign the function of a binary input signal to the output of the
logic equation.
Parameter Address
[spacer]
Enable/disable the function group LOG_2 (Programmable Logic 2).
[spacer] LOG_2: Fct.assig nm. outp. 1 050 000
[spacer]
These settings assign functions to the outputs.
[spacer] LOG_2: Op . m ode t output 1 050 001
[spacer]
These settings define the operating modes for the output timer stages.
[spacer] LOG_2: T im e t 1 output 1 050 002
0 0 60000 s
0 0 60000 s
0 0 60000 s
[spacer]
Settings of timer stage t1 for the respective outputs.
[spacer] LOG_2: T im e t 2 output 1 050 003
0 0 60000 s
0 0 60000 s
Parameter Address
0 0 60000 s
[spacer]
Settings for timer stage t2 for the respective outputs.
Note: This setting has no effect in the “minimum time” operating mode.
[spacer] LOG_2: S ig.as sig. o ut p. 1 064 000
[spacer]
These settings assign the function of a binary input signal to the output of the
logic equation.
[spacer] LOG_2: S ig.as sig.out p. 1 (t ) 064 001
[spacer]
These settings assign the function of a binary input signal to the output of the
logic equation.
Parameter Address
[spacer]
Disabling or enabling TIMER protection.
[spacer] TIM ER : Calendar 1 014 178
[spacer]
The setting defines the calender day of week for the TIMER. One or more of the
seven weekdays can be selected.
[spacer] TIM ER : S tart hour 1 014 089
0 0 23 h
0 0 23 h
0 0 23 h
[spacer]
The parameter defines the start hour of the TIMER.
[spacer] TIM ER : S tart m inute 1 014 102
0 0 59 min
0 0 59 min
0 0 59 min
[spacer]
The parameter defines the start minute of the TIMER.
[spacer] TIM ER : E nd hour 1 014 109
0 0 23 h
0 0 23 h
Parameter Address
0 0 23 h
[spacer]
The parameter defines the end hour of the TIMER.
[spacer] TIM ER : E nd m inute 1 014 118
0 0 59 min
0 0 59 min
0 0 59 min
[spacer]
The parameter defines the end minute of the TIMER.
Parameter Address
commands
1: C001
2: C002
3: C003
4: C004
5: C005
6: C006
7: C007
8: C008
9: C009
10: C010
11: C011
12: C012
13: C013
14: C014
15: C015
16: C016
17: C017
18: C018
Parameter Address
19: C019
20: C020
21: C021
22: C022
23: C023
24: C024
25: C025
26: C026
[spacer]
Selection of the command designation.
[spacer] CMD_1: Oper. mode cmd. C 001 200 002
3: Persistent command
3: Persistent command
3: Persistent command
3: Persistent command
3: Persistent command
3: Persistent command
3: Persistent command
3: Persistent command
3: Persistent command
Parameter Address
3: Persistent command
3: Persistent command
3: Persistent command
3: Persistent command
3: Persistent command
3: Persistent command
3: Persistent command
3: Persistent command
3: Persistent command
3: Persistent command
3: Persistent command
3: Persistent command
3: Persistent command
3: Persistent command
3: Persistent command
3: Persistent command
[spacer]
Selection of the command operating mode.
Parameter Address
1: S001
2: S002
3: S003
4: S004
5: S005
6: S006
7: S007
8: S008
9: S009
10: S010
11: S011
12: S012
13: S013
14: S014
15: S015
16: S016
17: S017
18: S018
19: S019
Parameter Address
20: S020
21: S021
22: S022
23: S023
24: S024
25: S025
26: S026
27: S027
28: S028
29: S029
30: S030
31: S031
32: S032
33: S033
34: S034
35: S035
36: S036
37: S037
38: S038
Parameter Address
39: S039
40: S040
41: S041
42: S042
43: S043
44: S044
45: S045
46: S046
47: S047
48: S048
49: S049
50: S050
51: S051
52: S052
53: S053
54: S054
55: S055
56: S056
57: S057
Parameter Address
58: S058
59: S059
60: S060
61: S061
62: S062
63: S063
64: S064
[spacer]
Selection of the signal designation.
[spacer] SIG_1: Op er. mod e s ig. S 001 226 001
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
Parameter Address
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
Parameter Address
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
Parameter Address
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
1: Start/end signal
[spacer]
Selection of the signal operating mode.
[spacer] SIG_1: Gr.as g. de bounc.S0 01 226 003
1: Group 1
1: Group 1
Parameter Address
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
Parameter Address
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
Parameter Address
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
Parameter Address
1: Group 1
1: Group 1
1: Group 1
1: Group 1
[spacer]
Group assignment for the debouncing time and the chatter suppression.
[spacer] SIG_1: M in. sig. dur. S0 01 226 002
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
Parameter Address
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
Parameter Address
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
Parameter Address
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
0 0 254 s
[spacer]
The logic “1” signal must be available for this minimum time setting so that a
telegram can be sent in the Start/end signal mode.
Parameter Address
[spacer]
Disabling or enabling binary counts.
[spacer] COUNT : Deb ounce t. c ount. 1 217 160
3 0 1000 ms
3 0 1000 ms
3 0 1000 ms
[spacer]
Setting for the debounce time of the binary signal to be counted.
[spacer] COUNT : Limit count e r 1 217 221
Blocked 1 65000
Blocked 1 65000
Blocked 1 65000
Blocked 1 65000
[spacer]
Setting a limit for the counter value. A warning signal is issued if the counter
value exceeds the set limit. Setting this parameter to Blocked disables the limit
check.
[spacer] COUNT : Cycle t.count t r ans m 217 007
[spacer]
Setting the cycle time for the periodic transmission of the counts.
[spacer] COUNT : IEC61850 pulsQty 221 096
1 0 1000
[spacer]
Setting the scaling factor to transmit the counter value via IEC 61850. According
to the standard the resulting value is calculated as:
Value transmitted = actual value · pulsQty
(see IEC 61850: Value = actVal · pulsQty).
Parameter Address
Main function MAIN: Rush I(2fn)/I( fn) PS x 017 098 001 091 001 092 001 093
[spacer]
Setting for the operate value of inrush stabilization.
[spacer] MAIN: I> lif t rush rs tr PSx 017 095 001 085 001 086 001 087
[spacer] MAIN: I> e nable r ush r .P S x 017 058 017 113 017 254 017 255
[spacer]
Setting for the current threshold for disabling the inrush stabilization.
[spacer] MAIN: t lift rus h r st r. PSx 019 001 019 002 019 003 019 004
[spacer]
Setting for the maximum duration of inrush stabilization.
[spacer] MAIN: Funct.R us h r est r. PS x 017 093 017 064 017 082 017 083
[spacer]
Select the protection elements that shall be blocked when the inrush
stabilization is triggered.
[spacer] MAIN: I(3fn)/I(fn) PS x 020 229 020 230 020 231 020 232
[spacer] MAIN: I(5fn)/I(fn) PS x 020 233 020 235 020 236 020 237
[spacer] MAIN: I(7fn)/I(fn) PS x 020 238 020 239 020 242 020 243
[spacer]
Setting for the ratio of the third, fifth and seventh harmonic current components
to the fundamental.
[spacer] MAIN: I>Enable harm.b. PS x 020 244 020 245 020 246 020 247
[spacer] MAIN: I>Lift harm.blk . P Sx 020 248 020 249 020 250 020 251
[spacer]
Settings for the current thresholds of the range in which harmonic blocking
activates.
[spacer] MAIN: Funct.Har m.block .P Sx 020 252 020 253 020 254 020 255
[spacer]
Select the protection elements that shall be blocked when the harmonics
blocking is triggered.
Parameter Address
Fault data FT_DA: For w.lengt h A- 1 P Sx 010 005 010 006 010 007 010 008
acquisition
10.00 0.01 500.00 km Fig. 3-109, (p. 3-152)
[spacer] FT_DA: For w.lengt h A- 2 P Sx 008 115 008 116 008 117 008 118
[spacer] FT_DA: For w.lengt h A- 3 P Sx 008 119 008 120 008 121 008 122
[spacer] FT_DA: For w.lengt h A- 4 P Sx 008 123 008 124 008 125 008 126
[spacer] FT_DA: For w.lengt h A- 5 P Sx 008 127 008 128 008 129 008 130
[spacer] FT_DA: For w.lengt h A- 6 P Sx 008 131 008 132 008 133 008 134
[spacer] FT_DA: For w.lengt h A- 7 P Sx 008 135 008 136 008 137 008 138
[spacer] FT_DA: For w.lengt h A- 8 P Sx 008 139 008 140 008 141 008 142
[spacer] FT_DA: For w.lengt h A- 9 P Sx 008 143 008 144 008 145 008 146
[spacer] FT_DA: For w.lengt h A- 10 PSx 008 147 008 148 008 149 008 150
[spacer]
The forward line length A-y defines the length - in km - of line section y of the
catenary line. The calculation of fault location is based on this value.
A maximum of 10 line sections may be defined; line distance and line reactance
for line sections not needed are to be set to Blocked.
[spacer] FT_DA: XLf orw.,s ec A- 1 PS x 010 012 010 013 010 014 010 015
[spacer] FT_DA: XLf orw.,s ec A- 2 PS x 008 151 008 152 008 153 008 154
[spacer] FT_DA: XLf orw.,s ec A- 3 PS x 008 155 008 156 008 157 008 158
[spacer] FT_DA: XLf orw.,s ec A- 4 PS x 008 159 008 164 008 165 008 166
Parameter Address
[spacer] FT_DA: XLf orw.,s ec A- 5 PS x 008 167 008 168 008 169 008 170
[spacer] FT_DA: XLf orw.,s ec A- 6 PS x 008 171 008 172 008 173 008 174
[spacer] FT_DA: XLf orw.,s ec A- 7 PS x 008 175 008 176 008 177 008 178
[spacer] FT_DA: XLf orw.,s ec A- 8 PS x 008 179 008 180 008 181 008 182
[spacer] FT_DA: XLf orw.,s ec A- 9 PS x 008 183 008 184 008 185 008 186
[spacer] FT_DA: XLf orw.,s ec A- 10 P S x 008 187 008 188 008 189 008 190
[spacer]
The forward line reactance A-y defines reactance Xy of section y of the catenary
line. The calculation of fault location is based on this value.
A maximum of 10 line sections may be defined; line distance and line reactance
for line sections not needed are to be set to Blocked.
[spacer] FT_DA: For w.lengt h B- 1 P Sx 011 145 011 146 011 147 011 148
[spacer] FT_DA: For w.lengt h B- 2 P Sx 011 149 011 150 011 151 011 152
[spacer] FT_DA: For w.lengt h B- 3 P Sx 011 153 011 154 011 155 011 156
[spacer] FT_DA: For w.lengt h B- 4 P Sx 011 157 011 158 011 159 011 160
[spacer] FT_DA: For w.lengt h B- 5 P Sx 011 161 011 162 011 163 011 164
[spacer] FT_DA: For w.lengt h B- 6 P Sx 011 165 011 166 011 167 011 168
[spacer] FT_DA: For w.lengt h B- 7 P Sx 011 169 011 170 011 171 011 172
Parameter Address
[spacer] FT_DA: For w.lengt h B- 8 P Sx 011 173 011 174 011 175 011 176
[spacer] FT_DA: For w.lengt h B- 9 P Sx 011 177 011 178 011 179 011 180
[spacer] FT_DA: For w.lengt h B- 10 PSx 011 181 011 182 011 183 011 184
[spacer]
The forward line length B-y defines the length - in km - of line section y of the
feeder line. The calculation of fault location is based on this value.
A maximum of 10 line sections may be defined; line distance and line reactance
for line sections not needed are to be set to Blocked.
Note: Not available when setting MAIN: Fe e der mode = Classic single
feed.
[spacer] FT_DA: XLf orw.,s ec B- 1 P Sx 011 185 011 186 011 187 011 188
[spacer] FT_DA: XLf orw.,s ec B- 2 P Sx 011 189 011 190 011 191 011 192
[spacer] FT_DA: XLf orw.,s ec B- 3 P Sx 011 193 011 194 011 195 011 196
[spacer] FT_DA: XLf orw.,s ec B- 4 P Sx 011 197 011 198 011 199 011 200
[spacer] FT_DA: XLf orw.,s ec B- 5 P Sx 011 201 011 202 011 203 011 204
[spacer] FT_DA: XLf orw.,s ec B- 6 P Sx 011 205 011 206 011 207 011 208
[spacer] FT_DA: XLf orw.,s ec B- 7 P Sx 011 209 011 210 011 211 011 212
[spacer] FT_DA: XLf orw.,s ec B- 8 P Sx 011 213 011 214 011 215 011 216
Parameter Address
[spacer] FT_DA: XLf orw.,s ec B- 9 P Sx 011 217 011 218 011 219 011 220
[spacer] FT_DA: XLf orw.,s ec B- 10 P Sx 011 221 011 222 011 223 011 224
[spacer]
The forward line reactance B-y defines reactance Xy of section y of the feeder
line. The calculation of fault location is based on this value.
A maximum of 10 line sections may be defined; line distance and line reactance
for line sections not needed are to be set to Blocked.
Note: Not available when setting MAIN: Fe e der mode = Classic single
feed.
[spacer] FT_DA: Outp . f lt.locat . P Sx 010 032 010 033 010 034 010 035
[spacer]
Setting for the conditions under which a fault location is output.
[spacer] FT_DA: Backw.length A-1 PS x 023 053 023 064 023 065 023 066
[spacer] FT_DA: Backw.length A-2 PS x 023 054 023 067 023 068 023 090
[spacer] FT_DA: Backw.length A-3 PS x 023 056 023 091 023 092 023 093
[spacer] FT_DA: Backw.length A-4 PS x 023 057 023 094 023 095 023 096
[spacer] FT_DA: Backw.length A-5 PS x 023 058 023 097 023 098 023 099
[spacer] FT_DA: Backw.length A-6 PS x 023 059 023 100 023 101 023 102
[spacer] FT_DA: Backw.length A-7 PS x 023 060 023 103 023 104 023 105
[spacer] FT_DA: Backw.length A-8 PS x 023 061 023 106 023 107 023 110
[spacer] FT_DA: Backw.length A-9 PS x 023 062 023 111 023 112 023 113
[spacer]
The backward line length A-y defines the length - in km - of line section y of the
catenary line. The calculation of fault location is based on this value.
A maximum of 10 line sections may be defined; line distance and line reactance
for line sections not needed are to be set to Blocked.
Parameter Address
[spacer] FT_DA: XLbackw.,s ecA- 1 P Sx 023 157 023 167 023 168 023 169
[spacer] FT_DA: XLbackw.,s ecA- 2 P Sx 023 158 023 170 023 171 023 172
[spacer] FT_DA: XLbackw.,s ecA- 3 P Sx 023 159 023 173 023 174 023 175
[spacer] FT_DA: XLbackw.,s ecA- 4 P Sx 023 160 023 176 023 177 023 178
[spacer] FT_DA: XLbackw.,s ecA- 5 P Sx 023 161 023 179 023 180 023 181
[spacer] FT_DA: XLbackw.,s ecA- 1 P Sx 023 162 023 182 023 183 023 184
[spacer] FT_DA: XLbackw.,s ecA- 7 P Sx 023 163 023 185 023 186 023 187
[spacer] FT_DA: XLbackw.,s ecA- 8 P Sx 023 164 023 188 023 189 023 190
[spacer] FT_DA: XLbackw.,s ecA- 9 P Sx 023 165 023 191 023 192 023 193
[spacer]
The backward line reactance A-y defines reactance Xy of section y of the
catenary line. The calculation of fault location is based on this value.
A maximum of 10 line sections may be defined; line distance and line reactance
for line sections not needed are to be set to Blocked.
[spacer] FT_DA: Backw.length B-1 PS x 023 117 023 127 023 128 023 129
[spacer] FT_DA: Backw.length A-10PS x 023 063 023 114 023 115 023 116
[spacer] FT_DA: Backw.length B-2 PS x 023 118 023 130 023 131 023 132
Parameter Address
[spacer] FT_DA: Backw.length B-3 PS x 023 119 023 133 023 134 023 135
[spacer] FT_DA: Backw.length B-4 PS x 023 120 023 136 023 137 023 138
[spacer] FT_DA: Backw.length B-5 PS x 023 121 023 139 023 140 023 141
[spacer] FT_DA: Backw.length B-6 PS x 023 122 023 142 023 143 023 144
[spacer] FT_DA: Backw.length B-7 PS x 023 123 023 145 023 146 023 147
[spacer] FT_DA: Backw.length B-8 PS x 023 124 023 148 023 149 023 150
[spacer] FT_DA: Backw.length B-9 PS x 023 125 023 151 023 152 023 153
[spacer] FT_DA: Backw.length B-1 0PS x 023 126 023 154 023 155 023 156
[spacer]
The backward line length B-y defines the length - in km - of line section y of the
feeder line. The calculation of fault location is based on this value.
A maximum of 10 line sections may be defined; line distance and line reactance
for line sections not needed are to be set to Blocked.
Note: Not available when setting MAIN: Fe e der mode = Classic single
feed.
[spacer] FT_DA: XLbackw.,s ecB- 1 P Sx 023 205 023 223 023 224 023 225
[spacer] FT_DA: XLbackw.,s ecA- 10 P S x 023 166 023 194 023 195 023 204
[spacer] FT_DA: XLbackw.,s ecB- 2 P Sx 023 206 023 226 023 227 023 228
[spacer] FT_DA: XLbackw.,s ecB- 3 P Sx 023 207 023 229 023 230 023 231
[spacer] FT_DA: XLbackw.,s ecB- 4 P Sx 023 208 023 232 023 233 023 234
Parameter Address
[spacer] FT_DA: XLbackw.,s ecB- 5 P Sx 023 209 023 235 023 236 023 237
[spacer] FT_DA: XLbackw.,s ecB- 6 P Sx 023 210 023 238 023 239 023 240
[spacer] FT_DA: XLbackw.,s ecB- 7 P Sx 023 211 023 241 023 242 023 243
[spacer] FT_DA: XLbackw.,s ecB- 8 P Sx 023 212 023 244 023 245 023 246
[spacer] FT_DA: XLbackw.,s ecB- 9 P Sx 023 221 023 247 023 248 023 249
[spacer] FT_DA: XLbackw.,s ecB- 10 P Sx 023 222 023 250 023 251 023 252
[spacer]
The backward line reactance B-y defines reactance Xy of section y of the feeder
line. The calculation of fault location is based on this value.
A maximum of 10 line sections may be defined; line distance and line reactance
for line sections not needed are to be set to Blocked.
Note: Not available when setting MAIN: F eede r mode = Classic single
feed.
Parameter Address
Distance protection DIST: Enable PS x 072 200 073 200 074 200 075 200
[spacer]
This setting defines the setting group in which distance protection is enabled.
[spacer] DIST: Characteristic P Sx 012 040 073 097 074 097 075 097
[spacer]
Selection of the characteristic used in distance measurement.
[spacer] DIST: I> PSx 072 195 073 195 074 195 075 195
[spacer]
Setting for the minimum current sensitivity of the distance zones.
[spacer] DIST: Z1, f orward P S x 076 093 077 093 078 093 079 093
[spacer] DIST: Z1, backward PSx 076 100 077 100 078 100 079 100
[spacer] DIST: Z1' , f orwar d PSx 076 096 077 096 078 096 079 096
[spacer] DIST: Z1' , backward P Sx 076 103 077 103 078 103 079 103
[spacer] DIST: Z2, f orward P S x 076 094 077 094 078 094 079 094
[spacer] DIST: Z2, backward PSx 076 101 077 101 078 101 079 101
[spacer] DIST: Z2' , f orwar d PSx 076 097 077 097 078 097 079 097
[spacer] DIST: Z2' , backward P Sx 076 104 077 104 078 104 079 104
[spacer] DIST: Z3, f orward P S x 076 095 077 095 078 095 079 095
[spacer] DIST: Z3, backward PSx 076 102 077 102 078 102 079 102
[spacer] DIST: Z3' , f orwar d PSx 076 098 077 098 078 098 079 098
Parameter Address
[spacer] DIST: Z3' , backward P Sx 076 105 077 105 078 105 079 105
[spacer] DIST: Z4, f orward P S x 080 015 081 015 082 015 083 015
[spacer] DIST: Z4, backward PSx 080 017 081 017 082 017 083 017
[spacer] DIST: Z4' , f orwar d PSx 080 016 081 016 082 016 083 016
[spacer] DIST: Z4' , backward P Sx 080 018 081 018 082 018 083 018
[spacer]
Setting for the impedance boundaries of zones 1 to 4 (or 1' to 4') of the circular
and polygonal characteristics, in forward and reverse directions, in secondary
values.
[spacer] DIST: R1, f or w. ( pol y) P Sx 076 115 077 115 078 115 079 115
[spacer] DIST: R1, b ackw.( poly ) PSx 076 121 077 121 078 121 079 121
[spacer] DIST: R1' , forw.( poly ) P Sx 076 118 077 118 078 118 079 118
[spacer] DIST: R1' , backw.(poly) PSx 076 124 077 124 078 124 079 124
[spacer] DIST: R2, f or w. ( pol y) P Sx 076 116 077 116 078 116 079 116
[spacer] DIST: R2, b ackw.( poly ) PSx 076 122 077 122 078 122 079 122
[spacer] DIST: R2' , forw.( poly ) P Sx 076 119 077 119 078 119 079 119
[spacer] DIST: R2' , backw.(poly) PSx 076 125 077 125 078 125 079 125
[spacer] DIST: R3, f or w. ( pol y) P Sx 076 117 077 117 078 117 079 117
[spacer] DIST: R3, b ackw.( poly ) PSx 076 123 077 123 078 123 079 123
[spacer] DIST: R3' , forw.( poly ) P Sx 076 120 077 120 078 120 079 120
[spacer] DIST: R3' , backw.(poly) PSx 076 126 077 126 078 126 079 126
Parameter Address
[spacer] DIST: R4, f or w. ( pol y) P Sx 080 019 081 019 082 019 083 019
[spacer] DIST: R4, b ackw.(poly ) PSx 080 021 081 021 082 021 083 021
[spacer] DIST: R4' , forw.( poly ) P Sx 080 020 081 020 082 020 083 020
[spacer] DIST: R4' , backw.(poly) PSx 080 022 081 022 082 022 083 022
[spacer]
Setting for the resistance boundaries (arc reserve) of zones 1 to 4 (or 1' to 4') of
the polygonal characteristic, in forward and reverse directions, in secondary
values.
[spacer] DIST: Rg1, forward P Sx 076 138 077 138 078 138 079 138
[spacer] DIST: Rg1, backwar d PS x 076 144 077 144 078 144 079 144
[spacer] DIST: Rg1', for ward PS x 076 141 077 141 078 141 079 141
[spacer] DIST: Rg1', backwar d PS x 076 147 077 147 078 147 079 147
[spacer] DIST: Rg2, forward P Sx 076 139 077 139 078 139 079 139
[spacer] DIST: Rg2, backwar d PS x 076 145 077 145 078 145 079 145
[spacer] DIST: Rg2', for ward PS x 076 142 077 142 078 142 079 142
[spacer] DIST: Rg2', backwar d PS x 076 148 077 148 078 148 079 148
[spacer] DIST: Rg3, forward P Sx 076 140 077 140 078 140 079 140
[spacer] DIST: Rg3, backwar d PS x 076 146 077 146 078 146 079 146
Parameter Address
[spacer] DIST: Rg3', for ward PS x 076 143 077 143 078 143 079 143
[spacer] DIST: Rg3', bac kwar d PS x 076 149 077 149 078 149 079 149
[spacer] DIST: Rg4, forward P Sx 080 023 081 023 082 023 083 023
[spacer] DIST: Rg4, backwar d PS x 080 025 081 025 082 025 083 025
[spacer] DIST: Rg4', for ward PS x 080 024 081 024 082 024 083 024
[spacer] DIST: Rg4', bac kwar d PS x 080 026 081 026 082 026 083 026
[spacer]
Setting for the limit resistance for simultaneous load blinding of zones 1 to 4 (or
1' to 4') of the circular and polygonal characteristics, in forward and reverse
directions, in secondary values.
Note: The maximum setting value Rg is set to the same value as that of
impedance reach Z of the respective zone. If Rg is higher, the signal “Setting
Error Distance Protection” is issued and the protection function is blocked.
[spacer] DIST: Alpha_L 1 (poly) PS x 012 013 012 063 013 013 013 063
[spacer] DIST: Alpha_L 2 (poly) PS x 012 014 012 064 013 014 013 064
[spacer] DIST: Alpha_L 3 (poly) PS x 012 015 012 065 013 015 013 065
45 40 90 °
[spacer] DIST: Alpha_L 4 (poly) PS x 080 010 081 010 082 010 083 010
45 40 90 °
[spacer]
Setting for the slope angle of the tripping characteristic of impedance zones 1 to
4 in R-direction (resistance line), usually identical to the line impedance angle.
[spacer] DIST: Be ta 1 PSx 072 208 073 208 074 208 075 208
[spacer] DIST: Be ta 2 PSx 072 209 073 209 074 209 075 209
[spacer] DIST: Be ta 3 PSx 072 210 073 210 074 210 075 210
135 90 135 °
Parameter Address
[spacer] DIST: Be ta 4 PS x 080 013 081 013 082 013 083 013
135 90 135 °
[spacer]
Angle setting for load blinding (directional line) in quadrant 2 or 4 of impedance
zones 1 to 4 of the circular and polygonal characteristics.
[spacer] DIST: Alpha 1 PS x 076 090 077 090 078 090 079 090
[spacer] DIST: Alpha 2 PS x 076 091 077 091 078 091 079 091
[spacer] DIST: Alpha 3 PS x 076 092 077 092 078 092 079 092
0 0 40 °
[spacer] DIST: Alpha 4 PS x 080 014 081 014 082 014 083 014
0 0 40 °
[spacer]
Angle setting for load blinding (directional line) in the first or third quadrant of
impedance zones 1 to 4 of the circular characteristic.
[spacer] DIST: Gamm a 1 PSx 076 247 077 247 078 247 079 247
[spacer] DIST: Gamm a 2 PSx 076 248 077 248 078 248 079 248
[spacer] DIST: Gamm a 3 PSx 076 249 077 249 078 249 079 249
-45 -45 0 °
[spacer] DIST: Gamm a 4 PSx 080 027 081 027 082 027 083 027
-45 -45 0 °
[spacer]
Angle setting in quadrant 4 or 2 until the limit resistance is active with a
simultaneous load blinding, for the impedance zones 1 to 3 of the circular and
polygonal characteristics.
[spacer] DIST: X1', backward P Sx 021 244 021 254 021 255 022 198
[spacer] DIST: X1, for ward PSx 021 239 021 245 021 246 021 247
[spacer] DIST: X1, backwar d PS x 021 242 021 248 021 249 021 250
[spacer] DIST: X1', forwar d PS x 021 243 021 251 021 252 021 253
[spacer] DIST: X2, for ward PSx 022 199 023 004 023 005 023 006
Parameter Address
[spacer] DIST: X2, backwar d PS x 023 001 023 007 023 008 023 009
[spacer] DIST: X2', forwar d PS x 023 002 023 044 023 045 023 046
[spacer] DIST: X2', back ward P Sx 023 003 023 010 023 011 023 012
[spacer] DIST: X3, for ward PSx 023 016 023 013 023 014 023 015
[spacer] DIST: X3, backwar d PS x 023 017 023 020 023 021 023 022
[spacer] DIST: X3', forwar d PS x 023 018 023 047 023 048 023 049
[spacer] DIST: X3', back ward P Sx 023 019 023 023 023 024 023 025
[spacer] DIST: X4, for ward PSx 023 029 023 026 023 027 023 028
[spacer] DIST: X4, backwar d PS x 023 032 023 035 023 036 023 037
[spacer] DIST: X4', forwar d PS x 023 033 023 038 023 039 023 040
[spacer] DIST: X4', back ward P Sx 023 034 023 041 023 042 023 043
[spacer]
Setting for the reactance boundaries of zones 1 to 4 (or 1' to 4') of the polygonal
characteristics, in forward and reverse directions, in secondary values.
[spacer] DIST: t1 PS x 012 028 012 078 013 028 013 078
[spacer] DIST: t3S PS x 012 030 012 080 013 030 013 080
[spacer]
Setting for the timer stages of impedance zone 1.
[spacer] DIST: t2S PS x 012 029 012 079 013 029 013 079
Parameter Address
[spacer] DIST: t4S PS x 080 011 081 011 082 011 083 011
[spacer]
Setting for the timer stages of impedance zones 2 to 4 if short circuit detection
is active (dependent on dx/dt detection).
[spacer] DIST: t2L PSx 012 190 012 191 012 192 012 193
[spacer] DIST: t3L PSx 012 194 012 195 012 196 012 197
[spacer] DIST: t4L PSx 080 012 081 012 082 012 083 012
[spacer]
Setting for the timer stages of impedance zones 2 to 4 if starting detection is
active (dependent on dx/dt detection).
[spacer] DIST: kze, HSR PSx 012 034 012 084 013 034 013 084
[spacer]
Setting for the zone extension factor HSR for zone1.
Note: The zone extension HSR is controlled by
● Switch on to fault protection,
● an appropriately configured binary signal input.
[spacer] DIST: kze, TDR PSx 012 046 012 096 013 046 013 096
[spacer]
Setting for the zone extension factor TDR for zone 1.
[spacer] DIST: kzeExt/SO TF/PS IG P Sx 012 067 012 068 012 069 012 070
[spacer]
Setting for the zone extension factor of external zone extension, switch on to
fault protection or protective signaling function.
[spacer] DIST: t1,ze Ext /S OF / PS G P Sx 012 198 012 199 012 200 012 201
[spacer]
Setting for the timer stage of external zone extension, switch on to fault
protection or protective signaling function.
[spacer] DIST: Op.mod e dx/ dt , Z 2PS x 072 107 073 107 074 107 075 107
[spacer] DIST: Op.mod e dx/ dt , Z 3PS x 072 197 073 197 074 197 075 197
0: Without
Parameter Address
[spacer] DIST: Op.mod e dx / dt , Z 4PS x 080 029 081 029 082 029 083 029
0: Without
[spacer]
Setting for the operating mode of train start-up detection in zones 2, 3 or 4.
[spacer] DIST: De lta I( di/ dt), Z2PS x 072 198 073 198 074 198 075 198
[spacer] DIST: De lta I( di/ dt), Z3PS x 072 203 073 203 074 203 075 203
[spacer] DIST: De lta I( di/ dt), Z4PS x 080 030 081 030 082 030 083 030
[spacer]
Setting for the current increase required to detect a short circuit operation in the
zone 2, 3 or 4. It must be set to Blocked in order to disable sudden current
change monitoring.
[spacer] DIST: De lta V(dv/ dt) ,Z2 P Sx 072 139 073 139 074 139 075 139
[spacer] DIST: De lta V(dv/ dt) ,Z3 P Sx 072 108 073 108 074 108 075 108
[spacer] DIST: De lta V(dv/ dt) ,Z4 P Sx 080 028 081 028 082 028 083 028
[spacer]
Setting for the voltage drop required to detect a short circuit operation in the
zone 2, 3 or 4. It must be set to Blocked in order to disable sudden voltage
change monitoring.
[spacer] DIST: D.phi( dphi/ dt ),Z2P Sx 072 206 073 206 074 206 075 206
[spacer] DIST: D.phi( dphi/ dt ),Z3P Sx 072 227 073 227 074 227 075 227
30 5 90 °
[spacer] DIST: D.phi( dphi/ dt ),Z4P Sx 080 031 081 031 082 031 083 031
30 5 90 °
[spacer]
Setting for the angle change required to detect a short circuit operation in the
zone 2, 3 or 4. It must be set to Blocked in order to disable sudden angle change
monitoring.
[spacer] DIST: WPC enable d PS x 076 130 077 130 078 130 079 130
[spacer]
Enabling/disabling the zone of wrong phase coupling protection.
[spacer] DIST: WPC V< PS x 076 132 077 132 078 132 079 132
[spacer]
Setting for the undervoltage conditions to detect a wrong phase coupling.
Parameter Address
[spacer] DIST: WPC Zmin PS x 076 135 077 135 078 135 079 135
[spacer]
Setting for the internal limit impedance of the wrong phase coupling protection
zone.
[spacer] DIST: WPC Zmax PS x 076 136 077 136 078 136 079 136
[spacer]
Setting for the external limit impedance of the wrong phase coupling protection
zone.
[spacer] DIST: WPC alp ha PSx 076 133 077 133 078 133 079 133
[spacer]
Setting for the left limit angle of the wrong phase coupling protection zone.
[spacer] DIST: WPC be ta PS x 076 134 077 134 078 134 079 134
[spacer]
Setting for the right limit angle of the wrong phase coupling protection zone.
[spacer] DIST: WPC t PSx 076 137 077 137 078 137 079 137
[spacer]
Setting for the timer stage of the wrong phase coupling protection zone.
Parameter Address
tection
0: No Fig. 3-138, (p. 3-184)
[spacer]
This setting defines the setting group in which high impedance protection is
enabled.
[spacer] DELT A: I min PS x 062 031 063 031 064 031 065 031
[spacer]
Setting for the minimum current trigger for high impedance protection.
[spacer] DELT A: D elta I PSx 062 037 063 037 064 037 065 037
[spacer]
Setting for the operate threshold to detect a sudden current change.
[spacer] DELT A: D elta Phi PSx 062 034 063 034 064 034 065 034
[spacer]
During a defined sampling interval should the angle (with sudden angle change
monitoring enabled) change by more than the value set for this parameter, then
this signal is issued: DELTA: D elt a Phi star ting
[spacer] DELT A: I (3fn) / I (fn) P Sx 062 040 063 040 064 040 065 040
[spacer]
Setting for the ratio of the third harmonic current component to the
fundamental. This value is used as the operate threshold for the harmonics
stabilization feature.
[spacer] DELT A: I (5fn) / I (fn) P Sx 062 042 063 042 064 042 065 042
[spacer]
Setting for the ratio of the fifth harmonic current component to the
fundamental. This value is used as the operate threshold for the harmonics
stabilization feature.
[spacer] DELT A: k S t,I( x fn) /I(fn) P Sx 062 041 063 041 064 041 065 041
[spacer]
Setting whether high impedance protection is Blocked or stabilized (dynamically
extended by multiplication with the factor set here).
[spacer] DELT A: X, forwar d PS x 062 032 063 032 064 032 065 032
[spacer]
Setting for the reactance limit in the forward direction.
Note: The value range depends on the setting at M AIN: Inom devic e.
Parameter Address
[spacer] DELT A: X, backward P Sx 062 033 063 033 064 033 065 033
[spacer]
Setting for the reactance limit in the reverse direction.
Note: The value range depends on the setting at M AIN: Inom device.
[spacer] DELT A: t De lta PS x 062 039 063 039 064 039 065 039
[spacer]
The timer stage tDelta is triggered with operation of high impedance protection
and a Trip signal is issued when the tDelta time-delay set here has elapsed.
[spacer] DELT A: t Block PS x 062 045 063 045 064 045 065 045
[spacer]
Setting for the blocking time duration.
[spacer] DELT A: M ode w/o Volt g. P Sx 062 036 063 036 064 036 065 036
[spacer]
Setting whether high impedance protection will continue to operate or be
Blocked even where voltage measurement in Delta I operating mode is not
available.
Parameter Address
Measuring-circuit MCM ON: Enable PS x 014 200 014 201 014 202 014 203
monitoring
0: No Fig. 3-145, (p. 3-192)
Fig. 3-146, (p. 3-193)
Fig. 3-232, (p. 3-286)
[spacer]
This setting defines the setting group in which CT and VT Supervision is enabled.
[spacer] MCM ON: I -m onit. e nable d PSx 014 240 014 241 014 242 014 243
[spacer]
Disabling and enabling current plausibility.
[spacer] MCM ON: S e le ct curr e nt PSx 014 092 014 093 014 094 014 095
1: IA
[spacer]
When selecting the operating modes Autotransformer feed and Single feed w.
sum I, this setting is used to define whether the plausibility of the resulting
current or a phase current is to be checked for measuring-circuit monitoring
(MCMON) of the current.
[spacer] MCM ON: I d>, I- monit . PSx 014 244 014 245 014 246 014 247
[spacer]
Setting for the operate threshold of the differential characteristic of current
plausibility.
[spacer] MCM ON: m 1, I-monit . P Sx 014 248 014 249 014 250 014 251
[spacer]
Setting for the gradient of the differential characteristic of current plausibility.
[spacer] MCM ON: I > lift monit or. PS x 006 207 006 208 006 209 006 210
[spacer]
Maximum value of the plausibility check current.
[spacer] MCM ON: V-monit . e nable d PSx 014 225 014 226 014 227 014 228
[spacer]
Disabling/enabling undervoltage monitoring.
[spacer] MCM ON: V<, V- monit . PSx 014 229 014 230 014 231 014 232
[spacer]
Setting for the operate threshold of undervoltage monitoring.
[spacer] MCM ON: t V<, V-monit . P Sx 014 233 014 234 014 235 014 236
[spacer]
Setting for the time delay of undervoltage monitoring.
Parameter Address
[spacer] MCM ON: FF enable d PS x 014 204 014 205 014 206 014 207
[spacer]
Enabling/disabling “Fuse Failure” monitoring.
[spacer] MCM ON: I > e nable V<,F F PS x 014 188 014 237 014 238 014 239
[spacer]
Enabling undervoltage and fuse failure monitoring.
[spacer] MCM ON: V<, FF PS x 014 208 014 209 014 210 014 211
[spacer]
Setting for the enable value V< of “Fuse Failure” monitoring.
[spacer] MCM ON: V>, FF PS x 014 212 014 213 014 214 014 215
[spacer]
Setting for the reset value V> of “Fuse Failure” monitoring.
[spacer] MCM ON: Delta V, FF PS x 014 216 014 217 014 218 014 219
[spacer]
Setting for the minimum voltage change for the detection of a “Fuse Failure”
condition.
[spacer] MCM ON: Delta I, FF PS x 014 221 014 222 014 223 014 224
[spacer]
Setting for the maximum current change for the detection of a “Fuse Failure”
condition.
Parameter Address
time protection
0: No Fig. 3-153, (p. 3-199)
[spacer]
This setting defines the setting group in which backup overcurrent-time
protection is enabled.
[spacer] BUOC: I> PS x 010 058 010 078 010 098 011 018
[spacer]
Setting for operate threshold I> of the phase current of the backup overcurrent-
time protection.
[spacer] BUOC: I>> PS x 010 127 010 129 010 131 010 133
[spacer]
Setting for operate threshold I>> of the current of the backup overcurrent-time
protection.
[spacer] BUOC: tI> PS x 010 059 010 079 010 099 011 019
[spacer]
Setting for the operate delay of stage I> of the backup overcurrent-time
protection.
[spacer] BUOC: tI>> PSx 010 128 010 130 010 132 010 134
[spacer]
Setting for the operate delay of stage I>> of the backup overcurrent-time
protection.
Parameter Address
Switch on to fault SOT F : Enab le PS x 011 120 011 121 011 122 011 123
protection
0: No Fig. 3-156, (p. 3-201)
[spacer]
This setting defines the setting group in which switch on to fault protection is
enabled.
[spacer] SOT F : Operating mode PS x 011 061 011 114 011 115 011 116
[spacer]
The setting of the operating mode defines whether, while the timer is running, a
general starting will lead to a trip command (Trip with starting) or if the
measuring range of the impedance zone 1 is extended by the set zone extension
factor DIST : k ze, HS R PS x (Trip with overreach).
[spacer] SOT F : Man. close t ime r P Sx 011 060 011 111 011 112 011 113
[spacer]
Setting for the timer stage that will be started by a manual close.
Parameter Address
Protective signaling PSIG1: Enable PS x 015 014 015 015 015 016 015 017
[spacer] PSIG2: Enable PS x 020 002 020 003 020 004 020 005
0: No
[spacer]
This setting defines the parameter subset in which protective signaling is
enabled.
[spacer] PSIG1: Operating mode P Sx 015 000 024 000 024 060 025 020
[spacer] PSIG2: Operating mode P Sx 019 239 019 242 019 243 019 244
0: Without
[spacer]
Setting for the operating mode of protective signaling.
[spacer] PSIG1: Fct. S end S ignal PS x 019 108 019 114 019 115 019 117
[spacer] PSIG2: Fct. S end S ignal PS x 020 030 020 031 020 032 020 033
[spacer]
N-to-m parameter to select, which starting signals and direction shall be logically
combined with NOT/AND/OR logic to get sent as an active PSIG signal to the
opposite device.
[spacer] PSIG1: R ele ase t . send PS x 015 002 024 001 024 061 025 021
[spacer] PSIG2: R ele ase t . send PS x 019 245 019 246 019 247 019 248
[spacer]
This setting determines the duration of the send signal.
[spacer] PSIG1: Trip de lay t ime P Sx 019 179 019 180 019 181 019 182
[spacer] PSIG2: Trip de lay t ime P Sx 020 047 020 048 020 049 020 050
[spacer]
Setting for the trip delay of the trip signal.
[spacer] PSIG1: Echo on rec eiv e PSx 015 003 024 002 024 062 025 022
[spacer] PSIG2: Echo on rec eiv e PSx 019 249 019 251 019 252 019 253
0: Without
[spacer]
This setting determines whether protective signaling operates with or without
echo.
Parameter Address
[spacer] PSIG1: Op. delay e cho PS x 015 022 024 008 024 068 025 028
[spacer] PSIG2: Op. delay e cho PS x 020 018 020 019 020 020 020 021
[spacer]
Setting for the operate delay of the echo pulse.
[spacer] PSIG1: Puls e du r. e cho P Sx 015 023 024 009 024 069 025 029
[spacer] PSIG2: Puls e du r. e cho P Sx 020 022 020 023 020 024 020 025
[spacer]
Setting for echo pulse duration.
[spacer] PSIG1: Fct.Telecom.chnl. PSx 019 149 019 160 019 161 019 162
[spacer] PSIG2: Fct.Telecom.chnl. PSx 020 039 020 040 020 041 020 042
[spacer]
Definition of the related communication link to the relevant PSIG receive signal.
[spacer] PSIG1: Telecom.fl t.enl. PS x 019 175 019 176 019 177 019 178
[spacer] PSIG2: Telecom.fl t.enl. PS x 020 043 020 044 020 045 020 046
[spacer]
Time stage to enlarge the telecommunication fault signal for a further duration
time to be reliably detected by the alarm logic.
[spacer] PSIG1: t Trans.bl ock . PS x 015 024 024 010 024 070 025 030
[spacer] PSIG2: t Trans.bl ock . PS x 020 026 020 027 020 028 020 029
[spacer]
Setting for the transient blocking time of protective signaling.
[spacer] PSIG1: Fct. Trip Signal PS x 019 118 019 119 019 146 019 147
[spacer] PSIG2: Fct. Trip Signal PS x 020 034 020 035 020 036 020 037
[spacer]
Definition of the receive signal in combination with internal starting & state
signals to generate a related trip command.
[spacer] PSIG1: Funct.B lock S ig P Sx 019 222 019 223 019 224 019 225
Parameter Address
[spacer] PSIG2: Funct.B lock S ig P Sx 020 052 020 053 020 054 020 055
[spacer]
Definition of the blocking signal activated by the received signal.
[spacer] PSIG1: V< weak infee d PS x 015 020 024 006 024 066 025 026
[spacer] PSIG2: V< weak infee d PS x 020 010 020 011 020 012 020 013
[spacer]
Setting for the threshold of the weak infeed logic.
[spacer] PSIG1: Trip signal V< PSx 015 021 024 007 024 067 025 027
[spacer] PSIG2: Trip signal V< PSx 020 014 020 015 020 016 020 017
0: Without
[spacer]
This setting determines whether a trip signal will be issued when the weak-
infeed logic is triggered.
[spacer] PSIG1: tV< PSx 015 019 024 005 024 065 025 025
[spacer] PSIG2: tV< PSx 020 006 020 007 020 008 020 009
[spacer]
Setting for the operate delay of weak-infeed logic.
Parameter Address
Auto-reclosing ARC: Enable PS x 015 046 015 047 015 048 015 049
control
0: No Fig. 3-175, (p. 3-220)
[spacer]
This setting defines the parameter subset in which ARC is enabled.
[spacer] ARC: C B clos.pos .s ig. PS x 015 050 024 024 024 084 025 044
[spacer]
This setting defines whether the CB closed position will be taken into account or
not. If the setting is With, a binary signal input must be configured accordingly.
Then the ARC function is ready only if the CB is closed.
[spacer] ARC: Paralle l trip PS x 015 053 024 027 024 087 025 047
[spacer]
This setting defines whether and how the trip command(s) of a protection device
operating in parallel to the P438 will affect operation of the ARC function.
[spacer] ARC: Op erative t ime 1 P Sx 015 066 024 035 024 095 025 055
[spacer]
Setting for operative time 1.
If the fault is cleared within this time, the fixed dead time 1p or 3p (depending
on the trip condition and HSR operating mode) is started.
[spacer] ARC: Op erative t ime 2 P Sx 015 083 024 042 025 002 025 062
[spacer]
Setting for operative time 2.
If the fault is cleared within this time, the maximum dead time is started.
[spacer] ARC: V> PS x 015 128 015 129 015 138 015 139
[spacer]
Voltage enabling of reclosure when operative time 2 is used.
[spacer] ARC: t V> PSx 015 140 015 141 015 142 015 143
[spacer]
Time delay of voltage enabling.
[spacer] ARC: HSR -tr.DIS T t1 P Sx 015 072 024 040 025 000 025 060
[spacer]
Setting for the HSR tripping timer stage initiated by a distance protection zone 1
start.
[spacer] ARC: HSR -tr.DIS T t2S PS x 015 144 015 145 015 146 015 147
Parameter Address
[spacer] ARC: HSR -tr.DIS T t2L P Sx 015 152 015 153 015 154 015 155
[spacer]
Setting for the HSR tripping timer stage initiated by a distance protection zone 2
start together with train start-up detection dx/dt in zone 2.
[spacer] ARC: HSR -tr.DIS T t3S PS x 015 160 015 161 015 162 015 163
[spacer] ARC: HSR -tr.DIS T t3L P Sx 015 168 015 169 015 170 015 171
[spacer]
Setting for the HSR tripping timer stage initiated by a distance protection zone 3
start together with train start-up detection dx/dt in zone 3.
[spacer] ARC: HSR -tr.DIS T t4S PS x 015 180 015 181 015 182 015 183
[spacer] ARC: HSR -tr.DIS T t4L P Sx 015 188 015 189 015 190 015 191
[spacer]
Setting for the HSR tripping timer stage initiated by a distance protection zone 4
start together with train start-up detection dx/dt in zone 4.
[spacer] ARC: HSR -tr.DEL TA t D. PS x 008 192 008 193 008 194 008 195
[spacer]
Setting for the HSR tripping timer stage initiated by a start of the high
impedance protection.
[spacer] ARC: HSR -tr.DTOC t I>H PS x 015 069 024 052 024 053 024 054
[spacer]
Setting for the HSR tripping timer stage initiated by a start of the DTOC high-
current stage.
[spacer] ARC: HSR -tr.DTOC t I> PS x 015 105 020 105 021 105 022 105
[spacer] ARC: HSR -tr.DTOC t I>> PS x 015 074 020 107 021 107 022 107
[spacer]
Setting for the HSR tripping timer stage initiated by a start of the DTOC 1st or
2nd high-current stage.
[spacer] ARC: HSR -tr.DTOC A t I > PS x 015 196 020 196 021 196 023 196
[spacer] ARC: HSR -tr.DTOC A t I >>PS x 015 197 020 197 021 197 023 197
[spacer] ARC: HSR -tr.DTOC B tI> PS x 015 213 020 213 021 213 023 213
Parameter Address
[spacer] ARC: HSR -tr.DTOC B tI>>PS x 015 214 020 214 021 214 023 214
[spacer]
Setting for the HSR tripping timer stage initiated by a start of the 1st or 2nd high-
current stage of DTOCA or DTOCB.
Note: The function groups DTOCA and DTOCB analyze only CT A or CT B,
respectively, and therefore they are active only with the setting
MAIN: Fe e de r mode = Autotransformer feed.
[spacer] ARC: HSR -tr.I DMT k IrefP Sx 015 094 020 113 021 113 022 113
[spacer]
Setting for the HSR tripping timer stage initiated by a start of the IDMT Ikref
stage.
[spacer] ARC: HSR -tr.I DMT AkI r efPSx 015 217 020 217 021 217 023 217
[spacer] ARC: HSR -tr.I DMT Bk IrefP Sx 015 219 020 219 021 219 023 219
[spacer]
Setting for the HSR tripping timer stage initiated by a start of the Ikref stage of
IDMTA or IDMTB.
Note: The function groups IDMTA and IDMTB analyze only CT A or CT B,
respectively, and therefore they are active only with the setting
M AI N: Feeder mode = Autotransformer feed.
[spacer] ARC: HSR -tr.BUOC t I> PS x 015 109 020 109 022 109 023 109
[spacer] ARC: HSR -tr.BUOC t I>> PS x 015 111 020 111 021 111 022 111
[spacer]
Setting for the HSR tripping timer stage initiated by a start of the BUOC 1st or
2nd high-current stage.
[spacer] ARC: HSR -tr. LO GIC P S x 015 098 024 110 024 160 025 110
[spacer]
Setting for the HSR tripping time and start via programmable logic.
[spacer] ARC: HSR d ead t ime P Sx 015 056 024 030 024 090 025 050
[spacer]
Dead time setting for a three-pole HSR.
[spacer] ARC: Dead tim e max P Sx 015 084 024 043 025 003 025 063
[spacer]
Setting for the maximum dead time.
Parameter Address
[spacer] ARC: Zone e x t . f . HS R P Sx 015 059 024 033 024 093 025 053
[spacer]
This setting determines whether the measuring range shall be extended by the
zone extension factor kze HSR during normal system operation and while the
operative times are elapsing.
Note: This setting is only active if protective signaling is not ready.
[spacer] ARC: No. permit . T DR PS x 015 068 024 037 024 097 025 057
[spacer]
Setting for the number of time-delayed reclosures permitted. With the 0 setting,
only one HSR is carried out.
[spacer] ARC: T DR -tr.DIS T t1 PS x 015 073 024 041 025 001 025 061
[spacer]
Setting for the TDR tripping timer stage initiated by a distance protection zone 1
start.
[spacer] ARC: T DR -tr.DIS T t2 S P Sx 015 148 015 149 015 150 015 151
[spacer] ARC: T DR -tr.DIS T t2 L PS x 015 156 015 157 015 158 015 159
[spacer]
Setting for the TDR tripping timer stage initiated by a distance protection zone 2
start together with train start-up detection dx/dt in zone 2.
[spacer] ARC: T DR -tr.DIS T t3 S P Sx 015 164 015 165 015 166 015 167
[spacer] ARC: T DR -tr.DIS T t3 L PS x 015 172 015 173 015 174 015 175
[spacer]
Setting for the TDR tripping timer stage initiated by a distance protection zone 3
start together with train start-up detection dx/dt in zone 3.
[spacer] ARC: T DR -tr.DIS T t4 S P Sx 015 184 015 185 015 186 015 187
[spacer] ARC: T DR -tr.DIS T t4 L PS x 015 192 015 193 015 194 015 195
[spacer]
Setting for the TDR tripping timer stage initiated by a distance protection zone 4
start together with train start-up detection dx/dt in zone 4.
[spacer] ARC: T DR -tr.DEL TA tD . P Sx 008 196 008 197 008 198 008 199
[spacer]
Setting for the TDR tripping timer stage initiated by a start of the high
impedance protection.
Parameter Address
[spacer] ARC: T DR -tr.DTO C t I>H P Sx 015 070 024 055 024 056 024 057
[spacer]
Setting for the TDR tripping timer stage initiated by a start of the DTOC high-
current stage.
[spacer] ARC: T DR -tr.DTO C t I> P Sx 015 106 020 106 021 106 022 106
[spacer] ARC: T DR -tr.DTO C t I>> PS x 015 075 020 108 022 108 023 108
[spacer]
Setting for the TDR tripping timer stage initiated by a start of the DTOC 1st or
2nd high-current stage.
[spacer] ARC: T DR -tr.DTO CA t I> PSx 015 198 020 198 021 198 023 198
[spacer] ARC: T DR -tr.DTO CA t I>>P Sx 015 199 020 199 021 199 023 199
[spacer] ARC: T DR -tr.DTO CB t I> P Sx 015 215 020 215 021 215 023 215
[spacer] ARC: T DR -tr.DTO CB t I>>P Sx 015 216 020 216 021 216 023 216
[spacer]
Setting for the TDR tripping timer stage initiated by a start of the 1st or 2nd high-
current stage of DTOCA or DTOCB.
Note: The function groups DTOCA and DTOCB analyze only CT A or CT B,
respectively, and therefore they are active only with the setting
MAIN: Fe e de r mode = Autotransformer feed.
[spacer] ARC: T DR -tr.I DMT kIre fPS x 015 095 020 114 021 114 022 114
[spacer]
Setting for the TDR tripping timer stage initiated by a start of the IDMT Ikref
stage.
[spacer] ARC: T DR -tr.I DMT AkIre fPS x 015 218 020 218 021 218 023 218
[spacer] ARC: T DR -tr.I DMT BkIre fPS x 015 220 020 220 021 220 023 220
[spacer]
Setting for the TDR tripping timer stage initiated by a start of the Ikref stage of
IDMTA or IDMTB.
Note: The function groups IDMTA and IDMTB analyze only CT A or CT B,
respectively, and therefore they are active only with the setting
M AI N: Feeder mode = Autotransformer feed.
[spacer] ARC: T DR -tr.BUO C tI> P Sx 015 110 020 110 021 110 022 110
Parameter Address
[spacer] ARC: T DR -tr.BUO C tI>> PS x 015 112 020 112 021 112 022 112
[spacer]
Setting for the TDR tripping timer stage initiated by a start of the BUOC 1st or
2nd high-current stage.
[spacer] ARC: T DR -tr. L OGI C PS x 015 099 024 122 024 172 025 122
[spacer]
Setting for the TDR tripping time and start via programmable logic.
[spacer] ARC: T DR d ead time PSx 015 057 024 031 024 091 025 051
[spacer]
Setting for the TDR dead time.
[spacer] ARC: Zone e x t . f . T DR PS x 015 071 024 039 024 099 025 059
[spacer]
This setting determines whether the measuring range shall be extended prior to
a TDR.
[spacer] ARC: R eclaim time 1 PS x 015 054 024 028 024 088 025 048
[spacer]
Setting for reclaim time 1.
[spacer] ARC: R eclaim time 2 PS x 015 124 015 125 015 126 015 127
[spacer]
Setting for reclaim time 2.
[spacer] ARC: Block. AR C f. I> PS x 015 104 016 104 017 104 020 104
[spacer]
Setting for the current threshold via which the auto-recloser is blocked.
[spacer] ARC: Block. tim e int . P Sx 015 043 024 021 024 081 025 041
[spacer]
Setting for the time that will elapse before the ARC will be ready again after
cancellation of the blocks set by internal functions, such as SOTF.
[spacer] ARC: Block. tim e e xt. PS x 015 058 024 032 024 092 025 052
[spacer]
Setting for the time that will elapse before the ARC will be ready again after
blocking by a binary signal input.
Parameter Address
[spacer] ARC: Zone e x t .dur. RC P S x 015 088 024 047 025 007 025 067
[spacer]
This setting defines whether the following takes place:
● A zone extension will be carried out during a close command by a HSR that
is not synchronism-checked.
● Zone extension will occur with each reclose command.
[spacer] ARC: R C f. THER M t r ip PS x 015 176 015 177 015 178 015 179
[spacer]
This setting determines whether a reclose command shall be issued for a
thermal overload protection trip signal.
Parameter Address
Automatic ASC: Enab le PS x 018 020 018 021 018 022 018 023
synchronism check
0: No Fig. 3-195, (p. 3-246)
[spacer]
This setting defines the parameter subset in which automatic synchronism check
(ASC) is enabled.
[spacer] ASC: CB ass ignm ent PS x 037 131 037 132 037 133 037 134
[spacer]
This setting defines the function group DEVxx that will control the circuit
breaker.
[spacer] ASC: Sys te m int e grat . PS x 037 135 037 136 037 137 037 138
[spacer]
This setting defines whether ASC will operate in “Autom. synchron. check” or
“Autom. synchr. control” mode.
[spacer] ASC: Active for HSR PS x 018 001 077 030 078 030 079 030
[spacer]
This setting defines whether reclosing after a three-pole HSR will occur only
after being enabled by ASC.
[spacer] ASC: Active for TDR PS x 018 002 077 031 078 031 079 031
[spacer]
This setting defines whether reclosing after a three-pole TDR will occur only
after being enabled by ASC.
[spacer] ASC: Clos .rej.w.block PS x 018 003 077 032 078 032 079 032
[spacer]
This setting defines whether reclosing is rejected after being blocked by ASC.
[spacer] ASC: Op erative time PS x 018 010 077 034 078 034 079 034
[spacer]
Setting for the operative time for ASC.
[spacer] ASC: Phi off set PS x 018 034 077 042 078 042 079 042
[spacer]
Setting for a Phi offset that may be necessary so that determination of the
differential angle is correct.
[spacer] ASC: AR op. m ode P Sx 018 025 018 026 018 027 018 028
1: Voltage-checked
[spacer]
Auto-reclosing control: Criteria for a close enable are defined by setting for the
operating mode.
Parameter Address
[spacer] ASC: AR with tCB PSx 000 038 000 039 000 050 000 051
0: No
[spacer]
Function ASC provides a choice as to whether the CB operating time (tCB), as
configured at M AI N: tCB , C los e is to be taken into account for the precisely
synchronized reclosure (AR) or not.
[spacer] ASC: AR Op.m ode v- chk .P Sx 018 029 018 030 018 031 018 032
[spacer]
Auto-reclosing control: This setting defines the logic linking of trigger decisions
for a voltage controlled close enable.
[spacer] ASC: AR V> volt.che ck PS x 026 017 077 043 078 043 079 043
[spacer]
Auto-reclosing control: Setting the voltage threshold that the phase-to-ground
voltages and the reference voltage must exceed so that they are recognized as
“Voltage present”.
Note: The logic linking of trigger decisions is defined by setting ASC: AR
Op.mode v-chk.PS x.
[spacer] ASC: AR V< volt.che ck PS x 018 017 077 040 078 040 079 040
[spacer]
Auto-reclosing control: Setting the voltage threshold that the phase-to-ground
voltages and the reference voltage must fall below so that they are recognized
as “No voltage”.
Note: The logic linking of trigger decisions is defined by setting ASC: AR
Op.mode v-chk.PS x.
[spacer] ASC: AR tmin v- check PS x 018 018 077 041 078 041 079 041
[spacer]
Auto-reclosing control: Setting for the operate delay value to define the
minimum time period during which voltage conditions must be met so that the
close enable of the ASC is effected.
[spacer] ASC: AR V> s ync.che ck PS x 018 011 077 035 078 035 079 035
[spacer]
Auto-reclosing control: Setting for the threshold of the minimum voltage to
obtain a synchronism checked close enable.
[spacer] ASC: AR Delt a Vmax PSx 018 012 077 036 078 036 079 036
[spacer]
Auto-reclosing control: Setting the maximum differential voltage between
measured and reference voltages to obtain a synchronism checked close enable.
Parameter Address
[spacer] ASC: AR Delt a f max PS x 018 014 077 038 078 038 079 038
[spacer]
Auto-reclosing control: Setting the maximum differential frequency between
measured and reference voltages to obtain a synchronism checked close enable.
[spacer] ASC: AR Delt a phi max PS x 018 013 077 037 078 037 079 037
[spacer]
Auto-reclosing control: Setting the maximum differential angle between
measured and reference voltages to obtain a synchronism checked close enable.
[spacer] ASC: AR tmin sync.chk PS x 018 015 077 039 078 039 079 039
[spacer]
Auto-reclosing control: Setting for the operate delay value to define the
minimum time period during which synchronism conditions must be met so that
the close enable of the ASC is effected.
[spacer] ASC: MC op. mod e P Sx 000 056 000 057 000 058 000 059
1: Voltage-checked
[spacer]
Manual close command: Criteria for a close enable are defined by setting for the
operating mode.
[spacer] ASC: MC wit h tCB P Sx 000 102 000 103 000 104 000 105
0: No
[spacer]
Manual close command: In slightly asynchronous power systems, setting this
parameter to Yes ensures that the circuit breaker closing time is taken into
account by the automatic synchronism check (ASC) to issue of a close
command.
[spacer] ASC: MC op.mode v- chk. PSx 000 060 000 061 000 062 000 063
[spacer]
Manual close command: This setting defines the logic linking of trigger decisions
for a voltage controlled close enable.
[spacer] ASC: MC V> volt .che ck PSx 000 064 000 065 000 066 000 067
[spacer]
Manual close command: Setting the voltage threshold that the phase-to-ground
voltages and the reference voltage must exceed so that they are recognized as
“Voltage present”.
Note: The logic linking of trigger decisions is defined by setting ASC: MC
op.mode v-chk .PS x.
Parameter Address
[spacer] ASC: MC V< volt .che ck PSx 000 068 000 069 000 070 000 071
[spacer]
Manual close command: Setting the voltage threshold that the phase-to-ground
voltages and the reference voltage must fall below so that they are recognized
as “No voltage”.
Note: The logic linking of trigger decisions is defined by setting ASC: MC
op.mode v-chk .PS x.
[spacer] ASC: MC tm in v-che ck P Sx 000 072 000 073 000 074 000 075
[spacer]
Manual close command: Setting for the operate delay value to define the
minimum time period during which voltage conditions must be met so that the
close enable of the ASC is effected.
[spacer] ASC: MC V> sync .che ck P Sx 000 052 000 053 000 054 000 055
[spacer]
Manual close command: Setting for the threshold of the minimum voltage to
obtain a synchronism checked close enable.
[spacer] ASC: MC De lta Vmax PS x 000 080 000 081 000 082 000 083
[spacer]
Manual close command: Setting the maximum differential voltage between
measured and reference voltages to obtain a synchronism checked close enable.
[spacer] ASC: MC De lta f max P S x 000 084 000 086 000 087 000 088
[spacer]
Manual close command: Setting the maximum differential frequency between
measured and reference voltages to obtain a synchronism checked close enable.
[spacer] ASC: MC De lta phi max P Sx 000 089 000 091 000 092 000 093
[spacer]
Manual close command: Setting the maximum differential angle between
measured and reference voltages to obtain a synchronism checked close enable.
[spacer] ASC: MC tm in s ync.chk PS x 000 098 000 099 000 100 000 101
[spacer]
Manual close command: Setting for the operate delay value to define the
minimum time period during which synchronism conditions must be met so that
the close enable of the ASC is effected.
Parameter Address
Definite-time over‐ DTOC: Enable PSx 072 098 073 098 074 098 075 098
current protection
0: No Fig. 3-210, (p. 3-263)
[spacer]
This setting defines the parameter subset in which definite-time overcurrent
protection is enabled.
[spacer] DTOC: I>H PS x 072 009 073 009 074 009 075 009
[spacer]
Setting for the threshold of the instantaneous high-set stage I>H.
[spacer] DTOC: I> PS x 072 007 073 007 074 007 075 007
[spacer] DTOC: I>> PS x 072 008 073 008 074 008 075 008
[spacer]
Setting for operate value of the overcurrent stage.
[spacer] DTOC: tI>H PSx 072 021 073 021 074 021 075 021
[spacer]
Setting for the operate delay of instantaneous high-set stage I>H.
[spacer] DTOC: tI> PSx 072 019 073 019 074 019 075 019
[spacer] DTOC: tI>> PSx 072 020 073 020 074 020 075 020
[spacer]
Setting for the operate delay of the overcurrent stage.
[spacer] DTOC: Tim er St art tI> P Sx 071 146 071 147 071 148 071 149
[spacer]
This setting defines whether timer stage tI> is started with triggering of current
thresholds I> or, additionally, with a directional signal.
[spacer] DTOC: Tim er St art tI>> P Sx 072 245 073 044 074 044 075 044
[spacer]
This setting defines whether timer stage tI>> is started with the triggering of
current thresholds I>> or, additionally, with a directional signal.
[spacer] DTOC: Be ta (I>) P Sx 076 068 077 068 078 068 079 068
[spacer]
Angles β and γ set the range in which the I> starting signal logic determines
that the direction is forward.
Parameter Address
[spacer] DTOC: Be ta (I>>) P Sx 076 069 077 069 078 069 079 069
[spacer]
Angles β and γ set the range in which the I>> starting signal logic determines
that the direction is forward.
[spacer] DTOC: Gamm a (I>) PSx 076 073 077 073 078 073 079 073
[spacer]
Angles β and γ set the range in which the I> starting signal logic determines
that the direction is forward.
[spacer] DTOC: Gamm a (I>>) PSx 076 074 077 074 078 074 079 074
[spacer]
Angles β and γ set the range in which the I>> starting signal logic determines
that the direction is forward.
[spacer] DTOC: Direction (I>) P Sx 076 080 077 080 078 080 079 080
[spacer]
Setting for the measuring direction for which a tI> trip signal is sent: forward,
reverse or non-directional.
[spacer] DTOC: Direction (I>>) P Sx 076 088 077 088 078 088 079 088
3: Non-directional
[spacer]
Setting for the measuring direction for which a tI>> trip signal is sent: forward,
reverse or non-directional.
[spacer] DTOC: V< (I>) PS x 076 131 077 131 078 131 079 131
[spacer]
The tI> trip signal is enabled only if the voltage is lower than the set value.
Enabling is permanent if it is set to Blocked.
[spacer] DTOC: V< (I>>) PS x 076 150 077 150 078 150 079 150
[spacer]
The tI>> trip signal is enabled only if the voltage is lower than the set value.
Enabling is permanent if it is set to Blocked.
[spacer] DTOC: Vmin ( I>) PSx 076 157 077 157 078 157 079 157
[spacer]
A direction decision of the I> overcurrent stage is possible only if the short
circuit voltage is higher than this set value.
[spacer] DTOC: Vmin ( I>>) PSx 076 158 077 158 078 158 079 158
[spacer]
A direction decision of the I>> overcurrent stage is possible only if the short
circuit voltage is higher than this set value.
Parameter Address
[spacer] DTOC: Mod e w/ o V (I>) PS x 076 128 077 128 078 128 079 128
[spacer]
This setting defines whether, for a voltage measuring circuit failure, the I>
overcurrent stage should operate non-directional or should be blocked.
[spacer] DTOC: Mod e V<Vmin ( I>) PSx 076 113 077 113 078 113 079 113
[spacer]
This setting defines whether, for a short circuit voltage which is lower than Vmin,
the I> overcurrent stage should operate non-directional or should be blocked.
[spacer] DTOC: Mod e V<Vmin(I>>) P Sx 076 127 077 127 078 127 079 127
1: Non-directional
[spacer]
This setting defines whether, for a short circuit voltage which is lower than Vmin,
the I>> overcurrent stage should operate non-directional or should be blocked.
[spacer] DTOC: Mod e w/ o V (I>>) PS x 076 129 077 129 078 129 079 129
2: Blocked
[spacer]
This setting defines whether, for a voltage measuring circuit failure, the I>>
overcurrent stage should operate non-directional or should be blocked.
Parameter Address
Definite-time over‐ DTOCA: Enab le PS x 130 060 131 060 132 060 133 060
current protection
0: No Fig. 3-216, (p. 3-269)
[spacer] DTOCB: E nable PSx 130 080 131 080 132 080 133 080
0: No
[spacer]
This setting defines the parameter subset in which definite-time overcurrent
protection – DTOCA / DTOCB – is enabled.
[spacer] DTOCA: I> PS x 130 061 131 061 132 061 133 061
[spacer] DTOCB: I > PS x 130 081 131 081 132 081 133 081
[spacer]
Setting for operate value I>. Note that only CT A / CT B is taken into account,
and MAIN: Fe eder mode must be set to Autotransformer feed.
[spacer] DTOCA: I>> PS x 130 062 131 062 132 062 133 062
[spacer] DTOCB: I >> PS x 130 082 131 082 132 082 133 082
[spacer]
Setting for operate value I>>. Note that only CT A / CT B is taken into account,
and MAIN: Fe eder mode must be set to Autotransformer feed.
[spacer] DTOCA: tI> PSx 130 063 131 063 132 063 133 063
[spacer] DTOCB: tI > PS x 130 083 131 083 132 083 133 083
[spacer]
Setting for the operate delay of overcurrent stage I>. Note that only CT A / CT B
is taken into account, and MAIN: F eede r mode must be set to
Autotransformer feed.
[spacer] DTOCA: tI>> PSx 130 064 131 064 132 064 133 064
[spacer] DTOCB: tI >> PS x 130 084 131 084 132 084 133 084
[spacer]
Setting for the operate delay of overcurrent stage I>>. Note that only CT A /
CT B is taken into account, and M AIN: F ee der mode must be set to
Autotransformer feed.
Parameter Address
rent protection
0: No Fig. 3-218, (p. 3-271)
[spacer]
This setting defines the parameter subset in which inverse-time overcurrent
protection is enabled (phase current system).
[spacer] IDMT: I ref PSx 072 050 073 050 074 050 075 050
[spacer]
Setting for the reference current of the curve.
[spacer] IDMT: C haracteristic P Sx 072 056 073 056 074 056 075 056
[spacer]
Setting for the tripping characteristic.
[spacer] IDMT: C har. factor kt P S x 072 053 073 053 074 053 075 053
[spacer]
Setting for the characteristic time multiplier
[spacer] IDMT: M in. trip t ime P Sx 072 077 073 077 074 077 075 077
[spacer]
Setting for the minimum trip time.
[spacer] IDMT: Hold t ime PSx 072 071 073 071 074 071 075 071
[spacer]
Setting for the hold time or intermittent faults.
[spacer] IDMT: R e se t PS x 072 059 073 059 074 059 075 059
[spacer]
Setting for the release or reset characteristic (phase current system).
[spacer] IDMT: T im e r S ta. tIre f>P S x 006 061 006 062 006 063 006 064
[spacer]
This setting defines whether timer stage tIref> is started with the triggering of
IDMT protection or, additionally, with a directional signal.
[spacer] IDMT: B e ta PS x 072 046 073 046 074 046 075 046
Parameter Address
[spacer] IDMT: Gamm a PSx 072 047 073 047 074 047 075 047
[spacer]
Angles β and γ set the range in which the inverse-time overcurrent starting
signal logic determines that the direction is “forward”.
[spacer] IDMT: D ire ct ion ( I>) PS x 072 048 073 048 074 048 075 048
[spacer]
Setting for the measuring direction for which a tIref> trip signal is sent: forward,
reverse or non-directional.
[spacer] IDMT: V< PS x 072 081 073 081 074 081 075 081
[spacer]
The tIref> trip signal is enabled only if the voltage is lower than the set value.
Enabling is permanent if it is set to Blocked.
[spacer] IDMT: Vm in PSx 072 133 073 133 074 133 075 133
[spacer]
A direction decision of the definite-time overcurrent protection is possible only if
the short circuit voltage is higher than this set value.
[spacer] IDMT: O p. m ode V<Vmin P Sx 072 138 073 138 074 138 075 138
1: Non-directional
[spacer]
This setting defines whether, for a short circuit voltage which is lower than Vmin,
the definite-time overcurrent protection should operate non-directional or should
be blocked.
[spacer] IDMT: M ode w/o v olt age PSx 072 119 073 119 074 119 075 119
[spacer]
This setting defines whether, in case of voltage measuring circuit failure, the
definite-time overcurrent protection function should operate non-directionally or
should be blocked.
Parameter Address
rent protection
0: No Fig. 3-229, (p. 3-283)
[spacer] IDMTB : Enab le PS x 130 120 131 120 132 120 133 120
0: No
[spacer]
This setting defines the parameter subset in which inverse-time overcurrent
protection – IDMTA / IDMTB – is enabled (phase current system).
[spacer] IDMTA: I r ef PSx 130 101 131 101 132 101 133 101
[spacer] IDMTB : I ref PS x 130 121 131 121 132 121 133 121
[spacer]
Setting for the reference current of the curve. Note that only CT A / CT B is taken
into account, and M AIN: Fe ede r mode must be set to Autotransformer
feed.
[spacer] IDMTA: C haracteri stic P Sx 130 102 131 102 132 102 133 102
[spacer] IDMTB : C haracteri stic P Sx 130 122 131 122 132 122 133 122
0: Definite Time
[spacer]
Setting for the tripping characteristic. Note that only CT A / CT B is taken into
account, and MAIN: F eede r mode must be set to Autotransformer feed.
[spacer] IDMTA: C har. factor kt P Sx 130 103 131 103 132 103 133 103
[spacer] IDMTB : C har. f actor kt P Sx 130 123 131 123 132 123 133 123
[spacer]
Setting for the characteristic time multiplier. Note that only CT A / CT B is taken
into account, and M AIN: Fe ede r mode must be set to Autotransformer
feed.
[spacer] IDMTA: M in. trip time PS x 130 104 131 104 132 104 133 104
[spacer] IDMTB : M in. t rip time PS x 130 124 131 124 132 124 133 124
[spacer]
Setting for the minimum trip time. Note that only CT A / CT B is taken into
account, and MAIN: F eede r mode must be set to Autotransformer feed.
[spacer] IDMTA: Hold t ime PSx 130 105 131 105 132 105 133 105
Parameter Address
[spacer] IDMTB : Hold time P S x 130 125 131 125 132 125 133 125
[spacer]
Setting for the hold time or intermittent faults. Note that only CT A / CT B is
taken into account, and MAIN: Fe ede r mode must be set to
Autotransformer feed.
[spacer] IDMTA: R e s et PS x 130 106 131 106 132 106 133 106
[spacer] IDMTB : R ese t PS x 130 126 131 126 132 126 133 126
1: Without delay
[spacer]
Setting for the release or reset characteristic. Note that only CT A / CT B is taken
into account, and MAIN: Fe ede r mode must be set to Autotransformer
feed.
Parameter Address
Defrost protection DFR ST : Enab le PS x 019 130 019 131 019 132 019 133
[spacer]
This setting defines the setting group in which defrost protection is enabled.
[spacer] DFR ST : Id> PS x 019 134 019 135 019 136 019 137
[spacer]
Setting for the pickup threshold of the differential characteristic of the defrost
protection function.
[spacer] DFR ST : m1 PS x 019 138 019 139 019 140 019 141
[spacer]
Setting for the gradient of the differential characteristic of the defrost protection
function.
[spacer] DFR ST : t PSx 019 142 019 143 019 144 019 145
[spacer]
Setting for the operate delay of the defrost protection function.
Parameter Address
Thermal overload THER M : Enable PSx 072 175 073 175 074 175 075 175
protection
0: No Fig. 3-234, (p. 3-287)
[spacer]
This setting defines the parameter subset in which thermal overload protection
is enabled.
[spacer] THER M : Ir ef PSx 072 179 073 179 074 179 075 179
[spacer]
Setting for the reference current.
[spacer] THER M : S tar t .f act.OL_RC PS x 072 180 073 180 074 180 075 180
[spacer]
Setting for the starting factor to trigger overload recording.
[spacer] THER M : Tim.const .1 ,>Ibl PSx 072 187 073 187 074 187 075 187
[spacer]
Setting for the thermal time constants of the protected object with current flow
(Ibl: base line current).
[spacer] THER M : Tim.const .2 ,<Ibl PSx 072 188 073 188 074 188 075 188
[spacer]
Setting for the thermal time constants of the protected object without current
flow (cooling time constant).
Note: This setting option is only relevant when machines are running. In all
other cases, time constant 2 must be set equal to time constant 1.
[spacer] THER M : O/ T f .Iref pe r s. PS x 072 167 073 167 074 167 075 167
80 0 300 K
[spacer]
Setting for the overtemperature resulting from persistent thermal limit current.
Note: This setting is only enabled in the Absolute replica mode of operation.
[spacer] THER M : R e l. O/ T warning P Sx 072 184 073 184 074 184 075 184
[spacer]
Setting for the operate threshold of the warning stage.
Note: This setting is enabled only in the Relative replica operating mode.
[spacer] THER M : R e l. O/ T t rip P Sx 072 181 073 181 074 181 075 181
[spacer]
Setting for the operate threshold of the trip stage.
Note: This setting is enabled only in the Relative replica operating mode.
Parameter Address
[spacer] THER M : Abs. O/ T warning PS x 072 153 073 153 074 153 075 153
95 0 300 °C
[spacer]
Setting for the temperature (in °C) to trigger a warning alarm.
Note: This setting is only enabled in the Absolute replica mode of operation.
[spacer] THER M : M ax.pe rm.obj .t mp.PS x 072 182 073 182 074 182 075 182
[spacer]
Setting for the maximum permissible temperature of the protected object.
[spacer] THER M : M ax.pe rm.cool.t mpPS x 072 185 073 185 074 185 075 185
[spacer]
Setting for the maximum permissible coolant temperature.
Note: This setting is active only if the coolant temperature is measured via the
PT 100 or the 20 mA input.
[spacer] THER M : S ele ct CTA P Sx 072 177 073 177 074 177 075 177
[spacer]
This setting defines whether coolant temperature (ambient) shall be measured
and, if so, whether data acquisition shall take place via the PT 100 or the 20 mA
input.
[spacer] THER M : De fault CTA PS x 072 186 073 186 074 186 075 186
[spacer]
Setting for the coolant temperature to be used for calculation of the trip time if
coolant temperature is not measured.
[spacer] THER M : Funct.f.CT A fai l. PSx 076 177 077 177 078 177 079 177
[spacer]
The setting defines how the thermal overload protection function will continue to
operate in the event of faulty coolant temperature acquisition. User can select
between Default temp. value, Last meas.temperat. and Blocking.
[spacer] THER M : M inimu m te mper at.PS x 076 178 077 178 078 178 079 178
[spacer]
Setting for the minimum coolant temperature to be used for trip time calculation
if a cable runs in an underground tunnel system.
[spacer] THER M : Hyste re sis t ri p PSx 072 183 073 183 074 183 075 183
[spacer]
Setting for the hysteresis of the trip stage.
[spacer] THER M : R e tain r e pl ic a PS x 009 019 009 030 009 032 009 039
0: No
[spacer]
With this parameter it can be configured whether the thermal replica is retained
in the non-volatile section of the device's memory so that it will still be available
after an interruption of the supply voltage.
Parameter Address
[spacer] THER M : Warning pre-t rip PS x 072 191 073 191 074 191 075 191
[spacer]
A warning will be given in advance of the trip. The time difference between the
warning time and the trip time is set here.
[spacer] THER M : Factor 2 PL PS x 072 173 073 173 074 173 075 173
[spacer] THER M : Factor 3 PL PS x 072 174 073 174 074 174 075 174
[spacer]
Setting for the parallel line factors for 2- or 3-parallel line operation.
Parameter Address
tion
0: No Fig. 3-240, (p. 3-295)
[spacer]
This setting defines the setting group in which V<> protection is enabled.
[spacer] V<>: V> PSx 076 003 077 003 078 003 079 003
[spacer]
Setting for operate value V>.
[spacer] V<>: V> > PSx 076 004 077 004 078 004 079 004
[spacer]
Setting for operate value V>>.
[spacer] V<>: tV> PS x 076 005 077 005 078 005 079 005
[spacer]
Setting for the operate delay of overvoltage stage V>.
[spacer] V<>: tV>> PS x 076 006 077 006 078 006 079 006
[spacer]
Setting for the operate delay of overvoltage stage V>>.
[spacer] V<>: V< PSx 076 007 077 007 078 007 079 007
[spacer]
Setting for operate value V<.
[spacer] V<>: V< < PSx 076 008 077 008 078 008 079 008
[spacer]
Setting for operate value V<<.
[spacer] V<>: Vm in PS x 076 046 077 046 078 046 079 046
[spacer]
Setting for the lower threshold of the window function.
[spacer] V<>: tV< PS x 076 009 077 009 078 009 079 009
[spacer]
Setting for the operate delay of undervoltage stage V<.
[spacer] V<>: tV<< PS x 076 010 077 010 078 010 079 010
[spacer]
Setting for the operate delay of undervoltage stage V<<.
[spacer] V<>: tT rans ient P Sx 076 029 077 029 078 029 079 029
[spacer]
Setting for the time limit of the signals generated by the undervoltage stages.
Parameter Address
[spacer] V<>: Hyst . V<> meas. PSx 076 048 077 048 078 048 079 048
[spacer]
Setting for the hysteresis of the trigger stages for monitoring measured
voltages.
Parameter Address
Over-/ f<> : Enable PSx 018 196 018 197 018 198 018 199
underfrequency pro‐
tection
0: No Fig. 3-243, (p. 3-298)
[spacer]
This setting defines the parameter subset in which over-/underfrequency
protection is enabled.
[spacer] f<> : Oper. m ode f1 PS x 018 120 018 121 018 122 018 123
[spacer] f<> : Oper. m ode f2 PS x 018 144 018 145 018 146 018 147
1: f
[spacer] f<> : Oper. m ode f3 PS x 018 168 018 169 018 170 018 171
1: f
[spacer] f<> : Oper. m ode f4 PS x 018 192 018 193 018 194 018 195
1: f
[spacer] f<> : Oper. m ode f5 PS x 019 171 019 172 019 173 019 174
1: f
[spacer]
Setting for the operating mode of the timer stages of over-/underfrequency
protection.
[spacer] f<> : f1 PS x 018 100 018 101 018 102 018 103
[spacer] f<> : f2 PS x 018 124 018 125 018 126 018 127
[spacer] f<> : f3 PS x 018 148 018 149 018 150 018 151
[spacer] f<> : f4 PS x 018 172 018 173 018 174 018 175
[spacer] f<> : f5 PS x 019 151 019 152 019 153 019 154
[spacer]
Setting for the frequency threshold. The over-/underfrequency protection
function will operate if one of the following two conditions applies: The
threshold is higher than the set nominal frequency and the frequency exceeds
this threshold. The threshold is lower than the set nominal frequency and the
frequency falls below this threshold. Depending on the chosen operating mode,
either a signal is issued without further monitoring, or further monitoring
mechanisms are started.
[spacer] f<> : tf1 PSx 018 104 018 105 018 106 018 107
[spacer] f<> : tf2 PSx 018 128 018 129 018 130 018 131
Parameter Address
[spacer] f<> : tf3 PSx 018 152 018 153 018 154 018 155
[spacer] f<> : tf4 PSx 018 176 018 177 018 178 018 179
[spacer] f<> : tf5 PSx 019 155 019 156 019 157 019 158
[spacer]
Setting for the operate delay of over-/underfrequency protection.
[spacer] f<> : df1/dt PS x 018 108 018 109 018 110 018 111
[spacer] f<> : df2/dt PS x 018 132 018 133 018 134 018 135
[spacer] f<> : df3/dt PS x 018 156 018 157 018 158 018 159
[spacer] f<> : df4/dt PS x 018 180 018 181 018 182 018 183
[spacer] f<> : df5/dt PS x 019 159 013 092 013 093 013 094
[spacer]
Setting for the frequency gradient to be monitored.
Note: This setting is ineffective unless operating mode f with df/dt has been
selected.
[spacer] f<> : De lta f1 PS x 018 112 018 113 018 114 018 115
[spacer] f<> : De lta f2 PS x 018 136 018 137 018 138 018 139
[spacer] f<> : De lta f3 PS x 018 160 018 161 018 162 018 163
[spacer] f<> : De lta f4 PS x 018 184 018 185 018 186 018 187
[spacer] f<> : De lta f5 PS x 019 163 019 164 019 165 019 166
[spacer]
Setting for Delta f.
Note: This setting is ineffective unless operating mode f w. Delta f/Delta t has
been selected.
[spacer] f<> : De lta t1 PS x 018 116 018 117 018 118 018 119
[spacer] f<> : De lta t2 PS x 018 140 018 141 018 142 018 143
Parameter Address
[spacer] f<> : De lta t3 PSx 018 164 018 165 018 166 018 167
[spacer] f<> : De lta t4 PSx 018 188 018 189 018 190 018 191
[spacer] f<> : De lta t5 PSx 019 167 019 168 019 169 019 170
[spacer]
Setting for Delta t.
Note: This setting is ineffective unless operating mode f w. Delta f/Delta t has
been selected.
Parameter Address
Circuit breaker CBF: Enable PS x 072 110 073 110 074 110 075 110
failure protection
0: No Fig. 3-246, (p. 3-303)
[spacer]
This setting defines the setting group in which breaker failure protection is
enabled.
[spacer] CBF: I min< PS x 072 112 073 112 074 112 075 112
[spacer]
Setting for the Imin< current threshold. Current falling below this threshold will
be interpreted as breaker opening, and reset the CBF timers.
[spacer] CBF: t Im in< PSx 072 113 073 113 074 113 075 113
[spacer]
Setting for the operate delay of CB auxiliary contact monitoring.
[spacer] CBF: Op er ative time PS x 072 114 073 114 074 114 075 114
[spacer]
Setting for the operative time of CB auxiliary contact monitoring.
[spacer] CBF: M on. time M - trip PS x 072 115 073 115 074 115 075 115
[spacer]
Setting for the monitoring time of the main-trip command before issuing a re-
trip.
[spacer] CBF: M on. time R - trip P S x 072 116 073 116 074 116 075 116
[spacer]
Setting for the monitoring time of the re-trip command before issuing a back-
trip.
Parameter Address
Limit value LIMIT : Enable PS x 072 240 073 240 074 240 075 240
monitoring
0: No Fig. 3-257, (p. 3-315)
[spacer]
This setting defines the setting group in which the limit value monitoring
function is enabled.
[spacer] LIMIT : I> PSx 072 241 073 241 074 241 075 241
[spacer]
Setting for operate threshold I>.
[spacer] LIMIT : I> > PSx 072 242 073 242 074 242 075 242
[spacer]
Setting for operate threshold I>>.
[spacer] LIMIT : tI> PS x 072 243 073 243 074 243 075 243
[spacer]
Setting for operate delay tI>.
[spacer] LIMIT : tI>> PS x 072 244 073 244 074 244 075 244
[spacer]
Setting for operate delay tI>>.
[spacer] LIMIT : IA> PS x 076 200 077 200 078 200 079 200
[spacer]
Setting the operate value of the first overcurrent stage of catenary current IA or
catenary 1 current.
Note: Valid only with settings
● MAIN: Fee de r mode = Autotransformer feed and
● M AIN: Fee de r mode = Single feed w. sum I.
[spacer] LIMIT : IA>> PS x 076 201 077 201 078 201 079 201
[spacer]
Setting the operate value of the second overcurrent stage of catenary current IA
or catenary 1 current.
Note: Valid only with settings
● MAIN: Fee de r mode = Autotransformer feed and
● M AIN: Fee de r mode = Single feed w. sum I.
Parameter Address
[spacer] LIMIT : tIA> PSx 076 202 077 202 078 202 079 202
[spacer]
Setting the operate delay of the first overcurrent stage of catenary current IA or
catenary 1 current.
Note: Valid only with settings
● MAIN: Fee de r mode = Autotransformer feed and
● M AIN: Fee de r mode = Single feed w. sum I.
[spacer] LIMIT : tIA>> PSx 076 203 077 203 078 203 079 203
[spacer]
Setting the operate delay of the second overcurrent stage of catenary current IA
or catenary 1 current.
Note: Valid only with settings
● MAIN: Fee de r mode = Autotransformer feed and
● M AIN: Fee de r mode = Single feed w. sum I.
[spacer] LIMIT : IB> PS x 076 204 077 204 078 204 079 204
[spacer]
Setting the operate value of the first overcurrent stage of feeder current IB or
catenary 2 current.
Note: Valid only with settings
● MAIN: Fee de r mode = Autotransformer feed and
● M AIN: Fee de r mode = Single feed w. sum I.
[spacer] LIMIT : IB>> PS x 076 205 077 205 078 205 079 205
[spacer]
Setting the operate value of the second overcurrent stage of feeder current IB or
catenary 2 current.
Note: Valid only with settings
● MAIN: Fee de r mode = Autotransformer feed and
● M AIN: Fee de r mode = Single feed w. sum I.
[spacer] LIMIT : tIB> PSx 076 206 077 206 078 206 079 206
[spacer]
Setting the operate delay of the first overcurrent stage of feeder current IB or
catenary 2 current.
Note: Valid only with settings
● MAIN: Fee de r mode = Autotransformer feed and
● M AIN: Fee de r mode = Single feed w. sum I.
Parameter Address
[spacer] LIMIT : tIB>> PSx 076 207 077 207 078 207 079 207
[spacer]
Setting the operate delay of the second overcurrent stage of feeder current IB or
catenary 2 current.
Note: Valid only with settings
● MAIN: Fee de r mode = Autotransformer feed and
● M AIN: Fee de r mode = Single feed w. sum I.
[spacer] LIMIT : Iplaus/ I dfr st > P Sx 076 224 077 224 078 224 079 224
[spacer]
Setting for the operate delay of the first overcurrent stage of the CT Plausibility
check current or defrost current.
[spacer] LIMIT : Iplaus/ I dfr st >> P Sx 076 225 077 225 078 225 079 225
[spacer]
Setting for the operate delay of the first overcurrent stage of the CT Plausibility
check current or defrost current.
[spacer] LIMIT : tIp laus /I dfr st > PS x 076 226 077 226 078 226 079 226
[spacer]
Setting for the operate delay of the first overcurrent stage of the CT Plausibility
check current or defrost current.
[spacer] LIMIT : tIp laus /I dfr st > PS x 076 227 077 227 078 227 079 227
[spacer]
Setting for the operate delay of the second overcurrent stage of the CT
Plausibility check current or defrost current.
[spacer] LIMIT : V> PSx 072 247 073 247 074 247 075 247
[spacer]
Setting for operate threshold V>.
[spacer] LIMIT : V>> PS x 072 248 073 248 074 248 075 248
[spacer]
Setting for operate threshold V>>.
[spacer] LIMIT : tV> PS x 072 249 073 249 074 249 075 249
[spacer]
Setting for the operate delay of overvoltage stage V>.
[spacer] LIMIT : tV>> PS x 072 250 073 250 074 250 075 250
[spacer]
Setting for the operate delay of overvoltage stage V>>.
Parameter Address
[spacer] LIMIT : V< PSx 072 251 073 251 074 251 075 251
[spacer]
Setting for operate threshold V<.
[spacer] LIMIT : V<< PS x 072 252 073 252 074 252 075 252
[spacer]
Setting for operate threshold V<<.
[spacer] LIMIT : tV< PS x 072 253 073 253 074 253 075 253
[spacer]
Setting for the operate delay of undervoltage stage V<.
[spacer] LIMIT : tV<< PS x 072 254 073 254 074 254 075 254
[spacer]
Setting for the operate delay of undervoltage stage V<<.
[spacer] LIMIT : VA> PS x 076 208 077 208 078 208 079 208
[spacer]
Setting for the operate value of the first overvoltage stage of catenary voltage
VA.
Note: Valid only with settings
● MAIN: Fee de r mode = Autotransformer feed and
● M AIN: Fee de r mode = Single feed w. sum I.
[spacer] LIMIT : VA>> PS x 076 209 077 209 078 209 079 209
[spacer]
Setting for the operate value of the second overvoltage stage of catenary
voltage VA.
Note: Valid only with settings
● MAIN: Fee de r mode = Autotransformer feed and
● M AIN: Fee de r mode = Single feed w. sum I.
[spacer] LIMIT : tVA> PS x 076 210 077 210 078 210 079 210
[spacer]
Setting for the operate delay of the first overvoltage stage of catenary voltage
VA.
Note: Valid only with settings
● MAIN: Fee de r mode = Autotransformer feed and
● M AIN: Fee de r mode = Single feed w. sum I.
Parameter Address
[spacer] LIMIT : tVA>> PS x 076 211 077 211 078 211 079 211
[spacer]
Setting for the operate delay of the second overvoltage stage of catenary
voltage VA.
Note: Valid only with settings
● MAIN: Fee de r mode = Autotransformer feed and
● M AIN: Fee de r mode = Single feed w. sum I.
[spacer] LIMIT : VA< PS x 076 216 077 216 078 216 079 216
[spacer]
Setting for the operate value of the first undervoltage stage of catenary voltage
VA.
Note: Valid only with settings
● MAIN: Fee de r mode = Autotransformer feed and
● M AIN: Fee de r mode = Single feed w. sum I.
[spacer] LIMIT : VA<< PS x 076 217 077 217 078 217 079 217
[spacer]
Setting for the operate value of the first undervoltage stage of catenary voltage
VA.
Note: Valid only with settings
● MAIN: Fee de r mode = Autotransformer feed and
● M AIN: Fee de r mode = Single feed w. sum I.
[spacer] LIMIT : tVA< PS x 076 218 077 218 078 218 079 218
[spacer]
Setting for the operate delay of the first undervoltage stage of catenary voltage
VA.
Note: Valid only with settings
● MAIN: Fee de r mode = Autotransformer feed and
● M AIN: Fee de r mode = Single feed w. sum I.
[spacer] LIMIT : tVA<< PS x 076 219 077 219 078 219 079 219
[spacer]
Setting for the operate delay of the second undervoltage stage of catenary
voltage VA.
Note: Valid only with settings
● MAIN: Fee de r mode = Autotransformer feed and
● M AIN: Fee de r mode = Single feed w. sum I.
Parameter Address
[spacer] LIMIT : VB> PSx 076 212 077 212 078 212 079 212
[spacer]
Setting for the operate threshold of the first overvoltage stage of the feeder
voltage.
Note: Valid only with settings MAIN: F e ede r mode = Autotransformer feed
and
MAIN: Fe e de r m ode = Single feed w. sum I.
[spacer] LIMIT : VB>> PSx 076 213 077 213 078 213 079 213
[spacer]
Setting for the operate threshold of the second overvoltage stage of the feeder
voltage.
Note: Valid only with settings MAIN: F e ede r mode = Autotransformer feed
and
MAIN: Fe e de r m ode = Single feed w. sum I.
[spacer] LIMIT : tVB> PS x 076 214 077 214 078 214 079 214
[spacer]
Setting for the operate delay of the first overvoltage stage of the feeder voltage.
Note: Valid only with settings MAIN: F e ede r mode = Autotransformer feed
and
MAIN: Fe e de r m ode = Single feed w. sum I.
[spacer] LIMIT : tVB>> PS x 076 215 077 215 078 215 079 215
[spacer]
Setting for the operate delay of the second overvoltage stage of the feeder
voltage.
Note: Valid only with settings MAIN: F e ede r mode = Autotransformer feed
and
MAIN: Fe e de r m ode = Single feed w. sum I.
[spacer] LIMIT : VB< PSx 076 220 077 220 078 220 079 220
[spacer]
Setting for the operate threshold of the first undervoltage stage of the feeder
voltage.
Note: Valid only with settings MAIN: F e ede r mode = Autotransformer feed
and
MAIN: Fe e de r m ode = Single feed w. sum I.
Parameter Address
[spacer] LIMIT : VB<< PSx 076 221 077 221 078 221 079 221
[spacer]
Setting for the operate threshold of the second undervoltage stage of the feeder
voltage.
Note: Valid only with settings MAIN: F e ede r mode = Autotransformer feed
and
MAIN: Fe e de r mode = Single feed w. sum I.
[spacer] LIMIT : tVB< PS x 076 222 077 222 078 222 079 222
[spacer]
Setting for the operate delay of the first undervoltage stage of the feeder
voltage.
Note: Valid only with settings MAIN: F e ede r mode = Autotransformer feed
and
MAIN: Fe e de r mode = Single feed w. sum I.
[spacer] LIMIT : tVB<< PSx 076 223 077 223 078 223 079 223
[spacer]
Setting for the operate delay of the second undervoltage stage of the feeder
voltage.
Note: Valid only with settings MAIN: F e ede r mode = Autotransformer feed
and
MAIN: Fe e de r mode = Single feed w. sum I.
[spacer] LIMIT : f > PSx 072 211 073 211 074 211 075 211
[spacer]
Setting for operate threshold f>.
[spacer] LIMIT : f >> PSx 072 212 073 212 074 212 075 212
[spacer]
Setting for operate threshold f>>.
[spacer] LIMIT : tf> PS x 072 213 073 213 074 213 075 213
[spacer]
Setting for the operate delay of f>.
[spacer] LIMIT : tf>> PS x 072 214 073 214 074 214 075 214
[spacer]
Setting for the operate delay of f>>.
[spacer] LIMIT : f < PSx 072 215 073 215 074 215 075 215
[spacer]
Setting for operate threshold f<.
Parameter Address
[spacer] LIMIT : f << PSx 072 216 073 216 074 216 075 216
[spacer]
Setting for operate threshold f<<.
[spacer] LIMIT : tf< PS x 072 217 073 217 074 217 075 217
[spacer]
Setting for the operate delay of f<.
[spacer] LIMIT : tf<< PS x 072 218 073 218 074 218 075 218
[spacer]
Setting for the operate delay of f<<.
Parameter Address
[spacer]
Enabling the bay interlocking function from the local control panel.
[spacer] MAIN: SI active USER 221 002
[spacer]
Enabling the station interlocking function from the local control panel.
[spacer] MAIN: Inp.asg. fct .block. 1 221 014
[spacer]
Definition of the binary signals assigned to function block 1 and 2.
[spacer] MAIN: Op. delay fct . block 221 029
[spacer]
Setting for the operate delay of the function blocks.
[spacer] MAIN: Pe rm.No.mot .dr iv e op 221 027
[spacer]
Setting for the permissible motor drive operations within the time interval
defined at M AIN: Mon.ti me mot .dr iv e s.
[spacer] MAIN: Mon.time mot. drive s 221 026
[spacer]
Setting for the monitoring time to monitor the number of motor drives.
[spacer] MAIN: Cool.t ime mot.drive s 221 028
[spacer]
Setting for the cooling time for motors in motor-operated switchgear.
[spacer] MAIN: Mon.time Dir.Cont r. 221 060
[spacer]
Setting for the monitoring time for the motor relay.
[spacer] MAIN: CB1 max . ope r. c ap. 221 084
1 1 99
1 1 99
[spacer]
Setting for the maximum number of CB operations for an ARC cycle (or for a
limited time period).
Parameter Address
[spacer]
Selecting the event which, when present, will initialize the counter at
MAIN: CB1 act. oper . cap. with the value at MAIN: CB1 max. ope r.
cap..
[spacer] MAIN: CB2 re ady fct. ass ign 221 089
[spacer]
Selecting the event which, when present, will initialize the counter at
MAIN: CB1 act. oper . cap. (or MAIN: CB2 act. oper. cap.) with the
value at MAI N: CB1 max. oper . cap. (or M AI N: CB 2 max. oper .
cap., respectively).
[spacer] MAIN: W. ex t. cmd. t ermin. 221 063
0: No
[spacer]
This setting determines if bay types, defined for direct motor control, can be
used together with external termination contacts to directly influence the control
process of motor driven switchgear.
Parameter Address
0: Not assigned
0: Not assigned
0: Not assigned
0: Not assigned
0: Not assigned
0: Not assigned
0: Not assigned
0: Not assigned
0: Not assigned
0: Not assigned
[spacer]
Setting for the designation of the respective external device. Either one of the
pre-defined designations or the term Device Name User may be selected. In the
latter case any text (max 4 characters) may be entered at DEV01: D EV-
Name Use r that will be used as the devices' designation. (The same holds for
DEV02 etc.)
[spacer] DEV01: DEV- Name Us er 218 101
0:
0:
0:
0:
0:
0:
Parameter Address
0:
0:
0:
0:
[spacer]
Any text (max. 4 characters) may be entered as the devices’ name which will
then be used as the designation, if the associated parameter
DEV01: De signat. e xt. dev. has been set to Device Name User. When
instead one of the pre-defined designations is selected at DE V01: Des ig nat.
ext. de v. it will be used and DE V01: D EV- Name User is ignored. A
designation with more than 4 characters is internally truncated. (The same holds
for DEV02 etc.)
[spacer] DEV01: Oper. m ode cmd. 210 024
3: Time control
3: Time control
3: Time control
3: Time control
3: Time control
3: Time control
3: Time control
3: Time control
3: Time control
[spacer]
Selecting the operating mode of the command from long command, short
command or time control.
Parameter Address
[spacer]
Setting for the time that a control command is sustained after a switchgear
position signal – “Open” or “Closed” – has been received.
[spacer] DEV01: Op.tim e swit ch. dev. 210 004
20 0 254 s
20 0 254 s
20 0 254 s
20 0 254 s
Parameter Address
20 0 254 s
20 0 254 s
20 0 254 s
20 0 254 s
20 0 254 s
[spacer]
Setting the operating time for switchgear (switching device).
[spacer] DEV01: Gr. as s ign. de bounc . 210 011
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
1: Group 1
[spacer]
Assigning the external device to one of eight groups for debouncing and chatter
suppression.
[spacer] DEV01: S tartCm dTi me superv . 210 007
Parameter Address
[spacer]
This parameter allows for defining a monitoring timer for the begin of a switch
command.
After sending an Open / Close command, the corresponding timer starts. If the
switchgear unit has not reached its intermediate position after this time has
elapsed then the command is deactivated and MAIN: S tar tcmdtime
exceed. is signaled.
In the default setting blocked this monitoring is switched off. This is
recommended for switchgear units for which it is impossible to detect the
intermediate position.
[spacer] DEV01: Interm . pos. s uppr . 210 012
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
[spacer]
This setting determines whether the “intermediate position” signal will be
suppressed or not, while the switchgear is operating.
[spacer] DEV01: S tat .ind .in ter m.pos. 210 027
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
[spacer]
This setting determines whether the actual status will be signaled with a 5 s
delay after the “Faulty position” signal is issued.
[spacer] DEV01: Inp.asg . s w.tr . pl ug 210 014
Parameter Address
[spacer]
Definition of the binary signal that is used to signal the position (“plugged-in” /
“unplugged”) of the switch truck plug.
[spacer] DEV01: With ge n. trip cmd.1 210 021
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
[spacer]
This setting specifies whether the circuit breaker will be opened by “general trip
command 1” of the protection function.
Note: This setting is only visible (active) for external devices that are defined as
“circuit breakers”. This definition is included in the bay type definitions.
[spacer] DEV01: With ge n. trip cmd.2 210 022
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
[spacer]
This setting specifies whether the circuit breaker will be opened by “general trip
command 2” of the protection function.
Note: This setting is only visible (active) for external devices that are defined as
“circuit breakers”. This definition is included in the bay type definitions.
[spacer] DEV01: With close c md. /pr ot 210 023
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
[spacer]
This setting specifies whether the circuit breaker will be closed by the “close
command” of the protection function.
Note: This setting is only visible (active) for external devices that are defined as
“circuit breakers”. This definition is included in the bay type definitions.
[spacer] DEV01: Inp.asg .e l.ctrl.open 210 019
Parameter Address
[spacer]
This setting defines the binary signal that will be used as the control signal to
move the switchgear unit to the open position.
Note: Only signals that are defined in the DEVxx function groups can be
selected.
[spacer] DEV01: Inp.asg .el.ctr.clos e 210 020
[spacer]
This setting defines the binary signal that will be used as the control signal to
move the switchgear unit to the “Closed” position.
Note: Only signals that are defined in the DEVxx function groups can be
selected.
[spacer] DEV01: Block cmd ope n 218 120
Parameter Address
[spacer]
Select whether open commands for the switchgear unit shall be blocked.
[spacer] DEV01: Block cmd clos e 218 160
[spacer]
Select whether close commands for the switchgear unit shall be blocked.
[spacer] DEV01: Oper.count .l imit 218 211
Parameter Address
Blocked 1 65000
Blocked 1 65000
Blocked 1 65000
Blocked 1 65000
Blocked 1 65000
Blocked 1 65000
Blocked 1 65000
Blocked 1 65000
Blocked 1 65000
[spacer]
Setting a limit value for the number of switching commands for the respective
switchgear unit.
[spacer] DEV01: Inp. as g. e nd Ope n 210 015
Parameter Address
[spacer]
This setting defines the binary signal that will be used to terminate the “Open”
command.
[spacer] DEV01: Inp. as g. e nd Close 210 016
[spacer]
This setting defines the binary signal that will be used to terminate the “Close”
command.
[spacer] DEV01: Open w/o s tat. int e rl 210 025
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
[spacer]
This setting specifies whether switching to “Open” position is permitted without
a check by the station interlock function.
[spacer] DEV01: Clos e w/ o stat . int . 210 026
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
[spacer]
This setting specifies whether switching to “Closed” position is permitted
without a check by the station interlock function.
[spacer] DEV01: Fct.as sig.BI wS I open 210 039
Parameter Address
[spacer]
This setting defines which output will issue the “Open” enable to the interlocking
logic when there is “bay interlock with substation interlock”.
Note: The interlock conditions for bay interlock with station interlock are
included in the bay type definitions (see “List of Bay Types” in the Appendix).
If the interlock condition is to be modified, this is possible by modifying the
corresponding Boolean equation in the interlocking logic or by defining a new
interlocking logic equation. Only in the latter case is it necessary to change the
function assignment.
[spacer] DEV01: Fct.as sig.BI wS I clos 210 040
Parameter Address
[spacer]
This setting defines which output will issue the “Close” enable to the interlocking
logic when there is “bay interlock with substation interlock”.
Note: The interlock conditions for bay interlock with station interlock are
included in the bay type definitions (see “List of Bay Types” in the Appendix).
If the interlock condition is to be modified, this is possible by modifying the
corresponding Boolean equation in the interlocking logic or by defining a new
interlocking logic equation. Only in the latter case is it necessary to change the
function assignment.
[spacer] DEV01: Fct.as g.BI w/ o S I op 210 041
[spacer]
This setting defines which output will issue the “Open” enable to the interlocking
logic when there is “bay interlock without substation interlock”.
Note: The interlock conditions for bay interlock without station interlock are
included in the bay type definitions (see “List of Bay Types” in the Appendix).
If the interlock condition is to be modified, this is possible by modifying the
corresponding Boolean equation in the interlocking logic or by defining a new
interlocking logic equation. Only in the latter case is it necessary to change the
function assignment.
Parameter Address
[spacer]
This setting defines which output will issue the “Close” enable to the interlocking
logic when there is “bay interlock without substation interlock”.
Note: The interlock conditions for bay interlock without station interlock are
included in the bay type definitions (see “List of Bay Types” in the Appendix).
If the interlock condition is to be modified, this is possible by modifying the
corresponding Boolean equation in the interlocking logic or by defining a new
interlocking logic equation. Only in the latter case is it necessary to change the
function assignment.
Parameter Address
0 0 65000 s
0 0 65000 s
[spacer]
Setting for the secondary timer.
Parameter Address
[spacer]
The interlock conditions are also transmitted together with reporting in the
“phase 2” of the IEC 61850 communication protocol. Therefore it is a
requirement that these interlock conditions are cyclically checked and not, as
with software versions that still implement “phase 1”, only with the request for a
switching operation.
This parameter sets the cycle time, after which a check of the interlock
conditions is carried out.
As additional processor capacity must be provided for each of these checks it
must be ensured that a favorable compromise is found for the cycle time setting
value. On the one hand it is desirable to select a cycle time value which is as
short as possible so that changes in the interlock conditions are updated without
any notable delays, but on the other hand this cycle time value should not be so
short that the P438 will be under too much strain. As the CPU load of the P438 is
dependent on the total number of function groups having been configured it is
not possible to suggest a generally acceptable cycle time value.
[spacer] ILOCK: R se t ILOCK violati on 221 123
[spacer]
The interlock violation signal (221 018) M AIN: Interlock equ. viol. will be
automatically reset after the time period set here. (The default value Blocked
disables the automatic reset.)
[spacer] ILOCK: Fct.assig nm. outp. 1 250 000
Parameter Address
Parameter Address
[spacer]
Definition of the interlock conditions.
8.1 Operation
The P438 generates a large number of signals, processes binary input signals,
and acquires measured data during fault-free operation of the protected object
as well as fault-related data. A number of counters are available for statistical
purposes. This information can be read out from the integrated local control
panel or via the operating program.
All this information can be found in the “Operation” and “Events” folders in the
menu tree.
Note
Detailed information about all parameters, including complete selection tables and
IEC 60870‑5‑103 protocol properties, are separately available as a set of interlinked
PDF files for user-friendly navigation, packed in one ZIP archive named
DataModelExplorer_P438_en_P01.zip.
A list of the Logical Nodes that have been implemented for the IEC 61850 protocol
can be found in a separate document.
Parameter Address
interface
0.0 0.0 100.0 %
[spacer]
Display of the updated measured operating value for the number of corrupted
messages within the last 1000 received messages.
[spacer] COMM 3: No.t.err.,max,st ore d 120 041
[spacer]
Display of the updated measured operating value for the proportion of corrupted
messages within the last 1000 received messages.
[spacer] COMM 3: Loop back res ult 120 057
[spacer]
While the hold time is running, the loop back test results can be checked by
reading out these values.
Parameter Address
[spacer]
Display of the input current.
[spacer] MEASI: Curr e nt IDC p.u. 004 135
[spacer]
Display of the input current referred to IDC,nom.
[spacer]
Display of the linearized input current referred to IDC,nom.
[spacer]
Display of the scaled linearized value.
[spacer] MEASI: T emp eratur e T 004 133
[spacer]
Display of the temperature measured at the “PT 100” temperature input on the
analog p/c board.
[spacer] MEASI: T emp eratur e Tmax 004 233
[spacer]
Display of the maximum temperature measured at the “PT 100” temperature
input on the analog p/c board.
[spacer] MEASI: T emp eratur e p.u. T 004 221
[spacer]
Display of the temperature measured at the “PT 100” temperature input on the
analog p/c board referred to 100°C.
Parameter Address
output
0.00 0.00 20.00 mA Fig. 3-49, (p. 3-82)
[spacer]
Display of the current on the analog measured data output (A1: channel 1; A2:
channel 2).
Parameter Address
[spacer]
Date display. The date can also be set here. The centuries are not displayed.
The supported dates range from January 1st, 1997, until November 7th, 2098.
[spacer] MAIN: Tim e of day 003 091
[spacer]
Display of the time of day. The time can also be set here.
[spacer] MAIN: Tim e s witc hing 003 095
[spacer]
Setting for standard time or daylight saving time.
This setting is necessary in order to avoid misinterpretation of the times
assigned to signals and event data that can be read out through the PC or
communication interfaces.
[spacer] MAIN: Fre que nc y f 004 040
[spacer]
Display of system frequency.
[spacer] MAIN: Iplaus / Id frst . pr im. 004 200
[spacer]
Display of CT plausibility check current or defrost current as a primary quantity.
[spacer] MAIN: Current I prim. 004 110
[spacer]
Display of phase current as a primary quantity.
[spacer] MAIN: Current IA pr im. 005 040
[spacer]
Display of catenary current IA or catenary 1 current as a primary quantity.
Note: Valid only with settings
● MAIN: Fee de r mode = Autotransformer feed and
● M AIN: Fee de r mode = Single feed w. sum I.
[spacer] MAIN: Current IB prim. 006 040
[spacer]
Display of feeder current IB or catenary 2 current as a primary quantity.
Note: Valid only with settings
● MAIN: Fee de r mode = Autotransformer feed and
● M AIN: Fee de r mode = Single feed w. sum I.
Parameter Address
[spacer]
Display of the fundamental current component as a primary quantity.
[spacer] MAIN: Current I(2fn) pr im 008 095
[spacer]
Display of the second harmonic current component as a primary quantity.
[spacer] MAIN: Current I(3fn) pr im 008 097
[spacer]
Display of the third harmonic current component as a primary quantity.
[spacer] MAIN: Current I(5fn) pr im 008 099
[spacer]
Display of the fifth harmonic current component as a primary quantity.
[spacer] MAIN: Current I(7fn) pr im 021 051
[spacer]
Display of the seventh harmonic current component as a primary quantity.
[spacer] MAIN: Voltage V prim. 004 112
[spacer]
Display of the updated voltage as a primary quantity.
[spacer] MAIN: Voltage VA pr im. 005 042
[spacer]
Display of the updated value for the catenary voltage as a primary quantity.
Note: Valid only with setting M AIN: F ee der mode = Autotransformer feed.
[spacer] MAIN: Voltage VB/ Vref prim 006 042
[spacer]
Display of the updated value for feeder voltage VB or reference voltage Vref as a
primary quantity.
Note: Valid only with setting
● M AI N: Fee de r mode = Autotransformer feed.
[spacer] MAIN: Act.energy outp. prim 008 065
2: MWh
2: MWh
2: Mvarh
Parameter Address
2: Mvarh
[spacer]
Display of the updated active energy output (or active energy input, reactive
energy output, reactive energy input, respectively) as a primary quantity.
At run-time, the value is displayed with 32 bit precision. (But note that for
technical reasons, this value is internally stored as a text value.)
Value ranges:
● MAIN: Act .e ne rgy outp.pr im – 0 … 6,553,500.00 MWh
● MAIN: Act.ene rgy inp. pri m – 0 … 6,553,500.00 MWh
● MAIN: Re act .e n. out p. pr im – 0 … 6,553,500.00 Mvar h
● MAIN: Re act. e n. inp. prim – 0 … 6,553,500.00 Mvar h
Note: As an alternative, the same values also exist as numbers with 16 bit
precision:
● (005 061) M AIN: Act .e ne rgy out p.prim
● (005 062) M AI N: Act .e ne r gy inp. pri m
● (005 063) M AIN: Re act .e n. out p. prim
● (005 064) M AIN: Reac t. e n. inp. prim
[spacer] MAIN: Active powe r P pr im. 004 050
[spacer]
Display of the updated active power value as a primary quantity.
[spacer] MAIN: Re ac. powe r Q prim. 004 052
[spacer]
Display of the updated reactive power value as a primary quantity.
[spacer] MAIN: Act.energy outp. prim 005 061
Parameter Address
[spacer]
Display of the updated active energy output (or active energy input, reactive
energy output, reactive energy input, respectively) as a primary quantity.
The value is displayed as a number with 16 bit precision.
Whenever the maximum value of 655.35 MWh or 655.35 MVAr h is exceeded,
the determination of the energy output is restarted, and the value that
exceeded the range is transferred to the new cycle. Moreover, a counter is
incremented:
● (009 090) M AI N: No.ov e r fl.act .e n.out: Counter for value overflow
of MAI N: Act.e nergy out p.prim
● (009 091) M AIN: No.ov e rfl.act .e n.inp: Counter for value overflow
of M AIN: Act .ene rgy inp. pri m
● (009 092) M AI N: No.ov /fl. re ac.e n.out: Counter for value overflow
of M AIN: Re act.en. outp. pr im
● (009 093) M AI N: No.ov/ fl.r eac.e n.inp: Counter for value overflow
of MAI N: R eact . en. inp. pr im
Note that the maximum value of these counters is 10000.
As an alternative to these 16 bit numbers, there are also 32 bit precision values
available:
● (008 065) M AIN: Act. ene r gy o utp.pr im
● (008 066) M AIN: Act .ene rgy i np. prim
● (008 067) M AI N: R eact .e n. outp. pri m
● (008 068) M AI N: R eact . en. inp. pri m
[spacer] MAIN: Load im pe d. Z prim. 005 005
[spacer]
Display of the updated load impedance value as a primary quantity.
[spacer] MAIN: Load react. X prim. 005 196
[spacer]
Display of the updated load reactance value as a primary quantity.
[spacer] MAIN: Load res is t . R pr im. 005 198
[spacer]
Display of the updated load resistance value as a primary quantity.
[spacer] MAIN: Load flow dir e ct ion 004 166
[spacer]
Display of the load flow direction.
[spacer] MAIN: Load angle phi 004 167
[spacer]
Display of the load angle (power factor angle).
Parameter Address
[spacer]
Display of system frequency referred to fn.
[spacer] MAIN: Iplaus / Id frst . p. u. 004 201
[spacer]
Display of the CT plausibility check current or defrost current referred to Iplaus/
dfrst,n.
[spacer]
Display of the current referred to In.
[spacer] MAIN: Current IA p.u. 005 041
[spacer]
Display of catenary current IA or catenary 1 current referred to Inom.
Note: Valid only with settings
● MAIN: Fee de r mode = Autotransformer feed and
● M AIN: Fee de r mode = Single feed w. sum I.
[spacer] MAIN: Current IB p.u. 006 041
[spacer]
Display of feeder current IB or catenary 2 current referred to Inom.
Note: Valid only with settings
● M AI N: Feeder mode = Autotransformer feed and
● MAIN: Fe eder mode = Single feed w. sum I.
[spacer] MAIN: Current I( fn) p.u. 008 110
[spacer]
Display of the fundamental current component referred to Inom.
[spacer]
Display of the second harmonic current component referred to Inom.
[spacer]
Display of the third harmonic current component referred to Inom.
[spacer]
Display of the fifth harmonic current component referred to Inom.
Parameter Address
[spacer]
Display of the seventh harmonic current component referred to Inom.
[spacer]
Display of the voltage referred to Vn.
[spacer] MAIN: Voltage VA p. u. 005 043
[spacer]
Display of the updated catenary voltage referred to Vnom.
[spacer]
Display of the updated feeder voltage VB or reference voltage Vref referred to
Vnom.
Note: Valid only with setting
● M AIN: Fe eder mode = Autotransformer feed.
[spacer] MAIN: Active powe r P p. u. 004 051
[spacer]
Display of the updated active power value referred to nominal apparent power
Snom.
[spacer]
Display of the updated value for reactive power referred to nominal apparent
power Snom.
[spacer]
Display of the updated operating impedance referred to Znom = 300 Ω.
[spacer]
Display of the updated value for the load angle referred to φnom = 100°.
[spacer]
Display of the updated active power factor.
[spacer] MAIN: Load im pe dance Z s ec 005 000
[spacer]
Display of the updated value for the load impedance as secondary quantity.
Parameter Address
[spacer]
Display of the updated value for the load reactance as secondary quantity.
[spacer] MAIN: Load res is t . R se c 005 197
[spacer]
Display of the updated value for the load resistance as secondary quantity.
Parameter Address
[spacer]
Display of the per-unit differential current of the defrost protection.
[spacer] DFR ST : Cur rent IR p.u. 004 197
[spacer]
Display of the per-unit restraining current of the defrost protection.
Parameter Address
protection
Not measured -25000 25000 % Fig. 3-238, (p. 3-293)
[spacer]
Display of the buffer content of the thermal overload protection function.
[spacer] THER M : Curre nt I,t he rm pr im 007 220
[spacer]
Display of the “thermal current” (as a primary quantity, or as a per unit quantity,
respectively).
These measured operating values are calculated as follows:
Statustherm. repl.
I therm,prim = I ref I nom,CT,prim
100
I therm,prim
I therm,p.u. =
I ref I nom,CT,prim
With:
● Itherm,prim = THERM : Cur re nt I, ther m prim
● Itherm,p.u. = THE RM: C ur rent I,t herm p.u
● Statustherm. repl. = THE RM : St at us the rm.re plica
● Iref = THER M: Ire f P Sx
● Inom,CT,prim = M AIN: Inom C. T. pri m.
In a measured values message the thermal current is processed as a per-unit
variable referred to Iref.
[spacer]
Display of the temperature of the protected object.
[spacer] THER M : Coolant t empe ratur e 004 149
[spacer]
Display of coolant temperature, dependent on the setting for THE RM: Sel ect
CTA PSx.
When set to Default temp. value the set temperature value will be displayed.
When set to From PT100 the temperature measured by the resistance
thermometer will be displayed. When set to From 20 mA input the temperature
measured via an external 20 mA transducer will be displayed.
[spacer] THER M : Pre - trip t ime left 004 139
[spacer]
Display of the time remaining before the thermal overload protection function
will reach the tripping threshold (“time-to-trip”).
Parameter Address
[spacer]
Display of the buffer content of the thermal overload protection function
referred to a buffer content of 100%.
[spacer] THER M : Object te mp. p.u. 004 179
[spacer]
Display of the temperature of the protected object referred to 100°C.
[spacer] THER M : Coolant t emp. p.u. 004 178
[spacer]
Display of the coolant temperature referred to 100°C.
[spacer] THER M : Te m p. offse t re pli ca 004 109
[spacer]
Display of the additional reserve if coolant temperature is taken into account
and if the measured coolant temperature is lower than the set maximum
permissible coolant temperature. (In this case, the thermal model has been
shifted downwards.)
If there is no coolant temperature acquisition and if the coolant temperature and
the maximum permissible coolant temperature have been set to the same
value, then the coolant temperature is not taken into account and the
characteristic is a function of the current only. The additional reserve amounts
to 0 in this case.
Parameter Address
0 0 65535
0 0 65535
0 0 65535
[spacer]
Display of the updated count.
Note: The count value can be set here (Preload-Function).
Parameter Address
tion keys
0: "Off"
0: "Off"
0: "Off"
0: "Off"
0: "Off"
0: "Off"
[spacer]
The state of the function keys is displayed as follows:
● Without function: No functions are assigned to the function key.
● "Off": The function key is in the “Off” position.
● "On": The function key is in the “On” position.
Parameter Address
interface
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
[spacer]
Display of the relevant receive signal.
[spacer] COMM 3: State send 1 121 000
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
[spacer]
Display of the updated value for the relevant send signal.
Parameter Address
Orientated
Substation Events
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
Parameter Address
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
Parameter Address
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
Parameter Address
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
Parameter Address
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
Parameter Address
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
Parameter Address
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
[spacer]
Display of the virtual binary GOOSE input state.
Parameter Address
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
Parameter Address
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
Parameter Address
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
Parameter Address
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
0: 0
Parameter Address
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
Parameter Address
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
Parameter Address
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
Parameter Address
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
Parameter Address
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
Parameter Address
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
Parameter Address
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
0: "Low"
[spacer]
The state of the binary signal inputs is displayed as follows:
● Without function: No functions are assigned to the binary signal input.
● "Low": Not energized.
● "High": Energized.
This display appears regardless of the setting for the binary signal input mode.
Parameter Address
output
0: Inactive Fig. 3-41, (p. 3-69)
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
Parameter Address
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
Parameter Address
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
Parameter Address
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
Parameter Address
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
[spacer]
The state of the output relays is displayed as follows:
● Without function: No functions are assigned to the output relay.
● Inactive: The output relay is not energized.
● Active: The output relay is energized.
This display appears regardless of the operating mode set for the output relay.
Parameter Address
1: Active
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
Parameter Address
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
0: Inactive
Parameter Address
0: Inactive
0: Inactive
0: Inactive
0: Inactive
[spacer]
The state of the LED indicators is displayed as follows:
● Inactive: The LED indicator is not energized.
● Active: The LED indicator is energized.
Parameter Address
0: No
[spacer]
The signal shows the PIN code of HMI is changed.
[spacer] CS: COMM pas s w. change 180 101
0: No
[spacer]
The signal shows the password of communication interface is changed.
[spacer] CS: HM I pincode invalid 180 102
0: No
[spacer]
The signal shows the PIN code via HMI is invalid.
[spacer] CS: COMM pas s w. inv alid 180 103
0: No
[spacer]
The signal shows the password via communication interface is invalid.
[spacer] CS: re set tok en ge ne rat e 180 104
0: No
[spacer]
The signal shows the reset token is generated.
[spacer] CS: RBAC re s et s uc ce ss 180 105
0: No
[spacer]
Display when the RBAC reset is successful.
[spacer] CS: RBAC re s et f ailed 180 106
0: No
[spacer]
Display when the RBAC reset is failed.
[spacer] CS: Us e r01 blocke d 180 107
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
[spacer]
The signal shows the user is blocked.
[spacer] CS: HM I logged in 180 122
0: No
[spacer]
The signal shows the user is logged in via HMI.
[spacer] CS: COMMS logge d in 180 123
0: No
[spacer]
The signal shows the user is logged in via communication interface.
[spacer] CS: IEC C S br ick faul ty 180 124
1: Yes
Parameter Address
0: No
[spacer]
Signal that the protection unit is in edit mode. As a standard this signal is linked
to LED: Fct.as sig. H1 7 r ed.
[spacer] LOC: Tr ig. m enu jmp 1 E XT 030 230
0: No
[spacer]
Signal that menu jump list 1 is being triggered. (See the corresponding setting
at LOC: Fct. menu jmp lis t 1.)
[spacer] LOC: Tr ig. m enu jmp 2 E XT 030 231
0: No
[spacer]
Signal that menu jump list 2 is being triggered. (See the corresponding setting
at LOC: Fct. menu jmp lis t 2.)
[spacer] LOC: Illum ination on EX T 037 101
1: Yes
[spacer]
This signal shows that the backlighting for the front panel LCD is switched on.
[spacer] LOC: Loc.acc.block .act iv e 221 005
Parameter Address
communication
interface 1
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
interface
0: No
0: No
0: No
0: No
Parameter Address
Communication
0: No Fig. 3-26, (p. 3-50)
[spacer]
Display when an Ethernet module is not operational, i.e. if the MAC address is
missing or there is a non-plausible parameter setting.
[spacer] IEC: Com m and block. EX T 104 086
0: No
0: No
0: No
[spacer]
Display when control from multiple levels is allowed, i.e. (225 208) L OC: Fc t.
ass ig n. L/R k e y is set to R & L <-> L, and relay is in 'R&L' mode.
[spacer] IEC: Com m and blocki ng 104 087
0: No
0: No
[spacer]
Display when a client has made a reservation to control an external device
(“select” for control by control mode “select before operate”).
[spacer] IEC: Sig./me as.val.block. 104 090
0: No
[spacer]
Display when control via communication is blocked, i.e. (221 125) IEC: Ctrl
blocke d us er is set to Yes.
[spacer] IEC: Port A/ B blocke d 104 075
0: No
[spacer]
Display when Port A for SEB or Port A&B for REB is blocked.
[spacer] IEC: Port C blocked 104 076
0: No
[spacer]
Display when Port C is blocked.
[spacer] IEC: Port A fault y 104 197
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
Parameter Address
Orientated
Substation Events
0: No
[spacer]
Display which appears as soon as receipt of at least one of the configured
GOOSEs is faulty or not available. To each GOOSE the GOOSE sending device
will attach a validity stamp, up to which a repetition of GOOSE will be carried out
independent of a change of state. Thus the unit monitors the time period at
which the next state signal must be received.
[spacer] GOOSE: IE D01-16 link ed 107 251
2:
2:
2:
2:
2:
2:
2:
2:
2:
2:
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
Parameter Address
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
Parameter Address
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
Parameter Address
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
Parameter Address
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
Parameter Address
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
Parameter Address
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
Parameter Address
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
0: Interm. pos.
[spacer]
State of the virtual two-pole GOOSE input, representing the state of an external
device.
[spacer] GOOSE: Ext .De v01 ope n 109 001
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
[spacer]
Binary open state of the virtual two-pole GOOSE input, representing the state of
an external device.
[spacer] GOOSE: Ext .De v01 close d 109 002
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
[spacer]
Binary closed state of the virtual two-pole GOOSE input, representing the state
of an external device.
[spacer] GOOSE: Ext .De v01 int erm.pos 109 003
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
[spacer]
Binary intermediate position state of the virtual two-pole GOOSE input,
representing the state of an external device.
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
Parameter Address
0: No
Parameter Address
Binary and analog OUTP: Block outp.r el. EXT 040 014
output
0: No
0: No
Parameter Address
output
1: Yes
0: No
0: No
0: No
Parameter Address
0: No
Parameter Address
2: Not configured
2: Not configured
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
[spacer]
Inrush stabilization may be blocked using this setting.
[spacer] MAIN: Block. harm.bl k. E X T 021 073
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: Standard time
0: No
Parameter Address
1: Yes
[spacer]
Signal that the protection unit is operational. By default this signal is linked to
LED: F ct.ass ig. H 1 gre e n.
[spacer] MAIN: Tim e s ynchr oniz ed 009 109
0: No
0: No
0: No
Parameter Address
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
[spacer]
In the case of direct motor control by motor relay K200 this fault signal is issued
(as a group signal) when no positive position signal (status signal) has been
received from the external device after it has been issued a close command and
the set running time-delay has elapsed.
[spacer] MAIN: Chatt.s uppr . st arte d 221 121
0: No
[spacer]
Signal that the chatter suppression has started.
[spacer] MAIN: St artcm dt ime e xce e d. 221 112
[spacer]
If the monitoring, set by D EV01 : St artC mdTime superv. (or
DEV02: S tartCmdTi me superv . etc.), is active then an exceeded timer is
flagged by this logic state signal.
[spacer] MAIN: Shunt t rip ove rr un 221 114
0: No
[spacer]
Signal that any of the operated switchgear units happens to end up in a faulty
position after termination of the switching command.
[spacer] MAIN: Mult. sig. 1 act iv e 221 017
Parameter Address
1: Yes
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
selection
0: No
2: Not configured
2: Not configured
2: Not configured
2: Not configured
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
Parameter Address
recording
0: No Fig. 3-93, (p. 3-131)
Parameter Address
recording
0: No
Parameter Address
0: No
Parameter Address
acquisition
0: No
[spacer]
Calculation of the fault location is blocked. The parameters FT_DA: Fault
location, FT_DA: Fault locat ion A, F T_D A: Fault location B are
set to Not measured.
Note: FT _DA: Fault locat ion A, F T_D A: Fa ult location B are
available only with the settings MAIN: Fe ede r mode = Autotransformer
feed and
MAIN: Fee de r mode = Single feed w. sum I.
[spacer] FT_DA: Wrong s et ting F. loc 008 191
0: No
Parameter Address
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
1: Yes
Parameter Address
1: Yes
1: Yes
1: Yes
1: Yes
1: Yes
1: Yes
1: Yes
0: No
Parameter Address
Parameter Address
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
Parameter Address
tection
0: No
[spacer]
Blocking of timer stage DE LTA: t Del ta PSx.
[spacer] DELT A: E nable d 038 054
[spacer]
Indicates that high impedance protection is switched on.
[spacer] DELT A: Not ready 038 055
[spacer]
Indicates that high impedance protection is not ready (i.e. a blocking condition is
apparent).
[spacer] DELT A: D elta I ext ende d 038 066
[spacer]
Indicates that the harmonics stabilization feature has detected a load variation.
[spacer] DELT A: D elta I blocked 038 068
[spacer]
Indicates that the sudden current change criterion is blocked.
[spacer] DELT A: I min s tar t ing 038 059
[spacer]
The full-cycle r.m.s. value of the current has exceeded the set minimum current
value.
[spacer] DELT A: D elta I s tarti ng 038 060
[spacer]
Indicates that the sudden current change criterion is met. This signal is used as
a starting for high impedance protection.
[spacer] DELT A: D elta Phi st art ing 038 063
[spacer]
This signal is issued if the angle (with sudden angle change monitoring enabled)
changes by more than the value set for DE LT A: Delta Phi PSx within a
defined sampling interval.
[spacer] DELT A: I (3fn) s tart ing 038 076
[spacer]
Indicates that the ratio of the third harmonic current component to the
fundamental has exceeded the starting value set for DELT A: I(3fn)/ I( fn )
PSx.
Parameter Address
[spacer]
Indicates that the ratio of the fifth harmonic current component to the
fundamental has exceeded the starting value set for DELT A: I(5fn)/ I(fn )
PSx.
[spacer] DELT A: X- release 038 065
[spacer]
Indicates that the measured reactance value is within the set limits.
[spacer] DELT A: T rip s ignal 038 056
[spacer]
Trip signal by the high impedance protection function.
Parameter Address
monitoring
0: No
0: No
[spacer]
This parameter allows to block the “Fuse Failure” monitoring of the reference
voltage via binary input (e. g. from circuit breaker auxiliary contacts) or
programmable logic.
[spacer] MCM ON: Enabled 040 094
0: No
Parameter Address
time protection
0: No
0: No
Parameter Address
protection
0: No
0: No
Parameter Address
2: Not configured
2: Not configured
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
Parameter Address
2: Not configured
2: Not configured
0: No
0: No
0: No
0: No
0: No
0: No
0: No
1: Yes
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
control
2: Not configured
2: Not configured
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
Parameter Address
Parameter Address
synchronism check
0: No
2: Not configured
2: Not configured
0: No
0: No
[spacer]
Close request via external signal for a test triggering of the ASC in operating
mode automatic reclosure.
[spacer] ASC: Te s t M C close r. EXT 037 064
0: No
[spacer]
Close request via external signal for a test triggering of the ASC in operating
mode manual reclosure.
[spacer] ASC: Enab l.close re qu.E X T 037 063
1: Yes
0: No
[spacer]
Close request via external signal for a triggering of the ASC in operating mode
manual reclosure.
[spacer] ASC: AR close re que st E X T 008 236
0: No
[spacer]
Close request via external signal for a triggering of the ASC in operating mode
automatic reclosure.
[spacer] ASC: Ext./us e r enabled 037 092
Parameter Address
[spacer]
Signaling of a close request for a test triggering of the ASC in operating mode
automatic reclosure.
[spacer] ASC: Te s t M C clos e re qu. 034 019
[spacer]
Signaling of a close request for a test triggering of the ASC in operating mode
manual reclosure.
[spacer] ASC: AR Clos e r e ques t 008 239
[spacer]
Signaling of a close request for a triggering of the ASC in operating mode
automatic reclosure.
[spacer] ASC: MC Close r eques t 034 018
[spacer]
Signaling of a close request for a triggering of the ASC in operating mode
manual reclosure.
[spacer] ASC: Cycle running 038 019
Parameter Address
current protection
0: No
0: No
0: No
1: Yes
Parameter Address
0: No
0: No
Parameter Address
current protection
0: No
0: No
[spacer]
Function groups DTOCx are blocked.
Note: Blocking DTOCx via binary input signal can be required, e.g. for the case
that the overcurrent supervision is needed only in case of disconnected
autotransformers.
[spacer] DTOCA: Blocking t I> EX T 130 066
0: No
0: No
0: No
0: No
[spacer]
Blocking of DTOCx timer stage tI> or tI>>, respectively.
[spacer] DTOCA: Enab led 130 073
0: No
[spacer]
Signal that the function group DTOCx is enabled.
[spacer] DTOCA: Not re ady 130 076
1: Yes
[spacer]
Signal that the function group DTOCx is not ready.
Note: The function groups DTOCx are never ready with the setting
MAIN: Fe e de r m ode = Classic single feed.
[spacer] DTOCA: St arting I> 130 069
0: No
Parameter Address
0: No
[spacer]
An overcurrent fault is detected by the function group DTOCx.
[spacer] DTOCA: tI> e lapse d 130 077
[spacer]
Signal that the DTOCx timer stage has elapsed.
[spacer] DTOCA: Trip s ignal t I> 130 071
[spacer]
Trip signal from function group DTOCx. This signal can be assigned to the trip
commands (e.g. MAIN: Fc t.as g. M-t rip cmd1).
Parameter Address
rent protection
0: No
Parameter Address
Parameter Address
rent protection
0: No
0: No
[spacer]
Function groups IDMTx are blocked.
Note: Blocking IDMTx via binary input signal can be required, e.g. for the case
that the overcurrent supervision is needed only in case of disconnected
autotransformers.
[spacer] IDMTA: B lock. tIre f> EX T 130 108
0: No
[spacer]
Blocking of IDMTx timer stage tIref>.
[spacer] IDMTA: Enabled 130 109
0: No
[spacer]
Signal that the function group IDMTx is enabled.
[spacer] IDMTA: Not r e ady 130 117
1: Yes
[spacer]
Signal that the function group IDMTx is not ready.
Note: The function groups IDMTx are never ready with the setting
MAIN: Fee de r mode = Classic single feed.
[spacer] IDMTA: S tar ting I re f> 130 110
0: No
[spacer]
An overcurrent fault is detected by the function group IDMTx.
[spacer] IDMTA: t Ir e f> ela pse d 130 112
Parameter Address
[spacer]
Signal that the DTOCx timer stage tIref> has elapsed.
[spacer] IDMTA: T r ip s ignal tIre f> 130 113
[spacer]
Trip signal from function group IDMTx. This signal can be assigned to the trip
commands (e.g. MAIN: Fc t.as g. M-t rip cmd1).
[spacer] IDMTA: Hold t ime running 130 114
0: No
[spacer]
Signal that the hold-time for IDMTx (see IDM TA: Hold time PSx,
IDMTB : Hold time P S x) is running.
[spacer] IDMTA: M e m ory cle ar 130 115
1: Yes
[spacer]
Signal that the memory storing the sum of the starting times is clear.
Parameter Address
0: No
Parameter Address
protection
0: No
0: No
0: No
0: No
0: No
0: No
1: Yes
0: No
Parameter Address
0: No
Parameter Address
tion
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
Parameter Address
underfrequency pro‐
tection
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
failure protection
0: No
2: Not configured
2: Not configured
1: Yes
Parameter Address
Parameter Address
condition monitoring
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
monitoring
0: No Fig. 3-257, (p. 3-315)
Parameter Address
Parameter Address
0: Not triggered
0: Not triggered
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
2: Not configured
2: Not configured
2: Not configured
2: Not configured
2: Not configured
2: Not configured
2: Not configured
2: Not configured
2: Not configured
2: Not configured
2: Not configured
2: Not configured
2: Not configured
2: Not configured
2: Not configured
2: Not configured
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
[spacer]
Warning that the number of switching commands has exceeded the set limit
value.
Parameter Address
0: No
0: No
0: No
0: Intermediate pos.
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: Intermediate pos.
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: Intermediate pos.
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: Intermediate pos.
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: Intermediate pos.
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: Intermediate pos.
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: Intermediate pos.
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: Intermediate pos.
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: Intermediate pos.
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
[spacer]
Output of the respective equation of the interlocking logic.
These logic state signals are transmitted with the request for a switching
operation, and cyclically (according to the setting ILO CK: Cycle t
inte rl.che ck).
Parameter Address
commands
0: No Fig. 3-295, (p. 3-360)
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
Parameter Address
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
0: No
[spacer]
Warning that the counter value has exceeded the set limit value.
Parameter Address
0: No
Parameter Address
0: No
[spacer]
Setting the enable for changing values from the local control panel.
Parameter Address
communication
interface 1
060 000: MAIN: Without function Fig. 3-18, (p. 3-26)
[spacer]
Signal selection for testing purposes.
[spacer] COMM 1: Tes t s pont .s ig.s t ar t 003 184
[spacer]
Triggering of transmission of a selected signal as “starting”.
[spacer] COMM 1: Tes t s pont .s ig. end 003 186
[spacer]
Triggering of transmission of a selected signal as “ending”.
[spacer] COMM 1: Se l. po s. dev. tes t 221 105
0: Not assigned
[spacer]
Select a device DEVxx for testing the transmission of switchgear device position
in monitoring direction.
[spacer] COMM 1: Tes t p osition de v. 221 106
0: don't execute
[spacer]
Carry out a test to check the transmission of switchgear device position in
monitoring direction for the device selected at C OMM1: S el. pos .
dev.test.
Parameter Address
communication
interface 2
060 000: MAIN: Without function Fig. 3-20, (p. 3-29)
[spacer]
Signal selection for testing purposes.
[spacer] COMM 2: Tes t s pont .s ig.s t ar t 103 184
[spacer]
Triggering of transmission of a selected signal as "starting".
[spacer] COMM 2: Tes t s pont .s ig. end 103 186
[spacer]
Triggering of transmission of a selected signal as "ending".
Parameter Address
interface
0: don't execute
[spacer]
Resetting counter for number of telegram errors.
[spacer] COMM 3: Se nd s ignal for t es t 120 050
0: None
1: 1
0: don't execute
170 0 255
[spacer]
Setting a bit pattern consisting of 3 bits.
[spacer] COMM 3: Loop back t est 120 054
0: don't execute
[spacer]
Carrying out a loop back test with the PCOMM interface.
[spacer] COMM 3: Hold time for te s t 120 052
10 1 600 s
[spacer]
Selecting the hold time (in seconds) for the functional testing.
Parameter Address
Communication
060 000: MAIN: Without function Fig. 3-29, (p. 3-53)
0: Not assigned
0: don't execute
Parameter Address
0: don't execute
[spacer]
Resetting measured maximum temperatures Tmax and Tmax Tx (x=1...9) to
updated measured values.
Parameter Address
output
0: don't execute Fig. 3-41, (p. 3-69)
[spacer]
Reset of latched output relays from the user interface.
[spacer] OUTP: Re lay assign. f.t e st 003 042
[spacer]
Selection of the relay to be tested.
[spacer] OUTP: Re lay te st 003 043
[spacer]
The relay selected for testing is triggered for the duration set at OUTP: H ol d -
time f or tes t.
[spacer] OUTP: Hold- tim e for t e st 003 044
[spacer]
Setting for the time period for which the selected output relay is triggered for
functional testing.
Parameter Address
output
0: don't execute Fig. 3-45, (p. 3-72)
[spacer]
Resetting the measured data output function.
Parameter Address
[spacer]
Reset of the following memories:
● All counters
● LED indicators
● Operating data memory
● All event memories
● Event counters
● Fault data
● Measured overload data
● Recorded fault values
[spacer] MAIN: Re s e t indicat. USE R 021 010
[spacer]
Reset of the following displays:
● LED indicators
● Fault data
[spacer] MAIN: Rs e t .lat ch.t rip US ER 021 005
0: don't execute
[spacer]
Reset of latched trip commands from the local control panel.
[spacer] MAIN: Re s e t m eas .v. en.USE R 003 032
[spacer]
The display of active and reactive energy output and input is reset.
[spacer] MAIN: Re s e t c. cl/ t r. cUS ER 003 007
[spacer]
The counters for counting the close and trip commands are reset.
[spacer] MAIN: Group res e t 1 USER 005 253
[spacer]
Group of resetting commands.
[spacer] MAIN: En.m an.trip cmd.USER 003 064
[spacer]
Enabling of manual trip commands from the local control panel.
Parameter Address
[spacer]
A trip command is issued from the local control panel for 100 ms.
[spacer] MAIN: Man.M- trip cmd2 US ER 003 082
[spacer]
A trip command is issued from the front panel HMI for the 100 ms.
[spacer] MAIN: Man.R- trip cmd US ER 003 066
[spacer]
A trip command is issued from the front panel HMI for the 100 ms.
Note: This command is not executed unless the manual trip has been
configured as re-trip command.
[spacer] MAIN: Man.R- trip cmd2 US ER 003 083
[spacer]
A trip command is issued from the front panel HMI for the 100 ms.
Note: This command is not executed unless the manual trip has been
configured as a re-trip command 2.
[spacer] MAIN: Man.B-trip cmd USE R 003 067
[spacer]
A trip command is issued from the front panel HMI for the 100 ms.
Note: This command is not executed unless the manual trip has been
configured as a back-trip command.
[spacer] MAIN: Man.B-trip cmd2 U SE R 003 087
[spacer]
A trip command is issued from the front panel HMI for the 100 ms.
Note: This command is not executed unless the manual trip has been
configured as a back-trip command 2.
[spacer] MAIN: En.m an.clos .cmd.USE R 003 105
[spacer]
Setting the enable for the issue of a close command from the local control panel
(enables manual breaker close operations).
[spacer] MAIN: Man. clos e cmd. US ER 018 033
[spacer]
A close command is issued from the local control panel for the set reclose
command time.
Parameter Address
0: don't execute
[spacer]
A warm restart is carried out. The device functions as it does when the power
supply is turned on.
[spacer] MAIN: Warm re star t 010 166
0: don't execute
[spacer]
A warm restart is carried out. The device functions as it does when the power
supply is turned on.
[spacer] MAIN: Sof t Cold re star t 000 085
0: don't execute
[spacer]
A cold restart is carried out. A cold restart means that all settings and recordings
are cleared. Parameter values used by the P438 after a cold restart have been
selected in such a manner that the P438 is blocked after a cold restart.
[spacer] MAIN: Cold rest art 009 254
0: don't execute
[spacer]
A cold restart is carried out. A cold restart means that all settings and recordings
are cleared. Parameter values used by the P438 after a cold restart have been
selected in such a manner that the P438 is blocked after a cold restart.
Parameter Address
recording
0: don't execute Fig. 3-98, (p. 3-139)
[spacer]
The operating data memory and the counter for operation signals are reset.
Parameter Address
recording
0: don't execute Fig. 3-99, (p. 3-140)
[spacer]
Reset of the monitoring signal memory.
Parameter Address
[spacer]
Reset of the overload memory.
Parameter Address
[spacer]
Fault recording is enabled from the local control panel for 500 ms.
[spacer] FT_RC: Res et record. USE R 003 006
[spacer]
Reset of the following memories:
● LED indicators
● Fault memory
● Fault counter
● Fault data
● Recorded fault values
Parameter Address
[spacer]
Protective signaling is enabled from the local control panel.
[spacer] PSIG1: Disab le USER 003 131
[spacer]
Protective signaling is disabled from the local control panel.
[spacer] PSIG1: T es t telecom. USE R 015 009
[spacer]
A send signal is issued for 500 ms.
Parameter Address
0: don't execute
0: don't execute
0: don't execute
Parameter Address
control
0: don't execute Fig. 3-175, (p. 3-220)
[spacer]
The auto-reclosing control function is enabled from the local control panel.
[spacer] ARC: Disable USER 003 133
[spacer]
The auto-reclosing control function is disabled from the local control panel.
[spacer] ARC: T est HS R USER 011 066
[spacer]
A three-pole test HSR is triggered.
[spacer] ARC: R ese t recl.t ime 2US E R 003 025
0: don't execute
[spacer]
The reset of the reclaim time 2 (which has been triggered after the final trip)
removes the auto-reclose blocking.
[spacer] ARC: R ese t counte rs US ER 003 005
[spacer]
The ARC counters are reset.
Parameter Address
synchronism check
0: don't execute Fig. 3-195, (p. 3-246)
[spacer]
Automatic synchronism check is enabled from the local control panel.
[spacer] ASC: Disable USER 003 135
[spacer]
Automatic synchronism check is disabled from the local control panel.
[spacer] ASC: AR close re qu. US E R 008 238
[spacer]
A close request is issued with Automatic Reclose parameters. This will trigger
the ASC functional operation. A close command is transmitted to the CB if the
check of the ASC is positive.
[spacer] ASC: MC clos e r e qu. USE R 018 004
[spacer]
A close request is issued from the integrated local control panel. This will trigger
the ASC functional operation. A close command is transmitted to the CB if the
check of the ASC is positive.
[spacer] ASC: Te s t AR clos e r .US ER 008 237
[spacer]
A close request is issued with Automatic Reclose parameters. This will trigger
the ASC functional operation. No close command is transmitted to the CB if the
check of the ASC is positive. Only a signal is issued.
[spacer] ASC: Te s t M C close r.USER 018 005
[spacer]
A close request is issued from the integrated local control panel. This will trigger
the ASC functional operation. No close command is transmitted to the CB if the
check of the ASC is positive. Only a signal is issued.
[spacer] ASC: R es et counter s US ER 003 089
[spacer]
The ASC counters are reset.
Parameter Address
protection
0: don't execute Fig. 3-239, (p. 3-294)
[spacer]
Resetting the thermal replica of the thermal overload protection function.
Parameter Address
underfrequency pro‐
tection
0: don't execute
[spacer]
Resetting the measured event values f<>: M ax. frequ. for
f> and f<>: Min. fre qu. for f<.
Parameter Address
failure protection
0: don't execute
[spacer]
Circuit breaker failure protection is enabled from the local control panel.
[spacer] CBF: Disable USER 003 015
0: don't execute
[spacer]
Circuit breaker failure protection is disabled from the local control panel.
Parameter Address
condition monitoring
0: don't execute
[spacer]
Values are initialized to trigger circuit breaker condition monitoring.
[spacer] CBM: R e se t m eas .val . USER 003 013
0: don't execute
[spacer]
Resetting circuit breaker condition monitoring
[spacer] CBM: S e t No. CB oper. A 022 131
Blocked 0 65000
Blocked 0 65000
[spacer]
Set the number of CB operations.
[spacer] CBM: S e t remain. CB op. A 022 134
Blocked 0 65000
Blocked 0 65000
[spacer]
Set the remaining CB operations.
[spacer] CBM: S e t ΣItrip A 022 137
[spacer]
Set the limit values for the ruptured currents and their squares. (An alarm is
displayed if these limit values are exceeded.)
Parameter Address
0: don't execute
0: don't execute
0: don't execute
0: don't execute
0: don't execute
0: don't execute
[spacer]
Intervention in the logic at the appropriate point by a 100 ms pulse.
Parameter Address
[spacer]
Count transmission.
[spacer] COUNT : Re s e t USE R 217 003
[spacer]
Count reset.
Parameter Address
recording
0 0 100 Fig. 3-98, (p. 3-139)
[spacer]
Point of entry into the operating data log.
Parameter Address
recording
0 0 30 Fig. 3-99, (p. 3-140)
[spacer]
Point of entry into the monitoring signal log.
8.2 Events
Parameter Address
interface
0 0 65535
[spacer]
Number of corrupted telegrams.
Parameter Address
[spacer]
Number of general starting signals.
[spacer] MAIN: CB1 act. oper . cap. 221 087
1 1 99
1 1 99
[spacer]
Setting for the maximum number of CB operations for an ARC cycle (or for a
limited time period).
[spacer] MAIN: No. M -trip cmds. 1 009 005
[spacer]
Number of main-trip commands.
[spacer] MAIN: No. M -trip cmds. 2 009 027
[spacer]
Number of main-trip 2 commands.
[spacer] MAIN: No. R -trip cmds. 1 009 006
[spacer]
Number of re-trip commands.
[spacer] MAIN: No. R -trip cmds. 2 009 028
[spacer]
Number of re-trip 2 commands.
[spacer] MAIN: No. B- trip cmds. 1 009 007
[spacer]
Number of back-trip commands.
[spacer] MAIN: No. B- trip cmds. 2 009 029
[spacer]
Number of back-trip 2 commands.
[spacer] MAIN: No. f inal t rip c mds . 004 005
[spacer]
Number of final trip commands.
[spacer] MAIN: No. close c ommands 009 055
[spacer]
Number of close commands.
Parameter Address
[spacer]
Counter for the number of times the measuring range of the active energy
output was exceeded.
Note: The maximum value of this counter is 10000.
[spacer] MAIN: No.overfl .act.e n. inp 009 091
[spacer]
Counter for the number of times the measuring range of the active energy input
was exceeded.
Note: The maximum value of this counter is 10000.
[spacer] MAIN: No.ov/f l.re ac.e n.out 009 092
[spacer]
Counter for the number of times the measuring range of the reactive energy
output was exceeded.
Note: The maximum value of this counter is 10000.
[spacer] MAIN: No.ov/f l.re ac.e n.inp 009 093
[spacer]
Counter for the number of times the measuring range of the reactive energy
input was exceeded.
Note: The maximum value of this counter is 10000.
[spacer] MAIN: No. m otor dri ve op. 221 025
[spacer]
Number of times external devices with direct motor control are activated during
the monitoring time.
[spacer] MAIN: Count, binary 221 020
0: don't execute
Parameter Address
recording
0 0 100 Fig. 3-98, (p. 3-139)
[spacer]
Number of signals stored in the operating data memory.
Parameter Address
recording
0 0 30 Fig. 3-99, (p. 3-140)
[spacer]
Number of signals stored in the monitoring signal memory.
Parameter Address
[spacer]
Number of overload events.
Parameter Address
[spacer]
Number of faults.
[spacer] FT_RC: No. sys te m dis t urb. 004 010
[spacer]
Number of system disturbances.
Parameter Address
control
0: don't execute Fig. 3-193, (p. 3-243)
[spacer]
Number of three-pole high-speed reclosures.
[spacer] ARC: No. of TDR 004 008
[spacer]
Number of time-delay reclosures.
Parameter Address
synchronism check
0: don't execute Fig. 3-209, (p. 3-261)
[spacer]
Number of reclosures after a manual close request.
[spacer] ASC: No. clos e re que st s 009 033
[spacer]
Number of close requests.
[spacer] ASC: No. clos e re je ct ions 009 034
[spacer]
Number of close rejections.
Parameter Address
condition monitoring
0 0 65000 Fig. 3-252, (p. 3-310)
Fig. 3-253, (p. 3-311)
[spacer]
Number of mechanical switching operations made.
[spacer] CBM: R e main. No. CB op. A 008 014
[spacer]
Number of remaining switching operations (as shown by evaluating wear with
reference to the CB wear characteristic).
Parameter Address
0 0 65535
0 0 65535
0 0 65535
0 0 65535
0 0 65535
0 0 65535
0 0 65535
0 0 65535
0 0 65535
[spacer]
Number of switching operations made. It is also possible to manually set this
counter to any value from 0 to 65535.
[spacer] DEV01: De v. op. c apabi li ty 210 003
1 1 99
1 1 99
1 1 99
1 1 99
1 1 99
1 1 99
1 1 99
1 1 99
Parameter Address
1 1 99
1 1 99
[spacer]
Number of remaining switching operations. It is also possible to manually set
this counter to any value from 1 to 99.
Parameter Address
acquisition
Not measured 0.0 6500.0 s Fig. 3-100, (p. 3-141)
[spacer]
Duration of the overload event.
[spacer] OL_DA: S tatus TH ERM r e pl ic a 004 147
[spacer]
Display of the buffer content of the thermal overload protection function.
[spacer] OL_DA: L oad curre nt T HERM 004 058
[spacer]
Display of the load current used by the thermal overload protection function to
calculate the tripping time.
[spacer] OL_DA: Ob ject t emp. THE RM 004 035
[spacer]
Display of the temperature of the protected object.
[spacer] OL_DA: C oolant temp. T HERM 004 036
[spacer]
Display of coolant temperature, dependent on the setting for THE RM: Sel ect
CTA PSx.
When set to Default temp. value the set temperature value will be displayed.
When set to From PT100 the temperature measured by the resistance
thermometer will be displayed. When set to From 20 mA input the temperature
measured via an external 20 mA transducer will be displayed.
[spacer] OL_DA: Pre - trip t .le ft THE RM 004 148
[spacer]
Display of the time remaining before the thermal overload protection function
will reach the tripping threshold (“time-to-trip”).
[spacer] OL_DA: Of fs et THERM r epl ic a 004 154
[spacer]
Display of the additional reserve if coolant temperature is taken into account
and if the measured coolant temperature is lower than the set maximum
permissible coolant temperature. (In this case, the thermal model has been
shifted downwards.)
If there is no coolant temperature acquisition and if the coolant temperature and
the maximum permissible coolant temperature have been set to the same
value, then the coolant temperature is not taken into account and the
characteristic is a function of the current only. The additional reserve amounts
to 0 in this case.
Parameter Address
acquisition
Not measured 0.0 6500.0 s Fig. 3-104, (p. 3-146)
[spacer]
Display of the fault duration.
[spacer] FT_DA: Running t ime 004 021
[spacer]
Display of the running time.
[spacer] FT_DA: Fault d et er m. 004 198
[spacer]
Display of the protection element/zone that has identified the fault.
[spacer] FT_DA: Run tim e t o meas . 004 199
[spacer]
Display of the fault data acquisition time from the onset of the fault.
[spacer] FT_DA: Fault curre nt p.u. 004 025
[spacer]
Display of the fault current referred to Inom.
[spacer]
Display of the catenary current referred to In.
[spacer] FT_DA: Fault curre nt B p.u. 004 182
[spacer]
Display of the feeder current referred to In.
[spacer] FT_DA: Fault vol tage p.u. 004 026
[spacer]
Display of the fault voltage referred to Vnom.
[spacer]
Display of the catenary voltage referred to Vnom.
[spacer]
Display of the feeder voltage referred to Vnom.
[spacer]
Display of the fault angle.
Parameter Address
[spacer]
Display of the fault angle for the catenary line or feeder line.
Note: This measurement value is available only with the settings
MAIN: Fe e de r m ode = Autotransformer feed and
MAIN: Fe e de r m ode = Single feed w. sum I.
[spacer] FT_DA: Fault react ance, pr im 004 029
[spacer]
Display of the fault reactance as a primary quantity.
[spacer] FT_DA: Fault react .,pri A 235 206
[spacer]
Display of the fault reactance as a primary quantity for the catenary line or
feeder line.
Note: This measurement value is available only with the settings
MAIN: Fe e de r m ode = Autotransformer feed and
MAIN: Fe e de r m ode = Single feed w. sum I.
[spacer] FT_DA: Fault im pedance ,pr im 004 176
[spacer]
Display of the fault impedance as a primary quantity.
[spacer] FT_DA: Fault im ped.,pri A 235 207
[spacer]
Display of the fault impedance as a primary quantity for the catenary line or
feeder line.
Note: This measurement value is available only with the settings
MAIN: Fe e de r m ode = Autotransformer feed and
MAIN: Fe e de r m ode = Single feed w. sum I.
[spacer] FT_DA: Fault react ance, se c. 004 028
[spacer]
Display of the fault reactance as a secondary quantity.
[spacer] FT_DA: Fault react .,s ec A 235 205
Parameter Address
[spacer]
Display of the fault reactance as a secondary quantity for the catenary line or
feeder line.
Note: This measurement value is available only with the settings
MAIN: Fe e de r mode = Autotransformer feed and
MAIN: Fe e de r mode = Single feed w. sum I.
[spacer] FT_DA: Fault impe dance ,se c. 004 023
[spacer]
Display of the fault impedance as a secondary quantity.
[spacer] FT_DA: Fault impe d.,s e c. A 235 202
[spacer]
Display of the fault impedance as a secondary quantity for the catenary line or
feeder line.
Note: This measurement value is available only with the settings
MAIN: Fe e de r mode = Autotransformer feed and
MAIN: Fe e de r mode = Single feed w. sum I.
[spacer] FT_DA: Fault locat. pe rce nt 004 027
[spacer]
Display of the fault location of the last fault (in %) referred to the setting at
FT_DA: XLf orw.,s ec A- 1 PS x.
[spacer] FT_DA: Fault loc. pe rce nt A 235 204
[spacer]
Display of the fault location of the last fault (in %), referred to the setting at
FT_DA: XLf orw.,s ec A- 1 PS x, for the catenary line or feeder line.
Note: This measurement value is available only with the settings
MAIN: Fe e de r mode = Autotransformer feed and
MAIN: Fe e de r mode = Single feed w. sum I.
[spacer] FT_DA: Fault location 004 022
[spacer]
Display of the fault location of the last fault in km.
Parameter Address
[spacer]
Display of the fault location of the last fault in km for the catenary line or feeder
line.
Note: This measurement value is available only with the settings
MAIN: Fe e de r m ode = Autotransformer feed and
MAIN: Fe e de r m ode = Single feed w. sum I.
[spacer] FT_DA: Ip laus/Idfrst. p.u. 004 177
[spacer]
Display of the CT plausibility check current or defrost current referred to In.
Parameter Address
synchronism check
Not measured 0.000 3.000 Vnom Fig. 3-208, (p. 3-261)
[spacer]
Display of the difference between amplitudes of the measurement loop voltage
and the reference voltage during a close request, referred to Vnom. The display
only appears if ASC is operating.
[spacer] ASC: Angle dif fe rence 004 089
[spacer]
Display of the angle difference between measured voltage and reference
voltage at the time of the close request (in degrees).
This display only appears when the automatic synchronism check function is
active.
[spacer] ASC: Fre qu. dif fe re nce 004 090
[spacer]
Display of the frequency difference between measured voltage and reference
voltage at the time of the close request (in Hz). This display only appears when
the automatic synchronism check function is active.
Parameter Address
underfrequency pro‐
tection
Not measured 12.00 70.00 Hz
[spacer]
Maximum frequency during an overfrequency condition.
[spacer] f<> : M in. frequ. for f< 005 001
[spacer]
Minimum frequency during an underfrequency condition.
Parameter Address
condition monitoring
Not measured 0 65000 A
[spacer]
Ruptured currents and their squared values.
[spacer] CBM: I *t A 009 061
[spacer]
Current-time integral of the per-unit ruptured current for each circuit breaker
contact.
[spacer] CBM: ΣItr ip A 009 071
0 0 65000 Inom,CB
0 0 65000 Inom,CB
[spacer]
Sum of the per-unit ruptured currents for each circuit breaker contact.
[spacer] CBM: ΣItr ip **2 A 009 077
0 0 65000 Inom,CB**
2
0 0 65000 Inom,CB**
2
[spacer]
Sum of the squared per-unit ruptured currents for each circuit breaker contact.
[spacer] CBM: ΣI* t A 009 087
Parameter Address
[spacer]
Sum of the current-time integrals of the per-unit ruptured currents for each
circuit breaker contact.
Parameter Address
0 0 9999
0 0 9999
0 0 9999
0 0 9999
0 0 9999
0 0 9999
0 0 9999
[spacer]
Point of entry into the overload log.
Parameter Address
0 0 9999
0 0 9999
0 0 9999
0 0 9999
0 0 9999
0 0 9999
0 0 9999
0 0 9999
[spacer]
Point of entry into the fault log.
Parameter
Name of the configuration bank currently valid. Setting is carried out with the
IED Configurator, after a connection with the device has been established (via
menu item “Manage IED”).
Version number of the configuration bank currently valid. Setting is carried out
with the IED Configurator, after a connection with the device has been
established (via menu item “Manage IED”).
Parameter
Name of the inactive configuration bank. Setting is carried out with the IED
Configurator, after a connection with the device has been established (via menu
item “Manage IED”).
Version number of the inactive configuration bank. Setting is carried out with
the IED Configurator, after a connection with the device has been established
(via menu item “Manage IED”).
Identification of the .MCL configuration file. If required, this preset value may be
modified by, for example, entering a bay name.
Specific value to identify the IEC 61850 data model and configuration.
If required, this preset value may be modified by, for example, identifying the
revision states during engineering.
Parameter Address
Explicitly assigned device name for the function in the system (IED); is part of
the Logical Device Name.
Important note: According to the IEC standard the name must consist of only
letters (A..Z, a..z), digits (0..9) and underscore characters (_), and the name
must start with a letter. Note that a non-standard name causes problems with
the IEC 61850 communication.
Parameter
Description
Type
Configuration Revision
Supported Models
The values listed in the column “Template Details” only provide information.
They are preset and cannot be modified.
9.3 Communications
The category “Communications” contains the general network-related settings.
Assigned IP address of the Interface1 of P437 for the server function in the
system.
The subnet mask defines which part of the IP address is addressed by the sub-
network and which part by the device that is logged-on to the network.
This parameter shows the IPv4 address of the network gateway for
communication links to clients outside of the local network.
Assigned IP address of the Interface2 of P437 for the server function in the
system.
The subnet mask defines which part of the IP address is addressed by the sub-
network and which part by the device that is logged-on to the network.
This parameter shows the IPv4 address of the network gateway for
communication links to clients outside of the local network.
2 104 096
The subnet mask of VLAN defines which part of the IP address is addressed by
the sub-network and which part by the device that is logged-on to the network.
This parameter shows the IPv4 address of the network gateway of the VLAN for
communication links to clients outside of the local network.
Return time period for setting procedures that have commenced. (The default
value above is in seconds. The IED Configurator, however, displays converts this
to minutes.)
9.4 SNTP
The category “SNTP” contains the clock synchronization settings.
Parameter
Location
Contents
9.6.1 System/LLN0
Virtual MAC address that the sending device provides as the destination; preset.
ID-number of the virtual LAN with which the GOOSE is sent; preset.
VLAN Priority 4
Priority with which the GOOSE is sent in the virtual LAN; preset.
First send repetition of the GOOSE occurring after the set time period; preset.
Continuous send repetition of the GOOSE occurring after the set time period;
preset.
Increment 900
Specification factor for the transition of time intervals for GOOSE send
repetitions from the first to the continuous repetition.
GOOSE ID consisting of the Device Name and the GOOSE Control Block.
Dataset Reference
Configuration Revision 1
Application ID (hex) 0
GOOSE Identifier
Dataset Reference
Configuration Revision 0
Distance of the quality descriptor to the data object if not preset. The quality of
the received information is to be tested if such has been configured.
Default value for the information in case GOOSE receipt has failed.
● False – not set
● True – set
● Last Known Value – retain last value received
● Double Point: intermediate (00) – switching device in intermediate position
● Double Point: Off (01) – switching device open
● Double Point: On (10) – switching device closed
● Double Point: Bad state (11) – switching device in intermediate position
9.8.1 System/LLN0
Report type:
● Unbuffered (updating)
● Buffered (saving)
Report ID TEMPLATESystem/
LLN0$RP
$urcbA, ...,
TEMPLATESystem/
LLN0$RP
$urcbP, ...,
TEMPLATESystem/
LLN0$BR
$brcbA, ...,
TEMPLATESystem/
LLN0$BR$brcbH
Report ID consisting of the Device Name and the Report Control Block.
Dataset Reference
Configuration Revision 1
9.9 Controls
Parameter
sboTimeout
Application ID (hex) 0
GOOSE Identifier
Dataset Reference
Configuration Revision 0
Default value for the information in case GOOSE receipt has failed:
● False – not set
● True – set
● Last Known Value – retain last value received
● Double Point: intermediate (00) – switching device in intermediate position
● Double Point: Off (01) – switching device open
● Double Point: On (10) – switching device closed
● Double Point: Bad state (11) – switching device in intermediate position
9.10 Measurements
Parameter
Parameter
Multiplier for the smallest display value of the measured value. In order to have
the current measured value sent when it has changed from the value last sent
the result of the set dead band value multiplied by the smallest display value
must exceed the smallest display value.
9.11.1 System/LLN0
Parameter
Mod.measCyc Value
Parameter
Mod.enCyc Value
Cyclic transmission of measured values without dead band check: Time interval
in seconds between transmissions of two energy count values.
Parameter
Mod.comtrade Value
Parameter
Mod.distExtr Value
10 Commissioning
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ Only qualified personnel, trained, authorized and familiar with the device
and all the safety instructions in the general Safety Guide (SFTY/5LM/L11
or later version) and appropriate Chapter 5, Chapter 10, Chapter 11,
Chapter 12 and Chapter 13 of this manual, shall work on installation,
connection, commissioning, maintenance or servicing of this device.
⚫ When installing and connecting the device the warning notices at the
beginning of Chapter “Installation and Connection” (Chapter 5) must be
observed.
Failure to follow these instructions will result in death or serious
injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ Switch off the auxiliary power supply before any work in the terminal strip
area.
⚫ Switch off all the power supplies in connection to the equipment before
any work in the terminal strip area to isolate the device.
⚫ Do not touch the terminal strip area when equipment is in operation.
⚫ Do not remove or add wires in the terminal strip area when equipment is
in operation.
⚫ Short-circuit the system current transformers before disconnecting wires
to the transformer board (valid only for pin terminals, not required for ring
terminals which have a shortening block).
⚫ A protective conductor (ground/earth) of at least 1.5 mm2 must be
connected to the protective conductor terminal on the power supply board
and on the main relay case.
⚫ Do never remove the protective conductor connection to the device casing
as long as other wires are connected to it.
⚫ Where stranded conductors are used, insulated crimped wire end ferrules
must be employed.
Failure to follow these instructions will result in death or serious
injury.
Note: Regarding the appropriate wiring connections of the equipment refer to the
document Px3x_Grounding_Application_Guide_EN_h.pdf.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ The device must be reliably grounded to meet protective equipment
grounding requirements.
⚫ The surface-mounted case is grounded using the bolt and nut,
appropriately marked, as the ground connection. The flush-mounted case
must be grounded in the area of the rear sidepieces at the location
provided. The bracket is marked with the protective ground symbol: .
The cross-section of the ground conductor must conform to applicable
national standards. A minimum cross section of 2.5 mm² (≤ AWG12) is
required.
⚫ In addition, a protective ground connection at the terminal contact on the
power supply module (identified by the letters “PE” on the terminal
connection diagram) is also required for proper operation of the device.
The cross-section of this ground conductor must also conform to applicable
national standards. A minimum cross section of 1.5 mm² (US: AWG14 or
thicker) is required.
⚫ All grounding connections must be low-inductance, i.e. it must be kept as
short as possible.
⚫ The protective conductor (earth) must always be connected to the
protective grounding conductor terminal in order to guarantee the safety
given by this setup.
Failure to follow these instructions will result in death or serious
injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ Application of analog signals to the measuring inputs must be in
compliance with the maximum permissible rating of the measuring inputs
(see “Technical Data”, Chapter 2).
⚫ Do not open the secondary circuit of live system current transformers! If
the secondary circuit of a live CT is opened, there is the danger that the
resulting voltages will endanger personnel and damage the insulation.
⚫ For pin-terminal connection devices, the terminal block for system current
transformer connection is not a shorting block! Therefore always short-
circuit the system current transformers before loosening the threaded
terminals.
Failure to follow these instructions will result in death or serious
injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ The power supply must be turned off for at least 5 s before power supply
module V is removed. Otherwise there is the danger of an electric shock.
Failure to follow these instructions will result in death or serious
injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ When increased-safety machinery is located in a hazardous area the
device must always be installed outside of this hazardous area to protect
this equipment.
Failure to follow these instructions will result in death or serious
injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ The PC interface is not designed as a permanent connection.
Consequently, the female connector does not have the extra insulation
from circuits connected to the system that is required per IEC/EN
60255-27. Therefore DO NOT leave any permanent cable connection on
the PC interface connector at the HMI front panel.
Failure to follow these instructions will result in death or serious
injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ Do not connect or disconnect the RS 485 or fiber-optic interface when the
supply voltage for the device is under power and in operation.
Failure to follow these instructions will result in death or serious
injury.
WARNING
HAZARD OF UNINTENDED EQUIPMENT OPERATION
⚫ When using the programmable logic (function group LOGIC), the user must
carry out a functional type test to conform to the requirements of the
relevant protection/control application.
⚫ In particular, it is necessary to verify that the requirements for the
implementation of logic linking (by setting) as well as the time
performance during device startup, during operation and when there is a
fault (device blocking) are fulfilled.
Failure to follow these instructions can result in unintended
equipment operation.
10.2.1 Preparation
After the P438 has been installed and connected as described in Chapter 5, (p. 5-
1), the commissioning procedure can begin.
Before turning on the power supply voltage, the following items must be checked
again:
● Is the device connected to the protective ground at the specified location?
● Does the nominal voltage of the battery agree with the nominal auxiliary
voltage of the device?
● Are the current and voltage transformer connections, grounding, and phase
sequences correct?
After the wiring work is completed, check the system to make sure it is properly
isolated. The conditions given in IEC/EN 60255-27 must be satisfied.
Once all checks have been made, the power supply voltage may be turned on.
After voltage has been applied, the device starts up. During startup, various
startup tests are carried out (see Section 3.15, (p. 3-136)). The LED indicators for
HEALTHY (H1) and OUT OF SERVICE (H2) will light up. After approximately 15 s,
the P438 is ready for operation. By default (factory setting) or after a cold restart,
the device type “P438” and the time are displayed on the first line of the LCD
after the device has started up. If a bay type has already been selected this bay
will then be shown as a single-pole display.
Once the change enabling command has been issued (see Section 6.13.3, (p. 6-
38)), all settings can be entered. The procedure for entering settings from the
integrated local control panel is described in Section 6.13.4, (p. 6-41).
If either the PC interface or the communication interface will be used for setting
the P438 and reading out event records, then the following settings must first be
made from the integrated local control panel.
The settings given above apply to the IEC 60870-5-103 communication protocol. If
another protocol is being used for the communication interface, additional settings
may be necessary. See Chapter “Settings” for further details.
After the settings have been made, the following checks should be carried out
again before the blocking is cancelled:
You can edit rights (associated Element To Secure (ETS)) for each role:
You can edit Elements To Secure (ETS) by editing permissions, objects and
rights:
Please, refer to the “Security Administration Tool ” for complete information about
security administration tool.
10.2.3 Testing
When testing trip or close commands configured to standard outputs, the CB must
not be mechanically locked, so that its auxiliary 52a/b contact could operate and
break the DC current. If the CB has to stay locked, tripping or closing circuit has to
be opened by terminal disconnection or test switch. Otherwise there is a high risk
of damaging the P438 output contact.
The manual trip command is not executed unless the manual trip is included in the
selection of possible functions to effect a trip (in the configuration of trip
commands).
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ Before starting the test, open any triggering circuits for external devices so
that no inadvertent switching operations will take place.
Failure to follow these instructions will result in death or serious
injury.
Furthermore, the signal at the binary signal input configured for MA IN: M.c. b.
trip V EX T must have a logic value of 0 before checking all the distance zones.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ Application of analog test values to the measuring inputs must be in
compliance with the maximum permissible rating of the measuring inputs
(see Chapter “Technical Data”, Chapter 2).
Failure to follow these instructions will result in death or serious
injury.
10.2.8.1.1 Characteristics
With the P438, the user may choose between a polygonal and a circular tripping
characteristic. This selection of the tripping characteristic will then govern
calculation of the tripping impedances. This selection of the tripping
characteristic will then govern calculation of the testing impedances. Functional
testing at significant fault angles (for example, 0°, line impedance angle, 90°), in
each case at the zone boundary (tripping impedances +5% or -5%), is
recommended.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ Application of analog test values to the measuring inputs must be in
compliance with the maximum permissible rating of the measuring inputs
(see Chapter “Technical Data”, Chapter 2).
Failure to follow these instructions will result in death or serious
injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ Application of analog test values to the measuring inputs must be in
compliance with the maximum permissible rating of the measuring inputs
(see Chapter “Technical Data”, Chapter 2).
Failure to follow these instructions will result in death or serious
injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ Application of analog test values to the measuring inputs must be in
compliance with the maximum permissible rating of the measuring inputs
(see Chapter “Technical Data”, Chapter 2).
Failure to follow these instructions will result in death or serious
injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ Application of analog test values to the measuring inputs must be in
compliance with the maximum permissible rating of the measuring inputs
(see Chapter “Technical Data”, Chapter 2).
Failure to follow these instructions will result in death or serious
injury.
Before the thermal overload protection can be tested the thermal replica must
always be cleared. Clearing the thermal replica is done by short term disabling of
the protection by setting M AIN: P rotecti on e nabled to No (= off) (Par/Func/
Glob menu branch). The actual status of the thermal replica may be read out
from the operating data display at TH ER M: Stat us therm .r eplica (Oper/Cycl/
Data menu branch). The tripping time may be checked:
With the thermal replica cleared an applied test current is abruptly changed from
0 to the value ≥ 0.1·Iref
I
(I )2 - Δϑ0
ref
t = τ · ln Θa - Θa,max
I
(I )2 - Δϑtrip · (1 - Θ )
ref max - Θa,max
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ Application of analog test values to the measuring inputs must be in
compliance with the maximum permissible rating of the measuring inputs
(see Chapter “Technical Data”, Chapter 2).
Failure to follow these instructions will result in death or serious
injury.
● The ASC function is not enabled. (This can be determined by checking logic
state signal A SC : En able d, (Oper/Cycl/Log menu branch.) This can have
the following causes:
o ASC : Gen eral en abl e USER (Par/Func/Gen menu branch) has been
set to No.
o ASC: E nabl e P Sx (Par/Func/PSx menu branch, depending on the
parameter subset) has been set to No.
o ASC is disabled via an appropriately configured binary signal input or a
setting parameter.
(This can be determined by checking logic state signal ASC: Ext ./use r
ena ble d, Oper/Cycl/Log menu branch.)
● A logic “1” signal is present at the binary signal inputs configured for
M AI N: M.c.b. t r ip V EXT.
● The ASC function will be blocked by triggering the binary signal input
configured for ASC: Blocki ng EXT.
The setting determines whether a close enable may be carried out in case of
blocking.
For test purposes, a close request can be generated for 500 ms using ASC: Te st
MC close r.USER the setting parameter (Oper/CtrlTest menu branch) or by
triggering an appropriately configured binary signal input (ASC: Test MC clo se
r. EX T). The check can only be carried out if there is no ARC cycle running. The
P438 checks whether enabling is permitted or not according to the set
conditions. If a positive decision is reached, then there is an ASC: Close
enabl e signal. No (re-)close command takes place! If the check determines that
enabling is not permitted, the signal A SC : C los e re je ction is issued.
A substation interlock is only effective when a communication link exists from the
communication interface to the substation control level. If the communication link
is disrupted then the device switches automatically to bay interlock (BI) without
substation interlock (SI). Whether or not a communication error is present can be
checked at M A I N : C o m m u n i c a t i o n e r r o r (Oper/Cycl/Log menu branch).
The substation interlock (SI) can be deactivated selectively for any switchgear unit
and in any control direction – “Open” or “Close”. (Check – e.g. for DEV01 – at
D E V 0 1 : O p e n w / o s t a t . i n t e r l or D E V 0 1 : C l o s e w / o s t a t . i n t . (Par/Func/
Cont menu branch).
11 Troubleshooting
This chapter describes problems that might be encountered, their causes, and
possible methods for eliminating them. It is intended as a general orientation
only, and in cases of doubt it is better to return the P438 to the manufacturer.
Please follow the packaging instructions in Section 5.1, (p. 5-4) when returning
equipment to the manufacturer.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ Only qualified personnel, trained, authorized and familiar with the device
and all the safety instructions in the general Safety Guide (SFTY/5LM/L11
or later version) and appropriate Chapter 5, Chapter 10, Chapter 11,
Chapter 12 and Chapter 13 of this manual, shall work on installation,
connection, commissioning, maintenance or servicing of this device.
⚫ Before checking further, disconnect the P438 from the power supply.
⚫ Switch off all the power supplies in connection to the equipment to isolate
the device.
Failure to follow these instructions will result in death or serious
injury.
WARNING
HAZARD OF EQUIPMENT DAMAGE
⚫ The local control panel (or front element) is connected to processor
module P by a plug-in connecting cable. Make sure the connector position
is correct. Do not bend the connecting cable!
Failure to follow these instructions can result in equipment damage
or unintended equipment operation.
Problem
● Lines of text are not displayed on the local control panel.
o Check to see whether there is supply voltage at the device connection
points.
o Check to see whether the magnitude of the auxiliary voltage is correct.
The P438 is protected against damage resulting from polarity reversal.
● The P438 issues an “Alarm” signal on LED H 3.
o Identify the specific problem by reading out the monitoring signal
memory (see Section 6.13.6.2, (p. 6-48)). The table below lists possible
monitoring or warning indication (provided that a configuration setting
has been entered at SFMON: Fct. ass ign. warning), the faulty area,
the P438's response, and the mode of the output relay configured for
“Warning” and “Blocked/faulty”.
Key
● –: No reaction and/or no output relay triggered.
● Yes: The corresponding output relay is triggered.
● Updating: The output relay configured for 'Warning' starts only if the
monitoring signal is still present.
Parameter Address
Parameter Address
[spacer]
The external input MAIN: C B1 faulty E XT or MAIN: CB2 faulty EXT
has become active.
Device reaction: –
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: W arning (LE D) 036 070
[spacer]
Warning configured for LED H3.
[spacer] SFMO N: W arning (re lay ) 036 100
[spacer]
Warning configured for an output relay.
[spacer] SFMO N: W arm re start e x ec. 041 202
[spacer]
A warm restart has been carried out.
[spacer] SFMO N: C old re star t exe c. 041 201
[spacer]
A cold restart has been carried out.
[spacer] SFMO N: C old re star t 093 024
[spacer]
A cold restart has been carried out on account of a checksum error in the
memory (NOVRAM).
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
[spacer] SFMO N: C old re st./ SW update 093 025
[spacer]
A cold restart has been carried out following a software update.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
[spacer] SFMO N: B lockin g /HW fail ure 090 019
[spacer]
Supplementary warning that this device is blocked.
“Warning” output relay: Updating
“Blocked/faulty” output relay: –
[spacer] SFMO N: R elay Kxx faulty 041 200
[spacer]
Multiple signal: output relay defective.
Device reaction: –
'Warning' output relay: Updating
'Blocked/faulty' output relay: Yes
Parameter Address
[spacer]
The hardware clock has failed.
Device reaction: –
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: B at te ry failure 090 010
[spacer]
Battery voltage too low. Replace battery.
Device reaction: –
“Warning” output relay: Updating
“Blocked/faulty” output relay: –
[spacer] SFMO N: I nvalid SW d.loade d 096 121
[spacer]
Wrong or invalid software has been downloaded.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
[spacer] SFMO N: +15V s upply faulty 093 081
[spacer]
The +15 V internal supply voltage has dropped below a minimum value.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
[spacer] SFMO N: +24V s upply faulty 093 082
[spacer]
The +24 V internal supply voltage has dropped below a minimum value.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
[spacer] SFMO N: - 15V s upply faulty 093 080
[spacer]
The −15 V internal supply voltage has dropped below a minimum value.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
[spacer] SFMO N: W rong m odule s lot 1 096 100
Parameter Address
[spacer]
Module in wrong slot.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
[spacer] SFMO N: W rong module D ig.Bus 096 123
[spacer]
The device has been fitted with a wrong digital bus. Since this is checked using
the module variant number this signal can also occur after a firmware upgrade
to a version that is not compatible with the hardware.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
[spacer] SFMO N: W rong module HM I 096 124
[spacer]
The device has been fitted with a wrong HMI. Since this is checked using the
module variant number this signal can also occur after a firmware upgrade to a
version that is not compatible with the hardware.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
Parameter Address
[spacer]
The device has been fitted with a wrong communication module. Since this is
checked using the module variant number this signal can also occur after a
firmware upgrade to a version that is not compatible with the hardware.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
[spacer] SFMO N: W rong m odule Ana. Bus 096 126
[spacer]
The device has been fitted with a wrong analog bus. Since this is checked using
the module variant number this signal can also occur after a firmware upgrade
to a version that is not compatible with the hardware.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
[spacer] SFMO N: D e fe ct.module slot 1 097 000
[spacer]
Defective module in slot x.
Device reaction: –
“Warning” output relay: Updating
“Blocked/faulty” output relay: –
Parameter Address
[spacer]
Dual-Port-RAM fault on communication module A. This fault is only detected
during device startup.
Device reaction: –
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: M odule A RAM fault y 093 071
[spacer]
RAM fault on communication module A.
Device reaction: –
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: M odule Y DP R fault y 093 110
[spacer]
The checksum feature of analog I/O module Y has detected a fault in the data
transmission of the Dual-Port-RAM.
Device reaction: –
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: M odule Y RAM fault y 093 111
[spacer]
Fault in the program or data memory of the analog I/O module.
Device reaction: –
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: I RIGB faulty 093 117
[spacer]
The IRIGB interface is enabled but there is no plausible input signal.
Device reaction: –
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: U nd ef . ope r at. code 093 010
[spacer]
Undefined operation code.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
Parameter Address
[spacer]
The application has been terminated in an unexpected way. If this error occurs
during a (re-)start of the device then this message is displayed and the device is
blocked.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
[spacer] SFMO N: B ad arg. s ys t em call 093 031
[spacer]
Invalid parameter when calling a function of the operating system. If this error
occurs during a (re-)start of the device then this message is displayed and the
device is blocked.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
[spacer] SFMO N: M ute x de adloc k 093 032
[spacer]
Software threads are locked from each other by mutex. If this error occurs
during a (re-)start of the device then this message is displayed and the device is
blocked.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
[spacer] SFMO N: I nvalid memory ref. 093 033
[spacer]
Attempt to access an invalid memory segment. If this error occurs during a
(re-)start of the device then this message is displayed and the device is blocked.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
[spacer] SFMO N: U ne xpe ct e d e xc ept ion 093 034
[spacer]
Miscellaneous error message from the processor or operating system. If this
error occurs during a (re-)start of the device then this message is displayed and
the device is blocked.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
Parameter Address
[spacer]
Invalid arithmetic operation.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
[spacer] SFMO N: U nd ef ined i nter rupt 093 012
[spacer]
Undefined interrupt.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
[spacer] SFMO N: E x ce pt ion oper .s ys t . 093 013
[spacer]
Interrupt of the operating system.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
[spacer] SFMO N: Pr ote ction f ailure 090 021
[spacer]
Watchdog is monitoring the periodic start of protection routines. It has detected
an error.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
[spacer] SFMO N: C he ck s um error param 090 003
[spacer]
A checksum error involving the parameters in the memory (NOVRAM) has been
detected.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
[spacer] SFMO N: C lock sync. e rror 093 041
[spacer]
In 10 consecutive clock synchronization telegrams, the difference between the
time of day given in the telegram and that of the hardware clock is greater than
10 ms.
Device reaction: –
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
Parameter Address
[spacer]
Faulty test pattern in the RAM. This can occur, for example, if the processor
module or the power supply module is removed from the bus module (digital).
This fault is only detected during device startup. After the fault is detected, the
software initializes the RAM. This means that all records are deleted.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
[spacer] SFMO N: O ve rflow MT_RC 090 012
[spacer]
Last entry in the monitoring signal memory in the event of overflow.
Device reaction: –
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: C he ck s um DM OD 093 023
[spacer]
A checksum that was calculated from the data model in the memory of the
device yielded a wrong result. If this error occurs during a (re-)start of the device
then this message is displayed and the device is blocked.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
[spacer] SFMO N: S em aph. M T_RC block . 093 015
[spacer]
Software overloaded.
Device reaction: –
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: I nvalid type of bay 096 122
[spacer]
If the user has selected a bay type that requires a P438 hardware configuration
that is not actually fitted, then this signal is generated.
1st device reaction: Warm restart
2nd device reaction: Device blocking
“Warning” output relay: Yes
“Blocked/faulty” output relay: Yes
[spacer] SFMO N: I nval. S W ve r s .C OMM1 093 075
[spacer]
Incorrect or invalid communication software has been downloaded.
Device reaction: –
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
Parameter Address
[spacer]
Invalid parameters in the IEC configuration.
Device reaction: –
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: I nvalid SW ver s. Y 093 113
[spacer]
Incorrect or invalid software for analog I/O module Y has been downloaded.
Device reaction: –
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: I nom not adjust able 093 118
[spacer]
Transformer module T is not suitable for setting Inom.
Device reaction: –
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: T im e -out module Y 093 112
[spacer]
Watchdog is monitoring the periodic status signal of the analog I/O module Y. It
has detected an error.
Device reaction: –
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: M .c.b. trip Vref 098 011
[spacer]
The m.c.b. monitoring the reference voltage transformer has tripped.
Device reaction: Blocking of automatic synchronism check (ASC).
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: M .c.b. trip V 098 000
[spacer]
The line-side voltage transformer m.c.b. has tripped.
Device reaction: Blocking of the short-circuit direction determination.
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: W rong s et. DIST Rg1 098 046
Parameter Address
[spacer]
The set value Rg is too high and no closed tripping characteristic can be
determined.
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: W rong s et. DIST X/ R 097 023
[spacer]
There is a mismatch on the combination of the setting parameters DIS T: X
parameter avail., DIST: Z par ame ter avail. and DIS T: X
parameter us ed.
Note: The parameter DIS T: X parame te r use d enables the usage of X
values as setting parameter for the polygon characteristic instead of Z values. It
shall be set to "yes" only, if the parameter DIST : X parameter avail. is
set to "yes" and DIST : Z par ame ter av ail . is set to "No".
[spacer] SFMO N: U nd er volt age 098 009
[spacer]
The measuring-circuit monitoring function has detected an undervoltage.
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: F F, V trigge r ed 098 021
[spacer]
The fuse failure monitoring function has detected a fault in the voltage-
measuring circuit.
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: M .circ. V,Vref fl ty. 098 023
[spacer]
Multiple signal: Voltage-measuring circuits for phase-to-ground voltages or the
reference voltage faulty.
Device reaction: Depends on type of fault.
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: M eas . cir c. V f aul ty 098 017
[spacer]
Multiple signal: Voltage-measuring circuits faulty.
Device reaction: Depends on type of fault.
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: M .circ. Vre f fault y 098 255
[spacer]
The voltage-measuring circuits for the reference voltage are faulty.
Device reaction: Selective blocking of the neutral-point displacement voltage
monitor in function groups V<> and LIMIT as well as blocking of ASC.
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
Parameter Address
[spacer]
The amplitude matching factor of the defrost protection is invalid.
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: M atch.fct.I M CMONinv 098 059
[spacer]
The amplitude matching factor of the current measuring circuit monitoring is
invalid.
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: M eas . cir c. I fault y 098 005
[spacer]
The measuring-circuit monitoring function has detected a fault in the current-
measuring circuits.
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: M eas .circ .V,I fault y 098 016
[spacer]
Multiple signal: Multiple signaling: Current- or voltage-measuring circuits faulty.
Device reaction: Depends on type of fault.
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: C ommunic.fault C OMM 3 093 140
[spacer]
The set time C OMM3: T ime -out comm.faul t has elapsed since the most
recent 100% valid telegram was received. The receive signals are set to their
user-defined default values.
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: Hardware e r ror COM M3 093 143
[spacer]
The device has detected a hardware error in the effective connection
InterMiCOM (communication interface 3).
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: I nvalid SW ver s DHMI 093 145
[spacer]
Incorrect or invalid software was loaded to operate the detachable display
(DHMI).
Device reaction: –
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
Parameter Address
[spacer]
Measurement of the coolant temperature via the analog module is faulty.
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: C omm.link fail.C OMM3 093 142
[spacer]
Timer stage COM M3: T ime -out link fail . has elapsed indicating a
persistent failure of the transmission channel. The receive signals are set to
their user-defined default values.
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: L im .e x ce ed.,t e l.e r r. 093 141
[spacer]
The threshold set for timer stage COMM3: Limit telegr. e rrors was
exceeded and the receive signals are set to their user-defined default values.
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: T elecom. faulty / PSI G 098 006
[spacer]
The transmission channel of protective signaling is faulty.
Device reaction: Blocking of protective signaling.
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: S etting e rror THE RM 098 035
[spacer]
Invalid parameters in the setting for the thermal replica.
Device reaction: Blocking of thermal overload protection.
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: W rong S ett ing F .loc 098 200
[spacer]
Signal indicating that the line sections have been incorrectly set for the
calculation of fault location.
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: S etting e rror CB M 098 020
[spacer]
An invalid characteristic has been set for circuit breaker monitoring.
Device reaction: Depends on type of fault.
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
Parameter Address
[spacer]
The maximum number of CB operations performed has been exceeded.
Device reaction: Depends on type of fault.
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: C B rem. No. C B op. < 098 067
[spacer]
The minimum number of CB operations performed at nominal current has fallen
below the threshold.
Device reaction: Depends on type of fault.
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: C B ΣItrip > 098 068
[spacer]
The maximum sum of disconnection current values has been exceeded.
Device reaction: Depends on type of fault.
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: C B ΣItrip**2 > 098 069
[spacer]
The maximum sum of the disconnection current values to the second power has
been exceeded.
Device reaction: Depends on type of fault.
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: I nvalid scali ng BCD 093 124
[spacer]
An invalid characteristic has been set for the BCD output channel of analog I/O
module Y.
Device reaction: Depends on type of fault detected.
“Warning” output relay: Updating
“Blocked/faulty” output relay: –
[spacer] SFMO N: C B tm ax> A 098 070
[spacer]
The maximum duration for the opening of a CB pole has been exceeded.
Disconnection is not determined for this CB pole.
Device reaction: Depends on type of fault.
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
[spacer] SFMO N: I nvalid scali ng A-1 093 114
Parameter Address
[spacer]
An invalid characteristic has been set for one of the analog output channels of
analog I/O module Y.
Device reaction: Depends on type of fault detected.
“Warning” output relay: Updating
“Blocked/faulty” output relay: –
[spacer] SFMO N: I nvalid scali ng IDC 093 116
[spacer]
An invalid characteristic has been set for the analog input channel of analog I/O
module Y.
Device reaction: Depends on type of fault detected.
“Warning” output relay: Updating
“Blocked/faulty” output relay: –
[spacer] SFMO N: PT 100 open c ir cuit 098 024
[spacer]
The P438 has detected an open circuit in the connection of the resistance
thermometer “PT100” to the analog I/O module Y.
Device reaction: Depends on type of fault detected.
“Warning” output relay: Updating
“Blocked/faulty” output relay: –
[spacer] SFMO N: O ve rload 20 mA input 098 025
[spacer]
The 20 mA input of analog I/O module Y is overloaded.
Device reaction: Depends on type of fault detected.
“Warning” output relay: Updating
“Blocked/faulty” output relay: –
[spacer] SFMO N: O pe n circ. 20 mA inp. 098 026
[spacer]
The P438 has detected an open circuit in the connection of the 20 mA input.
Device reaction: Depends on type of fault detected.
“Warning” output relay: Updating
“Blocked/faulty” output relay: –
[spacer] SFMO N: S etting e rror f<> 098 028
[spacer]
The over-/underfrequency protection function has been set for “overfrequency”
monitoring (based on the settings for operate value and nominal frequency).
This setting is not valid in the f w. Delta f/Delta t operating mode.
Device reaction: Blocking of the over-/under frequency protection function
“Warning” output relay: Updating
“Blocked/faulty” output relay: –
Parameter Address
[spacer]
The function was configured to a binary signal input on the analog I/O module Y.
Such a configuration is not permitted for this function.
Device reaction: –
“Warning” output relay: Updating
“Blocked/faulty” output relay: –
[spacer] SFMO N: O utput 30 098 053
[spacer]
These LOGIC outputs can be included in the list of warning signals by selection
at S FMON: Fct. ass ign. warning. The warning signals are also recorded
in the monitoring signal memory.
“Warning” output relay: Yes
“Blocked/faulty” output relay: –
12 Maintenance
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ Only qualified personnel, trained, authorized and familiar with the device
and all the safety instructions in the general Safety Guide (SFTY/5LM/L11
or later version) and appropriate Chapter5, Chapter 10, Chapter 11,
Chapter 12 and Chapter 13 of this manual, shall work on installation,
connection, commissioning, maintenance or servicing of this device.
Failure to follow these instructions will result in death or serious
injury.
The P438 is a low-maintenance device. The components used in the units are
selected to meet exacting requirements. Recalibration is not necessary.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ Always disconnect the device from the auxiliary power supply, before
removing any hardware module.
⚫ Switch off all the power supplies in connection to the equipment to isolate
the device, before removing any hardware module.
Failure to follow these instructions will result in death or serious
injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ The power supply must be turned off for at least 5 s before power supply
module V is removed. Otherwise there is the danger of an electric shock.
Failure to follow these instructions will result in death or serious
injury.
WARNING
HAZARD OF EQUIPMENT DAMAGE
⚫ The local control panel (or front element) is connected to processor
module P by a plug-in connecting cable. Make sure the connector position
is correct. Do not bend the connecting cable!
Failure to follow these instructions can result in equipment damage
or unintended equipment operation.
In general, the electronic components used for the device family Easergy MiCOM
30 are designed for a long service life.
For the power supply, however, dimensioning requirements dictate the use of
electrolytic capacitors that are subject to increased wear and tear. The useful life
of these capacitors depends on their temperature and thus on the components
fitted in the device, the load conditions, device location and environmental
conditions.
The internal voltage levels are cyclically checked by the P30 self-monitoring
functions. In case the voltage levels deviate from their specified values a warning
message will be issued or, for persistent problems, the device will be set to a
safe condition (blocking). Hence, there is no imperative need to replace the
power supply module after a pre-defined period of time. However, should you
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
⚫ Before starting the test, open any triggering circuits for external devices so
that no inadvertent switching operations will take place.
Failure to follow these instructions will result in death or serious
injury.
13 Storage
Devices must be stored in a dry and clean environment. A temperature range of
-25°C to +70°C (-13°F to +158°F) must be maintained during storage (see
chapter entitled “Technical Data”). The relative humidity must be controlled so
that neither condensation nor ice formation will result.
If the units are stored without being connected to auxiliary voltage, then the
electrolytic capacitors in the power supply area need to be recharged every
4 years. Recharge the capacitors by connecting auxiliary voltage to the P438 for
approximately 10 minutes.
If the units are stored during a longer time, the battery of the power supply
module is used for the continuous buffering of the event data in the working
memory of the processor module. Therefore the battery is permanently required
and discharges over time. In order to avoid this continuous discharge, it is
recommended to remove the power supply module from the mounting rack
during long storage periods. The contents of the event memory should be
previously read out and stored separately!
WARNING
HAZARD OF EQUIPMENT DAMAGE OR LIFETIME REDUCTION
⚫ Do not sustain exposure to high humidity during storage, the value shall
not exceed 75% relative humidity.
⚫ Once the device has been unpacked, it is recommended to energize it
within the three following months.
⚫ The device has to be energized at least once in 4 years, if it is not in
permanent operation.
⚫ Where electrical equipment is being installed, sufficient time should be
allowed for acclimatization to the ambient temperature of the environment
before energization.
Failure to follow these instructions can result in equipment damage,
unintended equipment operation or reduction of equipment lifetime.
84 TE frame 88512‑4‑9650723‑301
15 Order Information
Basic Configuration Variants
Rail catenary protection device P438- 0 2 -311 -4xx -661 -46x -9x x -9x x -8xx
Basic device:
Basic device 40TE, CT/VT ring-, I/O pin-terminal connection, 5 -418
Basic device 84TE, pin-terminal connection, 7 -419
Basic device 84TE, ring-terminal connection, 8 -420
basic complement with 4 binary inputs, 8 output relays
and 6 function keys
26)
Additional binary I/O options:
Without 0
With 1 binary module (add. 6 binary inputs and 8 output relays) 1
With 2 binary modules (add. 12 binary inputs and 16 output relays) 2
5)
With 3 binary modules (add. 18 binary inputs and 24 output relays) 3
5) 29)
With 4 binary modules (add. 24 binary inputs and 32 output relays) 4
With 1 binary module (add. 6 binary inputs and 6 output relays (2-pole)) 5
for the control of up to 3 additional switchgear units
15)
With 2 binary module (add. 12 binary inputs and 12 output relays (2-pole)) 6
for the control of up to 6 additional switchgear units
With 1 binary module (add. 6 binary inputs and 6 output relays (2-pole)) 8
for the control of up to 3 switchgear units
and 1 binary module (add. 6 binary inputs and 8 output relays)
With 2 binary modules (add. 12 binary inputs and 12 output relays (2-pole))
5) 15)
9
for the control of up to 6 switchgear units
and 1 binary module (add. 6 binary inputs and 8 output relays)
With 2 binary modules (add. 12 binary inputs and 12 output relays (2-pole))
5) 15) 29)
A
for the control of up to 6 switchgear units
and 2 binary modules (add. 12 binary inputs and 16 output relays)
5)
With 1 binary module (add. 6 binary inputs and 6 output relays (2-pole)) B
for the control of up to 3 switchgear units
and 2 binary modules (add. 12 binary inputs and 16 output relays)
5) 29)
With 1 binary module (add. 6 binary inputs and 6 output relays (2-pole)) C
for the control of up to 3 switchgear units
and 3 binary modules (add. 18 binary inputs and 24 output relays)
Further Options
Rail catenary protection device P438- 0 2 -311 -4xx -661 -46x -9x x -9x x -8xx
Communication Options
Rail catenary protection device P438- 0 2 -311 -4xx -661 -46x -9x x -9x x -8xx
Language:
4)
English (German) Without order extension No.
4)
Px40 English (English) -800
4)
German (English) -801
4)
French (English) -802
4)
Spanish (English) Not yet available - on request -803
Key
2) Switching via parameter, default setting is underlined!
3) This option is excluded in 40 TE if the InterMiCOM interface (‑95x) is ordered.
4) Second included language in brackets.
5) For 84TE version only.
8) Standard variant recommended if higher pickup threshold not explicitly required
by the application.
13) Graphic display with minimum of one binary module (6 binary inputs and 6
output relays) only.
15) Option with graphic display only.
24) Analog module on Slot 3 and add. 24 binary module on Slot 8.
25) Only for datamodel <660 with IEC 61850 Edition 1, no Cyber Security
compatibility.
26) Maximum 2 binary input/ output boards for 40TE version and max 4 for 84TE
version in total.
27) BI6 BO6 for 84TE version on slot 12+14.
28) According BDEW / NERC / IEEE 1686.
29) This option is excluded when BI24 is ordered
A1 Function Groups
CS Cyber Security
DVICE Device
PC PC link
SFMON Self-monitoring
A2 Internal Signals
A3 Glossary
Modules
A: Communication module
L: MMI module
P: Processor module
T: Transformer module
Symbols
Symbol Description
Components of a symbol
A symbol consists of a contour or contour combination and one or
more qualifiers.
Control block
A control block contains an input function common to several
symbols. It is used for the collective setting of several trigger
elements, for example.
D5Z08X3B
Output block
An output block contains an output function common to several
symbols.
D5Z08X4B
1.0: 1.0 A
meaning to each setting.
5.0: 5.0 A
D5Z08X6B
Static input
Only the state of the binary input variable is effective.
D5Z08XBB
Dynamic input
Only the transition from value 0 to value 1 is effective.
D5Z08XAB
Negation of an output
The value up to the border line is negated at the output.
D5Z08X8B
Negation of an input
The input value is negated before the border line.
D5Z08X7B
D5Z08X9B
AND element
& The output variable will be 1 only if all input variables are 1.
D5Z08XCB
OR element
The output variable will be 1 only if at least one input variable is
D5Z08XDB
1.
Threshold element
The output variable will be 1 only if at least two input variables
D5Z08XEB
are 1. The number in the symbol may be replaced by any other
number.
(m out of n) element
The output variable will be 1 only if just one input variable is 1.
D5Z08XFB The number in the symbol may be replaced by any other number
if the number of inputs is increased or decreased accordingly.
Delay element
t1 t2
The transition from value 0 to 1 at the output occurs after a time
D5Z08XGB
delay of t1 relative to the corresponding transition at the input.
The transition from value 1 to 0 at the output occurs after a time
delay of t2 relative to the corresponding transition at the input.
t1 and t2 may be replaced by the actual delay values (in seconds
or strobe ticks).
Monostable flip-flop
1 The output variable will be 1 only if the input variable changes to
100ms
D5Z08XHB
1. The output variable will remain 1 for 100 ms, regardless of the
duration of the input value 1 (non-retriggerable).
Without a 1 in the function block, the monostable flip-flop is
retriggerable.
The time is 100 ms in this example, but it may be changed to any
other duration.
Analog-digital converter
An analog input signal is converted to a binary signal.
D5Z08XJB
Subtractor
The output variable is the difference between the two input
D5Z08XKB
variables.
A summing element is obtained by changing the minus sign to
a plus sign at the symbol input.
Memory, general
Storage of a binary or analog signal.
D5Z08XMB
Non-stable flip-flop
When the input variable changes to 1, a pulse sequence is
D5Z08XNB
generated at the output.
The ! to the left of the G indicates that the pulse sequence starts
with the input variable transition (synchronized start).
If there is a ! to the right of the G, the pulse sequence ends with
the ending of the 1 signal at the input (synchronized stop).
Amplifier
The output variable is 1 only if the input variable is also 1.
D5Z08XOB
Counter
+
At the + input the input variable transitions from 0 to 1 are
R
D5Z08YFB
counted and stored in the function block.
At the R(eset) input a transition of the input variable from 0 to 1
resets the counter to 0.
D5Z08YGB
V1
with electrical isolation between input and output.
L-
D5Z08XQB L+ = pos. voltage input
L− = neg. voltage input
U1 = device identifier
D5Z08XRB
Phase identifiers for current inputs:
● for A: A1 and A2
● for B: B1 and B2
● for C: C1 and C2
● for N: N1 and N2
Item identifiers
● for current transformers:
o for A: T1
o for B: T2
o for C: T3
o for N: T4
● for voltage transformer 1:
o for A: T5
o for B: T6
o for C: T7
o for N: T8
● for VG-N transformer: T90
● for voltage transformer 2:
o for A: T15
Change-over contact
with item identifier
D5Z08XSB
Special symbol
Output relay in normally-energized arrangement (“closed-circuit
D5Z08XTB
operation”).
PC interface
with pin connections
−12V 9
+12V 1
0V 5
RXD 3
V24
TXD 2
D5Z08XVB
Multiplier
The output variable is the result of the multiplication of the two
D5Z08XWB
input variables.
Divider
The output variable is the result of the division of the two input
D5Z08XXB
variables.
Comparator
The output variable becomes 1 only if the input variable(s) are
equal to the function in the function block.
D5Z08XYB
Formula block
The output variable becomes 1 only if the input variable(s) satisfy
2.5
the equation in the function block
D5Z08XZB
Symbols Used
Symbol Meaning
t Time duration
V̲ Complex voltage
I Electrical current
I̲ Complex current
Z̲ Complex impedance
f Frequency
δ Temperature in °C
Σ Sum, result
α Angle
τ Time constant
ΔT Temperature difference in K
A4 Telecontrol Interfaces
A4.1.1 Interoperability
This application-based standard (companion standard) specifies parameter sets
and other options from which subsets are to be selected in order to implement
specific telecontrol systems. Certain parameters such as the number of bytes
(octets) in the COMMON ADDRESS of the ASDU are mutually exclusive. This
means that only one value of the defined parameter is allowed per system. Other
parameters, such as the listed set of different process information in the
command and monitor direction, permit definition of the total number or of
subsets that are suitable for the given application. This section combines the
parameters given in the previous sections in order to facilitate an appropriate
selection for a specific application. If a system is made up of several system
components supplied by different manufacturers, then it is necessary for all
partners to agree on the selected parameters.
The boxes for the selected parameters should be checked [see National Preface
of EN 60870-5-101].
The overall definition of a system may also require individual selection of certain
parameters for specific parts of a system such as individual selection of scaling
factors for individually addressable measured values.
[✓] Structured
[✓] Unstructured
Frame Length
[✓] <10> = Measured value, normalized value with time tag M_ME_TA_1
[✓] <12> = Measured value, scaled value with time tag M_ME_TB_1
[ ] <14> = Measured value, short floating point value with time tag M_ME_TC_1
[✓] <18> = Packed start events of protection equipment with time ME_EP_TB_1
tag
[ ] <50> = Set point command, short floating point value C_SE_NC_1
[ ] <112> = Parameter of measured value, short floating point value P_ME_NC_1
[ ] <122> = Call directory, select file, call file, call section F_SC_NA_1
[✓] Global
[ ] Direct set point command [ ] Select and execute set point
transmission command
[ ] Short pulse duration (Execution duration determined by a system parameter in the
outstation)
[ ] Long pulse duration (Execution duration determined by a system parameter in the
outstation)
A4.2.1 Interoperability
Note: EIA RS 485 defines the loads in such a way that 32 of such loads can be
operated on one line. For detailed information see EIA RS 485, Section 3.
INF Description
[✓] <19> LED reset (021 010) MA IN: Res et in dicat. USER
[✓] <20> Blocking of monitor direction (037 075) C OMM1 : Si g./meas .val. blo ck.
[✓] <32> Measurand supervision I (040 087) MCMON: Mea s. circ. I faulty
[✓] <33> Measurand supervision V (038 023) MCMON: Mea s. circ. V fault y
[✓] <36> Trip circuit supervision (041 200) SFMON: Rel ay K xx faulty
(The message content is
formed from the OR operation
of the individual signals.)
[✓] <38> VT fuse failure (004 061) MA IN: M.c. b. trip V EXT
[✓] <39> Teleprotection disturbed (036 060) P SI G1: Tel e com. faulty
[✓] <47> Group alarm (004 065) MA IN: Blocke d/f aul ty
[✓] <68> General trip (036 251) MA IN: Gen . tri p si gnal
[✓] <72> Trip I>> (back-up operation) (036 014) BUOC : Tri p s ignal I >
[✓] <73> Fault location X in ohms (004 029) F T_DA : F aul t re actan ce ,pri m
[✓] <74> Fault forward/line (036 018) MA IN: Faul t for ward
[] <82> Zone 5
[] <83> Zone 6
[✓] <84> General starting (036 000) MA IN: Gen eral startin g
[] <144> Measurand I
[] <145> Measurands I, V
[] <146> Measurands I, V, P, Q
INF Description
INF Description
[✓] <19> LED reset (021 010) MA IN: Res et in dicat. U SER
[✓] <23> Activate characteristic 1 (003 060) P SS: Param .s u bs. se l. USER
(Switches
PSS: Pa ram.su bs. se l .
USE R to Parameter subset
1.)
[✓] <24> Activate characteristic 2 (003 060) P SS: Param .s u bs. se l. USER
(Switches
PSS: Pa ram.su bs. se l .
USE R to Parameter subset
2.)
[✓] <25> Activate characteristic 3 (003 060) P SS: Param .s u bs. se l. USER
(Switches
PSS: Pa ram.su bs. se l .
USE R to Parameter subset
3.)
[✓] <26> Activate characteristic 4 (003 060) P SS: Param .s u bs. se l. USER
(Switches
PSS: Pa ram.su bs. se l .
USE R to Parameter subset
4.)
INF Description
A4.2.1.3.6 Miscellaneous
Measured values are transmitted both with ASDU 3 and ASDU 9. As defined in
Sec. 7.2.6.8, the maximum MVAL can be either 1.2 or 2.4 times the rated value.
In ASDU 3 and ASDU 9, different ratings may not be used; in other words, there is
only one choice for each measurand.
1.2 or 2.4
A5 Version History
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
FT_DA The calculation of the short circuit impedance and reactance and of the fault
location is now also carried out correctly for In = 5 A.
C&VTS Fuse failure monitoring has been accelerated so that unwanted distance
protection operation can also be prevented when the load current has exceeded
the low-end threshold I> of the distance measuring system.
The default set value of the enabling threshold (C&VTS: V< VTS/F use Fail
SGx) has been increased to 0.65 Vn.
The (038 023) C&VTS: VTS V olts Failure signal is issued when the M.C.B.
trip of the binary input is triggered, even if C&VTS is disabled or not enabled in
the active setting group.
NOT When the current threshold is exceeded the start of the timer stages only takes
place after the enabling of the backup overcurrent-time protection.
SOTF Processing of the function in the 'trip with start' operating mode has been
optimized so that shorter typical tripping times, < 45 ms, are obtained.
DTOC The time tagging of the signals resulting from instantaneous high-current
tripping has been improved. This concerns the following signals:
● (035 022) DTOC: St art ing I>H
● (040 076) D TO C: Tr ip Si gn al tI>H
● (036 000) MA IN: Gen eral Start
● (036 251) MA IN: Gen Tri p Signal
● (039 101) MA IN: Main-Tri p Signal
● (039 011) MA IN: Mai n-Trip Comman d
The reset mode has been improved so that reset times represent a maximum of
one cycle (measured in the event of a current decrease from double the operate
value to 0).
DFRST The setting range of operate values DIF_X: Id> SGx has been extended to
0.01...1.00 In.
THERM The function's competition problem at start-up initialization has been corrected.
The incorrectly issued (039 110) TH ER M: Sett in g Error,Block. alarm is no
longer displayed.
LOGIC Signals LOGIC : Re se t 6 EXT and LOGIC: Re se t 8 EXT are now available in
the selection table for the configuration of the binary inputs.
Hardware
No changes.
Diagram
No changes.
Software
C&VTS The minimum current enabling threshold of the undervoltage and fuse failure
monitoring has been unified to 0.05 In.
The current discontinuity recognition now operates even when the current
decreases.
A detected fuse failure condition is only reset if the measured voltage exceeds
the C&VTS: V > VTS/Fu se Fai l SGx threshold and if simultaneously a
minimum current of 0.05 In flows.
THERM The competition problem of the function in the start-up initialization has been
corrected. The incorrectly issued alarm (039 110) THER M: Set tin g
Error,Block . is no longer displayed.
Hardware
No changes.
Diagram
No changes.
Software
THERM The dead time for very fast alterations of the coolant temperature has been
extended to 1.5 s in order to correct competition problems with measuring-
circuit monitoring of the analog module (for example the (040 190) RTDmA:
PT100 F aulty signal was not always issued in time in order to exclude an
unwanted operation).
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
OP_RC The list of the following entries has been modified as follows.
Those added:
● (038 073) THERM: 2 P L Se l ect. Exte r n.
● (040 145) LIMIT: tV>> & tV << Elaps ed
● (040 197) LI MIT: tf>> Elaps ed
● (004 062) L I MI T: tI>> Elaps ed
Those removed:
● (039 076) MA IN: Powe r Fl ow Forward
● (039 077)MAIN: P ower Flow Re ve rs e
● (041 085) D I ST: Wrong Se ttin g R g,x
● (040 170) L IMIT: Star ting T>
● (040 171) LIMIT: Startin g T>>
● (040 174)LIMI T: Star ting T<
● (040 175) LI MIT: Start in g T<<
● (040 180) L IMIT: Star ting I DC,l in>
● (040 181)LIMI T: Star ting ID C,li n>>
● ( 040 184) LIMIT: Startin g IDC ,l i n<
● (040 185) LIMI T: Start ing IDC, lin <<
Thus the LIMIT stages do not enter starting signals, but only the signal “timer
stage elapsed”.
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
RTDmA Open-circuit monitoring of the 20 mA input and the “PT 100” input has been
improved. The plausibility check of displayed measured variables was extended.
THERM The plausibility check of the “PT 100” measurement was cancelled and now
occurs exclusively in function group RTDmA.
Hardware
No changes.
Diagram
No changes.
Software
MAIN An inrush detection function, operating with the second harmonic of the phase
current, has been added in order to prevent unwanted tripping signals issued by
the catenary protection device when autotransformers are switched on or circuit
breakers on locomotives are closed. Blocking of each protection function may be
set individually, when an inrush occurrence is detected.
C&VTS The minimum current enable thresholds for undervoltage protection and fuse
failure monitoring are now set via mutual parameters at (014 188) C& VTS: I>
E nab V< FuseF S Gx. External blocking of undervoltage protection and fuse
failure monitoring have been added. Minimum hold-time for fuse failure
monitoring is now set at 125 ms (previously 250 ms).
Hardware
No changes.
Diagram
No changes.
Software
COMM1(2) The new communication software version 3.17 has been introduced. With this
version the intermittent interruptions of telegrams during communication per
IEC 60870-5-101 protocol no longer occur.
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
MAIN The close command to the circuit breaker may now be generated from the front
panel user interface (HMI) or via binary signal inputs as well as through auto-
reclose control (RECLS).
It is now possible to select whether the close command is to be terminated by
the 'Closed' position status signal by setting (015 042) MAIN: ClC md Inhib. by
CB C l.
The binary input function (044 131) MAIN: CB Tri p EXT has been
implemented.
CHECK A number of device bugs previously led to a blocking with the second entry to
the monitoring signal memory (i.e. if the recurring fault was already stored in
the monitoring signal memory – see Chapter 10 in the Technical Manual). This
reaction was changed in such a manner that device blocking will only occur if a
renewed appearance of the same device fault lies within a set "memory
retention time" (021 018 C H EC K: Mon .Sig. Re tention). This makes it
possible to tolerate sporadic faults, resulting from control actions, without
having to clear the monitoring signal memory in the interim.
The significance of the time stamp was modified to accommodate this new
feature. The time stamp now represents the last appearance of the fault.
DIST Factors for the zone extension function D IST: kze E xt ende d HSR SGx and
DI ST: kze Ex tended TDR SGx are now only applied in conjunction with auto-
reclose control RECLS.
Setting D I ST: kze SO TF /EXT SGx was introduced in order to enable zone
extension via a binary signal input (036 046 DIST: Zon e E xt e ns ion EXT) or
the switch on to fault protection (SOTF) function.
SOTF This function may now be blocked by a binary signal input, SOTF: Blocking
E XT.
Additionally a blocking signal is sent to auto-recloser (RECLS) during the manual
close time period.
RECLS Auto-reclose control, function group RECLS, has been implemented. It is now
possible to have automatic reclosures consisting of one highspeed reclosure and
up to 9 time-delayed reclosures.
For each tripping function the RECLS function range allows the selection that the
type of fault will permit reclosure or not. Moreover it is possible to block the
function for high current faults.
THERM All parameters associated with coolant temperature acquisition are hidden if
analog module Y has not been fitted to the device. The function operates with a
default coolant temperature.
The further operation may now be selected when there is a CTA failure. (076
177) THER M: Funct .f.CTA Fai l.SGx
A minimum coolant temperature may be set for the power feed of catenary
sections situated in long tunnels: (076 178) TH ERM: Min im um
Temperat.SGx
The following parameter has been deleted: (072 178) THER M: Blk for CTA
Fail SGx
CBM Circuit breaker monitoring, function group CBM, has been implemented. The
permitted remaining number of CB operations at nominal current is calculated
and presented phase selectively and within the framework of CB state
evaluation according to the settable circuit breaker wear characteristic.
The disconnection currents (ruptured current, and also its square) and the
current-time area integrals for each disconnection are phaseselectively
evaluated and accumulated.
mA_OP The listing of possible entries for the analog measured data output with either
BCD or 20 mA (outputs A-1 & A-2) has been extended.
Hardware
The device’s case size 40TE has been released.
Binary signal inputs with a higher switching threshold are now available.
Installation is only recommended if the application specifically requires such
binary signal inputs.
Diagram
The new terminal connection diagram is now available for device variant 40TE.
Designation texts for binary signal inputs and output relays have been changed
to comply to the Px3x standard, i.e. a designation is now made up out of the slot
number (1 or 2 digits) and a listing number (2 digits). Example: K2001 instead of
K201 (= first output relay at slot number 20).
These new connection diagrams are now valid:
● P438.403 (for 40TE case, transformer module: ring-terminal connection
other modules: pin-terminal connection)
● P438.404 (for 84TE case, with pin-terminal connection)
● P438.405 (for 84TE case, with ring-terminal connection)
Software
CBM Two independent correction values are now available in order to determine the
trip time. Timing tolerances caused by leading or lagging auxiliary contacts on
the CB may now be compensated by applying parameter (022 018) C BM: C orr .
Acqu.T.CB Sig. A time-delay between the internal forming of the trip
command and the actual opening of the CB contacts may now be set at (022
153) CBM: C orr. A cqu. T. Tri p.
LIMIT The new (041 043) L I MIT: Not R eady signal now indicates that the function
has been globally enabled but that it has not been enabled in the active setting
group itself. This new multiple signal is transmitted using the IEC 60870-5-103
communication protocol as follows:
● Type: 8A, Inf: 3D
● ASDU: 1, GA: Yes
Hardware
No changes.
Diagram
No changes.
Software
MAIN The primary source for date and time synchronization may now be selected.
Available are COMM1, COMM2/PC, IRIG-B or a binary input for minute signal
pulses. Available are COMM1, COMM2/PC, IRIG-B or a binary input for minute
signal pulses. Additionally a back-up source can now be selected.
● (103 210) MA IN: P ri m.Source Time Sync
● (103 211) MAIN: BackupSou rce Time Sync
COMM2/PC With the new setting (103 203) C OMM2 : Pos iti ve Ackn. F ault it is possible
to set whether or not faults can be acknowledged positively after transmission
(and consequently deleted from the fault overview at the COMM2/PC interface).
Hardware
For all model versions there is now a variant available that features an optional
extended detachable, serially-connected, HMI and provides the following new
functions:
● 6 freely configurable function keys as well as 6 freely configurable LED
indicators (H 18 to H 23) each situated next to a function key.
● The freely configurable LED indicators (H 4 to H 16 and H 18 to H 23) are
provided as multi-color LEDs.
To disconnect inductive loads there is a module available with 4 heavyduty
contacts fitted to slot 10 on the 40TE case or slot 18 on the 84TE case devices.
The new Ethernet communications module for communication per IEC 61850 is
now available and may be fitted to slot 2 as an alternative to communication
module A. For the optical interface (100 Mbit/s) on the Ethernet communications
module the user may either select the ordering option ST connector or SC
connector.
Diagram
The updated terminal connection diagrams include the wiring configuration for
the new heavy-duty binary I/O module as well as the new Ethernet
communications module.
The following numbers have been generated for the new terminal connection
diagrams:
● P438.406 (for 40TE case, pin-terminal connection)
● P438.407 (for 84TE case, pin-terminal connection)
● P438.408 (for 84TE case, ring-terminal connection)
Software
DEVICE As the new detachable serial HMI is now available, the following parameters
have been added:
● (002 131) D VIC E: SW Ve rsi on DH MI
● (002 132) DV IC E: SW V ers ion DHMI D M
The order numbers:
● (001 000) DVI CE: A FS Order No.
● (001 200) D VI C E: P CS Orde r No.
may now be entered as an alphanumeric variable containing up to 20
characters.
LED The new detachable, serially-connected, HMI provides the following extended
display functions:
● The operating mode for the LED indicators has been extended by the
operating mode LED flashing.
● Two differing signals may now be assigned to the freely configurable LED
indicators (H 4 to H 16 and H 18 to H 23) to emit either red or green light.
If both assigned signals are active the resulting LED color will be 'amber'
(yellow).
Configuration, operating mode and physical state of the permanently configured
LED indicators H 1 and H 17 are now displayed via configuration parameters and
physical state signals.
F_KEY The new detachable serial HMI provides 6 freely configurable function keys
operated either as a key or switch Each function key is provided with
configurable password protection.
HMI As the new detachable, serially-connected, HMI is now available and its
presence is indicated by this additional device identification parameter: (221
099) HMI : L ocal HMI Exi sts.
The setting range for parameter (080 110) HMI: Fct. Read Ke y has been
extended. Instead of selecting only one assigned protocol by pressing the
"READ" key there are now up to 16 different addresses assigned which can be
triggered in sequence by repeated pressing of the "READ" key (menu jump
function).
Now it is possible to configure two menu jump lists:
● (030 238) HMI : Fct. Men u Jmp Li st 1
● (030 239) HMI : Fct. Men u Jmp Li st 2
These menu jump lists make it possible to select individual menu points (e.g. set
values, counters, triggering functions, event logs) in a freely configurable
sequence via function keys, binary signal inputs etc.
CHECK The outputs of Boolean equations 30, 31 and 32 may now be used to form
specific alarm signals.
GOOSE For the exchange of binary information in an Ethernet network section the IEC
61850 communication procedure (IEC-GOOSE) has been implemented.
HMI / MAIN Corresponding binary signal inputs (if previously unavailable) are assigned to all
default reset functions. Together with the already identified configuration
options these binary input functions are now made available in a configuration
list for the two newly implemented group resetting functions as well as the
extended functional assignment for the "CLEAR" key ('C'):
● (005 248) MAIN : Fct.A s si gn. R es e t 1
● (005 249) MA IN : Fct.As s ign. Res et 2
● (005 251) HMI: Fct. Res et Ke y
MAIN The primary source for date and time synchronization may now be selected.
Available are COMM1, COMM2/PC, IRIG-B or a binary input for minute signal
pulses. Available are COMM1/IEC, COMM2/PC, IRIGB or a binary input for minute
signal pulses. Additionally a back-up source can now be selected. Switching over
to the back-up source will occur according to a settable monitoring time period:
● (103 210) MA IN : Pri m. Source Time Sync
● (103 211) MA IN: Backup Sou rce Time Sync
● (103 212) MAIN : Time Syn c. Time -Out
The outputs of Boolean equations 30, 31 and 32 may now be used to form
specific fault signals. A device blocking will not occur should such a fault signal
be present.
Bug fixing:
With previous versions, blocking of trip commands was not signaled if blocking
was generated by the following parameters:
● (021 012) MAI N: Trip Cmd.Block USE R
● (036 045) MAI N: Bl ock. Trip cmd. EXT
Hardware
A new communication module A, providing the InterMiCOM protective interface,
COMM3, can now be fitted in slot 3.
Bug fixing:
Binary signal inputs with a higher operate threshold are now also available for
the power supply and the analog modules. Installation is only recommended if
the application specifically requires such binary signal inputs.
Diagram
The new terminal connection diagrams include the COMM3 interfaces of the
InterMiCOM teleprotection feature.
● P438 -409: (40TE case, transformer module with ring-terminal connection,
all other modules with pin-terminal connection
● P438 -410: (84TE case, with pin-terminal connection)
● P438 -411: (84TE case, with ring-terminal connection)
Software
COMM3 Function group COMM3 has been implemented to permit protective signaling
between two MiCOM protection devices.
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
IEC The state of the LN (BocPhsPTOC1 and BocPhsPTOC2) linked to Backup DTOC is
now signaled by the Mode.
With distance protection operating normal and Backup DTOC ready these LN are
signaled as 'Blocked' (MODE = 2). When the Backup DTOC is activated (i.e. a VT
M.C.B. trip or triggering by the voltagemeasuring circuit monitoring) the LN is
signaled as 'On' (MODE = 1). When the Backup DTOC has not been activated for
a LN then it will remain 'Off' (Mode = 5).
INP In order to comply with standard IEC 60255-22-7, class A, the INP: Filter (010
220) setting is now available. The state of binary signal inputs is now logged by
a circular or ring buffer. When the filter function is used a selected binary signal
input is only then considered as enabled if the set number of sampling steps
was enabled.
DIST The setting value to enable the first undervoltage stage of the wrong phase
coupling protection (076 132) has been extended.
C&VTS The setting values for the voltage monitoring stages (014 229, 014 208, 014
212) have been extended.
DTOC The setting values to enable the undervoltage stages (076 131, 076 150) have
been extended.
IDMT The setting value to enable the first undervoltage stage (072 081) has been
extended.
RECLS The voltage criterion for a reclose command to be issued after the maximum
dead time period (015 128) has been extended.
CBF The CB trip monitoring function has been removed from the circuit breaker
failure protection. The function will now be enabled only if no trip command has
been issued by the protection device.
Hardware
As an option the processor module with an integrated DSP coprocessor is now
available. This module offers an enhanced feature and the highspeed processing
of the device’s additional functions. Such high-speed processing is the pre-
condition for the successful application of the new high impedance protection
function (DELTA).
Diagram
No changes.
Software
Note:
Software version -613 is compatible with all previous hardware releases. Some of
the functional enhancements are only visible and available if the optional
processor module with an integrated DSP coprocessor is fitted.
HMI The functional assignment for the "CLEAR" key ('C') has been extended. The
reset of the reclaim time for the RECLS function at parameter (036 223)RECLS :
Reset Recl.Tim e2 EXT may now be selected from the selection table for (005
251) HMI : Fct . Re set Key.
F_KEY The default setting of passwords for the function keys have been changed. Now
no password entry is required when a function key is pressed.
Enabling a password may still be configured for each function key.
MAIN When the optional processor module with an integrated DSP coprocessor is
fitted the second, third and fifth harmonic current components are determined
and issued as measured operating data.
The following measured values are now additionally available:
● (008 095) MA IN : Curre nt I (2fn ) Prim
● (008 097) MA IN : Curre nt I (3fn ) Prim
● (008 099) MA IN : C urr en t I( 5f n) Pri m
● (008 096) MA IN : Cu rren t I( 2f n) p.u.
● (008 098) MAI N: Curre nt I( 3f n) p. u.
● (008 100) MAIN : Curre nt I (5f n) p.u .
When the optional processor module with an integrated DSP coprocessor is
fitted, the ratio of the sum of the second, third and fifth harmonic current
components to the fundamental is calculated and issued as a measured value
M AI N: kHarm, ∑I( xfn) /I( f n).
The General Start has been extended by the addition of the starting signal from
the high impedance protection function (DELTA, only when the optional
processor module with an integrated DSP coprocessor is fitted).
The Trip signals and Trip commands have been extended by the addition of the
starting signal from the high impedance protection function (DELTA, only when
the optional processor module with an integrated DSP coprocessor is fitted).
The multiple blockings 1 and 2 have been extended by the addition of the high
impedance protection function blocking (DELTA, only when the optional
processor module with an integrated DSP coprocessor is fitted).
The inrush stabilization has been extended by the addition of the high
impedance protection function blocking (DELTA, only when the optional
processor module with an integrated DSP coprocessor is fitted).
The voltage memory function is now comprehensively available for the distance
protection function and the directional overcurrent stages. The following signals
have been shifted within the function groups:
● Previously: (040 034) DI ST: tV me mor y Active
● Now: (040 034) MA IN: tV memory Active
Synchronization of the voltage memory is now terminated by a General Start.
OSCIL The selection of starting conditions for fault recording has been extended by the
conditions for enabling, starting and tripping from the high impedance
protection function (DELTA, only when the optional processor module with an
integrated DSP coprocessor is fitted).
FT_DA The setting of the fault location determination has been extended. Line
reactance and line length can now be configured in 10 successive sections.
DELTA The DELTA function group has been implemented. This function is available only
when the optional processor module with an integrated DSP coprocessor is
fitted.
High impedance errors are detected by sudden current change monitoring and
stabilized by monitoring odd-numbered harmonic current components.
Additional stabilization by sudden angle change monitoring or reactance limits
can be configured.
DIST The accuracy of timer stages of individual zones has been enhanced.
Load blinding has be extended to the polygonal (quadrilateral) tripping
characteristics. Angle Alpha and reactance limit Rg can now be used to set this
feature. Up to the previous version these parameters were available only for the
circular characteristic.
The following parameters have been renamed:
● D IST : Rg y, Forward SGx
● DI ST: Rgy , Re ve rs e SGx
● DIS T: A lp ha y SGx
The visibility control for circular characteristics has been cancelled. The (022
001) DI ST: Circl e Ch ar A vailab. parameter has been removed.
A fourth distance stage with train start-up detection dx/dt has been
implemented.
A visibility control for zones 3 and 4 has been added.
Parameters: (022 195) DIST: Zone 3 Available and (022 196) DIST: Z one 4
Availabl e are used to render visible input, output and setting parameters for
the respective zones.
Zones are always without effect unless their respective availability has been set.
Bug fixing:
Up to the previous version the WPC zone was processed even when the
corresponding availability had been not set.
When the optional processor module with an integrated DSP coprocessor is
fitted then the distance protection measured values (Z, R, X) may be corrected
by harmonics factor MAI N: kH arm, ∑I( xfn )/I( fn ). Distance zone reaches are
reduced dynamically according to the second, third and fifth harmonic current
components.
DTOC / IDMT Starting timer stages in the directional mode can now be freely selected. It is
now possible to select whether a time delay is started when a stage start is
issued or with an additional directional criterion.
Direction determination by overcurrent stages are now stabilized by the voltage
memory function (function group MAIN). If voltage memory is not enabled a
Fault forward decision is issued, independently of the actual fault direction,
when the short-circuit voltages are < 1.0 V.
A load flow direction is now displayed when the short-circuit direction
determination function is available.
Hardware
No changes.
Diagram
No changes.
Software
DIST In the case of load blinder blocking (V < 10V) the evaluation of Rg and alpha is
now skipped.
Hardware
No changes.
Diagram
No changes.
Software
FT_DA The calculation of Vmax now takes into account the feeder mode (Classic Single
Feed or Autotransformer Feed).
Hardware
No changes.
Diagram
No changes.
Software
DIST The resolution for the settings of R and Z of zones 3 and 4 has been reduced
from 0.01 Ω to 0.1 Ω.
Hardware
New Schneider-Electric design for the local control panel (HMI).
Diagram
No changes.
Software
PC The following menu point has been removed: (003 183) PC: Man ufact urer
Note: Compatibility even with older versions of the operating program continues
to be guaranteed.
COMM1 The menu point (003 214) COMM1 : MOD BUS V arian t may now be used to
set the MODBUS protocol to the variant Private or Compatible.
The protocol variant Compatible corresponds to the MODBUS implementation in
the MiCOM Px20 and Px40 protection devices. The protocol variant Private
corresponds to the first implementation of the MODBUS protocol.
Note: As before this setting is hidden unless the MODBUS protocol is enabled.
COMM1, COMM2 The menu points (003 161) COMM1: Name of man ufact urer and (103 161)
COMM2: Name of manu factu rer can no longer be set by using a selection
list but, for reasons of compatibility, they may now be defined as free text. The
default is SE but, in individual cases, it may become necessary to enter texts
differing from the default.
Notes:
● These parameters can only be set using the operating program and it is
not possible to set them locally using the integrated local control panel
(HMI). The maximum text length is 8 characters and designations
exceeding this will be truncated.
● The parameter COMM1: Name of manu factu rer is hidden unless an
IEC 60870-5 protocol is enabled.
DIST The resolution for the settings of R and Z of zones 3 and 4 has been reduced
from 0.01 Ω to 0.1 Ω. Moreover, the maximum setting value for the reactance of
zones 3 and 4 has been increased from 650 Ω to 750 Ω.
Hardware
The P438 is now fitted with an improved power supply module.
Note that the voltage range has changed for DC input:
● For the DC / AC variant, the range is now 60 … 250 VDC / 100 ... 230 VAC
(previously 48 … 250 VDC / 100 ... 230 VAC)
● For the DC-only variant, the range is now 24 … 60 VDC
(previously 24 VDC)
A new communication module (“REB” = “Redundant Ethernet Board”) is now
available as an ordering option. This module can be used for redundant
communication via IEC 61850 and may be fitted to slot 2, as an alternative to the
other communication modules. The following communication protocols are
supported:
● SHP (Self-Healing Protocol)
● RSTP (Rapid Spanning Tree Protocol)
● DHP (Dual-Homing Protocol)
A detailed description of the module and the appropriate network connections is
available as a separate document (“Redundant Ethernet Board, Application
Guide”).
The binary module X(6I 3O) with 6 binary signal inputs and 3 output relays is now
optionally available and may be fitted to slot 10 (40 TE case) or 18 (84 TE cases).
Diagram
The diagrams have been adapted to the new selection of modules:
● P438 -412 (transformer module for ring-terminal connection, other modules
for pin-terminal connection)
● P438 -413 (for 84TE pin-terminal connection)
● P438 -414 (for 84TE ring-terminal connection)
Software
Note: Software version -616 is compatible with all previous hardware releases.
However, some of the functional enhancements are only visible and available if
the processor variant with an integrated DSP coprocessor (order option) is fitted.
FT_DA The determination of the fault location has been enhanced for the operating
mode “Autotransformer feed”. It is now possible to set the section lengths and
reactances separately for the catenary and the feeder line.
Therefore there are now parameters FT_D A: Li ne len g t h z - y PSx (for the
line feeds z with z=A / ”catenary line” and z=B / ”feeder line”), instead of the
previously available parameters FT_DA : Lin e len g t h y PSx (y = 1,…,10).
The same holds for the reactances, so there are now parameters FT_D A: Line
reac,secz - y PSx instead of the previously available FT_DA : L ine react , s
ec y PSx.
In operating mode “Classic single feed” only the parameters for line feed A are
available.
The new parameter (011 225) FT_D A: Blocking fau l t l oc. allows for
blocking the determination of the fault location via binary signal, e.g. in case the
autotransformers are still connected.
DIST The parameter (076 132, 077 132, 078 132, 079 132) DI ST: WPC V< PSx can
now be set to Blocked. In this case, protection against wrong phase coupling is
performed without voltage supervision.
DTOC, DTOCA, Two new DTOC function groups, DTOCA and DTOCB, have been implemented.
DTOCB These function groups provide a definite time phase current (IA, IB) supervision
in the operating mode “Autotransformer feed”. If the operating mode is set to
“Classic single feed” both function groups are inactive.
The DTOC function group is still available and unchanged. In both operating
modes it supervises the total current independently of the DTOCx function
groups.
The parameters (130 079) DTOC A : Bl ockin g EXT and (130 099) D TOC B:
Bloc k in g EX T allow for blocking these new DTOCx functions, e.g.if the
supervision is needed only in the case of disconnected autotransformers.
IDMT, IDMTA, IDMTB Two new IDMT function groups, IDMTA and IDMTB, have been implemented.
These function groups provide an inversetime phase current (IA, IB) supervision
in the operating mode “Autotransformer feed”. If the operating mode is set to
“Classic single feed” both function groups are inactive.
The IDMT function group is still available and unchanged. In both operating
modes it supervises the total current independently of the IDMTx function
groups.
The parameters (130 116) ID MTA: Bl ocki ng EXT and (130 136) ID MTB: Bl
ocki ng EXT allow for blocking these new IDMTx functions, e.g. if the
supervision is needed only in the case of disconnected autotransformers.
ARC The ARC function group has been extended to include the new overcurrent
supervision functions DTOCx and IDMTx.
Hardware
The Redundancy Ethernet Board (REB) can now be ordered with an additional
redundancy protocol: PRP (Parallel Redundancy Protocol) is available now as an
alternative to RSTP, SHP or DHP.
The P438 is now fitted with an improved communication module for the
InterMiCOM protocol.
Note: This new module is not supported by previous firmware due to differences
in uploading the firmware to the controller from the main processor during
service bootup.
Diagram
No changes.
Software
The software has been modified to support the new PRP board and the new
InterMiCOM board.
Hardware
The P438 is now fitted with Ethernet module (SEB LC/RJ45 or REB LC/RJ45). This
module is used for IEC 61850 Edition 1 and Edition 2 and is fitted to slot 2, as an
alternative to other communication modules.
PRP/HSR/RSTP communication protocols are supported.
The P438 is now available with text display or graphic display as an order option.
Diagram
The updated connection diagrams now include the Ethernet module
communication interface with SEB and REB.
● P438 -418 (for 40 TE case, with CT/VT ring-, I/O pin-terminal connection)
● P438 -419 (for 84 TE case, with pin-terminal connection)
● P438 -420 (for 84 TE case, with ring-terminal connection)
Software
IEC The protocol of the redundant connection is configurable with IEC : E TH COMM
Mode .
When Ethernet module (REB or SEB) is used, second Ethernet information is
provided.
● (104 080) IE C: E TH C OMM Mode
● (104 072) IE C: Gate way addre ss 2
● (104 070) IEC : IP addr es s 2
● (104 073) I EC: Block Port A /B
● (104 074) I EC : Bl ock P ort C
● (221 125) IEC : C trl blocke d use r
● (104 071) I EC : Subn et mask 2
● (104 079) I EC : IEC prot. varian t
MAIN The setting (010 135) MA IN: F e eder Mode is extended to an additional
operating mode “Single feed w. sum I”.
Measurement parameters of 3rd CT for MCMON CT Plausibility check or
alternatively DFRST function are added.
● (010 016) MA IN: Ipl aus /Idf rst,CTpri m
● (010 017) MAIN: Iplaus/I df rst,CTn om
● (010 036) MA IN: Ms Ci rc.I pl aus/I df r st
The following measurements are used:
● (005 040) MAIN: Curre nt IA pri m.
● (006 040) MA IN: Cu rren t IB pri m.
● (005 042) MAIN: V oltage VA pri m.
● (006 042) MA IN: Vol tage VB/V ref prim.
● (005 041) MAI N: Cu rren t IA p.u.
● (006 041) MAI N: Cu rren t IB p.u.
● (005 043) MAI N: V oltage V A p.u .
● (006 043) MA IN: Vol tage VB/V r ef p.u .
● (004 200) MA IN: Ipl aus /Idf r st. pri m.
● (004 201) MAIN: Ipl aus/I df r st. p.u .
The following measurements are used to provide the CB open state:
● (031 028) MA IN: C B ope n EXT
● (031 040) MAI N: CB ope n
The selection table for the following m-out-of-n parameters:
● (021 007) MA IN: Fct. asg. M-tri p cmd1
● (021 008) MAIN: Fct. asg. M-tri p cmd2
● (021 025) MA IN: Fct. asg. R -trip cm d1
● (021 026) MA IN: Fct.as g. R-tri p cmd2
● (021 027) MAI N: Fct.as g. B-trip cmd1
● (021 028) MAIN: Fct.as g. B-trip cmd2
are extended to add the following state signals as well:
● (042 032) LOGIC: Outpu t 01 to
● (047 126) L OGI C: Ou tpu t 12 8
● (042 181) LOGIC : Ou tput 33( t ) to
● (047 127) LOGIC: Outpu t 12 8(t)
The harmonics detection and related blocking functionality are added.
● (021 051) MA IN: Curre nt I (7fn ) pri m
● (021 058) MA IN: Curre nt I (7fn ) p.u .
● (020 238) MAI N: I (7fn )/I (fn ) PSx
● (020 252) MAIN: Fun ct. Harm .bl ock P Sx
● (020 244) MAIN: I>E nabl e harm.b. P Sx
● (020 248) MAIN: I>L ift h ar m.blk. P Sx
FT_DA The enhanced fault locator function with up to 10 impedance segments with
forward and backward. The following addresses are renamed and added
accordingly, take forward as example.
● (010 005) FT_D A: Forw. le ngth A-1 PSx to
● (008 147) F T_D A: F or w. l e ngth A -1 0 PSx
● (010 012) F T_D A : XL f or w, se c A -1 P Sx to
● (008 187) FT_DA : XLf orw,se c A -1 0 P Sx
● (011 145) FT_D A: Forw. le ngth B-1 PSx to
● (011 181) FT_D A: F orw. l e ngth B-10 P Sx
● (011 185) FT_D A: XLf orwt, se c B-1 PSx to
● (011 221) FT_D A: XLf orw,se c B-10 P Sx
DELTA The order option for DELTA function is removed and the function is always
visible now.
MCMON Enhanced MCMON function measuring Iplause with 3rd current transformer is
provided. The following addresses are required:
● (004 255) MC MON: Scali ng f act. Iplaus
● (014 240) MCMON: I-moni t. en able d P Sx
● (014 092) MC MO N: Sele ct cu rren t PSx
● (014 244) MC MON: I d>, I-mon it. P Sx
● (014 248) MC MO N: m 1, I-moni t. PSx
● (006 207) MCMON: I> li f t moni tor. PSx
The following measurements are required:
● (040 087) MC MON: Me as. ci rc. I f aul ty
● (037 020) MC MO N: Me as.circ. V,I fau lty
● (040 129) MC MO N: Mi smatch scal .I pl aus
PSIG1, PSIG2 Two new Protective Signaling function groups, PSIG1 and PSIG2, have been
implemented. The function is transmitting binary signals via binary inputs/
outputs, InterMicom (COMM3) or Ethernet interface (GOOSE) from one to the
other protection device for system wide distance protection applications.
ASC The ASC function (Synchronism Check) has been implemented. Two voltages -
supply caternary voltage and reference voltage -and synchronism conditions are
checked before an automatiic or manual closing occurs.
CBF The CBF function of the P438 considers the monitoring of 2 CB (circuit breaker).
The following input signals become available to configure related CB supervision
states:
● (036 051) MAI N: CB clos e d A EXT
● (031 030) MAIN : CB cl ose d B E XT
In the “Classic single feed” mode, the CB Closed B signal is not used, whereas
the CB closed A signal is used for the one CB state.
In the “Autotransformer feed” or “Single feed with sum I” mode, both signals
will be used for the CB supervision.
The following logical state signals become available to signalize the CB failure
states as output from the CBF function:
● (036 075) CBF: CB1 fail ure
● (036 076) CBF: CB2 fail ure
The following state signals are kept as building the OR of the two CB states in
the the “Autotransformer feed” or “Single feed with sum I” mode:
● (039 000) CB F: C B Su perv. Sign al
● (036 017) C B F: C B fail ure
In the “Classic single feed” mode, the “CB1 failure” and “CB failure” signals are
equal, normally the CB failure signal is used only.
CBM The CBM function of the P438 considers the monitoring of 2 CB (circuit breaker).
The following logical state signals and function behind become available:
● (044 206) CB M: Cycl e ru n ni ng B
● (044 178) C BM: t max> B
● (044 202) C BM: C urr . fl ow e nde d B
The following command signals and function behind become available:
● (022 132) CB M: Set No. CB ope r. B
● (022 135) CBM: Se t re mai n. CB op. B
● (022 138) CB M: Set Σ Itri p B
● (022 141) C BM: Set ΣI trip**2 B
● (022 144) C BM: Se t Σ I*t B
The following event counters and function behind become available:
● (008 012) CBM: No. of CB ope r. B
● (008 015) C BM: Remai n. No. CB op. B
The following fault data and function behind become available:
● (009 213) C BM: It rip, pri m B
● (009 048) C BM: I tri p B
● (009 052) C B M: Itrip**2 B
● (009 073) C BM: ΣItri p B
● (009 078) C BM: ΣI trip**2 B
● (009 062) C BM: I *t B
● (009 088) CB M: ΣI* t B
LIMIT Regarding the CT plausibility check and the defrost function, using similar CT
input for measurement, the following harmonized parameter are provided:
● (076 224) LIMIT: Iplau s /Idfrs t> PSx
● (076 225) LIMIT: Iplau s /Idfr s t>> PSx
● (076 226) L IMIT: tI plaus/I df rst> P Sx
● (076 227) LIMIT: tIpl aus /Idf r st>> PSx
The following parameter are renamed to be used for MCMON and DFRST
thresholds together:
● (040 236) LIMIT: tIplau s/Idfrs t> e lps
● (040 237) L IMIT: tIplaus /Idf rst>> el ps
DEV To use a common output contact the protection and control commands can be
internally connected. Common state signal “MAIN: Gen. trip command” is an OR
state of “MAIN: M-trip command 1” and “MAIN: M-trip command 2”.
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00
www.schneider-electric.com
Publishing: Schneider Electric
Publication: P438/EN M/R-b5-A 09/2018